WARNING: DOWNLIGHTS MUST BE FITTED CORRECTLY IN FIRE RATED CEILINGS

Size: px
Start display at page:

Download "WARNING: DOWNLIGHTS MUST BE FITTED CORRECTLY IN FIRE RATED CEILINGS"

Transcription

1 WARNING: DOWNLIGHTS MUST BE FITTED CORRECTLY IN FIRE RATED CEILINGS Requirement I: The fire protection rating of the downlight must be the same as, or exceed that of the ceiling. Ceilings range from 30 to 90 minutes so selecting a downlight rated for 90 minutes or more will meet all requirements. Note: Wholesalers must ensure that the product they supply is Fit for purpose. BS476 Part 23 the standard for fire integrity requires openings to be sealed by an intumescent barrier when exposed to sufficient heat. Fire Rated Ceiling Section 11 of the approved document B, The building regulations 2000 states that a fire barrier will be fitted to the opening to seal any gap between the ceiling material and the fitment*. This is required to be: Ceramic resin fire mortar or intumescent mastic. Fire Rated Ceiling * This requirement is adopted under the IEE Wiring Regulations 16/17th Editions and BS7671:2001 (Section ). Failure to comply compromises the fire rating of the ceiling and can lead to civil and criminal liability where a ceiling fails to protect property and life. NOTE: Under the european supply of goods directives, wholesalers and wholesalers staff not ensuring that the correct prodcut is supplied or offering incorrect advice on installation may share this liability at both company and personal level. Section 11 of approved ducument B, The building regulations 2000 is headed: Protection of openings and fire stopping. NOW COMPLIANT TO 30,60 & 90 MINUTES FIRE PROTECTION FEATURING OUR ENERGY SAVING RANGE FIRE RATED RANGE Emcogroup have 3 ranges of 100 minute fire rated downlights. Our standard range are the readily available, popular, steel and die cast fittings. The Atlantic range consists of a fire rated canister to which a variety of accessories can be added to suit your design, available in low voltage, 230v GU10, which accept PL7/9/11/15 W lamps as well as standard GU10, lastly the 35w Britespot version for commercial applications. The Pacific range, 18 & 26w PL-T version also accepts a variety of accessories to suit your design. All fire rated products tested by Warrington Fire or Darchem (Esterline). Certificates kept on file. Lastly we have a range of firehoods available allowing a wider choice of light fittings to be used.

2 LEGISLATION AND CERTIFICATION Fire Safety Approved Document B is concerned with Fire Safety and Section 11 of this document relates to - Protection of Openings and Fire Stopping. Specifically Clause 11.2 states that - If a fire separating element is to be effective, then every joint, or imperfection of fit, or opening to allow services to pass through the element, should be adequately protected by sealing or fire-stopping so that the fire resistance of the element is not impaired. All of the Emcogroup Fire Rated products achieved 30,60 & 90 minutes. Surpassing BS 476 part 20 & 21. Acoustic Performance Testing Approved Document E is concerned with resistance to the passage of sound. The intergrity of a structures sound attenuation as determined in this document, must not be compromised by the fitting of downlights. In these tests the level of both airbourne and impact noise through a ceiling/floor is measured both before and after the fitting of the downlights. The requirement is that the transmission of sound must not increase by more that 1db (decibel). In all cases of the downlights tested, there was no increase in sound transmitted and in some cases reduced by up to one decibel. All of the Emcogroup fire rated products comply and some even surpass BS EN ISO and -2:1997. Electrical Safety Regulation 4(2) states that, on completion of the work, the building should be no worse in terms of the level of compliance with other applicable Parts of Schedule 1 to the Building Regulations. For example, one or more perforations of a ceiling lining beneath a floor made to accommodate recessed lighting or similar fittings - may have an adverse effect on that floor s performance to it s resistance to fire and sound penetraction. The Emcogroup fire rated downlight were to be tested to 30, 60 & 90 minutes but were found to be resisting fire for up to 100 minutes. Complies With Approved Document Part C Where shown downlights are suitable for use to meet the requirements of building regulation approved document C - moisture and airflow. The regulation requires that a sufficient air-tight seal is provided to avoid condensation forming in cold, unvented roof spaces. Total leakage should not exceed 0.06m 3 (Hr per metre 2 tested at 2 pa (pascales) Part L1 & L2 The Pacific range fitting meets the requirements of Part L of building regulations relating to the installation of low energy luminaries. Complies with Scottish building regulations, section 2 (fire), section 3 (air movement) and section 5 (noise).

3 LEGISLATION AND CERTIFICATION The Wiring Regulations Section 527 of wiring Regulations (BS 7671:2008) relates to - selection and erection to minimise the spread of fire Clause states - The risk of the spread of fire shall be minimised by the selection of appropriate materials and erection in accordance with section 527. Clause states - Where a wiring system passes through elements of building construction... the opening remaining after the passage of the wiring system shall be sealed according to the degree of fire resistance required of the element concerned. Clearly where a hole is cut into a fire resistant ceiling to mount a downlight, the electrical contractor must ensure that the fire integrity of the ceiling is maintained. This can be ensured by installing an Emcogroup fire rated downlight. BS 7671: 2008 The 17th Edition of the IEE wiring regulations (BS 7671: 2008) was published in January 2008 and came into effect from 1st July All commercial, domestic and industrial wiring installations must be designed, constructed, inspected, tested and certified to meet the requirements of BS 7671: 2008 BS : 1987 Fire tests on building materials and structures BS476 PART 20 & 21 A number of test standards are used to show the performance of product/constructions under fire situations. The BS 476 fire test on building materials and structures, the method for determination of the fire resistance of elements of contruction (Part 20) and loadbearing elements of construction (Part 21). The Emcogroup fire rated range has been tested and surpasses all of the requirements of BS Parts 20 & 21. PACIFIC Compact fluorescent Low voltage Mains voltage Britespot 18w PL-T Lamp 26w PL-T Lamp 12v GX5.3/MR16 20w dichroic/reflector lamp 12v GX5.3/MR16 35w dichroic/reflector lamp 12v GX5.3/MR16 50w dichroic/reflector lamp LED version 230v 7/9/11/13/15w GU10 compact fluorescent lamp 230v GU10 Par16 50w reflector lamp 230v GU10 Par16 35w reflector lamp LED version 35w Sylvania Britespot

4 ABOUT FIREBLOK The popularity of downlights in dwellings has had a much bigger effect than just transforming how modern lighting looks. Twenty years ago a typical room would have a plaster board ceiling with plaster skim and one or two ceiling roses to provide light. The plaster and board provided effective heat and fire integrity, often exceeding thirty minutes of fire containment, even though temperatures would exceed 1000ºC. Today, that same room may have twenty or more downlights each providing a 70 to 120mm diameter hole through which flame and high temperatures gain immediate access to the underside of the wooden or chipboard floor of the room above. This has drastically reduced the ability of ceiling surfaces to contain fire and allows fire to travel vertically more quickly. As most houses have bedrooms on the upper floor, the increased danger to occupants is obvious. Fire rated downlights have been introduced to maintain the fire integrity of ceiling surfaces but these products have also changed the liability that the installer is now exposed to. With these products the installer is taking on life-time liability for the fire integrity of the structure under the Building Regulations. The installer is completely responsible for the installation throughout its lifetime Products that have been tested within the specifications of BS476 by a UKAS Accredited Test House will bear the accreditation mark in figure 2. Products may claim to have been tested to this standard but only the accreditation mark on the product, or its packaging, provides assurance of compliance. As installers may be held to account for their work where a fire event occurs for many years to come, using accredited products proves that the installer has used reasonable care to ensure their installation complies with the regulations. APERTURES AND FIRE STOPPING The Building Regulations Section 11 of Approved Document B Building Regulation 2000 requires the installer to fit a fire stopping barrier to the aperture between the downlight and the ceiling surface in intumescent material, ceramic resin or fibreglass fire blanket. To save installers time, all of Emcogroup s fire rated downlights are supplied with a fire barrier either pre-fitted between the rim and the underside of the ceiling surface (figure 3) or as an item to be fitted on the canister side to seal against the inside edge of the aperture cut out (figure 4). Intumescent material expands when exposed to heat to fill gaps and irregularities without pressure so that there is no risk of any components dislodging during a fire event. Failure by an installer to fit fire stopping is a blatant breach of regulations and compromises the fire integrity of the ceiling structure. This could lead to civil and criminal proceedings where there is a premature fire integrity failure. BS476 YOUR PEACE OF MIND Figure 1 shows in red the room temperatures specified during a BS476 test, a test which simulates a fire event in a typical room. The green line shows the temperature at which aluminium is molten (600ºC). All of Emcogroup s products featuring an aluminium trim or front rely on the steel canister for fire resistance and integrity as the aluminium fronts fall away within 25 minutes of the test commencing. Figure 5 shows the steel lip arrangement which locates to the underside of the ceiling surface to provide resistance against the fixing springs once the aluminium front has detached in a fire event. Emcogroup s downlights use steel (1500ºC melting point) with either welded steel parts or steel thread and bolt in the construction of the fire resisting canister. Our research found that aluminium components and rivets failed rapidly in fire testing which can lead to the downlight dis-assembling within the ceiling void before achieving the required duration.

5 MINUTE FIRE PROTECTION Further testing has been carried out on our fire rated range and we are pleased to announce that all of the downlights have been independently tested for 30, 60 and 90 minute fire rated ceilings. What does this mean to you? The ceiling type constructed depends on the type of building under construction. The ceilings have to be constructed to provide protection to occupied floors above and also to adjacent buildings for a duration as specified in Building Regulations Part B. 600mm joist centres 600mm joist centres 450mm joist centres Single layer 12.5mm plasterboard Double layer 15mm plasterboard Double layer 15mm plasterboard 30 minutes A typical application is for a residential dwelling property of two stories. 60 minutes A typical application is for a commercial property with residential units above. House and residential units with floors between 5M - 10M above ground. 90 minutes A typical application is greater than 10M or residential units over 30M above ground level. PLEASE REFER TO BUILDING REGULATIONS: PART B FOR FULL DETAILS ON APPLICATION OF CEILING RATINGS. THE TECHNICAL THEORY BEHIND FIREBLOK - standard range The new Emcogroup fire rated downlighters are manufactured to and surpass the Positioning nut Pre-loaded rotating shutter requirements of the building regulations of building regulations Approved Document B and fire tested in accordance with BS 476 PT 20 & 21. Ventilation hole Spring Body With this new technology we can offer a recessed fire rated downlight which despenses with the requirements of the intumescent seal. In the event of the ambient temperature rising to 300ºC a thermal link releases a pre-loaded shutter to rotate within Open Support body Thermal link Closed 0.5 seconds closing the ventilation holes to prevent fire spreading. Normally the ventilation holes on the body and rotating shutter are opened. When temperature rises to 300º - 350ºC, the ventilation holes will be closed.

Title: Indicative fire test. WF Report No: /A. Prepared for: Hoody Speaker Hoods Ltd

Title: Indicative fire test. WF Report No: /A. Prepared for: Hoody Speaker Hoods Ltd Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: Indicative fire test WF Report

More information

New 10YR. The market leading range of fire-rated LED downlights. Introducing FGLED10 WARRANTY

New 10YR. The market leading range of fire-rated LED downlights. Introducing FGLED10 WARRANTY New Introducing FGLED10 The market leading range of s 10YR E X T E N D E D WARRANTY 10 year domestic and 5 year commercial warranty. Register at JCC.co.uk/warranty Service & support If you have any questions

More information

The Radiators With Brains

The Radiators With Brains Electrical Storage Radiators of the NEXT Generation Based on established German Technology..fine tuned By Cornish Engineering The Radiators With Brains Report of independent efficiency and electricity

More information

IS-ORANGE Envirograf. Orange Book. Ventilation. T +44 (0) F +44 (0)

IS-ORANGE Envirograf. Orange Book. Ventilation. T +44 (0) F +44 (0) IS-ORANGE-01-15 Orange Book Ventilation Envirograf Innovators - Developers - Manufacturers Passive Fire Prevention Products T +44 (0) 1304 842 555 F +44 (0) 1304 842 666 sales@envirograf.com www.envirograf.com

More information

Loss Prevention Standards

Loss Prevention Standards Introduction Fire compartmentation is an essential part of an effective fire safety design of a building. The primary objective of fire compartmentation or passive fire protection is to prevent a building

More information

Welcome to the. Firestop Seminar. Hilti Technical and Engineering Support

Welcome to the. Firestop Seminar.  Hilti Technical and Engineering Support Welcome to the Firestop Seminar www.hilti.co.uk/technical Hilti Technical and Engineering Support 1 Agenda 1. Passive Fire Protection a) The Importance of Firestop b) What are the Regulations c) Test Criteria

More information

Schedule of works required for Fire Protection in a 2 Storey semi-detached/terraced house

Schedule of works required for Fire Protection in a 2 Storey semi-detached/terraced house Schedule of works required for Fire Protection in a 2 Storey semi-detached/terraced house THIS DOES NOT COVER 3 STOREY PROPERTIES you must consult with the Private Sector Housing Team on any 3 storey property.

More information

1.4 Provide and fix the following ironmongery.

1.4 Provide and fix the following ironmongery. Schedule of works required for Fire Protection in a first & second floor purpose built masionette above shops where the exit door is at first floor level. THIS DOES NOT COVER NORMAL 3 STOREY PROPERTIES

More information

FIRE SAFETY MANAGEMENT PROTOCOL FIRE DOORS & FIRE DOOR ASSEMBLIES

FIRE SAFETY MANAGEMENT PROTOCOL FIRE DOORS & FIRE DOOR ASSEMBLIES FIRE SAFETY MANAGEMENT PROTOCOL FIRE DOORS & FIRE DOOR ASSEMBLIES This is a new procedural document, please read in full. Did you print this document yourself? The Trust discourages the retention of hard

More information

Fire-rated downlights

Fire-rated downlights 01 Fire-rated downlights NEW NEW NEW 15 HYBRID9 & LEVLINK 19 HYBRID7 21 HYBRID7 OVERBEZEL 23 FGLED10 25 FGLED6 27 FGLED6 TILT 28 FGLED6 SQUARE 31 FGLED3 NEW 32 FGLED3 TILT 34 FGLED3 SQUARE 35 FGLED ANTI-GLARE

More information

- CONSTRUCTION FIRE SAFETY STANDARDS

- CONSTRUCTION FIRE SAFETY STANDARDS SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Construction Planning All construction sites shall plan and sequence their construction activities to ensure the early installation and operation of permanent

More information

Agrément Certificate 92/2841 website: Product Sheet 1

Agrément Certificate   92/2841 website:   Product Sheet 1 Lorient Polyproducts Ltd Endeavour House Fairfax Road Heathfield Industrial Estate Newton Abbot Devon TQ12 6UD Tel: 01626 834252 Fax: 01626 833166 Page 1 of 1 Agrément Certificate e-mail: mktg@lorientuk.com

More information

ELECTRICAL FIRE STOPPING SOLUTIONS

ELECTRICAL FIRE STOPPING SOLUTIONS ELECTRICAL FIRE STOPPING SOLUTIONS TENMAT is a leading manufacturer of unique, high performance intumescent materials and solutions with over 30 years of passive fire protection experience. TENMAT manufacture

More information

Others ( 50Hz areas ) ADVANCED SUBJECT DATE: May-08 PRODUCT NEWS. Advanced Product News: Launching of New KPI-(502~2002)E1E & KPI-3002H1E units

Others ( 50Hz areas ) ADVANCED SUBJECT DATE: May-08 PRODUCT NEWS. Advanced Product News: Launching of New KPI-(502~2002)E1E & KPI-3002H1E units PAGE 1/32 Summary This document (_r2) updates the previous one (_r1) issued on Mar 08. Revised items are identified by using: 2 (1 Location). This Advanced Products News introduces the new line-up of KPI-(502~2002)E1E

More information

CONCEALED CEILING SYSTEMS INSTALLATION GUIDE

CONCEALED CEILING SYSTEMS INSTALLATION GUIDE CONCEALED CEILING SYSTEMS INSTALLATION GUIDE rondo key-lock CONCEALED CEILING SYSTEMS VARIOUS KEY-LOCK COMPONENTS INTRODUCTION Whether you re looking to direct fix or fully suspend your plasterboard ceiling,

More information

CMX-S. Company name: Contact: Tel: Central Mechanical Extract Ventilation (cmev) appliance. Installation and Operating Instructions

CMX-S. Company name: Contact: Tel:   Central Mechanical Extract Ventilation (cmev) appliance. Installation and Operating Instructions V EN T IL AT ION V EN T IL AT ION CMX-S Installer contact details: Company name: Contact: Tel: Email: Central Mechanical Extract Ventilation (cmev) appliance Installation and Operating Instructions These

More information

STATEMENT OF SOLID FUEL APPLIANCE PERFORMANCE

STATEMENT OF SOLID FUEL APPLIANCE PERFORMANCE STATEMENT OF SOLID FUEL APPLIANCE PERFORMANCE Name of Appliance Name and Address of manufacturer Type of appliance eg 'freestanding roomheater' Minimum distance to combustibles Minimum distance from combustibles

More information

Ceiling Sweep Fan Assembly Instructions

Ceiling Sweep Fan Assembly Instructions Ceiling Sweep Fan Assembly Instructions CSF Series Installation Note: This fan must be installed by a licenced electrical contractor Improperly installed ceiling sweep fans can be dangerous and expensive

More information

Smoke extraction duct of sheet steel

Smoke extraction duct of sheet steel Smoke extraction duct of sheet steel The accessories that are available, as for example inspection openings, steel grilles, plenum boxes, ceiling diffusers, splitter attenuators, bends, tees and connecting

More information

Mechanical Ventilation with Heat Recovery: Designing and implementing a robust and effective ventilation system

Mechanical Ventilation with Heat Recovery: Designing and implementing a robust and effective ventilation system Viewpoint August 2012 Mechanical Ventilation with Heat Recovery: Designing and implementing a robust and effective ventilation system Dr Sarah Price and Helen Brown Summary Mechanical Ventilation and Heat

More information

Green Line CMX. Central Mechanical Extract Ventilation (cmev) appliance. Installation and Operating Instructions. Model: CMX

Green Line CMX. Central Mechanical Extract Ventilation (cmev) appliance. Installation and Operating Instructions. Model: CMX Green Line CMX Central Mechanical Extract Ventilation (cmev) appliance Installation and Operating Instructions Model: CMX These instructions must be given to the householder DO NOT SWITCH OFF THE UNIT

More information

Life Safety and Fire Resistant Glazing Systems

Life Safety and Fire Resistant Glazing Systems Life Safety and Fire Resistant Glazing Systems Kevin Hulin CEO, Mann McGowan Group Agenda GGF Introduction GGF and The Fire Resistant Glazing Group (FRGG) Fire Testing, Reports, Assessments and 3rd Party

More information

FIREPRO SoftSeal System

FIREPRO SoftSeal System PENETRATION AND AND LINEAR LINEAR JOINTS JOINTS APRIL JULY 2015 FIREPRO SoftSeal System www.rockwool.co.uk PENETRATION AND LINEAR JOINTS FIREPRO Range The ROCKWOOL FIREPRO SoftSeal system is part of this

More information

Guide to sollysta Wiring Accessories

Guide to sollysta Wiring Accessories Guide to sollysta Wiring Accessories Introduction This guide expands upon some of the requirements found in the 17 th Edition of the IEE Wiring Regulations and Building Regulations and how they affect

More information

BUILDING STANDARDS SUPPORTING GUIDANCE DOMESTIC VENTILATION

BUILDING STANDARDS SUPPORTING GUIDANCE DOMESTIC VENTILATION BUILDING STANDARDS SUPPORTING GUIDANCE DOMESTIC VENTILATION 2 ND EDITION 1 Contents 1. Purpose of this document 3 Page 2. Ventilation 4 3. Purpose provided ventilation 6 4. Natural ventilation- windows,

More information

TransShield ACS Fully Automated Intumescent Fire and Sliding Plate Smoke Damper

TransShield ACS Fully Automated Intumescent Fire and Sliding Plate Smoke Damper September 2010 TransShield ACS TransShield ACS Fully Automated Intumescent Fire and Sliding Plate Smoke Features and Design Guide Slimline non-vision intumescent fire and smoke damper with unique sliding

More information

THE HOME OF REACTIVE PROTECTION SYSTEMS

THE HOME OF REACTIVE PROTECTION SYSTEMS THE HOME OF REACTIVE PROTECTION SYSTEMS CONTENTS Page Introduction 1 Role of air transfer grilles 1 Definitions and functions 1 Fire performance requirements 2 Varieties of air transfer grilles 3 Recommended

More information

TransShield ACS Fully Automated Intumescent Fire and Sliding Plate Smoke Damper

TransShield ACS Fully Automated Intumescent Fire and Sliding Plate Smoke Damper Fully Automated Intumescent Fire and Sliding Plate Smoke www.actionair.co.uk sales@actionair.co.uk Introduction The TransShield ACS fully automated intumescent fire and sliding plate smoke dampers are

More information

SAC 100 Automatic Smoke Curtain System. - Specifier Information -

SAC 100 Automatic Smoke Curtain System. - Specifier Information - SAC 100 Automatic Smoke Curtain System - Specifier Information - CONTENTS 1. Introduction Page 3 2. Construction and Method of Operation Page 5 3. Performance 3.1. Resistance to Fire/Heat Page 6 3.2. Deflection

More information

Product Compliance Andy Guest

Product Compliance Andy Guest Product Compliance Andy Guest EDA Forum November 2015 www.thelia.org.uk What do we mean by compliant in lighting? How do we know products are compliant? Its CE Marked That means its OK doesn t it? What

More information

Contents Page No. Page 1 of Introduction Specimen verification Description of supporting constructions...

Contents Page No. Page 1 of Introduction Specimen verification Description of supporting constructions... Contents Page No Page 1 of 14... 1 1 Introduction... 3 2 Specimen verification... 3 3 Description of supporting constructions... 3 4 Description of specimen... 3 4.1 Air transfer grille blocks... 3 5 Test

More information

Fire Protection. Intumescent fire and smoke seals for door assemblies

Fire Protection. Intumescent fire and smoke seals for door assemblies Fire Protection Intumescent fire and smoke seals for door assemblies Intumescent Seals Fire Protection Quality you can trust Exitex offer a wide range of fully tested intumescent strips, glazing seals

More information

Maintenance. Why Maintain Fire Doors? Regulations

Maintenance. Why Maintain Fire Doors? Regulations Introduction Fire doors are commonly overlooked as an essential part of a commercial or public building maintenance regime. However, fire doors help sub-divide a building into compartments, slowing down

More information

INTEGRATED LED DOWNLIGHT IP65 FIRE & ACOUSTIC RATED WITH FLEXI-DRIVER

INTEGRATED LED DOWNLIGHT IP65 FIRE & ACOUSTIC RATED WITH FLEXI-DRIVER INTEGRATED LED DOWNLIGHT IP65 FIRE & ACOUSTIC RATED WITH FLEXI-DRIVER INTEGRATED LED DOWNLIGHT IP65 FIRE & ACOUSTIC RATED WITH FLEXI-DRIVER Features 550lm output (4000K) Up to 70 lm/w Integrated LED driver

More information

Code of Practice - Ventilation- Mechanical Extract Ventilation (MEV) + Mechanical Ventilation with Heat Recovery (MHVR)

Code of Practice - Ventilation- Mechanical Extract Ventilation (MEV) + Mechanical Ventilation with Heat Recovery (MHVR) Code of Practice - Ventilation- Mechanical Extract Ventilation (MEV) + Mechanical Ventilation with Heat Recovery (MHVR) Contractors Requirements & Competency This section outlines the general Standards

More information

Intumescent Fire Dampers

Intumescent Fire Dampers Ph 1300 858 010 Intumescent Fire Dampers Fire resistant walls and floors in a building play an important part in containing the spread of fire and smoke. However, a building also needs to be well ventilated

More information

- CONSTRUCTION FIRE SAFETY STANDARDS

- CONSTRUCTION FIRE SAFETY STANDARDS SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Hot Work Permits All construction sites shall implement a system of Hot Work Permits for all work activities that generate heat, sparks or flames. All of the

More information

Fact File 75. Published Document PD CEN/TS 54-32:2015 Fire detection and fire alarm systems

Fact File 75. Published Document PD CEN/TS 54-32:2015 Fire detection and fire alarm systems Fact File 75 Published Document PD CEN/TS 54-32:2015 Fire detection and fire alarm systems Published Document PD CEN/TS 54-32:2015 Fire detection and fire alarm systems INTRODUCTION... 3 BACKGROUND...

More information

TT302 (200W) Wireless receiver Pull cord Dimmer

TT302 (200W) Wireless receiver Pull cord Dimmer TT302 (200W) Wireless receiver Pull cord Dimmer Product Description The TT302 Wireless receiver allows you to convert a standard 1 way light switch or pull cord in to a taptile compatible Dimmer circuit

More information

Installation and Maintenance

Installation and Maintenance 38 70 = 100 410 = 60 1.0 INTRODUCTION MRXBOXAB-ECO4-AESW (Standard Unit) MRXBOXAB-ECO4-AEOHSW (Opposite hand Unit) Mechanical Ventilation Units with Heat Recovery for Wall Mounting Installation and Maintenance

More information

WARRES No Page 1 of 27. Fire Resistance Test Generally In Accordance With BS 476: Part 22: 1987, Clause 5, on an Insulated Fabric Barrier

WARRES No Page 1 of 27. Fire Resistance Test Generally In Accordance With BS 476: Part 22: 1987, Clause 5, on an Insulated Fabric Barrier Page 1 of 27 Fire Resistance Test Generally In Accordance With BS 476: Part 22: 1987, Clause 5, on an Insulated Fabric Barrier Test Sponsor Saveguard (UK) Limited Warrington Fire Research Centre Ltd.,

More information

Supplement A- Improving Forced Air Heating Systems

Supplement A- Improving Forced Air Heating Systems Supplement A Improving Forced Air Heating Systems The Challenge Recent research and testing of new homes in the Pacific Northwest and across the United States shows the importance of a properly installed

More information

FIREMASTER ACTIVE FIRE CURTAIN BARRIER ASSEMBLIES LEADING THE WAY IN FIRE PROTECTION

FIREMASTER ACTIVE FIRE CURTAIN BARRIER ASSEMBLIES  LEADING THE WAY IN FIRE PROTECTION FIREMASTER ACTIVE FIRE CURTAIN BARRIER ASSEMBLIES WWW.COOPERSFIRE.COM LEADING THE WAY IN FIRE PROTECTION DESIGN SOLUTIONS THAT WORK FOR YOU CASE STUDY: FORTNUM & MASON LONDON UK Active Fire Curtain Barrier

More information

CERTIFICATE OF FIRE APPROVAL

CERTIFICATE OF FIRE APPROVAL LR2009.030. CERTIFICATE OF FIRE APPROVAL This is to certify that The product(s) detailed below will be accepted for compliance with the applicable Lloyd s Register Rules and Regulations for use on offshore

More information

The Association for Specialist Fire Protection

The Association for Specialist Fire Protection The Association for Specialist Fire Protection Passive Fire Protection Understanding the Risks! Wilf Butcher Chief Executive Officer Association for Specialist Fire Protection How does the dictionary define

More information

FIRE PROTECTION INNOVATORS IN CABLE MANAGEMENT

FIRE PROTECTION INNOVATORS IN CABLE MANAGEMENT FIRE PROTECTION INNOVATORS IN CABLE MANAGEMENT Power Data Control Ventilation of cables Installed cost reduction Proven suitability Mechanical protection Free draining EMC protection Adaptability Bypasses

More information

Title: Room-sealed fanned draught flue systems concealed within voids

Title: Room-sealed fanned draught flue systems concealed within voids Date issued: 11 th June 2007 Author: Jamie Cooper Status: Current Reviewer: 11 th June 2008 Introduction Title: Room-sealed fanned draught flue systems concealed within voids With the advent of modern

More information

The Passive Fire Protection Handbook

The Passive Fire Protection Handbook Useful Contact Numbers Promat Technical Services Department Telephone: 01344 381 400 Fax: 01344 381 401 E-mail: technicaluk@promat.co.uk Promat Marketing Services Department Telephone: 01344 381 350 Fax:

More information

Installation and Maintenance

Installation and Maintenance 1.0 INTRODUCTION MRXBOXAB-ECO-LP1 (Standard Unit) MRXBOXAB-ECO-LP1-OH (Opposite Hand Unit) Mechanical Ventilation Unit with Heat Recovery for Ceiling Void Mounting Installation and Maintenance The LP1

More information

The Association for Specialist Fire Protection. Understanding Best Practice in passive fire protection

The Association for Specialist Fire Protection. Understanding Best Practice in passive fire protection The Association for Specialist Fire Protection Understanding Best Practice in passive fire protection Niall Rowan, Technical Officer Association for Specialist Fire Protection The Association for Specialist

More information

Sargasso Range. Installation manual. Sargasso A. Issue 001 January 2018 ENGLISH UK IRL SmithsEP.co.uk

Sargasso Range. Installation manual. Sargasso A. Issue 001 January 2018 ENGLISH UK IRL SmithsEP.co.uk Sargasso Range Installation manual Sargasso A Issue 001 January 2018 ENGLISH UK IRL SmithsEP.co.uk Contents Introduction 2 Symbols used in this guide 2 Declaration of conformity 2 Important safety and

More information

XB-EFA-8L-BK & XB-EFA-8R-BK

XB-EFA-8L-BK & XB-EFA-8R-BK Supply & Extract Ventilation Unit with Heat Recovery The EMC Directive 2014/30/EU The Low Voltage Directive 2014/35/EU The information contained in this document provides details of installation, operation

More information

fire resistance testing

fire resistance testing fire resistance testing Chiltern International Fire and Chiltern Dynamics, as part of the BM TRADA Group, have more than 70 years experience in providing practical solutions in the field of testing and

More information

FIREMASTER PLUS 2 TENABLE ZONE / HEAT PROTECTION ACTIVE FIRE CURTAIN BARRIER ASSEMBLIES LEADING THE WAY IN FIRE PROTECTION

FIREMASTER PLUS 2 TENABLE ZONE / HEAT PROTECTION ACTIVE FIRE CURTAIN BARRIER ASSEMBLIES  LEADING THE WAY IN FIRE PROTECTION FIREMASTER PLUS 2 TENABLE ZONE / HEAT PROTECTION ACTIVE FIRE CURTAIN BARRIER ASSEMBLIES WWW.COOPERSFIRE.COM LEADING THE WAY IN FIRE PROTECTION MEANS OF ESCAPE PROTECTION CASE STUDY: SSE HYDRO GLASGOW UK

More information

Airflow. Add a little Sunshine to your bathroom

Airflow. Add a little Sunshine to your bathroom Airflow Add a little Sunshine to your bathroom clipsal.com Airflow Sunshine 2 x 275W heat-lamp model 6600A The 6600A is suitable for small bathrooms and en suites with ceilings of average height 2.7 metres

More information

Installation and Maintenance

Installation and Maintenance 1.0 INTRODUCTION MRXBOXAB-ECO-LP1SW (Standard Unit) MRXBOXAB-ECO-LP1-OHSW (Opposite Hand Unit) Mechanical Ventilation Unit with Heat Recovery for Ceiling Void Mounting Installation and Maintenance The

More information

BACKGROUND VENTILATION SOLUTIONS FOR DOMESTIC BUILDINGS

BACKGROUND VENTILATION SOLUTIONS FOR DOMESTIC BUILDINGS ...................................... CI/SfB (57) Uniclass L753 July 2015 BACKGROUND VENTILATION SOLUTIONS FOR DOMESTIC BUILDINGS................................................................... ...................................................................................

More information

60cm Canopy Extractor

60cm Canopy Extractor 60cm Canopy Extractor LAM2300 User & Installation Guide Dear Customer, Congratulations on your choice of domestic appliance which has been designed to give you excellent service. The user manual will help

More information

Emergency Evacuation Lighting Inspection & Maintenance

Emergency Evacuation Lighting Inspection & Maintenance Emergency Evacuation Lighting Inspection & Maintenance Got Questions? We re here to help 1300 038 847 Why Test Emergency Lighting Online Enquiry Australian Standard AS/NZS 2293.2 1995 relates to inspection

More information

Water Heating UK 14 th May 2016

Water Heating UK 14 th May 2016 Water Heating UK 14 th May 2016 Hot Water Storage Systems for Heating by Solid Fuel Appliances - General Requirements and Test Methods 1.0 Introduction All hot water storage systems installed in the UK

More information

Aluminium range of condensing boilers. Works every time. Designed to meet carbon reduction targets. Lifetime service and support

Aluminium range of condensing boilers. Works every time. Designed to meet carbon reduction targets. Lifetime service and support Aluminium range of condensing boilers Outputs from 30kW to 600kW Designed to meet carbon reduction targets Lifetime service and support Works every time. www.pottertoncommercial.co.uk Aluminium range of

More information

ART cm Island Curved Glass

ART cm Island Curved Glass ART28101 90cm Island Curved Glass [01] x 1 [02] x 1 [03] x 1 [04] x 1 [05] x 4 [06] x 1 [07] x 1 [08] x 1 [09] x 4 [10] x 4 [11] x 1 [12] x 4 (6x70mm) [13] x 4 (6.3x17x2mm) [14] x 8 (4x12x1mm) [15] x 4

More information

Certificate No: EWS534

Certificate No: EWS534 Certificate No: EWS534 Plumis Automist Smartscan Hydra Description of Product This is an assessment of the Plumis Automist multiroom Smartscan Hydra targeted fire suppression system. The system utilises

More information

C08. S05. P02 P05 Decorative effects

C08. S05. P02 P05 Decorative effects ! This section includes updated information, added since it was first published in December 2015. Last updated 16/12/2016 C08. S05. P02 P05 Decorative effects Including C08. S01. P02 Finishes introduction

More information

Attic ventilation options can be confusing to roofing contractors

Attic ventilation options can be confusing to roofing contractors 30 www.professionalroofing.net JANUARY 2014 Attic ventilation options can be confusing to roofing contractors by Joan P. Crowe, AIA Attic ventilation can be a confusing, complex subject and is the topic

More information

Legal Requirements. There is no general legal requirement to install sprinklers. in places of work

Legal Requirements. There is no general legal requirement to install sprinklers. in places of work 01 A sprinkler system is a pipework distribution system charged with water, with a network of heatsensitive sprinkler heads supplied via a tank/reservoir or a water main. If the temperature rises above

More information

SYSTEM MANUAL Description

SYSTEM MANUAL Description SYSTEM MANUAL Description PUCK is a revolutionary fire suppression system offering discrete protection coupled with industry leading pricing, efficient system design and easy install. PUCK s lightweight

More information

M07. Wunda Premium Manifold. Before you start: Check the contents THE BRAND YOU CAN TRUST

M07. Wunda Premium Manifold. Before you start:  Check the contents THE BRAND YOU CAN TRUST Before you start: Check the manifold box contents against the list below. Check the contents 1. 2 x Manifold end blanks 2. 2 x Manual air vent & drain cocks 3. 2x Adjustable mounting brackets 4. Manifold

More information

OWNERS INSTRUCTION MANUAL

OWNERS INSTRUCTION MANUAL OWNERS INSTRUCTION MANUAL 132CM/52 Classic INSTALLATION OPERATION MAINTENANCE CAUTION READ INSTRUCTIONS CAREFULLY FOR SAFE INSTALLATION AND FAN OPERATION. IF UNSURE CONSULT A QUALIFIED ELECTRICIAN SUITABLE

More information

PLASTER TRIMLESS FLUSH LUMINAIRES

PLASTER TRIMLESS FLUSH LUMINAIRES PLASTER TRIMLESS FLUSH LUMINAIRES SEAMLESS INTEGRATED LUMINAIRES PLASTER - A NATURAL BIODEGRADABLE MATERIAL Introducing our latest range of trimless plaster wall and ceiling lights... Our latest range

More information

PASSIVE FIRE PROTECTION FTI-MARNEROS LTD

PASSIVE FIRE PROTECTION FTI-MARNEROS LTD PASSIVE FIRE PROTECTION FTI-MARNEROS LTD the art of passive fire protection since 1989 ABOUT FTI - MARNEROS is the joining of the fire department of Chr. Marneros & Co Ltd and Fire and Thermal Installations

More information

AFUMEX LSX LOW SMOKE ZERO HALOGEN SCREENED WIRING CABLES BS8436 PRODUCT DATASHEET & APPLICATIONS GUIDE KEY BENEFITS:

AFUMEX LSX LOW SMOKE ZERO HALOGEN SCREENED WIRING CABLES BS8436 PRODUCT DATASHEET & APPLICATIONS GUIDE KEY BENEFITS: PRODUCT DATASHEET & APPLICATIONS GUIDE LOW SMOKE ZERO HALOGEN SCREENED WIRING CABLES BS8436 KEY BENEFITS: BASEC approved for the full size range of BS8436 (1.0mm 2 to 2.5mm 2 ) Additionally tested for

More information

ADMINISTRATIVE ORDER # CERTIFICATES OF USE AND OCCUPANCY FOR EXISTING BUILDINGS

ADMINISTRATIVE ORDER # CERTIFICATES OF USE AND OCCUPANCY FOR EXISTING BUILDINGS 1) Purpose: In an effort to provide for consistency in administering the Existing Building Code and Property Maintenance Code for existing buildings as they pertain to Certificates of Use and Occupancy,

More information

AFUMEX LSX BASEC APPROVED LOW SMOKE ZERO HALOGEN SCREENED WIRING CABLES BS8436 PRODUCT DATASHEET & APPLICATIONS GUIDE KEY BENEFITS:

AFUMEX LSX BASEC APPROVED LOW SMOKE ZERO HALOGEN SCREENED WIRING CABLES BS8436 PRODUCT DATASHEET & APPLICATIONS GUIDE KEY BENEFITS: PRODUCT DATASHEET & APPLICATIONS GUIDE BASEC APPROVED LOW SMOKE ZERO HALOGEN SCREENED WIRING CABLES BS8436 KEY BENEFITS: BASEC approved for the full size range of BS8436 (1.0mm 2 to 2.5mm 2 ) Additionally

More information

Regulatory Reform (Fire Safety) Order 2005

Regulatory Reform (Fire Safety) Order 2005 Regulatory Reform (Fire Safety) Order 2005 This document has been prepared by ASDMA (Architectural & Specialist Door Manufacturers Association) to provide for guidance for Responsible Persons in respect

More information

CBC - Active Chilled Beam. Halton CBC. Active Chilled Beam

CBC - Active Chilled Beam. Halton CBC. Active Chilled Beam Halton CBC Active Chilled Beam Combined cooling, heating, and supply air unit for flush installation within a suspended ceiling Well suited for spaces with high cooling loads and low humidity load Ideal

More information

PRODUCT SPECIFICATION FireMaster Plus

PRODUCT SPECIFICATION FireMaster Plus PRODUCT SPECIFICATION FireMaster Plus 1 GENERAL 1.1 Scope Coopers FireMaster Plus active fire curtain barrier assemblies ( Fire Curtains ) are to be designed, fabricated, delivered, installed and commissioned

More information

The Passive Fire Protection Handbook

The Passive Fire Protection Handbook The Passive Fire Protection Handbook The UK s comprehensive guide to passive fire protection Chapter 1 Introduction AUGUST 2017 The Passive Fire Protection Handbook Contents Chapter 1: Introduction2 Applications

More information

Standards to facilitate the HCFC phase-out

Standards to facilitate the HCFC phase-out Standards to facilitate the HCFC phase-out 9 th April 2014 Suriname Daniel Colbourne RE PHRIDGE d.colbourne@re-phridge.co.uk Usefulness of safety standards Important to apply safety standards Provide indication

More information

AUTOMATIC FIRE CURTAIN FIRE CURTAIN FM 1

AUTOMATIC FIRE CURTAIN FIRE CURTAIN FM 1 PRODUCT DATA SHEET AUTOMATIC FIRE CURTAIN FM 1 AUTOMATIC FIRE CURTAIN FIRE CURTAIN FM 1 FM-1 fire curtains are used where, if there is a fire, it is necessary to create a temporary barrier within an opening

More information

Install, Protect and Comply

Install, Protect and Comply Install, Protect and Comply Best Practice for BS 7671+A3 The Installation and use of metal fixings to support cables in all areas. Malcolm Broomfield CMIOSH Issue two Issue Date 10 th January 2017 Malcolm

More information

The Inceptor Lighting Range is perfect for all types of installation...

The Inceptor Lighting Range is perfect for all types of installation... INCEPTOR LIGHTING The Inceptor Lighting Range is perfect for all types of installation... The Inceptor lighting range combines a number of key features which we believe sets it apart from competitor products.

More information

Installation and Maintenance

Installation and Maintenance MRXBOX95B-LP1 (Standard Unit) MRXBOX95B-LP1-OH (Opposite Hand Unit) Mechanical Ventilation Unit with Heat Recovery & Summer Bypass for Ceiling Void Mounting Installation and Maintenance The EMC Directive

More information

SUNWARM AIR SOLAR PRE-HEAT VENTILATION SYSTEM

SUNWARM AIR SOLAR PRE-HEAT VENTILATION SYSTEM SOLAR PRE-HEAT VENTILATION SYSTEM SUNWARM USES SOLAR ENERGY TO REDUCE THE HEATING DEMAND OF THE HOME AS WELL AS PROVIDING A COMPLETE VENTILATION SOLUTION. 76 BENEFITS Sunwarm Air provides both a ventilation

More information

The Series LFII (TY3596) Residential

The Series LFII (TY3596) Residential Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Series LFII Residential Concealed Pendent Sprinklers, Flat Plate 4.9 K-factor General Description The Tyco Rapid Response Series LFII (TY3596)

More information

Technical reference Reference & design

Technical reference Reference & design The requirement for emergency lighting originates from the Fire Precautions Act 1971 and was further enforced by the Fire Precautions (Workplace) Regulations 1997 (Amended 1999). The Regulatory Reform

More information

ZIP Varipoint III. Installation, Maintenance and User Instructions. Models VP303, VP503 VP803, VP953 direct unvented water heaters. Issued August 2008

ZIP Varipoint III. Installation, Maintenance and User Instructions. Models VP303, VP503 VP803, VP953 direct unvented water heaters. Issued August 2008 Varipoint cover qxd:varipoint cover qxd 22/8/08 11:14 Page 1 Installation, Maintenance and User Instructions ZIP Varipoint III Models VP303, VP503 VP803, VP953 direct unvented water heaters Issued August

More information

Regulatory Reform (Fire Safety) Order 2005

Regulatory Reform (Fire Safety) Order 2005 Regulatory Reform (Fire Safety) Order 2005 Solutions for acoustic, smoke and fire containment What is the RRO? The Regulatory Reform (Fire Safety) Order 2005 came into force almost ten years ago in England

More information

An introduction to Part L Insulating pipes and ducts

An introduction to Part L Insulating pipes and ducts An introduction to Part L 2013 Insulating pipes and ducts The insulation of pipes and ducts is essential to minimise heat losses for heated systems and s for cooled systems. For cooled systems, it is also

More information

ENGLISH Parcan 16 GU10D socket V1

ENGLISH Parcan 16 GU10D socket V1 MANUAL ENGLISH Parcan 16 GU10D socket V1 Highlite International B.V. Vestastraat 2 6468 EX Kerkrade the Netherlands Table of contents Warning... 2 Safety Instructions... 2 Operating Determinations... 4

More information

Product. Regulations. Agrément Certificate No 92/2841 Third issue* Designated by Government to issue European Technical Approvals

Product. Regulations. Agrément Certificate No 92/2841 Third issue* Designated by Government to issue European Technical Approvals Lorient Polyproducts Ltd Fairfax Road Heathfield Industrial Estate Newton Abbot Devon TQ12 6UD Tel: 01626 834252 Fax: 01626 833166 e-mail: admin@lorientuk.com website: www.lorientgroup.com CI/SfB (32.5)

More information

Guide to the use of Smoke Seals in Doorsets

Guide to the use of Smoke Seals in Doorsets Information Sheet No. 3 Intumescent Fire Seals Association Guide to the use of Smoke Seals in Doorsets THE HOME OF REACTIVE PROTECTION SYSTEMS CONTENTS Page Effect of Smoke 1 The Role of the Doorstop 1

More information

Secondary systems used in Europe.

Secondary systems used in Europe. Secondary systems used in Europe. Production Distribution Consumption Preface Secondary systems are the parts of the heating systems with a lower pressure and temperature level, installed in buildings.

More information

Title: The Air Leakage Performance of Timber Doorsets fitted with NOR710 Smoke Seals in Accordance with BS 476: Part 31, Section 31.

Title: The Air Leakage Performance of Timber Doorsets fitted with NOR710 Smoke Seals in Accordance with BS 476: Part 31, Section 31. Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: The Air Leakage Performance of

More information

BENSON LINEAR RADIANT TUBE

BENSON LINEAR RADIANT TUBE BENSON LINEAR RADIANT TUBE Natural or Propane (Gas fired) I N S T A L L A T I O N C O M M I S S I O N I N G S E R V I C I N G U S E R I N S T R U C T I O N S September 2001 CONTENTS Page Compliance Notices

More information

INSTALLATION GUIDE. Isodrive / V1.0

INSTALLATION GUIDE. Isodrive / V1.0 INSTALLATION GUIDE Isodrive 900 12.2016 / V1.0 www.schweigen.com.au Welcome Thank you for purchasing your new Schweigen Isodrive system. To get the maximum output from this unit, please read through this

More information

FIRE INSPECTION GUIDELINES FOR FOSTER GROUP HOME PARENTS Effective June 1, 2002, Update September 2011

FIRE INSPECTION GUIDELINES FOR FOSTER GROUP HOME PARENTS Effective June 1, 2002, Update September 2011 HCFMO Harris County Fire Marshal M.S. Montgomery Fire Marshal FIRE INSPECTION GUIDELINES FOR FOSTER GROUP HOME PARENTS Effective June 1, 2002, Update September 2011 EFFECTIVE JANUARY 1, 2007 These guidelines

More information

Aluminium range of condensing boilers. Works every time. Designed to meet carbon reduction targets. Lifetime service and support

Aluminium range of condensing boilers. Works every time. Designed to meet carbon reduction targets. Lifetime service and support Aluminium range of condensing boilers Outputs from 30kW to 600kW Designed to meet carbon reduction targets Lifetime service and support Works every time. www.pottertoncommercial.co.uk Aluminium range of

More information

Technical Seminar on the Code of Practice for Fire Safety in Buildings 2011

Technical Seminar on the Code of Practice for Fire Safety in Buildings 2011 Technical Seminar on the Code of Practice for Fire Safety in Buildings 2011 The Code of Practice for Fire Safety in Buildings 2011 The FS Code comprises 7 parts and 1 annex: Part A Introduction Part B

More information

Titon CME1 Q Plus Mechanical Extract Ventilation Unit

Titon CME1 Q Plus Mechanical Extract Ventilation Unit Titon CME1 Q Plus Mechanical Extract Ventilation Unit Product Manual ventilation systems 2 PCT Patent Application No PCT/GB2009/000114 Contents This is the Product Manual for the Titon CME1 Q Plus Introduction...................................

More information