Specification, installation & maintenance of fire doors: Technical Note 2
|
|
- Sheryl Hicks
- 6 years ago
- Views:
Transcription
1 Specification, installation & maintenance of fire doors: Technical Note 2 March 2016 You & Your Care \\raptor\user data\users\kbyard Karen Byard: Fire Officer Tel: Karen.byard@bdct.nhs.uk
2 Contents Contents Certification... 3 Fire door signs... 3 Fire doors (General)... 3 Where fire doors are required... 4 All sites containing sleeping accommodation... 4 Hazard rooms include... 4 Office and health centre accommodation... 4 Door leaf & frame... 6 Threshold gap... 6 Door Protection... 6 Intumescent and cold smoke seals Permissible gaps around the door Threshold gap Hinges Number and Position of Hinges Locks and latches Mortise latches and locks Digi locks Lever handles and knobs Glazing including vision panels Intumescent seal types for glazing Glazing bead Replacement Vision Panels Panic and emergency exit devices Door closers Other Components Pull handles, kick plates, push plates, letter plates & spy holes (door viewers) Air transfer grilles... 70
3 Certification BEFORE ANY WORK IS UNDERTAKEN ON ANY FIRE DOOR YOU MUST CHECK THAT THE DOOR DOES NOT HAVE ANY CERTIFICATION LABELS. IF IT DOES YOU MUST FOLLOW THE ADVICE GIVEN FOR THAT DOOR OR THE CERTIFICATION WILL BE VOID. CERTIFICATION MARKS ARE SHOWN BELOW & WOULD USUALLY BE ON THE TOP OR HINGE EDGE OF THE DOOR Fire door signs All fire doors must be signed using one of the following standard signs. For mental health wards please seek advice from the Trust Fire Officer Fire door keep closed: Positioned at eye level on outer facing part of door. Corridor doors shall have signs fitted at both sides. On double leaf doors, signs shall be fitted on both sides (and both leaves if a corridor door) Fire door keep locked: Positioned at eye level on outer face of door. To be used on fire doors that are not fitted with self-closers and are designated hazard rooms (ie store cupboards, service risers, plant rooms and laundries) Automatic fire door keep clear: Positioned on visible open leaf at eye level. Used on doors connected to automatic hold open devices that release the door on activation of the fire alarm Fire doors (General) FD30s doors generally shall not be less than 44mm in thickness FD60s doors generally shall not be less that 54mm in thickness
4 Where fire doors are required All sites containing sleeping accommodation The requirements of Firecode must be met. All doors leading on to an escape route must be fire doors. All hazard rooms must have a fire door fitted (these are detailed below) Ward areas: All doors that lead on to a corridor must be fire doors Communal bathrooms in mental health wards must have fire doors fitted Hazard rooms include Cleaner s stores/cupboards. Clothes or linen cupboards. Laundries. Staff changing rooms/locker rooms. Store rooms. Ward kitchens. Medical record stores. Stationery Cupboards. Contractors/workmen s stores. Lift motor rooms Plant rooms Electrical intake rooms or cupboards Boiler rooms Main gas intake rooms Gas bottle storage or manifold rooms Workshops Any confined spaces roof-spaces, ducts or voids etc Flammable liquid stores Communal bathrooms on mental health ward Office and health centre accommodation All hazard rooms must have a fire door fitted (these are detailed above) All corridor doors must have fire doors fitted All doors leading onto a dead end corridor must have a fire door fitted
5
6 Door leaf & frame The selection and installation of the door and frame is very important. Where purpose built frames are installed they shall be matched with the recommended door, as the fire resistance of one may depend on the design features of the other. Fire doors must be supplied by the company that has designed, tested & manufactured door themselves. Cascaded evidence is not acceptable New or replacement fire doors must be solid core or flaxboard core with at least 10mm solid wood lippings. In high traffic & in-patient areas these should have a laminated face with edge protection fitted. Please see Appendix 3 & 4 No work is to be carried out on the top edge of the door (head) Fire doors shall fit close to the frame with a 3mm gap allowed; the gap must not exceed 5mm. Any gaps between the frame and the wall must be in-filled with the appropriate fire stopping material (Please see below & Technical Note 1) When intumescent material on the frame faces the same on the door edge, they must be the same type New door sets will not be accepted, unless accompanied by the appropriate test evidence. Cascaded evidence is not acceptable If a new frame & door is required these must be produced under the control of a single manufacturer that is responsible for the evidence of performance of the fire door Please see BM TRADA Accepted Repair Techniques: ART 1, 3, 6, 7, 9, 17, 18 and 20 at the end of this section Everbuild Fire Sealant 300 can be used to repair surface damage to non-certificated fire doors. The damage must be no more that 50mm wide & deep. Please see the appendix 1 at the end of this section for further information A filled penetration can be covered with impact protection. Metal plates must not be used to cover any penetrations unless they have been filled Threshold gap The threshold gap must not exceed 10mm. If it is more than 10mm then a face fixed or drop down threshold seal must be fitted. Please see section on intumescent & cold smoke seals for further information Door frame Door frames at community sites can be softwood, except in high traffic areas where hardwood should be used Door frames for in-patient buildings must be hardwood. The frame must be as deep as the aperture will allow & be fixed to the wall & the door with the maximum length screws possible Architrave to wall gaps The frame must be fixed securely to the surrounds, with the gap not exceeding 10mm between the frame and the wall. 0-6mm gaps must be filled with Pyroplex intumescent mastic. Gaps over 6mm must be packed with mineral fibre & then capped off with Pyroplex intumescent mastic. The specification for the fire stopping used, must be placed in the buildings fire manual. Please see Appendix 2 & the Fire technical note 1: Passive fire protection which is available from the Trust Fire Officer Door Protection Laminate faced doors must be considered when installing doors in high traffic areas or areas where the doors may be vulnerable to abuse. Impact protection should also be fitted to doors frames & door leaf edges in areas where damage may occur.
7 Impact protection can also be retro fitted to an existing door after consultation with the Trust Fire Officer Manufacturer s instructions The manufacturer s installation instructions & product types must be followed when fitting any new fire door Making changes to how a fire door is installed If any changes from the manufacturers instruction are required when fitting a fire door advice must be sought from the Trust Fire Officer prior to these alterations. This ensures that we have an evidenced tested solution from the door manufacturer to the changes that are made
8
9
10
11
12
13
14 APPENDIX 1
15
16 APPENDIX 2
17
18
19
20 APPENDIX 3 Flaxboard core 30 minute fire door Core: Door Thickness: Facing: Door leaf Solid 450kg/m 3 flax core 63x36mm softwood perimeter frame 44mm thick for FD30(S) MDF/veneer/laminate Lipping: Visible 10mm hardwood lipping to all edges Glazing details: To Trust Fire Door Technical Specification Finish as delivered: Factory finished one coat primer to two faces of paint grade doors/two coats factory lacquer to two faces of veneer doors Frame Wood species: Hardwood for paint finish Class (to BS EN 942): J40 and J50 Finish as delivered: Primed for site painting Moisture content on delivery 9 to 13% Architrave Wood Species MDF Class (to BS EN 942) J40 and J50 Finish as delivered Primed for site painting Moisture content on delivery 9 to 13%
21 Solid core 30 minute fire door APPENDIX 4 Door leaf Core: Solid 640kg/m 3 laminated timber core Door Thickness: 44mm thick for FD30(S) Facing: MDF/veneer/laminate Lipping: Visible 10mm hardwood lipping to all edges Glazing details: To Trust Fire Door Technical Specification Finish as delivered: Factory finished one coat primer to two faces of paint grade doors/two coats factory lacquer to two faces of veneer doors Frame Wood species: Hardwood for paint finish Class (to BS EN 942): J40 and J50 Finish as delivered: Primed for site painting Moisture content on delivery 9 to 13% Architrave Wood Species MDF Class (to BS EN 942) J40 and J50 Finish as delivered Primed for site painting Moisture content on delivery 9 to 13%
22
23 Intumescent and cold smoke seals The area where the door leaf meets the door frame is the part most susceptible to penetration by fire and cold smoke. Please see BM TRADA Accepted Repair Techniques: ART 4, 11 and 22 at the end of this section An intumescent strip can either be fitted in the door frame or in the door edge itself and must be centrally fitted. Intumescent strips must not be fitted to the bottom edge of the door as the door will be forced open as the strip expands. The different types of intumescent seals are not interchangeable. If you are unsure of the type used the complete seal must be replaced. If the type of seal is not known a Pyroplex brush intumescent & cold smoke seal must be used All new doors must have Pyroplex brush intumescent & cold smoke seals If intumescent or cold smoke seals become damaged they must be replaced with the identical product. If unsure of type used the complete seals must be replaced Intumescent and cold smoke seals must be fitted to the top edge and both sides of the door, or frame, they must not be fitted along the bottom edge FD30 doors generally shall not be less than 44mm in thickness o Intumescent strips and cold smoke seals can be interrupted for hinges and latches FD60 doors generally shall not be less that 54mm in thickness o Intumescent strips and cold smoke seals are generally fitted in double strips. One strip must be uninterrupted and the other can be interrupted for hinges and latches. Single strips of 30mm wide can also be fitted, but these must be uninterrupted. When a door is required to have cold smoke and intumescent seals this is should be achieved by using a single strip combining both functions. If this is not possible please seek advice from the Trust Fire Officer Intumescent and cold smoke seals must be protected during painting. If paint covers the cold smoke seal it must be replaced. In in-patient areas the intumescent & cold smoke seal must be cut every 300mm & then pinned into the rebate to reduce the ligature risk Permissible gaps around the door 3mm gaps are permitted in the head, opening & closing edge of the door Up to 10mm gap is permitted at the threshold edge. Drop down threshold or face fixed seals are required if the gap exceeds this Threshold gap The threshold gap must not exceed 10mm. If it is more than 10mm then a face fixed or drop down threshold seal must be fitted. Community buildings & non-patient areas of in-patient buildings: A face fixed threshold seal can be fitted if the gap is less than 15mm. Please see appendix 6 In-patient areas: A drop down threshold seal can be fitted if the gap is less than 15mm. Please see Appendix 5
24
25
26 APPENDIX 5
27 APPENDIX 6
28
29 Hinges Hinges fitted to fire resisting doors must achieve the intended fire rating, also the hinge must be able to allow the door closing device to close the door fully to latch Generally all doors on escape routes shall open in the direction of emergency travel. For further advice please speak to the Trust Fire Officer At the same time, where escape route doors are part of the final exit from a building, there will be some additional requirements for security of the door against intrusion and burglary. In this case the hinges shall be of a design so that they cannot be removed or parted whilst the door is closed, ensuring that the building and its contents are secured against unauthorised entry. Where escape route doors are part of the fire compartmentation of the building, there will be additional requirements to ensure that the hinges fitted meet the same fire-resisting performance of the door set. For hinges in in-patient areas anti-ligature continuous geared hinges or anti ligature secura hinges should be fitted. Please see Appendix 7 & 8 for fixing instructions Please see BM TRADA Accepted Repair Techniques: ART 8, 13 and 15 at the end of this section Hinges in community buildings must be a bushed bearing hinge that is: CE Marked to BS EN 1935, including its Annex B. This document is available from Bradford District Care Trust Fire Officer if required. Provided with certification by an approved third party certification body. The strength and features must be correct for the size of door and weight to which it is to be fitted, bearing in mind: o The use of the door (main entrance, toilet lobby, duct door), o Position of door stop if being used (position on floor or wall in relation to width of door) o Whether subject to factors such as heavy traffic use, abusive treatment o Whether or not a door closer is being used o Height and width and weight of the door and number and position of hinges o Whether the door is on an accessible route and therefore must to satisfy Part M of the Building Regulations The following type of hinges are not permitted on Trust fire doors Rising butt hinges Spring hinges Lift off, loose pin and journal supported hinges Ball bearing hinges General information about hinges on fire doors For timber doors and frames, fixing screws shall be not less than size No.8 (3.8 mm) and not less than 30 mm in length. Some fire doors are being manufactured with Graduated Density Core materials. These require a longer fixing screw of at least 50mm. If there is any doubt, advice must be sought from the door manufacturer regarding the material of the door core.
30 For timber door leaves of 44mm thickness part of the hinge shall extend across the door thickness to a position closer than 12 mm from the opening edge. For timber door leaves of 54 mm thickness no part of the hinge shall extend across the thickness to a position closer than 18 mm from the opening edge. If intumescent material was used when the hinge was fire tested, it is essential that the same material be used in order for the test evidence to be valid and maintain the integrity of the door set. If the hinges require packing Pyroplex hinge pads. Cardboard must not be used to pack hinges under any circumstances If the hinge rebate is too large Pyroplex intumescent mastic must be used to fill the gap Hinges must have a minimum melting point of at least 800 C Number and Position of Hinges It is usual for at least 3 hinges to be fitted on fire and escape route doors. With fire-resisting doors becoming heavier, two hinges are required at the top of the door with the third hinge at the bottom of the door. The door manufacturers guidelines must be followed, it is unsafe to alter the as tested position of a hinge on a fire door, without assessment from a suitably qualified authority. For doors heavier than 160 kg or exceeding 2000 mm in height and 1000 mm in width, a recommendation from the hinge and/or door manufacturer shall be obtained. Annex D of BS EN 1935 gives additional advice regarding the use of hinges on doors of excessive width. (A wide door is one where the width is more than half the height.) This document is available from the Bradford District Care Trust Fire Officer on request.
31
32
33
34 APPENDIX 7
35 APPENDIX 8
36
37 Locks and latches In order to provide an effective barrier to a fully developed fire, a door has to remain closed within the frame. The addition of a lock or latch to a fire-resisting door set can reduce the fire performance of the door set. The reduction in the amount of wood in the stile or rail can also impair the stability of the door, leaving it less able to resist distortion caused by the heat of a fully developed fire. Where security is in conflict with easy egress, consultation with the regulatory authority or fire officer must be made in order to reach a satisfactory solution. Please see BM TRADA Accepted Repair Techniques: ART 12 at the end of this section A locked fire door must be able to be opened with a single action; this can be achieved by fitting one of the following A thumb turn lock A panic bar An electronic lock which releases on fire alarm activation, this must also be accompanied by a green break glass In fitting locks or latches to fire-resisting door sets, the potential fire performance of the door set can be reduced due to Removal of a section of the door leaf, door frame or seal. To minimise this, the locks and latches shall be as small as is practicable. Leaving voids within the structure of a timber door, Adding materials which could cause heat transfer problems in a timber door, Through fixings creating thermal bridges in a timber door, using materials of low melting point (less than 800ºC) Locks containing materials which might flame. The lock or latch must be CE marked to BS EN Provided with additional product certification by an approved third party certification body. Section 6: Lock and Latches Page 61 Voids in the Structure of the Door All mortising in fire-resisting timber doors must be performed as accurately as possible to avoid creating unnecessary voids. Clearance holes for keys, cylinders and spindles must be no larger than the sizes specified on the manufacturer s fitting instructions. If the latch or lock specifies the fitting of some form of intumescent protection and/or use of covered escutcheons, these must be used to ensure that the fire resistance of the door is no less than when tested. The following types of door hardware are not permitted on any Trust fire door Roller ball catches Rim latches Bored-in knob sets
38 Mortise latches and locks Mortise latches are normally mortised into the door edge. Please see BM TRADA Accepted Repair Techniques: ART 2 at the end of this section Where mortise locks are provided, the cut-out in the door must be the minimum necessary to prevent any voids which fire can penetrate. After the edges, the mortise lock and latch areas represent the next zone of weakness. Any voids in the cut-out must be filled with intumescent paste to lessen the weakness in this area. As the latch is the only holding device on the closing edge, it is important that it must be strong and that the nib of the latch must engage into the latch plate at least 12 mm to ensure that the closing edge will not spring open when the door deforms. Extended flap latch plates are required for one-hour doors. The lock or latch shall be CE marked to BS EN and shall have additional product certification by an approved third party certification body. The Trust requires that pairs of timber fire doors have plain edge stiles with a conventional latch and striking plate rather than rebated meeting stiles with forend conversion units. However, providing there is satisfactory fire test evidence, timber rebated doors with their appropriate fittings may be permitted. As mortise locks are generally larger than latches, the amount of wood removed in fixing and the extra amount of metal introduced can make the reduction in fire integrity that much greater. Any voids in the cut-out must be filled with intumescent paste to lessen the weakness in this area. Digi locks Digi locks must not be fitted on any fire door due to the large penetration through the door leaf. If a Digi lock is required a Coded handle E3100 (Assa Abloy) can be used but must be approved by the Trust Fire Officer prior to the work being agreed. Please see Appendix 9 Lever handles and knobs Fire-resisting door sets usually incorporate either: Lever handles or knobs if the doors are latched, or Pull handles/push plates if unlatched. Lever handles and knobs must comply fully with: BS EN Building hardware - Lever handles and knobs This evidence must be provided by an approved third party certification or testing body. Pull handles must comply fully with: BS 8424 Building hardware, Pull handles, Requirements and test methods This evidence must be provided by an approved third party certification or testing body. All door furniture must have demonstrated its suitability for the intended purpose, by inclusion in satisfactory fire tests to BS 476:22, BS EN or BS EN , on a type of door set and configuration on which it is proposed to be used. This evidence must be provided by an approved third party certification or testing The use of intumescent sleeves around the fixing holes is required for timber doors. The material used in the construction of lever handles, knobs and pull handles/protection plates has not been found to greatly affect the fire performance of the timber door sets to which they are fitted. Generally it is also true that the actual size of the lever handle or pull handle has no effect upon the fire performance of the doors to which it is fitted.
39
40
41 APPENDIX 9
42
43
44 Glazing including vision panels If vision panels or glazing is required in an existing fire door or partition then a new fire door is required Fire-resistant glass must only be used as part of a fire-resistant glazing system which includes the glass, the glazing seals, glazing beads, fixings and frame. Glazing for fire doors must be 10-12mm Pyrobellite. Temporary repairs can be made with 10mm clear polycarbonate All the essential components of such a system must be compatible under fire conditions and the performance must be referenced to appropriate and relevant test evidence Please see BM TRADA Accepted Repair Techniques: ART 14 at the end of this section What is required when glazing is fitted? Official evidence from a competent authority demonstrating the fire resistant performance of the glazing system used Evidence of installer competence (e.g. UKAS-accredited certification body) Permanent stamp on the glass that indicates as a minimum, the name of the glass product and the manufacturer/supplier and possibly the fire performance rating The stamp must be visible and readable after glazing Any necessary refurbishments must be carried out according to the approved original specification for the glazing system and shall be completed on a like for like basis All components must be replaced with a new, complete and approved fire-resistant glazing system if the original glazing system specification cannot be established or was originally specified incorrectly Intumescent seal types for glazing Intumescent seals are based on materials that expand and foam on exposure to heat. The degree of intumescence and the expansion pressure vary according to the material and its formulation. In particular, the following must be noted Sodium silicate and graphite based materials may have a high expansion pressure which means they have to be used and applied carefully as the application of too much material may push the beads off, leading to premature failure Ammonium phosphate materials do not show expansion pressure to the same degree, but if the expansion is too great then the density of the material left in the gap between the glass and the bead may be too low to inhibit erosion leading to premature failure Pre-formed strips of intumescent compound ensure that the correct thickness and amount of material is applied. Intumescent seal strip materials may be unprotected if they are composed of a material that is not particularly sensitive to moisture and they will generally have a self-adhesive layer to fix to the bead
45 Glazing bead Anti-Tamper screw fixings, counter sunk flush, as pictured, to be used on glazing beads Replacement Vision Panels To fit a replacement vision panel to an existing fire door the technical specification in the Vision Panel guidance must be used. This is available from Estates Maintenance or the Trust Fire Officer Vision Panel must not be fitted to a fire door that currently does not have one fitted without seeking approval from the Trust Fire Officer
46 Emergency glazing repair 240mm coach bolt M12 nylock nuts to clamp plus washers Emergency Glazing repairs should avoid fixing anything directly to the face of the door or damaging the door in anyway. If the broken glass cannot be held securely in place using a film and the area needs boarding please see below for how to temporarily repair the door In an emergency situation please follow the below steps Carefully remove and clear any broken glass and dispose of, remove the beading if necessary. 2x 18mm ply boards should be cut oversized by a minimum of 50mm all-round if possible so they sit on the outside of the door on either side of the glazed area. The boards are to be clamped together with 4x 240mm coach bolts & M12 nylock nuts as detailed below. These bolts should be fixed in each corner of the original glazed area so it stops the temporary boarding being slid in any direction. The coach bolt must be on the patient side of the door to reduce the ligature risk
47
48
49 Panic and emergency exit devices Push pads must not be fitted on any Trust door, Exidor panic bars must be used where required Signage must accompany all panic bars stating how they are operated Experience relating to escape from buildings and general safety has shown the importance of fitting doors on escape routes with suitable exit devices to enable the occupants of the building to escape quickly and easily in the case of fire or some other emergency. Factors to consider include: Different groups of users will have differing requirements to enable them to make an effective escape and this has to be reflected in the type of device chosen. Where escape route doors are part of the final exit from a building, there will be some additional requirements for security of the door against intrusion and burglary. In this case there can be a conflict between the requirements of building users to be able to escape easily and the requirements of building owners to secure their building and its contents against crime. Where escape route doors are part of the fire compartmentation of the building there will be additional requirements to ensure that the escape hardware fitted does not compromise the fire-resisting performance of the doorset. Devices intended for use must be CE Marked to BS EN Panic exit devices operated by a horizontal bar, and preferably provided with additional product certification by an approved third party certification body. Devices for use on pairs of doors shall have been specifically tested and approved for that purpose. Care must be taken that hinges and any seals are correctly fitted so that the escape doors are able to open freely once the exit device is operated. No additional security devices must ever be fitted to escape route doors unless specifically approved by the Trust Fire Officer Section 12: Panic and Emergency Exit Devices Page 97 The exit device and any accessories shall have demonstrated their ability to be suitable for the intended purpose, by inclusion in satisfactory fire tests to BS EN or BS EN , on the type of timber doorset and configuration in which it is proposed to be used. This evidence must be provided by an approved third party certification or testing body. The Building Regulations (England and Wales) 2000 Approved Document B 2006 Edition requires that all doors on escape routes be fitted with escape hardware that is simple to operate and does not require specialist knowledge or tools for its operation (e.g. panic bars).page Break-glass emergency bolts must not be used on emergency exit doors in any Trust building
50
51 Door closers If a closer is required on a fire door a Dorma TS92 cam action closer must be used. Please see Appendix 10 If a closer is required that does not add any additional opening force to the door (ie in elderly wards) then a Dorma TS73 EMF free swing door closer can be used. Please see Appendix 12 For closers in ward areas Closers in non-patient areas on the wards should be Dorma TS92 cam action closers. Please see Appendix 10 For closers in patient areas a Safehinge Symphony closer must be used. Please note this closer requires a 54mm door. If this closer is not already fitted to the door a new frame will also be required. Please see Appendix If a frame mounted free swing closer is required a Dorma RTS 87-RTS80 EMB closer can be used. Please see Appendix 11 Rack and pinion closers should not be used on Trust fire doors Freedor Any requirement for a Freedor must be approved by the Trust Fire Officer. Please see Appendix 12 Dorguard Any requirement for a Dorguard must be approved by the Trust Fire Officer. Dorguards must not be used on corridor or hazard room doors unless approval is given by the Trust Fire Officer Please see Appendix 13 Please see advice from the Trust Fire Officer for other options
52
53 APPENDIX 10
54 APPENDIX 12
55 DORGUARD APPENDIX 13
56 FREEDOR APPENDIX 14
57 SAFEHINGE SYMPHONY APPENDIX 16
58
59
60
61
62
63
64
65
66
67
68
69
70 Other Components Pull handles, kick plates, push plates, letter plates & spy holes (door viewers) Pull handles shall use bolt-through fixings, rather than face-fixed screws, as these will prove more durable. The heads of the fixing bolts shall be protected by a push plate or rose. Door protection (kick) plates fitted at the bottom of the door have not been shown to have any effect on the fire performance of timber door sets. Push plates of conventional sizes, which can be screwed or adhesive-fixed, can also be fitted without problems. Letter plates must not be fitted to any fire door Door viewers/spy holes must not be fitted to any fire door unless the door viewer model is supported by evidence of fire performance in a door of the relevant material & has been approved by the Trust Fire Officer prior to the start of any work. Please see Appendix Air transfer grilles Air transfer grilles in fire doors will not only allow air to pass through but fire and smoke. It is essential that any air transfer grille fitted to a fire door does not reduce the fire and smoke resisting properties of the door. Air transfer grilles will only be permitted on any fire doors, once all other methods of venting have been explored. Any air transfer grille fitted to a Trust fire door must be interfaced with a fire alarm & activate on heat & smoke Air transfer grilles in fire doors shall not be fitted higher than 1000mm from the bottom of the door. Please speak to the Trust Fire Officer before specifying any air transfer grille
71 APPENDIX 15
72 Glossary Automatic fire door sign Ball bearing hinges Bored-in knob set Break glass emergency bolts Bushed bearing hinge Fire door keep closed sign
73 Fire door keep locked sign Digi lock Digi lock coded handle Door viewer (spy hole) Intumescent & cold smoke seal Lever handles Lift off, loose pin and journal supported hinges Mortise lock
74 Panic bar Pull handles Push bar to open sign Push pad Rack & pinion door closer Rim latch Rising butt hinge
75 Vision panel Roller ball catches Spring hinges
IDD 033C - Fire door sets
IDD 033C - Fire door sets Why are fire door sets important? Fire doors are one of the most important features of a building s fire precautions and have two key functions: To protect escape routes from
More informationFIRE DOORS RHUL REQUIREMENTS
Fire Safety Technical Guide FIRE DOORS RHUL REQUIREMENTS This guide draws together the general requirements of a range of published standards and reference documents and is to be used in addition to any
More informationRegulatory Reform (Fire Safety) Order 2005
Regulatory Reform (Fire Safety) Order 2005 This document has been prepared by ASDMA (Architectural & Specialist Door Manufacturers Association) to provide for guidance for Responsible Persons in respect
More informationFire Doors Technical Guidance
Fire Doors Technical Guidance Introduction Buildings are compartmented to delay the spread of fire from one area to another. The compartments are usually linked by doors to allow for passage of traffic
More informationFire Protection. Intumescent fire and smoke seals for door assemblies
Fire Protection Intumescent fire and smoke seals for door assemblies Intumescent Seals Fire Protection Quality you can trust Exitex offer a wide range of fully tested intumescent strips, glazing seals
More informationFIRE DOORS - GENERAL UCL OVERVIEW AND REQUIREMENTS
Fire Safety Technical Note FIRE DOORS - GENERAL UCL OVERVIEW AND REQUIREMENTS Fire Door Provision In UCL Buildings - what you need to know: Mandatory - all doors on main traffic and circulation routes,
More informationMaintenance. Why Maintain Fire Doors? Regulations
Introduction Fire doors are commonly overlooked as an essential part of a commercial or public building maintenance regime. However, fire doors help sub-divide a building into compartments, slowing down
More information25 th November Title:
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: The Fire Resistance Performance
More informationfire doors the burning issues From specification to maintenance the life cycle of a fire door explained guide
fire doors the burning issues From specification to maintenance the life cycle of a fire door explained guide Passive Fire Protection Passive fire protection products are built into the fabric of a building,
More informationThe Association for Specialist Fire Protection
The Association for Specialist Fire Protection The Role of Fire Doors, Frames and Fire Seals, Door Hardware Maintenance and Replacement John Fletcher Technical Consultant British Woodworking Federation
More informationCERTIFICATE OF APPROVAL No CF 530 HOPPE (UK) LIMITED
CERTIFICATE OF APPROVAL No CF 530 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Gailey Park Industrial
More informationSchedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK
2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK UK Test Laboratory School Street Willenhall WV13 3PW Contact: Mr I Bridge Tel: +44 (0) 1902 364600 Fax: +44 (0) 1902 364681 E-Mail: ian.bridge@assaabloy.com
More informationC/S Fire Rated Door Edge Protection Product Range FD60
DE-06 Plain Edge Protector Seal Options used with/without s Range FD60 Product Range FD60 Intumescent & Smoke seal (brush seal) DE-04 with Intumescent Seal DE-05 with Intumescent & Smoke Seal (twin fin)
More informationGuide to Fire and Escape Doors: Part 1 - What are they? Produced by the Guild of Architectural Ironmongers Sponsored by Abloy UK
Guide to Fire and Escape Doors: Part 1 - What are they? Produced by the Guild of Architectural Ironmongers Sponsored by Abloy UK www.gai.org.uk Introduction This will be a brief overview of the subject,
More informationCERTIFICATE OF APPROVAL No CF 5542 ASSA ABLOY SECURITY SOLUTIONS
CERTIFICATE OF APPROVAL No CF 5542 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of 11B Street, Jebel Ali
More informationSchedule of works required for Fire Protection in a 2 Storey semi-detached/terraced house
Schedule of works required for Fire Protection in a 2 Storey semi-detached/terraced house THIS DOES NOT COVER 3 STOREY PROPERTIES you must consult with the Private Sector Housing Team on any 3 storey property.
More information1.4 Provide and fix the following ironmongery.
Schedule of works required for Fire Protection in a first & second floor purpose built masionette above shops where the exit door is at first floor level. THIS DOES NOT COVER NORMAL 3 STOREY PROPERTIES
More informationStrebord 35 FD30 Strebord 44 FD30 Strebord 54 FD60
.1 Strebord 35 FD30 Strebord 44 FD30 Strebord 54 FD60 Falcon Panel Products Ltd Clock House Station Approach Shepperton Middlesex TW17 8AN Strebord Technical Manual (Version 9.1) Validation of Data against
More informationCERTIFICATE OF APPROVAL No CF 530 HOPPE (UK) LIMITED
CERTIFICATE OF APPROVAL No CF 530 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Gailey Park Industrial
More informationCylinder Mortice Dead lock Lockcase(mm) A=87 Backset (mm) B=55. Follower (mm) 8 Latch Bolt
Product ID: KL.1902 Name: Cylinder Mortice Dead lock Lockcase(mm) A=87 Backset (mm) B=55 Centres C=N/A Follower (mm) 8 Latch Bolt N/A Mechanism Euro- Profile Forend Finish SSS Rebates available (mm) KL.1902A
More informationAbout the Instructor & Presenter:
About the Instructor & Presenter: Paul G. Baillargeon, AHC, FDAI Vice President, Technical Consulting Door Security & Safety Foundation A noted veteran in the door and hardware industry, Mr. Baillargeon
More informationFire Rated Door Assemblies: Compliant Designs
Fire Rated Door Assemblies: Compliant Designs Steel Door Institute www.steeldoor.org AIA Provider #G389 Course #: SDIFIRE 1 HSW CE hour 1 Credit(s) earned on completion of this course will be reported
More informationDORMA. Free Swing and Hold-open Solutions for Fire Doors. An alternative to Fire door keep shut
DORMA Free Swing and Hold-open Solutions for Fire Doors An alternative to Fire door keep shut Permanently closed fire doors can present an obstacle to building occupants, particularly on circulation routes,
More informationUpdated to. include Declaration of Performance Certificates WHICH DOOR CONTROL? Meeting the requirements of the Equality Act & Fire regulations
Updated to include Declaration of Performance Certificates WHICH DOOR CONTROL? Meeting the requirements of the Equality Act & Fire regulations WHICH DORMA DOOR CONTROL? INTRODUCTION There are two main
More informationCERTIFICATE OF APPROVAL No CF 5494 ASSA ABLOY AB
CERTIFICATE OF APPROVAL No CF 5494 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Klarabergsviadukten
More informationFIRE SAFETY MANAGEMENT PROTOCOL FIRE DOORS & FIRE DOOR ASSEMBLIES
FIRE SAFETY MANAGEMENT PROTOCOL FIRE DOORS & FIRE DOOR ASSEMBLIES This is a new procedural document, please read in full. Did you print this document yourself? The Trust discourages the retention of hard
More informationCERTIFICATE OF APPROVAL No CF 5118 ASSA ABLOY LTD
CERTIFICATE OF APPROVAL No CF 5118 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of School Street, Willenhall,
More informationFire doors are a lifeline. When properly fitted and properly cared for they give vital minutes for people to safely escape from fire and smoke.
Fire Doors: A Guide About This Guide Fire doors are a lifeline. When properly fitted and properly cared for they give vital minutes for people to safely escape from fire and smoke. It s critical then that
More informationSection 2 - Applications - General. Section 2A - FD30 Strebord 35+, 38+, 44 & Superpan with MDF & Wood Frames
Section 2 - Applications - General Section 2A - FD30 Strebord 35+, 38+, 44 & Superpan with MDF & Wood Frames Section 2B - FD30 Strebord 35+, 38+, 44, Superpan & Strebord 54 with Steel Frames Section 2C
More informationCERTIFICATE OF APPROVAL No CF 850 ZOO HARDWARE LIMITED
CERTIFICATE OF APPROVAL No CF 850 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Unit B, Dukes Drive,
More informationFire Door Maintenance Guide.
Fire Door Maintenance Guide http://www.c-sgroup.co.uk/products/acrovyn-impact-resistant-doors/ Introduction Fire Doors are a critical safety feature of any building in which people work or visit, as they
More informationThe Association for Specialist Fire Protection
The Association for Specialist Fire Protection Door hardware Maintenance and replacement Jacky Sinclair Technical Consultant Guild of Architectural Ironmongers Pioneering fire protection through innovation
More informationTHE INSTITUTE OF HEALTHCARE ENGINEERING AND ESTATE MANAGEMENT FIRE SAFETY TECHNICAL PLATFORM (FSTP) LIBRARY OF TECHNICAL GUIDANCE. No 2.
THE INSTITUTE OF HEALTHCARE ENGINEERING AND ESTATE MANAGEMENT FIRE SAFETY TECHNICAL PLATFORM (FSTP) LIBRARY OF TECHNICAL GUIDANCE No 2. FIRE DOOR PPM Introduction The FSTP has at its core, to act as the
More informationMeeting the requirements of the Equality Act & Fire regulations. Which Door Control?
Meeting the requirements of the Equality Act & Fire regulations Which Door Control? Introduction There are two main considerations in specifying door controls: Does it meet the requirements of the Equality
More informationRegulatory Reform (Fire Safety) Order 2005
Regulatory Reform (Fire Safety) Order 2005 Solutions for acoustic, smoke and fire containment What is the RRO? The Regulatory Reform (Fire Safety) Order 2005 came into force almost ten years ago in England
More informationABLOY EFEND. New name for security
ABLOY EFEND New name for security SET SECURITY TO NEXT LEVEL ABLOY is now available in ANSI door environment. OPTIONS FOR EVERY NEED Inclusive product range includes both electric and mechanical locking
More informationWHAT TO EXPECT DURING A FIRE DOOR INSPECTION
WHAT TO EXPECT DURING A FIRE DOOR INSPECTION Basic Fire Door Inspections 1. Fire door basic function 2. Understanding codes 3. Responsibility of end user 4. Common fire door deficiencies 5. What your door
More informationUniversity of Rochester October 17, 2008 Brooks Landing Business Center
SECTION 087100 - DOOR HARDWARE PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Commercial door hardware. 2. Cylinders for doors specified in other Sections. 1.2 SUBMITTALS A. Product
More informationA Guide to the Selection of Smoke Seals for Doorsets. Information Sheet No. 5. Intumescent Fire Seals Association
Information Sheet No. 5 Intumescent Fire Seals Association A Guide to the Selection of Smoke Seals for Doorsets THE HOME OF REACTIVE PROTECTION SYSTEMS CONTENTS Page Introduction 1 Purpose of smoke seals
More informationFire doors guidance. Provided by
Fire doors guidance Provided by Contents 1. Scope... 3 2. Introduction... 3 3. Where you could find a fire door... 4 4. Doors not required to be fire doors... 5 5. Which way should a fire door open?...
More informationPassive Fire Protection Guidance for the Fire Risk Assessor. Niall Rowan Technical Officer Association for Specialist Fire Protection
Passive Fire Protection Guidance for the Fire Risk Assessor Niall Rowan Technical Officer Association for Specialist Fire Protection ASFP has just completed a guide on what to look for when undertaking
More information30 Minute Firedoor. 30 minute firedoor
30 minute firedoor 30 Minute Firedoor Rockdoor design and manufacture bespoke 30 minute accredited Firedoors in a pre-hung fire door set, helping house builders, local authorities and contractors to meet
More informationCode of Practice: Hardware for Fire and Escape Doors. Issue No.2 June 2006 THE GUILD OF ARCHITECTURAL IRONMONGERS
Code of Practice: Hardware for Fire and Escape Doors Issue No.2 June 2006 THE GUILD OF ARCHITECTURAL IRONMONGERS Index Page Foreword 1 Section 1...Introduction 1.0 General 3 1.1 Scope 3 1.2 Terminology
More informationPanic Exit Devices. We take the worry out of protecting what s valuable to you. Lockwood: no worries.
Panic Exit Devices We take the worry out of protecting what s valuable to you. Lockwood: no worries www.lockweb.com.au Contents FLUID Series Exit Device Panic Exit Hardware FLUID Series Exit Mortice Lock
More information- CONSTRUCTION FIRE SAFETY STANDARDS
SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Construction Planning All construction sites shall plan and sequence their construction activities to ensure the early installation and operation of permanent
More informationDeveloping a Healthcare Facility Fire Door Inspection Program
Developing a Healthcare Facility Fire Door Inspection Program WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio QUESTIONS How To Ask a Question: 1 POLLING There will be occasional interactive
More informationIntroduction of MSBC Secure India Pvt Ltd. Manufacturer & Installer of Fire Resistance Timber Doorsets
Introduction of MSBC Secure India Pvt Ltd Manufacturer & Installer of Fire Resistance Timber Doorsets Introduction MSBC Secure India Pvt Ltd MSBC Secure is a pioneer in the Door industry having vast knowledge
More informationCERTIFICATE OF APPROVAL No CF 5075 EXIDOR LIMITED
CERTIFICATE OF APPROVAL No CF 5075 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Progress Drive, Cannock,
More informationNFPA 80 Overview January 21, 2016
NFPA 80 Overview January 21, 2016 Kristin Bigda, P.E. Senior Fire Protection Engineer National Fire Protection Association Presenter Kristin Bigda, P.E. Senior Fire Protection Engineer, NFPA Building Fire
More informationHigh Security Locking. Product Catalogue
High Security Locking Product Catalogue An ASSA ABLOY Group company 2 Adams Rite Europe Limited About the company Adams Rite was formed in 1946 in Los Angeles, California and over the years we have created
More informationCERTIFICATE OF APPROVAL No CF 114 EXIDOR LIMITED
CERTIFICATE OF APPROVAL No CF 114 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Progress Drive, Cannock,
More informationProduct. Regulations. Agrément Certificate No 92/2841 Third issue* Designated by Government to issue European Technical Approvals
Lorient Polyproducts Ltd Fairfax Road Heathfield Industrial Estate Newton Abbot Devon TQ12 6UD Tel: 01626 834252 Fax: 01626 833166 e-mail: admin@lorientuk.com website: www.lorientgroup.com CI/SfB (32.5)
More informationThe Fire Resistance Performance Of Timber Or Mineral Composite Based Insulated Doorsets When Fitted With D & E Architectural Hardware Spring Hinges
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: The Fire Resistance Performance
More informationDIVISION 08 OPENINGS HARDWARE AND KEYING PART 1 - GENERAL 1.01 SUMMARY
08 70 00 PART 1 - GENERAL 1.01 SUMMARY A. Section includes the design and coordination for all necessary hardware and coordination for all doors. Hardware shall include but not necessarily be limited to
More informationPassive Fire Protection Guidance. Niall Rowan Technical Officer Association for Specialist Fire Protection
Passive Fire Protection Guidance for the Fire Risk Assessor Niall Rowan Technical Officer Association for Specialist Fire Protection ASFP has just completed a guide on what to look for when undertaking
More informationManaging Fire Safety in your building: Fire Doors Inspections. Part of the KCC Architectural Group
Managing Fire Safety in your building: Fire Doors Inspections Part of the KCC Architectural Group 2 Fire Door Inspections 3 The unavoidable truth Fire doors are a crucial part of any public, commercial
More informationBWF-Certifire Fire Doors and Doorsets. Best Practice Guide
BWF-Certifire Fire Doors and Doorsets Best Practice Guide 1 BWF-Certifire BWF-Certifire: The leading authority on fire door safety A fire door is a vital safety device engineered to save lives and property.
More informationCERTIFICATE OF APPROVAL No CF 267. DORMA UK LIMITED Wilbury Way, Hitchin, Hertfordshire SG4 0AB Tel: Fax:
CERTIFICATE OF APPROVAL No CF 267 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of DORMA UK LIMITED Wilbury
More informationCode of Practice: Hardware for Fire and Escape Doors
Code of Practice: Hardware for Fire and Escape Doors Issue No.3 July 2009 This page is intentionally left blank Index Section 1 Section 2 Section 3 Section 4 Page Foreword 1 Introduction 1.0 General 3
More informationBest Practice BS 3621: 2007 BS 8621: 2007 BS 10621: 2007 dhf
Thief Resistant Lock Assemblies Thief resistant lock assemblies - Key egress BS 3621: 2007 Thief resistant lock assemblies - Keyless egress BS 8621: 2007 Thief resistant dual mode lock assemblies BS 10621:
More informationAll by design. ASSA ABLOY Door Controls
All by design. ASSA ABLOY Door Controls Designed to work for you ASSA ABLOY door controls span three technologies that cover everything you could want from a door closer: from unique features that enhance
More informationCERTIFICATE OF APPROVAL No CF 5506 ALLEGION (UK) LIMITED
CERTIFICATE OF APPROVAL No CF 5506 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of 35 Rocky Lane, Aston,
More informationHardware Selection Process
ASSA ABLOY s door hardware products are ideal for a wide range of situations from private homes to the commercial or public sector and for heavy or lightweight doors. The modular design simplifies planning,
More informationBWF-Certifire Fire Doors and Doorsets. Best Practice Guide
BWF-Certifire Fire Doors and Doorsets Best Practice Guide 1 BWF-Certifire BWF-Certifire: The leading authority on fire door safety A fire door is a vital safety device engineered to save lives and property.
More informationFire and Smoke Door Inspections Qualified Training 02/03/17
Fire and Smoke Door Inspections Qualified Training 02/03/17 Basis of Requirements NFPA 101 requires annual fire and smoke door inspections (Section 18/19.2.2.2.1) Sections 18/19.2.2.1 require compliance
More informationTHE HOME OF REACTIVE PROTECTION SYSTEMS
THE HOME OF REACTIVE PROTECTION SYSTEMS CONTENTS Page Introduction 1 Role of air transfer grilles 1 Definitions and functions 1 Fire performance requirements 2 Varieties of air transfer grilles 3 Recommended
More informationDIVISION 08 OPENINGS HARDWARE AND KEYING PART 1 - GENERAL 1.01 SUMMARY
08 70 00 PART 1 - GENERAL 1.01 SUMMARY A. Section includes the design and coordination for all necessary hardware and coordination for all doors. Hardware shall include but not necessarily be limited to
More informationBest practice guide. Door coordinator devices to BS EN in association with. Association of Building Hardware Manufacturers
CI/SfB (32) Xt7 June 2003 Association of Building Hardware Manufacturers Best practice guide Door coordinator devices to BS EN 1158 in association with BRITISH HARDWARE FEDERATION Extracts from BS EN 1158:
More informationTitle: The Air Leakage Performance of Timber Doorsets fitted with NOR710 Smoke Seals in Accordance with BS 476: Part 31, Section 31.
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: The Air Leakage Performance of
More informationPanic and Emergency Exit Devices
Panic and Emergency Exit Devices BS EN 1125: 2008 & BS EN 179: 2008 www.dhfonline.org.uk 01 dhf Best Practice dhf Best Practice : Panic and Emergency Exit Devices BS EN 1125: 2008 & BS EN 179: 2008 dhf
More informationCENTRAL HOUSING GROUP LTD. General Property Standards Guide
CENTRAL HOUSING GROUP LTD General Property Standards Guide THE FOLLOWING BASIC STANDARDS ARE REQUIRED TO ALLOW THE MANAGEMENT OF YOUR PROPERTY TO BE UNDERTAKEN BUT THIS LIST IS NOT COMPREHENSIVE. ALL OF
More informationAgrément Certificate 92/2841 website: Product Sheet 1
Lorient Polyproducts Ltd Endeavour House Fairfax Road Heathfield Industrial Estate Newton Abbot Devon TQ12 6UD Tel: 01626 834252 Fax: 01626 833166 Page 1 of 1 Agrément Certificate e-mail: mktg@lorientuk.com
More informationCERTIFICATE OF APPROVAL No CF 810 HOPPE (UK) LIMITED
This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of HOPPE (UK) LIMITED Gailey Park, Gravelly Way, Standeford,
More informationCERTIFICATE OF APPROVAL No CF 5350 TAIWAN DAEDALUS DOOR CONTROL CO. LTD
CERTIFICATE OF APPROVAL No CF 5350 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of TAIWAN DAEDALUS DOOR
More informationIS-ORANGE Envirograf. Orange Book. Ventilation. T +44 (0) F +44 (0)
IS-ORANGE-01-15 Orange Book Ventilation Envirograf Innovators - Developers - Manufacturers Passive Fire Prevention Products T +44 (0) 1304 842 555 F +44 (0) 1304 842 666 sales@envirograf.com www.envirograf.com
More informationIronmongery Schedule. Prepared for: ABC Architects Project Title: Education Vertcial Market Our Ref: ABC123
Ironmongery Schedule Prepared for: ABC Architects Project Title: Education Vertcial Market Our Ref: ABC123 Ironmongery Performance Specifications 1.0 Door Hardware Briton Levers, Escutcheon s & Bathroom
More informationIronmongery Schedule. Prepared for: ABC Architects Project Title: Healthcare Vertcial Market Our Ref: ABC123
Ironmongery Schedule Prepared for: ABC Architects Project Title: Healthcare Vertcial Market Our Ref: ABC123 Ironmongery Performance Specifications 1.0 Door Hardware Briton Levers, Escutcheon s & Bathroom
More informationCEN/TC 33 - Doors, windows, shutters, building hardware and curtain walling. EN 107:1980 Methods of testing windows - Mechanical test 89/106/EEC
C/TC 33 - Doors, windows, shutters, building hardware and curtain walling Standard reference Title Directive 107:1980 Methods of testing windows - Mechanical test 129:1984 130:1984 179:2008 477:1995 478:1995
More informationSpecifying Security Hardware for Doors
Specifying Security Hardware for Doors A guide for security and building professionals, installers and locksmiths produced by dhf and The Glass and Glazing Federation. www.dhfonline.org.uk 01 dhf Best
More informationFIRE DOOR SAFETY. Important information for leaseholders about fire doors in your property. September 2017 Version 1
FIRE DOOR SAFETY Important information for leaseholders about fire doors in your property. September 2017 Version 1 It s important that everybody knows their role in keeping themselves and others safe
More informationIronmongery Schedule. Prepared for: ABC Architects Project Title: Transport Vertcial Market Our Ref: ABC123
Ironmongery Schedule Prepared for: ABC Architects Project Title: Transport Vertcial Market Our Ref: ABC123 Ironmongery Performance Specifications 1.0 Door Hardware Briton Levers, Escutcheon s & Bathroom
More informationLoss Prevention Standards
Introduction Fire compartmentation is an essential part of an effective fire safety design of a building. The primary objective of fire compartmentation or passive fire protection is to prevent a building
More informationTitle: WF Assessment Report No B. Prepared for: CHEMOLLI S.A.S. di Eros Chemolli & C. Via Fitta, Arco (TN), Italy
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: The Fire Resistance Performance
More informationFirst Aspen Federal Regulation Set: K LSC 2000 Health Existing
First Aspen Federal Regulation Set: K 01.01 LSC 2000 Health Existing K 0000 Title CFR Type INITIAL COMMENTS Memo K 0011 If the building has a common wall with a nonconforming building, the common wall
More informationCERTIFICATE OF APPROVAL No CF 5507 CONSORT ARCHITECTURAL HARDWARE LTD
1 CERTIFICATE OF APPROVAL No CF 5507 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of 29-31 Lower Loveday
More informationCERTIFICATE OF APPROVAL No CF 392 EXIDOR LIMITED
CERTIFICATE OF APPROVAL No CF 392 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Progress Drive, Cannock,
More informationDesign Guidelines Fire Safety in New and Refurbished Buildings
Design Guidelines Fire Safety in New and Refurbished Buildings Introduction All major new or refurbishment projects must comply with the Technical Standards (Scotland) Regulations as a matter of course.
More informationCERTIFICATE OF APPROVAL No CF 391 UNION ARCHITECTURAL HARDWARE
CERTIFICATE OF APPROVAL No CF 391 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of School Street, Willenhall,
More informationLife Safety and Fire Resistant Glazing Systems
Life Safety and Fire Resistant Glazing Systems Kevin Hulin CEO, Mann McGowan Group Agenda GGF Introduction GGF and The Fire Resistant Glazing Group (FRGG) Fire Testing, Reports, Assessments and 3rd Party
More informationCHAPTER 7 ALTERATIONS LEVEL
CHAPTER 7 ALTERATIONS LEVEL 2 SECTION 701 GENERAL 701.1 Scope. Level 2 alterations as described in Section 404 shall comply with the requirements of this chapter. Exception: Buildings in which the reconfiguration
More informationIronmongery Schedule. Prepared for: ABC Architects Project Title: Commercial Vertcial Market Our Ref: ABC123
Ironmongery Schedule Prepared for: ABC Architects Project Title: Commercial Vertcial Market Our Ref: ABC123 Ironmongery Performance Specifications 1.0 Door Hardware Briton Levers, Escutcheon s & Bathroom
More informationTransShield ACS Fully Automated Intumescent Fire and Sliding Plate Smoke Damper
September 2010 TransShield ACS TransShield ACS Fully Automated Intumescent Fire and Sliding Plate Smoke Features and Design Guide Slimline non-vision intumescent fire and smoke damper with unique sliding
More informationPractice Guidee No.1. of the
Intumescent Fire Seals Association Good Practice Guide No. 1 The Fire Risk Assessors Good Practice Guidee No.1 Guidance to risk assessors in respect of the use of intumescent door sealss THE HOME OF REACTIVE
More informationCERTIFICATE OF APPROVAL No CF 117 DORMA UK LTD
CERTIFICATE OF APPROVAL No CF 117 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Wilbury Way, Hitchin,
More informationNFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES
NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES Sharon S. Gilyeat, P.E., Principal Koffel Associates, Inc. www.koffel.com sgilyeat@koffel.com Expertly Engineering Safety From Fire
More informationCERTIFICATE OF APPROVAL No CF 5657 UNION ARCHITECTURAL HARDWARE
CERTIFICATE OF APPROVAL No CF 5657 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of School Street, Willenhall,
More informationPanic Exit Devices. ASSA ABLOY, the global leader in door opening solutions
ASSA ABLOY, the global leader in door opening solutions Contents 9000 Series Panic Exit Devices - Introduction 2 9000/9100 Series Rim Type Panic Exit Device 4 9300/9400 Series Vertical Type Panic Exit
More informationHD72 Euro Profile Mortice Lockcase. The high performance lock that goes beyond the standard. ASSA ABLOY, the global leader in door opening solutions
HD72 Euro Profile Mortice Lockcase The high performance lock that goes beyond the standard ASSA ABLOY, the global leader in door opening solutions UNION Trusted by professionals From our first lock made
More informationUNIVERSITY OF ROCHESTER DESIGN STANDARDS FEBRUARY 2005MARCH 2007
SECTION 08710 - DOOR HARDWARE 1.1 SUMMARY A. Door hardware required for swinging doors. No pocket or folding doors permitted at U of R. 1.2 SUBMITTALS A. Hardware Schedule: To be coordinated with doors,
More informationIronmongery Schedule. Prepared for: ABC Architects Project Title: Hospitality Vertcial Market Our Ref: ABC123
Ironmongery Schedule Prepared for: ABC Architects Project Title: Hospitality Vertcial Market Our Ref: ABC123 Ironmongery Performance Specifications 1.0 Door Hardware Briton Levers, Escutcheon s & Bathroom
More information