Installation Manual January Canoga Traffic Sensing System Model 702 Non-Invasive Microloop

Size: px
Start display at page:

Download "Installation Manual January Canoga Traffic Sensing System Model 702 Non-Invasive Microloop"

Transcription

1 Installation Manual January 2008 Canoga Traffic Sensing System Model 702 Non-Invasive Microloop

2 Installation 1 Table of Contents 1 About This Installation Instruction Purpose Conventions Related Publications Installation Instruction Organization Safety Messages and Safety Labels Safety Message Formats Damage Prevention Messages Safety Label Formats Safety Label Locations Safety Safety Messages in this Installation Instruction Manual Safety Labels on these Devices Electric Shock and Electrocution Work Zone Traffic Control Personal Safety Equipment and Clothing Excavation Disposal of Material Description Features Planning Conduit Installation Installed Conduit Recommendations Pull boxes Conduit Type Conduit Installation Specification Installation of the Microloop Sensor Assemblies Installation Completion and Checkout Installation Completion Splicing Lead-in Cables Installation Checkout Troubleshooting...24

3 2 Installation 1 2 About This Installation Instruction 2.1 Purpose This installation instruction provides step-by-step instructions for installing and setting-up the Canoga 702 Non-invasive Microloops. This document is intended for use by installation and maintenance personnel responsible for installation of the system. 2.2 Conventions The conventions in Table 1-1 help to make this installation instruction easier to use by presenting a uniform approach to the descriptions, phrases and nomenclature. 2.3 Related Publications The Canoga Vehicle Detector Installation Instructions and Operations Manual, Canoga C900 Configuration Software and Canoga 701 Microloop Installation Manual. 2.4 Installation Instruction Organization This installation instruction manual is divided into 10 sections. Section 1. About This Installation Instructions This section describes the purpose of the installation instructions, identifies the audience, defines the writing conventions, lists the related publications, and summarizes the organization of the installation instruction. Section 2. Safety Messages and Safety Labels This section contains important information about the safety messages in this installation instruction manual. This section also contains important information about safety precautions and procedures for installation of the 702 Non- Invasive Microloop and sources for other safety information. This section also contains a compilation of all the safety messages and warning labels that appear in the instructions or on the Microloop. Section 3. This section contains important safety information for you to consider before beginning the installation. Table 1-1. Conventions Model Names Model Name Canoga 702 Noninvasive Microloop sensor assembly System Conditioners and Signal Names First or formal reference: initial caps Subsequent use or informal reference: Initial caps for model, lowercase for remainder Each Microloop assembly consists of one or more Microloop sensors s and the lead-in wire Canoga 702 Non-invasive Microloop 702 non-invasive Microloop, or the 702 Microloop Single, double or triple 702 Microloop sensor assembly System mode or phase Initial caps Enable microloop mode System status Initial caps The Status output or indication Signal name Initial caps the Reset signal

4 Installation 3 Section 4. Description This section describes the function of the 702 non-invasive Microloop, the theory of operation and depicts the physical configuration of the device. Section 5. Features This section contains a list of the features of the device. Section 6. Planning This section contains instructions about preparing for installing the conduit and 702 Microloop. Section Non-invasive Microloop Installation This section contains step-by-step instructions for preparing and installing 702 Microloops. Section 9. Installation Checkout and Completion This section contains information and procedures recommended for checkout and acceptance test the installed system. Section 10. Troubleshooting This section contains information to assist in the identification and correction of problems. Section 7. Conduit Installation This section contains step-by-step instructions for preparing and installing the conduit.

5 4 Installation 3 Safety Messages and Safety Labels Your safety and the safety of others is very important. We provide important safety messages in this installation instruction and on the device. Please read the safety messages and safety labels carefully before beginning the work. We also provide important damage prevention messages in this installation instruction. 3.1 Safety Message Formats A safety message alerts you to potential hazards that can cause personal injury to you and others, or property damage. Each safety message includes a safety alert symbol ( ) and one of three words: DANGER, WARNING, or CAUTION to describe the relative level of hazard. The words and symbols and their meanings are shown below: DANGER! The safety message is in this box. DANGER means you and/or someone else WILL be KILLED or SERIOUSLY HURT if you do not follow these instructions. Damage Prevention Messages We provide important safety messages in this manual to help you prevent damage to the devices. Each damage prevention message includes the word NOTICE. This word and its meaning are shown below: NOTICE The damage prevention message is in this box. NOTICE means that this device, or another device, may be damaged if you do not follow the instructions. These messages are to help you prevent damage to the device, other devices, and to the environment. 3.3 Safety Label Formats A safety label alerts you to potential hazards that can cause personal injury to you and others, or property damage. Each safety label includes a symbol or pictogram, a word to describe the relative level of the hazard and explanatory text. The words and symbols or pictograms and their meanings are shown below: WARNING! The safety message is in this box. WARNING means you and/or someone else MAY be KILLED or SERIOUSLY HURT if you do not follow these instructions. CAUTION! The safety message is in this box. CAUTION means you and/or someone else MAY be HURT or property damage may result if you do not follow these instructions. DANGER means you WILL be KILLED or SERIOUSLY HURT if you do not follow the instructions. Each safety message explains what the hazard is, what can happen to you or others, and what you can and should do to avoid the risk of exposure to the hazard. Please read the safety messages and safety labels carefully before beginning the work. 3.2 WARNING means you MAY be KILLED or SERIOUSLY HURT if you do not follow the instructions.

6 Installation 5 CAUTION means you MAY be HURT or property damage may result if you do not follow the instructions. Please read the safety messages and safety labels carefully before beginning the work. Safety Label Locations Safety labels are placed on the devices where you will see them before you may be exposed to a hazard. Please read the safety labels. They contain important safety information. We consider safety labels to be an important part of the device and they should be replaced if they are damaged or they become hard to read. If any of the safety labels on this device are missing or cannot be read please contact your dealer or Global Traffic Technologies Technical Service for a replacement. 3.4

7 6 Installation 4 Safety Below are some of the common hazards associated with the installation traffic control devices. Although many of the hazards are included in this list it does not contain all of the possible hazards and this list should not be a substitute for your judgment and experience. Included below is a compilation of all of the safety messages contained in this installation instruction manual and a compilation of all of the safety labels on the device(s). 4.1 Safety Messages in this Installation Instruction Manual There are no safety messages in this installation instruction manual: 4.2 Safety Labels on these Devices There are no safety labels on any of the 702 Microloops. Work Zone Traffic Control Proper control of vehicle traffic is important during many procedures. When you switch the traffic controller to and from the flash mode we recommend that you have people trained in manual traffic control, such as police officers, assist you. When you install devices that require you to position vehicles, equipment, or people in or near the roadway it is important that you use appropriate work zone traffic control techniques, equipment and procedures. Sometimes you may have to work on or near the roadway and these same techniques, equipment and procedures should be used for your protection. If you are unsure of which procedure is recommended or appropriate for the job ask your supervisor or foreman Electric Shock and Electrocution As a trained installer of electrical equipment you are aware of the dangers associated with installation of electrical devices. Always be sure that the power to the equipment, and all associated equipment, is turned off before beginning any procedure. Use the equipment, techniques and procedures that you learned during your training or apprenticeship or other electrical industry recognized safety procedures. 4.4

8 Installation 7 Personal Safety Equipment and Clothing Personal safety equipment includes high visibility vests, hard hats, gloves, electrical shock or electrocution protection clothing and equipment, safety shoes, and safety glasses. These are just some of the items available to you. Choose the right equipment for the job. If you are unsure of which safety equipment is recommended or appropriate for the job ask your supervisor or foreman. 4.6 Excavation Excavation in areas where buried utilities and services may be present is dangerous. The excavation, or piercing or boring equipment may come in contact with these and you could be exposed to the risk of injury or death. Please take appropriate steps to identify and locate buried utilities and services before you begin the work. Contact the appropriate agencies for information about the utilities or services. Contact your supervisor if you are unsure. Do not proceed. 4.7 Disposal of Material Please dispose of material or devices in accordance with local, state and federal laws and regulations.

9 8 Installation 5 Description The following section contains general information concerning the installation and use of the system. The Canoga 702 Non-invasive Microloop is intended to replace conventional 6-foot by 6-foot (1.8 m by 1.8 m) inductive loops for intersection presence detection, advance detection, freeway traffic monitoring, ramp metering, and traffic survey applications. The components of the 702 Non-invasive Microloop sensors are the 702 Microloop probe assembly and the carrier system which includes a conduit end cap, an end cap carrier with pull rope, carrier sections, cable ties with labels, carrier cradle, cradle lock, landscape fabric and re-usable cable tie clamps. The 702 Microloop can be installed under the roadway without cutting or sawing of the road surface. Horizontal directional drilling is used to install the conduit under the roadway. Trenching methods may also be used as appropriate. The conduit can also be installed prior to roadway paving on new construction projects. Each component is designed for quick assembly and insertion into the conduit. Installation preparation is made easy by marking the intended locations of the sensors on the pull rope. Then, the carrier sections are assembled and pushed into the conduit, along with the pull rope. A 702 Microloop assembly is inserted into the carrier when a mark on the pull rope is encountered. The carrier sections are twelve inches (30.5 cm) long. They are designed with sensor placement openings every six-inches (15 cm) after the carriers are assembled. Each carrier section is secured to the previous section by a stainless steel clip. The final carrier section is secured to the cradle with the cradle carrier lock, which is fixed in place by screws (provided). This step insures that the final assembly is held securely in position. Note In a typical installation consisting of a double Microloop sensor assembly per lane, the 702 Microloops are positioned four feet (1.22 m) apart across the lane with the sensor assembly midpoint located at the center of the traffic lane. Thus the Microloops are located two feet (60 cm) on each side of the center of the travel lane.

10 Installation 9 Figure 4-1. Typical 702 Non-invasive Microloop installation showing cross section of a roadway and of the conduit used under the roadway in a typical advance detection installation Breakdown Lane 20' (6m) 10 ft (3 m) 12 ft (3.65 m) Figure 4-2. Figure 4-2. Typical 702 Non-invasive Microloop installation for measuring speed and vehicle length showing the conduits, pull boxes, and Microloops 12 ft (3.65 m) Median 20 ft (6 m) 12 ft (3.65 m) 20' (6m) 12 ft (3.65 m) Breakdown Lane 10 ft (3 m) Pullboxes Cabinet

11 10 Installation 6 Features Easily installed in three inch (7.6 cm) Schedule 80 PVC or seamless polyethylene conduit. Easily removed, relocated or sensors added as travel lanes are reconfigured or restriped without impacting traffic. 702 Microloops can be installed within three inches (7.6 cm) of desired location in the lane. Minimal, if any, interruption of traffic during installation, service, adjustment or relocation. Preserves pavement integrity - no cutting or drilling of road pavement. No required maintenance. Service can be performed from the roadside - no need to close lanes. Road can be resurfaced without disturbing the underground sensors. Sensors are not affected by pavement deterioration, mechanical impact of traffic or the environment. Can be used under gravel or dirt roads. Conduits can be installed prior to paving on new roadway construction projects. In combination with the Canoga C900 vehicle detectors or the Traffic Monitoring Cards, closely spaced vehicles can be detected and most adjacent lane vehicles rejected. Seven year warranty on all system components.

12 Installation 11 7 Planning Global Traffic Technologies (GTT) recommends the following planning steps: 1. Visit the site to plan the installation with accurate information and knowledge of the site. If you have a plan of the site, 2. Record all pertinent measurements and notes on the plan for the site, if available. 3. Determine the best location(s) for the 702 Microloop(s), the conduit and the pull box(s) and then mark their locations on the plan. Note Figure 6-5 shows a sample worksheet on which the measurements and notes can be recorded. Determine the number of Microloops per assembly (single, double or triple sensor assemblies), the number of assemblies, the length of the lead-in cable and the number of carriers required for the installation. GTT recommends that standard assemblies are used to minimize a mix-up of different assemblies during installation. 4. Record the details of each Microloop assembly, especially custom assemblies, and cross-reference them to the plan or site drawings. 5. Discuss the locations and the conduit installation specifications with the horizontal directional drilling contractor to ensure a clear understanding of the drilling requirements (ask for a copy of the horizontal directional boring depth log). 6. Revisit the site after conduit and pull box installation in case the conduit or pull box had to be installed at a different location. Revise the installation plans as required. 7. Make accurate measurements of the depths, the location and length of the conduit run(s) and the location(s) of the pull box(es). Measure from the first Microloop sensor location to the end of the conduit in the pull box.

13 12 Installation Location: Lane 1 Ft. Lane 2 Ft. Single Microloop Sensor Assembly Pullbox Ft. Ft. Ft. Ft. Ft. Double Microloop Sensor Assembly Pullbox Ft. Ft. Ft. Ft. Ft. Triple Microloop Sensor Assembly Pullbox Ft. Ft. Ft. Lane Center Line Lane Center Line Number of lanes to monitor: Number of 702 Microloops/lane: Number of 702 Microloop assemblies: Lead-in cable length/assembly: Number of installation kits: Number of carriers: Note: GTT recommends the use of standard Microloop sensor assemblies Figure 6-5. Site Plan Worksheet

14 Installation 13 8 Conduit Installation These instructions include recommendations for the installation of the conduit. 8.1 Installed Conduit Recommendations The installed conduit must meet or exceed the following recommendations to provide a useable installation of the Canoga 702 Non-invasive Microloops Pull boxes The pull boxes must be a minimum of 24 inches (60 cm) in diameter for round type pull boxes or in length for rectangular type pull boxes to allow sufficient space to install the carriers and to attaché the cradle to the conduit in the pull box Conduit Type Rigid 3 inch (7.6 cm) PVC Schedule 80 conduit is recommended. The dimensions must comply with those shown in the Table 7-1. Table 7-1. Conduit Dimensions Inside Diameter Outside Diameter 2.9 inches (7.4 cm) 3.5 inches (8.9 cm) Mechanical joints are allowed if the joints are smooth and the carriers scan slide freely over the joints. Seamless Polyethylene, PE Schedule 80, may also be used as an alternate. Polyethylene conduit must be free from welds or joints to allow free passage of the carriers along the entire length of the conduit Conduit Installation Specification The following specification must be met to provide a useable installation. 1. The conduit must be installed at a depth of 21 inches, +/- 3 inches (45-60 cm), from the road surface to the conduit centerline. If the surface is crowned the conduit installation depth shall conform to the shape of the crown. (See Figure 7-1.) 2. The conduit should extend 2 to 3.5 inches (5-9 cm) into the pull box to allow for attachment of the cradle to the conduit (shown in Figure 7-1).

15 14 Installation Figure 7-1. Specification 0f The Depth for the Installed Conduit

16 Installation As it follows the surface contour, the conduit must consistently maintain its depth from the road surface to avoid vertical dips and horizontal deviations. The conduit should not deviate from a straight line direction by more than 0.25 inches per foot (0.63 cm per 300 cm) either horizontally or vertically. (See Figure 7-2.) 0.25" (0.64 cm) 1 foot (30.5 cm) Figure 7-2. Directional Truing Specification for the Installed Conduit 4. Check, and record the depth of the conduit every two feet (60 cm) during the process of installing the conduit to ensure that the specified depth is maintained (obtain the depth log from the horizontal drilling contractor) 5. As the conduit extends beneath the surface from the roadway edge to the pull box, it should taper slightly downward to help drain any moisture. (See Figure 7-3.) 6. Cap the end of the conduit opposite the pull box with the endcap provided in the installation kit to prevent water flow that could introduce soil into the conduit. Accumulation of soil deposits in the conduit will make the carriers difficult or impossible to remove. Position the weep hole in the end cap at the bottom of the conduit to allow any accumulated water to drain. To allow for possible service, GTT recommends that the end cap be pressfit, not glued, on the conduit. (See Figure 7-4.) Figure 7-3. Tapering Conduit for Drainage Figure 7-4. Positioning End Cap for Drainage

17 16 Installation 9 Installation of the Microloop Sensor Assemblies The following steps detail the preparation and installation of the Canoga 702 Non-invasive Microloop assemblies and carrier system. Please read the safety messages and safety labels in Section 2 carefully before beginning the work. 1. Review the site plans you prepared earlier. The actual installation may differ from the plan. 2. Measure the distance from the end of the conduit in the pull box to the desired final position in the lane of the first sensor (sensor furthest away from the pull box) of each sensor assembly. Record these distances and the space between each sensor of a multisensor assembly. 3. Identify each sensor assembly and check the continuity of each assembly with an ohmmeter. The ohmmeter reading should be within ±20% of the sum of 2.0 ohms per sensor plus 3.0 ohms/100 feet (3 ohms/30 m) of lead-in wire. 4. Lay the end carrier with pull rope attached out along the ground. 5. Using the updated site plan and a suitable tape measure, mark the location of each sensor on the pull rope using an electrical tape or the tie wraps provided. 6. Make a knot in the pull rope so that it will be at the end of the cradle after all carriers are inserted and the Microloop sensors in their correct locations. Remember to start measuring from the second hole of the end carrier. (The pull rope passes through the first hole in the end carrier.) 7. Verify your measurements along the pull rope. 8. Use the provided tie wraps to write the plan designation ID of the Microloop sensor assembly on each cable tie using a permanent ink marker. This identifies the lane location of each sensor assembly. 9. Glue the cradle coupler (connector) onto the conduit stub in the pull box. 10. Insert the cradle into the coupler. Make sure that the cradle can be rotated and position the cradle with the open side up (See Figure 8-2 for details). Figure 8-1. Microloop Layout Plan: The plan shows the layout for single (one sensor per lane), double (two sensors per lane), and triple (three sensors per lane) assemblies with respect to the centerline of the lane. On East-West roads the sensors should be shifted one foot (30 cm) North from the locations shown in the figure.

18 Installation Remove cradle and then glue and install the cradle into the conduit coupler. Important: Quickly level the cradle using a torpedo level resting on the cradle lock attachment area to (+ or - 2 ) from level. This must be completed before the glue hardens. 12. Insert the end carrier into the cradle with the open side up and the sensor insertion holes plumb (at a 90 angle, + or 2, from horizontal). See Figure 8-2 for details. Figure 8-2 Carrier Section Plumb in the Cradle 13. Locate the sensor assembly that is to be installed in the farthest lane from the pull box. Place a cable tie about one foot (30 cm) from the end of the lead-in cable. Using permanent ink marker, write the plan designation ID for this sensor assembly on the cable tie. 14. Place a second cable tie, labeled with the same ID information, near the first Microloop sensor of this sensor assembly (sensor furthest from the pull box). 15. Carefully uncoil the lead-in and lay it out straight to simplify dressing of the cable into the carrier sections as those sections are inserted into the conduit. 16. Repeat Steps for each sensor assembly to be inserted in this conduit. 17. Place the first sensor of the first Microloop sensor assembly (the farthest from the pull box) into the second hole of the end carrier. (The pull rope passes through the first hole.) Install the sensor by pressing it firmly into the hole until it snaps into place. (Refer to Figure 8-1.) 18. Install another carrier onto the first and secure it with the attached clip. Dress the rope and the cable neatly inside the carrier. Make certain there is no slack in the rope. Push the carrier sections into the conduit. 19. Check to ensure that sensor installation holes are vertical. If necessary, rotate the carrier until they are vertical. 20. Continue clipping carriers together and inserting them into the conduit, until you reach the cable tie or tape marking for the next sensor. 21. Install the next Microloop sensor in the sensor installation hole nearest the cable tie or tape marker. The cable between individual sensors of a multiple sensor assembly contains an extra six inches (15 cm) to allow for installation flexibility. 22. Dress this extra six inches (15 cm) of interconnecting cable into the carrier by making an S-fold and placing it into the cable holding area of the carrier. Also, carefully dress the pull rope into the carrier making certain there is no slack. 23. Continue installing carriers and sensor assemblies until the knot in the rope is reached. This marks the end of the carrier installation. All Microloops are situated in the pre-determined locations under the lanes. 24. Secure the last carrier by doing the following: a) Lower the wide end of the slotted holes in the cradle carrier lock over the screws provided. b) Slide the cradle carrier lock so the narrow ends of the slotted holes are adjacent to the screws. See enlargement in Figure 8-3. c) Tighten the screws provided. 25. Cut off the excess pull rope.

19 18 Installation Figure 8-3 Securing the Carriers with Carrier Lock 5. Make sure the sensor assembly identification tags are outside of the landscape fabric material. 6. Use the re-enterable tie wraps provided to secure one end of the landscape fabric material around the cradle connector, and the other end around the sensor cables and pullrope. See Figure Check the end cap over at the far end of the conduit to make sure that the weep hole allows water to drain from the conduit. Do not glue on the end cap. See Figure Installation Completion and Checkout 10.1 Installation Completion This section explains how to prevent sediment from entering and accumulating inside the conduit. 1. Make sure that the carrier assembly is securely fastened in the carrier lock. 2. Make sure that the cables and pull rope are positioned in the cradle. 3. Check the continuity of the Microloop cables with an ohmmeter. 4. Wrap the landscape fabric material (provided in the installation kit) around the conduit and cradle assembly. Figure 9-1. Installation Detail

20 Installation 19 Figure 9-2. Positioning End Cap for Drainage

21 20 Installation 10.2 Splicing Lead-in Cables This section explains how to make reliable splices. All splices should be soldered, insulated and waterproofed. The cable jacket ends must be sealed against moisture entry at the points the cables were cut for the splicing. 1. Obtain underground rated splice kits to provide the required protection (such as the 3M Scotchcast 3832 Buried Service Wire Encapsulation Kit). Read the instruction for using the splicing kits. 2. Prepare splice end cap ports to fit snugly over cable jackets, slide end caps over cables and down out of the way. Move cable ID markers, as required, to ensure that they will be visible after the splicing operation is complete. 3. Prepare the lead-in and home-run cables and wires for splicing. Remove 2 to 3.75 inches (5-9 cm) of cable jacket from each cable taking care not to damage the insulation on interior conductors. 4. If Canoga Model Home-run cable is being used, it is necessary to heat the jacket with a heat gun or another safe heat source to slide the jacket off the interior shield and conductors. 5. Remove about 0.5 inches (1.3 cm) of insulation on each conductor that will be used. As instructed by the splicing kit instructions, scuff and clean surfaces that will come in contact with the encapsulating compound. 6. If shrink tubing is being used to insulate the splice, slide a piece of shrink tubing at least 1.5 inches (3.8 cm) long over the wires to be spliced. Twist the wires to be spliced as shown in Figure 9-3. Solder the twisted wires together. Insulate the soldered connection by shrinking the tubing or by wrapping with at least two layers of electrical tape. 7. Carefully dress all wires and cable jacket ends into the splice kit encapsulation area to prepare the splice kit for adding the encapsulation compound. 8. Complete the splice by adding the encapsulation compound if required. Figure 9-3 shows a typical splicing application. Figure 9-3. Typical Splicing Application

22 Installation 21 Figure 9-4 shows how to splice sensors or sensor assemblies in series. Figure 9-4. Splicing Microloop Sensors in Series 10.3 Installation Checkout Final checkout requires connection of the sensors to an ohmmeter, a Megohmmeter and then to an inductive loop detector. These instructions assume that a Canoga C900 Series Vehicle Detector or Traffic Monitoring Card is available for measurement of operating results. 2. Using a Megohmmeter, measure the insulation resistance from each sensor terminal to Earth ground at 500 volts. Be certain the Microloop is not connected to a loop detector or transient suppresser during this test. The resistance should be greater than 100 megohms. 1. At the cabinet where the loop detectors are located, measure the DC resistance of the sensor. Make certain the sensor is not connected to a loop detector. Touch the meter probes to terminal block contacts where the home-run cable for the sensor being checked is attached. Record the reading. Calculate the expected resistance using the information in Table 9-1. Table 9-1. Resistance Checks Measuring Point Between Microloop Lead-in cables Either Lead-in cables to Earth Resistance Checks Item Resistance 702 Microloop 2.0 ohms/sensor Lead-in Homerun Cable Test at 500 VDC 3.0 ohms/ ohms/100 >100 megohms

23 22 Installation 3. Connect the Microloop sensor assembly being tested to a C900 series loop detector or Traffic Monitoring Card. Connect a PC to the C900/TMC and start the C900/TMC configuration software. Using the activity screen, observe the inductance L that the C900/TMC measures, record it, and compare it to the expected inductance calculated using the information in Table 9-2. The measured inductance should be within ±20% of the calculated inductance (usually within ±10%). Measuring Point Between Sensor Lead-in cables Table 9-2 Inductance Checks Inductance Checks Item Inductance 702 sensor 50 μh to 63 μh per sensor Homerun Cable 23 μh per 100 feet (23 μh per 30 m) 4. Using the same set-up as described in Step 3, observe the change of inductance (ΔL) shown on the screen when different types of vehicles pass over the Microloop sensor assembly being checked. The ΔL values measured should be similar to those listed in Table 9-3. Record typical ΔL values for each type of vehicle. Then compare the values measured to those shown in the table.

24 Installation 23 Table 9-3. Typical ΔL Values Typical Change in Inductance Values (ΔL Values): Vehicles Traveling Directly Over 702 Microloop Sensor Installed at a Depth of 24 Inches (60 cm) Vehicle Type Single Sensor Double Sensor 4 (1.21 m) spacing Triple Sensor 3 (0.91 m) spacing Bicycle 130 nh 130 nh 130 nh Small Motorcycle 105 nh 105 nh 105 nh Intermediate Auto 475 nh 950 nh 1400 nh Van Truck 800 nh 1600 nh 2200 nh Tractor-Trailer 955 nh 1900 nh 3700 nh 5. Using the set-up in Step 3, record the value of the Reference Frequency. Also observe the Loop Frequency. It should return to the same value as the Reference Frequency, within one Hertz, after each vehicle has passed over the Microloop sensor assembly. 6. Set the sensitivity for the channel to which the 702 Microloop sensor assembly is attached to detect 1/8 to 1/16 of the peak auto ΔL change. A ratio of 1/8 gives the most consistent occupancy readings, while 1/16 will detect nearly all vehicles, including small motorcycles. 7. Set the Bridge Time for this channel in the C900/TMC to cover about 16 feet (4.8 m) of vehicle travel for a vehicle traveling at the typical speed at this location. Assuming the typical speed is 55 mph: Bridge time = 16 feet / [55 mph * feet/(sec*mph)] = second or.2 seconds Bridge time = 4.8 m/ (88 kph* cm/sec*kph) = second or.2 seconds A Bridge time of.2 sec. to.4 sec. will give good results in this location, e.g. 27 mph (43 kph). 8. Leave the Setback Time for this channel in the C900/TMC set to the factory default setting.

25 24 Installation 11 Troubleshooting This section provides guidance on areas to examine, if any tests during installation check-out failed. Table 10-1 lists the symptoms of 702 Non- Invasive Microloop installation problems. The table also shows the possible causes of those problems and suggests actions to correct them. Many of the actions check L, ΔL, Loop Frequency, Reference Frequency, fault indications require use of a Canoga 900 series vehicle detector, a personal computer (PC) and C900 Configuration Software (C900 CS). Consult Canoga 900/TMC series Installation Instructions and C900/TMC CS on-line help for directions on using these products. Table Troubleshooting Symptoms, Possible Causes, and Actions Symptom Possible Cause Solution DC resistance too high. Home-run/lead-in may be connected to a different sensor than specified. Home-run/lead-in is longer than anticipated. Home-run/lead-in wire gauge is smaller than anticipated. 702 Microloop sensor assembly contains more sensors than anticipated. Confirm that the detector channel is connected to the proper sensor by inserting the Canoga 900 or TMC vehicle detector into its rack slot and monitoring the Call indicator LED for this channel. You should see a Call only when a vehicle passes over the 702 Microloop to which the tested channel should be connected. If the vehicles and calls don t correlate, determine which 702 Microloop is connected to the channel and correct the wiring. Determine actual routing of homerun/lead-in cable and that routing is acceptable. Correct as required. Determine AWG of home-run/lead-in wire. It is normally OK if the size of the wire is 22 AWG or larger for lengths of less than 1000 feet (300 m) Connect a Canoga C900 or TMC vehicle detector to the Microloop being checked. First check that vehicles are being sensed (calls occur). Using the Activity screen, check the channel L. If it is one or more increments of 56 μh more than expected, it is likely that the sensor assembly contains additional sensors. Then monitor the ΔL caused by autos and compare it to that given in Table 9-3. Each additional sensor will add approximately the ΔL of a single sensor. Correct as required.

26 Installation 25 Table Troubleshooting Symptoms, Possible Causes, and Actions (Cont.) Symptom Possible Cause Solution DC resistance too high. (Cont.) Poor wiring connection. 1. Flex, jar or otherwise manipulate each connection point, one connection point at a time. If the resistance changes, the connection is faulty. Repair it. 2. Connect a Canoga 900 or TMC vehicle detectors to the sensor being checked. Using the Activity screen, check the channel Loop Frequency. If the Loop Frequency does not return to the Reference Frequency after each vehicle or it strays several Hertz from the Reference Frequency when no vehicles are near, there is a possibility that a poor connection is being manipulated by vehicle induced vibrations. Recheck all splices and connections. Repair if required. DC resistance too low. Home-run/lead-in may be connected to a different Microloop sensor than specified. Home-run/lead-in is shorter than anticipated. Home-run/lead-in wire gauge is larger than anticipated. Microloop assembly contains fewer sensors than anticipated or sensors are connected in parallel. Confirm that the detector channel is connected to the proper sensor by inserting the Canoga 900 or TMC vehicle detector into its rack slot and monitoring the Call indicator LED for this channel. A Call should occur only when a vehicle passes over the 702 Microloop to which the tested channel should be connected. If the vehicles and calls don t correlate, determine which 702 Microloop is connected to the test channel and correct the wiring. Determine actual routing of home-run/leadin cable and that routing is acceptable. Correct as required. Determine AWG of home-run/lead-in wire. It is normally OK if the size of the wire is larger than specified. Connect a vehicle detector to the sensor being checked. Using the Activity screen, check the channel L. If it is one or more increments of 56 μh less than expected, it is likely that the sensor assembly contains fewer sensors than anticipated. Then monitor the ΔL caused by autos and compare it to that given in Table 9-3. Each missing sensor will cause a reduction in ΔL of approximately the ΔL of a single sensor. Correct as required. If the L is about ½ of that expected and the ΔL is about ¼ of that expected, the sensor assembly is likely connected in parallel. Correct by splicing in series.

27 26 Installation Table Troubleshooting Symptoms, Possible Causes, and Actions (Cont.) Symptom Possible Cause Solution DC resistance too low. (Cont.) Short circuit in system. Connect a Canoga 900 or TMC vehicle detector to the 702 Microloop sensor assembly being checked. First check that vehicles are being sensed. If vehicles are being sensed, it is unlikely that there is a short in the wiring. Most shorts will be directly indicated by the C900/TMC fault indicators and on the Activity screen. Megohmmeter resistance too low. One of the following: Lead-in cable insulation damaged. Home-Run cable insulation damaged. Home-Run cable water-logged. Splice poorly insulated or waterlogged. Dirty terminal\block-home-run cable connections. Vehicle detector connected to the sensor. 702 sensor(s) failed. Test to determine the causes. Readings above 10 megohm indicate operation may continue temporarily, but that failure will occur in the future. Closely examine readings under 10 megohm. 1. Ensure that a detector is not attached to the home-run cable. Retest. If the results are OK, the problem is likely that the detector was plugged in. 2. Determine whether the sensor is working properly (e.g. inductance is OK, ΔL caused by vehicles is OK, and the oscillation frequency is stable). If all functional parameters are as expected, decide whether to fix the low resistance problem. If one or more functional parameters are unacceptable, most likely oscillator stability, the problem must be fixed. 3. Determine whether the problem is in the cabinet or external to the cabinet by detaching the lead-in wires from the terminal block. Retest the leadin. If the results are OK, the problem is in the cabinet and vice-versa. 4. If testing indicates the problem is not in the cabinet containing the vehicle detector, go to the first splice to the lead-in of the 702 Micorloop sensor assembly, remove the splice, and retest the 702 Microloop sensor assembly and the home-run cable. 5. Correct the problem indicated by testing. Replace either the 702 Microloop assembly, the home-run cable, or the splice.

28 Installation 27 Table Troubleshooting Symptoms, Possible Causes, and Actions (Cont.) Symptom Possible Cause Solution L (inductance) is too high or too low. Lead-in and/or home-run cables longer than anticipated. If the inductance and the resistance are greater than expected, the lead-in and/or home-run may be longer than anticipated. Ensure that cable routing is acceptable. Verify that desired functionality is occurring, e.g. ΔLs caused by vehicles are OK and that the Loop Frequency is stable and returns to the same value after each vehicle. If there is a very long cable to the 702 Microloop sensor assembly, e.g feet (762 m) or greater, the oscillator may be very unstable. Lead-in and/or home-run cables shorter than anticipated. Lead-in and/or home-run cable open. Microloop sensor count is different than expected. Microloop Sensor failed. If the inductance and the resistance are less than expected, the lead-in and/or home-run cable is shorter than anticipated. Shorter cable runs are not a problem. Use a Canoga 900 or TMC vehicle detector. If there is an open in the cable to the sensor, the detector will indicate an open unless the lead-in/home-run cable length is very long, e.g. >2500 feet (762 m). The problem should have been found by the test with the ohmmeter. If there are fewer sensors than expected, the sensor L will be low by 56 μh per Microloop and the sensor ΔL readings for vehicles will be much lower than expected. The reverse is true, if there are extra sensors. Check the splicing and the sensor assembly. Microloop Sensors can fail in two ways. 1. Failure Mode: The L will be 500 μh larger than expected. While the failed Microloop will not detect, if it is one sensor of a multiple sensor assembly, detection will still occur at a lower than expected ΔL. 2. Failure Mode: Open connection that should be indicated by the fault status of the detector. This may be confirmed by measuring a very large resistance with an ohmmeter when the detector is not attached to the sensor. The open may be somewhere in the home-run or in the sensor assembly. To determine that the open is in the sensor assembly requires a resistance reading taken with the sensor assembly lead-in disconnected from the home-run cable. If a defective sensor assembly is indicated, replace it and retest.

29 28 Installation Table Troubleshooting Symptoms, Possible Causes, and Actions (Cont.) Symptom Possible Cause Solution L (inductance) is too high or too low. (Cont.) ΔL (change in inductance) is too high or too low. Microloop sensors wired in parallel rather than in series. Incorrect Microloop sensor depth. Microloop sensors not vertically aligned. Sensors spliced in parallel rather than in series. Incorrect Microloop sensor count. If a Microloop is connected in parallel in a sensor assembly, ΔL readings for vehicles, as well as the L reading, will be much lower, one-quarter or less, than expected. Check the splicing and the Microloop sensor assembly. ΔL readings increase as Microloop sensor depth decreases and vice versa. Review the conduit depth plot. The installation contractor can check conduit depth using his depth measuring equipment. Have the contractor correct problems as required. The ΔL readings will be lower than expected if the sensors are not vertical. Remove the landscape fabric conduit cover and cradle lock. While holding the end carrier section vertical, push the carrier sections in and out of the conduit a few times to help the system rotate to vertical. Significantly more force is required than normal if the conduit is constricted by tight radius bends (a probable cause for sensors not being vertical). Retest. If ΔL readings are acceptable, reinstall the Cradle Lock and landscape fabric conduit end cover. If sharp lateral bends are suspected to cause the sensors to rotate, remove all 702 carriers from the conduit and have the contractor replot the depth and position of the conduit. Have the contractor correct problems as required. L readings may be about ½ that expected and ΔL readings may be about ¼ of that expected. Examine the splice. Fix as required. The ΔL readings will increase if there are more Microloop sensors than expected and ΔL readings will decrease if there are fewer Microloops than expected. Check the number of Microloops in a sensor assembly by removing all sensors and carriers from the conduit. Carefully record the number of carrier sections from the conduit end and each Microloop in each sensor assembly. Correct any problems found.

30 Installation 29 Table Troubleshooting Symptoms, Possible Causes, and Actions (Cont.) Symptom Possible Cause Solution ΔL (change in inductance) is too high or too low. (Cont.) Loop Frequency (F) and/or Reference Frequency (Fref) is unstable, e.g. false calls or missed calls or Loop Frequency doesn t return to same value between vehicles. Microloop sensors installed near pavement reinforcement rod (or other ferromagnetic structure). Incorrect sensor-to-lane location. Sensor assembly failed. Cross-talk. The ΔL readings may be smaller than expected, if the sensor is in a very high or very low magnetic field. Measure the magnetic field directly above the sensor location using a magnetometer, such as Meda Model μmag. If the magnetic field strength measured is significantly above or below the vertical component of Earth magnetic field at that general location, a problem may exist. Move the measuring probe 6 inches (15 cm) to the left and right (across the traffic lane). If the measured field is constant over this 1-foot (30 cm) distance, there is unlikely a problem. If it varies significantly, look for a position to the left or right of the original sensor location (in the direction of the conduit) that has a constant magnetic field. Change the specified Microloop location to this constant field location. (Fields must be between 200 and 800 millioerstads or gauss.) The ΔL may be smaller than expected or adjacent lane calls may occur, if the Microloop(s) are at the wrong location. Check the lane position of all sensors by removing all Microloops and carriers from the conduit. Correct any problems found. Test by replacing the M702 Microloop sensor assembly. 1. Attach the 702 Microloop sensor assemblies to the same Canoga 900 series vehicle detector. 2. Ensure that the frequency at which a different detector is driving its sensor assembly is separated by more than 10,000 Hz from the frequency at which the other detector is driving its 702 Microloop sensor assembly.

31 30 Installation Table Troubleshooting Symptoms, Possible Causes, and Actions (Cont.) Symptom Possible Cause Solution Loop Frequency (F) and/or Reference Frequency (Fref) is unstable, e.g. false calls or missed calls or Loop Frequency doesn t return to same value between vehicles. (Cont.) Line frequency magnetic interference. Poor connection to Microloop sensor. Inconsistent resistance to Earth. Microloop sensor physical rotational movement. Incorrect Microloop sensor location. Microloop sensors spliced in parallel rather than in series. Incorrect Microloop sensor count. Turn on 60 Hz or 50 Hz filtering. If the calls disappear, they were caused by line frequency magnetic interference. Turning on line filtering is a method of distinguishing crosstalk from line frequency magnetic interference. NOTE: Detection tasks that require rapid measurement response, such as speed measurement, vehicle travel direction detection and occupancy measurement of high speed vehicles, are adversely affected when line filtering is turned on. 1. Flex, jar or otherwise manipulate each connection point, one connection point at a time. Changing resistance will cause calls, just like inductance changes. If the resistance changes, the connection is faulty. Repair it. 2. If the Loop Frequency does not return to the same value after each vehicle, there is still a possibility that there is a poor connection that is being manipulated by vehicle induced vibrations. Recheck each connection. See Megohmmeter resistance too low. Check conduits mounted underneath bridges or other structures for movement and stabilize as required. To help prevent calls from tall tractors or trucks to a sensor set located in an adjacent lane, install the sensor sets on East-West roads with an offset of one (1) foot (30cm) north of lane center. Correct sensor position as required. Examine the splice. Fix as required. Check the number of Microloops in a sensor assembly by removing all Microloops and carrier sections from the conduit. Carefully record the number of carrier sections from the conduit end and each Microloop in each sensor assembly. Correct any problems found.

32 Important Notice to Purchaser: EXCEPT FOR THE LIMITED WARRANTIES SET FORTH IN THIS DOCUMENT, GLOBAL TRAFFIC TECHNOLOGIES (GTT) MAKES NO OTHER WARRANTIES AND EXPRESSLY DISCLAIMS ALL OTHER WARRANTIES, WHETHER EXPRESS OR IMPLIED, INCLUDING, WITHOUT LIMITATION, ANY WARRANTY AS TO MERCHANTABILITY OR FITNESS FOR A PARTICULAR USE. Global Traffic Technologies (GTT) will, at its sole option, repair, replace or refund the purchase price of Canoga TM Traffic Sensing System components or Canoga TM vehicle detectors described herein found to be defective in materials or manufacture within seven (7) years from the date of shipment from GTT. This warranty shall not apply to Canoga traffic sensing system components or Canoga vehicle detectors which have been (1) repaired or modified by persons not authorized by GTT; (2) subjected to misuse, neglect or accident; (3) damaged by extreme atmospheric or weather conditions; or (4) subject to events or use outside the normal or anticipated course. IN NO EVENT SHALL GTT BE LIABLE FOR ANY INJURY (INCLUDING, WITHOUT LIMITATION, PERSONAL INJURY), DEATH, LOSS, OR DAMAGE (INCLUDING, WITHOUT LIMITATION, PROPERTY DAMAGE), WHETHER DIRECT, INDIRECT, INCIDENTAL, SPECIAL, CONSEQUENTIAL, OR OTHERWISE, ARISING OUT OF THE USE OR INABILITY TO USE, REPAIR OR FAILURE TO REPAIR, ANY GTT PRODUCT. REGARDLESS OF THE LEGAL THEORY ASSERTED. THE REMEDIES SET FORTH IN THIS DOCUMENT ARE EXCLUSIVE. Statements or recommendations not contained herein shall have no force or effect unless in an agreement signed by officers of seller and manufacturer. Global Traffic Technologies, LLC Global Traffic Technologies Canada, Inc. Canoga and Microloop are trademarks of Global 7800 Third Street North 157 Adelaide Street West Traffic Technologies, LLC St. Paul, Minnesota Suite 448 Used under license in Canada Toronto, ON M5H 4E7 Please recycle. Printed in the U.S.A Global Traffic Technologies, LLC All rights reserved (Rev. B)

Installation Manual February Opticom Infrared System. Model 575 Confirmation Light Kit

Installation Manual February Opticom Infrared System. Model 575 Confirmation Light Kit Installation Manual February 2008 Opticom Infrared System Model 575 Confirmation Light Kit Installation i Table of Contents 1 About This Manual... 1 1.1 Purpose of Manual... 1 1.2 Manual Conventions...

More information

Installation Manual September Opticom Infrared System. Model 798 Emitter Bezel Mount Kit

Installation Manual September Opticom Infrared System. Model 798 Emitter Bezel Mount Kit Installation Manual September 2009 Opticom Infrared System Model 798 Emitter Bezel Mount Kit Installation i Table of Contents 1 About This Manual... 1 1.1 Purpose of Manual... 1 1.2 Manual Conventions...

More information

Technical Bulletin April Opticom Infrared System. Optical Preemption Detector Identification Guide

Technical Bulletin April Opticom Infrared System. Optical Preemption Detector Identification Guide Technical Bulletin April 2010 Opticom Infrared System Optical Preemption Detector Identification Guide Overview This document is intended to be used as a guide to identify the various manufacturers and

More information

Operating Instructions

Operating Instructions CS101 CarSense Vehicle Motion Detector Operating Instructions CAUTIONS AND WARNINGS Never use the CS101 as a safety reversing or presence detection system. The CS101 requires that a vehicle be moving for

More information

Installation Guide

Installation Guide Installation Guide 502-018 TOA1 Series Sensor SUPERSEDES: October 22, 2010 EFFECTIVE: November 17, 2010 Plant ID: 001-3966 Table of Contents TOA1 Sensor................................ 2 Features..................................

More information

ALL-WEATHER LANDSCAPE BURIAL SUBWOOFERS Burial Subwoofers: 10 & 12 (250mm & 300mm)

ALL-WEATHER LANDSCAPE BURIAL SUBWOOFERS Burial Subwoofers: 10 & 12 (250mm & 300mm) ALL-WEATHER LANDSCAPE BURIAL SUBWOOFERS Burial Subwoofers: 10 & 12 (250mm & 300mm) CONTENTS 10 Burial Subwoofer: (1) Burial Subwoofer with Direct Burial Cable Attached (2) Silicone-Filled Wire Connectors

More information

FLEXIBLE DUCTS BY SUBSURFACE INSTALLATION FOR MAGNETIC DETECTORS - Item No. RIGID DUCTS, CONCRETE ENCASED FOR MAGNETIC DETECTORS - Item No.

FLEXIBLE DUCTS BY SUBSURFACE INSTALLATION FOR MAGNETIC DETECTORS - Item No. RIGID DUCTS, CONCRETE ENCASED FOR MAGNETIC DETECTORS - Item No. FLEXIBLE DUCTS BY SUBSURFACE INSTALLATION FOR MAGNETIC DETECTORS - Item No. RIGID DUCTS, CONCRETE ENCASED FOR MAGNETIC DETECTORS - Item No. Special Provision No. 682S33 February 2016 Amendment to OPSS

More information

D2E Duct Smoke Detector

D2E Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS D2E Duct Smoke Detector Specifications Operating Temperature: 20 to 60 C Storage Temperature: 20 to 60 C Humidity: 0% to 93% Relative Humidity Non-condensing Air

More information

Silicone Rubber Heating Tape with Adjustable Thermostat Control (HSTAT Series) Instruction Manual

Silicone Rubber Heating Tape with Adjustable Thermostat Control (HSTAT Series) Instruction Manual Silicone Rubber Heating Tape with Adjustable Thermostat Control (HSTAT Series) Instruction Manual Read and understand this material before operating or servicing these heating tapes. Failure to understand

More information

DSP-13 Tri-Axis Detection (TRIAD TM ) System

DSP-13 Tri-Axis Detection (TRIAD TM ) System User Manual DSP-13 Tri-Axis Detection (TRIAD TM ) System DSP-13M_MAN_G 09/05/18 Page 1 of 24 Pros Who Know Trust Diablo 1. Contents 2. Table of Figures... 3 3. Introduction... 4 4. Technical Data... 5

More information

GG-VL-R REFRIGERANT VENT LINE SENSOR. Installation and Operation Manual

GG-VL-R REFRIGERANT VENT LINE SENSOR. Installation and Operation Manual GG-VL-R REFRIGERANT VENT LINE SENSOR Installation and Operation Manual 2 GG-VL-R Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified

More information

GASGUARD VENT LINE3. Ammonia Sensor OPERATING & INSTALLATION MANUAL

GASGUARD VENT LINE3. Ammonia Sensor OPERATING & INSTALLATION MANUAL GASGUARD VENT LINE3 Ammonia Sensor OPERATING & INSTALLATION MANUAL Operating and Installation Manual Warning Use this product only in the manner described in this manual. If the equipment is used in a

More information

Detection System Model 3500 Series

Detection System Model 3500 Series Detection System Model 3500 Series Architect/Contractor Information Package 3M Library Systems 3M Center, Building 225-4N-14 St. Paul, Minnesota 55144-1000 Copyright 2001-2006 3M. All rights reserved.

More information

Wrap-Around TOTE Tank / IBC Heaters (TOTE and TOT Series)

Wrap-Around TOTE Tank / IBC Heaters (TOTE and TOT Series) Wrap-Around TOTE Tank / IBC Heaters (TOTE and TOT Series) Instruction Manual Read and understand this material before operating or servicing these heating tapes. Failure to understand how to safely operate

More information

(HSTAT Series) Instruction Manual

(HSTAT Series) Instruction Manual Silicone Rubber Heating Tapes with Adjustable Thermostat Control (HSTAT Series) Instruction Manual Read and understand this material before operating or servicing these heating tapes. Failure to understand

More information

D-TEK O P E R A T I N G I N S T R U C T I O N S V E HI C L E L O O P DETECTOR Johnston Parkway, Cleveland, Ohio 44128

D-TEK O P E R A T I N G I N S T R U C T I O N S V E HI C L E L O O P DETECTOR Johnston Parkway, Cleveland, Ohio 44128 O P E R A T I N G I N S T R U C T I O N S D-TEK V E HI C L E L O O P DETECTOR 4564 Johnston Parkway, Cleveland, Ohio 44128 P. 800 426 9912 F. 216 518 9884 Sales Inquiries: salessupport@emxinc.com Technical

More information

LV-S-5. Instruction Manual DIRECT CONTACT STRAY VOLTAGE DETECTOR GENERAL DESCRIPTION HOW IT WORKS

LV-S-5. Instruction Manual DIRECT CONTACT STRAY VOLTAGE DETECTOR GENERAL DESCRIPTION HOW IT WORKS LV-S-5 DIRECT CONTACT STRAY VOLTAGE DETECTOR Instruction Manual GENERAL DESCRIPTION The LV-S-5 is a hand held stray voltage detector for testing exposed metallic surfaces and conductors for the presence

More information

Sentry LIQUID LEVEL GAUGE MODEL 200 or 200C OWNER MANUAL REV 1.7 SEPT08 PAGE 1 OF 12

Sentry LIQUID LEVEL GAUGE MODEL 200 or 200C OWNER MANUAL REV 1.7 SEPT08 PAGE 1 OF 12 PAGE 1 OF 12 TABLE OF CONTENTS PAGE 1. SAFETY PRECAUTIONS 1.1. Electrical shock 3 2. APPLICATION 3 3. INSTALLATION 3.1. Mount indoor alarm display 3.2. Mount the outdoor junction box 3.3. Install interconnecting

More information

HotPoly Tote Tank / IBC Heaters (TTH Series)

HotPoly Tote Tank / IBC Heaters (TTH Series) HotPoly Tote Tank / IBC Heaters (TTH Series) Instruction Manual Read and understand this material before operating or servicing these heaters. Failure to understand how to safely operate these heaters

More information

Sentry LIQUID LEVEL CONTROLLER MODEL 120 OPERATING MANUAL.

Sentry LIQUID LEVEL CONTROLLER MODEL 120 OPERATING MANUAL. Sentry LIQUID LEVEL CONTROLLER MODEL 120 OPERATING MANUAL www.aquaticsentry.com TABLE OF CONTENTS 1. SAFETY PRECAUTIONS... 3 2. APPLICATION... 3 2.1 HIGH AND LOW LEVEL ALARM 2.2 PUMP DOWN CONTROLLER 2.3

More information

Manual No: Revision: E. Groundwater Sensor. Installation Guide

Manual No: Revision: E. Groundwater Sensor. Installation Guide Manual No: 576013-763 Revision: E Groundwater Sensor Installation Guide Notice Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied warranties

More information

Frost Heave Protection System Installation and Operation Manual

Frost Heave Protection System Installation and Operation Manual Frost Heave Protection System Installation and Operation Manual FHPC Constant Power Density Heating Cable Systems Thermal management solutions EN-RaychemFHPS-IM-INSTALL103 R1 WARNING: Fire and Shock Hazard.

More information

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC AQB09JJ6WC_IM_E_2585 2006.4.17 4:26 PM Page 17 INSTALLATION MANUAL Indoor Unit AQB09JJWC AQB12JJWC Outdoor Unit UQB09JJWC UQB12JJWC ENGLISH FRANÇAIS ESPAÑOL Split-type Air Conditioner (Cooling and Heating)

More information

OPERATION MANUAL MODEL & ACCELEROMETER

OPERATION MANUAL MODEL & ACCELEROMETER OPERATION MANUAL MODEL 8011-01 & 8021-01 ACCELEROMETER TE CONNECTIVITY SENSORS///MODEL 8011-01 & 8021-01 ACCELEROMETER 05/2016 Page 1 WARRANTY Measurement Specialties, Inc. accelerometers are warranted

More information

DUVAL 52 CEILING FAN MODELS #50201, Español p. 19 LISTED FOR DAMP LOCATION

DUVAL 52 CEILING FAN MODELS #50201, Español p. 19 LISTED FOR DAMP LOCATION DUVAL 52 CEILING FAN MODELS #50201, 50206 Español p. 19 LISTED FOR DAMP LOCATION Questions, problems, missing parts? Before returning to your retailer, call our customer service department at 1-877-361-3883,

More information

Model: EF34. Owner's Guide & Installation Manual

Model: EF34. Owner's Guide & Installation Manual Owner's Guide & Installation Manual WARNING: Read this manual before using this product. Failure to follow the instructions and safety precautions in this manual can result in damage to property, serious

More information

ImPress IRONING STATION

ImPress IRONING STATION CONSUMER SERVICES TECHNICAL EDUCATION GROUP PRESENTS L-73 ImPress IRONING STATION Model LFB2611L JOB AID Part No. 8178203 FORWARD This Whirlpool Job Aid, ImPress Ironing Station, (Part No. 8178203), provides

More information

SAFETY INFORMATION AND WARNINGS

SAFETY INFORMATION AND WARNINGS This manual refers to the Model SST-3 control panel manufactured since October 31, 2013, which uses a universal (100 277 VAC; 50/60 Hz) power supply. Older units use a voltage-specific power supply and

More information

Non-Programmable Digital Thermostat

Non-Programmable Digital Thermostat OWNER'S MANUAL MODEL P474-0140 Non-Programmable Digital Thermostat HEAT PUMP THERMOSTAT 2 HEAT, 1 COOL emergency aux. heat normal energy save Fan On Fan Auto Millivolt Compatible Battery or System Powered

More information

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Indoor Unit AQB18J6WC AQB24J2WC. Outdoor Unit UQB18J6WC UQB24J2WC

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Indoor Unit AQB18J6WC AQB24J2WC. Outdoor Unit UQB18J6WC UQB24J2WC AQB8J6WC_IM_E_25864 2006.4.4 3:29 PM Page 7 INSTALLATION MANUAL Indoor Unit AQB8J6WC AQB24J2WC Outdoor Unit UQB8J6WC UQB24J2WC ENGLISH FRANÇAIS ESPAÑOL Split-type Air Conditioner (Cooling and Heating)

More information

Installation GUIDE VDWU524SS VDWU524WSSS FDWU524WS FDWU524 VDWU324SS FDWU324

Installation GUIDE VDWU524SS VDWU524WSSS FDWU524WS FDWU524 VDWU324SS FDWU324 Installation GUIDE VDWU524SS VDWU524WSSS FDWU524WS FDWU524 VDWU324SS FDWU324 To prevent accidents, which could cause serious injury or death, as well as machine damage read these instructions before installation

More information

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13 R 410A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFS4(A/H) System, DFC4(A/H)3 Outdoor, DFF4(A/H)H Indoor NOTE: Read the entire instruction manual before starting the installation.

More information

52 CEILING FAN. Owner s Manual Models #50336, 50337

52 CEILING FAN. Owner s Manual Models #50336, 50337 52 CEILING FAN Owner s Manual Models #50336, 50337 If a problem cannot be remedied or you are experiencing difficulty in installation, please contact the Service Department: 1-877-706-3267, 9 a.m.- 5 p.m.

More information

3 Scotch Mini-Weld Adhesive System User s Manual

3 Scotch Mini-Weld Adhesive System User s Manual 3 Scotch Mini-Weld Adhesive System User s Manual The Scotch Mini-Weld Adhesive System Includes The items shown below: Contents of User s Manual Ordering Replacement Parts... 1 Important Safety Information...

More information

breeze easytm model # F100-1W

breeze easytm model # F100-1W DewStop breeze easytm model # F100-1W Installation Guide Read and Save These Instructions LISTED Questions, Problems, Missing Parts? Please Call 1-360-876-2974 or E-Mail info@dewstop.com please retain

More information

IntelliDoX Operator Manual

IntelliDoX Operator Manual IntelliDoX Operator Manual OPERATOR MANUAL TABLE OF CONTENTS Table of Contents Table of Contents...1 About this Publication...3 Important Safety Information: Read First...4 Getting Started...5 About the

More information

Installation, Operation & Service Manual

Installation, Operation & Service Manual Installation, Operation & Service Manual WARNING Improper installation, adjustment, alteration, service or maintenance can result in death, injury or property damage. Read the Installation, Operation and

More information

GASGUARD Cl 2. Chlorine Sensor OPERATING & INSTALLATION MANUAL

GASGUARD Cl 2. Chlorine Sensor OPERATING & INSTALLATION MANUAL GASGUARD Cl 2 Chlorine Sensor OPERATING & INSTALLATION MANUAL Operating and Installation Manual 2 Table of Contents GasGuard Cl 2 Operating and Instruction Manual General description. 4 Installation..

More information

SEALING FIBER SEALING COMPOUND

SEALING FIBER SEALING COMPOUND ARCTIC TRACE INSTALLATION INSTRUCTIONS Type GUAT26C Hazardous Location Power Connection and Butt Splice Kit for Temperature Limiting Submersible Heating Cable JUNCTION BOX SEALING FIBER SEAL OFF SEALING

More information

Installation Instructions

Installation Instructions P700U -21NHP Base Non -Programmable Thermostats Installation Instructions Designed and Assembled in the USA. US patents: US20060165149 A1, USD578026 SI, US6205041 B1 A14005 Base Non---Programmable Thermostat

More information

GASGUARD NH 3. Ammonia Sensor OPERATING & INSTALLATION MANUAL

GASGUARD NH 3. Ammonia Sensor OPERATING & INSTALLATION MANUAL GASGUARD NH 3 Ammonia Sensor OPERATING & INSTALLATION MANUAL Operating and Installation Manual 2 Table of Contents GasGuard NH 3 Operating and Instruction Manual General description. 4 Installation.. 4

More information

Reacti-Therm I and III Heating Modules

Reacti-Therm I and III Heating Modules INSTRUCTIONS Reacti-Therm I and III Heating Modules TS-18822 TS-18824 Number TS-18822 TS-18824 Description Reacti-Therm I Heating Module (single block) Reacti-Therm III Heating Module (triple block) 2101.1

More information

SPA BLOWER OWNER'S MANUAL XXXX, XXXX, XXXX, XXXX, XXXX, XXXX fax

SPA BLOWER OWNER'S MANUAL XXXX, XXXX, XXXX, XXXX, XXXX, XXXX fax SPA BLOWER OWNER'S MANUAL 80015-XXXX, 80016-XXXX, 80017-XXXX, 80018-XXXX, 80019-XXXX, 80020-XXXX fax 888.610.3839 2015 323300-015 6/15 THIS PAGE INTENTIONALLY LEFT BLANK. 2 Operating Instructions and Parts

More information

MaxLite LED VAPOR TIGHT LINEAR FIXTURES

MaxLite LED VAPOR TIGHT LINEAR FIXTURES A cost effective LED Vapor Tight Fixture features a full length polycarbonate lens and a one-piece white glass reinforced polyester (GRP) body. Designed to meet or exceed seven to 10 foot-candles at 8

More information

Combustible Gas Sample-Draw Detector Operator s Manual

Combustible Gas Sample-Draw Detector Operator s Manual 35-3001-01 Combustible Gas Sample-Draw Detector Operator s Manual Part Number: 71-0282RK Revision: A Released: 8/3/17 www.rkiinstruments.com WARNING Read and understand this instruction manual before operating

More information

CarSense 303 O P E R A T I N G I N S T R U C T I O N S M A G N E T O R E S I T I V E V E H I C L E D E T E C T O R

CarSense 303 O P E R A T I N G I N S T R U C T I O N S M A G N E T O R E S I T I V E V E H I C L E D E T E C T O R O P E R A T I N G I N S T R U C T I O N S CarSense 303 TM M A G N E T O R E S I T I V E V E H I C L E D E T E C T O R 4564 Johnston Parkway, Cleveland, Ohio 44128 P. 800 426 9912 F. 216 518 9884 Sales

More information

TAG MR VOLTAGE DETECTORS AND ACCESSORIES. Instruction & Operation Manual

TAG MR VOLTAGE DETECTORS AND ACCESSORIES. Instruction & Operation Manual TAG 200 200MR 2000 330 VOLTAGE DETECTORS AND ACCESSORIES Instruction & Operation Manual TAG-200, TAG-200MR and TAG-2000 (Distribution Voltages) and TAG-330 (Transmission Voltages) units are shown with

More information

Installation Instructions Wall Ovens

Installation Instructions Wall Ovens Installation Instructions Wall Ovens TESTED IN ACCORDANCE WITH THE LATEST EDITION OF UL858 STANDARD FOR HOUSEHOLD ELECTRIC COOKING APPLIANCES. IMPORTANT 1. Before beginning installation, please thoroughly

More information

CarSense 303 O P E R A T I N G I N S T R U C T I O N S M A G N E T O R E S I T I V E V E H I C L E D E T E C T O R

CarSense 303 O P E R A T I N G I N S T R U C T I O N S M A G N E T O R E S I T I V E V E H I C L E D E T E C T O R O P E R A T I N G I N S T R U C T I O N S CarSense 303 TM M A G N E T O R E S I T I V E V E H I C L E D E T E C T O R 4564 Johnston Parkway, Cleveland, Ohio 44128 P. 800 426 9912 F. 216 518 9884 Sales

More information

Web Pages for Construction and Traveler Information Condition Reporting System 511 Phone Power. Data Processing and Response Formulation

Web Pages for Construction and Traveler Information Condition Reporting System 511 Phone Power. Data Processing and Response Formulation Existing Existing To Be Modified To Be Developed Not Applicable Visual Surveillance (e.g. CCTV) Traffic Detectors (excluding presence detectors at intersections for signal control) Dynamic Message Sign

More information

GG-NO2 NITROGEN DIOXIDE GAS SENSOR. Installation and Operation Manual

GG-NO2 NITROGEN DIOXIDE GAS SENSOR. Installation and Operation Manual GG-NO2 NITROGEN DIOXIDE GAS SENSOR Installation and Operation Manual 2 GG-NO2 Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified by

More information

MaxLite LED Vapor Tight Linear Fixture

MaxLite LED Vapor Tight Linear Fixture General Safety Information To reduce the risk of death, personal injury or property damage from fire, electric shock, falling parts, cuts/abrasions, and other hazards read all warnings and instructions

More information

Here is what comes in your box:

Here is what comes in your box: Here is what comes in your box: We recommend that you pull everything out of the box and lay it out. We have grouped the drawn components below with the hardware you ll need for those parts. The screws

More information

In data sheets and application notes which still contain NXP or Philips Semiconductors references, use the references to Nexperia, as shown below.

In data sheets and application notes which still contain NXP or Philips Semiconductors references, use the references to Nexperia, as shown below. Important notice Dear Customer, On 7 February 2017 the former NXP Standard Product business became a new company with the tradename Nexperia. Nexperia is an industry leading supplier of Discrete, Logic

More information

2. All connections are 24 volt AC. Verify all planned connections at TT thermostat connections, before turning on power

2. All connections are 24 volt AC. Verify all planned connections at TT thermostat connections, before turning on power .1. Turn off all power to the boiler at the circuit breaker. This will avoid accidental injury, or short circuits. 2. All connections are 24 volt AC. Verify all planned connections at TT thermostat connections,

More information

ST. KITTS CEILING FAN

ST. KITTS CEILING FAN ITEM #0845047 ST. KITTS CEILING FAN MODEL #40829 Questions, problems or missing parts? Before returning this item to your retailer, call our customer service department at 1-800-643-0067, Monday - Thursday,

More information

TURBO Fiberglass Cone Fan and Grill Fan 48'' Belt Drive. Installation & Operator s Instruction Manual

TURBO Fiberglass Cone Fan and Grill Fan 48'' Belt Drive. Installation & Operator s Instruction Manual TURBO Fiberglass Cone Fan and Grill Fan 48'' Belt Drive Installation & Operator s Instruction Manual July 1998 MV1383B Chore-Time TURBO TM Fan Extended Warranty Chore-Time Equipment warrants new TURBO

More information

GG-NH3 AMMONIA GAS SENSOR. Installation and Operation Manual

GG-NH3 AMMONIA GAS SENSOR. Installation and Operation Manual GG-NH3 AMMONIA GAS SENSOR Installation and Operation Manual 2 GG-NH3 Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified by Calibration

More information

DISHWASHER. Models DW2432 and DW2432SS. Installation Manual. Write Serial Number (on inner door of unit) here:

DISHWASHER. Models DW2432 and DW2432SS. Installation Manual. Write Serial Number (on inner door of unit) here: DISHWASHER Models DW2432 and DW2432SS Installation Manual Write Serial Number (on inner door of unit) here: Felix Storch, Inc. Summit Appliance Division 770 Garrison Avenue Bronx, New York 10474 www.summitappliance.com

More information

WVD100. EZ Loop. Product Manual. Wireless Vehicle Detector. Installation Instructions Program Instructions. AP100 Relay Board S200 Sensor

WVD100. EZ Loop. Product Manual. Wireless Vehicle Detector. Installation Instructions Program Instructions. AP100 Relay Board S200 Sensor Wireless Vehicle Detector EZ Loop AP100 Relay Board S200 Sensor ACCESS STATUS < ONE PROGRAM Installation Instructions Program Instructions! Read and follow all U.L. and Safety Standards before installing

More information

HOTFOIL HB MODULE HEATING SYSTEM INSTALLATION, OPERATION & MAINTENANCE MANUAL HB.IOM.R3

HOTFOIL HB MODULE HEATING SYSTEM INSTALLATION, OPERATION & MAINTENANCE MANUAL HB.IOM.R3 HOTFOIL HB MODULE HEATING SYSTEM INSTALLATION, OPERATION & MAINTENANCE MANUAL HB.IOM.R3 Hotfoil,Inc. 109 North Gold Drive Robbinsville, NJ 08691 Phone # (609) 259.4118 Fax # (609) 259-4119 http:\\hotfoil.com

More information

Gardian W51. Approvals

Gardian W51. Approvals Gardian W51 120 V pre-assembled electric heating cables for pipe freeze protection and roof & gutter de-icing Installation Instructions Description Gardian W51 120 V pre-assembled self-regulating heating

More information

GG-R REFRIGERANT SENSOR. Installation and Operation Manual

GG-R REFRIGERANT SENSOR. Installation and Operation Manual GG-R REFRIGERANT SENSOR Installation and Operation Manual 2 GG-R Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified by Calibration

More information

Wiring Instructions. High-Capacity Steam Humidifiers

Wiring Instructions. High-Capacity Steam Humidifiers Wiring Instructions for High-Capacity Steam Humidifiers Including Instructions for Compensating Humidistat and Safety Control Shutoff CONTRACTOR: Read these instructions before installing or servicing

More information

Carbon Dioxide Sample-Draw Detector Operator s Manual

Carbon Dioxide Sample-Draw Detector Operator s Manual 35-3001-05-03 Carbon Dioxide Sample-Draw Detector Operator s Manual Part Number: 71-0413 Revision: 0 Released: 8/4/17 www.rkiinstruments.com WARNING Read and understand this instruction manual before operating

More information

52 SAN LUCAS CEILING FAN

52 SAN LUCAS CEILING FAN 52 SAN LUCAS CEILING FAN Owner s Manual Models #20551 If a problem cannot be remedied or you are experiencing difficulty in installation, please contact the Service Department: 1-877-459-3267, 9 a.m.-

More information

GASGUARD SO2 Sulfur Dioxide Sensor OPERATING & INSTALLATION MANUAL

GASGUARD SO2 Sulfur Dioxide Sensor OPERATING & INSTALLATION MANUAL GASGUARD SO2 Sulfur Dioxide Sensor OPERATING & INSTALLATION MANUAL Operating and Installation Manual Warning Use this product only in the manner described in this manual. If the equipment is used in a

More information

Fire Bowls and Fire Bowl Inserts (Automated Operation) Operating and Maintenance Instructions

Fire Bowls and Fire Bowl Inserts (Automated Operation) Operating and Maintenance Instructions Table of Contents Section 1: Gas and Electric Requirements... 1 Section 2: Installation... 2 Section 3: Burner Setup and Adjustment... 8 Burner Adjustment... 9 Section 4: Maintenance... 10 Section 5: Operation...

More information

Manual No: Revision: D. Mag Sump Sensor. Installation Guide

Manual No: Revision: D. Mag Sump Sensor. Installation Guide Manual No: 577013-812 Revision: D Mag Sump Sensor Installation Guide Notice Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied warranties

More information

Torrena 42 Ceiling Fan

Torrena 42 Ceiling Fan Torrena 42 Ceiling Fan Owner s Manual Part # 269268, 269269 Model # 32096, 32097 Exclusively Distributed by: HD Supply Facilities Maintenance, Ltd. Atlanta, GA 30339 2017 Made in China If you are experiencing

More information

SUTTON 52 CEILING FAN

SUTTON 52 CEILING FAN SUTTON 52 CEILING FAN MODELS #50188, 50189, 50190 Español p. 19 Questions, problems, missing parts? Before returning to your retailer, call our customer service department at 1-877-361-3883, Monday - Thursday,

More information

INSTRUCTION MANUAL P Heating and 1 Cooling

INSTRUCTION MANUAL P Heating and 1 Cooling REPLACEMENT COMPONENTS DIVISION CARRIER CORPORATION www.totaltouch.info Technical Support: 1-866-90TOUCH (1-866-908-6824) INSTRUCTION MANUAL P286-1200 2 Heating and 1 Cooling Physical Dimensions Case:

More information

Lifetime Limited Warranty

Lifetime Limited Warranty Hampton Bay Lifetime Limited Warranty The retailer warrants the fan motor to be free from defects in workmanship and material present at time of shipment from the factory for a lifetime after the date

More information

Owner s Manual FEATURING. IMPORTANT! Save this manual and read it in full before use. Non-penetrating fastening system for thermoplastic roofing

Owner s Manual FEATURING. IMPORTANT! Save this manual and read it in full before use. Non-penetrating fastening system for thermoplastic roofing Non-penetrating fastening system for thermoplastic roofing Owner s Manual FEATURING IMPORTANT! Save this manual and read it in full before use. RB1002/v3.7 Rev. 1113 153 BOWLES ROAD AGAWAM, MA 01001 USA

More information

Gas Connector Installation Instructions

Gas Connector Installation Instructions Gas Connector Installation Instructions 6015 Enterprise Drive Export, PA 15632 USA 1-800-DORMONT (367-6668) (724) 733-4800 Fax (724) 733-4808 www.dormont.com Safety Precautions - Read warnings carefully

More information

Sentry LIQUID LEVEL ALARM MODEL 100 OPERATING MANUAL.

Sentry LIQUID LEVEL ALARM MODEL 100 OPERATING MANUAL. Sentry LIQUID LEVEL ALARM MODEL 100 OPERATING MANUAL www.aquaticsentry.com TABLE OF CONTENTS 1. SAFETY PRECAUTIONS... 3 2. APPLICATION... 3 2.1 HIGH Liquid Level Alarm 2.2 LOW Liquid Level Alarm 3. INSTALLATION...

More information

DH400. Accessories. NOTE: Set up for this sensor should be performed by an AAADM-certified installer.

DH400. Accessories. NOTE: Set up for this sensor should be performed by an AAADM-certified installer. NOTE: Set up for this sensor should be performed by an AAADM-certified installer. Section 1 General Description The is a high mount microprocessor controlled active infrared presence detector for all types

More information

AIC Series Float & Thermostatic Steam Trap Installation and Maintenance Instructions

AIC Series Float & Thermostatic Steam Trap Installation and Maintenance Instructions AIC Series Float & Thermostatic Steam Trap Installation and Maintenance Instructions 138-EN Please read and save these instructions Contents General Safety Information... 3 Product Information...3-5 Product

More information

52 STRATHMERE CEILING FAN

52 STRATHMERE CEILING FAN 52 STRATHMERE CEILING FAN Owner s Manual Models #20341 If a problem cannot be remedied or you are experiencing difficulty with installation, please contact the Service Department: 1-877-459-3267, 9 a.m.-

More information

GASGUARD NH 3 2% Ammonia Sensor OPERATING & INSTALLATION MANUAL

GASGUARD NH 3 2% Ammonia Sensor OPERATING & INSTALLATION MANUAL GASGUARD NH 3 2% Ammonia Sensor OPERATING & INSTALLATION MANUAL 2 Table of Contents GasGuard NH 3 2% General description. 4 Installation.. 4 Locating the sensor. 4 Installation guidelines 5 Wiring.. 6

More information

52 BARSTOW CEILING FAN

52 BARSTOW CEILING FAN 52 BARSTOW CEILING FAN Owner s Manual Models #20519 If a problem cannot be remedied or you are experiencing difficulty with installation, please contact the Service Department: 1-877-459-3267, 9 a.m.-

More information

Installation Manual PS-225 & PS-275

Installation Manual PS-225 & PS-275 Installation Manual PS-225 & PS-275 Table of Contents Pre-Uncrating Checklist... 1 Verifying System Requirements... 2 Verifying System Direction... 2 Verifying the Electrical Requirements... 2 Removal

More information

GG-NH3-2% AMMONIA GAS SENSOR. Installation and Operation Manual

GG-NH3-2% AMMONIA GAS SENSOR. Installation and Operation Manual GG-NH3-2% AMMONIA GAS SENSOR Installation and Operation Manual 2 GG-NH3-2% Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified by Calibration

More information

Three Phase Simplex. Installation (937) Installation Instructions and Operation/Troubleshooting Manual. Installation of Floats.

Three Phase Simplex. Installation (937) Installation Instructions and Operation/Troubleshooting Manual. Installation of Floats. Three Phase Simplex Installation Instructions and Operation/Troubleshooting Manual This control panel must be installed and serviced by a licensed electrician in accordance with the National Electric Code

More information

MODEL RWM RADIATION WASTE MONITOR LUDLUM MODEL RWM RADIATION WASTE MONITOR INSTALLATION MANUAL

MODEL RWM RADIATION WASTE MONITOR LUDLUM MODEL RWM RADIATION WASTE MONITOR INSTALLATION MANUAL LUDLUM MODEL 3500-1000RWM RADIATION WASTE MONITOR INSTALLATION MANUAL August 2001 1 RECEIVING CONDITION EXAMINATION Be sure to verify that the shipping carton is received in good condition with no visible

More information

Neon LED Rope Light Installation Instructions

Neon LED Rope Light Installation Instructions Neon LED Rope Light Installation Instructions 1 Specifications 12V (WW, CW, BL) 24V (WW, CW, BL) Beam angle (FWHM) 160 Power Consumption Luminous Flux (lm)* 2.44W/ft 85lm/ft Lifetime hours (70% light output)

More information

AMERICA AMERICA 52 CEILING FAN INSTALLATION AND OPERATION MANUAL

AMERICA AMERICA 52 CEILING FAN INSTALLATION AND OPERATION MANUAL AMERICA AMERICA 52 CEILING FAN INSTALLATION AND OPERATION MANUAL Ceiling Fan Weight Including Accessories: 21.00 Lbs. READ AND SAVE THESE INSTRUCTIONS TABLE OF CONTENTS Tools and Materials Required...

More information

IC6-B, IC6-MB, IC6-BB, IC8-B, IC8-MB, IC8-BB, ICA6-B, ICA6-MB, ICA6-BB, IC6DVC-B, BS650 ICS6-MB, ICS8-MB

IC6-B, IC6-MB, IC6-BB, IC8-B, IC8-MB, IC8-BB, ICA6-B, ICA6-MB, ICA6-BB, IC6DVC-B, BS650 ICS6-MB, ICS8-MB Beale Street Audio IC6-B, IC6-MB, IC6-BB, IC8-B, IC8-MB, IC8-BB, ICA6-B, ICA6-MB, ICA6-BB, IC6DVC-B, BS650 In Ceiling Speakers ICS6-MB, ICS8-MB In Ceiling Subwoofers Installation Guide Introduction Congratulations

More information

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW)

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW) SECTION 26 05 21 PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, and connection of the low voltage power and lighting wiring. 1.2 RELATED WORK A. Excavation and backfill

More information

WET/DRY VACUUM. QUEST for Continuous Improvement Windsor s Quality Management System is Certified ISO MODEL: T1. Operating Instructions (ENG)

WET/DRY VACUUM. QUEST for Continuous Improvement Windsor s Quality Management System is Certified ISO MODEL: T1. Operating Instructions (ENG) WET/DRY VACUUM Operating Instructions (ENG) MODEL: T1 y QUEST for Continuous Improvement Windsor s Quality Management System is Certified ISO 9001. Read these instructions before operating the machine.

More information

Single-Point Mini Hydrostatic Sensor for Double-Wall Sumps

Single-Point Mini Hydrostatic Sensor for Double-Wall Sumps Manual No: 577013-838 Revision: B Single-Point Mini Hydrostatic Sensor for Double-Wall Sumps Installation Guide Notice Veeder-Root makes no warranty of any kind with regard to this publication, including,

More information

SERVICE MANUAL FOR 6795B,C,D SERIES PACKAGED AIR CONDITIONERS

SERVICE MANUAL FOR 6795B,C,D SERIES PACKAGED AIR CONDITIONERS SERVICE MANUAL FOR 6795B,C,D SERIES PACKAGED AIR CONDITIONERS TABLE OF CONTENTS 1. Warnings.................................................................. 2 2. Unit Dimensions And Specifications............................................

More information

GG-H2S HYDROGEN SULFIDE GAS SENSOR. Installation and Operation Manual

GG-H2S HYDROGEN SULFIDE GAS SENSOR. Installation and Operation Manual GG-H2S HYDROGEN SULFIDE GAS SENSOR Installation and Operation Manual 2 GG-H2S Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified by

More information

TOUCHDOWN 48 CEILING FAN

TOUCHDOWN 48 CEILING FAN TOUCHDOWN 48 CEILING FAN MODEL #50205 Español p. 20 Questions, problems, missing parts? Before returning to your retailer, call our customer service department at 1-877-361-3883, Monday - Thursday, 8 am

More information

HIDE-A-BLAST HB615X / HB915X INSTALLATION & OPERATION MANUAL IMPORTANT: 6 LED and 9 LED WARNING LIGHT

HIDE-A-BLAST HB615X / HB915X INSTALLATION & OPERATION MANUAL IMPORTANT: 6 LED and 9 LED WARNING LIGHT INSTALLATION & OPERATION MANUAL Hide-A-BlasT LED Warning Light HIDE-A-BLAST HB615X / HB915X 6 LED and 9 LED WARNING LIGHT IMPORTANT: Read all instructions and warnings before installing and using. INSTALLER:

More information

Lifetime Limited Warranty

Lifetime Limited Warranty World Imports Lifetime Limited Warranty The retailer warrants the fan motor to be free from defects in workmanship and material present at time of shipment from the factory for a lifetime after the date

More information

TMC. Installation and Operation Manual TMC. Temperature and Pressure Monitoring for Heating and Cooling Applications. Temperature Monitoring Control

TMC. Installation and Operation Manual TMC. Temperature and Pressure Monitoring for Heating and Cooling Applications. Temperature Monitoring Control Installation and Operation Manual Temperature and Pressure Monitoring for Heating and Cooling Applications Temperature Monitoring Control VALVE OPEN ALARM System= 128 o F Alarm At= 130 o F RESET /BACK

More information

52 BERKSHIRE CEILING FAN

52 BERKSHIRE CEILING FAN 52 BERKSHIRE CEILING FAN Owner s Manual Models #20223, 20224 If a problem cannot be remedied or you are experiencing difficulty in installation, please contact the Service Department: 1-877-459-3267, 9

More information

Installation Guide. For Models: E-MLV36BNK4LK1 E-MLV36ESP4LK1 E-MLV36WW4LK1 READ THESE INSTRUCTIONS AND AND SAVE THEM FOR FUTURE USE

Installation Guide. For Models: E-MLV36BNK4LK1 E-MLV36ESP4LK1 E-MLV36WW4LK1 READ THESE INSTRUCTIONS AND AND SAVE THEM FOR FUTURE USE READ THESE INSTRUCTIONS AND AND SAVE THEM FOR FUTURE USE Federal regulations require ceiling fans with light kits manufactured or imported after January 1, 2009, to limit total wattage consumed by the

More information

The DEF-System by BRUGG. The Best Way to defeat the problem of DEF heat Installation Instructions

The DEF-System by BRUGG. The Best Way to defeat the problem of DEF heat Installation Instructions The -System by BRUGG The Best Way to defeat the problem of heat Installation Instructions -System Installation Instructions Content Page 3 Page 4 Page 5 Page 6 Page 7 Description of System Installation

More information