International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures
|
|
- Abraham Hardy
- 6 years ago
- Views:
Transcription
1 International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures Please note this is not an all-inclusive list. The type and complexity of your project may require additional details or engineering by a state licensed design professional. Failure to provide the minimum information required for plan review will result in plans being rejected or result in delays in the plan review process. The normal time frame for a plan review is ten (10) working days. Failure by the AHJ to identify a discrepancy during the plan review, DOES NOT grant the permit applicant the right to violate the fire code. Any fire code violation viewed by the fire code official must be corrected before final compliance inspection. All projects are subject to periodic field inspections and a final compliance inspection. An occupancy permit will not be issued until all requirements have been met. 1) Permit Required: Unless exempt or otherwise approved, a permit shall be obtained prior to beginning any construction or installation regulated by section Required Construction Permits, of the 2006 International Fire Code; A separate permit is required for each system, e.g. A design including two wet pipe fire sprinkler systems and one-pre-action system, will require a total of four permits three fire sprinkler permits and one fire alarm permit; Permit applications are available at the Bridgeport Charter Township Building Department; Permits shall be kept on the job site at all times and shall be readily available for inspection by the fire code official. 2) Construction Documents shall comply with the 2006 International Fire Code, sec Construction Documents, this document, and the following: a) Fire alarm systems NFPA 72, 2007 ed., National Fire Alarm Code, annex A ; b) Fire sprinkler sprinklers: i) NFPA 13, 2007 ed., Standard for the Installation of Sprinkler Systems, Chapter 22 Plans and Calculations; ii) NFPA 13D 2007 ed., Standard for the Installation of Sprinkler in One-and Two- Family Dwellings and Manufactured Homes, annex A.4.8; iii) NFPA 13R 2007 ed., Standard for the Installation of Sprinkler Systems in Residential Occupancies up to and Including Four Stories in Height, section 6.2, Working Plans. c) Standpipe and Hose Systems NFPA 14, 2007 ed., Standard for the Installation of Standpipe and Hose Systems, Chapter 8, Plans and Calculations;
2 d) Fire Pumps NFPA 20, 2007 ed., Standard for the Installation of Stationary Pumps for Fire Protection, section 5.2, Approval Required; e) Underground Fire Lines NFPA 24, 2007 ed., Standard for the Installation of Private Fire Service Mains and their Appurtenances, Section 4.1 Plans; f) Commercial Cooking Fire Suppression Systems NFPA 96, 2008 ed., Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations, section 10.9 Review and Certification; g) Clean Agent Fire Suppression System Documents NFPA 2001, 2008 ed., Standard on Clean Agent Fire Extinguishing System, Section Working Plans; h) Other systems submittals shall include plans, cut-sheets, calculations and other documents sufficient to verify that the system complies with applicable sections of the 2006 International Fire Code as adopted by the Township of Bridgeport. System designs not covered by the International Fire Code, shall comply with the applicable NFPA standards and/ or other applicable regulations. 3) General: a) Three complete sets of drawings and one submittal book (containing applicable cut-sheets, calculations, and other documents) shall be submitted for review. b) When field changes are made, as-built drawings shall be provided prior to the start of system acceptance testing. 4) Plans: a) Color plans are preferred as they simplify identification of system components and circuits; b) A summary description of the work to be permitted should be included on the first page of the plans: c) Note on the plans, AHJ is the Bridgeport Township Fire Department; d) Note the applicable codes under which the system is to be reviewed as of this revision date, these include: i) 2006 International Fire Code, as adopted by the Township of Bridgeport; ii) Latest edition of the applicable NFPA standard(s); iii) Other applicable statutes, codes and standards e) Plans shall be drawn in a clearly legible and professional manner; f) Plans shall indicate the job name, address, suite number, phase and/ or description of job; g) Plans shall indicate Type of Construction; h) Plans shall indicate the Use Group Classification for all parts of the building;
3 i) Plans shall identify the Occupancy and Number of Occupants on every floor (including basements) and all rooms or spaces; j) Plans shall show Means of Egress calculations used to determine exit requirements; k) Plans shall be drawn to scale (1/8 = 1 0 preferred) scale shall be indicated; l) Plans shall indicate any fire separations in the floor, ceiling and walls required by the code; m) Plans shall indicate location of all exit signs and emergency lighting; n) Plans shall include the Fire Department Key Box (Knox Box) location. Application for Knox Box is located at the Bridgeport Fire Department. Fire Code Officials will help to determine the size of the Knox Box for the occupancy in accordance with Section 506 of the 2006 International Fire Code; o) Ceiling height must be indicated; p) North shall be indicated; q) A legend identifying each symbol, component, make and model number, and quantity shall be provided; r) Symbols shall conform to the 2006 ed. of NFPA 170, Standard for Fire Safety and Emergency Symbols; s) Plans shall indicate the location of current and proposed fire hydrant locations; t) Construction documents shall be prepared by a registered design professional; u) Room name and/ or numbers, and room use shall be identified; 5) Specific Submittals: a) Fire Alarm Systems: i) In addition to the requirements of NFPA 72, 2007 ed., National Fire Alarm Code, annex A , the following shall be provided: (1) Calculations for each power supply shall be submitted; (Show how the existing power supplies were determined sufficient and/ or upgraded to support the modification.) (2) Point to point wiring and end-of-line (EOL) resistors shall be shown on plans;
4 (3) Pre-Testing is required: Before requesting final acceptance of the system, the applicant shall furnish a written statement that the system has been installed in accordance with the approved plans and has been tested in accordance with the manufacturer s published instructions and the appropriate NFPA standards. This statement shall be in one of the following forms, with the permit number clearly noted: (a) A letter on the alarm contractor s letterhead; or, (b) A preprinted form intended for such use; or, (c) A Record of Completion form in accordance with NFPA 72, 2007 ed., section 4.5 Documentation ii) In duct smoke detectors connected to the fire alarm system shall be installed in accordance with the approved plans and tested in accordance with the manufacturer s published instructions and NFPA 72, 2007 ed., Table (g) (4) Test Methods (Air duct detectors shall be tested or inspected to ensure device will sample the air stream. The test shall be in accordance with the manufacturer s instructions.) (1) The following must be submitted to the Bridgeport Fire Department (Attn: Fire Marshal), with the Permit number indicated as part of the final acceptance of the system: (a) A copy of the manufacturer s instruction describing the test methods and the acceptable range; (b) The individual measurements and differential calculations for each unit. The measurements and results must be on letterhead, signed by a representative of the fire alarm or HVAC contractor. b) Fire Sprinkler Systems: i) Water supplies shall be protected from contamination by a RPZ (Reduced Pressure Zone water backflow valve) installed between the water supply and the fire sprinkler system (Contact the Bridgeport Township Water Department at (989) , for specifications and requirements); (1) A copy of the Backflow Prevention Assembly Test and Maintenance Report must be submitted to the Bridgeport Fire Department (Attn: Fire Marshal) and Bridgeport Township Water Department (Attn: DPW Supervisor). ii) Plans shall include flow test results, working drawings with pipe sizes, spacing of branch lines and sprinkler heads; iii) Plans shall indicate sprinkler head type and hanger plan; iv) Visual inspections must be scheduled prior to installation of ceiling tiles or other visual obstructions. Unauthorized items attached to the sprinkler piping must be eliminated prior to approval. Visual inspections should coincide with the hydrostatic pressure tests, where applicable. (1) Main Drain test results and as-built drawings (if applicable) must be submitted prior to final acceptance.
5 c) Hood Suppression Systems: i) Show all piping, system detectors, manual-pull, class K extinguishers, placard, fuel shut-off device(s) and tank locations on plans; (1) A floor plan of the area indicating means of egress and component locations must be submitted. ii) An audible alarm and visual indicator shall be provided to show the system has activated; iii) Make-up air and fuel sources under the hood must shut-off upon activation exhaust fan(s) stay on; iv) Include manufacturer s nozzle application and installation sheet(s); v) Provide complete appliance descriptions, appliance layouts, cooking area dimensions (depth x width), hood shape and dimensions (depth x width), duct dimensions (depth x width) and nozzle height as necessary for proper selection and location of nozzles. d) Fire Service Mains: i) Fire Service Mains, Fire Hydrants and Fire Department Connections shall be installed in accordance with the International Fire Code 2006 ed., applicable NFPA standards and local codes and ordinances. ii) The following list may not include all requirements and is subject to modification. It is the responsibility of the designer/ installer to follow all applicable codes and standards. (1) Plans shall be drawn in a clearly legible and professional manner; (2) Plans shall indicate job name, address, suite number, phase and/ or description of the job; (3) North shall be indicated; (4) Plans shall be drawn to scale (1/8 = 1 0 preferred) scale shall be indicated; (5) Fire lanes shall be identified on plans; (6) Building height shall be indicated on plans; (7) The following details shall be shown, as applicable, on the plans (a) Thrust-block; (b) Embedment; (c) Vault (if present); (d) Riser; (e) Fire Department Connection (FDC) and related piping; (f) Backflow Prevention; (g) Piping; (h) Other related details.
6 e) Stationary Storage Battery System: i) Provide documentation showing how the system complies with, or is exempt from, each requirement of Section 608 of the 2006 International Fire Code. d) Storage of Flammable and Combustible Liquids: i) Provide documentation showing how the system complies with, or is exempt from, each requirement of Section 3404 of the 2006 International Fire Code and other applicable codes, standards, and regulations. e) Other Systems: i) Provide documentation showing how the system complies with, or is exempt from, each applicable requirement of the 2006 International Fire Code and other applicable codes, standards and regulations.
New Construction Fire Inspection Process
New Construction Fire Inspection Process This document is intended to provide the Owner, Designer, and/or Contractor of new construction with an outline of required fire inspections and with the specific
More informationAUTOMATIC FIRE SPRINKLER SYSTEMS
MCKINNEY FIRE DEPARTMENT FIRE MARSHAL S OFFICE AUTOMATIC FIRE SPRINKLER SYSTEMS These guidelines are to be followed when a business, facility or organization installs an automatic fire sprinkler system
More informationSeptember 30, Dear Fire Suppression System Contractor/Designer:
CITY OF BOZEMAN FIRE DEPARTMENT P.O. Box 1230 Bozeman, Montana 59771-1230 Phone (406) 582-2350 CITY OF BOZEMAN BUILDING DEPARTMENT 20 E Olive St, STE 208 Bozeman, Montana 59715-4790 Phone (406) 582-2375
More informationFire Permit Application
Fire Permit Application FOR STAFF USE ONLY Case Permit Number: Plan Number: Related permits: Project #: Responsibility for information Although designated Department staff members will help you with general
More informationFire Sprinkler Plan Submittal Form
Contents Fire Sprinkler Plan Submittal Form... 2 Standpipe Plan Review Submittals... 4 Fire Pump Plan Submittal Requirements... 6 Fire Alarm Plan Submittal Form... 8 Kitchen Hood Wet Chemical Submittal...10
More informationBold items are particular to the City of Euless
EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 8/2004 Fire Chief Lee Koontz Fire Marshal Paul Smith EFD-FMO 3-1 2003 International Fire & Building Code as Amended NFPA Standards
More informationGLENDALE FIRE DEPARTMENT FIRE MARSHAL S OFFICE
GLENDALE FIRE DEPARTMENT FIRE MARSHAL S OFFICE To: From: Subject: Whom It May Concern Carl Ray Austerman, Fire Marshal Contractor s Guide Welcome to the Glendale Fire Department s Contractors Guide. This
More informationFIRE SPRINKLER SHOP DRAWING SUBMITTAL REQUIREMENTS
Department of Fire Rescue & Emergency Services Fire Marshal s Office Dania Beach District 103 West Dania Beach Blvd. Dania Beach, Florida 33004 Office: (954)342-4262 Fax: (954)342-4265 FIRE SPRINKLER SHOP
More informationYORK COUNTY DEPARTMENT OF FIRE SAFETY BUILDING PLAN REVIEW REQUIREMENTS
YORK COUNTY DEPARTMENT OF FIRE SAFETY BUILDING PLAN REVIEW REQUIREMENTS The York County Department of Fire Safety reviews all commercial building plan submittals for compliance with the 2015 International
More informationEL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD
EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD INSTALLATION OF COMMERCIAL FIRE SPRINKLER SYSTEMS STANDARD #C-001 EFFECTIVE 03-25-2009 PURPOSE: To ensure that sprinkler plans submitted for review contain
More informationRancho Cucamonga Fire Protection District Prevention Bureau Standard
Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Updated: December 2016 for consistency
More informationFIRE INSPECTORS GUIDELINES FOR PLAN REVIEWS AND INSPECTIONS OF NEW CONSTRUCTION / ADDITIONS AND CHANGE OF OCCUPANCY
FIRE INSPECTORS GUIDELINES FOR PLAN REVIEWS AND INSPECTIONS OF NEW CONSTRUCTION / ADDITIONS AND CHANGE OF OCCUPANCY PLAN REVIEWS SITE PLANS: 1) Access to buildings (Volume V NC Building Code sections 602.6.1
More informationFire Sprinkler Submittal Requirements and Acceptance Testing
Lubbock Fire Marshal s Office 1601 Mac Davis Lane Lubbock, Texas 79401 806-775-2646 Fax 806-775-3508 fireprevention@mylubbock.us Fire Sprinkler Submittal Requirements and Acceptance Testing To all Registered
More informationWinnipeg Fire Department Fire Prevention Branch
Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of
More informationCommercial Remodel/ Add On Rules and Regulations
Commercial Remodel/ Add On Rules and Regulations Public Works and Community Development Department City of Shenandoah 29955 I-45 North Shenandoah, Texas 77381 281-298-5522 www.shenandoahtx.us Construction
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST FIRE AND LIFE SAFETY SYSTEMS FOR STRUCTURES FIVE OR MORE STORIES IN HEIGHT AND LESS THAN 75 FEET IN HEIGHT FROM THE POINT
More informationTo expedite the plan review and inspection processes, please refer to the information below.
Guidelines: The goal of the Denison Fire Department is to assist its customers in understanding our submittal, plan review and inspection process and policies, as they pertain to new construction. Familiarity
More informationSACRAMENTO FIRE DEPARTMENT FIRE PREVENTION DIVISION FIRE DEPARTMENT DEVELOPMENT SERVICES UNIT CONTRATOR INFORMATION PACKET
SACRAMENTO FIRE DEPARTMENT FIRE PREVENTION DIVISION FIRE DEPARTMENT DEVELOPMENT SERVICES UNIT CONTRATOR INFORMATION PACKET 1 SACRAMENTO FIRE DEPARTMENT FIRE PREVENTION DIVISION FIRE DEPARTMENT DEVELOPMENT
More informationModule 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements
Module 3 Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements 1 WATER-BASED SUPPRESSION SYSTEMS-PART TWO This module covers: 1. Ohio Building Code requirements and when and why
More informationSprinkler Permit Applications
REQUIREMENTS FOR NFPA 13 SYSTEM Building Inspections Sprinkler Permit Applications A complete application for a Sprinkler Permit will comply with the requirements of Chapter 8 of NFPA 13. Hydraulic calculations
More informationWEST VIRGINIA UNIVERSITY
WEST VIRGINIA UNIVERSITY Environmental Health and Safety (SOP) WV State Fire Marshal (SFM) Project Plans Review Process & Procedures West Virginia University Environmental Health & Safety Page 1 of 10
More informationMINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry
MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Fire Alarm Systems Plan Review Checklist Date: Permit Number: Business Name: Address: Fire Alarm System Submittal
More informationMay 1, Dear Fire Suppression System Contractor/Designer:
CITY OF BOZEMAN FIRE DEPARTMENT P.O. Box 1230 Bozeman, Montana 59771-1230 Phone (406) 582-2350 Fax (406) 582-2355 CITY OF BOZEMAN BUILDING DEPARTMENT 20 E Olive St, STE 208 Bozeman, Montana 59715-4790
More informationOklahoma. 265: Incorporated national codes and standards The following national codes and standards are incorporated by reference:
Oklahoma 310:451-1-3. Adopted references The Board of Health hereby incorporates by reference the International Code Council (ICC) 2006 (IBC) Edition International Building Code; the 2007 Edition Standard
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST TENANT IMPROVEMENTS Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved w/comments;
More informationMoreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline
Moreno Valley Fire Department Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 8, 2017 Alarm & Signaling Systems PURPOSE Fire alarm and signaling systems are designed to
More informationFlorida Building Code 2010
Introduction Florida Building Code 2010 Chapter 9 Fire Protection Systems This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors are familiar with
More informationLarge Family Daycare Guideline
Moreno Valley Fire Department Fire Prevention Bureau Large Family Daycare Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: April 10, 2017 Large Family Daycare Guideline Purpose
More informationEl Reno Fire Department Fire Alarm Plan Review Worksheet
El Reno Fire Department Fire Alarm Plan Review Worksheet This Fire Alarm Plan Review Checklist is provided as a guide to assist with your Fire Alarm Plan Review Submittal requirements. Please contact us
More informationGLENDALE FIRE DEPARTMENT FIRE MARSHAL S OFFICE
GLENDALE FIRE DEPARTMENT FIRE MARSHAL S OFFICE To: Contractors From: Charles Jenkins, Fire Marshal Subject: Contractor s Guide This guide is provided by the Fire Marshal as a service to the construction
More informationFIRE PREVENTION OFFICE Placer Hills Fire Protection District NEW PROJECT GUIDELINES
Established 1949 FIRE PREVENTION OFFICE Placer Hills Fire Protection District NEW PROJECT GUIDELINES The following are guidelines for new development. Any submitted plans must comply with these guidelines,
More informationFIRE SPRINKLER SYSTEMS POLICY
FIRE SPRINKLER SYSTEMS POLICY Revised 1/1/17 DESIGN AND SUBMITTAL REQUIREMENTS All new and existing fire sprinkler systems within the jurisdiction of the City Fire Department shall meet all of the applicable
More informationAUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations)
AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations) This standard applies to the design and installation of automatic fire sprinkler systems in conjunction with
More informationAPPENDIX H (DESIGN SUBMISSION CRITERIA)
APPENDIX H (DESIGN SUBMISSION CRITERIA) FIRE ALARM SYSTEM As per ACCORD standard Part 5, section 5.7 Fire Alarm System Design to be verified by ACCORD Chief Safety Inspector. Testing of the installation
More informationFIRE SPRINKLER SYSTEMS POLICY
FIRE SPRINKLER SYSTEMS POLICY VERSION 1.012/2015 FIRE SPRINKLER SYSTEMS Design and Submittal requirements All new and existing fire sprinkler systems within the jurisdiction of the City of San Mateo Fire
More informationCITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU FIRE ALARM / ELECTRICAL FIRE PLAN REVIEW CHECKLIST
CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU FIRE ALARM / ELECTRICAL FIRE PLAN REVIEW CHECKLIST DATE: PROJECT NO.: EXPIRATION DATE: STATUS: INFORMATION PROJECT ADDRESS:
More informationPLAN REVIEW SUBMITTAL GUIDE
PLAN REVIEW SUBMITTAL GUIDE Plans, specifications and other construction documentation for the initial plan review should be as complete as possible at the time of submittal. Use this convenient guide
More informationCALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL UL 300
CALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL UL 300 FREQUENTLY ASKED QUESTIONS CONCERNING COMMERCIAL COOKING PROTECTION Published by FIRE ENGINEERING DIVISION
More informationCITY OF PASADENA FIRE DEPARTMENT
Page 1 of 8 CITY OF PASADENA FIRE DEPARTMENT INSTALLATION OF COMMERCIAL SPRINKLERS (Revised 12/10/2014) SCOPE: This standard applies to the design and installation of automatic fire sprinkler systems in
More informationDesign & Construction Standards, Revised January
PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for fire-extinguishing systems other than water-based fire suppression systems.
More informationRocky Mountain Fire Protection District 4390 Eldorado Springs Drive Boulder, CO
Rocky Mountain Fire Protection District 4390 Eldorado Springs Drive Boulder, CO 80303 303-494-3735 Contractor s Checklist and Installation Guide TABLE OF CONTENTS Fire Protection Narrative........... 3
More informationBrighton Area Fire Authority
615 W. Grand River Ave. Brighton, MI 48116 o: 810-229-6640 f: 810-229-1619 January 14, 2019 Fire Alarm Contractors RE: Fire Alarm Credential & Submittal Requirements To Whom It May Concern: The following
More informationNASSAU COUNTY FIRE PROTECTION PERMIT APPLICATION
BUILDING PERMIT# Revised 6/30/15 AP# PERMIT # Cost $ Check# Receipt# NASSAU COUNTY FIRE PROTECTION PERMIT APPLICATION 5 TH EDITION (2014) OF THE FLORIDA BUILDING CODE IS IN EFFECT THE 2012 FLORIDA FIRE
More informationBlack Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment
Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment February 2017 Alberta Fire Code safety equipment maintenance requirements: The Black Diamond Fire Department has
More informationResidential-based Care Facility R-4 Guideline
Moreno Valley Fire Department Fire Prevention Bureau Residential-based Care Facility R-4 Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: April 7, 2017 Residential-based Care
More informationCommercial Rules and Regulations
Commercial Rules and Regulations Public Works and Community Development Department City of Shenandoah 29955 I 45 North Shenandoah, Texas 77381 281 298 5522 www.shenandoahtx.us Construction Documents Submit
More informationFlorida Building Code Chapter 9 Fire Protection Systems Advanced Course
Florida Building Code 2010 Chapter 9 Fire Protection Systems Advanced Course 1 Introduction This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors
More informationEL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD
EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD Installation of Residential Fire Sprinkler Systems STANDARD #C-002 EFFECTIVE 03-19-2009 PURPOSE: To ensure that sprinkler plans submitted for review contain
More informationWausau Fire Department Inspection Violation Code Listing (Modified) All Applicable Records
VIOLATION Code AISLES/EXITS NFPA 1-14.13.2.1 NFPA 1-14.4.1 NFPA 1-14.4.2.1 NFPA 101-7.10.9 Violation Codes Description Aisles and Exits Emergency Lighting Working Required emergency lighting systems shall
More informationCLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau
CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 Permit Type: 105.7.13 Control Number: A.0 Effective Date: 11/15/11 TITLE:
More informationYou are required to READ ALL PAGES. of this application
Fire/Smoke/Heat/CO Application Checklist You are required to READ ALL PAGES of this application NEW ROCHELLE FIRE DEPARTMENT 90 Beaufort Pl, New Rochelle, NY 10801 - (914) 654-2213 APPLICATION FOR FIRE/SMOKE/HEAT/CO
More informationPort of St Helens SIA Aircraft Hanger Scappoose, OR
Port of St Helens SIA Aircraft Hanger Scappoose, OR AUTOMATIC FIRE SPRINKLER SYSTEM REVISION 2 MARCH 12, 2018 Scope: Furnish and install foam and water fire protection system including underground entrance
More informationFIRE ALARM APPLICATION CITY OF MADISON HEIGHTS
FIRE ALARM APPLICATION CITY OF MADISON HEIGHTS www.madison-heights.org COMMUNITY DEVELOPMENT DEPARTMENT BUILDING DIVISION 300 W. THIRTEEN MILE RD. MADISON HEIGHTS, MICHIGAN 48071 (248) 583-0831 FAX (248)
More informationTRI-LAKES MONUMENT FIRE PROTECTION DISTRICT
TRI-LAKES MONUMENT FIRE PROTECTION DISTRICT LOCAL AMENDMENTS INTERNATIONAL FIRE CODE 2009 December 5, 2012 1 Chapter 1 Administration Chapter 5 Fire Service Features Chapter 9 Fire Protection Systems Chapter
More informationCarrollton Fire Rescue
Carrollton Fire Rescue Fire Prevention Division Guide for Construction 2016 edition 2 Carrollton Fire Rescue Prevention Division Table of Contents Fire Prevention Division... 3 General Guidelines... 4
More informationCommon Fire Code Violation Checklist. Listed are some of the most commonly found fire code violations and should not be considered as all inclusive.
Common Fire Code Violation Checklist Listed are some of the most commonly found fire code violations and should not be considered as all inclusive. Exterior Features All fire access roads signed per TFD
More informationCHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS
CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS 61G15-32.001 61G15-32.002 61G15-32.003 61G15-32.004 61G15-32.005 61G15-32.006 61G15-32.007
More informationPlan Submittal Checklist
City of Aurora Public Works Department HIGH-PILED COMBUSTIBLE STORAGE Plan Submittal Checklist Building Division 15151 E. Alameda Parkway, Ste 2400 Aurora, CO 80012 303-739-7420 Fax: 303-739-7551 Project
More informationSECTION (13900) - FIRE SUPPRESSION SYSTEMS
PART 1 GENERAL 1.01 SUMMARY SECTION 21 10 00 (13900) - FIRE SUPPRESSION SYSTEMS A. Section Includes: 1. Pipe and Fittings. 2. Sprinklers. B. Related Documents: 1. Marriott s Fire Protection and Life Safety
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD LICENSED CARE FACILITIES SCOPE: This standard provides requirements for licensed care facilities known as for the Elderly with seven
More informationCHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2012 EDITION
CHAPTER 23.45 LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2012 EDITION Sections 23.45.100... Local amendments to the International Fire Code, 2012 Edition.... 2 23.45.105.4.2 Information on construction
More informationLiberty Township Fire Department Fire Prevention Bureau. Clean Agent Fire Protection Plan Submittal Checklist
Liberty Township Fire Department Fire Prevention Bureau Clean Agent Fire Protection Plan Submittal Checklist Project Name: Date: Project Address: Designers Name: Company Name: Phone Number: Email: Fax:
More informationFIRE DEPARTMENT SYSTEM PERMIT APPLICATION
Permit No:_ FIRE DEPARTMENT SYSTEM PERMIT APPLICATION Thank you for submitting plans for the installation or modification of a required fire protection or detection system. Typical review of system plans
More informationSANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)
FIRE DEPARTMENT SANTA CLARA COUNTY 14700 Winchester Blvd., Los Gatos, CA. 95032-1818 (408) 378-4010 (408) 378-9342 (fax) www.sccfd.org STANDARD DETAILS & SPECIFICATIONS Spec No C-4 Rev. Date 03/10/10 SUBJECT:
More informationGENERAL AREAS OF INSPECTION
This information is intended to assist you in preparation for the annual high-rise inspection. This is not a complete list and the Inspector may identify other conditions or issues in the building that
More informationPlan Review Check List Fire Alarm System
Plan Review Check List Fire Alarm System EXCELSIOR FIRE DISTRICT 241OO SMITHTOWN ROAD SHOREWOOD, MN 55331 Alarm system must be installed according to NFPA 72, 2010 Edition, National Fire Alarm and Signaling
More informationINSPECTOR I SKILLS ADMINISTRATION
INSPECTOR I SKILLS ADMINISTRATION 1- Prepare inspection reports so that the report is clear and concise and reflects the findings of the inspection in accordance with the applicable codes and standards..
More information*HB0217* H.B. 217 H.B STATE FIRE CODE ACT AMENDMENTS. LEGISLATIVE GENERAL COUNSEL 6 Approved for Filing: C.R. Gilbert :11 PM 6
LEGISLATIVE GENERAL COUNSEL 6 Approved for Filing: C.R. Gilbert 6 6 02-04-13 2:11 PM 6 H.B. 217 1 STATE FIRE CODE ACT AMENDMENTS 2 2013 GENERAL SESSION 3 STATE OF UTAH 4 Chief Sponsor: James A. Dunnigan
More informationSPRINKLER PROTECTION OF COMBUSTIBLE CONCEALLED SPACES WITH LESS THAN 6 BETWEEN OPPOSITE FACES IN CAVITY.
STATE OF LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS OFFICE OF STATE FIRE MARSHAL CODE ENFORCEMENT AND BUILDING SAFETY 8181 INDEPENDENCE BOULEVARD, BATON ROUGE, LA 70806 800-256-5452 225-925-4920
More informationOsceola County Department of Fire Rescue and Emergency Medical Services
St. Number Dir Street Name Street Type Inspected Time of Day to be Re-inspected Zip Code Occupancy Type Emergency Contact Phone (Inc. Area Code) Building Owner Building Owner Mailing Address Bldg. Owner
More informationFIRE CODE. Coal City Fire District International Fire Code Update. 35 S. DeWitt Place Coal City, IL
. 2015 FIRE CODE 2015 International Fire Code Update Coal City Fire District 35 S. DeWitt Place Coal City, IL 60416 815-634-4700 Table of Contents SECTION 109 VIOLATIONS... 3 SECTION 111 STOP WORK ORDER...
More informationSTATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT
STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT The interaction of fire protection systems can be extremely complex. The detection of a fire in a building by an automatic device
More informationSAFETY. USE OF SAFETY CHECK LISTS A safety check for compliance with current regulations should be performed yearly.
SAFETY GENERAL Buildings must be designed according to building and fire safety codes and other regulatory standards at the time of construction. However, such codes and standards are continuously changing.
More informationConstruction and Development Guide
Construction and Development Guide **Based on the 2014 Indiana Fire Prevention Code and relevant NFPA Codes and Standards ** Copyright 2018 Clay Fire CRRD 1 P a g e Table of Contents Map of Jurisdiction...
More informationC I T Y O F B A N N I N G BANNING FIRE SERVICES 3900 W. WILSON STREET (951) PHONE (951) FAX
C I T Y O F B A N N I N G BANNING FIRE SERVICES 3900 W. WILSON STREET (951) 922-3210 - PHONE (951) 922-0318 - FAX CITY OF BANNING FIRE SERVICES STANDARD CONDITIONS OF APPROVAL FOR RESIDENTIAL BUILDINGS
More informationTitle: BFST1505 Syllabus
DEPARTMENT OF FINANCIAL SERVICES Division of State Fire Marshal Bureau of Fire Standards and Training Title: BFST1505 Syllabus Revision: April 5, 2018 Section I - Course Information Course Title: Fire
More informationMOBILE FOOD VENDING Food Trucks & Trailers
MCKINNEY FIRE DEPARTMENT FIRE MARSHAL S OFFICE MOBILE FOOD VENDING Food Trucks & Trailers These guidelines are to be followed when a business, facility or organization plans to operate a food truck or
More informationD. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following:
PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of Sam Houston State University for the design and construction of standpipe systems to include combination standpipe
More informationWelcome to the Keys to a Successful Fire / Life Safety Inspection and Sustained Tenant & Building Safety
Welcome to the Keys to a Successful Fire / Life Safety Inspection and Sustained Tenant & Building Safety 2017 Keys to a Successful Fire / Life Safety Inspection and Sustained Tenant & Building Safety First
More informationBurnsville Fire Department 100 Civic Center Pky, Burnsville, MN Fire Marshal: FAX:
Burnsville Fire Department 100 Civic Center Pky, Burnsville, MN 55337 Fire Marshal: 952-895-4579 FAX: 952-895-4512 2018 FIRE SUPPRESSION PERMIT APPLICATION PERMIT Wet System Dry System Cooking Hood Clean
More informationPLAN REVIEW CHECKLIST
PLAN REVIEW CHECKLIST Date Documents Submitted: Log No.: File No.: Property Information Building Name: Building Address: Owner s Name: Owner s Address: Owner s Phone: Fax: E-mail: System Designer/Contractor
More informationICC Update - Laboratory Issues Code Changes / Proposals / Trends of Interest 10/2005
ICC Update - Laboratory Issues Code Changes / Proposals / Trends of Interest 10/2005 Kenneth Kretchman, CIH, CSP Mgr, Industrial Hygiene NC State University Ken_Kretchman@ncsu.edu International Building
More informationAPPLICATION CERTIFICATE OF OCCUPANCY $50.00 FEE (non-refundable)
APPLICATION CERTIFICATE OF OCCUPANCY $50.00 FEE (non-refundable) CITY OF HALTOM CITY, TEXAS, 5024 BROADWAY AVE., HALTOM CITY, TEXAS 76117 Tel~hone - 817-222-7730 FAX - 817-222-7739 *** C/O APPLICATION
More informationVIOLET TOWNSHIP ZONING & BUILDING DEPARTMENT Rustic Drive Pickerington, Ohio (614) Fax (614)
VIOLET TOWNSHIP ZONING & BUILDING DEPARTMENT 12970 Rustic Drive Pickerington, Ohio 43147 (614) 575-5559 Fax (614) 575-5562 To: From: Subject: All Commercial Zoning and Building Permit Applicants Don Day,
More informationOCFA Planning and Development Section Fees Effective September 28, 2015
Description (IFP) PLANNING & SITE DEVELOPMENT PR0 PR4 PR5 California Environmental Quality Act (CEQA), Environmental Impact Report (EIR), Notice of Preparation (NOP), Advance Planning requests for information
More informationSECTION WET-PIPE SPRINKLER SYSTEMS
SECTION 21 13 13 WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SCOPE OF WORK A. Design, installation and testing shall be in accordance with NFPA 13 except for specified exceptions. B. The demolition
More informationD. Reference Standards (Utilize latest editions available):
1.01 Scope of Standard A. This standard provides general requirements of The Sam Houston State University for fireextinguishing systems other than water-based fire suppression systems. This document is
More informationHealth Chapter ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE
Health Chapter 420-5-22 ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE CHAPTER 420-5-22 SUBMISSION OF PLANS AND SPECIFICATIONS FOR HEALTH CARE FACILITIES TABLE OF
More informationMULTI-LEVEL & COVERED BOOTH CONDITIONS
MULTI-LEVEL & COVERED BOOTH CONDITIONS Covered Booth Definition To place something over or upon an exhibit or portion of an exhibit (e.g., roof, ceiling, tenting, lattice, fabric, plastic) to cover the
More information2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content
Based on the 2018 International Fire Code, (IFC ) The International Fire Code (IFC ), establishes minimum regulations for fire safety. This handout will identify important changes in the IFC from 2015
More informationENGINEERING/PLAN REVIEW - FEE SCHEDULE Exhibit A
CCCFPD ORDINANCE 2018 21 Date of Adoption July 10, 2018 ENGINEERING/PLAN REVIEW - FEE SCHEDULE Exhibit A Page 1 of 11 Review Number 1.1 1.2 PLAN REVIEW Preliminary Plan Review - Consultations - Meetings
More informationIs the address of your property clearly visible and marked in large numbers that can be easily seen from the street?
PRE-INSPECTION CHECKLIST THE FOLLOWING INFORMATION IS PROVIDED TO YOU TO ASSIST YOUR FACILITY IN BECOMING COMPLIANT WITH THE NEW YORK STATE FIRE CODE, LOCAL LAWS, AND ORDINANCES GOVERNING THE TOWN OF BABYLON.
More informationA. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:
SECTION 21 13 13 WET-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
More informationFIRE PLAN CHECK CORRECTION List for Commercial Occupancies
PASS / RESUBMIT Rancho Santa Fe Fire Protection District P.O. Box 410 18027 Calle Ambiente Rancho Santa Fe California 92067-0410 Tel. (858) 756-5971 Fax (858) 756-4799 FIRE PLAN CHECK CORRECTION List for
More informationDesign & Construction Standards, Revised January
PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for the design and construction of standpipe systems to include combination standpipe
More informationFIRE & LIFE SAFTEY STANDARD
Title: Effective Date: 01/01/14 Revised Date: 1/1/14 Code References: Title 16, Chapter 16.16 of the Roseville Municipal Code, NFPA 72 Note: This standard is a summary of Fire Department clarifications
More informationTAMARAC FIRE RESCUE DEPARTMENT FIRE PREVENTION BUREAU 6000 North Hiatus Road Tamarac, Florida Telephone: (954) , Fax: (954)
TAMARAC FIRE RESCUE DEPARTMENT FIRE PREVENTION BUREAU 6000 North Hiatus Road Tamarac, Florida 33321 Telephone: (954) 597-3800, Fax: (954) 597-3810 SITE PLAN REVIEW CHECKLIST A goal of the Tamarac Fire
More informationFirst Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM
of 25 7/30/2015 1:35 PM First Revision No. 49-NFPA 17A-2015 [ Detail ] Make the following change to 5.2.1.10.2: 5.2.1.10.2* The manual actuation device shall clearly identify the hazard protected and provide
More informationDenver Fire Department Fire Prevention Division
/A 505.1 505.1 Address: Clearly marked from street, Arabic numbers or alphabetical letters. Numbers shall not be spelled out. Address identification characters shall contrast with their background. Each
More informationMinimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016
1. Introduction The intent of this document is to establish minimum standards for the practice of fire protection engineering within the State of Oklahoma as conducted by licensed professional engineers.
More information