1 Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance Checklist Code No. LIT Release 1.2 Issued February 10, 2005 Document Introduction Related Documentation Smoke Control UL 864 UUKL Compliance Checklist Overview UL 864 UUKL Smoke Control Compliance Survey General UUKL Requirements Fire Fighter s Smoke Control Station (FSCS) UUKL FSCS UUKL Requirements DX-9100 Applications UUKL Requirements Smoke Control Wiring UUKL Requirements Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance Checklist 1

2 2 Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance Checklist

3 Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance Checklist Document Introduction This document summarizes the most common requirements to configure the Metasys system extended architecture to comply with Underwriters Laboratories, Inc. (UL), UL 864 UUKL Smoke Control Listing. A UL 864 UUKL Smoke Control Compliance Survey form is followed by tables listing the requirements for UL 864 UUKL Listing compliance. The purpose of the enclosed UL 864 UUKL Smoke Control Compliance Survey is to provide a record of those elements of National Fire Protection Association (NFPA) 92A and UUKL that Johnson Controls, Inc. does or does not provide. Related Documentation If you are bidding, engineering, installing, or commissioning a Metasys system extended architecture requiring UUKL Smoke Control Listing compliance, follow the guidelines and procedures outlined in the documents listed in Table 1. Table 1: Related Documentation For Information On Refer to LIT No./Part No. Smoke Control Guidelines and Procedures Smoke Control Wiring Network Automation Engine (NAE) Installation Smoke Control Applications Metasys System Extended Architecture Smoke Control System Technical Bulletin Metasys System Extended Architecture Smoke Control Wiring Technical Bulletin LIT LIT NAE55/NIE Installation Instructions Part No Single Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System Extended Architecture Application Note Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture Application Note Warehouse Smoke Control with FSCS Override -Metasys System Extended Architecture Application Note Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture Application Note Weekly Testing of Dedicated Stairwell Pressurization Fans - Metasys System Extended Architecture Application Note LIT LIT LIT LIT LIT Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance Checklist 3

4 Smoke Control UL 864 UUKL Compliance Checklist Overview UUKL is an identifier created by UL to identify those products Listed under UL 864 as part of a Smoke Control system. Products covered by this listing are intended to be installed in conjunction with Heating, Ventilating, and Air Conditioning (HVAC) equipment to form a system for controlling the flow of smoke in a building during a fire condition in accordance with NFPA Recommended Practice 92A. It is important that we document the system elements that are being provided. The UL 864 UUKL Smoke Control Compliance Survey can be used to provide that documentation. In the case where a project specification dictates compliance with the UUKL Listing, but contains elements of the system design that conflict with the Listing or are omitted, the completed UL 864 UUKL Smoke Control Compliance Survey can be given to the designer and/or the AHJ to obtain recognition and agreement on the extent of Listing compliance. This should occur prior to bid and/or proposal. Once agreement is reached with the AHJ, designer, and customer, the signed or initialed Smoke Control Compliance Checklist must become a permanent part of the project file. Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance Checklist 4

5 UL 864 UUKL Smoke Control Compliance Survey Date of Survey Conducted By Project Location Branch Office Project Manager Specifications UL Compliance Required By: Building Codes Contract Applicable Building Codes and Standards Local (Branch) Person Providing and Verifying Information Initials Name Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance Checklist 5

6 General UUKL Requirements Table 2 lists general requirements for UL 864 UUKL Listing compliance. Mark Yes/No for compliance and initial each item that was verified. Table 2: General UUKL Requirements Requirement Communication links between buildings are fiber-optic cable or copper cable buried in a conduit separate from power wiring. Each binary output object used for pressurization and exhaust control is configured with positive feedback. The feedback input monitors the associated controlled equipment status (for example, both open and closed, on and off). For smoke control dampers, there may be a pair of feedback binary inputs for two damper end switches. Any mismatch of a command and status of the binary output occurring longer than the allowed response time must create a trouble light indication at the FSCS. For fans there is positive indication of airflow. Non UL-Listed control equipment must be isolated from the UL-Listed network. The Weekly Testing of Dedicated Stairwell Pressurization Fans application is used on all dedicated smoke control systems. Automatic smoke control sequences take precedence over HVAC automatic and manual commands. Manual FSCS takes precedence over all else. Automatic activation of any smoke control sequence of operation has priority over any non-smoke control manual commands and any automatic environmental control strategy, when an auto smoke control sequence is initiated. High and low temperature protection devices and return and exhaust air-duct smoke detectors are bypassed. Response time for individual smoke control fans to reach commanded state is no more than 60 seconds. Response time for individual smoke control dampers to reach commanded state is no more than 75 seconds. Fire alarm system manual pull stations do not initiate automatic smoke control sequences. Smoke detectors are used to initiate a smoke control strategy only as detailed in the Metasys System Extended Architecture Smoke Control System Technical Bulletin (LIT ). All Application Specific Controls (ASCs) that monitor or control smoke control equipment are UUKL Listed. Electrical disconnects, overloads, duct static pressure limits, and supply air duct smoke detectors are not overridden by manual or automatic smoke control strategies. Y/N NA Person Verifying Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance Checklist 6

7 Fire Fighter s Smoke Control Station (FSCS) UUKL FSCS UUKL Requirements Table 3 lists general requirements for UL 864 UUKL Listing compliance for FSCSs where required. Mark Yes/No for compliance and initial each item that was verified. Table 3: FSCS UUKL Requirements Requirement FSCS is UUKL Listed and provides manual control of the smoke control system, a UUKL Listed annunciator panel is used as FSCS. Custom annunciator FSCS is connected to a UUKL Listed Smoke Control NAE55. FSCS provides positive indication of the operation of all smoke control equipment (for example, both open and closed, on and off). FSCS provides audible and visible trouble indication when any smoke control equipment does not respond to automatic or manual commands. FSCS simultaneously displays the status of all smoke control systems dampers, fans FSCS has manual control over all smoke control systems. FSCS can override (partially or in full) any operation in progress, including programmed actions, non-smoke control manual overrides. FSCS has highest priority over all smoke control systems. A building diagram or equivalent at FSCS clearly indicates the type and location of all smoke control equipment. FSCS indicates the actual status (not the command status) of systems and equipment used for smoke control. This includes the current position of each damper used in an active smoke control sequence and the status of airflow status of every fan. FSCS activates an audible signal if the operation proof sensor (binary feedback point) failed to provide positive feedback that fan or damper reached its intended position. Only one FSCS on Metasys system is used for smoke control applications unless approved by the AHJ. The FSCS manual activation or deactivation of any smoke control device has priority over any automatic smoke or environmental sequence of operation. Any return air duct smoke detectors in duct work of each HVAC fan system used for smoke control exhaust or purge only reports an alarm condition to the FSCS or fire alarm annunciator located at the FSCS and does not stop the fan. All hardware supervision alarms, such as binary feedback alarms on fans and dampers, as well as system alarm points turn on FSCS alarm horn. Annunciation on the FSCS of change of state of smoke control equipment is no more than 10 seconds after reaching commanded state. Y/N NA Person Verifying Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance Checklist 7

8 DX-9100 Applications UUKL Requirements Table 4 lists general requirements for UL 864 UUKL Listing compliance for DX-9100 hardware with fire alarm panel applications. Mark Yes/No for compliance and initial each item that was verified. Table 4: DX-9100 Applications UUKL Requirements Requirement If the Digital Inputs (DIs) are used for smoke control, the fuse on the DI circuit of that DX-9100 is monitored by a jumper wire across a DI, mapped to the NAE/NIE/Site Director. If the fuse goes into trouble then the alarm is activated in the NAE and a trouble light for the affected equipment energizes at the FSCS. If Analog Outputs (AOs) are used for smoke control, the fuse on the AO circuit of that DX-9100 is monitored by doing the following. They are fused and the fuse is monitored. To do this, set one AO for voltage and define an Analog Input (AI) for voltage. Connect a Control Output (CO) set for 50.0 to the AO that is ranged for This gives the AO a 50 percent signal or a 5 volt output. This output is hardwired back to the AI defined for voltage with a range of and a low limit of 20. If the AO fuse blows, the voltage will go to 0 and the AI will go into low alarm. This alarm must be monitored as a critical alarm. Each DX-9100 used for smoke control has a Metasys system poll priority of 1 or 2. All fans controlled by the DX-9100 have an airflow status switch. Any mismatch of command and status of the fans reports a critical alarm at FSCS. An IFC-640/1010/2020/3030 is connected to the Metasys system via the BACnet Gateway to initiate automatic smoke control actions. If the fire alarm control panel alarms are not displayed on an annunciator at the FSCS, all alarm input DIs are monitored and report critical alarms at the NAE when they close (turn On), such as a fire alarm control panel smoke detector alarm point. Locate the annunciator panel at the FSCS to enable the operator to monitor all alarms in the fire alarm system. The buttons on the face of the DX-9100 are not used to override smoke control points. Any DX-9100 for smoke control is locked in a Listed enclosure, such as the EN-EWC25-0 to prevent unauthorized access. All alarm input DIs are monitored and report critical alarms at the NAE/NIE/Site Director when they close (turn On). Any signal circuits connected to the XP9102 do not leave the room in which the XP9102 is mounted unless transient protection is applied as detailed in the Metasys System Extended Architecture Smoke Control Wiring Technical Bulletin (LIT ). If signal circuits leaves the room, transient protection is applied as detailed in the Metasys System Extended Architecture Smoke Control Wiring Technical Bulletin (LIT ). Y/N NA Person Verifying Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance Checklist 8

9 Smoke Control Wiring UUKL Requirements Table 5 lists requirements for UL 864 UUKL Listing compliance for Smoke Control Wiring. Mark Yes/No for compliance and initial each item verified. Table 5: Smoke Control Wiring UUKL Requirements Requirement Communication links between buildings are fiber-optic cable or copper cable buried in a conduit separate from power wiring. If N1 or N2 signal circuits leave the room, transient protection is applied as detailed in the Metasys System Extended Architecture Smoke Control Wiring Technical Bulletin (LIT ). When using DX-9100 product line for smoke control, the DX F base must be used. If the XP-9102 is used and the signal circuit leaves the room in which the XP-9102 is installed, the protection is shown in the Metasys System Extended Architecture Smoke Control Wiring Technical Bulletin (LIT ). The Metal Oxide Varistor (MOV) must be a Johnson Controls Code No. SMOKE-MOVEKIT-0. The transzorbs in the Metasys System Extended Architecture Smoke Control Wiring Technical Bulletin (LIT ) are installed on the base frame products. Only terminals in use and signal circuits leaving a room where a controller is installed have transient protection. The transzorb must be a Johnson Controls Code No. SMOKE-TRNKIT-0. MOVs are installed on the AHU, UNT, and VAV products as shown in the Metasys System Extended Architecture Smoke Control Wiring Technical Bulletin (LIT ). Only terminals in use, and I/O wiring leaving a room where a controller is installed, or wire more than 20 feet in length have transient protection. The MOV is a Johnson Controls Code No. SMOKE-MOVKIT-0. For faston versions use Johnson Controls Code No. AS-MOVKIT-0 Verify that a Tripp Lite ISOBAR8ULTRA surge protector or a Tripp Lite ISOBAR12ULTRA surge protector protects all 120 VAC power sources. If fiber-optic cable is used, verify that it meets the requirements listed in the Metasys System Extended Architecture Smoke Control System Wiring Technical Bulletin (LIT ) If copper cable is used, verify that it meets the requirements listed in the Metasys System Extended Architecture Smoke Control System Wiring Technical Bulletin (LIT ). Verify that copper cable connected to media converters does not leave the room in which the media converter is installed. Verify that all RJ45 cables are protected from electrical surges through the use of the American Power Conversion (APC) Protect Net (Model PNET1) surge protector at each end of the RJ45 cable. Verify that only the Smoke Control NAE, MS-NAE5510-0U, is used for smoke control in a UUKL smoke control system. If an RS-485-to-RS485 repeater is used to isolate UUKL from non-uukl devices on an N2 Bus, verify that it is installed in a UL-Listed enclosure. Verify that the power-limited and non-power limited wiring from the repeater is seperated. Refer to the Metasys System Extended Architecture Smoke Control System Wiring Technical Bulletin (LIT ). The transzorb must be a Johnson Controls Code No. SMOKE-TRNKIT-1. Y/N NA Person Verifying Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance Checklist 9

10 Controls Group 507 E. Michigan Street Milwaukee, WI Metasys is a registered trademark of Johnson Controls, Inc. All other marks herein are the marks of their respective owners Johnson Controls, Inc. 10 Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance Checklist Published in U.S.A.

Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT

Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT-1201739 Release 1.2 Issued Date July 30, 2004 Supersedes Document Introduction.................................................

More information

Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture

Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture Code No. LIT-1201743 Release 1.2 Issued Date July 30, 2004 Supersedes Document Introduction.................................................

More information

Metasys System Extended Architecture Smoke Control System

Metasys System Extended Architecture Smoke Control System Metasys System Extended Architecture Smoke Control System Technical Bulletin MS-NAE5510-0U Code No. LIT-1201684 Release 1.2 Issued February 10, 2005 Document Introduction.................................................

More information

Single Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System Extended Architecture

Single Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System Extended Architecture Single Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System Extended Architecture Application Note Code No. LIT-1201736 Release 1.2 Issued January 10, 2005 Document Introduction.................................................

More information

Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture

Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture Code No. LIT-1201737 Release 1.2 Issued January 10, 2005 Document Introduction.................................................

More information

DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans

DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans Metasys Network Technical Manual 636 DX-9100/9120 Applications Section Application Note Issue Date 0497 APPLICATION NOTE DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans Introduction

More information

DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit

DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit Metasys Network Technical Manual 636 DX-9100/9120 Applications Section Application Note Issue Date 0497 APPLICATION NOTE DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit Introduction

More information

York 25-Ton VAV Rooftop Unit

York 25-Ton VAV Rooftop Unit HVAC PRO for Windows User s Manual 637.5 OEM Section Technical Bulletin Issue Date 0996 York 25-Ton VAV Rooftop Unit Introduction Page 3 Overview *3 Configuration 5 Sequence of Operation 7 Modes of Operation

More information

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL SECTION 15910 SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division

More information

Solution Guide. UUKL Smoke Control System. 1/6. UL 864, 9th Edition, UUKL Smoke Control Listing. Overview

Solution Guide. UUKL Smoke Control System.  1/6. UL 864, 9th Edition, UUKL Smoke Control Listing. Overview Solution Guide UL 864, 9th Edition, UUKL Smoke Control Listing Overview Applications Distech Controls UUKL smoke control system can be used for: Dedicated smoke control applications: Used exclusively for

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

Metasys System Extended Architecture Fire System Integration Using the IFC BACnet Gateway

Metasys System Extended Architecture Fire System Integration Using the IFC BACnet Gateway Metasys System Extended Architecture Fire System Integration Using the IFC BACnet Gateway Code No. LIT-1201993 Software Release 2.1 Issued April 12, 2006 Supersedes July 20, 2005 Document Introduction.................................................

More information

Smoke Control Manual

Smoke Control Manual Smoke Control Manual For BACnet Systems ON BAC-5800 Controller OFF ON BAC-5800 Controller Pressurized Third Floor Stairwell Fan ON OFF BAC-5800 Controller Exhausted Second Floor OFF BAC-5800 Controller

More information

WHITE PLAINS SMOKE CONTROL CODE PART 1. GENERAL REQUIREMENTS

WHITE PLAINS SMOKE CONTROL CODE PART 1. GENERAL REQUIREMENTS WHITE PLAINS SMOKE CONTROL CODE a. Application of Code. PART 1. GENERAL REQUIREMENTS The following uniform standards and procedures shall apply to the design, installation and testing of new smoke purge

More information

DX-9100/9120 Local Sonalert Logic

DX-9100/9120 Local Sonalert Logic Metasys Network Technical Manual 636 DX-9100/9120 Applications Section Application Note Issue Date 0497 APPICATION NOTE DX-9100/9120 ocal Sonalert ogic Introduction Page 3 Application Description *3 Design

More information

Fire Operator Workstation (Fire OWS) User s Guide

Fire Operator Workstation (Fire OWS) User s Guide Fire Operator Workstation (Fire OWS) User s Guide 1-1 Fire Operator Workstation (Fire OWS) User s Guide Introduction This user s guide details the components, capabilities, and operation procedures of

More information

DX-9100 Applications from Engineering Services

DX-9100 Applications from Engineering Services System 9100 Technical Manual 636.4 Application Examples Section Technical Bulletin Issue Date 0896 DX-9100 Applications from Engineering Services Introduction Page 3 Overview 3 Air Handling Unit Applications

More information

Metasys Integrator Compu-Aire Application

Metasys Integrator Compu-Aire Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0496 APPLICATION NOTE Metasys Integrator Compu-Aire Application lntroduction Page 3 Application Details

More information

Metasys Integrator TITUS Application

Metasys Integrator TITUS Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date October 12, 2005 APPLICATION NOTE Metasys Integrator TITUS Application lntroduction Page 3 Application

More information

ONYX FirstVision Specification Interactive Firefighters Display

ONYX FirstVision Specification Interactive Firefighters Display ONYX FirstVision Specification Interactive Firefighters Display NOTIFIER is a registered trademark, and ONYX FirstVision, NOTI FIRE NET, and VeriFire are trademarks of Honeywell International Inc. Microsoft

More information

Multi-Story Building Floor Above/Floor Below Pressurization and Exhaust Logic

Multi-Story Building Floor Above/Floor Below Pressurization and Exhaust Logic Metasys Network Technical Manual 636 GPL Applications Section Application Note ssue Date 0497 APPLCATN NT Multi-Story Building Floor Above/Floor Below Pressurization and xhaust Logic ntroduction Page 3

More information

P2000 and Metasys System Integration

P2000 and Metasys System Integration P2000 and Metasys System Integration Product Bulletin Code No. LIT-12011781 Software Release 3.12 Issued June 20, 2013 Supersedes April 20, 2012 Refer to the QuickLIT Web site for the most up-to-date version

More information

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL MADE IN THE U.S.A. U.L. LISTED CANADIAN LISTED CSFM: 7300-1418:100 GENERAL DESCRIPTION SERIAL NUMBER The Cookson Company FIREFLY II PLUS Time Delay Release

More information

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment. SECTION 23 09 93 - SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1 WORK INCLUDES A. Base Bid: Heating Contractor provide: Control sequences for HVAC systems, subsystems, and equipment. B. Alternate

More information

RELEASE DEVICES RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: :100 GENERAL DESCRIPTION:

RELEASE DEVICES RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: :100 GENERAL DESCRIPTION: RELEASE DEVICES MADE IN THE U.S.A. RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: 7300-1418:100 GENERAL DESCRIPTION: S/N: The "WPS" World Power Series, Time Delay Release

More information

Firefly II Multi Voltage RELEASE DEVICES. Firefly II & IIB-MV INSTALLATION MANUAL

Firefly II Multi Voltage RELEASE DEVICES. Firefly II & IIB-MV INSTALLATION MANUAL Firefly II Multi Voltage RELEASE DEVICES Firefly II & IIB-MV INSTALLATION MANUAL GENERAL DESCRIPTION: S/N The The Cookson Company Firefly II-MV time delay release devices are designed for use on rolling

More information

Metasys Integrator Cleaver-Brooks Application

Metasys Integrator Cleaver-Brooks Application Metasys Connectivity Technical Manual 69. Metasys Integrator Section Application Note Issue Date 0900 APPLICATION NOTE Metasys Integrator Cleaver-Brooks Application lntroduction Page Application Details

More information

TrueAlarm Analog Sensing

TrueAlarm Analog Sensing TrueAlarm Analog Sensing UL, ULC Listed* Addressable Duct Sensor Housings with TrueAlarm Photoelectric Sensor; Available with Multiple Relay Features Compact air duct sensor housing with clear cover to

More information

COUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III

COUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III SECTION 28 3111 - DIGITAL ADDRESSABLE FIRE ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

Metasys Integrator Airflow Application

Metasys Integrator Airflow Application Metasys Connectivity Technical Manual 69. Metasys Integrator Section Application Note Issue Date 0998 APPLICATION NOTE Metasys Integrator Airflow Application lntroduction Page Application Details * Component

More information

MODEL B2 INSTALLATION MANUAL

MODEL B2 INSTALLATION MANUAL RELEASE DEVICES GENERAL DESCRIPTION MODEL B2 INSTALLATION MANUAL S/N: The B2 Series Time Delay Release Devices are UL Listed, Canadian Listed, and CSFM Listed for use on rolling doors, single-slide and

More information

Reciprocating Chiller

Reciprocating Chiller HVAC PRO for Windows User s Manual 637.5 OEM Section Technical Bulletin Issue Date 1094 Reciprocating Chiller Reciprocating Chiller Page 3 Description 3 Theory of Operation 5 Overview 5 Control Sequence

More information

JCI - Smoke Control Systems Overview 10/27/2016

JCI - Smoke Control Systems Overview 10/27/2016 If the you can read this Click on the icon to choose a picture or To Reset: Right click on the slide thumbnail and select reset slide or choose the Reset button on the Home ribbon (next to the font choice

More information

SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. SS90-WPS MODEL A/B INSTALLATION MANUAL

SOLID STATE SECURITIES, INC. THE SS90 SERIES RELEASE DEVICES MADE IN THE U.S.A. SS90-WPS MODEL A/B INSTALLATION MANUAL S S S S S S LISTED L * PATENT PENDING S S 90 OLID TATE ECURITIES, INC SOLID STATE FAIL-SAFE UNIT U 99Y9 RESET RELEASING DEVICE SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE

More information

DIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM

DIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM DIVISION 26 ELECTRICAL SECTION 26 81 11 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install all equipment and accessories for a complete local, analog addressable, manually and automatically actuated,

More information

GCS Multipoint Carbon Dioxide Gas Concentration Sampler

GCS Multipoint Carbon Dioxide Gas Concentration Sampler Electronic Control Manual 16 Sensors and Stats Section S Technical Bulletin Issue Date 0101 GCS-000- Multipoint Carbon Dioxide Gas Concentration Sampler Product Overview Page *3 Installation 5 Mounting

More information

Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit

Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit Metasys Network Technical Manual 636 GPL Applications Section Application Note ssue Date 0497 APPLATN NTE Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit ntroduction Page 3 Application Description

More information

THE "SS90" SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL

THE SS90 SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL S S S S S S S S 90 OLID TATE ECURITIES, INC SOLID STATE FAIL-SAFE UNIT * PATENT PENDING LISTED U 99Y9 RESET L RELEASING DEVICE SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE

More information

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016 Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting Prepared Especially for : OSFM TEC 2016 Acceptance Testing 11-2008 Agenda Before you begin Completing the

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. Minimum lighting control (base scope of work) shall include all corridors. The lighting in all the corridors shall be turned on (if not already on) if

More information

MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL

MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL RELEASE DEVICES MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: 7300-1418:100 GENERAL DESCRIPTION: S/N: These Time Delay Release Devices are U.L. Listed, Canadian Listed,

More information

THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL

THE SS90 SERIES RELEASE DEVICES MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL S S S S S S OLID TATE ECURITIES, INC S S 90 SOLID STATE FAIL-SAFE UNIT * PATENT PENDING LISTED 99Y9 RESET U L RELEASING DEVICE SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE

More information

TEC1100 Series Thermostats

TEC1100 Series Thermostats Metasys Network Sales Resource Manual 635 Application Specific Controllers Section Product Bulletin Issue Date 0601 TEC1100 Series Thermostats TEC1100 is a series of non-programmable thermostats with a

More information

TC-9102 Applications

TC-9102 Applications Application Note January 7, 2004 APPLICATION NOTE TC-9102 Applications Configuring TC-9102 Applications...3 Introduction... 3 Key Concepts... 4 TC-9102 Controller... 4 Control Modes...8 Procedure Overview...

More information

UNT Applications. Using UNT Applications...3. Introduction Key Concepts UNT Controller Applications Fan Coil Units...

UNT Applications. Using UNT Applications...3. Introduction Key Concepts UNT Controller Applications Fan Coil Units... Application Note Issue Date 04/17/08 Supersedes 01/11/01 APPLICATION NOTE Using...3 Introduction... 3 Key Concepts... 4 UNT Controller Applications... 4 Fan Coil Units... 8 Unit Ventilators... 11 Rooftop

More information

Johnson Controls Fan Coil Units and Direct Digital Controls

Johnson Controls Fan Coil Units and Direct Digital Controls Product Bulletin Issue Date August 12, 2005 Johnson Controls Fan Coil Units and Direct Digital Controls This offering includes Johnson Controls fan coil units with a factory-installed Johnson Controls

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Building Automation System (BAS) Design Criteria

Building Automation System (BAS) Design Criteria 25 0520 Building Automation System (BAS) Design Criteria 1. Design Statement a. During the various design phases of this project, the Engineer will develop options and strategies for selection of the appropriate

More information

P2000 and Metasys System Integration

P2000 and Metasys System Integration P2000 and Metasys System Integration Product Bulletin Code No. LIT-12012141 Software Release 3.14 SP1 Issued June 23, 2017 The Johnson Controls P2000 Security Management System supports the integration

More information

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes

More information

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2

More information

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL RELEASE DEVICES MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL The LiftMaster Fire Control (LM21-AFC) Release Device/Control Panel is UL/CUL listed normally energized fail-safe device incorporating

More information

PSN-1000 & PSN 1000(E) Installation Manual

PSN-1000 & PSN 1000(E) Installation Manual PSN-1000 & PSN 1000(E) Installation Manual Potter Electric Signal Company, LLC St. Louis, MO Customer Service: (866) 240-1870 Technical Support: (866) 956-1211 Fax: (314) 595-6999 www.pottersignal.com

More information

TEC210x-2 Series Networked Thermostats

TEC210x-2 Series Networked Thermostats Product Bulletin Issue Date February 1, 2005 TEC210x-2 Series Networked Thermostats The TEC210x-2 Series of thermostats is a family of highly advanced thermostats specifically designed for control of equipment

More information

PART 4 ELECTRICAL STANDARDS

PART 4 ELECTRICAL STANDARDS PART 4 ELECTRICAL STANDARDS 1.0 INTRODUCTION AND SCOPE: These standards reflect the general requirements and recommendations of elevator contractors, with respect to the power distribution system to achieve

More information

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. 2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is

More information

MANUAL RESET ALARM RELEASE BOX

MANUAL RESET ALARM RELEASE BOX MANUAL RESET ALARM RELEASE BOX (For 100~240VAC or 24VAC or 24VDC) INSTRUCTION MANUAL WARNING 1. CAUTION: Review all installation instructions, procedures, cautions and warnings contained within this manual

More information

OKLAHOMA STATE UNIVERSITY

OKLAHOMA STATE UNIVERSITY ENVIRONMENTAL HEALTH & SAFETY ADDRESSABLE FIRE ALARM SYSTEM STANDARD Revised 6/15 Revised: 6/15 Contact(s) Implementation Date Comments Gerald Petre, EHS June 2016 Review and Update Page 1 1.1 GENERAL

More information

RELEASE DEVICE CONTROLS

RELEASE DEVICE CONTROLS RELEASE DEVICE CONTROLS RELEASE DEVICE MODEL C+ INSTALLATION MANUAL UL LISTED CANADIAN LISTED CSFM: 7300-48:00 GENERAL DESCRIPTION: MADE IN THE U.S.A. S/N: The LM0-C+ Release Device/Control Panel is a

More information

TEC2100 Series Networked Thermostats

TEC2100 Series Networked Thermostats Product Bulletin Issue Date February 11, 2004 TEC2100 Series Networked Thermostats The TEC2100 Series of thermostats is a family of highly advanced thermostats specifically designed for control of equipment

More information

Digital Precise Air Control - DPAC

Digital Precise Air Control - DPAC Digital Precise Air Control - DPAC Mode Enable Sensor Options The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during Occupied operation. The following options

More information

ACCURATE ELECTRONICS INC

ACCURATE ELECTRONICS INC ACCURATE ELECTRONICS INC Page 1 of 7 Model 108078 2 Sept 09 WWW.ACCURATE.ORG PO BOX 1654 97075-1654 8687 SW Hall Blvd 97008 BEAVERTON OR USA 503.641.0118 FAX 503.646.3903 Practice Section 108078 Rev A

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved

More information

Functional Performance Test

Functional Performance Test Fire Alarm Control Panel & Fire Alarm Annunciator Panel Notify all building occupants that testing will be conducted. Fire alarm contractor shall have personnel with 2-way radios at the fire alarm control

More information

Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems

Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems Your Presenter: Merton Bunker, PE Inspections and tests are intended to reduce or limit: Loss of life

More information

TEC2620 Series Non-Programmable Fan Coil Network Thermostat Controller and Remote I/O Relay Packs

TEC2620 Series Non-Programmable Fan Coil Network Thermostat Controller and Remote I/O Relay Packs TEC2620 Series Non-Programmable Fan Coil Network Thermostat ler and Remote I/O Relay Packs TEC2620H-0, TEC2620C-0, TEC2620H-0+PIR, TEC2620C-0+PIR, TEC2621H-0, TEC2621C-0, TEC2621H-0+PIR, TEC2621C-0+PIR

More information

Multi-Zone Wireless Control Training Systems ( )

Multi-Zone Wireless Control Training Systems ( ) Multi-Zone Wireless Control Training Systems 593306 (3467-00) LabVolt Series Datasheet Festo Didactic en 120 V - 60 Hz 11/2018 Table of Contents General Description 2 Courseware 2 Topic Coverage 3 List

More information

Smoke Management Application Guide Rev. D

Smoke Management Application Guide Rev. D Smoke Management Application Guide 574-465 Rev. D Acknowledgements Acknowledgements Tyco Safety Products Westminster, gratefully acknowledges the contributions of the following organizations to this publication:

More information

CONTENTS AUTOMATIC TRANSFER SWITCHES

CONTENTS AUTOMATIC TRANSFER SWITCHES CONTENTS AUTOMATIC TRANSFER SWITCHES PART 1 GENERAL 1.1 Related Documents 1.2 Summary 1.3 References 1.4 Quality Assurance 1.5 Submittals 1.6 Delivery, Storage and Handling 1.7 Instructions And Training

More information

SECTION GENERATOR PARALLELING CONTROLS

SECTION GENERATOR PARALLELING CONTROLS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 23 13 GENERATOR PARALLELING CONTROLS SPEC WRITER NOTE: Delete between // -- // if not applicable to project. Also delete any other item or paragraph not applicable

More information

Soft Start Series MP700 Solid State, Reduced Voltage

Soft Start Series MP700 Solid State, Reduced Voltage Metron Fire Pump Controls and Accessories Soft Start Series MP700 Solid State, Reduced Voltage Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s

More information

University Design Standard Fire Alarm Systems

University Design Standard Fire Alarm Systems 1.0 Overview University Design Standard Fire Alarm Systems This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit

More information

TM-3100 Series Room Temperature Sensor

TM-3100 Series Room Temperature Sensor PB_TM-3100_12 2009 TM-3100 Series Room Temperature Sensor The Johnson Controls TM-3100 Series Room Temperature Sensor provide passive sensing of temperature in HVAC application. The TM-3100 is equipped

More information

ADDENDUM No: 3 JOSEPHINE COUNTY BUILDING OPERATIONS DEPARTMENT. February 29, NO CHANGE: March 8, 2012 / NOT LATER THAN 2:00 PM

ADDENDUM No: 3 JOSEPHINE COUNTY BUILDING OPERATIONS DEPARTMENT. February 29, NO CHANGE: March 8, 2012 / NOT LATER THAN 2:00 PM ADDENDUM No: 3 JOSEPHINE COUNTY BUILDING OPERATIONS DEPARTMENT February 29, 2012 RFP NO: 17 PROJECT: Josephine County Justice Center HVAC Upgrades BID CLOSING DATE: NO CHANGE: March 8, 2012 / NOT LATER

More information

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems 5/25/16 rev 6 elite Model ELN General Specification 550 W to 1.5 KW elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems 1.0 General General Specification This specification

More information

Surviving Survivability A User s Guide to Survivable Fire Alarm Circuits Larry D. Rietz, SET 23 May 2018

Surviving Survivability A User s Guide to Survivable Fire Alarm Circuits Larry D. Rietz, SET 23 May 2018 Surviving Survivability A User s Guide to Survivable Fire Alarm Circuits Larry D. Rietz, SET 23 May 2018 Automatic FireAlarm Association SURVIVING SURVIVABILITY - A USER S GUIDE TO Larry D. Rietz, SET

More information

SECTION : FIRE ALARM & DETECTION SYSTEMS

SECTION : FIRE ALARM & DETECTION SYSTEMS SECTION 28 31 10: FIRE ALARM & DETECTION SYSTEMS 1. GENERAL A. This section applies to fire detection/alarm system and carbon monoxide system components and equipment installed during new construction

More information

ACT2-CS Convenience Store Controller

ACT2-CS Convenience Store Controller Refrigeration Systems Technical Manual 804 Product Bulletins Section Product Bulletin Issue Date 0899 ACT2-CS Convenience Store Controller The ACT2-CS Convenience Store Controller is a fully programmable,

More information

Fire Protection Coffee Break Training May 2016

Fire Protection Coffee Break Training May 2016 Fire Protection Coffee Break Training May 2016 Introduction High-Rise Requirements Questions and Answers Agenda Overview Site Fire Access Aerial Access Power/Back-up Power Elevators and Access Sprinklers

More information

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES Part One General 1.01 Scope A. It is the intent of this specification to provide a medium voltage automatic transfer system. B. All components, testing and services specified and required for a complete

More information

Full Service Central Station Fire Alarm Listing Evaluation

Full Service Central Station Fire Alarm Listing Evaluation Full Service Central Station Fire Alarm Listing Evaluation Listing Evaluation A UL Listing project includes: 1. Evaluating the central station facility for compliance with UL 827, Central-Station Alarm

More information

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Fire Alarm Systems Plan Review Checklist Date: Permit Number: Business Name: Address: Fire Alarm System Submittal

More information

TEC3000 Series Wireless, Stand-Alone, and Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers Catalog Page

TEC3000 Series Wireless, Stand-Alone, and Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers Catalog Page Code. LIT-1900896 Issued February 17, 2017 TEC3000 Series Wireless, Stand-Alone, and Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers Catalog Page Description The TEC3000 Series Thermostat

More information

DESIGN GUIDELINE SBA 5.11

DESIGN GUIDELINE SBA 5.11 GeneralScope DESIGN GUIDELINE SBA 5.11 FIRE COMMAND CENTER This design guideline clarifies how certain Michigan Building Code (MBC) requirements for Fire Command Centers are to be applied on University

More information

Annunciators, 8 LED. D7030X, D7030X-S2, and D7030X-S8. Installation Manual

Annunciators, 8 LED. D7030X, D7030X-S2, and D7030X-S8. Installation Manual Annunciators, 8 LED D7030X, D7030X-S2, and D7030X-S8 en Installation Manual Annunciators, 8 LED Notices en 3 1 Notices These instructions cover the installation of the D703X, D7030X-S2, and D7030X-S8

More information

Installation and Operation. Tracer ZN521 Zone Controller CNT-SVX07C-EN

Installation and Operation. Tracer ZN521 Zone Controller CNT-SVX07C-EN Installation and Operation Tracer ZN521 Zone Controller CNT-SVX07C-EN Installation and Operation Tracer ZN521 Zone Controller CNT-SVX07C-EN April 2005 CNT-SVX07C-EN Tracer ZN521 Zone Controller Installation

More information

Environmental Health & Safety

Environmental Health & Safety Environmental Health & Safety Oklahoma State University ADDRESSABLE FIRE ALARM SYSTEM STANDARD Environmental Health and Safety University Health Services Suite 002 Stillwater, OK 74078 (405) 744-7241 www.ehs.okstate.edu

More information

Idaho Surveying & Rating Bureau, Inc South Cobalt Point Way Tel: (208) Meridian, Idaho FAX: (208)

Idaho Surveying & Rating Bureau, Inc South Cobalt Point Way Tel: (208) Meridian, Idaho FAX: (208) Idaho Surveying & Rating Bureau, Inc. 1871 South Cobalt Point Way Tel: (208) 343-5483 Meridian, Idaho 83642 FAX: (208) 895-8059 www.isrb.com e-mail info@isrb.com Joseph C. Harbacheck, CIC Secretary - General

More information

SLATE. Base Module INSTALLATION INSTRUCTIONS R8001A1001

SLATE. Base Module INSTALLATION INSTRUCTIONS R8001A1001 SLATE Base Module R8001A1001 INSTALLATION INSTRUCTIONS Scan for more information Application SLATE brings configurable safety and programmable logic together into one single platform. The platform can

More information

FCC Fan-Coil Units High-Performance, Vertical

FCC Fan-Coil Units High-Performance, Vertical FCC Fan-Coil s High-Performance, Vertical Model FCC construction features Piping and supply-duct connections are from top of unit, eliminating the need for side or back access Right or left-hand configurations

More information

Model 17A00 Expansion Enclosure

Model 17A00 Expansion Enclosure HOME AUTOMATION, INC. Model 17A00 Expansion Enclosure Installation Manual Document Number 17I00-1 Rev A March, 2002 Home Automation, Inc. Model 17A00 Expansion Enclosure Installation Manual Document Number

More information

Across-the-Line SERIES MP300 Combined Manual and Automatic

Across-the-Line SERIES MP300 Combined Manual and Automatic Across-the-Line SERIES MP300 Combined Manual and Automatic Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s Standard for Centrifugal Fire Pumps

More information

"SS90" SERIES CONTROLS MODEL C INSTALLATION MANUAL

SS90 SERIES CONTROLS MODEL C INSTALLATION MANUAL S S S SS O L I D S S90 TATE ECURITIES, INC SOLID STATE FAIL-SAFE UNIT * PATENT PENDING LISTED U L 99Y9 RESET RELEASING DEVICE SOLID STATE SECURITIES, INC. "SS90" SERIES CONTROLS MADE IN THE U.S.A. MODEL

More information

AIRPORT OFFICE BUILDING. Smoke Control System. Testing Procedures Manual. September 10, 2016

AIRPORT OFFICE BUILDING. Smoke Control System. Testing Procedures Manual. September 10, 2016 IMPACT ENGINEERING, INC. AIRPORT OFFICE BUILDING Smoke Control System Testing Procedures Manual September 10, 2016 All Rights Reserved This manual is protected by the U.S. Copyright Law (Title 17 United

More information

Fire System Objects. Introduction Page *3. Engineering *17. Data Base Generation *43

Fire System Objects. Introduction Page *3. Engineering *17. Data Base Generation *43 Metasys etwork Technical Manual 636 Objects Section Technical Bulletin Issue Date 696 Fire System Objects Introduction Page *3 Description *3 Purpose *5 Capabilities *7 Functional Diagram *1 Operator Interface

More information

16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5

16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5 Construction Standards Page 1 of 5.1 General Description.1 The University requires that all new fire alarm system control panel, components, and devices, as required for the project, be Secutron 2900 Series

More information

LifeAlarm Fire Alarm Controls

LifeAlarm Fire Alarm Controls UL, ULC Approved* LifeAlarm Fire Alarm Controls 4009 IDNet NAC Extender for Control with IDNet Communications or Conventional NACs Features Provides additional notification appliance circuit (NAC) capacity

More information

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option Installation PS6 SERIES Power Supplies PS6 SERIES Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option Installation and Specifications Manual ISDPS6_SERIES 08121590 PCN15016 R05/15GR

More information

LC150 VIEW-AT-A-GLANCE PUMP CONTROL-TELEMETRY UNIT

LC150 VIEW-AT-A-GLANCE PUMP CONTROL-TELEMETRY UNIT LC150 VIEW-AT-A-GLANCE PUMP CONTROL-TELEMETRY UNIT Simply Features In Brief Telemetry Ready Security 2 or 3 Pump Control UL Listed Alarm/Event Log Volumetric Flow Calculator VFD Control Optional Dialer

More information