Addressable NAC Output Module D327A

Size: px
Start display at page:

Download "Addressable NAC Output Module D327A"

Transcription

1 Installation Instructions Notice Addressable NAC Output Module D327A These instructions cover the installation of the D327A Addressable NAC Output Module in an analog system controlled by a Bosch D8024, D9024 or D10024 Series Analog Fire Alarm Control Panel (FACP). Install, test and maintain the D327A according to these instructions, NFPA 72, Local Codes and the Authority Having Jurisdiction (AHJ). Failure to follow these instructions might result in failure of the device to operate properly. Bosch is not responsible for improperly installed, tested or maintained devices. These instructions contain procedures to follow in order to avoid personal injury and damage to equipment. NFPA 72 requires a complete system-wide functional test be performed following any modifications, repair, upgrades or adjustments made to the system s components, hardware, wiring, programming and software/ firmware. 1.0 Device Description The D327A Addressable Notification Appliance Circuit (NAC) Output Module is used to supervise and control notification appliances, such as horn/strobes, operating in a single circuit. At a single address on the FACP s polling circuit, the D327A provides a connection point for an alarm notification circuit (such as horn/strobes and bells) to the system. It also provides terminals for connecting auxiliary power from the FACP, or from a regulated, power-limited auxiliary power supply to the notification circuit. The D327A supervises the wiring of the notification circuit attached to it and provides power to the notification devices on that circuit. In an alarm condition, the D327A switches power from the auxiliary power source to the notification circuit and supervises the auxiliary power input. A status LED confirms polling activity. The LED flashes green to indicate a normal condition. 2.0 Specifications Operating Voltage 17 to 41 VDC Nominal Supply Voltage 24 VDC Standby Current 320 µa (typical) Polling Current 22 ma ±20% Alarm Current 5 ma Operating Temperature +14 F to +120 F (-10 C to +49 C) Maximum Humidity 85% RH-non-condensing (@ +104 F, +40 C) Dimensions (H x W x D) 4 11/16 in. x 4 3/16 in. x 1 3/8 in. (12 cm x 11 cm x 4 cm)

2 D327A Setting the Detector Address 3.0 Setting the Detector Address Note: The D327A cannot be learned onto the Signaling Line Circuit (SLC) when in alarm or trouble. Also, the D327A must have 24 VDC power applied before it can be learned. Each analog device is assigned a specific address, which is set by programming an EEPROM microchip. It is not necessary to wire the devices to the FACP s polling circuit in any particular order. The D5070 Analog Device Programmer must be used to set the address on the D327A BEFORE connecting them to the FACP s polling circuit. Make sure the battery in the D5070 is connected prior to programming. Remote Programming Jack Receptacle Non-polarized plug (to device) To Remote Programming Jack Programming Buttons Display Module Programming Adapter Figure 1: D5070 Analog Device Programmer 3.1 Using the D5070 Analog Device Programmer D5070 Programming Buttons Refer to Table 1 for descriptions of the three programming buttons on the D5070 Analog Device Programmer. Programming Description Button Left Gray Button Power on. Automatically reads the address of a detector. Advances the address by ten. Right Gray Button Power off. Advances the address by one. Red Button Stores the displayed address in the detector. Reads analog level. Table 1: D5070 Programming Buttons Page Bosch

3 D327A Setting the Detector Address Setting the Address The following steps explain how to set an address using the D5070 Analog Device Programmer. See Figure 1 on page 2 and Figure 2 for more details. 1. Insert the non-polarized plug on the Module Programming Adapter onto the address pins on the D327A. 2. Plug the Remote Programming Jack on the Module Programming Adapter into the Remote Programming Jack Receptacle on the D5070 Analog Device Programmer (see Figure 2). 3. Press the left gray button to turn the D5070 on. A battery check message will appear followed by the device s address. 4. Set the address by pressing the left and right gray buttons until the desired address is reached. Note: The D5070 display will show three red flashing dots if the address being programmed is different than the device s current address. 5. When the desired address is displayed, press the red button to program that address. The three red dots disappear from the display. Non-Polarized Plug (to address pins) To Remote Programming Jack Receptacle on D5070 Analog Device Programmer Address Pins Module Programming Adapter D327A Figure 2: D327A to D5070 Programming Connections D5070 Display Messages Table 2 provides a description of each message that may appear on the D5070. Display Description Message bat Battery Check. Displayed upon power up and when the battery is low (low battery is good for approximately 3000 address setting operations) E01 Address past 126 will not be recognized by the panel. E1 Attempting to program an address with no device connected. E2 Cannot find the device after power up, or replace the device. E3 Invalid detector response (replace the detector). E4 Cannot find the device to program. E5 Device read error. E6 Fail during analog value reading (replace detector). Table 2: D5070 Display Messages 2004 Bosch Page 3

4 D327A Wiring the D327A 4.0 Wiring the D327A Inform the operator and the Local Authority before installing this device in an existing system. Remove all power (AC and battery) from the FACP before connecting or disconnecting any devices. Failure to do so might result in personal injury and/or damage to the equipment. Analog polling circuits connect to the FACP over two-wire cable. The bus protocol resists interference from most types of EMI and RF generated noise. Under extremely noisy conditions, use twisted pair wire to reduce interference. If EMI is a problem, use shielded cable. See Section Shielded Cable on page 5 for shielded cable guidelines. 4.1 Wiring Guidelines Data Circuit Length Data circuit length is the distance over the circuit wire from the connection at the D9067 Polling Circuit Module to the most distant device and back to the D9067 Module. Data circuit length must include the distance to any device connected to the circuit in a T tap. See Table 3 for polling circuit lengths and acceptable wire gauges. Polling Circuit Length Up to 4000 ft (1219 m) 4000 ft to 7000 ft (1219 m to 2134 m) Wire Gauge #18 AWG (1.2 mm) #16 AWG (1.5 mm) Table 3: Polling Circuit Length/Wire Gauge Sensor Circuit Wiring Requirements Nominal Capacitance: 28 pf/ft Typical Cable Resistance: 3 Ω/1000 ft Maximum Loop Resistance: 25 Ω Recommended Maximum Loop Capacitance: Not to exceed 0.25 µf Page Bosch

5 D327A Wiring the D327A Shielded Cable If shielded cable is used, and the cable is of good quality, then it should not have a significant effect on the polling circuit length. Good quality shielded cable will allow 0.25 µfd of capacitance, 1 mh of inductance and 25 Ω resistance. Connect the drain wire for shielded cable to the E terminal of the Data Terminal Block inside the FACP. Data/Power Positive (+) Return Earth Ground for Shield Cable Drain Data/Power Common (-) Return Data/Power Positive (+) Out + - E + - LOOP 1 Data/Power Common (-) Out Data Terminal Block D9067 Polling Circuit Module Figure 3: E Terminal Location Note: An improperly grounded shielded cable may aggravate rather than eliminate noise problems. Reconnect the shielded cable drain each time the cable is cut to install a device. 4.2 D327A Terminal Connections The D327A has connection points on Terminal Block 2 (TB2) for a NAC device and a regulated auxiliary power supply, such as Bosch D9142F 24 VDC, 4 A Auxiliary Power Supply. Note: Use only FPL, FPLR or FPLP wiring, or an approved equivalent, in accordance with Article 760 of the National Electric Code (NEC) D327A NAC Connections The NAC device wiring shall not exceed 50 Ω (#14 to #18 AWG, 1.8 to 1.2 mm). Install the EOL resistor provided with the D327A as shown in Figure 4 on page 6. NAC devices must be polarized (DC) and connected in polarity as shown in Figure 4. Total current drawn off this circuit cannot exceed 2 A. Maximum voltage is 30 VDC Bosch Page 5

6 1 6 SC OUT S OUT SC IN 4 S IN 1 D327A Wiring the D327A Regulated Power Limited Supply Connection Connection points 3 and 4 on Terminal Block 2 allow the connection of power from a regulated auxiliary power supply, such as Bosch D9142F 24 VDC, 4 A Auxiliary Power Supply, for NAC devices. See Figure 4. Note: All wiring shown on Terminal Blocks 1 and 2 in Figure 4 are supervised and inherently power-limited. + - TB1 D327A TB2 Out to next module To UL Listed compatible FACP SC (OUT) S (OUT) SC (IN) S (IN) 24+ (OUT) 24 - (OUT) 24+ (IN) 24 - (IN) OUT (+) OUT (-) Out to next module UL Listed, regulated, power limited supply for fire protection signaling service for audible devices. Refer to the manufacturer sinstallation instructions for compatible devices. 10K ohm UL Listed EOL Device (P/N: ) 4.3 Device to Polling Circuit Connections Figure 4: D327A Terminal Connections Wire the D327A in the polling circuit by connecting the data/power (+) and data/power (-) terminals as shown in Figure 5. Terminate the NAC circuit on the D327A by placing the supplied EOL resistor at the end of the NAC circuit as shown in Figure 4. SC OUT S OUT SC IN S IN 4 1 Jumper Wires + - E + - LOOP 1 Data/Power (+) Out Data/Power (-) Out Data/Power (+) Out Data/Power (-) Out Data/Power (-) In Data/Power (+) In D9067 Polling Circuit Module Data/Power (+) In Data/Power (+) Out 1 2 Data/Power (+) Out Data/Power (-) Out Data/Power (-) In D321A Analog Base Data/Power (-) Out Figure 5: D327A Polling Circuit Connections Page Bosch

7 5.0 Mounting the D327A D327A Mounting the D327A The D327A mounts on a plate that attaches to a 4.0 in. (10.2 cm), UL Listed electrical back box (supplied by installer) that is at least 2 1 /8 in. (5.4 cm) deep. A cover plate conceals the address pins, but leaves the LED visible. After all wiring connections have been made, attach the mounting plate to the back box as shown in Figure 6. Attach the cover plate over the front of the mounting plate (LED facing out). When the D327A is properly mounted and all system hardware modifications are completed (such as adding and removing devices), restore power to the system by connecting the standby batteries, and close the 120 VAC dedicated breaker that controls the power input to the FACP. Cover Plate D327A on Mounting Plate Figure 6: Mounting the D327A 4-inch Back Box 2004 Bosch Page 7

8 2004 Bosch 12/ Perinton Parkway, Fairport, NY USA Installation Instructions D327A Customer Service: (800) ; (888) Page 8 of 8

D326A/D334A/D339A. Installation Instructions. Point Contact Modules

D326A/D334A/D339A. Installation Instructions. Point Contact Modules D326A/D334A/D339A EN Installation Instructions Point Contact Modules D326A/D334A/D339A Installation Instructions 1.0 Description Notice Use these instructions to install the D326A, D334A, and D339A Point

More information

These instructions detail procedures to follow in order to avoid damage to equipment.

These instructions detail procedures to follow in order to avoid damage to equipment. D326A, D334A, D339A Point Contact Modules Installation Guide 1.0 Notice These instructions are for the installation of the D326A, D334A and D339A Point Contact Modules in an analog system controlled by

More information

D7052. Installation Instructions Multiplex Dual Input Module

D7052. Installation Instructions Multiplex Dual Input Module D EN Installation Instructions Multiplex Dual Input Module D Installation Instructions Notices Notices Figure : D Features These instructions cover the installation of the D Multiplex Dual Input Module

More information

D7044. Installation Instructions Multiplex Single Input Module

D7044. Installation Instructions Multiplex Single Input Module D EN Installation Instructions Multiplex Single Input Module D Installation Instructions Notices Notices These instructions cover the installation of the D Multiplex Single Input Module in a fire system,

More information

D7053. Installation Instructions Multiplex Input/Output Module

D7053. Installation Instructions Multiplex Input/Output Module D EN Installation Instructions Multiplex Input/Output Module D Installation Instructions Notices Notices These instructions cover the installation of the D Multiplex Input/Output Module in a fire system

More information

Notification Appliance Circuit Module

Notification Appliance Circuit Module Notification Appliance Circuit Module D192G en Installation guide Notification Appliance Circuit Module Notices en 3 1 Notices These instructions cover the installation of the D192G Notification Appliance

More information

F220-B6PS/M. Installation Guide. Addressable Detector Bases

F220-B6PS/M. Installation Guide. Addressable Detector Bases F220-B6PS/M EN Installation Guide Addressable Detector Bases F220-B6PS/M Installation Guide 1.0 Overview 1.0 Overview These instructions cover the installation of the B6PS/M Addressable Detector Bases

More information

Annunciators, 8 LED. D7030X, D7030X-S2, and D7030X-S8. Installation Manual

Annunciators, 8 LED. D7030X, D7030X-S2, and D7030X-S8. Installation Manual Annunciators, 8 LED D7030X, D7030X-S2, and D7030X-S8 en Installation Manual Annunciators, 8 LED Notices en 3 1 Notices These instructions cover the installation of the D703X, D7030X-S2, and D7030X-S8

More information

FMR Installation Instructions. Addressable Fire System Controller

FMR Installation Instructions. Addressable Fire System Controller FMR-7033 EN Installation Instructions Addressable Fire System Controller EN 2 FMR-7033 Installation Instructions Contents Contents Contents...2 1.0 Introduction...3 2.0 Description...3 3.0 Device Mounting...3

More information

DS7465i. Installation Instructions. Input/Output Module

DS7465i. Installation Instructions. Input/Output Module DS7465i EN Installation Instructions Input/Output Module DS7465i Installation Instructions.0 Introduction EN 2.0 Introduction The DS7465i Input/Output Module operates with compatible multiplex systems.

More information

Multiplex Eight Input Remote Modules

Multiplex Eight Input Remote Modules Multiplex Eight Input Remote Modules 1.0 Introduction These instructions cover the installation of the D7042/D7042B Eight Input Remote Modules in a fire system supervised by an FPD-7024 Fire Alarm Control

More information

Booster Power Supply Manual

Booster Power Supply Manual Supply Manual DEVELOPED BY COPYRIGHT NOTICE General Signal Building Systems Corporation 6411 Parkland Drive Sarasota, FL 34243 (941) 739-4300 Copyright 1999 General Signal Building Systems Corporation

More information

SIGA-CC1 Single Input Signal Module Installation Sheet

SIGA-CC1 Single Input Signal Module Installation Sheet SIGA-CC1 Single Input Signal Module Installation Sheet Personality codes Use the personality codes described below to configure the SIGA-CC1 module. See Table 1 for listing information Table 1: Personality

More information

Remote NAC Power Supply D7038

Remote NAC Power Supply D7038 Operation and Installation Guide Remote NAC Power Supply D7038 D7038 REMOTE NAC POWER SUPPLY Page 2 2005 Bosch Security Systems Contents Contents 1.0 Overview...5 1.1 Module Control...5 1.1.1 Option Bus

More information

Duct smoke housings, 4-wire D341/D341P and D342/D342P

Duct smoke housings, 4-wire D341/D341P and D342/D342P Duct smoke housings, 4-wire D341/D341P and D342/D342P en Installation manual Duct smoke housings, 4-wire Notices en 3 1 Notices These instructions cover the installation of the D341/D342 Duct smoke housings

More information

Print Specification. Publication. Instructions. Specific requirements. General requirements

Print Specification. Publication. Instructions. Specific requirements. General requirements Print Specification Publication GSA-CC1 Single Input Signal Module Installation Sheet P/N P-047550-1802-EN REV 04 ISS 23JUN15 Instructions This page is the print specification for the publication. It is

More information

LED Driver Module. These instructions contain procedures to follow in order to avoid personal injury and damage to equipment.

LED Driver Module. These instructions contain procedures to follow in order to avoid personal injury and damage to equipment. LED Driver Module Installation Guide 1.0 Notice These instructions are for installing Radionics LED Driver Module in a fire alarm system controlled by Radionics D8024 or D10024 Fire Alarm Control Panels

More information

Fire Safety. Installation Instructions Model SMB-2 Main Control Board OPERATION INSTALLATION

Fire Safety. Installation Instructions Model SMB-2 Main Control Board OPERATION INSTALLATION Fire Safety Installation Instructions Model SMB- Main Control Board OPERATION The SIEMENS Model SMB- board in each MXL-IQ System controls operations and monitors input device identity, network communication,

More information

D250A/D253/D261AW/D280A/D290 Series

D250A/D253/D261AW/D280A/D290 Series D0A/D/D6AW/D80A/D90 Series EN Installation Instructions / Smoke/Heat Detector Bases EN. D0A/D/D6AW/D80A/D90 Series Installation Instructions.0 Trademarks M Weatherban is a trademark of M. All rights reserved.

More information

FireNET Plus Wiring Instructions

FireNET Plus Wiring Instructions FireNET Plus Wiring Instructions This manual provides wiring instructions for the 1 loop and 2 loop version of the FireNET Plus panels, which supports our finest Hochiki s DCP protocol. Note: Refer to

More information

Duct smoke housing, 2-wire D340/D340P

Duct smoke housing, 2-wire D340/D340P Duct smoke housing, 2-wire D340/D340P en Installation manual Duct smoke housing, 2-wire Notices en 3 1 Notices These instructions cover the installation of the D340 Duct smoke housing and D340P Duct smoke

More information

D7050DH. Installation Instructions. Multiplex Photoelectric Duct Smoke Detector

D7050DH. Installation Instructions. Multiplex Photoelectric Duct Smoke Detector D700DH EN Installation Instructions Multiplex Photoelectric Duct Smoke Detector D700DH Installation Instructions.0 Description Notices These instructions cover the installation of the D700DH Multiplex

More information

Battery charger modules

Battery charger modules Battery charger modules D8132 and D8132LT en Installation manual Battery charger modules Notices en 3 1 Notices These instructions cover the installation of the D8132 Battery Charger and the D8132LT Battery

More information

ACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel

ACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel ACC-25/50ZST Zoned System Voice with Telephone Evacuation Control Panel General The AUDIO COMMAND CENTER 25/50 Zone System with FireFighters Telephone (ACC-25/50ZST) is a state-of-the-art Emergency Voice

More information

DS9400 Series. Release Notes for Firmware V2.07. Fire Alarm Control Panel

DS9400 Series. Release Notes for Firmware V2.07. Fire Alarm Control Panel DS9400 Series EN Release Notes for Firmware V2.07 Fire Alarm Control Panel DS9400 Series Release Notes for Firmware V2.07 Trademarks Trademarks Gentex is a trademark of Gentex Corporation, Fire Protection

More information

Signature Series Auto-Sync Output Module (CC1S)

Signature Series Auto-Sync Output Module (CC1S) Signature Series Auto-Sync Output Module (CC1S) Product description Mounting The Signature Series can be mounted in a North American 2-1/2 in (64 mm) deep 2-gang box or a standard 4 in square box 1-1/2

More information

Operation and Installation Guide. Zone Expansion Module D8125

Operation and Installation Guide. Zone Expansion Module D8125 Operation and Installation Guide Zone Expansion Module D8125 Page 2 2004 Bosch Security Systems, Inc. Contents 1.0 Introduction...7 1.1 Guide Organization... 7 1.2 Other Literature Referenced... 7 1.3

More information

Control Relay Modules

Control Relay Modules TM INTERNATIONAL ANALOG ADDRESSABLE INPUT/OUTPUT DEVICES Control Relay Modules Model SIGA-CR, SIGA-MCR, SIGA-CRR, Features! Provides one no/nc contact (SIGA-CR/MCR) Form C dry relay contact can be used

More information

30.45 Electric Release PDRP-2001

30.45 Electric Release PDRP-2001 The PDRP-2001 Fire Alarm Control Panel (FACP) is a six-zone control panel for single and dual hazard deluge and preaction applications. The FACP is compatible with conventional input devices (2-wire or

More information

MMF Six Zone Interface Module

MMF Six Zone Interface Module Installation and Maintenance Instructions I56-900-005 MMF-0-6 Six Zone Interface Module SPECIFICATIONS Normal Operating Voltage: 5- VDC Stand-By Current: ma Alarm Current: 40 ma (assumes all six LEDs solid

More information

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description MODUL-R FIRE ALARM CONTROL PANELS MR-2900/MR-2920 Addressable Fire Alarm Control Panels Description MR-2900 Fire Alarm Control Panel The MR-2900 fire alarm system control unit is the heart of a sophisticated

More information

Fire alarm system specification for multiple tenant retail buildings

Fire alarm system specification for multiple tenant retail buildings Date: June 20, 2011 Project name: Baederwood Shopping Center Multiple Tenant Buildings B & C City/ State: Abington, PA Landlord s Vendor Contact: Dan Morrin Jr., NECCO Security Phone: (215)638-7999 Email:

More information

SC-6 Six Supervised Control Module

SC-6 Six Supervised Control Module INSTALLATION AND MAINTENANCE INSTRUCTIONS SC-6 Six Supervised Control Module SPECIFICATIONS Normal Operating Voltage: Stand-By Current: Alarm Current: Temperature Range: Humidity: Dimensions: Accessories:

More information

IDP-Zone-6 Six Zone Interface Module

IDP-Zone-6 Six Zone Interface Module INSTALLATION AND MAINTENANCE INSTRUCTIONS IDP-Zone-6 Six Zone Interface Module BEFORE INSTALLING If the modules will be installed in an existing operational system, inform the operator and local authority

More information

LifeAlarm Fire Alarm Control Panels

LifeAlarm Fire Alarm Control Panels LifeAlarm Fire Alarm Control Panels UL, ULC Approved* Features Control panel operator convenience features: Wide viewing angle 2 x 20 (40 character) alphanumeric LCD and dedicated LEDs provide convenient

More information

/5121/5122 TrueAlert Power Supply Installation Instructions

/5121/5122 TrueAlert Power Supply Installation Instructions 4100-5120/5121/5122 TrueAlert Power Supply Installation Instructions Introduction This publication provides an overview of the features, specifications, and capabilities of the TrueAlert power supplies

More information

ECC-50/100(E) Emergency Command Center. General. Features. Emergency Voice Evacuation TYPICAL APPLICATIONS

ECC-50/100(E) Emergency Command Center. General. Features. Emergency Voice Evacuation TYPICAL APPLICATIONS ECC-50/100(E) Emergency Command Center DF-60734:A4 General Firelite s ECC-50/100 and ECC-50/100E are multipurpose emergency voice evacuation panels for fire applications, mass notification applications,

More information

4100U City and Relay Cards Installation Instructions

4100U City and Relay Cards Installation Instructions 4100U City and Relay Cards Installation Instructions Introduction This publication describes the installation procedure for the following: 4100-6031/6032 City Circuit Cards 4100-6033 Alarm Relay Card Inspecting

More information

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev Installation Guide for AL800UL-ADA NAC Power Extender Rev. 090500 Overview: The Altronix AL800UL-ADA is an extremely cost effective 8 amps voltage regulated remote power supply /battery charger. The AL800UL-ADA

More information

Product Guide. Fire Alarm Cables. Initiating Device, SLC Lines, and NAC Cables.

Product Guide. Fire Alarm Cables. Initiating Device, SLC Lines, and NAC Cables. Fire Alarm Cables Initiating Device, SLC Lines, and NAC Cables Product Guide STANDARDS Fire Alarm Systems A fire alarm system is number of devices working together to detect and warn people through visual

More information

XP6-C. Six Circuit Supervised Control Module and SYNC-1 Accessory Card

XP6-C. Six Circuit Supervised Control Module and SYNC-1 Accessory Card XP6-C Six Circuit Supervised Control Module and SYNC-1 Accessory Card General NOTIFIER s XP6-C six-circuit supervised control module provides intelligent alarm systems with supervised monitoring of wiring

More information

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option Installation PS6 SERIES Power Supplies PS6 SERIES Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option Installation and Specifications Manual ISDPS6_SERIES 08121590 PCN15016 R05/15GR

More information

ECC-50/100(E) Emergency Command Center

ECC-50/100(E) Emergency Command Center ECC-50/100(E) Emergency Command Center DF-60734:A9 C-200 General Fire Lite s ECC-50/100 and ECC-50/100E are multipurpose emergency voice evacuation panels for fire applications, mass notification applications,

More information

Installation Guide for models:

Installation Guide for models: 140 58th St. Brooklyn, NY Access Power Controllers with Power Supplies Installation Guide for models: Maximal3FD - 12VDC @ 4.6 amp or 24VDC @ 5.2 amp. - Sixteen (16) PTC protected power-limited outputs.

More information

LifeAlarm Fire Alarm Controls

LifeAlarm Fire Alarm Controls UL, ULC Approved* LifeAlarm Fire Alarm Controls 4009 IDNet NAC Extender for Control with IDNet Communications or Conventional NACs Features Provides additional notification appliance circuit (NAC) capacity

More information

PSN-1000 & PSN 1000(E) Installation Manual

PSN-1000 & PSN 1000(E) Installation Manual PSN-1000 & PSN 1000(E) Installation Manual Potter Electric Signal Company, LLC St. Louis, MO Customer Service: (866) 240-1870 Technical Support: (866) 956-1211 Fax: (314) 595-6999 www.pottersignal.com

More information

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev Installation Guide for AL600ULM Multi-Output Access Control Power Supply Charger Rev. 091800 1 AL600ULM - Multi-Output Access Control Power Supply/Charger Overview: The AL600ULM multi-output access control

More information

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual Fire Safety Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual Siemens Building Technologies, Inc. Siemens Building Technologies, Ltd. 8 Fernwood Road 2 Kenview

More information

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2 Architectural & Engineering Specifications Control Panel 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality assurance...

More information

Installation Guide for models:

Installation Guide for models: 140 58th St. Brooklyn, NY Access Power Controllers with Power Supplies Installation Guide for models: Maximal11F - Power Supply 1: 12VDC @ 3.3 amp or 24VDC @ 3.6 amp. - Power Supply 2: 12VDC @ 3.3 amp

More information

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 031703 Overview: The Altronix AL802ULADA is an extremely cost effective 8 amp voltage regulated

More information

D8125MUX. Operation and Installation Guide. Multiplex Bus Interface

D8125MUX. Operation and Installation Guide. Multiplex Bus Interface D8125MUX EN Operation and Guide Multiplex Bus Interface EN 2 D8125MUX Operation and Guide Contents Contents Contents...2 1.0 Introduction...3 1.1 Description...3 1.2 Programming...3 1.3 Listings...3 2.0

More information

AL800ULADA. NAC Power Extender. Installation Guide

AL800ULADA. NAC Power Extender. Installation Guide AL800ULADA NAC Power Extender Installation Guide Rev. 122000 AL800ULADA - NAC Power Extender Overview: The Altronix AL800ULADA is an extremely cost effective 8 amp voltage regulated remote power supply/battery

More information

D343. Installation Instructions. Air Duct Smoke Housing

D343. Installation Instructions. Air Duct Smoke Housing D E Installation Instructions Air Duct Smoke Housing D Installation Instructions.0 Overview. Trademarks ational Fire Alarm Code is a trademark of the ational Fire Protection Association, Inc. ife Safety

More information

ANNUNCIATOR FIXED MODULE

ANNUNCIATOR FIXED MODULE 12 Clintonville Road Northford, CT 06472 Phone: 203-484-7161 Fax: 203-484-7118 THE ANNUNCIATOR FIXED MODULE Installation Manual for the AFM-16ATF and AFM-32AF Annunciator Modules Document # 15970 3/27/95

More information

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep. 140 58th St. Brooklyn, NY Power Supply/Chargers Installation Guide Models Include: eflow4n/eflow4nx - 4 amp @ 12VDC or 24VDC eflow4n8/eflow4nx8 eflow4n8d/eflow4nx8d - 4 amp @ 12VDC or 24VDC - 4 amp @ 12VDC

More information

Multiple Input and Output Modules

Multiple Input and Output Modules Kingfisher Company, inc. Multiple Input and Output Modules Features: Removable 12 to 18 AWG plug-in terminal blocks Individual LED indicators Unused addresses may be disabled Rotary address switches Class

More information

July 14, 1999 DF C-100.

July 14, 1999 DF C-100. www.firelite.com GENERAL The Fire Lite FIRE COMMAND 25/50 is a state-of-theart, compact, stand-alone or slave Emergency Voice Evacuation Control Panel (VECP). The FIRE COMMAND 25/50 is offered in a self-contained,

More information

FCPS-24F FIRE ALARM FIELD CHARGER/POWER SUPPLY FOR FIRE PROTECTION/SIGNALING SERVICE FCPS-24F/FCPS-24FE. Field Charger/Power Supply

FCPS-24F FIRE ALARM FIELD CHARGER/POWER SUPPLY FOR FIRE PROTECTION/SIGNALING SERVICE FCPS-24F/FCPS-24FE. Field Charger/Power Supply One Fire-Lite Place Northford, CT 06472 Phone: (203) 484-7161 FAX: (203) 484-7118 FCPS-24F FIRE ALARM FIELD CHARGER/POWER SUPPLY FOR FIRE PROTECTION/SIGNALING SERVICE FCPS-24F/FCPS-24FE Field Charger/Power

More information

SPEC SHEET. Simple Expansion Solutions ZONE EXPANSION MODULES: SINGLE AND MULTIPLE POINT

SPEC SHEET. Simple Expansion Solutions ZONE EXPANSION MODULES: SINGLE AND MULTIPLE POINT SPEC SHEET Simple Expansion Solutions Expand your DMP panel options with a wide array of expansion modules. Add supervised Class B burglary zones. Connect non-powered burglary or fire type devices for

More information

AL600ULADA. NAC Power Extender. Installation Guide

AL600ULADA. NAC Power Extender. Installation Guide AL600ULADA NAC Power Extender Installation Guide Rev. 122000 AL600ULADA - NAC Power Extender Overview: The Altronix AL600ULADA is an extremely cost effective 6.5 amp voltage regulated remote power supply/battery

More information

FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200

FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200 FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200 1.0 General 1.1 Manufacturer Manufacturer of the Fire Alarm Control Panel (FACP) equipment shall be: Digital Monitoring Products, Incorporated 2500 N.

More information

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep. Power Supply/Chargers Installation Guide Models Include: eflow4na8-4a @ 12VDC or 24VDC - Eight (8) Fused Outputs eflow6na8-4a @ 12VDC or 24VDC - Eight (8) Fused Outputs eflow102na8-10a @ 12VDC - Eight

More information

ECC-50/100C. Emergency Command Center

ECC-50/100C. Emergency Command Center ECC-50/100C Emergency Command Center Canadian DF-60815:B Emergency Communications General Fire-lite s ECC-50/100C is a multipurpose emergency voice evacuation panel for fire applications, mass notification

More information

GENERAL STANDARD FEATURES. ISO-9001 Engineering and Manufacturing Quality System Certified to International Standard ISO-9001 PATENT PENDING

GENERAL STANDARD FEATURES. ISO-9001 Engineering and Manufacturing Quality System Certified to International Standard ISO-9001 PATENT PENDING GENERAL The VEC 25/50 is a state-of-the-art, compact, stand-alone or slave Emergency Voice Evacuation Control. The VEC 25/50 is offered in a self-contained, cost-effective design and includes a 25 Watt,

More information

General Routing Interface

General Routing Interface General Routing Interface Features The General Routing Interface Card is an optional module to provide Fire and Fault Routing Outputs compliant with BSEN54-2: 1998 Clauses 7.9 and 8.9 and BS5839-1: 2002.

More information

LDM Series Lamp Driver Modules For Graphic Annunciation and Control

LDM Series Lamp Driver Modules For Graphic Annunciation and Control 12 Clintonville Road Northford, CT 06472 (203) 484-7161 FAX: (203) 484-7118 LDM Series Lamp Driver Modules For Graphic Annunciation and Control Used with the System 500, System 5000, AM2020/AFP1010 and

More information

Installation Instructions Model HZM

Installation Instructions Model HZM Installation Instructions Model Remote Conventional Zone Module INTRODUCTION The Model from is an intelligent device that connects a single zone of conventional devices to a DLC (FireFinder-XLS System)

More information

Concerns: Affects: Dated: June 12, SECTION 1: GENERAL Scope Work Included... 3

Concerns: Affects: Dated: June 12, SECTION 1: GENERAL Scope Work Included... 3 Technical Service Note Detection Systems, Inc. Fairport, New York 14450-9199 Technical Service (800) 374-7454 Sales: (800) 289-0096 and (585) 223-4060 Fax: (585) 223-9180 Concerns: Affects: Dated: June

More information

ADEMCO 4208SNF V-Plex Universal Class A Module INSTALLATION AND SETUP GUIDE

ADEMCO 4208SNF V-Plex Universal Class A Module INSTALLATION AND SETUP GUIDE K3179V2 2/11 Rev. A ADEMCO 4208SNF V-Plex Universal Class A Module INSTALLATION AND SETUP GUIDE FEATURES The ADEMCO 4208SNF Universal Class A Module can be used in either of two different applications.

More information

RELEASE DEVICE CONTROLS

RELEASE DEVICE CONTROLS RELEASE DEVICE CONTROLS RELEASE DEVICE MODEL C+ INSTALLATION MANUAL UL LISTED CANADIAN LISTED CSFM: 7300-48:00 GENERAL DESCRIPTION: MADE IN THE U.S.A. S/N: The LM0-C+ Release Device/Control Panel is a

More information

Fire Control/Communicator

Fire Control/Communicator Operation and Installation Manual Fire Control/Communicator 1 2 3 4 5 12V AC,20V A, 60Hz or +24V DC 12V AC, 20V A, 60Hz or -24V DC EARTH GND BATTERY - BATTERY + 6 INITIATING A1-7 INITIATING A2-8 INITIATING

More information

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep. Power Supply/Chargers Installation Guide Models Include: eflow4na8d - 4A @ 12VDC or 24VDC - Eight (8) PTC Outputs eflow6na8d - 4A @ 12VDC or 24VDC - Eight (8) PTC Outputs eflow102na8d - 10A @ 12VDC - Eight

More information

GEMC-FW-SLC FIRE SIGNALING LINE CIRCUIT MODULE INSTALLATION INSTRUCTIONS

GEMC-FW-SLC FIRE SIGNALING LINE CIRCUIT MODULE INSTALLATION INSTRUCTIONS 333 Bayview Avenue Amityville, New York 11701 For Sales and Repairs, (800) 645-9445 For Technical Service, (800) 645-9440 Publicly traded on NASDAQ Symbol: NSSC GEMC-FW-SLC FIRE SIGNALING LINE CIRCUIT

More information

AU MX Digital Loop Card Installation Instructions

AU MX Digital Loop Card Installation Instructions 4100-6077AU MX Digital Loop Card Installation Instructions Cautions and Warnings READ AND SAVE THESE INSTRUCTIONS - Follow the instructions in this installation manual. These instructions must be followed

More information

Installation Guide. Control/Communicator

Installation Guide. Control/Communicator Installation Guide Control/Communicator 33120G Page 2 Copyright 2001 Radionics Contents 1.0 Introduction... 5 1.1 Listings and Approvals... 5 1.1.1 Fire... 5 1.1.2 Burglary... 5 1.2 FCC Notice... 5 1.2.1

More information

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN Honeywell 12 Clintonville Road Northford, CT 06472 http://www.honeywellpower.com HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN 04-350 Product Installation

More information

Addressable Fire Alarm Control Panel

Addressable Fire Alarm Control Panel PRODUCT SPECIFICATION XR2400F Addressable FACP Addressable Fire Alarm Control Panel Description The DMP XR2400F Addressable Fire Alarm Control Panel is an expandable Fire Alarm Control with built-in DACT

More information

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger Installation Guide for AL300ULM Multi-Output Access Control Power Supply Charger R AL300ULM - Multi-Output Access Control Power Supply/Charger Overview: The AL300ULM multi-output access control power supply/charger

More information

FireNET Fire Alarm Control Panel Installation Manual

FireNET Fire Alarm Control Panel Installation Manual FireNET L@titude Fire Alarm Control Panel Installation Manual Page 2 Contents Contents Contents 3 Glossary 9 Compliance Information 11 Section 1: Introduction 12 Technical Support 12 Return Material Authorization

More information

MONROE PUBLIC LIBRARY WATERFLOW MONITORING SYSTEM

MONROE PUBLIC LIBRARY WATERFLOW MONITORING SYSTEM Waterflow Alarm Submittal Booklet For MONROE PUBLIC LIBRARY WATERFLOW MONITORING SYSTEM 380 South 5th St Monroe, OR 2G CONSTRUCTION PO Box 11735 Eugene, OR Convergint Technologies LLC 16575 SW 72nd Avenue

More information

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC. M Series Multi-Output Access Control Power Supply Charger Installation Guide Models Include: AL300ULM AL400ULM - 2.5 amp @ 12VDC or 24VDC. - 4 amp @ 12VDC or 3 amp @ 24VDC. AL600ULM AL1012ULM - 6 amp @

More information

D9412GV2/D7412GV2. Approved Applications Compliance Guide. Control Panels

D9412GV2/D7412GV2. Approved Applications Compliance Guide. Control Panels D9412GV2/D7412GV2 EN Approved Applications Compliance Guide Control Panels D9412GV2/D7412GV2 Approved Applications Compliance Guide Listings and Approvals Listings and Approvals Fire UL Underwriters Laboratories

More information

MR-2602 Two Zone Fire Alarm Control Panel

MR-2602 Two Zone Fire Alarm Control Panel MR-2602 Two Zone Fire Alarm Control Panel Installation Manual Secutron LT-2015 Rev.3 July 2010 Table of Contents 1 Introduction 1.1 The MR-2602 Fire Alarm Control Unit... 11 1.1.1 General features...

More information

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER Cautions and Warnings DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED. Upon unpacking your Simplex product, inspect the contents of the carton for shipping damage. If damage is apparent, immediately

More information

Series. Access Power Controllers. Installation Guide

Series. Access Power Controllers. Installation Guide Series Access Power Controllers Installation Guide Models Include: Maxim11 - Power Supply 1: 12VDC @ 3.5 amp or 24VDC @ 2.7 amp. - Power Supply 2: 12VDC @ 3.5 amp or 24VDC @ 2.7 amp. - Sixteen (16) fuse

More information

AL1042ULADA. NAC Power Extender. Installation Guide (See Application Guide for additional information) Rev

AL1042ULADA. NAC Power Extender. Installation Guide (See Application Guide for additional information) Rev Altronix Corp. 140 58th St. Brooklyn, NY AL1042ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 052313 Agency Listings: UL Listed for Control Units for

More information

June 10, 2002 DF C S2424

June 10, 2002 DF C S2424 GENERAL www.firelite.com The Fire Lite FIRE COMMAND 25/50X is a state-of-theart Emergency Voice Evacuation Control Panel (VECP), with significant technological enhancements that set it apart from other

More information

D296/D297. Installation Instructions Long-Range Beam Smoke Detectors

D296/D297. Installation Instructions Long-Range Beam Smoke Detectors D96/D97 EN Installation Instructions Long-Range Beam Smoke Detectors D96/D97 Installation Instructions.0 Description FCC Compliance Notice This equipment was tested and complies with the limits for a Class

More information

Commercial Series TriTech Motion Detector. Reference Guide

Commercial Series TriTech Motion Detector. Reference Guide Commercial Series riech Motion Detector en Reference Guide Commercial Series riech Motion Detector able of contents en 3 able of contents 1 Safety 4 Introduction 5.1 About documentation 5. Bosch Security

More information

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC. M Series Multi-Output Access Control Power Supply Chargers Installation Guide Models Include: AL300ULM AL400ULM - 2.5 amp @ 12VDC or 24VDC. - 3 amp @ 12VDC or 4 amp @ 24VDC. AL600ULM AL1012ULM - 6 amp

More information

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906 s Data Sheet Fire Safety & Security Products SXL-EX Fire Alarm Control Panel Conventional Zone Fire Alarm Control Panel ARCHITECT AND ENGINEER SPECIFICATIONS Four (4) zones expandable to eight (8) zones

More information

CZ-6A Six Zone Interface Module

CZ-6A Six Zone Interface Module INSTALLATION AND MAINTENANCE INSTRUCTIONS CZ-6A Six Zone Interface Module 658 Kitimat Rd. Unit #6 Mississauga, Ontario L5N T5-800-SENSOR, FAX: 905-8-077 www.systemsensor.ca SPECIFICATIONS Normal Operating

More information

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger Installation Guide for AL400ULM Multi-Output Access Control Power Supply Charger R AL400ULM - Multi-Output Access Control Power Supply/Charger Rev. 072500 Overview: The AL400ULM multi-output access control

More information

Fire Safety. Installation Instructions Model MMB-2 Main Control Board OPERATION. INSTALLATION Always remove power before installation.

Fire Safety. Installation Instructions Model MMB-2 Main Control Board OPERATION. INSTALLATION Always remove power before installation. Fire Safety nstallation nstructions Model MMB- Main ontrol Board OPERATON The SEMENS Model MMB- board in each MXL System controls operations and monitors input device identity, network communication, and

More information

This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control

This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control File: S8485 Wiring Diagram This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control Panel. The operation of this product is intended for indoor

More information

1. POWERPATH Operation

1. POWERPATH Operation 273 Branchport Avenue Long Branch, NJ 07740 (800) 631-2148 www.wheelockinc.com Thank you for using our products. INSTALLATION INSTRUCTIONS MODEL PS-12/24-6 POWERPATH Use this product according to this

More information

Control Panel. D9412GV4/D7412GV4 v2.00. en UL Installation Instructions

Control Panel. D9412GV4/D7412GV4 v2.00. en UL Installation Instructions Control Panel D9412GV4/D7412GV4 v2.00 en UL Installation Instructions Control Panel Table of Contents en 3 Table of contents 1 Introduction 4 1.1 About documentation 4 1.2 Determine Bosch Security Systems,

More information

D285DH. Installation Instructions Photoelectric Duct Smoke Detector

D285DH. Installation Instructions Photoelectric Duct Smoke Detector D85DH EN Installation Instructions Photoelectric Duct Smoke Detector D85DH Installation Instructions.0 Introduction FCC Notice The D85DH Photoelectric Duct Smoke Detector complies with Part 5 of the Federal

More information

RM-1 Series. Remote Microphones. (RM-1, RM-1SA) Document Revision B RM-1 RM-1SA. RM-1 on ADP-4 dress panel. RM-1SA in a CAB-RM or CAB-RMR

RM-1 Series. Remote Microphones. (RM-1, RM-1SA) Document Revision B RM-1 RM-1SA. RM-1 on ADP-4 dress panel. RM-1SA in a CAB-RM or CAB-RMR This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864 9th Edition. The following products have not received UL

More information