Assessment of the Safety Integrity of Electrical Protection Systems in the Petrochemical Industry

Size: px
Start display at page:

Download "Assessment of the Safety Integrity of Electrical Protection Systems in the Petrochemical Industry"

Transcription

1 Assessment of the Safety Integrity of Electrical Protection Systems in the Petrochemical Industry 1. Introduction Author: Colin Easton ProSalus Limited ~ Independent Safety Consultants Within the United Kingdom process industries the functional safety standard IEC [2] is now recognised by the Health and Safety Executive (HSE) as relevant good practice for the design, installation, operation, maintenance and decommissioning of protection systems in the process industry sector. It is HSE s view that if the requirements of IEC are met, thereby demonstrating that the risks under the control of protection systems have been reduced to a level that can be considered as low as reasonably practicable, enough will have been done to comply with UK Health and Safety law so far as protection systems are concerned. The Safety Integrity assessment is a process that reviews and assesses a SIS based on the consequences of previously identified hazardous events. The verification process focuses on the ability of a protection system to meet the recommendations of IEC and the system design intent. The verification process examines the proposed protection system components and functions for purpose and adequacy and will determine what measures of protection and intervention they perform to minimise the risks of an incident and will establish what, if any remedial works are required to the system. The IEC standard is concerned with the functional safety of process plant protection systems. It requires: q q q q That a hazard and risk assessment is carried out to identify the overall safety requirements, this usually takes the form of a HAZOP study which is then used to develop the site s safety management system and COMAH compliance strategy. That an allocation of the safety requirements to the protection system(s) is carried out. That a business works within a framework which is applicable to all methods of achieving functional safety. Detailed use of certain activities, such as safety management, which may be applicable to all methods of achieving functional safety, this is normally addressed by the site s safety management system. IEC covers the whole safety lifecycle from design, installation, operation, maintenance and decommissioning and requires that an evaluation of the protection systems is undertaken and that all components of the protection system are considered as a part of that evaluation. Electrical supply protection forms apart of the overall protection system and must therefore be considered in the evaluation. Recently published Guidance on the assessment of electric protection systems by the Energy Institute (ref [3]) has added to the existing guidance and has now introduced a framework for applying IEC to electrical supply protection systems The objective of this paper is to introduce to the electrical engineer to the concepts of functional safety as described in IEC and to describe were the EI guidance fits within the overall safety lifecycle when applied to an electrical project to provide assurance that the identified protection function is capable of achieving the required contribution to risk reduction.

2 2. Tolerability of Risk and the Identification of Hazards and Safeguards The assessment of protection systems commences with the identification of the hazards associated with a business undertaking. One of the most popular hazard identification techniques is the hazard and operability study report, (HAZOP), which is a systematic assessment of the plant to identify causes / consequences of plant deviations from design intent and an assessment of the adequacy of safe guards, intended to protect the plant form these deviations. Fig-1 gives an overview of typical risk reduction methods as identified in IEC The HSE require that the risks from hazards identified in the HAZOP are reduced to a level that can be considered as low as Fig - 1: From IEC-61511; typical plant safeguards found in process reasonably practicable, thereby plants demonstrating that the business has the risks under the control, this is commonly termed the ALARP argument. The ALARP argument essentially means weighing a risk against the trouble, time and money needed to control it. The decision making process requires the company to exercise judgement, apply good practice and for high risk situations use formal techniques including cost benefit analysis to form a judgement. IEC is recognised by the Health and Safety Executive (HSE) as relevant good practice and as such is acceptable as a part of the ALARP argument (Ref 4, 5, 6 & 7) The necessary risk reduction may be achieved by either one or a combination of protection layers, such as electrical protection in the form of stopping an electric pump or fan by disconnecting the supply to it. The figure below, taken from IEC 61511, illustrates the general concepts of risk reduction.the various risks indicated are as follows: Residual Risk Partial risk covered by other non-sis prevention/mitigation protection layers Residual Risk Necessary Risk reduction Actual Risk reduction Partial risk covered by SIS Risk reduction achieved by all protection layers Partial risk covered by other protection layers Process Risk COMMUNITY EMERGENCY RESPONSE Emergency broadcasting PLANT EMERGENCY RESPONSE Evacuation procedures MITIGATION Mechanical mitigation system Safety Instrumented control system Safety instrumented mitigation systems Operator supervision PREVENTION Mechanical protection system Process alarms with operator corrective action Safety Instrumented control system Safety instrumented prevention systems Increasing risk CONTROL and MONITORING Basic Process Control Systems Monitoring system (process alarms) Operator supervision PROCESS Process risk: The hazards and risks for a specific plant as identified in the HAZOP, these are generally cause by equipment failures, control system failures or human error. Safeguards are not considered when evaluating the process risk although the protection provided by the control system is, but, it s contribution to risk reduction is limited to one order of magnitude. Tolerable risk:

3 The figure opposite shows the general concepts of the ALARP principle and in order to apply this principle a tolerable criterion must be set by the business to determine what levels of risk are considered tolerable and which are considered intolerable. Intolerable risks can not be justified on any grounds and therefore any risks within this region must be reduced to a level considered tolerable. Intolerable region The ALARP or tolerability region (Risk is undertaken only if a benefit is desired) Broadly acceptable region Risk magnitude Risk cannot be justified except in extraordinary circumstances Tolerable only if further risk reduction is impracticable or if its cost is grossly disproportionate to the improvement gained Tolerable if cost of reduction would exceed the improvements gained It is necessary to maintain assurance that risk remains at this level The tolerable risk criteria identified in Guidance on the assessment of electric protection systems by the Energy Institute (ref [3]) is a probability value for serious injury or fatality to an individual worker of no more than 1.0E-5/yr. The UK tolerability of risk framework used in HSE guidance (ref [4], [5], [6] & [7] indicates an upper limit of a risk of death to any individual worker at a frequency of one in one thousand per annum therefore the EI guidance criteria is two orders of magnitude less than that which is considered as a reasonable maximum and is only one order of magnitude above what is considered to be a broadly acceptable risk to any individual worker 1.0E-6/yr. This means that any assessment undertaken using the EI risk criteria for electrical plant failure will be at least 100 times more conservative than a general risk assessment using the HSE criteria for a individual worker and would usually be considered as the criteria for multiple fatalities. Residual risk: The residual risk is the risk of a hazardous event occurring after the addition of all protection systems and is sometimes designated as the background risk, for example slips trips and falls. Safeguards: As discussed above several layers of protection will be employed to reduce the risk to an acceptable level and electrical protection systems can form a part of those layers of protection. The problem with any protection layer is that the design, installation, operation, maintenance and decommissioning must be considered; this is addressed by applying a whole safety lifecycle approach to each protection system

4 3. IEC Safety Lifecycle Approach and the EI Guidance The safety lifecycle for electrical protection systems is detailed below: The Management Process Factory Tests and Commissioning Basic Design Detail:- Protection Phil osophy Single Line Diagram Fault Level Study Power syst ems St udy Risk Assessment Allocation of SIL Inspection, Test and Mai nte nanc e Changes to System, Protection or Procedures Records, Documents, Reports, Results of Analyses Ha rdware and Software Protection Sett ing Procedures and Doc ume nta tion Audit and Review By permission of the Energy Institute 3.1. Identification of relevant documentation for protection system assessment The first step in the life cycle is to identify information for the protection system under review, these drawings should include: 1. Plant Hazard and Operability Study (HAZOP) 2. Plant Process and Instrument diagrams (P&ID) 3. System Block Diagrams 4. Single Line Diagrams (SLD) 5. Circuit Diagrams 6. Plant layout drawings 7. Plant Operating Procedures 8. Control and Electrical protection philosophy. 9. Power System study 10. Operating and Maintenance Manuals for equipment 11. Site Safety Health and Environmental (SHE) Management System 12. Site maintenance and test records 13. Site Maintenance training records The assessment process comprises two main stages. The first stage is an evaluation of the risk reduction contribution required from the protection system ((target safety integrity level (SIL)) and the second stage is a numerical evaluation of the system to verify that the required risk reduction contribution can be achieved (Achieved safety integrity level). For this stage historical or estimated failure data and information about the quality systems / control, current status, remaining life and serviceability of equipment needs to be obtained. Where possible, original equipment manufacturers data sheets should be

5 used annex b of the EI guidance provides reliability data for the most common elements of electrical protection systems Safety Integrity Level Determination using the Risk Graph method The second step, the SIL Determination methodology should be based on that described in IEC (ref [2]), and requires a team of experienced people. The risk graph calibration parameters contained in the EI guidance annex A (ref [3]); provide typical examples for use in process industry applications. A typical example is shown below Consequence Severity C = No of People x V Exposure Probability F Probability of Avoiding Danger P Frequency of Demand W > 0.2/year Medium /year /year Negligible < 0.01/year Nil or Minor Injury a a a a to <0.05 >0.05 to <0.5 >0.5 a a a a 1 a a a 2 1 a a a a Represents No Special Requirements. Figure 1 SIL Graph for safety risk assessment (Copyright Energy Institute) In this methodology, the hazards due to each electrical protection failure are assessed. The aspects of Consequence, Exposure probability, Possibility of Avoidance of danger and Frequency of demand are scored using the calibrated Risk graph for the hazard resulting in a qualitative risk assessment for each protection system based on the probability value for serious injury or fatality to an individual worker of no more than 1.0E-5/yr which defines the target SIL required. Using this method a worksheet is produced for each protection system which describes the critical performance aspects for the protection system in protecting safety, environment and commercial The methodology for conducting the SIL Determination was as follows: Ø Identify the potential hazard. Ø Consider the hazardous event. Ø Assess the Consequences of the hazardous event should the protection function fail. Ø Assess the Exposure probability. Ø Assess the Possibility of avoiding danger. Ø Assess the frequency of demand. Ø Repeat until all hazards have been analysed. The study team should be composed of a combination of personnel consisting of an: Experienced facilitator

6 Electrical engineer Instrument Engineer Process engineer Maintenance Operations Safety The results of the study are normally recorded live during the meeting in the meeting using an appropriate software tool projected onto a screen for all team members to view Safety Integrity of Safety Instrumented Functions The performance criteria for the protection system, the target safety integrity level, also identifies the target hardware integrity probability of failure on demand (PFDavg) and this numerical value is shown in IEC Table - 3: Safety Integrity Levels ( Demand Mode). SIL Level Average probability of failure to perform its design function on demand 4 > 10-5 to < > 10-4 to < > 10-3 to < > 10-2 to < 10-1 Key aspects of the verification are dependant upon the system-operating mode, which is defined as either Demand or Demand (or continuous) Mode. Based on plant historical data a Demand Mode of operation is considered when a demand will not placed on the protection system more than once per year or twice the proof test interval.

7 4. SIL Verification The lifecycle approach now advances to check the validity of the claim of the SIL capability for the protection function. The SIL Verification must be carried out using the techniques referenced in IEC (ref [1]) and the EI guidance annex D (ref [3]). For each component in the protection system, its SIL capability is evaluated, that is the maximum SIL for which it can be used within a system while meeting the requirements of BS EN This is achieved in one of three ways. 1. Component certification, or evaluation, which deems it suitable for use up to a given SIL 2. Demonstrate prior use according to BS EN (Ref [2]) in which case a simplified set of requirements, as defined by BS EN are applied to evaluate SIL capability 3. If Prior Use cannot be demonstrated, the requirements of BS EN , BS EN , BS EN and BS EN are used to identify SIL capability Architectural Constraints on Hardware Safety Integrity ( Sect 7.4) The evaluation procedure should include analysis of hardware fault tolerance for each protection system. The required hardware fault tolerance is assessed in respect to the tables below to identify if any concession can be claimed for the protection system based on the achieved Safe failure Fraction, the ratio of the undetected dangerous failure rate to the total failure rate of the protection system, as stated in vendor data, independent body report or estimated from vendor supplied data and failure data. The protection systems are classified as either Type A or Type B in respect to architectural constraints depending on the known vendor data, programmable electronic features and failure characteristics of the devices (BS EN (Ref [1]). An example of the failure characteristics of a Type A system are: a. The failure mode of all constituent components is well defined; b. The behaviour of the subsystem under fault conditions can be completely determined; c. There is sufficient dependable failure data from field experience to show the claimed rates of failure for detected and undetected dangerous failures are met (BS EN and 4). The Type A system architectural constraints are described in table 1 below. Table 1 - Type "A" Component Hardware Tolerance Safe Failure Fraction Hardware fault tolerance (see note 1) 0 (note 2) 1 2 < 60% SIL1 SIL2 SIL3 60% - < 90% SIL2 SIL3 SIL4 90% - 99% SIL3 SIL4 SIL4 99% SIL3 SIL4 SIL4 NOTE 1 Hardware fault tolerance is the maximum number of faults in a subsystem, arising from random hardware failures that can occur without leading to a dangerous failure of the SIS. NOTE 2 A hardware fault tolerance of zero means a single fault could cause a dangerous failure (see note 3). NOTE 3 A dangerous failure is a failure, which has the potential to put the SIS into a hazardous or fail to function state. An example of the failure characteristics of a Type B system are: a. The failure mode of at least one constituent component is not well defined; b. The behaviour of the subsystem under fault conditions cannot be completely determined;

8 c. There is sufficient dependable failure data from field experience to show the claimed rates of failure for detected and undetected dangerous failures are met ( BS EN and 4). The Type B system architectural constraints are described in table 2 below. Table 2 - Type "B" Component Hardware Tolerance Diagnostic coverage Hardware fault tolerance (see note 1) 0 (see note 2) 1 2 None (0%) Not allowed SIL1 SIL2 (60%) SIL1 SIL2 SIL3 Medium (90%) SIL2 SIL3 SIL4 (99%) SIL3 SIL4 SIL4 NOTE 1 Hardware fault tolerance is the maximum number of faults in a subsystem, arising from random hardware failures that can occur without leading to a dangerous failure of the SIS. NOTE 2 A hardware fault tolerance of zero means a single fault could cause a dangerous failure (see note 3). NOTE 3 A dangerous failure is a failure, which has the potential to put the SIS into a hazardous or fail to function state Average PFD/dangerous failure rate When applying the EI guidance to hardware SIL verification evaluations the calculation of the probability of failure on demand (PFDavg) is based on the per unit time that the protection system is unavailable. If the protection system is based on a simplex hardware configuration i.e. zero fault tolerance then the probability of failure on demand (PFDavg) is equal to the failure rate per annum of the protection system multiplied by the functional test interval. PFDavg = r x u/2 Where r = the failure rate, per year of the protection system u = No of years to detect protection failure. This is effectively the functional test interval. To account for back up or other protection system arrangements a more complex reliability analysis is necessary. However the EI guidance offers a more simplified approach to take account of typical arrangements and terminology for electrical power system protection. For the purposes of rapid assessment the PFD may be approximated by: - PFDavg = r x u/2 x s x t x v Where: - s = A factor accounting for other independent protection on the same circuit t = A factor accounting for other independent protection that trips upstream circuits. v = A factor to account for any trip circuit supervision.

9 4.3. Systematic safety integrity BS EN includes a number of qualitative requirements, which must be met in order for a given SIL capability to be claimed for a protection system. These requirements help to ensure that systematic safety integrity is assured during the system build, installation and commissioning, and is preserved during operation, maintenance and subsequent modification. The SIS firmware will be built in accordance with BS EN (ref [1]). This includes application software development tools. The application software must be developed in accordance with either BS EN (ref [1]) or BS EN , section 12 (ref [2]) to assure that the application software for each programmable device will meet the target SIL for the protection system. To provide assurance that the application software has been developed in accordance with the standards a functional safety plan should be developed documenting the specifications and reports prepared that validate that the safety requirements as defined by the risk assessment have been met. These project documents prepared should at least include: a. Functional Safety Management Plan b. Component and sub-system selection schedule c. SIS Validation Plan d. Design Specification (Incorporating Hardware and Software Design) e. Test Specification (Incorporating Hardware and Software Tests) f. Safety Manual (incorporating O&M) 4.4. Confirmation of achieved SIL for Protection System The achieved SIL will be confirmed as the lowest of the achieved SIL ratings identified for: Each component of the protection system; The protection system as a whole as governed by its average PFD; The system as a whole as constrained by the systematic requirements. Where the achieved SIL is clearly capped by a single component, that single element should be reviewed again to reconfirm that it is absolutely a constraint. This is done to give additional confidence that a higher level of overall system integrity cannot be claimed. 5. References 1. IEC Functional safety of E/E/PES systems, Parts IEC Safety Instrumented systems for the process industry sector, Parts Guidance on assessing the safety integrity of electrical supply protection ISBN (2006) 4. Reducing Risks, Protecting People, HSE decision making process (R2P2) ISBN HSE - Principles and guidelines to assist HSE in its judgement that duty-holders have reduced risk as low as reasonably practicable. 6. HSE Assessing compliance with the law in individual cases and the use of good practice 7. HSE Policy and Guidance on reducing risks as low as reasonably practicable in design 8. Managing Competence for Safety-related Systems, HSE Safety, Competency and Commitment Competency Guidelines for Safety-Related Systems Practitioners 1999: The Institution of Electrical Engineers

10 6. Abbreviations Term BPCS β E/E/PE FSA FSCA IPL MTBF MTTF MTTR PFDavg RRF SFF SIF SIL Description Basic Process Control System Beta Factor - the proportion of failures attributable to a common cause Electrical / Electronic / Programmable Electronic Functional Safety Assessment Functional Safety Capability Assessment Independent Protection Layer Mean Time Between Failures Mean Time To Failure Mean Time to Repair Average Probability of Failure on Demand Risk Reduction Factor Safe Failure Fraction - Ratio of the Undetected Dangerous Failure rate to the Total Failure Rate of the system or Subsystem. (SFF does not include any faults detected by proof tests.) Safety Instrumented Function Safety Integrity Level

Safety Integrity Verification and Validation of a High Integrity Pressure Protection System to IEC 61511

Safety Integrity Verification and Validation of a High Integrity Pressure Protection System to IEC 61511 TÜV Rheinland International Symposium in China Functional Safety in Industrial Applications October 18 19, 2011 in Shanghai China Safety Integrity Verification and Validation of a High Integrity Pressure

More information

Process Safety - Market Requirements. V.P.Raman Mott MacDonald Pvt. Ltd.

Process Safety - Market Requirements. V.P.Raman Mott MacDonald Pvt. Ltd. Process Safety - Market Requirements V.P.Raman Mott MacDonald Pvt. Ltd. Objective of Process Safety Protect personnel Protect the environment Protect the plant equipment / production. Multiple Layers

More information

2015 Functional Safety Training & Workshops

2015 Functional Safety Training & Workshops HAZAN RISK SIS SIF - IEC 61508/61511 - SIL PFD SFF CCF 2015 Functional Safety Training & Workshops Select the right course for your organisation from our extensive choice of Functional Safety related training

More information

Technical Paper. Functional Safety Update IEC Edition 2 Standards Update

Technical Paper. Functional Safety Update IEC Edition 2 Standards Update Technical Paper Functional Safety Update IEC 61511 Edition 2 Standards Update Functional Safety Update Table of Contents 1.0 Introduction 2.0 IEC 61511-1 changes 3.0 IEC 61511-2 changes 4.0 IEC 61511-3

More information

100 & 120 Series Pressure and Temperature Switches Safety Manual

100 & 120 Series Pressure and Temperature Switches Safety Manual 100 & 120 Series Pressure and Temperature Switches Safety Manual MECH-SM-01 1 INTRODUCTION This Safety Manual provides information necessary to design, install, verify and maintain a Safety Instrumented

More information

ADIPEC 2013 Technical Conference Manuscript

ADIPEC 2013 Technical Conference Manuscript ADIPEC 2013 Technical Conference Manuscript Name: Heidi Fuglum Company: ABB AS Job title: Deployment Manager Address: Ole Deviksvei, Oslo, Norway Phone number: +47 91 36 98 70 Email: Heidi.Fuglum@no.abb.com

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 61511-3 First edition 2003-03 Functional safety Safety instrumented systems for the process industry sector Part 3: Guidance for the determination of the required safety integrity

More information

SIL Safety Guide Series MS Single-Acting Spring-Return Hydraulic Linear Actuators

SIL Safety Guide Series MS Single-Acting Spring-Return Hydraulic Linear Actuators SIL Safety Guide Series MS Single-Acting Spring-Return Hydraulic Linear Actuators Rev 0, November 17 2015 Page 1 of 9 Table of Contents 1 INTRODUCTION 3 1.1 Terms and abbreviations 3 1.2 Acronyms 4 1.3

More information

IEC an aid to COMAH and Safety Case Regulations compliance

IEC an aid to COMAH and Safety Case Regulations compliance IEC 61511 an aid to COMAH and Safety Case Regulations compliance C R Timms, Director, C&C Technical Support Services Limited INTRODUCTION There are specific safety related regulations for the UK offshore

More information

FUNCTIONAL SAFETY IN FIRE PROTECTION SYSTEM E-BOOK

FUNCTIONAL SAFETY IN FIRE PROTECTION SYSTEM E-BOOK FUNCTIONAL SAFETY IN FIRE PROTECTION SYSTEM E-BOOK USEFUL TERMINOLOGY BASIC PROCESS CONTROL SYSTEM (BPCS) System which responds to input signals from the process, its associated equipment, other programmable

More information

Measurement of Safety Integrity of E/E/PES according to IEC61508

Measurement of Safety Integrity of E/E/PES according to IEC61508 Measurement of Safety Integrity of E/E/PES according to IEC61508 Mr. Chen Zhenkang TUV Rheinland Singapore 18. May. 2018 Singapore World Metrology Day 2018 1 Agenda 1. TÜV Rheinland: a Certification Body

More information

New Developments in the IEC61511 Edition 2

New Developments in the IEC61511 Edition 2 New Developments in the IEC61511 Edition 2 Presented by Dr Issam Mukhtar PhD(Eng.) TÜV FS Expert (IDNo.:117/06) 6 th May 2013 2010 Invensys. All Rights Reserved. The names, logos, and taglines identifying

More information

Digital EPIC 2 Safety manual

Digital EPIC 2 Safety manual Safety manual Before installation these instructions must be fully read and understood Table of contents Safety manual... 1 1. Introduction... 1 1.1 Terms and abbreviations... 2 1.2 Acronyms... 2 1.3 Product

More information

Session Four Functional safety: the next edition of IEC Mirek Generowicz Engineering Manager, I&E Systems Pty Ltd

Session Four Functional safety: the next edition of IEC Mirek Generowicz Engineering Manager, I&E Systems Pty Ltd Abstract Session Four Functional safety: the next edition of IEC 61511 Mirek Generowicz Engineering Manager, I&E Systems Pty Ltd The functional safety standard IEC 61511 provides a framework for managing

More information

Safety in the process industry

Safety in the process industry Products Solutions Services Safety in the process industry Simply reliable Table of contents Endress+Hauser: At home in the process safety Smart devices and concepts for hazardous areas Introduction to

More information

IEC61511 Standard Overview

IEC61511 Standard Overview IEC61511 Standard Overview Andre Kneisel Instrumentation Engineer Chevron C.T. Refinery SAFA Symposium 2011 August 5 th, 2011 Presentation Overview Provide some understanding of the key aspects of Functional

More information

PPA Michaël GROSSI - FSCE PR electronics

PPA Michaël GROSSI - FSCE PR electronics Functional Safety Component selection according to IEC61511 Title 2 Presentation Michaël GROSSI: Ex / SIL Product manager @ Degree in Instrumentation & Measurement More than 10 years experience in Functional

More information

Overview of Emerging Safety Standards Machinery Sector By Phill Carroll Business Development Manager Topics Historical Situation Introduction of New Standards Terminology Safety Integrity identification

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 61511-2 First edition 2003-07 Functional safety Safety instrumented systems for the process industry sector Part 2: Guidelines for the application of IEC 61511-1 Reference number

More information

Session Ten Achieving Compliance in Hardware Fault Tolerance

Session Ten Achieving Compliance in Hardware Fault Tolerance Session Ten Achieving Compliance in Hardware Fault Tolerance Mirek Generowicz FS Senior Expert (TÜV Rheinland #183/12) Engineering Manager, I&E Systems Pty Ltd Abstract The functional safety standards

More information

Functional Safety: the Next Edition of IEC 61511

Functional Safety: the Next Edition of IEC 61511 HazAus2015/1507 Functional Safety: the Next Edition of IEC 61511 Mirek Generowicz Engineering Manager I&E Systems Pty Ltd Level 2, 445 Hay Street Perth WA 6000 Abstract The functional safety standard IEC

More information

InstrumentationTools.com

InstrumentationTools.com Author: Instrumentation Tools Categories: Safety Systems S84 / IEC 61511 Standard for Safety Instrumented Systems IEC 61511 is a technical standard which sets out practices in the engineering of systems

More information

Functional Safety Application of IEC & IEC to asset protection

Functional Safety Application of IEC & IEC to asset protection Functional Safety Application of IEC 61508 & IEC 61511 to asset protection Paulo Oliveira Engineering Manager Engineering Safety Consultants Ltd Engineering Safety Consultants Limited Page 1 Agenda Agenda

More information

Certification Report of the ST 3000 Pressure Transmitter with HART 6

Certification Report of the ST 3000 Pressure Transmitter with HART 6 Certification Report of the ST 3000 Pressure Transmitter with HART 6 Revision No.: 2.4 Date: Report Number: 2010-Mar-18 SAS-190/2006T Product: ST 3000 Pressure Transmitter with HART 6 Customer: Order Number:

More information

Certification Report of the ST3000 Pressure Transmitter

Certification Report of the ST3000 Pressure Transmitter Certification Report of the ST3000 Pressure Transmitter Revision No.: 1.0 Date: Report Number: Product: Customer: Order Number: Authority: Responsible: 2006-Dec-12 SAS-128/2006T ST3000 Pressure Transmitter

More information

United Electric Controls One Series Safety Transmitter Safety Manual

United Electric Controls One Series Safety Transmitter Safety Manual United Electric Controls One Series Safety Transmitter Safety Manual OneST-SM-02 1 INTRODUCTION This Safety Manual provides information necessary to design, install, verify and maintain a Safety Instrumented

More information

User s Manual. YTA110, YTA310, YTA320, and YTA710 Temperature Transmitters. Manual Change No

User s Manual. YTA110, YTA310, YTA320, and YTA710 Temperature Transmitters. Manual Change No User s Manual YTA110, YTA310, YTA320, and YTA710 Temperature Transmitters Manual Change No. 16-045 Please use this manual change for the manuals listed below. 1. Applicable manuals, revised item, revised

More information

Strathayr, Rhu-Na-Haven Road, Aboyne, AB34 5JB, Aberdeenshire, U.K. Tel: +44 (0)

Strathayr, Rhu-Na-Haven Road, Aboyne, AB34 5JB, Aberdeenshire, U.K. Tel: +44 (0) Strathayr, Rhu-Na-Haven Road, Aboyne, AB34 5JB, Aberdeenshire, U.K. Tel: +44 (0)1339 886618 www.silsupport.com 2012 TRAINING TÜV FS Engineer Certification Training (4 days) This 4 day course is run in

More information

Safety Transmitter / Logic Solver Hybrids. Standards Certification Education & Training Publishing Conferences & Exhibits

Safety Transmitter / Logic Solver Hybrids. Standards Certification Education & Training Publishing Conferences & Exhibits Safety Transmitter / Logic Solver Hybrids Standards Certification Education & Training Publishing Conferences & Exhibits Traditional Pressure Sensor Portfolio Trip Alarm or Trip Module Process Transmitter

More information

PRIMATECH WHITE PAPER CHANGES IN THE SECOND EDITION OF IEC 61511: A PROCESS SAFETY PERSPECTIVE

PRIMATECH WHITE PAPER CHANGES IN THE SECOND EDITION OF IEC 61511: A PROCESS SAFETY PERSPECTIVE PRIMATECH WHITE PAPER CHANGES IN THE SECOND EDITION OF IEC 61511: A PROCESS SAFETY PERSPECTIVE Summary From the perspective of process safety, the most notable change is the addition of requirements for

More information

Overfill Prevention Control Unit with Ground Verification & Vehicle Identification Options. TÜVRheinland

Overfill Prevention Control Unit with Ground Verification & Vehicle Identification Options. TÜVRheinland Scully Intellitrol Safety Manual Overfill Prevention Control Unit with Ground Verification & Vehicle Identification Options TÜVRheinland Functional Safety Type Approved FS IEC 61508 Certified SIL 2 / SIL

More information

67 th Canadian Chemical Engineering Conference EDMONTON, AB OCTOBER 22-25, 2017

67 th Canadian Chemical Engineering Conference EDMONTON, AB OCTOBER 22-25, 2017 Canadian Society for Chemical Engineering (CSChE) 67 th Canadian Chemical Engineering Conference EDMONTON, AB OCTOBER 22-25, 2017 MONDAY, 23 OCTOBER, 2017 Guillermo Pacanins, P. Eng., FS Senior Expert

More information

Australian Standard. Functional safety Safety instrumented systems for the process industry sector

Australian Standard. Functional safety Safety instrumented systems for the process industry sector AS IEC 61511.2 2004 IEC 61511-2:2003 AS IEC 61511.2 Australian Standard Functional safety Safety instrumented systems for the process industry sector Part 2: Guidelines for the application of AS IEC 61511.1

More information

The agri-motive safety performance integrity level Or how do you call it?

The agri-motive safety performance integrity level Or how do you call it? TÜV Rheinland InterTraffic GmbH Safety in Transportation 4 The agri-motive safety performance integrity level Or how do you call it? Dipl.-Ing. Sebastian Gräfling, TÜV Rheinland InterTraffic GmbH Contents

More information

Changes in IEC Ed 2

Changes in IEC Ed 2 1 Introduction As known IEC 61511 is the applicable standard for functional safety in the process industry. Defining the requirements for the specification, design, installation, operation and maintenance

More information

SIL DETERMINATION AND PROBLEMS WITH THE APPLICATION OF LOPA

SIL DETERMINATION AND PROBLEMS WITH THE APPLICATION OF LOPA SIL DETERMINATION AND PROBLEMS WITH THE APPLICATION OF LOPA Alan G King Hazard & Reliability Specialist, ABB Engineering Services, Billingham, Cleveland UK. TS23 4YS For a number of years, industry has

More information

Value Paper Authors: Stuart Nunns CEng, BSc, FIET, FInstMC. Compliance to IEC means more than just Pfd!

Value Paper Authors: Stuart Nunns CEng, BSc, FIET, FInstMC. Compliance to IEC means more than just Pfd! Value Paper Authors: Stuart Nunns CEng, BSc, FIET, FInstMC Compliance to IEC 61508 means more than just Pfd! Compliance to IEC 61508 means more than just Pfd! Market environment Statistics relating to

More information

Is your current safety system compliant to today's safety standard?

Is your current safety system compliant to today's safety standard? Is your current safety system compliant to today's safety standard? Abstract It is estimated that about 66% of the Programmable Electronic Systems (PES) running in the process industry were installed before

More information

SAFETY MANUAL. Electrochemical Gas Detector GT3000 Series Includes Transmitter (GTX) with H 2 S or O 2 Sensor Module (GTS)

SAFETY MANUAL. Electrochemical Gas Detector GT3000 Series Includes Transmitter (GTX) with H 2 S or O 2 Sensor Module (GTS) SAFETY MANUAL Electrochemical Gas Detector GT3000 Series Includes Transmitter (GTX) with H 2 S or O 2 Sensor Module (GTS) Sensor Module (GTS) Transmitter (GTX) Detector (GT3000) SAFETY CERTIFIED GT3000

More information

Guidelines. Safety Integrity Level - SIL - Valves and valve actuators. February Valves

Guidelines. Safety Integrity Level - SIL - Valves and valve actuators. February Valves Valves Guidelines Safety Integrity Level - SIL - Valves and valve actuators February 2009 VDMA German Engineering Federation Valves Manufacturers Association Chairman: Prof.-Dr.-Ing. Heinfried Hoffmann

More information

Practical Methods for Process Safety Management

Practical Methods for Process Safety Management Practical Methods for Process Safety Management Putting Process Safety Management At The Heart Of Our Lives Canadian Chemical Engineering Conference 2006 October 18, 2006 CSChE Conference 2006 Quote Concern

More information

Where Process Safety meets Machine Safety

Where Process Safety meets Machine Safety Where Process Safety meets Machine Safety A document to aid understanding between the end-user and machine builder for functional safety issues. by The 61508 Association Overriding key principle...it must

More information

Safety Instrumented Systems Overview and Awareness. Workbook and Study Guide

Safety Instrumented Systems Overview and Awareness. Workbook and Study Guide Safety Instrumented Systems Overview and Awareness Workbook and Study Guide V 1.0 Preface Copyright Notice and Disclaimer Copyright 2017, Kenexis Consulting Corporation All Rights Reserved 3366 Riverside

More information

NEW CENELEC STANDARDS & CSM-RA NEW CENELEC STANDARDS & CSM-RA 2017

NEW CENELEC STANDARDS & CSM-RA NEW CENELEC STANDARDS & CSM-RA 2017 NEW CENELEC STANDARDS & CSM-RA AGENDA New EN 501xx Standards What is new/changed/improved The use of CENELEC in CSM-RA process CENELEC & CSM-RA TIMELINE EN61508 EN61508 ENV50126 EN50126 EN50128 EN50129

More information

Topic MYTH FUNCTIONAL SAFETY IMPLIES HAVING A SIL RATED COMPONENT. Presented by : Arunkumar A

Topic MYTH FUNCTIONAL SAFETY IMPLIES HAVING A SIL RATED COMPONENT. Presented by : Arunkumar A Topic MYTH FUNCTIONAL SAFETY IMPLIES HAVING A SIL RATED COMPONENT Presented by : Arunkumar A DNV GL Who are we? Only by connecting the details can we impact the bigger picture We classify, certify, verify

More information

Integrated but separate

Integrated but separate End users of older automation systems essentially had to invest in two separate systems: a basic process control system and a separate safety instrumented system. Nowadays, suppliers differ in their opinions

More information

SITRANS. Temperature transmitter Functional safety for SITRANS TW. Introduction. General safety instructions 2. Device-specific safety instructions

SITRANS. Temperature transmitter Functional safety for SITRANS TW. Introduction. General safety instructions 2. Device-specific safety instructions Introduction 1 General safety instructions 2 SITRANS Temperature transmitter Device-specific safety instructions 3 Appendix List of Abbreviations/Acronyms A B Product Information Supplement to Operating

More information

New requirements for IEC best practice compliance

New requirements for IEC best practice compliance New requirements for IEC 61511 best practice compliance Proof testing and a SIL study may no longer be enough by Sven Grone Schneider Electric Safety Services Practice Leader Executive summary Since its

More information

Process Safety Workshop. Avoiding Major Accident Hazards the Key to Profitable Operations

Process Safety Workshop. Avoiding Major Accident Hazards the Key to Profitable Operations CC & technical support services www.silsupport.com Process Safety Workshop Avoiding Major Accident Hazards the Key to Profitable Operations A two (2) day workshop with many practical methods, case studies

More information

Functional Safety of Machinery: EN ISO Stewart Robinson. Overview of the presentation. References. TÜV SÜD Product Service

Functional Safety of Machinery: EN ISO Stewart Robinson. Overview of the presentation. References. TÜV SÜD Product Service Functional Safety of Machinery: EN ISO 13849-1 Stewart Robinson Overview of the presentation Defining Safety Functions Avoidance of Systematic Failures Defining Performance Levels Required Verifying Performance

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 61508-2 First edition 2000-05 BASIC SAFETY PUBLICATION Functional safety of electrical/electronic/ programmable electronic safety-related systems Part 2: Requirements for electrical/electronic/

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 61511-1 First edition 2003-01 Functional safety Safety instrumented systems for the process industry sector Part 1: Framework, definitions, system, hardware and software requirements

More information

SAFETY MANUAL. PointWatch Eclipse Infrared Hydrocarbon Gas Detector Safety Certified Model PIRECL

SAFETY MANUAL. PointWatch Eclipse Infrared Hydrocarbon Gas Detector Safety Certified Model PIRECL SAFETY MANUAL PointWatch Eclipse Infrared Hydrocarbon Gas Detector SIL 2 Certified Model PIRECL Safety Certified Model PIRECL PointWatch Eclipse IR Gas Detector This manual addresses the specific requirements

More information

Design & Use of Ground Based Pumps Guidance Document

Design & Use of Ground Based Pumps Guidance Document Design & Use of Ground Based Pumps The information and recommendations in this guidance are given in good faith and belief in their accuracy at the time of publication, but do not imply any legal liability

More information

Fire and Gas Detection and Mitigation Systems

Fire and Gas Detection and Mitigation Systems Fire and Gas Detection and Mitigation Systems Dr. Lawrence Beckman, PE, TÜV FSExp SafePlex Systems, Inc., Houston, Texas ABSTRACT Fire and Gas Detection systems are key components in the overall safety

More information

This document is a preview generated by EVS

This document is a preview generated by EVS IEC 61511-3 Edition 2.0 2016-07 REDLINE VERSION colour inside Functional safety Safety instrumented systems for the process industry sector Part 3: Guidance for the determination of the required safety

More information

AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY

AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY World-class services help reduce incidents, protect the environment, and keep people and plants safe White Paper PAGE 1 Introduction

More information

AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY

AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY World-class services help reduce incidents, protect the environment, and keep people and plants safe White Paper PAGE 1 Introduction

More information

Safety Instrumented Systems

Safety Instrumented Systems Safety Instrumented Systems What is a Safety Instrumented System? A Safety Instrumented System SIS is a new term used in standards like IEC 61511 or IEC 61508 for what used to be called Emergency Shutdown

More information

FMEDA Report. Failure Modes, Effects and Diagnostic Analysis. KFD0-CS-Ex*.54* and KFD0-CS-Ex*.56* Project: X7300

FMEDA Report. Failure Modes, Effects and Diagnostic Analysis. KFD0-CS-Ex*.54* and KFD0-CS-Ex*.56* Project: X7300 Failure Modes, Effects and Diagnostic Analysis Device Designation: KFD0-CS-Ex*.54* and KFD0-CS-Ex*.56* Project: X7300 Pepperl+Fuchs GmbH Mannheim Germany Mannheim norm sheet 1 of 16 Released EDM checkout

More information

The SIL Concept in the process industry International standards IEC 61508/ 61511

The SIL Concept in the process industry International standards IEC 61508/ 61511 The SIL Concept in the process industry International standards IEC 6508/ 65 Chris M. Pietersen MSc Safety Solutions Consultants BV (SSC) Director pietersen@safety-sc.com th Urea Symposium 9- May 008,

More information

FUNCTIONAL SAFETY CERTIFICATE. BG Break Glass Unit

FUNCTIONAL SAFETY CERTIFICATE. BG Break Glass Unit FUNCTIONAL SAFETY CERTIFICATE This is to certify that the BG Break Glass Unit manufactured by Eaton MEDC Ltd Unit B Sutton Parkway Oddicroft Lane Sutton-In-Ashfield NG17 5FB UK has been assessed by with

More information

This document is a preview generated by EVS

This document is a preview generated by EVS IEC 61511-1 Edition 2.0 2016-02 REDLINE VERSION colour inside Functional safety Safety instrumented systems for the process industry sector Part 1: Framework, definitions, system, hardware and software

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: Detcon FP-700 Combustible Gas Sensor Customer: Detcon The Woodlands, TX USA Contract No.: DC 06/08-04 Report No.: DC 06/08-04 R001 Version V1, Revision

More information

Options for Developing a Compliant PLC-based BMS

Options for Developing a Compliant PLC-based BMS Options for Developing a Compliant PLC-based BMS Jack Boone aesolutions Greenville, South Carolina, United States of America ABSTRACT Facilities are focusing on improving the reliability of their burner

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 61511-1 First edition 2003-01 Functional safety Safety instrumented systems for the process industry sector Part 1: Framework, definitions, system, hardware and software requirements

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: Fireye Flame Sensor Module CE Flameswitch, model MBCE-110/230FR Company: Fireye Derry, NH USA Contract Number: Q09/10-26 Report No.: FIR 09/10-26

More information

IEC Functional Safety Assessment

IEC Functional Safety Assessment IEC 61508 Functional Safety Assessment Project: Detcon IR-700 Combustible Hydrocarbon Gas Sensor Customer: Detcon The Woodlands, TX USA Contract No.: Q13/06-003 Report No.: DC 13-06-003 R002 Version V1,

More information

FUNCTIONAL SAFETY CERTIFICATE

FUNCTIONAL SAFETY CERTIFICATE FUNCTIONAL SAFETY CERTIFICATE This is to certify that the X5000 & S5000 Fixed Gas Detector Range MSA The Safety Company manufactured by General Monitors 1000 Cranberry Woods Drive 26776 Simpatica Cir Cranberry

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: Phoenix Type 85UVF/IRF Flame Scanner Company: FIREYE Derry, New Hampshire USA Contract Number: Q08/04-57 Report No.: FIR 08/04-57 R001 Version V2,

More information

Functional Safety: What It Is, Why It s Important And How to Comply

Functional Safety: What It Is, Why It s Important And How to Comply Functional Safety: What It Is, Why It s Important And How to Comply November 11, 2010 Copyright 1995-2010 Underwriters Laboratories Inc. All rights reserved. No portion of this material may be reprinted

More information

GUIDANCE ON ASSESSING THE SAFETY INTEGRITY OF ELECTRICAL SUPPLY PROTECTION

GUIDANCE ON ASSESSING THE SAFETY INTEGRITY OF ELECTRICAL SUPPLY PROTECTION GUIDANCE ON ASSESSING THE SAFETY INTEGRITY OF ELECTRICAL SUPPLY PROTECTION GUIDANCE ON ASSESSING THE SAFETY INTEGRITY OF ELECTRICAL SUPPLY PROTECTION September 2006 Published by ENERGY INSTITUTE, LONDON

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: Oldham OLCT 200 Transmitter Company: Industrial Scientific Corporation Oakdale, PA USA Contract Number: Q11/05-009 Report No.: IS 10/10-010 R001

More information

Session Number: 3 SIL-Rated Fire (& Gas) Safety Functions Fact or Fiction?

Session Number: 3 SIL-Rated Fire (& Gas) Safety Functions Fact or Fiction? Session Number: 3 SIL-Rated Fire (& Gas) Safety Functions Fact or Fiction? Raymond Wright PhD Senior Consultant, FSE Global Australia Pty Ltd Abstract SIL-rated process safety functions are now commonplace,

More information

innova-ve entrepreneurial global 1

innova-ve entrepreneurial global 1 1 www.utm.my innova-ve entrepreneurial global 1 Using redundant sensors and final redundant control elements Using multiple sensors with voting systems and redundant final control elements Testing the

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 61508-1 First edition 1998-12 BASIC SAFETY PUBLICATION Functional safety of electrical/electronic/ programmable electronic safety-related systems Part 1: General requirements

More information

Technical Report Proven In Use SITRANS P500

Technical Report Proven In Use SITRANS P500 Technical Report Proven In Use SITRANS P500, Industry Sector, Industry Automation Division, Sensors and Communication, PD PA PI R&D PM CRT Oestliche Rheinbrueckenstr. 50 76187 Karlsruhe, Germany Number:

More information

FMEDA and Proven-in-use Assessment. Pepperl+Fuchs GmbH Mannheim Germany

FMEDA and Proven-in-use Assessment. Pepperl+Fuchs GmbH Mannheim Germany FMEDA and Proven-in-use Assessment Project: Transmitter Supply Isolators KF**-CRG-*** Customer: Pepperl+Fuchs GmbH Mannheim Germany Contract No.: P+F 02/11-01 Report No.: P+F 02/11-01 R012 Version V2,

More information

SAFETY MANUAL. Multispectrum IR Flame Detector X3301

SAFETY MANUAL. Multispectrum IR Flame Detector X3301 SAFETY MANUAL Multispectrum IR Flame Detector X3301 SAFETY-CERTIFIED MODEL X3301 MULTISPECTRUM INFRARED DETECTOR This manual addresses the specific requirements and recommendations applicable to the proper

More information

SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR

SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR SAFETY MANUAL SIL 2 Certified Model FP-700 Combustible Hydrocarbon Gas Sensor Version 2.0 1 SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR This manual addresses the specific requirements and recommendations

More information

USER APPROVAL OF SAFETY INSTRUMENTED SYSTEM DEVICES

USER APPROVAL OF SAFETY INSTRUMENTED SYSTEM DEVICES USER APPROVAL OF SAFETY INSTRUMENTED SYSTEM DEVICES Angela E. Summers, Ph.D., P.E, President Susan Wiley, Senior Consultant SIS-TECH Solutions, LP Process Plant Safety Symposium, 2006 Spring National Meeting,

More information

Soliphant M with electronic insert FEM52

Soliphant M with electronic insert FEM52 Functional safety manual Soliphant M with electronic insert FEM52 Level Limit Measuring System Application Overfill protection or operating maximum detection of all types of solids in tanks to satisfy

More information

SAFETY MANUAL. X2200 UV, X9800 IR, X5200 UVIR SIL 2 Certified Flame Detectors

SAFETY MANUAL. X2200 UV, X9800 IR, X5200 UVIR SIL 2 Certified Flame Detectors SAFETY MANUAL X2200 UV, X9800 IR, X5200 UVIR SIL 2 Certified Flame Detectors SAFETY-CERTIFIED Flame DETECTORs This manual addresses the specific requirements and recommendations applicable to the proper

More information

Management of installed safety instrumented systems (SIS)

Management of installed safety instrumented systems (SIS) Health and and Safety Executive Management of installed safety instrumented systems (SIS) Sarabjit Purewal Principal Specialist Inspector BSc ACGI PGDip CEng MIET Humber Chemical Focus Group 21 July 2016

More information

Applying Buncefield Recommendations and IEC61508 and IEC Standards to Fuel Storage Sites

Applying Buncefield Recommendations and IEC61508 and IEC Standards to Fuel Storage Sites Applying Buncefield Recommendations and IEC61508 and IEC 61511 Standards to Fuel Storage Sites John Joosten Global Product Manager Radar and Safety John.Joosten@Honeywell.com Applying Buncefield Recommendations

More information

Addressing Challenges in HIPPS Design and Implementation

Addressing Challenges in HIPPS Design and Implementation Addressing Challenges in HIPPS Design and Implementation Valve Manufacturer s Association Afton Coleman, CFSP March 11, 2016 Agenda SIS and SIL basics HIPPS Purpose Increased demand for HIPPS, why? The

More information

FUNCTIONAL SAFETY OF ELECTRICAL INSTALLATIONS IN INDUSTRIAL PLANTS BY OTTO WALCH

FUNCTIONAL SAFETY OF ELECTRICAL INSTALLATIONS IN INDUSTRIAL PLANTS BY OTTO WALCH FUNCTIONAL SAFETY OF ELECTRICAL INSTALLATIONS IN INDUSTRIAL PLANTS BY OTTO WALCH Troublefree and safe operation of industrial systems is of great importance, not only for the safety of the systems and

More information

This document is a preview generated by EVS

This document is a preview generated by EVS IEC 61511-2 Edition 2.0 2016-07 REDLINE VERSION colour inside Functional safety Safety instrumented systems for the process industry sector Part 2: Guidelines for the application of IEC 61511-1:2016 IEC

More information

Failure Rate Data, Safety System Modeling Concepts, and Fire & Gas Systems Moderator: Lori Dearman, Webinar Producer Thursday, May 16th, 2013

Failure Rate Data, Safety System Modeling Concepts, and Fire & Gas Systems Moderator: Lori Dearman, Webinar Producer Thursday, May 16th, 2013 Welcome to Best Practices for the Latest Safety Instrumented System Performance Developments Failure Rate Data, Safety System Modeling Concepts, and Fire & Gas Systems Moderator: Lori Dearman, Webinar

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: Honeywell Temperature Transmitter STT650 with 4-20 ma Output Company: Honeywell International Inc. Field Products 512 Virginia Drive Fort Washington,

More information

Failure Modes, Effects and Diagnostic Analysis. PR electronics A/S Rønde Denmark

Failure Modes, Effects and Diagnostic Analysis. PR electronics A/S Rønde Denmark Failure Modes, Effects and Diagnostic Analysis Project: 9203 Solenoid / Alarm Driver Customer: PR electronics A/S Rønde Denmark Contract No.: PR electronics 06/03-19 Report No.: PR electronics 06/03-19

More information

Proof Testing Level Instruments

Proof Testing Level Instruments Proof Testing Level Instruments Partial proof testing of level instruments can save millions of dollars while maintaining required safety ratings By Bill Sholette, Level Product Business Manager Endress+Hauser

More information

Rosemount Functional Safety Manual. Manual Supplement , Rev AF March 2015

Rosemount Functional Safety Manual. Manual Supplement , Rev AF March 2015 Rosemount 2120 Functional Safety Manual Manual Supplement Manual Supplement Contents Contents 1Section 1: Introduction 1.1 Scope and purpose of the safety manual.................................. 1 1.2

More information

Functional safety according to IEC / IEC Important user information. Major changes in IEC nd Edition

Functional safety according to IEC / IEC Important user information. Major changes in IEC nd Edition International Symposium in China Functional Safety in Industrial Applications 18 19 October 2011, Shanghai - China Functional safety according to IEC 61508 / IEC 61511 Important user information Major

More information

Simply reliable: Process safety from Endress+Hauser

Simply reliable: Process safety from Endress+Hauser Products Solutions Services Simply reliable: Process safety from Endress+Hauser Safety by choice, not by chance: Functional Safety Slide 1 Oil & Gas industry Hai-Thuy Industry Manager Oil & Gas Slide 2

More information

Failure Modes, Effects and Diagnostic Analysis. Rosemount Inc. Chanhassen, Minnesota USA

Failure Modes, Effects and Diagnostic Analysis. Rosemount Inc. Chanhassen, Minnesota USA Failure Modes, Effects and Diagnostic Analysis Project: 2088 Pressure Transmitter Customer: Rosemount Inc. Chanhassen, Minnesota USA Contract No.: ROS 06/10-18 Report No.: ROS 06/10-18 R001 Version V1,

More information

Functional Safety of Machinery Presented by Greg Richards Manufacturing in America 02/22-23/2017

Functional Safety of Machinery Presented by Greg Richards Manufacturing in America 02/22-23/2017 Functional Safety of Machinery Presented by Greg Richards Manufacturing in America 02/22-23/2017 AGENDA Definition of Safety? Machinery Safety Standards Comparison of ISO 13849-1 and IEC 62061 Safety-related

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 61800-5-2 First edition 2007-07 Adjustable speed electrical power drive systems Part 5-2: Safety requirements Functional Commission Electrotechnique Internationale International

More information

Why AC800M High Integrity is used in Burner Management System Applications?

Why AC800M High Integrity is used in Burner Management System Applications? Why AC800M High Integrity is used in Burner Management System Applications? Prepared by: Luis Duran Product Marketing Manager Safety Systems ABB Process Automation/Control Technologies TÜV Functional Safety

More information

Implementing Safety Instrumented Burner Management Systems: Challenges and Opportunities

Implementing Safety Instrumented Burner Management Systems: Challenges and Opportunities Implementing Safety Instrumented Burner Management Systems: Challenges and Opportunities Mike Scott, PE, CFSE Standards Certification Education & Training Publishing Conferences & Exhibits Presenter Mike

More information