THE BASICS OF BUILDING FIRE PROTECTION DESIGN. RES Symposium April 18, 2017
|
|
- David Hampton
- 6 years ago
- Views:
Transcription
1 THE BASICS OF BUILDING FIRE PROTECTION DESIGN RES Symposium April 18, 2017
2 PRESENTER S BACKGROUND Ted Sherwood, PE, CFPS, LEED AP 5 years as a Code Enforcement Official and Division Head supervising all Construction Inspectors and performing Plan Reviews for the City of Rochester Building Bureau 125 HR Code Certificate required for New Building Officials 25 years of Fire Protection Design at Local National and International A&E firms Certified Fire Protection Specialist since 2000 Currently Lead Fire Protection Engineer & QA Engineer reviewing LaBella Associates Fire Protection Design across US Offices (NY, PA, OH, NC)
3 GOALS FOR THIS SESSION What we are going to cover Understand / Receive a Design Process For Fire Protection Systems in Buildings Learn Which Fire Protection Systems are in General Use and There Principles of Operation Understand which Codes Govern Fire Protection Systems Required Testing & Records Understand How to Determine What Fire Protection Systems are Required On Design Projects Free Codes Online Learn How to Evaluate a Water Supply The Alarm Side of Fire Protection Will Not Be Covered in this Presentation
4 FIRE PROTECTION ENGINEERING DESIGN PROCESS DETERMINE WHAT SYSTEMS ARE REQUIRED CREATE CONTRACT DRAWINGS PICK SYSTEM TYPE(S) DOWNLOAD & EDIT CSI SPECIFICATIONS EVALUATE WATER SYSTEM ESTIMATE WATER DEMAND (GPM & PRESSURE) FOR BUILDING CODE REVIEW OF APPLICABLE STANDARDS NFPA SECTIONS, OWNER, UNDERWRITER FOR SPECIFIC CASE DETERMINE WHICH TYPE OF BACKFLOW PREVENTION IS REQUIRED PERFORM HYDRAULICS (IF REQUIRED BY OWNER) OBTAIN QUALITY ASSURANCE REVIEW FROM SOMEONE IN ORGANIZATION HAVE AUTHORITY HAVING JURISDICTION (AND OWNER S UNDERWRITE IF APPLICABLE) REVIEW DRAWINGS REVIEW SUBMITTALS (HARDWARE / WORKING DRAWINGS / HYDRAULIC CALCULATIONS) ASK FOR CONTRACTOR S MATERIAL AND TEST CERTIFICATE FOR ABOVE GROUND PIPING FORM NFPA 13 AT END OF PROJECT
5 HOW TO DETERMINE WHAT FIRE PROTECTION SYSTEMS ARE REQUIRED ON YOUR PROJECT Current International Code Council (ICC) Building Codes $15
6 HOW TO DETERMINE WHAT FIRE PROTECTION SYSTEMS ARE REQUIRED ON YOUR PROJECT IBC USE Description (Example) OCCUPANCY A Assembly (Restaurants, Theaters, etc.) B Business (Offices, etc.) E Education (Schools) F Factory $15 H High Hazard (More Hazmat that shown in Table 307.1(1)) I Institutional (Assisted Living Facilities, Hospitals, Jails, etc.) M Mercantile (Stores) R Residential All Residential (Not Group I) S Storage U Utility (Agriculture and Misc., Also see Appendix C) Determine the IBC occupancy by asking Architect of Record rather than interpreting IBC yourself, where possible Ask Architect of Record if they want fire sprinklers for code benefits within their code (IBC) If project has work in existing building, the IEBC applies. Ask Architect of Record which compliance path they are using (alteration Level 1, 2, 3 change of occupancy, etc.), they are difficult to determine
7 HOW TO DETERMINE WHAT FIRE PROTECTION SYSTEMS ARE REQUIRED ON YOUR PROJECT Consider Owner s Standards (e.g. Sprinklers in all dorms in Universities) Find out if Owner has insurance underwriter and if underwriter has additional requirements such as factory mutual global $15 Determine what fire protection systems are required as a result of working through all the above
8 HOW TO EVALUTE A WATER SUPPLY Most Fire Protection Systems are Water Based Private Water Tank Regulated by NFPA 24 Standard for the Installation of Private Fire Service mains and their Appurtenances
9 HOW TO EVALUTE A WATER SUPPLY A REASONABLE HYDRANT FLOW TEST!
10 HOW TO EVALUTE A WATER SUPPLY Corroded Water Man Piping Showing the Importance of having a Hydrant Flow Test completed
11 HOW TO EVALUTE A WATER SUPPLY Same Corroded Water Main Piping End View
12 HOW TO EVALUTE A WATER SUPPLY Hydrant Flow Test Consists of Field Readings to Determine 3 Numbers: 1. Water Pressure at No Flow (Static Pressure) in PSI 2. Water Pressure at Any Known Flow in PSI 3. The Flow at that Pressure in Gallons Per Minute When 3 Numbers are Known, They Can Be Plotted on Semilog Paper (Also Know as 1.85 Paper) DU6 From: Station o NFPA 13 o o o Online Calculator Online Semilog Graph Paper The Blank in NFPA 291 Testing and Marking Hydrants You Can Only Remove Water Down to 20 PSI or You May Damage the Main
13 DEVELOPING THE FIRE WATER DEMAND For Water Based Systems, Fire Water Demand Consists of the Pressure and Flow Required by NFPA 13, but Modeled, Worked Back, to the Same Point in the Water System where the Hydrant Flow Test is Taken Two Methods for Determining Fire Water Demand: 1. Estimate the Pressure and Flow Independently and Combine 2. Full Hydraulic Calculations as Prescribed by NFPA 13
14 HOW TO EVALUTE A WATER SUPPLY 1. Estimate of Pressure and Flow Method (Use with Caution Requires Experience and Engineering Judgement) Estimate the GPM Flow: Look up the Hazard in NFPA 13 The GPM Required = [(gpm/ft 2 ) x ft 2 ] + [Waste %] + [Hose] Estimate Pressure Loss in PSI from Sprinklers Back to the Hydrant Flow Test Location. Use GPM Flow Developed above. Include the Following: Required Pressure to the Sprinklers Per NFPA 13 Safety Factor (10% or 10 PSI) Pressure Loss due to Height of Highest Sprinkler Pressure Loss to Friction in Building Piping Pressure Loss from Alarm Valve and Shutoff Valve(s) Pressure Loss from Backflow Preventer and Water Service Pressure Loss from Site Piping
15 HOW TO EVALUTE A WATER SUPPLY 2. Full Hydraulic Calculations as Prescribed by NFPA 13 o Sprinkcad by Tyco Inc. o Hass by HRS Systems Inc. o Auto Spink by MEP CAD Inc. The Resulting Estimate or Calculation of the GPM Flow and Pressure Low must be Plotted on the 1.85 Graph Paper and Be Under the Water System Curve (The Straight Line at the Top of the Graph) If Water Demand Point is Above the System Curve, You Do Not Have Enough Pressure and Flow to Design Code Compliant Protection System(s)
16 WHAT ARE THE BASIC FIRE PROTECTION SYSTEMS? Wet Pipe System WET PIPE SYSTEM RISER Note: Fire Department connection at the left. It bypasses most things that might go wrong. It is for the fire department to add water
17 WHAT ARE THE BASIC FIRE PROTECTION SYSTEMS? Wet Pipe System Delivers Water on Fire When Heat Boils the Glycol Mix in the Sprinkler Head and Glass Blub Explodes WET PIPE ALARM VALVE RETARD CHAMBER TRIM Delivers water on a fire when heat boils the glycol mix in the sprinkler head and the glass explodes
18 WHAT ARE THE BASIC FIRE PROTECTION SYSTEMS? Wet Pipe System How a wet pipe alarm valve with retard chamber opens, retards the alarms, delivers water to the fire and is drained
19 WHAT ARE THE BASIC FIRE PROTECTION SYSTEMS? Dry Pipe System Enables Water Based Suppression Where the Hazard Area is Below Freezing An air compressor (or nitrogen supply) is required to hold the valve closed and keep the water from freezing (below) Dry Piper Rise (top left) Wet Pipe Rise (top right) Full of air from the dry pipe value to the cold spaces
20 WHAT ARE THE BASIC FIRE PROTECTION SYSTEMS? Pre action System Helps Prevent Accidental Discharge or Water if a Head is Accidently Broken Takes two events to deliver water on the fire o o Heat on sprinkler head (s) to boil the glycol mix Electronic detection to pull the soleniod
21 WHAT ARE THE BASIC FIRE PROTECTION SYSTEMS? Clean Agent System Enables Protection of Mission Critical Equipment and Expensive Capital Equipment Typical Room Layout Liquid to Gas Discharge Pattern Halo Carbon Based Clean Agent Tanks, Dupont Novec 1230
22 WHAT ARE THE BASIC FIRE PROTECTION SYSTEMS? Hose Standpipes Enables Fighting a Fire in a Mid Rise Building Without Dragging the Hose Around and Around the Stairway
23 WHAT ARE THE BASIC FIRE PROTECTION SYSTEMS? Dry Chemical at for Gas Station Canopy Direct Application CO2 System Foam Deluge Foam Water Sprinkler Prevents a River of Fire in a Fuel Fire
24 WHEN DO YOU NEED A HOSE STANDPIPE?
25 WHEN DO YOU NEED A FIRE PUMP? Fire Pump, Skid Mounted, Diesel Drive Fire Pump, Skid Mounted, Electric Drive
26 WHEN DO YOU NEED A FIRE PUMP? Fire Pump is needed when the demand point is below the system line Fire pumps only come in listed sizes which can cause them to draw a larger GPM than the real demand point from the main Fire pumps must be run at 150% of their listed GPM capacity during the acceptance test This may draw 1.5 times the listed GPM from the main At Churn (aka deadhead) the max pressure is 1.4 times the Design Pressure
27 REQUIRED TESTING AND RECORDS BY OWNER From: NFPA 25: Table Summary of Sprinkler System Inspection, Testing, and Maintenance
28 REQUIRED TESTING AND RECORDS BY OWNER From NFPA 25: Table Summary of Fire Pump Inspections, Testing, and Maintenance
29 FREE ONLINE CODES Due to Veeck vs. Southern Building Code Congress International, a Federal Court Case in Louisiana in 2002, Building Codes Required by Law Must be Free CODE WRITING GROUP City of Rochester ICC NFPA Ohio AVAILABLE CODES LINK TO FREE CODE AT THIS WRITING DIRECTIONS 39 Building Code 54 Fire Code IBC IFC IEBC ALL NFPA CHAPTERS: 13 Sprinklers 14 Hose Standpipes 20 Fire Pumps 2001 Clean Agent 17 Dry Chemical 24 Private Water Supplies 16 Foam Systems 409 Aircraft Hangars 12 CO 2 IBC IFC IEBC Codes.html and standards/allcodes and standards/list of codes andstandards?mode=code&code=13&tab=editions Codes.html 1. Go to Link at Left 2. Click on the Book you Want 1. Go to Link at Left 2. Click on the Book You Want 3. Select the Chapter $15 1. Go to the Link at the Left 2. Click on the Section You Want 3. Current and Prior Additions Tab 4. Pick the Reference Standard Version (Date) You Need 5. Click on the View the Document Online Link 1. Go to the Link at Left 2. Click on the State You Want 3. Click on the Book You Want 4. Select the Chapter
30 TEST QUESTIONS 1 2 WHICH PART OF THE ICC CODES OF 2015 ADDRESSES ALTERATIONS TO BUILDINGS? THE INTERNATIONAL EXISTING BUILDING CODE MOST FIRE PROTECTION SYSTEMS ARE BASED. WATER 3 THE FIRE DEPARTMENT CONNECTION ON A FIRE SPRINKLERS SYSTEM IS USED FOR. ADDING WATER 4 5 ON A NEW BUILDING, A HOSE STANDPIPE SYSTEM IS REQUIRED IF THE HIGHEST OCCUPIED FLOOR IS MORE THAN FEET ABOVE THE LEVEL OF FIRE FIGHTER ACCESS. 30 WHAT NFPA SECTION REGULATES OWNER TESTING? NFPA 25
31 QUESTIONS
Fire Suppression Introduction Contact Information
Contact Information Jeffrey Mayers Fire Safety Engineering Manager Georgia State Fire Marshal s Office 404-617-8515 E-mail: jmayers@sfm.ga.gov 1 Goal of This Seminar: Hierarchy of Codes List reference
More informationUniversity of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL
SECTION 21 13 16 DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
More informationA. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:
SECTION 21 13 13 WET-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
More informationFIRE SPRINKLER SHOP DRAWING SUBMITTAL REQUIREMENTS
Department of Fire Rescue & Emergency Services Fire Marshal s Office Dania Beach District 103 West Dania Beach Blvd. Dania Beach, Florida 33004 Office: (954)342-4262 Fax: (954)342-4265 FIRE SPRINKLER SHOP
More informationCenter for Life Safety Education
Center for Life Safety Education Fire Sprinklers 101 Introduction, Building Codes, and Water Supplies Reprinted with permission from NFPA 13, Installation of Sprinkler Systems, Copyright 2007, National
More informationRevision May All designs must be submitted to FM Global for review and approval prior to issuing such for bids.
SECTION 211300 FIRE SUPPRESSION SYSTEMS 1.0 All new and renovated buildings shall be provided with automatic sprinklers throughout and fire standpipe systems. The design and installation of these systems
More informationA. This section includes design and performance information for fire protection and suppression systems.
SECTION 21 00 10: FIRE PROTECTION SYSTEM DESIGN 1. SUMMARY A. This section includes design and performance information for fire protection and suppression systems. 2. GENERAL A. All fire protection materials
More informationPLAN REVIEW CHECKLIST
PLAN REVIEW CHECKLIST Date Documents Submitted: Log No.: File No.: Property Information Building Name: Building Address: Owner s Name: Owner s Address: Owner s Phone: Fax: E-mail: System Designer/Contractor
More informationSECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE
SECTION 21 1316 DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE PART 1 GENERAL 1.01 SECTION INCLUDES A. Dry-pipe sprinkler system. B. System design, installation, and certification. C. Fire department
More information1 Exam Prep NFPA 14 Stand Pipe Systems Questions and Answers (Plumbing Contractors)
1 Exam Prep NFPA 14 Stand Pipe Systems Questions and Answers (Plumbing Contractors) 1. What is the minimum diameter for a non-hydraulically calculated Class III fire standpipe that is part of a combined
More informationB. The sprinkler system shall be designed to meet the more stringent of the requirements of NFPA 13 and FM Global requirements.
SECTION 21 13 13 FIRE PROTECTION SPRINKLER SYSTEMS PART 1 - GENERAL 1.01 SUMMARY A. Section includes labor and materials for the installation of a hydraulically calculated automatic, wet-pipe sprinkler
More informationAUTOMATIC FIRE SPRINKLER SYSTEMS
MCKINNEY FIRE DEPARTMENT FIRE MARSHAL S OFFICE AUTOMATIC FIRE SPRINKLER SYSTEMS These guidelines are to be followed when a business, facility or organization installs an automatic fire sprinkler system
More informationModule 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements
Module 3 Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements 1 WATER-BASED SUPPRESSION SYSTEMS-PART TWO This module covers: 1. Ohio Building Code requirements and when and why
More informationCONSTRUCTION REQUIREMENTS
CONSTRUCTION REQUIREMENTS Note: The buildings on the UCCS campus are divided into two categories: General Fund and Auxiliaries. General Fund Buildings include academic and administrative functions. Auxiliary
More informationPort of St Helens SIA Aircraft Hanger Scappoose, OR
Port of St Helens SIA Aircraft Hanger Scappoose, OR AUTOMATIC FIRE SPRINKLER SYSTEM REVISION 2 MARCH 12, 2018 Scope: Furnish and install foam and water fire protection system including underground entrance
More informationCITY OF MADISON FIRE DEPARTMENT (MFD) FIRE PROTECTION SYSTEM PLANS
CITY OF MADISON FIRE DEPARTMENT (MFD) FIRE PROTECTION SYSTEM PLANS Fire Protection Systems includes the following: Alternate Fire Suppression Systems Atrium Fire Protection Systems Automatic Fire Sprinkler
More informationFIRE SUPPRESSION SPRINKLER SYSTEM
PART 1 GENERAL 1.01 DESCRIPTION A. The provisions of the General Requirements, Supplementary Requirements, and Division 1 apply to the plumbing work specified in this Division. B. The requirements of this
More informationSECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE
SECTION 21 1316 DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE PART 1 GENERAL 1.01 SECTION INCLUDES A. Dry-pipe sprinkler system. B. System design, installation, and certification. C. Fire department
More informationCourse FP100 BACKFLOW PREVENTERS (BFPs) 101 FOR AUTOMATIC FIRE SPRINKLER SYSTEM M. Nabeel Waseem, M.Eng, PE, CFPS 2018
Course FP100 BACKFLOW PREVENTERS (BFPs) 101 FOR AUTOMATIC FIRE SPRINKLER SYSTEM M. Nabeel Waseem, M.Eng, PE, CFPS 2018 1 Introduction If you have ever been exposed to automatic fire sprinkler system, there
More information4/13/2015. Everything a firefighter wants to tell a design professional or building code official, in one hour.
Everything a firefighter wants to tell a design professional or building code official, in one hour. 1 2 3 1 4 The job of the fire department is to put the wet stuff on the red stuff. 5 Job #1. of the
More informationMcMAHON FP200 OUTAGAMIE COUNTY ADMINISTRATION CENTER S. WALNUT & W. 8TH, APPLETON, WI ALTERATION / ADDITION
4/5/017 1:58:50 PM C. 1445 DRIVE NEENAH, WI 54956 EXISTING JUSTICE CENTER IS FULLY SPRINKLED C. EXISTING FIRE PUMP BASEMENT LEVEL EXISTING FDC FOR DRY STANDPIPE IN STAIRWELL SHALL BE DEMOLISHED, SEE FP
More informationUNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1
GENERAL: 1. All fire protection systems shall be installed in accordance with the International Fire Code and applicable NFPA standards. This guideline provides additional requirements for the design and
More informationDivision 21: FIRE SUPRESSION WET-PIPE SPRINKLER PROTECTION SYSTEM. The Academy Sept Table of Contents 1 Division 21
Division 21: FIRE SUPRESSION 21 1313 WET-PIPE SPRINKLER PROTECTION SYSTEM Table of Contents 1 Division 21 SECTION 21 1313 WET-PIPE SPRINKLER PROTECTION SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A.
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST STANDPIPE SYSTEMS
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST STANDPIPE SYSTEMS Address: Permit #: Inspector: Date Inspected: Status: Inspector: Date Inspected: Status: A-Approved;
More informationAPPLICATION FOR INSTALLATION OF SPRINKLER SYSTEM.,. :" ROCHESTER, NH FIRE DEPARTMENT FIRE PREVENTION DIVISION
--= =--'" APPLICATION FOR INSTALLATION OF SPRINKLER SYSTEM.,. :"..~S" ".".,.,, " ROCHESTER, NH FIRE DEPARTMENT....~...... FIRE PREVENTION DIVISION 37 Wakefield Street.. Rochester, New Hampshire 03867"
More informationUBC Technical Guidelines Section Edition Fire Protection General Requirements Page 1 of 6
Page 1 of 6 1.0 GENERAL 1.1 Related UBC Guidelines.1 Section 20 00 05 Mechanical - General Requirements.2 Section 22 05 00 Plumbing - General Requirements.3 UBC Standard Fire Hydrant Drawings.4 Section
More informationSECTION (13900) - FIRE SUPPRESSION SYSTEMS
PART 1 GENERAL 1.01 SUMMARY SECTION 21 10 00 (13900) - FIRE SUPPRESSION SYSTEMS A. Section Includes: 1. Pipe and Fittings. 2. Sprinklers. B. Related Documents: 1. Marriott s Fire Protection and Life Safety
More informationGas Station & C Store SECTION CWM Job No
SECTION 21 1300 - PART 1 - GENERAL 1.1 WORK INCLUDED A. Provide labor, materials, equipment and services to perform operations required for the complete installation and related Work as required in Contract
More informationFire Protection System Contractors and Systems. Submission of the Application for a Water-Based Fire Protection Inspector Permit
NOTICE OF PROPOSED RULE DEPARTMENT OF FINANCIAL SERVICES DIVISION OF STATE FIRE MARSHAL RULE CHAPTER: RULE CHAPTER TITLE: 69A-46, F.A.C. Fire Protection System Contractors and Systems RULE: RULE TITLE:
More informationFire Sprinkler System Design and Installation Requirements
Fire Sprinkler System Design and Installation Requirements The Park City Fire Service District (PCFD) and Park City Municipal Corporation (PCMC) have made the following amendments to the State of Utah
More informationDesign & Construction Standards, Revised January
PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for the design and construction of standpipe systems to include combination standpipe
More informationPROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE
PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE Developed by the Midwestern Regional Work Group CONTENTS Item 15 Limited area sprinkler systems Item 20 Scope of IFC Ch 7 Item 21 Fire-resistance-rated
More informationDeluge/Preaction Systems Annotated Instructor s Guide
Deluge/Preaction Systems Annotated Instructor s Guide Module 18301-07 Module Overview This module covers different types of preaction and deluge systems. It discusses deluge valves, auxiliary detection
More informationDeluge/Preaction Systems Annotated Instructor s Guide
Deluge/Preaction Systems Annotated Instructor s Guide Module 18301-13 Module Overview This module covers different types of preaction and deluge systems. It discusses deluge valves, auxiliary detection
More informationSeptember 30, Dear Fire Suppression System Contractor/Designer:
CITY OF BOZEMAN FIRE DEPARTMENT P.O. Box 1230 Bozeman, Montana 59771-1230 Phone (406) 582-2350 CITY OF BOZEMAN BUILDING DEPARTMENT 20 E Olive St, STE 208 Bozeman, Montana 59715-4790 Phone (406) 582-2375
More informationFalse Sense of Security???
IS YOUR SPRINKLER SYSTEM GIVING YOU A FALSE SENSE OF SECURITY? Best Practices in Fire Safety An ASSE Virtual Symposium March 1 & 2, 2011 Walter S. Beattie CSP, CFPS, CSHM False Sense of Security??? Fire
More informationD. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following:
PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of Sam Houston State University for the design and construction of standpipe systems to include combination standpipe
More informationColorado Division of Fire Prevention & Control, Fire & Life Safety Section
Colorado Division of Fire Prevention & Control, Fire & Life Safety Section Partnering with Colorado s Fire Professionals to Protect Our Citizens from Fire November 24, 2015 Colorado Backflow Preventer
More informationCHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS
CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS 61G15-32.001 61G15-32.002 61G15-32.003 61G15-32.004 61G15-32.005 61G15-32.006 61G15-32.007
More informationFire Protection System Contractors and Systems. Submission of the Application for a Water-Based Fire Protection Inspector
NOTICE OF PROPOSED RULE DEVELOPMENT DEPARTMENT OF FINANCIAL SERVICES DIVISION OF STATE FIRE MARSHAL RULE CHAPTER: 69A-46, F.A.C. RULE: 69A-46.0165, F.A.C. RULE CHAPTER TITLE: Fire Protection System Contractors
More informationTable OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS
901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.
More informationEXHIBIT D ATTACHMENT G - UNIT PRICING DMS-14/15-039B - SIMPLEXGRINNELL, LP FIRE SPRINKLER SYSTEM INSPECTIONS YEARS 1-5
UNIT PRICING IS A "NOT TO EXCEED" PRICE EXHIBIT D ATTACHMENT G - UNIT PRICING DMS-14/15-039B - SIMPLEXGRINNELL, LP FIRE SPRINKLER SYSTEM INSPECTIONS YEARS 1-5 Unit Pricing to perform all required Test
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD STANDPIPE SYSTEMS PURPOSE This standard outlines the general requirements for the installation of standpipe systems. CODE REFERENCES
More informationFire Pump Supervision - Part 1 by Dean K. Wilson, P.E.
Fire Alarm Notebook by Dean K. Wilson. P.E. Page 1 Fire Pump Supervision - Part 1 by Dean K. Wilson, P.E. Question: As the Authority Having Jurisdiction in my suburban community, I have largely had to
More informationFIRE SUPPRESSION SYSTEM REVIEW APPLICATION 1. NEW PLAN REVIEW RESUBMITTAL
STATE OF LOUISIANA 10/09/2015 DEPARTMENT OF PUBLIC SAFETY - OFFICE OF STATE FIRE MARSHAL CODE ENFORCEMENT AND BUILDING SAFETY 8181 INDEPENDENCE BLVD., BATON ROUGE, LA 70806 800-256-5452 225-925-4920 FAX:
More informationReview of Residential Fire Sprinkler Systems for One- and Two-Family Dwellings
Review of Residential Fire Sprinkler Systems for One- and Two-Family Dwellings Reprinted with permission from NFPA 13D Installation of Sprinkler Systems in One- and two-family Dwellings and Manufactured
More informationSECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE
SECTION 21 1313 WET-PIPE SPRINKLER SYSTEMS PART 1 GENERAL 1.01 SECTION INCLUDES A. Wet-pipe sprinkler system. B. System design, installation, and certification. C. Fire department connections. 1.02 RELATED
More informationWestern Michigan University Facilities Management Engineering Division
Western Michigan University Facilities Management Engineering Division Design Guidelines for Facilities Construction: DESIGN GUIDELINE DG21-1 Fire Suppression Systems & Equipment I. GENERAL... 1 A. General
More informationFire Protection Coffee Break Training May 2016
Fire Protection Coffee Break Training May 2016 Introduction High-Rise Requirements Questions and Answers Agenda Overview Site Fire Access Aerial Access Power/Back-up Power Elevators and Access Sprinklers
More informationFIRE SERVICE FEATURES
CHAPTER 5 FIRE SERVICE FEATURES SECTION 501 GENERAL 501.1 Scope. Fire service features for buildings, structures and premises shall comply with this chapter. 501.2 Permits. A permit shall be required as
More information2015 Recommended Building Code with Amendments. The Executive Committee of the Central Iowa Code Consortium does ordain as follows:
2015 Recommended with Amendments A resolution of the Central Iowa Code Consortium recommending adoption of the 2015 edition of the International, regulating and governing the conditions and maintenance
More informationDIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses
PART 1 - GENERAL 1.1 SCOPE A. Through Class III Commodity Classification, up to 12.2m of single, double or multiple row rack storage, up to 14.6m building height (VanQuish Fire Sprinkler System). Cartoned
More informationEL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD
EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD Installation of Residential Fire Sprinkler Systems STANDARD #C-002 EFFECTIVE 03-19-2009 PURPOSE: To ensure that sprinkler plans submitted for review contain
More information1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements.
FIRE PROTECTION GENERAL INFORMATION 1.1 Refer to Section 230000 for General Mechanical Requirements. 1.2 Refer to Section 230529 for Hangers and Supports. 1.3 Refer to Section 230553 for Pipe and Equipment
More informationConstruction and Development Guide
Construction and Development Guide **Based on the 2014 Indiana Fire Prevention Code and relevant NFPA Codes and Standards ** Copyright 2018 Clay Fire CRRD 1 P a g e Table of Contents Map of Jurisdiction...
More informationElliot Gittleman, FPE - Principal ESH Consultants
Fire Protection Engineering viewpoint Elliot Gittleman, FPE - Principal ESH Consultants Fall 2002 Due Diligence If you have been an investor during the past three years, there is a good chance that directly
More informationPublic Input No. 4-NFPA [ Section No. 4.2 ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification
Public Input No. 4-NFPA 214-2013 [ Section No. 4.2 ] 4.2 * Fire Risk Analysis. A fire risk analysis shall be conducted. The following are some of the factors that shall be considered in determining the
More information2. Welding Materials and Procedures shall conform to the ASME Code.
PART 1 GENERAL 1.01 Scope of Standard A. The design guidelines contained herein include the requirements for systems, materials, fittings and valves utilized for fire protection systems at Sam Houston
More informationPRIVATE FIRE SERVICE INSTALLATION PACKET
PRIVATE FIRE SERVICE INSTALLATION PACKET The 2017 Edition supersedes all previous versions for Private Fire Service Installation To Whom It May Concern: SUBJECT: PRIVATE FIRE SERVICE INSTALLATION Illinois
More informationSecond Revision No. 20-NFPA [ Section No. 1.4 ] Supplemental Information. Submitter Information Verification. Committee Statement
Second Revision No. 20-NFPA 14-2015 [ Section No. 1.4 ] 1.4* Equivalency. Nothing in this standard is intended to prevent the use of systems, methods, or devices of equivalent or superior quality, strength,
More informationCLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau
CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 Permit Type: 105.7.13 Control Number: A.0 Effective Date: 11/15/11 TITLE:
More informationTHE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION
SECTION 21 1301- FIRE-SUPPRESSION SYSTEMS PART 1 - GENERAL 1.1 SUMMARY: A. This Section includes fire-suppression piping and equipment for the following building systems: 1. Wet-pipe, fire-suppression
More informationSECTION FIRE SUPPRESSION SYSTEMS
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. 1.2
More informationAmerican Fire Sprinkler Association. An Introduction to the IBC and IFC
American Fire Sprinkler Association Presents An Introduction to the IBC and IFC October 13, 2005 Speaker Roland Huggins, P.E. Vice President of Engineering and Technical Services American Fire Sprinkler
More informationDIVISION 21 FIRE SUPPRESSION
DIVISION 21 FIRE SUPPRESSION Table of Contents 21 00 01 General 21 00 02 Scope 21 00 03 Codes 21 00 04 Design Intent Report 21 00 05 Coordination with University of Minnesota Departments 21 00 06 Access
More informationDIVISION 21 FIRE SUPPRESSION FIRE SUPRESSION
DIVISION 21 FIRE SUPPRESSION 21 00 00 FIRE SUPRESSION 21 01 00 Operation and Maintenance of Fire Suppression 21 01 10 Operation and Maintenance of Water Based Fire Suppression Systems 21 01 20 Operation
More informationSPRINKLERS TABLE OF CONTENTS
SPRINKLERS TABLE OF CONTENTS SECTION 21 13 13 WET PIPE SPRINKLER SYSTEMS SECTION 211313 - WET PIPE SPRINKLER SYSTEMS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract,
More informationBy: Russell Bainbridge March 18th, 2016 FPE 596
By: Russell Bainbridge March 18th, 2016 FPE 596 Egress Analysis and Design California Polytechnic State University's Engineering IV building Fire Detection, Alarm and Communication Systems A warehouse
More informationBackflow Prevention for Fire Sprinkler Systems. State of Illinois Plumbing Code
Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code Backflow Prevention Fire safety systems connected to a public water supply will require a backflow prevention device between
More informationFIRE FIGHTER II APPLICATION PENNSYLVANIA VOLUNTARY FIRE SERVICE CERTIFICATION PROGRAM NFPA Edition
FIRE FIGHTER II APPLICATION PENNSYLVANIA VOLUNTARY FIRE SERVICE CERTIFICATION PROGRAM NFPA 1001 2008 Edition SECTION I Last Name First Name M.I. SSN (last four digits required) Street Address City State
More informationContren Learning Series Apprenticeship Training Program for Fire Sprinkler Fitters
Contren Learning Series Apprenticeship Training Program for Fire Sprinkler Fitters (Published jointly by American Fire Sprinkler Association and the National Center for Construction Education and Research.)
More informationFIRE INSPECTION CHECKLIST
Applicable Base Codes FIRE INSPECTION CHECKLIST Florida Fire Prevention Code, 5th Edition NFPA 1, Uniform Fire Code, Florida 2012 Edition NFPA 101, Life Safety Code, Florida 2012 Edition NFPA 13, 2010
More informationOxnard Fire Department 360 W. Second Street Oxnard, CA (805) Fax (805)
Oxnard Fire Department 360 W. Second Street Oxnard, CA 93030 (805) 385-7722 Fax (805) 385-8009 FIVE YEAR CERTIFICATION REPORT Service and maintenance report for automatic fire extinguishing systems, including
More informationOwner/Operator Guide for Successful Sprinkler and Fire Pump Systems
Owner/Operator Guide for Successful Sprinkler and Fire Pump Systems Adam Olomon, P.E. Associate Consultant Fire & Life Safety and Fire Protection Introduction Adam Olomon Licensed Professional Engineer
More informationC. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.
SECTION 218800 - FIRE PROTECTION 1. GENERAL A. Provisions of Division 1, GENERAL REQUIREMENTS, and Section 230000, MECHANICAL GENERAL CONDITIONS, and Section 230050, SEISMIC PROTECTION are a part of this
More informationFIRE INSPECTORS GUIDELINES FOR PLAN REVIEWS AND INSPECTIONS OF NEW CONSTRUCTION / ADDITIONS AND CHANGE OF OCCUPANCY
FIRE INSPECTORS GUIDELINES FOR PLAN REVIEWS AND INSPECTIONS OF NEW CONSTRUCTION / ADDITIONS AND CHANGE OF OCCUPANCY PLAN REVIEWS SITE PLANS: 1) Access to buildings (Volume V NC Building Code sections 602.6.1
More informationNfpa Fire Protection Guide To Hazardous Materials
We have made it easy for you to find a PDF Ebooks without any digging. And by having access to our ebooks online or by storing it on your computer, you have convenient answers with nfpa fire protection
More informationAUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations)
AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations) This standard applies to the design and installation of automatic fire sprinkler systems in conjunction with
More informationRESIDENTIAL MULTI-USE FIRE SPRINKLER SYSTEMS PERMIT SUBMITTAL REQUIREMENTS
History: RESIDENTIAL MULTI-USE FIRE SPRINKLER SYSTEMS PERMIT SUBMITTAL REQUIREMENTS Per the City adopted 2009 IRC, section R313, automatic fire sprinkler systems are required for all one and two family
More informationADDENDUM #3 DATE: August 8, 2018 Page 1 of 1. The Curators of the University of Missouri
ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1 TO CONTRACT DOCUMENTS ENTITLED: PROJECT MANUAL FOR: Women s and Children s Hospital New Water Service Main PROJECT NUMBER: CP172631 ADVERTISEMENT DATE: July
More informationHIGH-RISE RETROFIT ORDINANCES - NO and NO
INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: LAMC 91.8604 Effective: 9-06-90 DOCUMENT NO. P/BC 2002-054 Revised: 4-15-03 Previously Issued As: MGD 88 HIGH-RISE RETROFIT ORDINANCES - NO.
More informationWET-PIPE SPRINKLER SYSTEMS
SECTION 211313 - WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipes, fittings, and specialties. 2. Fire-protection valves. 3. Fire-department connections. 4. Sprinklers.
More informationFire Sprinkler Plan Submittal Form
Contents Fire Sprinkler Plan Submittal Form... 2 Standpipe Plan Review Submittals... 4 Fire Pump Plan Submittal Requirements... 6 Fire Alarm Plan Submittal Form... 8 Kitchen Hood Wet Chemical Submittal...10
More informationCubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM
SECTION 21 0000 AUTOMATIC FIRE SPRINKLER SYSTEM PART 1 GENERAL 1.1 QUALITY ASSURANCE A. Codes and Standards: 1. FBC (Florida Building Code 2015) 2. FBC (Florida Fire Code 2015) 3. NFPA #13R (Standard for
More informationSECTION WATER BASED FIRE SUPPRESSION SYSTEMS
PART 1: GENERAL 1.01 Scope of Standard A. This standard provides general guidance concerning the specific preferences of Texas State University-San Marcos for automatic fire sprinkler and standpipe systems.
More informationSprinkler Permit Applications
REQUIREMENTS FOR NFPA 13 SYSTEM Building Inspections Sprinkler Permit Applications A complete application for a Sprinkler Permit will comply with the requirements of Chapter 8 of NFPA 13. Hydraulic calculations
More informationDIVISION 21 - FIRE SUPPRESSION
DIVISION 21 - FIRE SUPPRESSION DESIGN CRITERIA It is the policy of UC Davis to install fire sprinkler systems in all new construction/facilities. If the building is classified as a pole barn, shed, carport,
More informationWater Purveyor s Guide to 2006 Fire Sprinklers in Single Family Dwellings
Water Purveyor s Guide to 2006 Fire Sprinklers in Single Family Dwellings Fire sprinklers have long been used in commercial buildings and large residential occupancies to provide economical life safety
More informationFIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University.
15500 - FIRE PROTECTION PART I DESIGN GUIDELINES A. General 1. Vertical fire pumps shall not be used at the University. 2. coupling piping shall be permitted for sprinkler and standpipe systems only. B.
More informationSUMMARY. Building receiving sprinkler credit: SPRINKLERED. Grade: 68. Percent of Building Sprinklered: 100% Sprinkler Demand Met: 91%
210 N CHURCH ST CHARLOTTE NC 28202-2256 MECKLENBURG COUNTY RISK ID: 32 NC99 040235 ON-SITE SURVEY: 4/1/2009 LAST UPDATE: 4/1/2009 SUMMARY Building receiving sprinkler credit: SPRINKLERED Grade: 68 Percent
More informationTECHNICAL DATA. 319a. January 27, 2012
January 27, 2012 319a 1. DEsCrIpTIoN (Refer to Figures 1-3.) Viking Electric/Pneumatic Double Interlocked Preaction Systems utilize a Viking deluge valve controlled by a pneumatic actuator (E.1), normally
More information2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content
Based on the 2018 International Fire Code, (IFC ) The International Fire Code (IFC ), establishes minimum regulations for fire safety. This handout will identify important changes in the IFC from 2015
More informationDistribution System Requirements for Fire Protection
Distribution System Requirements for Fire Protection AWWA MANUAL M31 Fourth Edition MANUAL OF WATER SUPPLY PRACTICES M31, Fourth Edition Distribution System Requirements for Fire Protection Copyright 1989,
More informationChapter 2: Identification, water and access
Chapter 2: Identification, water and access As you are approaching the occupancy to be inspected, take note of building and fire protection services. Put yourself in the shoes of a first arriving company
More informationInternational Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures
International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures Please note this is not an all-inclusive list. The type and complexity of your project
More informationBurnsville Fire Department 100 Civic Center Pky, Burnsville, MN Fire Marshal: FAX:
Burnsville Fire Department 100 Civic Center Pky, Burnsville, MN 55337 Fire Marshal: 952-895-4579 FAX: 952-895-4512 2018 FIRE SUPPRESSION PERMIT APPLICATION PERMIT Wet System Dry System Cooking Hood Clean
More informationMay 1, Dear Fire Suppression System Contractor/Designer:
CITY OF BOZEMAN FIRE DEPARTMENT P.O. Box 1230 Bozeman, Montana 59771-1230 Phone (406) 582-2350 Fax (406) 582-2355 CITY OF BOZEMAN BUILDING DEPARTMENT 20 E Olive St, STE 208 Bozeman, Montana 59715-4790
More informationSACRAMENTO FIRE DEPARTMENT FIRE PREVENTION DIVISION FIRE DEPARTMENT DEVELOPMENT SERVICES UNIT CONTRATOR INFORMATION PACKET
SACRAMENTO FIRE DEPARTMENT FIRE PREVENTION DIVISION FIRE DEPARTMENT DEVELOPMENT SERVICES UNIT CONTRATOR INFORMATION PACKET 1 SACRAMENTO FIRE DEPARTMENT FIRE PREVENTION DIVISION FIRE DEPARTMENT DEVELOPMENT
More informationFire Protection Systems Operation and Maintenance 3 PDH / 3 CE Hours
Fire Protection Systems Operation and Maintenance 3 PDH / 3 CE Hours United Facilities Criteria U. S. Department of Defense UFC 3-601-02 PDH Academy PO Box 449 Pewaukee, WI 53072 www.pdhacademy.com pdhacademy@gmail.com
More informationSECTION SPRINKLER SYSTEMS
SECTION 15325 SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Wet-pipe sprinkler systems. B. Preaction sprinkler systems. C. System design, installation, and certification. D. Fire department
More information