TLS-300 UST Monitoring and Leak Detection System

Size: px
Start display at page:

Download "TLS-300 UST Monitoring and Leak Detection System"

Transcription

1 Part 1 General System Requirements 1.1 Description TLS-300 UST Monitoring and Leak Detection System A. These Specifications are intended to provide information by which prospective bidders may understand the requirements relative to furnishing and installing a monitoring system for underground liquid storage tanks and associated below-grade product piping. B. These specifications shall describe specifically a continuous underground monitoring and leak detection system that shall perform in accordance with Subpart D of 40 CFR 280 and, as a standard of performance and quality, shall meet the performance specifications and functions of the Veeder-Root Company TLS-300 UST Monitoring system. C. The underground storage tank monitoring system shall meet all applicable standards and regulatory agency requirements including, but not limited to, the standards and requirements of the following: 1. American National Standards Institute (ANSI) 2. American Petroleum Institute (API) 3. American Society for Testing and Materials (ASTM) 4. Environmental Protection Agency (EPA) 5. National Bureau of Standards (NBS) 6. National Electrical Code (NEC) 7. National Fire Protection Agency (NFPA) 8. Underwriters Laboratories Inc. (UL) 9. Canadian Standards Association (CSA) 10. Canadian Underwriters Laboratories Inc. (cul) 11. Underground Storage Tanks: Subpart D, 40 CFR Part Federal Communications Commission (FCC) 13. British Approval Service for Electrical Equipment in Flammable Atmospheres (BASEEFA) 14. Factory Mutual (FM) Part 2 Operational Specifications 2.1 In-Tank Leak Detection A. The system shall utilize in-tank probes based on the magnetostrictive principle for liquid level measurement and in-tank leak detection. TLS-300 UST Monitoring and Leak Detection System Rev. C

2 B. The tank gauge shall be capable of performing a static tank tightness test to an accuracy of 0.1 GPH with at least a 98% probability of detection [P(D)] and no more than 1% probability of false alarm [P(FA)]. C. The system shall have the ability to be programmed to run a static 0.2 GPH quick leak test. This quick static leak test will take one hour, and commence 30 minutes after the last dispensing cycle, or five hours from the last delivery, whichever is greater. 2.2 Environmental Compliance Reports A. The system shall have the ability to provide a record of the last three occurrences of each type of alarm or warning condition detected by the system. B. The system shall provide the following types of reports related to environmental compliance matters: 1. System status messages 2. In-tank warning and alarm messages 3. In-tank tightness evaluation report 4. External input messages 2.3 Product Inventory Control (Tank Gauging) A. The tank management system shall collect product height and temperature data from up to eight magnetostrictive level sensors and compute gross and temperaturecompensated net gallons. The operator may choose from inventory or delivery information to generate a complete set of printed inventory or delivery reports. B. The system shall automatically generate an inventory increase report when a delivery of product to a tank has taken place. The report shall include the time and date of the delivery, the starting volume in the tank, the ending volume in the tank, the starting temperature of the fuel, the ending temperature of the fuel, and the inventory increase amount. C. The system shall have the ability to store up to ten of the most recent inventory increases in memory for business management purposes. D. The system shall provide the ability to monitor aboveground storage tanks, as well as underground storage tanks, for inventory management. 2.4 Inventory Management Reports A. The system shall monitor inventory in U.S., Metric or Imperial units for up to eight tanks and produce a combination of automatic and manual reports for each tank, which include the following information: TLS-300 UST Monitoring and Leak Detection System Rev. C

3 1. Fuel volume 2. Fuel height 3. Water height 4. Fuel temperature 5. Ullage 6. Temperature-compensated fuel volume 7. Last inventory increase amount 8. Last in-tank leak test results 9. Time and date 10. Tank identification 11. Fuel type identification % ullage B. A printout of the inventory status report shall be generated any time the operator presses the print button while the system is in the normal operating mode, or generated automatically four times a day with the information stored in memory. C. The system shall provide an automatic delivery report, programmed to print from 1 to 99 minutes after a bulk delivery to a tank is complete. The information shall include station header, product label, date, starting and ending time, starting and ending volumes, temperature of the fuel, as well as the net volume increase. The information shall be available in U. S., Metric or Imperial units. D. The system shall be able to generate reports in a display/printer format as well as a computer format upon demand. 2.5 Communications A. The tank monitoring system shall provide the ability to communicate with locally attached electronic devices through an RS-232 port, or remote locations via either an RS-232 port or internal modem. The system shall provide data in a display or packed computer data format. B. The communications protocol shall be Veeder-Root standard serial communications protocol or compatible. C. The tank monitoring system shall provide all reports available on the integral printer through the communications port. These shall include all reports associated with inventory management, environmental compliance and diagnostics/troubleshooting. D. The system shall provide for setup and configuration through the communications port using the Veeder-Root standard serial communications protocol or compatible Serial Communications TLS-300 UST Monitoring and Leak Detection System Rev. C

4 A. The system shall provide an RS-232 communications interface for data transmission to a computer, point of sale terminal, printing device, or a modem for remote communications. B. The system shall provide an auxiliary RS-232 communications interface for linking to a second tank monitoring system Wide Area Network Software (Remote Monitoring) A. The manufacturer shall provide a communications/database software package to poll remote tank monitoring sites from a central location. B. The communication/database software shall provide the ability to communicate directly with the tank monitoring system, via a 25-pin RS-232 serial interface or remotely via a dial-up network over the public telephone network. C. The software package shall provide the ability to remotely configure a system and download that information to the tank monitoring system. The software shall also provide the ability to call the tank monitoring system, upload information into the database and allow the user to make changes and transmit those changes to the system. D. The software shall provide a communication mode, in which it can automatically and continuously poll locations that have been designated for data retrieval, and store data in a standard database format. E. The stored data shall be easily transferable to other software packages, such as spreadsheets, database packages, etc., for data manipulation. F. The software shall provide an immediate on-line mode to retrieve specific information from a tank monitoring system and to download setup and configuration information. G. The software shall be able to generate inventory and environmental compliance management reports on demand for all of the data stored or specific ranges of data. H. The software system shall provide the user the ability to retrieve all diagnostic data from the tank monitoring system. It shall also provide the ability to backup and recover data that has been stored. I. The software package shall permit the user to connect on-line with a location and enter serial communication protocol commands for information retrieval Reports TLS-300 UST Monitoring and Leak Detection System Rev. C

5 A. The system shall be able to generate reports in a display/printer format as well as a computer format through the communication interface using the Veeder-Root serial communications protocol. All reports, including inventory, delivery, fuel management, environmental compliance (leak detect), alarm history and status may be retrieved through remote or local communications. 2.6 Input/Output Devices Output Relay A. The system shall provide the ability to enable external audible/visual alarms or control external devices through a relay contact closure. B. The system shall provide 2 Form C contact relays per interface module. C. The system shall provide the ability to program the relay in either a Normally Open or Normally Closed orientation. D. The system shall provide the ability to assign in-tank, line leak, sensor, external input, or system alarm conditions to a selected relay. E. The system shall provide the ability to designate a 20-character label to a device connected to the output relay through system programming Input Interface 2.7 Alarms A. The system shall provide the ability to accept an input from an external device and enable a relay to control an external device. B. The system shall have the ability to define the type of input connected to the system, standard or generator. C. The system shall have the ability to name, through system programming, each external device connected to an input position. D. The system shall provide the ability to identify the input switch type from a stand-by generator (Normally Open or Normally Closed) to properly recognize a generator off condition. E. The system shall provide the ability to identify which tanks supply fuel to the generator to properly conduct continuous leak tests on tanks when the generator is off. TLS-300 UST Monitoring and Leak Detection System Rev. C

6 A. The tank monitoring system shall provide an audible and visual indication of all system, in-tank, product line leak and external sensor alarm conditions. B. The system alarm conditions shall include: 1. Maximum product level 2. High level limit 3. Overfill alarm 4. High water alarm 5. Second high water alarm 6. Delivery needed alarm 7. Low limit 8. Theft 9. Periodic warning and alarm 10. Annual warning and alarm C. The tank monitoring system shall provide an audible and visual alarm indication for intank leak failures (3.0 GPH, 0.1 GPH and 0.2 GPH) and external sensor leak failures (fuel, water, sensor out). D. In conjunction with providing an audible and visual alarm, the system shall have the ability to print out all alarm conditions to the integral thermal printer. E. The system shall have the ability to send all alarm conditions to the RS-232 serial communications port for data transmission to a central computer. The system shall have the ability to transmit the alarm condition immediately, or program a delay time before sending. The system shall also have the ability to enter a repeat function in the programming to repeat sending the alarm condition. F. The system shall provide the operator with the ability to disable the audible portion of an alarm but the visual alarm shall not be disabled until the alarm condition has been corrected. G. The system shall be equipped with an external audible and visual alarm with acknowledgement switch. The external alarm box and acknowledgment switch shall be manufactured in a watertight gasketed enclosure for installation in an outdoor environment. The external alarm box and acknowledgement switch shall interface to the tank monitoring system via an internal relay. H. The system shall have the ability to store up to three alarm occurrences in memory. The operator shall have the ability to print the alarm history and alarm status on the integral printer, as well as retrieve alarm history and alarm status through the communications interface (RS-232 or 2400/1200/300 baud auto-dial fax/modem). 2.8 Setup (Startup/Installation) TLS-300 UST Monitoring and Leak Detection System Rev. C

7 A. The system shall contain parameter-driven software to adapt the tank monitor to site specifications. The parameters must be enterable in assigned fields at the time of system startup. In addition, the parameters must be field updatable so that changes in tank diameter/dimensions as well as site specifications can be added. B. The system shall provide the use of a security code to prohibit unauthorized entry to the systems set-up parameters. The system security code shall be a six-digit number entered through the front-panel keyboard or through the external communications interface. The security code shall have the capability of containing alpha or numeric characters. C. A four-line, 24-character customer location header to identify the site must be userprogrammable. The header must appear automatically on inventory status reports, leak detection reports and automatic delivery reports each time they are printed. D. Set-up parameters shall include the following: 1. System setup data 2. Communications setup data 3. In-tank setup data 4. In-tank leak test setup data 5. External input setup data 6. Output relay setup data 2.9 Diagnostics/Troubleshooting A. All diagnostic information shall be generated by the system itself. The system shall not allow the user to change or enter diagnostic information in any way. The following diagnostic information shall be included in the system: 2.10 Reports 1. Probe Diagnostics a. Probe type b. Serial number c. Probe length d. Factory calibration values 2. System diagnostics a. Software revision level b. Software part number c. Software creation date 3. In-tank diagnostics 4. In-tank leak results 5. Alarm history report TLS-300 UST Monitoring and Leak Detection System Rev. C

8 A. The system shall provide the ability to print diagnostic information, listed in Part 2, Section 2.15, paragraph A, subsection 1 through 14, on the system s integral printer for hard-copy documentation and historical record keeping. Part 3 Product Specifications/Capacities 3.1 Console A. The console shall be wall mounted using external mounting tabs. B. The console shall be equipped with a two-line 24-character liquid crystal display for on-site viewing of all inventory, leak detect and alarm information. C. The console shall be equipped with a 24-button front-panel keyboard with control and alphanumeric functions for programming, operating and reporting functions. D. The console shall be equipped with three front-panel indicators to provide a visual indication of power on, warning and alarm conditions. E. The console shall be equipped with an integral, 24-character, thermal report printer with built-in take-up spool for hard-copy documentation of inventory, leak detect, alarm information, and facsimile transmission confirmation. F. The console shall be equipped with a back-up battery to maintain all programming information as well as inventory, leak detect and alarm information in the event of a power outage. G. The console shall be separated into two compartments for: 1) intrinsically safe wiring and devices; 2) high-power wiring and devices. H. The console shall have an internal quick-disconnect connector for 120 Vac wiring to the console for ease of installation, service and troubleshooting. I. The console shall be equipped with the ability to communicate directly with an external POS terminal, printing device or PC. The system shall also have the ability to communicate with a remote device via the telephone lines. J. The console shall be capable of selectively communicating in multiple languages, including English, French, German, Polish, Portuguese, Spanish, and Swedish. K. The console shall be equipped with internal audible and visual warning and alarm indicators. L. The console shall be intrinsically safe, with Underwriters Laboratories (UL), Canadian Standards Association (CSA), and Canadian Underwriters Laboratories (cul) approvals. TLS-300 UST Monitoring and Leak Detection System Rev. C

9 3.2 Probes M. The console shall comply with Federal Communications Commission (FCC) testing, FCC Part 68, Subpart 15. N. The console shall be mounted and wired according to the manufacturer-supplied installation manuals, with all underground intrinsically safe field wiring enclosed in dedicated conduit and separate from all other wiring. The system s high-voltage wiring may share existing conduit with other high-voltage devices in accordance with the applicable guidelines published in the National Electrical Code (NEC). O. The console shall continuously monitor all probes and sensors, reporting not only normal operating conditions, but also system malfunctions or failures. A. There shall be no more than two conductors between each probe and the control console. B. The probe shall be capable of performing a leak detect test to 0.1 GPH or higher. C. Third-Party Certification is required in accordance with the U.S. EPA s Standard Test Procedure for Evaluating Leak Detection Methods: Automatic Tank Gauging Systems (0.2 GPH monthly monitoring). D. Third-Party Certification is required in accordance with the U.S. EPA s Volumetric Tank Tightness Testing Method (0.1 GPH annual tank tightness test). E. The probe shall be compatible with aboveground tank installations as well as underground tank installations. F. A cap and ring kit, available from the manufacturer, shall be supplied with each probe for easy installation and removal. G. The probe shall use a digital communications protocol format for maximum RF/EMF immunity. 3.3 Communications RS-232 Serial Communications Interface A. The system shall have the ability to communicate directly with a computer, teletype or printer. B. The system shall provide direct interface via a 25-pin D-connector using standard RS- 232 serial communications hand-shaking signals. TLS-300 UST Monitoring and Leak Detection System Rev. C

10 C. The system shall have the capacity to install up to three RS-232 serial communications modules Auxiliary RS-232 Serial Communications Interface A. The system shall have the capacity for an auxiliary 25-pin D-connector to interface with a second tank monitor. B. The system shall have the capacity to install up to two Auxiliary RS-232 serial communications modules. Part 4 Manufacturer s Support/Field Service 4.1 Technical Support A. The manufacturer shall provide technical phone support available to customers from 8:00 a.m. to 7:00 p.m. EST. B. The manufacturer shall provide technical phone support available to authorized distributors and service contractors for on-site troubleshooting of UST system problems. Phone support shall be available from 8:00 a.m. to 7:00 p.m. EST. 4.2 Field Service A. The manufacturer shall maintain a nationwide field service staff to provide on-site customer support and training, as well as overseeing installation of tank monitoring system by installation contractor. B. The distributor/contractor field service representative shall be available for on-site training of company maintenance personnel on installation, programming and troubleshooting of tank monitoring system. C. The manufacturer shall have a territorial field service staff to support the distributor/contractor field service network. 4.3 Certification Training A. The manufacturer shall require and provide mandatory certification training for all of its authorized distributors and service contractors/installers. B. The certification program shall consist of three certification levels covering installation, setup/operation, and service/troubleshooting of the manufacturer s UST monitoring systems. C. The manufacturer shall provide certification information regarding contractors and installers to regulatory agencies that require certification documentation. TLS-300 UST Monitoring and Leak Detection System Rev. C

11 D. The manufacturer shall offer re-certification training to keep contractors/installers current with updated information. E. The manufacturer shall conduct regional training seminars throughout North America. F. The manufacturer shall provide a home study certification program for installing contractors. 4.4 Warranty Registration and Checkout Form (WRACO) A. The manufacturer shall require that all UST monitoring systems be started up by an authorized distributor. B. The startup shall consist of installation checkout, operation checkout and customer training on use of the equipment. C. The manufacturer shall supply a Warranty Registration and Checkout Form to properly document the site information. 1. Installation location 2. Installer 3. Equipment identification 4. Tank information 5. Leak detector information 6. Start-up distributor information 7. Customer approval D. The manufacturer shall compensate the authorized distributor for the start-up procedure when a properly completed Warranty Registration and Checkout form is submitted to the manufacturer. E. Upon receipt of the Warranty Registration and Checkout form, the manufacturer will initiate the system warranty and input the data into a site database. 4.5 Replacement and Service Parts A. The manufacturer shall offer Authorized Distributors pre-selected parts kits to service UST monitoring systems. B. The manufacturer shall offer a pre-selected parts kits designed for service truck and shop. C. The manufacturer shall offer a quick ship service for parts that shall ensure that a parts shipment is sent within 24 hours of request/order. TLS-300 UST Monitoring and Leak Detection System Rev. C

12 4.6 Delivery A. The manufacturer shall have the ability to ship tank monitoring systems in three (3) working days from the time that an order is entered into the computerized system to the ship date. 4.7 ISO-9000 A. The manufacturer shall maintain an ISO-9001 rating ensuring quality management of design, manufacturing, training, and technical documentation. Part 5 Documentation 5.1 Manuals A. The manufacturer shall supply product documentation that addresses the following categories as additional support: a. Site preparation and installation instructions b. System setup instructions c. System operating instructions d. Individual sensor installation instructions e. Probe installation instructions f. Individual module installation instructions g. Product data sheets h. Troubleshooting and repair manuals i. Wiring diagrams which include the following: 1. Identification of all devices and equipment terminals, and all external connection terminal blocks. 2. All external wiring connections with approved wire colors and circuit designations. j. Serial communications manuals 5.2 Third-Party Certification A. The manufacturer shall supply third-party documentation for all products, certifying that performance meets or exceeds EPA requirements. 5.3 Authorized Service Personnel Listing A. The manufacturer shall supply a formal list of all Authorized Distributors and Service Contractors for sales, installation, training and support. Part 6 - System Warranty TLS-300 UST Monitoring and Leak Detection System Rev. C

13 6.1 System Warranty A. The tank monitoring system shall be warranted for a period of one year from date of installation or 15 months from date of invoice. B. The warranty is to include parts and labor, with all warranty work performed on site by an authorized manufacturer's representative. 6.2 Extended Warranty A. The manufacturer shall offer a one-year extension on the standard warranty for an additional cost to the end user. B. The end user may have until the expiration date of the original system warranty to purchase the option of the extended warranty. TLS-300 UST Monitoring and Leak Detection System Rev. C

TLS-350R UST Monitoring and Leak Detection System With Automatic Business Reconciliation

TLS-350R UST Monitoring and Leak Detection System With Automatic Business Reconciliation Part 1 General System Requirements 1.1 Description TLS-350R UST Monitoring and Leak Detection System With Automatic Business Reconciliation A. These Specifications are intended to provide information by

More information

Automatic Tank Gauging and Line Leak Detection System Bid Specification TS-550evo Fuel Management System

Automatic Tank Gauging and Line Leak Detection System Bid Specification TS-550evo Fuel Management System Automatic Tank Gauging and Line Leak Detection System Bid Specification TS-550evo Fuel Management System Franklin Fueling Systems 000-1739 r3, November 2017 An ISO 9001 Registered Company Part 1 General

More information

SiteSentinel itouch Console

SiteSentinel itouch Console SITESENTINEL ITOUCH CONSOLE SiteSentinel itouch Console OPW s SiteSentinel itouch is a multifunction, high-quality tank-monitoring system that provides real-time, accurate inventory information for up

More information

BID-SPEC_INTEGRA_100 Rev. 0. Bid Specifications and General Description OPW SiteSentinel Integra 100 Automatic Tank Monitoring System

BID-SPEC_INTEGRA_100 Rev. 0. Bid Specifications and General Description OPW SiteSentinel Integra 100 Automatic Tank Monitoring System BID-SPEC_INTEGRA_100 Rev. 0 Bid Specifications and General Description OPW SiteSentinel Integra 100 Automatic Tank Monitoring System Part 1. General Overview 1.1 Summary This document describes the minimum

More information

Veeder-Root TLS2 Console Gilbarco EMC2 Console

Veeder-Root TLS2 Console Gilbarco EMC2 Console Manual No: 5770-757 Revision: G Software Version 5 Veeder-Root TLS Console Gilbarco EMC Console Setup and Operation Manual Notice Veeder-Root makes no warranty of any kind with regard to this publication,

More information

VEEDER-ROOT CURRENT DATA STORAGE INTERFACE MANUAL. for. TLS-300 and TLS-350 UST Monitoring Systems. and

VEEDER-ROOT CURRENT DATA STORAGE INTERFACE MANUAL. for. TLS-300 and TLS-350 UST Monitoring Systems. and VEEDER-ROOT CURRENT DATA STORAGE INTERFACE MANUAL for TLS-300 and TLS-350 UST Monitoring Systems and TLS-350R Environmental & Inventory Management System through Software Versions 15/115 Manual Number

More information

Adam Sweet 4KGAL DIESEL TANK AST STEEL 4/7/2017 False

Adam Sweet 4KGAL DIESEL TANK AST STEEL 4/7/2017 False 2016 Capital Outlay Project - Plumbing Construction Category: Elementary, Pre Schools, High Schools, Project ID #: 1004335494 Junior High Schools Street Address: To Be Announced Lyndonville NY Staff Estimate

More information

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2 Architectural & Engineering Specifications Control Panel 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality assurance...

More information

Spectron LSN (Life Safety Network) Suggested Specifications

Spectron LSN (Life Safety Network) Suggested Specifications 1. General 1.1 Scope A Dual-Lite Spectron LSN (Life Safety Network) Series Inverter System shall be furnished to provide a reliable source of power, and shall operate during a utility line deficiency without

More information

CARD ACCESS CONTROL SYSTEM

CARD ACCESS CONTROL SYSTEM SECTION 13851 CARD ACCESS CONTROL SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete, operable, tested, integrated proximity access control system, to operate on a proximity principle where

More information

Architectural and Engineering Specification for a Real-Time Locating System Flare

Architectural and Engineering Specification for a Real-Time Locating System Flare Architectural and Engineering Specification for a Flare AE-T1-IN-R3-E-0617 Page 1 of 14 This document is intended to provide performance specifications and operational requirements for the Flare. It is

More information

INSTRUCTION MANUAL MODEL LDE 740. (Revised July 8, 2017)

INSTRUCTION MANUAL MODEL LDE 740. (Revised July 8, 2017) PNEUMERCATOR Liquid Level Control Systems Multi Tank Monitoring System INSTRUCTION MANUAL MODEL LDE 740 (Revised July 8, 2017) COPYRIGHT 2017 PNEUMERCATOR CO. 1785 EXPRESSWAY DRIVE NORTH, HAUPPAUGE, NY

More information

Fuel Management System Setup Guide

Fuel Management System Setup Guide Fuel Management System Setup Guide EVO-EXPC & EVO-EXPC2 Expansion Consoles for TS-5000 evo and TS-550 evo Franklin Fueling Systems 3760 Marsh Rd. Madison, WI 53718 USA Tel: +1 608 838 8786 800 225 9787

More information

FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200

FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200 FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200 1.0 General 1.1 Manufacturer Manufacturer of the Fire Alarm Control Panel (FACP) equipment shall be: Digital Monitoring Products, Incorporated 2500 N.

More information

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes

More information

Architectural and Engineering Specification for a. Flash / Flare

Architectural and Engineering Specification for a. Flash / Flare Architectural and Engineering Specification for a Flash / Flare June 27, 2014 Page 1 of 12 T1DA0115-001 Rev D This document is intended to provide performance specifications and operational requirements

More information

OPTIMUM APPLIED SYSTEMS,

OPTIMUM APPLIED SYSTEMS, OPTIMUM APPLIED SYSTEMS, INC. HEAT COMPUTER 3500 DSL TECHNICAL SPECIFICATIONS HC 3500 GENERAL SYSTEM DESCRIPTION The Heat Computer is a computerized building heating control system that utilizes sensors

More information

Remanufactured Veeder-Root Discriminating Dispenser Pan and Containment Sump Sensors

Remanufactured Veeder-Root Discriminating Dispenser Pan and Containment Sump Sensors Manual Number: 01-61-133 Revision : 1.8 Date: 10/27/16 Installation Instructions Remanufactured Veeder-Root Discriminating Dispenser Pan and Containment Sump Sensors PMP # 62322, 62352 Replaces Veeder-Root

More information

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION 1. GENERAL SPECIFICATION 1.1 The contractor shall provide an Intelligent AlarmLine Linear Heat Detection System to perform the following functionality: A. Fire Alarm, Supervisory and Trouble-Event Initiation

More information

Installation Instructions. Remanufactured Veeder-Root Position Sensitive Sump Sensor. PMP # Replaces Veeder-Root #

Installation Instructions. Remanufactured Veeder-Root Position Sensitive Sump Sensor. PMP # Replaces Veeder-Root # Manual Number: 01-61-141 Revision : 1.7 Date: 10/27/16 Installation Instructions Remanufactured Veeder-Root Position Sensitive Sump Sensor PMP # 62323 Replaces Veeder-Root #794380-323 Contents Disclaimer...

More information

Installation Instructions. Remanufactured Veeder-Root Overfill Alarm and. Acknowledgement Switch. Overfill Alarm PMP # OEM #

Installation Instructions. Remanufactured Veeder-Root Overfill Alarm and. Acknowledgement Switch. Overfill Alarm PMP # OEM # Manual Number: 01-62-768 Revision : 1.2 Date: 03/20/17 Installation Instructions Remanufactured Veeder-Root Overfill Alarm and Acknowledgement Switch Overfill Alarm PMP # 62625 OEM # 790091-001 Acknowledgement

More information

OJD ITB No Attachment E Duress Alarm Equipment Specifications

OJD ITB No Attachment E Duress Alarm Equipment Specifications Duress Alarm Equipment Specifications PART 1 GENERAL 1.1 SECTION INCLUDES A. Duress devices. B. Alarm control panel. C. Signaling devices. 1.2 REFERENCE STANDARDS A. NFPA 70 - National Electrical Code;

More information

DS7400Xi Addressable Control/ Communicator

DS7400Xi Addressable Control/ Communicator DS7400Xi Addressable Control/ Communicator DS7400Xi DS7400Xi-EXP 110VAC operation 220VAC operation Remotely Programmable WDSRP (Windows Detection Systems Remote Programming Software), allows the systems

More information

Omniguard 4: Features

Omniguard 4: Features OMNIGUARD 4 The clear choice for monitoring and documenting Vacuum and Pressure in a containment area. Ideal for Asbestos, Lead and Mold abatement and Clean Room monitoring. Omniguard 4: Features The Omniguard

More information

OPERATION MANUAL MODEL LC2000 COPYRIGHT 2017 PNEUMERCATOR CO., INC EXPRESSWAY DRIVE NORTH HAUPPAUGE, NY 11788

OPERATION MANUAL MODEL LC2000 COPYRIGHT 2017 PNEUMERCATOR CO., INC EXPRESSWAY DRIVE NORTH HAUPPAUGE, NY 11788 PNEUMERCATOR Liquid Level Control Systems LEAK/POINT LEVEL ALARM CONSOLE OPERATION MANUAL DRAWING NO. 20068 REV. N/C MODEL COPYRIGHT 2017 PNEUMERCATOR CO., INC. 1785 EXPRESSWAY DRIVE NORTH HAUPPAUGE, NY

More information

LaserFOCUS VLF-250 Engineering Specification

LaserFOCUS VLF-250 Engineering Specification Vision Fire & Security LaserFOCUS VLF-250 Engineering Specification May 2004 Part Number 20296 LaserFOCUS VESDA 2 VESDA LaserFOCUS Contents Scope...4 Description...4 General...4 Approvals...4 Codes, Standards

More information

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions. 11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

More information

Manual No: Revision: E. Groundwater Sensor. Installation Guide

Manual No: Revision: E. Groundwater Sensor. Installation Guide Manual No: 576013-763 Revision: E Groundwater Sensor Installation Guide Notice Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied warranties

More information

FDF Foam Pump Controllers Features

FDF Foam Pump Controllers Features FDF100 Diesel Engine Foam Pump Controllers 1-1 Product Description The FDF Series of Foam Pump Controllers are designed for use with foam concentrate injection, foam transfer and water mist systems for

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. Minimum lighting control (base scope of work) shall include all corridors. The lighting in all the corridors shall be turned on (if not already on) if

More information

Trident User s Manual

Trident User s Manual Labkotec Oy Myllyhaantie 6 33960 Pirkkala FINLAND Tel. +358 (0)29 006 260 18.05.2017 Fax +358 (0)29 006 1260 Internet: www.labkotec.fi 34 pages Trident Copyright 2017 Labkotec Oy 1/34 TABLE OF CONTENTS

More information

Control/Communicator

Control/Communicator Architectural & Engineering Specifications Control/Communicator 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality

More information

Architectural and Engineering Specification for a Fence-Mounted Perimeter Intrusion Detection System. FlexZone

Architectural and Engineering Specification for a Fence-Mounted Perimeter Intrusion Detection System. FlexZone Architectural and Engineering Specification for a Fence-Mounted Perimeter Intrusion Detection System FlexZone April 15, 2014 Page 1 of 14 G6DA0115-001 This document is intended to provide performance specifications

More information

Product Specifications

Product Specifications Southwest Microwave, Inc. 9055 S. McKemy Street Tempe, Arizona 85284 USA (480) 783-0201 Fax (480) 783-0401 Product Specifications Procurement Specifications INTREPID MicroPoint Cable System Perimeter Detection

More information

DIESEL Engine Fire Pump Controllers Features. FD120 Diesel Engine Controllers

DIESEL Engine Fire Pump Controllers Features. FD120 Diesel Engine Controllers DIESEL Engine Fire Pump Controllers Features FD120 Diesel Engine Controllers 1-1 March 2013 Diesel Product Description The DIESEL Plus Fire Pump Controllers from Eaton Corporation are designed to control

More information

1.1 SECTION INCLUDES.1 Materials and installation for aboveground oil storage tanks..2 Section Waste Management and Disposal.

1.1 SECTION INCLUDES.1 Materials and installation for aboveground oil storage tanks..2 Section Waste Management and Disposal. Page 1 of 8 PART 1 GENERAL 1.1 SECTION INCLUDES.1 Materials and installation for aboveground oil storage tanks. 1.2 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management

More information

The Kryos LN2 Liquid Level Control & Cryogenic Temperature Control

The Kryos LN2 Liquid Level Control & Cryogenic Temperature Control The Kryos LN2 Liquid Level Control & Cryogenic Temperature Control Created for Taylor-Wharton Gas Equipment By Pacer Digital Systems, Inc. INTRODUCTION... 4 TEXT FORMAT NOTATION... 4 SYSTEM COMPONENTS...

More information

Suggested Specification: Benchmark 1.5 Low NOx Gas-Fired Hydronic Boiler(s)

Suggested Specification: Benchmark 1.5 Low NOx Gas-Fired Hydronic Boiler(s) Furnish and install as shown on AERCO International plans and operation and maintenance manuals, with all applicable codes and authorities having local, state and federal jurisdiction, Benchmark Series

More information

Across-the-Line SERIES MP300 Combined Manual and Automatic

Across-the-Line SERIES MP300 Combined Manual and Automatic Across-the-Line SERIES MP300 Combined Manual and Automatic Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s Standard for Centrifugal Fire Pumps

More information

Operation Manual Fighter ProVision Software. Version: 0.0 Revision: 1

Operation Manual Fighter ProVision Software. Version: 0.0 Revision: 1 Operation Manual Fighter ProVision Software Version: 0.0 Revision: 1 TABLE OF CONTENTS 1. Introduction 5 2. Software Installation 5 3. PC Users 6 3.1 Introduction 6 3.2 Default Code 6 3.3 Edit PC User

More information

DIESEL Engine Fire Pump Controllers Features

DIESEL Engine Fire Pump Controllers Features September 007 DIESEL Engine Fire Pump Controllers Features FD0 Diesel Engine Controllers 1-1 Printer / Recorder The industrial grade thermal printer is housed in a rugged steel enclosure within the controller.

More information

Pipo Communications. Model ST-888. DTMF ANI/ENI Display Decoder

Pipo Communications. Model ST-888. DTMF ANI/ENI Display Decoder Pipo Communications Model ST-888 DTMF ANI/ENI Display Decoder 1516 Cassil Place Hollywood, California 90028-7106 Phone: 323-466-5444 Fax: 323-466-1520 www.pipo.cc Manual # 68-9888 May 1, 2002 Rev. 5/02

More information

PEGAsys. Multi-Loop Intelligent Suppression Control System FEATURES DESCRIPTION. Effective: March 2007 K

PEGAsys. Multi-Loop Intelligent Suppression Control System FEATURES DESCRIPTION. Effective: March 2007 K PEGAsys Multi-Loop Intelligent Suppression Control System A UTC Fire & Security Company Effective: March 2007 K-76-028 FEATURES UL Listed CSFM Approved MEA Approved Peer-to-Peer Networking (to 32 nodes)

More information

CALL FOR TENDER - MUNICIPALITY OF THE DISTRICT OF CLARE LITTLE BROOK, N.S.

CALL FOR TENDER - MUNICIPALITY OF THE DISTRICT OF CLARE LITTLE BROOK, N.S. CALL FOR TENDER - MUNICIPALITY OF THE DISTRICT OF CLARE LITTLE BROOK, N.S. NAME OF TENDER: CONSTRUCT, DELIVER AND COMMISSION 3 (THREE) LIFT STATION ELECTRICAL LOCATION OF WORK: 3 Separate work sites in

More information

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL MADE IN THE U.S.A. U.L. LISTED CANADIAN LISTED CSFM: 7300-1418:100 GENERAL DESCRIPTION SERIAL NUMBER The Cookson Company FIREFLY II PLUS Time Delay Release

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with automatic detection and control. The work described in

More information

Product Specification

Product Specification Southwest Microwave, Inc. 9055 S. McKemy Street Tempe, Arizona 85284 USA (480) 783-0201 Fax (480) 783-0401 Product Specification INTREPID MicroTrack Buried Cable Perimeter Intrusion Detection System System

More information

ION Meter Alerts TECHNICAL NOTE NOVEMBER In This Document

ION Meter Alerts TECHNICAL NOTE NOVEMBER In This Document 70072-0125-01 TECHNICAL NOTE NOVEMBER 2006 ION Meter Alerts A PowerLogic ION meter can send alerts to indicate a user specified power system condition such as a power quality problem (including surges,

More information

21-light Remote Annunciator. Owner s Manual

21-light Remote Annunciator. Owner s Manual 21-light Remote Annunciator Owner s Manual Annunciator Description... Inside Font Cover Detailed Specifications... 1 Environmental Specifications... 1 Power Supply Requirements... 1 Communication With

More information

PROTEUS Series OEL8000III-K. Tank Gauging System. Installation Manual

PROTEUS Series OEL8000III-K. Tank Gauging System. Installation Manual OMNTEC PROTEUS Series OEL8000III-K Tank Gauging System Installation Manual Page 1 of 23 PROPRIETARY INFORMATION NOTICE This document contains information and material developed by OMNTEC Mfg., Inc. All

More information

Mark 25 Ultrapure Water Conductivity Analyzer

Mark 25 Ultrapure Water Conductivity Analyzer Martek Instruments, Inc. Mark 25 Ultrapure Water Conductivity Analyzer Instruction Manual WARRANTY POLICY Unless otherwise stated, MARTEK INSTRUMENTS, INC. warrants this equipment to be free from defects

More information

ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL

ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL PRODUCT Specification FEATURES Designed To Meet The Requirements Of EN54 Expandable From 1 To 5 Loops As Standard A Variety Of Networking Options

More information

Laptop / PC Programming Manual

Laptop / PC Programming Manual Laptop / PC Programming Manual Doc. # Fire PC Program rev B 01.07 This Document is property of Evax Systems, Inc. The Evax Fire Solutions Programmer Components 2 1.0 System Setup 4 1.1 Interface Setup

More information

Soft Start Series MP700 Solid State, Reduced Voltage

Soft Start Series MP700 Solid State, Reduced Voltage Metron Fire Pump Controls and Accessories Soft Start Series MP700 Solid State, Reduced Voltage Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s

More information

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase General Specification 550 VA/Watts 1300 VA/Watts 1.0 GENERAL This specification defines the electrical and mechanical characteristics

More information

FlexPS. Architectural & Engineering. Specification for FlexPS. Architectural/Engineering Specification for a

FlexPS. Architectural & Engineering. Specification for FlexPS. Architectural/Engineering Specification for a Architectural/Engineering Specification for a Fence-Mounted Perimeter Intrusion Detection System FlexPS Disclaimer Senstar, and the Senstar logo are registered trademarks, and FlexPS, Silver Network and

More information

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems 5/25/16 rev 6 elite Model ELN General Specification 550 W to 1.5 KW elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems 1.0 General General Specification This specification

More information

Galaxy Pulsar Plus Digital Battery Plant Controller

Galaxy Pulsar Plus Digital Battery Plant Controller Galaxy Pulsar Plus Digital Battery Plant Controller Features Supports up to 60 Power Modules rectifiers and converters Supports dual voltage plants, with rectifiers and converters Auto-sensing dual voltage

More information

Variable Frequency Drive SERIES MP800 VFD

Variable Frequency Drive SERIES MP800 VFD Metron Fire Pump Controls and Accessories Variable Frequency Drive SERIES MP800 VFD Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s Standard for

More information

Specification for On-Line UPS Battery Monitoring and Data Management System

Specification for On-Line UPS Battery Monitoring and Data Management System 1 Scope This specification defines the minimum requirements for a predictive on-line Battery Monitoring BMDMS with test, analysis, and remote monitoring control capabilities. Unless noted otherwise, the

More information

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers. ModSync Sequencing System Installation & Operation Manual For use with Fulton Steam Boilers. Revision 3.0 8/21/2008 - 2 - Table of Contents Introduction Page 4 Features Page 4 Sequence of Operation Page

More information

Architectural and Engineering Specification for a Personal Alarm System System (PAS)

Architectural and Engineering Specification for a Personal Alarm System System (PAS) Architectural and Engineering Specification for a Personal Alarm System System (PAS) July 3, 2014 Page 1 of 10 This document is intended to provide performance specifications and operational requirements

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas 67357 Telephone: 620-421-0480,

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-28 31 75.00 10 (November 2008) ----------------------------------- Preparing Activity: USACE Superseding UFGS-28 31 75.00 10 (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

opti-visor ultra-efficient chiller plant automation Typical specification

opti-visor ultra-efficient chiller plant automation Typical specification opti-visor ultra-efficient chiller plant automation Typical File No: 90.893 Date: february 9, 2015 Supersedes: 90.893 Date: april 20, 2012 contents 1.0 Chilled water plant 4 1.1 General system requirements

More information

C. The system shall be capable of turning luminaires on/off (where supported by the luminaire) as well as full range dimming.

C. The system shall be capable of turning luminaires on/off (where supported by the luminaire) as well as full range dimming. SECTION 260943 SPECIFICATIONS - Wireless Network Lighting Controls. PART 1 - GENERAL 1.1 RELATED DOCUMENTS 1.2 SUMMARY AND KEY SYSTEM DIFFERENTIATORS A. The lighting control system specified herein shall

More information

REPEATER FS5200R INSTRUCTION MANUAL

REPEATER FS5200R INSTRUCTION MANUAL REPEATER FS5200R INSTRUCTION MANUAL Instruction Manual Page1 CONTENTS 1. Introduction... 3 2. Function... 3 3. Technical data... 3 4. Contents of delivery... 4 5. General information... 5 6. Duty Mode...

More information

Product Specifications

Product Specifications Southwest Microwave, Inc. 9055 S. McKemy Street Tempe, Arizona 85284 USA +1(480) 783-0201 Fax +1(480) 783-0401 Product Specifications 1.0 INTREPID Series II - MicroNet II Perimeter Intrusion Detection

More information

DGC-1000 DIGITAL GENSET CONTROLLER

DGC-1000 DIGITAL GENSET CONTROLLER DGC-1000 DIGITAL GENSET CONTROLLER Basler Electric s Digital Genset Controller (DGC-1000) offers a low cost microprocessor based integrated alternative for small to medium sized genset control and monitoring.

More information

20 Light Remote Annunciator

20 Light Remote Annunciator Light Remote Annunciator Owner s Manual Surface Mount Flush Mount 94-95- Standard Annunciator 94-, 94-95-, 95-4- 4- Annunciator w/remote Relay Panel 4-, 4-4-, 4-49-, 49-49-, 49- Time Multiplexed Annunciator

More information

FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS

FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS VALOUR COMMUNITY CENTRE FIRE ALARM SYSTEM Section 28 00 00 GYMNASIUM ADDITION & RENOVATION Page 1 of 3 28 00 00 FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS 1.2 SCOPE 1. The specification covering the General

More information

AUTOMATION. Operator s Manual RST Series Web Enabled Input Module. Rev. A2, 1/12

AUTOMATION. Operator s Manual RST Series Web Enabled Input Module. Rev. A2, 1/12 AUTOMATION P R O D U C T S GROUP, INC. Operator s Manual RST-5000 Series Web Enabled Input Module Rev. A2, 1/12 Tel: 1/888/525-7300 Fax: 1/435/753-7490 www.apgsensors.com E-mail: sales@apgsensors.com RST-5000

More information

THE "SS90" SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL

THE SS90 SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL S S S S S S S S 90 OLID TATE ECURITIES, INC SOLID STATE FAIL-SAFE UNIT * PATENT PENDING LISTED U 99Y9 RESET L RELEASING DEVICE SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE

More information

Manual No: Revision: J. Groundwater Sensor. Installation Guide

Manual No: Revision: J. Groundwater Sensor. Installation Guide Manual No: 576013-763 Revision: J Groundwater Sensor Installation Guide Notice Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied warranties

More information

SC-F3G User Manual 1.0

SC-F3G User Manual 1.0 SC-F3G User Manual 1.0 Table of Contents 1. Introduction... 3 2. Functions... 3 3. Features... 3 4. Package Contents... 3 5. Device Configuration... 4 6. Status LED signals... 5 7. Before You Start...

More information

MODEL 5104B. Installation and Operation Manual. Fire Communicator. Part Number E, 09/04

MODEL 5104B. Installation and Operation Manual. Fire Communicator. Part Number E, 09/04 MODEL 5104B Fire Communicator Installation and Operation Manual Part Number 151053 E, 09/04 Content Section 1 Introduction... 1-1 1.1 Feature... 1-1 1.2 Accessory Devices... 1-2 1.3 About This Manual...

More information

INSTALLATION AND OPERATION MANUAL ISM-4081 INTEGRATED SHUTDOWN MODULE

INSTALLATION AND OPERATION MANUAL ISM-4081 INTEGRATED SHUTDOWN MODULE INSTALLATION AND OPERATION MANUAL ISM-4081 INTEGRATED SHUTDOWN MODULE SYSTEM CONCEPT When not transferring fuel, the pressure in the underground piping system for gasoline distribution may fall due to

More information

Powerohm Resistors Digital HRG System

Powerohm Resistors Digital HRG System Installation and Operating Instructions Powerohm Resistors Digital HRG System This manual provides general information, installation, operation, maintenance, and system setup information for the Powerohm

More information

Architectural and Engineering Specification for a Fiber Optic Perimeter Intrusion Detection System. FiberPatrol FP1100X

Architectural and Engineering Specification for a Fiber Optic Perimeter Intrusion Detection System. FiberPatrol FP1100X Architectural and Engineering Specification for a Fiber Optic Perimeter Intrusion Detection System FiberPatrol FP1100X December 2017 Page 1 of 14 AE-FP-001-IN-R5-E-12/17 This document is intended to provide

More information

DIESEL Engine Fire Pump Controllers Features

DIESEL Engine Fire Pump Controllers Features 1-1 Product Description The FD100 Diesel Engine Controller is designed to control and monitor 12 or 24 volt, diesel fire pump engines. All models are listed by UL and ULC, and approved by Factory Mutual

More information

VHP ARD BIODECONTAMINATION SYSTEM

VHP ARD BIODECONTAMINATION SYSTEM VHP ARD BIODECONTAMINATION SYSTEM APPLICATION The VHP ARD Biodecontamination System is designed for portable biodecontamination* of clean, dry, sealed Enclosures.** The VHP 1000-ARD Biodecontamination

More information

Architectural and Engineering Specification for a Fiber Optic Perimeter Intrusion Detection System. FiberPatrol FP1150

Architectural and Engineering Specification for a Fiber Optic Perimeter Intrusion Detection System. FiberPatrol FP1150 Architectural and Engineering Specification for a Fiber Optic Perimeter Intrusion Detection System FiberPatrol FP1150 April 2018 Page 1 of 14 AE-FP-005-IN-R1-E-04/18 This document is intended to provide

More information

Architectural and Engineering Specification for a Hybrid Perimeter Intrusion Detection and Intelligent Lighting System.

Architectural and Engineering Specification for a Hybrid Perimeter Intrusion Detection and Intelligent Lighting System. Architectural and Engineering Specification for a Hybrid Perimeter Intrusion Detection and Intelligent Lighting System Senstar LM100 AE-E8-IN-R2-E-1118 Page 1 of 14 This document is intended to provide

More information

Installation Instructions. Remanufactured Veeder-Root Sump Sensor. PMP # 62208, Replaces Veeder-Root # , -209

Installation Instructions. Remanufactured Veeder-Root Sump Sensor. PMP # 62208, Replaces Veeder-Root # , -209 Manual Number: 01-60-291 Revision : 5.6 Date: 12/11/15 Installation Instructions Remanufactured Veeder-Root Sump Sensor PMP # 62208, 62209 Replaces Veeder-Root #794380-208, -209 Contents Disclaimer...

More information

Installation Instructions. Remanufactured Veeder-Root Steel Tank Interstitial Sensor. PMP # 62420, Replaces Veeder-Root # , -460

Installation Instructions. Remanufactured Veeder-Root Steel Tank Interstitial Sensor. PMP # 62420, Replaces Veeder-Root # , -460 Manual Number: 01-60-309 Revision : 5.5 Installation Instructions Remanufactured Veeder-Root Steel Tank Interstitial Sensor PMP # 62420, 62460 Replaces Veeder-Root #794380-420, -460 Contents Disclaimer...

More information

Single-Point Mini Hydrostatic Sensor for Double-Wall Sumps

Single-Point Mini Hydrostatic Sensor for Double-Wall Sumps Manual No: 577013-838 Revision: B Single-Point Mini Hydrostatic Sensor for Double-Wall Sumps Installation Guide Notice Veeder-Root makes no warranty of any kind with regard to this publication, including,

More information

SHORT CIRCUIT ISOLATOR TO NEXT COMPONENT REQUIRING POWER TO NEXT KEYPAD (** IF REQUIRED) STROBE RELAY MODULE KEYSWITCH ISOLATION MODULE STROBE

SHORT CIRCUIT ISOLATOR TO NEXT COMPONENT REQUIRING POWER TO NEXT KEYPAD (** IF REQUIRED) STROBE RELAY MODULE KEYSWITCH ISOLATION MODULE STROBE The Door Switch 11772 Westline Industrial Drive St. Louis, Mo 63146 (877) 998-5625 www.thedoorswitch.com Patent No. RE42,991 and RE44,039 CONTROL PANEL TRANSFORMER (SUPPLIED WITH CONTROL PANEL) NOTIFICATION

More information

The Challenger Version 8 User Guide

The Challenger Version 8 User Guide The Challenger Version 8 User Guide CONTENTS Function included in your system Introduction...4 Glossary... 6 The Challenger Console.. Liquid Crystal Display... 9 Keypad...10 Indicator Lights...11 User

More information

Alarm annunciation, control and communication systems

Alarm annunciation, control and communication systems Architectural & Engineering Specification for Alarm annunciation, control Purpose of document This document is intended to provide performance specifications and operational requirements for the Senstar

More information

AS950 ALL-WEATHER REFRIGERATED SAMPLERS

AS950 ALL-WEATHER REFRIGERATED SAMPLERS AS950 ALL-WEATHER REFRIGERATED SAMPLERS Applications Wastewater Collections Industrial Pretreatment Environmental Monitoring Stormwater Sampling has never been this easy. The AS950 All-Weather Refrigerated

More information

PERMACONN PM1030 Includes DI300. Installation Manual

PERMACONN PM1030 Includes DI300. Installation Manual PERMACONN PM1030 Includes DI300 Installation Manual Radio Data Comms Unit 5/20-30 Stubbs Street Silverwater NSW 2128 Telephone: 02 9352 1777 Facsimile: 02 9352 1700 Introduction The PERMACONN system provides

More information

Manual No: Revision: D. Mag Sump Sensor. Installation Guide

Manual No: Revision: D. Mag Sump Sensor. Installation Guide Manual No: 577013-812 Revision: D Mag Sump Sensor Installation Guide Notice Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied warranties

More information

Series 5000 Hydrazine Analyzer Model 60002

Series 5000 Hydrazine Analyzer Model 60002 Series 5000 Hydrazine Analyzer Model 60002 T he patented* Series 5000 Hydrazine Analyzer is a continuous-reading instrument using the p-dimethylaminobenzaldehyde method of analysis for colorimetric measurement

More information

MODEL B2 INSTALLATION MANUAL

MODEL B2 INSTALLATION MANUAL RELEASE DEVICES GENERAL DESCRIPTION MODEL B2 INSTALLATION MANUAL S/N: The B2 Series Time Delay Release Devices are UL Listed, Canadian Listed, and CSFM Listed for use on rolling doors, single-slide and

More information

LORAIN CSP DC Power System

LORAIN CSP DC Power System DC Power for Business-Critical Continuity Key Features Compact flexibility provides more space for revenue generating equipment Constant power delivers more current at lower voltages to meet load or recharge

More information

ACT2-CS Convenience Store Controller

ACT2-CS Convenience Store Controller Refrigeration Systems Technical Manual 804 Product Bulletins Section Product Bulletin Issue Date 0899 ACT2-CS Convenience Store Controller The ACT2-CS Convenience Store Controller is a fully programmable,

More information

LORAIN CIP 4890/48120 DC Power System

LORAIN CIP 4890/48120 DC Power System DC Power for Business-Critical Continuity Key Features Compact flexibility provides rectifiers, distribution, and controller in one shelf Constant power delivers more current at lower voltages to meet

More information

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description MODUL-R FIRE ALARM CONTROL PANELS MR-2900/MR-2920 Addressable Fire Alarm Control Panels Description MR-2900 Fire Alarm Control Panel The MR-2900 fire alarm system control unit is the heart of a sophisticated

More information

The EN54 Part 2 & 4 Fire System

The EN54 Part 2 & 4 Fire System Scope of work: To design, supply, install and commission an Analogue Addressable Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54

More information

TLS-4XX Setup and Operation

TLS-4XX Setup and Operation Manual No: 577013-940 Revision: B TLS-4XX Setup and Operation Screens Manual Notice Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied

More information