Releasing Systems. Rob Mennie Senior Consultant Gage-Babcock & Associates Ltd.
|
|
- Lionel Day
- 6 years ago
- Views:
Transcription
1 Releasing Systems Rob Mennie Senior Consultant Gage-Babcock & Associates Ltd.
2 Releasing Systems What is a releasing system? System designed to detect a fire Causes release of an extinguishing system in response to the fire
3 Types of Extinguishing Systems Releasing systems may control the release of: Sprinklers pre-action or deluge, water or foam, water mist Clean agents Inergen, Novec, Co 2, FM200
4 Releasing Systems Concept Three elements: Input detection Process sequence of operation Output notification, annunciation, and release of suppression agents Elements are similar to structure of a building fire alarm system, but different in detail
5 More Harm than Good? Fire suppression systems sometimes do more damage than fire Sprinklers spraying computer equipment or valuable artifacts Frozen piping in cold storage facilities Foam discharge on aircraft being serviced in hangars
6 More Harm than Good? Damage can result from fire suppression operating in absence of fire Sprinkler heads provide both fire detection and suppression Physically damaged sprinklers may discharge water as if activated Damaged piping has the same effect Even if there is a fire, water may inflict unacceptable damage
7 The Solution Separate fire detection and suppression activation Provide electrical detection of fire Prevent water release if sprinklers or piping are damaged Allow for use of systems that do not use water as a suppression agent
8 Releasing vs. Fire Alarm Systems Releasing systems: Use fire alarm equipment and components Do not meet Building Code requirements for building fire alarm systems Include functions not found in building fire alarm systems Provide detection only in limited area covered by associated fire suppression system
9 Codes and Standards Fire Alarm System BCBC CAN/ULC-S524 & CAN/ULC-S537 Clean Agent Releasing System no BCBC requirements Clean Agent Releasing systems not BCBCregulated nor mentioned in CAN/ULC-S524 Design is based on good engineering practice Installation and verification should follow ULC- S524 and ULC-S537 requirements for the systems/components provided
10 Why Use a Releasing Panel? Not all building fire alarm panels are listed for releasing Allows for continuous protection even if the building system is being serviced Less chance of accidental discharge during inspection of building system
11 Stand-alone Releasing Panels Panels must be listed by ULC for releasing Panels normally protect a single hazard Panels usually are pre-programmed with some releasing options Some panels are for pre-action systems and some for clean agent systems
12 Building Alarm Panels Most current panels have releasing capabilities Panel must be listed by ULC for releasing Panels may protect multiple hazards for single panel Releasing options normally selectable through panel software
13 Input Detection Automatic detection of a fire is based detection of heat Smoke light from flame
14 Heat Detection Heat detection is used where high-heatrelease fires are expected Types: Spot-type heat detectors Linear heat detectors (Protectowire)
15 Spot-Type Heat Detectors Spot-type heat detectors are used for area protection where a ceiling exists to bank heat Ex. Cold storage warehouse with pre-action sprinkler system
16 Linear Heat Detectors Linear heat detectors (Protectowire) are used: for detection near fuel sources that do not have a ceiling to bank heat where spot-type detectors are difficult to install Warehouse storage racks storage freezers Conveyor galleries
17 Smoke Detectors Smoke detectors are used where low-heat release or smoldering fires are expected Types: Spot-type smoke detectors Air aspirating smoke detectors
18 Spot-Type Smoke Detectors Spot-type smoke detectors are used for area protection where a ceiling exists and air currents are limited Small computer or server room Electrical rooms
19 Air Aspirating Smoke Detectors Air aspirating smoke detectors are used: for high value occupancy where expense is justified where greater sensitivity is required where spot-type detectors are difficult to install or service Large computer rooms Museums Atriums High voltage electrical rooms
20 Flame Detectors Flame detectors are used: for long range detection in large areas in outside areas where wind may move smoke and heat away from detectors Petrochemical plants Aircraft hangars
21 Manual Detection Manual detection is used as a backup for automatic detection It uses dedicated manual pull stations Manual pull stations are: clearly labeled for suppression agent releasing a different color from building pull stations at exits for egress from hazard area
22 Process and Output Sequence of Operation Releasing systems provide more control over response than building fire alarm systems Response: is based on a number of detectors or zones detecting fire may be automatically time-delayed manually delayed provides different stages of action
23 Pre-action Systems Common types of releasing sequences: Single interlock Double interlock
24 Deluge Systems Primarily open head sprinklers with solenoid release by single or cross-zoned signal
25 Cross-zoning: Process and Output Cross-Zoning helps reduce unwanted suppression agent discharges divides detectors into two zones Agent does not release unless at least one detector on each of two zones is activated First zone provides alarm Second zone provides releasing
26 Process and Output Automatic Time Delay Automatic time delay: provides time for occupants to leave the area is used where suppression agent may be harmful to human health provides time for investigation and prevention of unwanted agent release provides time for ancillary functions air handling door closers
27 Process and Output Manual Time Delay Manual time delay: uses an abort switch to prevent agent release while switch is held provides time for investigation and prevention of unwanted agent release while switch is held can be a mechanical delay in discharge piping
28 Process and Output Different Response Stages Cross-zoning: allows for escalating response First zone activation provides notification to start personnel response or evacuation calls fire department initiates alarm condition on building fire alarm system Second zone activation provides different notification signal releases suppression agent
29 Interaction with Base Building Fire Alarm System Releasing system must report: Alarm Supervisory Common Trouble
30 Additional Operations Building or Stand-alone systems may: Operate ancillary functions Air handling equipment Process equipment Shutdown equipment in hazard area Release motorized dampers to Seal room for some agents Pressure relief for Inergen
31 Device Types Alarm bells Alarm horns Strobe lights Notification Devices Signage Over exit/entrance doors for hazard area
32 Common Problems There are a number of common problems with: Releasing system panels Pre-action sprinkler system releasing Manual switches
33 Common Problems with Releasing System Panels Releasing solenoid connected to bell circuit rather than releasing panel Not listed for such service No releasing function if bells are by-passed Releasing function located on building fire alarm panel instead of releasing panel No suppression agent releasing if building system out of service Danger of accidental release during servicing
34 More Common Problems Releasing system not connected to building fire alarm system No alarm to other tenants May not be monitored
35 Common Problems with Pre-Action Sprinkler Releasing System Cross-zoned detection Pre-action sprinklers only release water after system detects fire and sprinkler activates because of heat If detection is cross-zoned, water will not release until: 1. First zone activates 2. Second zone activates 3. Sprinkler activates Required cross-zoning exists between electrical detection and sprinkler, not within electrical detection
36 More Common Problems Missing detectors Every space containing a pre-action sprinkler must contain a detector connected to the releasing panel Includes small rooms and closets Without this, no water is released (even if sprinkler operates) because the releasing panel will not activate if no detector exists in protected space
37 More Common Problems Abort switch on pre-action sprinkler system Water will not be released until sprinkler activates If sprinkler activates, water is immediately required to control fire Preventing water release is not appropriate
38 Common Problems with Manual Switches Manual release pull station same as building pull station May result in: accidental release of suppression agent delayed release if occupants do not understand system operation
39 More Common Problems with Manual Switches Abort switch is in isolated location Unless occupant can reach control panel or communicate with others, he is trapped while pressing abort switch
40 Any questions? Thank you for your attention.
SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)
FIRE DEPARTMENT SANTA CLARA COUNTY 14700 Winchester Blvd., Los Gatos, CA. 95032-1818 (408) 378-4010 (408) 378-9342 (fax) www.sccfd.org STANDARD DETAILS & SPECIFICATIONS Spec No C-4 Rev. Date 03/10/10 SUBJECT:
More informationUnified Fire Authority - Fire Prevention Bureau
Unified Fire Authority - Fire Prevention Bureau FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance
More informationDeluge & Preac tion Systems
Deluge & Preaction Systems Deluge Systems are normally used in special hazard installations where water must be applied to an entire area for protection. They use open sprinklers or spray nozzles attached
More information2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.
2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is
More informationFIRE SUPPRESSION SYSTEM
FIRE SUPPRESSION SYSTEM An effective fire suppression systems work fundamentally in three ways; The corner stone has to be an efficient means of early warning/detection. Followed by either an Oxygen reduction
More informationrpsa FIRE PROTECTION ENGINEERS
FIRE PROTECTION ENGINEERS R.P. SCHIFILITI ASSOCIATES, INC. P.O. Box 297 Reading, Massachusetts 01867-0497 USA 781.944.9300 Fax / Data 781.942.7500 Telephone Elevator Fire Safety: Elevator Recall and Elevator
More informationFire Sprinkler Plan Submittal Form
Contents Fire Sprinkler Plan Submittal Form... 2 Standpipe Plan Review Submittals... 4 Fire Pump Plan Submittal Requirements... 6 Fire Alarm Plan Submittal Form... 8 Kitchen Hood Wet Chemical Submittal...10
More informationMoreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline
Moreno Valley Fire Department Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 8, 2017 Alarm & Signaling Systems PURPOSE Fire alarm and signaling systems are designed to
More informationDoc. No Part No Rev. U * T*
Doc. No. 430545 Part No. 579-357 Rev. U *0579357T* Blank Page- Back of Front Cover Copyrights and Trademarks 2005-2018 Johnson Controls. All rights reserved. Specifications and other information shown
More informationVaults 5/03/2015. Introduction. Vault Types. Stand alone building Free standing structure VAULTS
Protect your Media Vault Protect your Assets Fire Protection Services Vaults Presented by Peter Glodic Introduction Vault Types VAULTS Vault Types Vault Construction Media Types Fire Types Extinguishing
More informationTABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2
Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2
More informationNFPA Changes
Chapter 21, Emergency Control Functions and Interfaces Summary. Chapter 21 is new. These requirements were formerly found in Chapter 6, Protected Premises Fire Alarm Systems. The term fire safety function
More informationCOURSE SYLLABUS FIRE ALARM AND FIRE SUPPRESSION SYSTEMS CORRESPONDENCE COURSE
COURSE SYLLABUS FIRE ALARM AND FIRE SUPPRESSION SYSTEMS CORRESPONDENCE COURSE 100130 Description The first part of the course presents the requirements for fire alarm systems. It describes the buildings
More informationSECTION TOTAL FLOODING ECARO-25 CLEAN AGENT FIRE EXTINGUISHING SYSTEM
SECTION 13966 TOTAL FLOODING ECARO-25 CLEAN AGENT FIRE EXTINGUISHING SYSTEM Display hidden notes to specifier by using Tools / Options / View / Hidden Text. PART 1 GENERAL 1.1 SECTION INCLUDES A. Total
More informationCAN/ULC-S INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS
2013 Randal Brown & Associates Engineering Ltd. 1 RANDAL BROWN & ASSOCIATES ENGINEERING LTD. CONSULTING ENGINEERS LIFE SAFETY & FIRE PROTECTION 105 6 LANSING SQUARE TORONTO, ONTARIO CAN/ULC-S1001-11 INTEGRATED
More informationSPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE CHEETAH Xi 50 CONTROL PANEL SYSTEM
SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Total Flood ECARO-25 TM clean agent fire suppression system utilizing HFC-125 as the fire extinguishing agent
More informationProtecting Your Property: Well Do You Know Your Fire Fire Systems Systems. Joe Szewczyk, Risk Control Consultant
Protecting Your Property: Protecting How Well Your Do Property: You Know How Your Well Do You Know Your Fire Fire Systems Systems Joe Szewczyk, Risk Control Consultant Joe Szewczyk, Risk Control Consultant
More informationSECTION 907 FIRE ALARM AND DETECTION SYSTEMS
SECTION 907 FIRE ALARM AND DETECTION SYSTEMS 907.1 General. This section covers the application, installation, performance and maintenance of fire alarm systems and their components in new and existing
More informationChecklist For Life Safety
INSPECTION CHECKLIST Date of Inspection: Location/Address: Weather Condition: Inspector: AFTER COMPLETING YOUR INSPECTION, TRANSFER YOUR CONCERNS/OBSERVATIONS TO THIS AREA Facility: Name: Staff Contact:
More informationFunctional Performance Test
Fire Alarm Control Panel & Fire Alarm Annunciator Panel Notify all building occupants that testing will be conducted. Fire alarm contractor shall have personnel with 2-way radios at the fire alarm control
More informationCAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015
CAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015 Fire Commissioning in Canadian Codes and Standards BACKGROUND Why Commissioning?
More informationAdvanced Fire Alarm Systems Training Program Outline (5 Day)
Advanced Fire Alarm Systems Training Program Outline (5 Day) Day 1 Prescriptive and Performance-Based Design Understand the methodology in accessing the threat of fire within a structure. Know the difference
More informationCAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning
CAN/ULC S1001-11 Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning Presentation To: Canadian Fire Alarm Association (CFAA) National Capital Region
More informationCAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS
RANDAL BROWN & ASSOCIATES ENGINEERING LTD. CONSULTING ENGINEERS LIFE SAFETY & FIRE PROTECTION 105 6 LANSING SQUARE TORONTO, ONTARIO CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY
More informationDetection, and Suppression Systems
Fire Detection, Protection, ti and Suppression Systems Objectives (1 of 5) Explain why all fire fighters should have a basic understanding of fire protection systems. Describe the basic components and
More informationRevised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required*
1.0 Description of Services Required: Revised March 2015 Fire Alarm Systems Verification Schedule I(A) Services *Manditory Site visit required* Perform the annual fire alarm system and sprinkler system
More informationAgency for Health Care Administration
Page 1 of 92 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS Type Memo Tag FED - KA100 - General Requirements - Other Title
More informationREED COLLEGE DEPARTMENT OF COMMUNITY SAFETY DEPARTMENTAL DIRECTIVE CSO FIRE & FIRE ALARM SYSTEM RESPONSE GUIDELINES
CSO FIRE & FIRE ALARM SYSTEM RESPONSE GUIDELINES Source: Departmental Directive issued by the CS Director. Original publication: January 27, 2011 Latest review & revision: August 2018 Departmental Policy
More informationFire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016
Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting Prepared Especially for : OSFM TEC 2016 Acceptance Testing 11-2008 Agenda Before you begin Completing the
More informationSPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL
SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with a Cheetah Xi 50 addressable detection and control system.
More informationEl Reno Fire Department Fire Alarm Plan Review Worksheet
El Reno Fire Department Fire Alarm Plan Review Worksheet This Fire Alarm Plan Review Checklist is provided as a guide to assist with your Fire Alarm Plan Review Submittal requirements. Please contact us
More informationRancho Cucamonga Fire Protection District Prevention Bureau Standard
Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Updated: December 2016 for consistency
More informationMECKLENBURG COUNTY FIRE MARSHAL S OFFICE
Effective Date: 11/01/02 Purpose: MECKLENBURG COUNTY To establish a set of guidelines for performance testing of all newly installed or upgraded fire alarm systems in order to ensure that all devices and
More informationFIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES
FIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES 1. The major objective is to provide an acceptable degree of life safety from fire in existing senior citizen lodges. This document
More informationI am Rick Jeffress and I handle sales for Fike Video Image Detection. We thank the AFAA for coordinating the venue for this presentation, and we
I am Rick Jeffress and I handle sales for Fike Video Image Detection. We thank the AFAA for coordinating the venue for this presentation, and we appreciate your taking the time to learn more about this
More informationSpecification/ Data Sheet
Specification/ Data Sheet TRITON RP Agent Release Control Panel FEATURES Agent Release Control Panel designed specifically for suppression release operation with: Four initiating device circuits (IDCs)
More information12/14/2013. Fire alarm and emergency power SPRINKLER HEAD
Fire alarm and emergency power SPRINKLER HEAD 1 Alert signal Alarm signal Fire detector Heat detector Smoke detector Smoke alarm 1. Detector locations 1. Fire detector locations (3.2.4.11) 2. Smoke detector
More informationFire Alarm System Fundamentals
Fire Alarm System Fundamentals Mircom is the largest and oldest privately owned fire alarm and life safety manufacturer in North America and 5th largest overall with 50 years of industry experience. Mircom
More informationNFPA CODE TESTING & INSPECTION. Requirements & Recommendations for. Licensed Florida Hospitals, Ambulatory Surgery Centers,
NFPA CODE TESTING & INSPECTION Requirements & Recommendations for Licensed Florida Hospitals, Ambulatory Surgery Centers, ICF/IID Healthcare, & In-patient Hospice Facilities per NFPA Life Safety Code 101
More informationBuilding Fire Safety in New York City s Existing Office Buildings
www.goldmancopeland.com Building Fire Safety in New York City s Existing Office Buildings Daniel Colombini, PE, LEED AP Principal, Director of Plumbing/Fire Protection Director of Plumbing and Fire Protection
More informationSPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL
SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with automatic detection and control. The work described in
More informationFire Alarm Wiring. Circuit types, styles and limitations
Fire Alarm Wiring Circuit types, styles and limitations What we will cover Types Classes Notification Appliance Circuits (NAC) Initiating Device Circuits (IDC) Signaling Line Circuits (SLC) Class A, B,
More informationDCSS (ACB) Data Center Fire Suppression Procedures
February 25th, 2016 DCSS (ACB) Data Center Fire Suppression Procedures Purpose: This document is intended for all individuals who have access to the data center at 1011 West Springfield Avenue, Advanced
More informationAn Overview of Extinguishing Systems for Computer Equipment
Risk Solutions An Overview of Extinguishing Systems for Computer Equipment Various types of automatic suppression systems are available for protecting computer equipment. This report discusses the uses
More informationSymbols for Control Panels
Symbols for Control Panels Symbol Description Control panel-basic shape FACP FSA FAA FTR ESR FAC Fire alarm control panel Fire systems annunciator alarm Annunciator panel-from NE 100, symbol 7.006 Fire
More informationFIRE INSPECTORS GUIDELINES FOR PLAN REVIEWS AND INSPECTIONS OF NEW CONSTRUCTION / ADDITIONS AND CHANGE OF OCCUPANCY
FIRE INSPECTORS GUIDELINES FOR PLAN REVIEWS AND INSPECTIONS OF NEW CONSTRUCTION / ADDITIONS AND CHANGE OF OCCUPANCY PLAN REVIEWS SITE PLANS: 1) Access to buildings (Volume V NC Building Code sections 602.6.1
More informationFIRE DETECTION & ALARM SYSTEM BASICS
FIRE DETECTION & ALARM SYSTEM BASICS. 8 Fernwood Road Florham Park, New Jersey 07932 Siemens Building Technoloiges, Inc. ii Table of Contents Fire Detection and Alarm System Basics 1 General System Types
More informationSPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM
SECTION 1 - GENERAL CONDITIONS SPECIFICATION FOR A TOTAL FLOOD I. SCOPE: This specification outlines the requirements for a Total Flood ECARO-25 TM clean agent fire suppression system utilizing HFC-125
More informationCOSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN
COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN Presented by Ian Levine June, 2016 Photo courtesy of Google Maps PRESENTATION OVERVIEW BUILDING
More informationCITY OF MADISON FIRE DEPARTMENT (MFD) FIRE PROTECTION SYSTEM PLANS
CITY OF MADISON FIRE DEPARTMENT (MFD) FIRE PROTECTION SYSTEM PLANS Fire Protection Systems includes the following: Alternate Fire Suppression Systems Atrium Fire Protection Systems Automatic Fire Sprinkler
More informationINTEGRATED LIFE SAFETY COMPLIANCE TESTING AND ITS PROCEDURES
INTEGRATED LIFE SAFETY COMPLIANCE TESTING AND ITS PROCEDURES By: Mehrdad Ghods Integrated Engineering Student Sept. 06, 2002 University of British Columbia Vancouver, BC i PREFACE: The purpose of this
More informationDate Issued: December 14, 2017 Revision: 2.1
2.1 1. Introduction A is implemented to ensure the fire safety of building occupants or a building area when the Fire Alarm System or a Fire Protection System has been temporarily disabled due to malfunction,
More informationCHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS
CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS 61G15-32.001 61G15-32.002 61G15-32.003 61G15-32.004 61G15-32.005 61G15-32.006 61G15-32.007
More informationSystem Test Report CLEAN AGENT
City of Black Hawk Fire Department 196 Clear Creek Street PO Box 68 Black Hawk, CO 80422-068 Office 303-582-0426 Fax 303-582-2229 www.cityofblackhawk.org System Test Report CLEAN AGENT Occupancy Information
More informationINSPECTION AND TESTING FORM
INSPECTION AND TESTING FORM Date: Time: SERVICE ORGANIZATION Name: Address: Representative: License No.: MONITORING ENTITY Contact: Monitoring Account Ref. No.: TYPE TRANSMISSION McCulloh Multiplex Digital
More informationPlan Review Check List Fire Alarm System
Plan Review Check List Fire Alarm System EXCELSIOR FIRE DISTRICT 241OO SMITHTOWN ROAD SHOREWOOD, MN 55331 Alarm system must be installed according to NFPA 72, 2010 Edition, National Fire Alarm and Signaling
More informationVideo Imaging Detection Systems
Video Imaging Detection Systems DESIGN SUPPLY INSTALL MAINTAIN your TRUSTED partner in fire safety STATE-OF-THE-ART FIRE DETECTION AND VIDEO SURVEILLANCE Due to the inherent nature of their design, many
More informationPWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R
Region Project Page 1 PART 1 - GENERAL 1.1 REFERENCES.1 CAN/ULC-S524-2006, Standard for the Installation of Fire Alarm Systems..2 CAN/ULC-S525-2007, Audible Signal Device for Fire Alarm Systems..3 CAN/ULC-S526-2007,
More information109-B Concord Drive Casselberry, FL DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72. Owner s Address: Owner's Phone Number:
109-B Concord Drive Casselberry, FL 32707 407.830.6500 DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72 Pg 1 of 4 Equity One 11180600 Owner/Representative: WO#: _Customer#: 1550 NE Miami Garden Dr
More informationTECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014
January 16, 2014 Release Control Panel 290a 1. Description The Viking VFR400 is a microprocessor based releasing control panel for use on preaction, deluge, Surefire, Firecycle multicycle sprinkler systems,
More informationSECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD
PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard
More informationSmoke Detector Activation of any smoke detector shall start the alarm verification mode.
Description: The purpose of the section is to provide the UMCP Design Standards for the design and implementation of Fire Alarm Systems at the UMCP campus. Related Sections: TBD Effective Date: July 10,
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017
SECTION 21 2400CA - CLEAN AGENT CHEMICAL SUPPRESSION SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
More informationGlobal Property. QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:
Global Property QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Plant: Date of Inspection Location: Inspected By: Reviewed By CONTROL VALVES (If Valves are Not Locked Open or Electronically Supervised
More informationFDF Foam Pump Controllers Features
FDF100 Diesel Engine Foam Pump Controllers 1-1 Product Description The FDF Series of Foam Pump Controllers are designed for use with foam concentrate injection, foam transfer and water mist systems for
More informationa) Establishment of emergency procedures to be followed at the time of an emergency;
5.10 Fire Safety 5.10.1 Introduction The Corporation is responsible for carrying out the provisions of the Ontario Fire Code. This section outlines our responsibilities as well as inspections and testing
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT DANNY'S KNITWEAR LTD. ACCORD ID: 12228 SURABARI, GAZIPUR, SADAR, GAZIPUR Other Factories: ne October 17, 2015 Page 2 Fire Safety Inspection Report Introduction manufacturing
More informationDivision 28 - Electronic Safety and Security
Division 28 - Electronic Safety and Security 28 31 11 Fire Alarm Systems Fire alarm systems shall be installed in buildings when required by this section. 1. Purpose: The primary purpose of a fire alarm
More informationFIRE SAFETY PRACTICES AND PROCEDURES
FIRE SAFETY PRACTICES AND PROCEDURES One of the most costly and destructive causes for loss of life and property that the City could experience would be from a major fire. Reporting Fires All employees
More informationUNPRECEDENTED SPEED ULTIMATE POWER. EXTREME intelligence
UNPRECEDENTED SPEED ULTIMATE POWER EXTREME intelligence Fike offers you a revolutionary advancement in fire safety and protection. Our innovative Cheetah Xi system saves lives and valuable assets through
More informationWinnipeg Fire Department Fire Prevention Branch
Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of
More informationBlack Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment
Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment February 2017 Alberta Fire Code safety equipment maintenance requirements: The Black Diamond Fire Department has
More informationSPECIFICATION: CARBON DIOXIDE ENGINEERED FIRE SUPPRESSION SYSTEM
1. GENERAL SPECIFICATION 1.1 An Engineered Carbon Dioxide Fire Suppression System shall be installed to meet a minimum design concentration of %, by volume in all designated spaces/areas to be protected.
More informationINFORMATION BULLETIN
INFORMATION BULLETIN Revised: April 9, 2013 Ministry of Justice Emergency Management BC Fire Safety Planning for Construction and Demolition Sites The purpose of this Information Bulletin is to provide
More information3.1 Introduction. 3.1 Introduction
DEPARTMENT OF ARCHITECTURE ABUBAKAR TAFAWA BALEWA UNIVERSITY, BAUCHI ARC 624: ADVANCED BUILDING SERVICES LESSON 3: FIRE DETECTION AND ALARM SYSTEMS IN BUILDINGS 3.1 Introduction 3.1 Introduction 3.2 Conventional
More informationExplosion Protection Engineering Principles
Handbook of Fire and Explosion Protection Engineering Principles for Oil, Gas, Chemical and Related Facilities Second edition Dennis P. Nolan ELSEVIER AMSTERDAM BOSTON HEIDELBERG LONDON NEW YORK OXFORD
More informationActive & Passive Fire Protection System. Page 1 Kalidasan S BT IN SSP-OP
Active & Passive Fire Protection System Page 1 Kalidasan S BT IN SSP-OP Fire Protection - Introduction Introduction: The definition of fire protection of a building refers to the building ability to detect,
More informationSPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPULSE VALVE, FK AGENT & CHEETAH Xi 50 CONTROL PANEL
SECTION 1 GENERAL CONDITIONS I. SCOPE: SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH This specification outlines the requirements for a Total Flood Clean Agent Fire Suppression System utilizing
More information(h) Pesticide Application.
Fire Code Cannabis Amendment Section 13.20.066 is added to the Marysville Municipal Code to read in its entirety as follows: 13.20.066 Cannabis Growing, Processing, or Extraction Facilities (a) Application.
More informationSPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPULSE VALVE, FK AGENT & CHEETAH Xi CONTROL PANEL
SECTION 1 GENERAL CONDITIONS I. SCOPE: SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM This specification outlines the requirements for a Total Flood Clean Agent Fire Suppression System utilizing
More informationPakenham Branch Library Section MacFarlane Street MULTIPLEX FIRE ALARM SYSTEM Project No Page 1 of 12
Project No. 16563.001 Page 1 of 12 1. General 1.1. WORK INCLUDED 1.1.1. Section 26 05 01 GENERAL INSTRUCTIONS FOR ELECTRICAL SECTIONS. 1.1.2. Section 26 05 04 SUBMITTALS/SHOP DRAWINGS. 1.1.3. Section 26
More informationBalloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition
Copyright National Fire Protection Association 2013. All rights reserved. This copy is solely for your personal, noncommercial use in connection with participation in the NFPA Standards Development Process.
More informationAEGIS FEATURES DESCRIPTION. Conventional Fire Alarm-Suppression Control Unit. Effective: March Programmable Relays
AEGIS Conventional Fire Alarm-Suppression Control Unit FEATURES Agency Approvals FM Approved FM Approved to ANSI/UL 864, 9th edition FM Approved to ULC-S527-99 Other domestic U.S. approvals/listings pending/
More informationICC CODE CORNER 2012 IFC Code & Commentary
SECTION 910 SMOKE AND HEAT VENTS 910.1 General. Where required by this code or otherwise installed, smoke and heat vents or mechanical smoke exhaust systems and draft curtains shall conform to the requirements
More informationSPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPUSLE VALVE, Fike FK AGENT & SHP PRO CONTROL PANEL
SECTION 1 GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Total Flood Clean Agent Fire Suppression System utilizing FK-5-1-12 as the fire extinguishing agent and with a
More informationFIRE SAFETY PLAN. BUILDING NAME: Pathobiology / AHL BUILDING NUMBER: 089. DATE: 15-August-10 FPO #2
FIRE SAFETY PLAN BUILDING NAME: Pathobiology / AHL BUILDING NUMBER: 089 DATE: 15-August-10 FPO #2 INDEX Introduction 2 Locations of Fire Safety Plans 3 Forward 4 Audit of Building Data 5-6 Fire Fighting
More informationAmerican Society of Safety Engineers Professional Development Conference June 9-12, Fire Protection. Stephen J.
American Society of Safety Engineers Professional Development Conference June 9-12, 2008 Session No. 101F Fire Protection Stephen J. Musur CSP, CFPS Chubb Group of Insurance Companies June 12, 2008 1 Fundamentals
More informationFIRE PROTECTION SYSTEMS
CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall specify where fire protection systems are required and shall apply to the design, installation and
More informationFlorida Building Code Chapter 9 Fire Protection Systems Advanced Course
Florida Building Code 2010 Chapter 9 Fire Protection Systems Advanced Course 1 Introduction This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors
More informationFIRE PROTECTION SYSTEMS
CHAPTER 9 FIRE PROTECTION SYSTEMS > SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall specify where fire protection systems are required and shall apply to the design, installation,
More informationBP U.S. Pipelines and Logistics (USPL) Safety Manual Page 1 of 6
BP U.S. Pipelines and Logistics (USPL) Safety Manual Page 1 of 6 1. Purpose This policy sets forth requirements for preventing and detecting fires, sounding an alarm, and suppressing fires. Fire protection
More informationHi, welcome to the topic on Fire Detection and Alarm Systems. This topic forms one of the critical knowledge areas for prospective fire safety
Hi, welcome to the topic on Fire Detection and Alarm Systems. This topic forms one of the critical knowledge areas for prospective fire safety manager. As the appointed fire safety manager for a premise,
More informationFlorida Building Code 2010
Introduction Florida Building Code 2010 Chapter 9 Fire Protection Systems This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors are familiar with
More informationCHILD CARE CENTER INSPECTION CHECKLIST 06C
CHILD CARE CENTER INSPECTION CHECKLIST 06C OCCUPANCY-SPECIFIC FIRE S November 2006: Kansas State Fire Marshal Page: 29 November 2006: Kansas State Fire Marshal Page: 30 CHILD CARE CENTERS & PRESCHOOLS
More informationAgency for Health Care Administration
Page 1 of 100 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS CFR Type Memo Tag FED - KA100 - General Requirements - Other
More informationStandard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.
A28.1 Standard of Practice - Fire Alarm Systems NOTE: Significant revisions or additions to the previous standards are highlighted in italics. OBJECTIVE OF STANDARD To provide compliant smart addressable
More informationRelease Control Fire Alarm Systems
SYSTEM ABORT PUSH AND HOLD COIL SUPERVISION MODULE (2 AMP) 2081-9046 RED INSTALLATION INSTRUCTIONS 574-437 REV YEL NAC+ MAINTAIN 1/4" SEPARATION BETWEEN POWER LIMITED (RED/) AND NONPOWER S LIMITED (YEL/)
More informationFire suppression systems for server rooms and data centres
Fire suppression systems for server rooms and data centres Fire suppression systems for server rooms and data centres Fire suppression systems for server rooms and data centres are essential to the server
More informationThermoCable Linear Heat Detection System
ThermoCable Linear Heat Detection System Estimating Guide 1. INTRODUCTION 1.1 Linear Heat Detection ThermoCable digital linear heat detection wire is a combination of advanced polymer and digital technologies
More information5 Key Stages to Risk Assessment
5 Key Stages to Risk Assessment Stage 1: Identify Fire Hazards For a fire to start, three things are needed: A source of ignition Fuel Oxygen If any one of these is missing, a fire cannot start. Taking
More information