Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance
|
|
- Roberta Fields
- 6 years ago
- Views:
Transcription
1 Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance Checklist Code No. LIT Release 1.2 Issued February 10, 2005 Document Introduction Related Documentation Smoke Control UL 864 UUKL Compliance Checklist Overview UL 864 UUKL Smoke Control Compliance Survey General UUKL Requirements Fire Fighter s Smoke Control Station (FSCS) UUKL FSCS UUKL Requirements DX-9100 Applications UUKL Requirements Smoke Control Wiring UUKL Requirements Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance Checklist 1
2 2 Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance Checklist
3 Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance Checklist Document Introduction This document summarizes the most common requirements to configure the Metasys system extended architecture to comply with Underwriters Laboratories, Inc. (UL), UL 864 UUKL Smoke Control Listing. A UL 864 UUKL Smoke Control Compliance Survey form is followed by tables listing the requirements for UL 864 UUKL Listing compliance. The purpose of the enclosed UL 864 UUKL Smoke Control Compliance Survey is to provide a record of those elements of National Fire Protection Association (NFPA) 92A and UUKL that Johnson Controls, Inc. does or does not provide. Related Documentation If you are bidding, engineering, installing, or commissioning a Metasys system extended architecture requiring UUKL Smoke Control Listing compliance, follow the guidelines and procedures outlined in the documents listed in Table 1. Table 1: Related Documentation For Information On Refer to LIT No./Part No. Smoke Control Guidelines and Procedures Smoke Control Wiring Network Automation Engine (NAE) Installation Smoke Control Applications Metasys System Extended Architecture Smoke Control System Technical Bulletin Metasys System Extended Architecture Smoke Control Wiring Technical Bulletin LIT LIT NAE55/NIE Installation Instructions Part No Single Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System Extended Architecture Application Note Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture Application Note Warehouse Smoke Control with FSCS Override -Metasys System Extended Architecture Application Note Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture Application Note Weekly Testing of Dedicated Stairwell Pressurization Fans - Metasys System Extended Architecture Application Note LIT LIT LIT LIT LIT Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance Checklist 3
4 Smoke Control UL 864 UUKL Compliance Checklist Overview UUKL is an identifier created by UL to identify those products Listed under UL 864 as part of a Smoke Control system. Products covered by this listing are intended to be installed in conjunction with Heating, Ventilating, and Air Conditioning (HVAC) equipment to form a system for controlling the flow of smoke in a building during a fire condition in accordance with NFPA Recommended Practice 92A. It is important that we document the system elements that are being provided. The UL 864 UUKL Smoke Control Compliance Survey can be used to provide that documentation. In the case where a project specification dictates compliance with the UUKL Listing, but contains elements of the system design that conflict with the Listing or are omitted, the completed UL 864 UUKL Smoke Control Compliance Survey can be given to the designer and/or the AHJ to obtain recognition and agreement on the extent of Listing compliance. This should occur prior to bid and/or proposal. Once agreement is reached with the AHJ, designer, and customer, the signed or initialed Smoke Control Compliance Checklist must become a permanent part of the project file. Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance Checklist 4
5 UL 864 UUKL Smoke Control Compliance Survey Date of Survey Conducted By Project Location Branch Office Project Manager Specifications UL Compliance Required By: Building Codes Contract Applicable Building Codes and Standards Local (Branch) Person Providing and Verifying Information Initials Name Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance Checklist 5
6 General UUKL Requirements Table 2 lists general requirements for UL 864 UUKL Listing compliance. Mark Yes/No for compliance and initial each item that was verified. Table 2: General UUKL Requirements Requirement Communication links between buildings are fiber-optic cable or copper cable buried in a conduit separate from power wiring. Each binary output object used for pressurization and exhaust control is configured with positive feedback. The feedback input monitors the associated controlled equipment status (for example, both open and closed, on and off). For smoke control dampers, there may be a pair of feedback binary inputs for two damper end switches. Any mismatch of a command and status of the binary output occurring longer than the allowed response time must create a trouble light indication at the FSCS. For fans there is positive indication of airflow. Non UL-Listed control equipment must be isolated from the UL-Listed network. The Weekly Testing of Dedicated Stairwell Pressurization Fans application is used on all dedicated smoke control systems. Automatic smoke control sequences take precedence over HVAC automatic and manual commands. Manual FSCS takes precedence over all else. Automatic activation of any smoke control sequence of operation has priority over any non-smoke control manual commands and any automatic environmental control strategy, when an auto smoke control sequence is initiated. High and low temperature protection devices and return and exhaust air-duct smoke detectors are bypassed. Response time for individual smoke control fans to reach commanded state is no more than 60 seconds. Response time for individual smoke control dampers to reach commanded state is no more than 75 seconds. Fire alarm system manual pull stations do not initiate automatic smoke control sequences. Smoke detectors are used to initiate a smoke control strategy only as detailed in the Metasys System Extended Architecture Smoke Control System Technical Bulletin (LIT ). All Application Specific Controls (ASCs) that monitor or control smoke control equipment are UUKL Listed. Electrical disconnects, overloads, duct static pressure limits, and supply air duct smoke detectors are not overridden by manual or automatic smoke control strategies. Y/N NA Person Verifying Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance Checklist 6
7 Fire Fighter s Smoke Control Station (FSCS) UUKL FSCS UUKL Requirements Table 3 lists general requirements for UL 864 UUKL Listing compliance for FSCSs where required. Mark Yes/No for compliance and initial each item that was verified. Table 3: FSCS UUKL Requirements Requirement FSCS is UUKL Listed and provides manual control of the smoke control system, a UUKL Listed annunciator panel is used as FSCS. Custom annunciator FSCS is connected to a UUKL Listed Smoke Control NAE55. FSCS provides positive indication of the operation of all smoke control equipment (for example, both open and closed, on and off). FSCS provides audible and visible trouble indication when any smoke control equipment does not respond to automatic or manual commands. FSCS simultaneously displays the status of all smoke control systems dampers, fans FSCS has manual control over all smoke control systems. FSCS can override (partially or in full) any operation in progress, including programmed actions, non-smoke control manual overrides. FSCS has highest priority over all smoke control systems. A building diagram or equivalent at FSCS clearly indicates the type and location of all smoke control equipment. FSCS indicates the actual status (not the command status) of systems and equipment used for smoke control. This includes the current position of each damper used in an active smoke control sequence and the status of airflow status of every fan. FSCS activates an audible signal if the operation proof sensor (binary feedback point) failed to provide positive feedback that fan or damper reached its intended position. Only one FSCS on Metasys system is used for smoke control applications unless approved by the AHJ. The FSCS manual activation or deactivation of any smoke control device has priority over any automatic smoke or environmental sequence of operation. Any return air duct smoke detectors in duct work of each HVAC fan system used for smoke control exhaust or purge only reports an alarm condition to the FSCS or fire alarm annunciator located at the FSCS and does not stop the fan. All hardware supervision alarms, such as binary feedback alarms on fans and dampers, as well as system alarm points turn on FSCS alarm horn. Annunciation on the FSCS of change of state of smoke control equipment is no more than 10 seconds after reaching commanded state. Y/N NA Person Verifying Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance Checklist 7
8 DX-9100 Applications UUKL Requirements Table 4 lists general requirements for UL 864 UUKL Listing compliance for DX-9100 hardware with fire alarm panel applications. Mark Yes/No for compliance and initial each item that was verified. Table 4: DX-9100 Applications UUKL Requirements Requirement If the Digital Inputs (DIs) are used for smoke control, the fuse on the DI circuit of that DX-9100 is monitored by a jumper wire across a DI, mapped to the NAE/NIE/Site Director. If the fuse goes into trouble then the alarm is activated in the NAE and a trouble light for the affected equipment energizes at the FSCS. If Analog Outputs (AOs) are used for smoke control, the fuse on the AO circuit of that DX-9100 is monitored by doing the following. They are fused and the fuse is monitored. To do this, set one AO for voltage and define an Analog Input (AI) for voltage. Connect a Control Output (CO) set for 50.0 to the AO that is ranged for This gives the AO a 50 percent signal or a 5 volt output. This output is hardwired back to the AI defined for voltage with a range of and a low limit of 20. If the AO fuse blows, the voltage will go to 0 and the AI will go into low alarm. This alarm must be monitored as a critical alarm. Each DX-9100 used for smoke control has a Metasys system poll priority of 1 or 2. All fans controlled by the DX-9100 have an airflow status switch. Any mismatch of command and status of the fans reports a critical alarm at FSCS. An IFC-640/1010/2020/3030 is connected to the Metasys system via the BACnet Gateway to initiate automatic smoke control actions. If the fire alarm control panel alarms are not displayed on an annunciator at the FSCS, all alarm input DIs are monitored and report critical alarms at the NAE when they close (turn On), such as a fire alarm control panel smoke detector alarm point. Locate the annunciator panel at the FSCS to enable the operator to monitor all alarms in the fire alarm system. The buttons on the face of the DX-9100 are not used to override smoke control points. Any DX-9100 for smoke control is locked in a Listed enclosure, such as the EN-EWC25-0 to prevent unauthorized access. All alarm input DIs are monitored and report critical alarms at the NAE/NIE/Site Director when they close (turn On). Any signal circuits connected to the XP9102 do not leave the room in which the XP9102 is mounted unless transient protection is applied as detailed in the Metasys System Extended Architecture Smoke Control Wiring Technical Bulletin (LIT ). If signal circuits leaves the room, transient protection is applied as detailed in the Metasys System Extended Architecture Smoke Control Wiring Technical Bulletin (LIT ). Y/N NA Person Verifying Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance Checklist 8
9 Smoke Control Wiring UUKL Requirements Table 5 lists requirements for UL 864 UUKL Listing compliance for Smoke Control Wiring. Mark Yes/No for compliance and initial each item verified. Table 5: Smoke Control Wiring UUKL Requirements Requirement Communication links between buildings are fiber-optic cable or copper cable buried in a conduit separate from power wiring. If N1 or N2 signal circuits leave the room, transient protection is applied as detailed in the Metasys System Extended Architecture Smoke Control Wiring Technical Bulletin (LIT ). When using DX-9100 product line for smoke control, the DX F base must be used. If the XP-9102 is used and the signal circuit leaves the room in which the XP-9102 is installed, the protection is shown in the Metasys System Extended Architecture Smoke Control Wiring Technical Bulletin (LIT ). The Metal Oxide Varistor (MOV) must be a Johnson Controls Code No. SMOKE-MOVEKIT-0. The transzorbs in the Metasys System Extended Architecture Smoke Control Wiring Technical Bulletin (LIT ) are installed on the base frame products. Only terminals in use and signal circuits leaving a room where a controller is installed have transient protection. The transzorb must be a Johnson Controls Code No. SMOKE-TRNKIT-0. MOVs are installed on the AHU, UNT, and VAV products as shown in the Metasys System Extended Architecture Smoke Control Wiring Technical Bulletin (LIT ). Only terminals in use, and I/O wiring leaving a room where a controller is installed, or wire more than 20 feet in length have transient protection. The MOV is a Johnson Controls Code No. SMOKE-MOVKIT-0. For faston versions use Johnson Controls Code No. AS-MOVKIT-0 Verify that a Tripp Lite ISOBAR8ULTRA surge protector or a Tripp Lite ISOBAR12ULTRA surge protector protects all 120 VAC power sources. If fiber-optic cable is used, verify that it meets the requirements listed in the Metasys System Extended Architecture Smoke Control System Wiring Technical Bulletin (LIT ) If copper cable is used, verify that it meets the requirements listed in the Metasys System Extended Architecture Smoke Control System Wiring Technical Bulletin (LIT ). Verify that copper cable connected to media converters does not leave the room in which the media converter is installed. Verify that all RJ45 cables are protected from electrical surges through the use of the American Power Conversion (APC) Protect Net (Model PNET1) surge protector at each end of the RJ45 cable. Verify that only the Smoke Control NAE, MS-NAE5510-0U, is used for smoke control in a UUKL smoke control system. If an RS-485-to-RS485 repeater is used to isolate UUKL from non-uukl devices on an N2 Bus, verify that it is installed in a UL-Listed enclosure. Verify that the power-limited and non-power limited wiring from the repeater is seperated. Refer to the Metasys System Extended Architecture Smoke Control System Wiring Technical Bulletin (LIT ). The transzorb must be a Johnson Controls Code No. SMOKE-TRNKIT-1. Y/N NA Person Verifying Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance Checklist 9
10 Controls Group 507 E. Michigan Street Milwaukee, WI Metasys is a registered trademark of Johnson Controls, Inc. All other marks herein are the marks of their respective owners Johnson Controls, Inc. 10 Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance Checklist Published in U.S.A.
Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT
Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT-1201739 Release 1.2 Issued Date July 30, 2004 Supersedes Document Introduction.................................................
More informationWeekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture
Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture Code No. LIT-1201743 Release 1.2 Issued Date July 30, 2004 Supersedes Document Introduction.................................................
More informationMetasys System Extended Architecture Smoke Control System
Metasys System Extended Architecture Smoke Control System Technical Bulletin MS-NAE5510-0U Code No. LIT-1201684 Release 1.2 Issued February 10, 2005 Document Introduction.................................................
More informationSingle Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System Extended Architecture
Single Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System Extended Architecture Application Note Code No. LIT-1201736 Release 1.2 Issued January 10, 2005 Document Introduction.................................................
More informationMulti-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture
Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture Code No. LIT-1201737 Release 1.2 Issued January 10, 2005 Document Introduction.................................................
More informationDX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans
Metasys Network Technical Manual 636 DX-9100/9120 Applications Section Application Note Issue Date 0497 APPLICATION NOTE DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans Introduction
More informationDX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit
Metasys Network Technical Manual 636 DX-9100/9120 Applications Section Application Note Issue Date 0497 APPLICATION NOTE DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit Introduction
More informationYork 25-Ton VAV Rooftop Unit
HVAC PRO for Windows User s Manual 637.5 OEM Section Technical Bulletin Issue Date 0996 York 25-Ton VAV Rooftop Unit Introduction Page 3 Overview *3 Configuration 5 Sequence of Operation 7 Modes of Operation
More informationSECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL
SECTION 15910 SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division
More informationSolution Guide. UUKL Smoke Control System. 1/6. UL 864, 9th Edition, UUKL Smoke Control Listing. Overview
Solution Guide UL 864, 9th Edition, UUKL Smoke Control Listing Overview Applications Distech Controls UUKL smoke control system can be used for: Dedicated smoke control applications: Used exclusively for
More informationSECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS
PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section
More informationMetasys System Extended Architecture Fire System Integration Using the IFC BACnet Gateway
Metasys System Extended Architecture Fire System Integration Using the IFC BACnet Gateway Code No. LIT-1201993 Software Release 2.1 Issued April 12, 2006 Supersedes July 20, 2005 Document Introduction.................................................
More informationSmoke Control Manual
Smoke Control Manual For BACnet Systems ON BAC-5800 Controller OFF ON BAC-5800 Controller Pressurized Third Floor Stairwell Fan ON OFF BAC-5800 Controller Exhausted Second Floor OFF BAC-5800 Controller
More informationWHITE PLAINS SMOKE CONTROL CODE PART 1. GENERAL REQUIREMENTS
WHITE PLAINS SMOKE CONTROL CODE a. Application of Code. PART 1. GENERAL REQUIREMENTS The following uniform standards and procedures shall apply to the design, installation and testing of new smoke purge
More informationDX-9100/9120 Local Sonalert Logic
Metasys Network Technical Manual 636 DX-9100/9120 Applications Section Application Note Issue Date 0497 APPICATION NOTE DX-9100/9120 ocal Sonalert ogic Introduction Page 3 Application Description *3 Design
More informationFire Operator Workstation (Fire OWS) User s Guide
Fire Operator Workstation (Fire OWS) User s Guide 1-1 Fire Operator Workstation (Fire OWS) User s Guide Introduction This user s guide details the components, capabilities, and operation procedures of
More informationDX-9100 Applications from Engineering Services
System 9100 Technical Manual 636.4 Application Examples Section Technical Bulletin Issue Date 0896 DX-9100 Applications from Engineering Services Introduction Page 3 Overview 3 Air Handling Unit Applications
More informationMetasys Integrator Compu-Aire Application
Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0496 APPLICATION NOTE Metasys Integrator Compu-Aire Application lntroduction Page 3 Application Details
More informationMetasys Integrator TITUS Application
Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date October 12, 2005 APPLICATION NOTE Metasys Integrator TITUS Application lntroduction Page 3 Application
More informationONYX FirstVision Specification Interactive Firefighters Display
ONYX FirstVision Specification Interactive Firefighters Display NOTIFIER is a registered trademark, and ONYX FirstVision, NOTI FIRE NET, and VeriFire are trademarks of Honeywell International Inc. Microsoft
More informationMulti-Story Building Floor Above/Floor Below Pressurization and Exhaust Logic
Metasys Network Technical Manual 636 GPL Applications Section Application Note ssue Date 0497 APPLCATN NT Multi-Story Building Floor Above/Floor Below Pressurization and xhaust Logic ntroduction Page 3
More informationP2000 and Metasys System Integration
P2000 and Metasys System Integration Product Bulletin Code No. LIT-12011781 Software Release 3.12 Issued June 20, 2013 Supersedes April 20, 2012 Refer to the QuickLIT Web site for the most up-to-date version
More informationFIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL
FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL MADE IN THE U.S.A. U.L. LISTED CANADIAN LISTED CSFM: 7300-1418:100 GENERAL DESCRIPTION SERIAL NUMBER The Cookson Company FIREFLY II PLUS Time Delay Release
More informationA. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.
SECTION 23 09 93 - SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1 WORK INCLUDES A. Base Bid: Heating Contractor provide: Control sequences for HVAC systems, subsystems, and equipment. B. Alternate
More informationRELEASE DEVICES RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: :100 GENERAL DESCRIPTION:
RELEASE DEVICES MADE IN THE U.S.A. RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: 7300-1418:100 GENERAL DESCRIPTION: S/N: The "WPS" World Power Series, Time Delay Release
More informationFirefly II Multi Voltage RELEASE DEVICES. Firefly II & IIB-MV INSTALLATION MANUAL
Firefly II Multi Voltage RELEASE DEVICES Firefly II & IIB-MV INSTALLATION MANUAL GENERAL DESCRIPTION: S/N The The Cookson Company Firefly II-MV time delay release devices are designed for use on rolling
More informationMetasys Integrator Cleaver-Brooks Application
Metasys Connectivity Technical Manual 69. Metasys Integrator Section Application Note Issue Date 0900 APPLICATION NOTE Metasys Integrator Cleaver-Brooks Application lntroduction Page Application Details
More informationTrueAlarm Analog Sensing
TrueAlarm Analog Sensing UL, ULC Listed* Addressable Duct Sensor Housings with TrueAlarm Photoelectric Sensor; Available with Multiple Relay Features Compact air duct sensor housing with clear cover to
More informationCOUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III
SECTION 28 3111 - DIGITAL ADDRESSABLE FIRE ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationSECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS
SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section
More informationMetasys Integrator Airflow Application
Metasys Connectivity Technical Manual 69. Metasys Integrator Section Application Note Issue Date 0998 APPLICATION NOTE Metasys Integrator Airflow Application lntroduction Page Application Details * Component
More informationMODEL B2 INSTALLATION MANUAL
RELEASE DEVICES GENERAL DESCRIPTION MODEL B2 INSTALLATION MANUAL S/N: The B2 Series Time Delay Release Devices are UL Listed, Canadian Listed, and CSFM Listed for use on rolling doors, single-slide and
More informationReciprocating Chiller
HVAC PRO for Windows User s Manual 637.5 OEM Section Technical Bulletin Issue Date 1094 Reciprocating Chiller Reciprocating Chiller Page 3 Description 3 Theory of Operation 5 Overview 5 Control Sequence
More informationJCI - Smoke Control Systems Overview 10/27/2016
If the you can read this Click on the icon to choose a picture or To Reset: Right click on the slide thumbnail and select reset slide or choose the Reset button on the Home ribbon (next to the font choice
More informationSOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. SS90-WPS MODEL A/B INSTALLATION MANUAL
S S S S S S LISTED L * PATENT PENDING S S 90 OLID TATE ECURITIES, INC SOLID STATE FAIL-SAFE UNIT U 99Y9 RESET RELEASING DEVICE SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE
More informationDIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM
DIVISION 26 ELECTRICAL SECTION 26 81 11 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install all equipment and accessories for a complete local, analog addressable, manually and automatically actuated,
More informationGCS Multipoint Carbon Dioxide Gas Concentration Sampler
Electronic Control Manual 16 Sensors and Stats Section S Technical Bulletin Issue Date 0101 GCS-000- Multipoint Carbon Dioxide Gas Concentration Sampler Product Overview Page *3 Installation 5 Mounting
More informationWarehouse Smoke Exhaust and Reset Logic for a Rooftop Unit
Metasys Network Technical Manual 636 GPL Applications Section Application Note ssue Date 0497 APPLATN NTE Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit ntroduction Page 3 Application Description
More informationTHE "SS90" SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL
S S S S S S S S 90 OLID TATE ECURITIES, INC SOLID STATE FAIL-SAFE UNIT * PATENT PENDING LISTED U 99Y9 RESET L RELEASING DEVICE SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE
More informationFire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016
Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting Prepared Especially for : OSFM TEC 2016 Acceptance Testing 11-2008 Agenda Before you begin Completing the
More informationDENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL
PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. Minimum lighting control (base scope of work) shall include all corridors. The lighting in all the corridors shall be turned on (if not already on) if
More informationMADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL
RELEASE DEVICES MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: 7300-1418:100 GENERAL DESCRIPTION: S/N: These Time Delay Release Devices are U.L. Listed, Canadian Listed,
More informationTHE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL
S S S S S S OLID TATE ECURITIES, INC S S 90 SOLID STATE FAIL-SAFE UNIT * PATENT PENDING LISTED 99Y9 RESET U L RELEASING DEVICE SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE
More informationTEC1100 Series Thermostats
Metasys Network Sales Resource Manual 635 Application Specific Controllers Section Product Bulletin Issue Date 0601 TEC1100 Series Thermostats TEC1100 is a series of non-programmable thermostats with a
More informationTC-9102 Applications
Application Note January 7, 2004 APPLICATION NOTE TC-9102 Applications Configuring TC-9102 Applications...3 Introduction... 3 Key Concepts... 4 TC-9102 Controller... 4 Control Modes...8 Procedure Overview...
More informationUNT Applications. Using UNT Applications...3. Introduction Key Concepts UNT Controller Applications Fan Coil Units...
Application Note Issue Date 04/17/08 Supersedes 01/11/01 APPLICATION NOTE Using...3 Introduction... 3 Key Concepts... 4 UNT Controller Applications... 4 Fan Coil Units... 8 Unit Ventilators... 11 Rooftop
More informationJohnson Controls Fan Coil Units and Direct Digital Controls
Product Bulletin Issue Date August 12, 2005 Johnson Controls Fan Coil Units and Direct Digital Controls This offering includes Johnson Controls fan coil units with a factory-installed Johnson Controls
More informationSECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM
SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationBuilding Automation System (BAS) Design Criteria
25 0520 Building Automation System (BAS) Design Criteria 1. Design Statement a. During the various design phases of this project, the Engineer will develop options and strategies for selection of the appropriate
More informationP2000 and Metasys System Integration
P2000 and Metasys System Integration Product Bulletin Code No. LIT-12012141 Software Release 3.14 SP1 Issued June 23, 2017 The Johnson Controls P2000 Security Management System supports the integration
More informationUltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW
12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes
More informationTABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2
Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2
More informationMADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL
RELEASE DEVICES MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL The LiftMaster Fire Control (LM21-AFC) Release Device/Control Panel is UL/CUL listed normally energized fail-safe device incorporating
More informationPSN-1000 & PSN 1000(E) Installation Manual
PSN-1000 & PSN 1000(E) Installation Manual Potter Electric Signal Company, LLC St. Louis, MO Customer Service: (866) 240-1870 Technical Support: (866) 956-1211 Fax: (314) 595-6999 www.pottersignal.com
More informationTEC210x-2 Series Networked Thermostats
Product Bulletin Issue Date February 1, 2005 TEC210x-2 Series Networked Thermostats The TEC210x-2 Series of thermostats is a family of highly advanced thermostats specifically designed for control of equipment
More informationPART 4 ELECTRICAL STANDARDS
PART 4 ELECTRICAL STANDARDS 1.0 INTRODUCTION AND SCOPE: These standards reflect the general requirements and recommendations of elevator contractors, with respect to the power distribution system to achieve
More information2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.
2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is
More informationMANUAL RESET ALARM RELEASE BOX
MANUAL RESET ALARM RELEASE BOX (For 100~240VAC or 24VAC or 24VDC) INSTRUCTION MANUAL WARNING 1. CAUTION: Review all installation instructions, procedures, cautions and warnings contained within this manual
More informationOKLAHOMA STATE UNIVERSITY
ENVIRONMENTAL HEALTH & SAFETY ADDRESSABLE FIRE ALARM SYSTEM STANDARD Revised 6/15 Revised: 6/15 Contact(s) Implementation Date Comments Gerald Petre, EHS June 2016 Review and Update Page 1 1.1 GENERAL
More informationRELEASE DEVICE CONTROLS
RELEASE DEVICE CONTROLS RELEASE DEVICE MODEL C+ INSTALLATION MANUAL UL LISTED CANADIAN LISTED CSFM: 7300-48:00 GENERAL DESCRIPTION: MADE IN THE U.S.A. S/N: The LM0-C+ Release Device/Control Panel is a
More informationTEC2100 Series Networked Thermostats
Product Bulletin Issue Date February 11, 2004 TEC2100 Series Networked Thermostats The TEC2100 Series of thermostats is a family of highly advanced thermostats specifically designed for control of equipment
More informationDigital Precise Air Control - DPAC
Digital Precise Air Control - DPAC Mode Enable Sensor Options The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during Occupied operation. The following options
More informationACCURATE ELECTRONICS INC
ACCURATE ELECTRONICS INC Page 1 of 7 Model 108078 2 Sept 09 WWW.ACCURATE.ORG PO BOX 1654 97075-1654 8687 SW Hall Blvd 97008 BEAVERTON OR USA 503.641.0118 FAX 503.646.3903 Practice Section 108078 Rev A
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved
More informationFunctional Performance Test
Fire Alarm Control Panel & Fire Alarm Annunciator Panel Notify all building occupants that testing will be conducted. Fire alarm contractor shall have personnel with 2-way radios at the fire alarm control
More informationAutomatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems
Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems Your Presenter: Merton Bunker, PE Inspections and tests are intended to reduce or limit: Loss of life
More informationTEC2620 Series Non-Programmable Fan Coil Network Thermostat Controller and Remote I/O Relay Packs
TEC2620 Series Non-Programmable Fan Coil Network Thermostat ler and Remote I/O Relay Packs TEC2620H-0, TEC2620C-0, TEC2620H-0+PIR, TEC2620C-0+PIR, TEC2621H-0, TEC2621C-0, TEC2621H-0+PIR, TEC2621C-0+PIR
More informationMulti-Zone Wireless Control Training Systems ( )
Multi-Zone Wireless Control Training Systems 593306 (3467-00) LabVolt Series Datasheet Festo Didactic en 120 V - 60 Hz 11/2018 Table of Contents General Description 2 Courseware 2 Topic Coverage 3 List
More informationSmoke Management Application Guide Rev. D
Smoke Management Application Guide 574-465 Rev. D Acknowledgements Acknowledgements Tyco Safety Products Westminster, gratefully acknowledges the contributions of the following organizations to this publication:
More informationCONTENTS AUTOMATIC TRANSFER SWITCHES
CONTENTS AUTOMATIC TRANSFER SWITCHES PART 1 GENERAL 1.1 Related Documents 1.2 Summary 1.3 References 1.4 Quality Assurance 1.5 Submittals 1.6 Delivery, Storage and Handling 1.7 Instructions And Training
More informationSECTION GENERATOR PARALLELING CONTROLS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 23 13 GENERATOR PARALLELING CONTROLS SPEC WRITER NOTE: Delete between // -- // if not applicable to project. Also delete any other item or paragraph not applicable
More informationSoft Start Series MP700 Solid State, Reduced Voltage
Metron Fire Pump Controls and Accessories Soft Start Series MP700 Solid State, Reduced Voltage Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s
More informationUniversity Design Standard Fire Alarm Systems
1.0 Overview University Design Standard Fire Alarm Systems This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit
More informationTM-3100 Series Room Temperature Sensor
PB_TM-3100_12 2009 TM-3100 Series Room Temperature Sensor The Johnson Controls TM-3100 Series Room Temperature Sensor provide passive sensing of temperature in HVAC application. The TM-3100 is equipped
More informationADDENDUM No: 3 JOSEPHINE COUNTY BUILDING OPERATIONS DEPARTMENT. February 29, NO CHANGE: March 8, 2012 / NOT LATER THAN 2:00 PM
ADDENDUM No: 3 JOSEPHINE COUNTY BUILDING OPERATIONS DEPARTMENT February 29, 2012 RFP NO: 17 PROJECT: Josephine County Justice Center HVAC Upgrades BID CLOSING DATE: NO CHANGE: March 8, 2012 / NOT LATER
More informationelite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems
5/25/16 rev 6 elite Model ELN General Specification 550 W to 1.5 KW elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems 1.0 General General Specification This specification
More informationSurviving Survivability A User s Guide to Survivable Fire Alarm Circuits Larry D. Rietz, SET 23 May 2018
Surviving Survivability A User s Guide to Survivable Fire Alarm Circuits Larry D. Rietz, SET 23 May 2018 Automatic FireAlarm Association SURVIVING SURVIVABILITY - A USER S GUIDE TO Larry D. Rietz, SET
More informationSECTION : FIRE ALARM & DETECTION SYSTEMS
SECTION 28 31 10: FIRE ALARM & DETECTION SYSTEMS 1. GENERAL A. This section applies to fire detection/alarm system and carbon monoxide system components and equipment installed during new construction
More informationACT2-CS Convenience Store Controller
Refrigeration Systems Technical Manual 804 Product Bulletins Section Product Bulletin Issue Date 0899 ACT2-CS Convenience Store Controller The ACT2-CS Convenience Store Controller is a fully programmable,
More informationFire Protection Coffee Break Training May 2016
Fire Protection Coffee Break Training May 2016 Introduction High-Rise Requirements Questions and Answers Agenda Overview Site Fire Access Aerial Access Power/Back-up Power Elevators and Access Sprinklers
More informationVACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES
Part One General 1.01 Scope A. It is the intent of this specification to provide a medium voltage automatic transfer system. B. All components, testing and services specified and required for a complete
More informationFull Service Central Station Fire Alarm Listing Evaluation
Full Service Central Station Fire Alarm Listing Evaluation Listing Evaluation A UL Listing project includes: 1. Evaluating the central station facility for compliance with UL 827, Central-Station Alarm
More informationMINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry
MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Fire Alarm Systems Plan Review Checklist Date: Permit Number: Business Name: Address: Fire Alarm System Submittal
More informationTEC3000 Series Wireless, Stand-Alone, and Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers Catalog Page
Code. LIT-1900896 Issued February 17, 2017 TEC3000 Series Wireless, Stand-Alone, and Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers Catalog Page Description The TEC3000 Series Thermostat
More informationDESIGN GUIDELINE SBA 5.11
GeneralScope DESIGN GUIDELINE SBA 5.11 FIRE COMMAND CENTER This design guideline clarifies how certain Michigan Building Code (MBC) requirements for Fire Command Centers are to be applied on University
More informationAnnunciators, 8 LED. D7030X, D7030X-S2, and D7030X-S8. Installation Manual
Annunciators, 8 LED D7030X, D7030X-S2, and D7030X-S8 en Installation Manual Annunciators, 8 LED Notices en 3 1 Notices These instructions cover the installation of the D703X, D7030X-S2, and D7030X-S8
More informationInstallation and Operation. Tracer ZN521 Zone Controller CNT-SVX07C-EN
Installation and Operation Tracer ZN521 Zone Controller CNT-SVX07C-EN Installation and Operation Tracer ZN521 Zone Controller CNT-SVX07C-EN April 2005 CNT-SVX07C-EN Tracer ZN521 Zone Controller Installation
More informationEnvironmental Health & Safety
Environmental Health & Safety Oklahoma State University ADDRESSABLE FIRE ALARM SYSTEM STANDARD Environmental Health and Safety University Health Services Suite 002 Stillwater, OK 74078 (405) 744-7241 www.ehs.okstate.edu
More informationIdaho Surveying & Rating Bureau, Inc South Cobalt Point Way Tel: (208) Meridian, Idaho FAX: (208)
Idaho Surveying & Rating Bureau, Inc. 1871 South Cobalt Point Way Tel: (208) 343-5483 Meridian, Idaho 83642 FAX: (208) 895-8059 www.isrb.com e-mail info@isrb.com Joseph C. Harbacheck, CIC Secretary - General
More informationSLATE. Base Module INSTALLATION INSTRUCTIONS R8001A1001
SLATE Base Module R8001A1001 INSTALLATION INSTRUCTIONS Scan for more information Application SLATE brings configurable safety and programmable logic together into one single platform. The platform can
More informationFCC Fan-Coil Units High-Performance, Vertical
FCC Fan-Coil s High-Performance, Vertical Model FCC construction features Piping and supply-duct connections are from top of unit, eliminating the need for side or back access Right or left-hand configurations
More informationModel 17A00 Expansion Enclosure
HOME AUTOMATION, INC. Model 17A00 Expansion Enclosure Installation Manual Document Number 17I00-1 Rev A March, 2002 Home Automation, Inc. Model 17A00 Expansion Enclosure Installation Manual Document Number
More informationAcross-the-Line SERIES MP300 Combined Manual and Automatic
Across-the-Line SERIES MP300 Combined Manual and Automatic Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s Standard for Centrifugal Fire Pumps
More information"SS90" SERIES CONTROLS MODEL C INSTALLATION MANUAL
S S S SS O L I D S S90 TATE ECURITIES, INC SOLID STATE FAIL-SAFE UNIT * PATENT PENDING LISTED U L 99Y9 RESET RELEASING DEVICE SOLID STATE SECURITIES, INC. "SS90" SERIES CONTROLS MADE IN THE U.S.A. MODEL
More informationAIRPORT OFFICE BUILDING. Smoke Control System. Testing Procedures Manual. September 10, 2016
IMPACT ENGINEERING, INC. AIRPORT OFFICE BUILDING Smoke Control System Testing Procedures Manual September 10, 2016 All Rights Reserved This manual is protected by the U.S. Copyright Law (Title 17 United
More informationFire System Objects. Introduction Page *3. Engineering *17. Data Base Generation *43
Metasys etwork Technical Manual 636 Objects Section Technical Bulletin Issue Date 696 Fire System Objects Introduction Page *3 Description *3 Purpose *5 Capabilities *7 Functional Diagram *1 Operator Interface
More information16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5
Construction Standards Page 1 of 5.1 General Description.1 The University requires that all new fire alarm system control panel, components, and devices, as required for the project, be Secutron 2900 Series
More informationLifeAlarm Fire Alarm Controls
UL, ULC Approved* LifeAlarm Fire Alarm Controls 4009 IDNet NAC Extender for Control with IDNet Communications or Conventional NACs Features Provides additional notification appliance circuit (NAC) capacity
More informationPS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option
Installation PS6 SERIES Power Supplies PS6 SERIES Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option Installation and Specifications Manual ISDPS6_SERIES 08121590 PCN15016 R05/15GR
More informationLC150 VIEW-AT-A-GLANCE PUMP CONTROL-TELEMETRY UNIT
LC150 VIEW-AT-A-GLANCE PUMP CONTROL-TELEMETRY UNIT Simply Features In Brief Telemetry Ready Security 2 or 3 Pump Control UL Listed Alarm/Event Log Volumetric Flow Calculator VFD Control Optional Dialer
More information