CUSTOMER SPECIFICATION
|
|
- Jemimah Byrd
- 6 years ago
- Views:
Transcription
1 MULTIPOINT GAS RE-IGNITER 120Vac Flame Re-Ignition For gas appliances Contents - Product description - Operating Principles - Compliance standards - Functional Requirements - Mechanical Requirements - Technical Specification - Environmental Specification - Physical Dimensions - Wiring Installation Schematic Product Re-igniter Interrupted Direct Spark Ignition system for use with natural, mixed, liquified petroleum and LP Gas mixtures. - Polarised 11 Way Input Connector allows for reduced assembly costs Vac operation. Page 1 of 7
2 Operating Principles The re-igniter monitors the flame presence at the burner and commences sparking if any flame fails. Correct operation of flame sense circuits requires the mains supply to the re-igniter to have at least a resistive connection to earth and the burners also to be earthed. An in-built delay of about one-second, between loss of flame sense and commencement of sparking, eliminates nuisance sparking if the flame is low and wavering. Compliance to Standards: ANSI Z /CSA manually Operated Electric gas Ignition Systems and Components ANSI Z21.92a 2005/CSA 6.29a-2005 manually Operated Electric gas Ignition Systems and Components Reference Standards: CAN/CSA-C22.2 No. 199-M89 Automatic Gas Ignition Systems and Components EN : 1997 Specification for Automatic controls for household and similar use EN50165: 1995 Clause Electrical equipment of non-electric appliances for household and similar purposes Functional Requirements: General The module provides (4) four interrupted, direct spark outlets to operate in conjunction with a 4 burner cook-top or range. Connected to the re-igniter is a single electrode at each burner. The electrode directs a generated spark through the gas/air medium surrounding the burner to ignite the mixture and also provides a means of detecting the flame. Each burner is individually controlled by a gas-cock. Opening the gas-cock simultaneously allows gas to flow to the burner and switches an AC voltage to the associated re-igniter channel through a micro switch. When a burner is turned on, sparks are simultaneously generated at all 4 outlets until flame is detected at the selected burner. The same process is repeated when any of the remaining burners are switched on. The circuit continues to monitor the flame presence at each burner and will recommence sparking at all burners if any flame fails. Sparking 4 independent high voltage output coils generate sufficient voltage and energy to generate a spark from the electrode across the spark gap to the earthed burner. A spark is guaranteed, provided the spark gap is within specifications and provided the electrode and cable load resulting from the cooktop or range design meets the maximum loading specifications. The spark rate varies primarily due to changes in the applied voltage, however other factors including temperature and component tolerance have an influence. Page 2 of 7
3 Flame Detection The module utilises a rectification flame sense circuit, which has distinct advantages over other reigniter flame sensing circuits. Flame conduction circuits are unable to differentiate between flame presence and leakage to earth. The flame rectification circuit applies an AC voltage (derived from the mains line voltage) to the sense electrode and detects the difference in current flow in each direction caused by the diode characteristic of the flame. Leakage paths caused by dirt or condensation do not have this diode or rectification characteristic and cannot be mistakenly sensed as a flame. The rectification sense circuit can tolerate, with no effect, leakage currents up to ten times larger than those that will cause a conduction circuit to falsely detect a flame. Even when the leakage current is large enough to have an effect, it safely results in continuous sparking, and not false flame detection as in the case of conduction circuits. The module detects flame under all flame conditions provided the electrode is positioned such that the detected flame current exceeds the minimum specified flame current. Burners with poor flame stability may result in momentary loss of sensed flame below the specified limits, however an in-built delay eliminates nuisance sparking if the flame is low and wavering. The flame failure re-ignition delay, which is dependent on the magnitude of the flame, is a delay between loss of flame sense and commencement of sparking on self re-ignition only. If flame sense is re-established within this period no sparking will occur. The module must only be used in a manner that meets all the relevant requirements of the Electrical and Gas Authorities in the country of use. Like other flame sense circuits, the AC supply to the re-igniter must have at least a resistive connection to Earth and the burners must also be earthed. When using an isolation transformer to supply the re-igniter, the Neutral connection on the re-igniter, the burners and one side of the transformer secondary are connected to earth. Alternatively Mains distribution networks with Line/Neutral have this characteristic. Mechanical Requirements Terminations HV Coil Output Terminal: 2.8*0.8mm (0.11 x0.032 ) Quick Connect tab. Input Connector: 11Way Receptacle 5mm/7.5mm Pitch. Tyco housing , pin Material (Housing Detail) Flame Retardant to standard UL94V- 0: Self extinguishing within 10sec. No flame drips that ignite. Mounting Method (Housing Detail) 2 screw mounting tabs have been integrated into the enclosure. Use No.8 Screw * 5/8 or ¾. Page 3 of 7
4 Technical Specifications Parameter Min Typ Max Units General Parameters Line Voltage Vac Frequency / Hz Current Input ma SR-Spark Rate *Note Spk/min Electrode & Cable Load to earth 40 pf Spark Max Load (40pF) *Note mm SV-Spark Output Peak Voltage * Note kv Spark Energy 15 mj Flame Sense Current *Note 2 ua FFRT-Flame Failure Reignition Time * Note sec FVT-Flame Verification Time * Note sec Note 1 : Maximum spark gap may be increase if load capacitance is reduced lower than Maximum specification. Note 2 : It is recommended that systems be designed to maintain the average minimum flame current above 0.5uA. This ensures the module does not spark due to drafts blowing flame away from the electrodes. Note 3 : CTQ Parameters ( CTQ - Critical to Quality ) Quality Assurance to monitor CTQ parameters. CTQ Data 120Vac 60Hz, 25C 15C ) Average Upper Pass Lower Units Limit Pass limit SR-Spark Rate Spk/Min SV-Spark Output Peak Voltage kv standard test load, equiv 40pF) FFRT-Flame Failure Reignition Time msec ( Flame current = 0.2uA (204 M )) FVT-Flame Verification Time (condition as FFRT) msec Definitions Flame Failure Re-ignition Time: Flame Verification Time: Spark Gap: Electrode & Cable Load to Earth: The period between loss of burner flame and a re-ignition attempt. The period between detection of burner flame and when sparking ceases. The closest distance from the electrode tip to any point on the cook-top range assembly that is connected to earth. The capacitance measured from the electrode to earth. Page 4 of 7
5 Environmental Specification Parameter Min Typ Max Units Operating Temperature ( continuous ) C Operating Temperature ( up to 1000 hours over 105 C life of product) Relative Humidity ( at 40C non condensing ) 95 % Page 5 of 7
6 Physical Dimensions Page 6 of 7
7 Wiring Installation Diagram Page 7 of 7
SERIES VAC Microprocessor-Based Intermittent Pilot Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION
R SERIES 35-703 120 VAC Microprocessor-Based Intermittent Pilot Ignition Control F-35-703 July 2016 FEATURES Safe start with DETECT-A-FLAME flame sensing technology Custom pre-purge and inter-purge timings
More informationSERIES VAC Microprocessor-Based Direct Spark Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION. Export Information (USA)
R SERIES 35-70 120 VAC Microprocessor-Based Direct Spark Ignition Control F-35-70 November 2015 FEATURES Safe start with DETECT-A-FLAME flame sensing technology Custom pre-purge and inter-purge timings
More informationBGH Series Hot Surface Ignition Control
Installation Instructions BGH Series Issue Date April 14, 2011 BGH Series Hot Surface Ignition Control Application The BASO Gas Products BGH Series Hot Surface Ignition (HSI) control is microprocessor
More information24 VAC Direct Spark Gas Ignition
Installation Instructions Issue Date March 3, 2017 Quick Reference Guide The Direct Spark Gas Ignition control module is designed for direct burner ignition and supervision. It can be used in new applications
More informationSERIES 35-63J APPLICATIONS FEATURES SPECIFICATIONS AGENCY CERTIFICATIONS
SERIES 35-63J INSTALLATION INSTRUCTIONS FOR REPLACING JOHNSON CONTROLS G77X AND OTHER MODELS WITH FENWAL SERIES 35-63J IP IGNITION CONTROL APPLICATIONS The Fenwal 35-63J series Intermittent Pilot Ignition
More informationQuick Reference Guide. Application. Gas Furnaces Boilers Water Heaters Commercial Cooking. Features
Installation Instructions E14QRG Issue Date June 28, 2018 Quick Reference Guide The Direct Spark Gas Ignition control module is designed for direct burner ignition and supervision. It can be used in new
More information24 VAC Intermittent Pilot Gas Ignition Control
C610U Universal 24 VAC Intermittent Pilot Gas Ignition Control Issue Date: 08/24/2016 Quick Reference Guide The C610U Universal Intermittent Pilot Gas Ignition Control module replaces many popular flame
More informationOperator: Save these instructions for future use!
50A66-743 Integrated Furnace Control Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL
More informationSERIES VAC Microprocessor-Based Direct Spark Ignition Control with Inducer Blower Relay FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION
R SERIES 35-61 24 VAC Microprocessor-Based Direct Spark Ignition Control with Inducer Blower Relay F-35-61 August 2015 FEATURES Safe start with DETECT-A-FLAME flame sensing technology Custom pre-purge
More informationEUROFLAT SERIES TYPES C... S... M...
EUROFLAT SERIES TYPES C... S... M... AUTOMATIC CONTROL SYSTEMS FOR GAS BURNERS AND GAS BURNING APPLIANCES WITH OR WITHOUT FAN APPLICATION The electronic systems of this range are suitable to control gas
More information21D83M-843 Integrated Single Stage Furnace Control Replacement Kit INSTALLATION INSTRUCTIONS
21D83M-843 Integrated Single Stage Furnace Control Replacement Kit INSTALLATION INSTRUCTIONS FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE
More information50M Integrated Single or Two-Stage HSI Integrated Furnace Control Kit INSTALLATION INSTRUCTIONS
50M56-743 Integrated Single or Two-Stage HSI Integrated Furnace Control Kit INSTALLATION INSTRUCTIONS FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD
More informationSpark Electrodes/Flame Sensors
Spark Electrodes/Flame Sensors For Gas Ignition Systems July 2016 DESCRIPTION Fenwal electrodes and sensors are an integral part of the ignition system for gas-fired equipment and ensure reliable ignition,
More informationINSTALLATION INSTRUCTIONS FOR SERIES 9 INTERMITTENT PILOT IGNITION CONTROL
INSTALLATION INSTRUCTIONS FOR SERIES 9 INTERMITTENT PILOT IGNITION CONTROL Figure 1 Series 9 Intermittent Pilot Ignition Control Application The Series 9 Intermittent Pilot Ignition Control is a microprocessor
More informationNew Power Vented Rheem FVIR Tanks
Technical Bulletin B06-08 Sept 26/ 2006 New Power Vented Rheem FVIR Tanks In the coming weeks new power vented FVIR tanks will be arriving in the field from our tank manufactures. We are supplying some
More informationEUROBOX SERIES TYPES CM... SM... MM...
EUROBOX SERIES TYPES CM... SM... MM... AUTOMATIC GAS BURNER CONTROL SYSTEMS FOR GAS BURNERS AND GAS BURNING APPLIANCES WITH OR WITHOUT FAN Application This range of electronic gas burner control systems
More informationSERIES VAC Microprocessor-Based Hot Surface Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION AGENCY CERTIFICATIONS
SERIES 35-65 24 VAC Microprocessor-Based Hot Surface Ignition Control F-35-65 August 2015 FEATURES Safe start with DETECT-A-FLAME flame sensing technology Custom pre-purge and inter-purge timings* 120/240
More informationOperator: Save these instructions for future use!
50A65-843 Universal Integrated Furnace Control INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING
More information1.03 DELIVERY, STORAGE, AND HANDLING Heater will be stored to secure against damage and handled per manufacturer s recommendations.
HVAC Guideline Specifications supraschwank Packaged Luminous Infrared Radiant Gas Heater Combined Intensity (produces both Low and High Intensity radiant output) Commercial/Industrial Applications Size
More informationNo. Of Ignition Trials: No. Of Re-Ignition Attempts. Reset by interrupting power for 5.0 Seconds. Diagnostic Output. Re-Ignition Limit Exceeded
DS1-Q INSTALLATION INSTRUCTIONS General Description Model DS1-Q is used to replace and eliminate the factory installed slow responding glow-bar igniter, sensor and associated wiring in commercial laundry
More information940ES Tankless Water Heater
Engineering Submittal Sheet Dimensions and Connections B C D C Combustion air inlet Exhaust outlet Optional combustion air inlet Top view Top view A Hot water outlet Cold water inlet E F Front view Side
More informationOperator: Save these instructions for future use!
WHITE-RODGERS 50A55-474 & 50A55-571 Integrated Furnace Controls INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
More information50A Integrated Furnace Control
Goodman White-Rodgers 0130F00005 PCBBF110 PCBBF123 50A55-743 0130F00005S PCBBF110S PCBBF123S 50A55-289 B1809926 PCBBF112 50T55-289 B1809926S PCBBF112S 50A55-743 Integrated Furnace Control INSTALLATION
More informationMICROFLAT SERIES TYPES C.../U T X
MICOFLAT SEIES TYPES C.../U T X AUTOMATIC GAS BUNE CONTOL SYSTEMS FO GAS BUNES AND GAS BUNING APPLIANCES WITH O WITHOUT FAN APPLICATION This range of electronic gas burner control systems is suitable for
More informationHot Surface Ignition (HSI) System Booklet
Hot Surface Ignition (HSI) System Booklet American Dryer Corporation 88 Currant Road Fall River MA 02720-4781 Telephone: (508) 678-9000 / Fax: (508) 678-9447 E-mail: techsupport@amdry.com 010298MFM/abe
More information940ES Tankless Water Heater
Engineering Submittal Sheet Overview and Certifications LOW-LEAD U P C C US Massachusetts Plumbing Board Approved Engineering Specifications Water heater shall be a Model Therm 940 ES. Plant shall consist
More informationCAUTION WARNING. 50T Integrated Furnace Control INSTALLATION INSTRUCTIONS DESCRIPTION PRECAUTIONS
50T35-743 Integrated Furnace Control INSTALLATION INSTRUCTIONS FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY
More informationMBCE-110/230FR Flame Sensor Module
MBCE-1001 APRIL 13, 2012 MBCE-110/230FR Flame Sensor Module DESCRIPTION The MBCE-110/230FR modules provide visual indication and electrical outputs that signal the user regarding flame presence in a combustion
More informationGAS COOKTOP MODELS: CTG365D, CTG305D, CTG304D TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING
By CNP INDUSTRIES, INC. P.O. Box 18645 Anaheim, Ca 92817 (877) 387-6721 INSTALLATION INSTRUCTIONS GAS COOKTOP MODELS: CTG365D, CTG305D, CTG304D IMPORTANT: Before beginning installation please read these
More informationFor use with models: PGM304-1, versions M-B PGM365-1, versions M-E, M-F & M-G
PGM-1 Cooktops For use with models: PGM304-1, versions M-B PGM365-1, versions M-E, M-F & M-G Install ation Instructions Part No. 65476 Rev. B Table of Contents Appliance Safety...1 Important Safety Instructions...2
More informationOperator: Save these instructions for future use!
50V64-743 Integrated Furnace Control for Furnaces with Variable Fan Speed INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY
More information50M56U-843 Universal Single Stage HSI Integrated Furnace Control Kit INSTALLATION INSTRUCTIONS
50M56U-843 Universal Single Stage HSI Integrated Furnace Control Kit INSTALLATION INSTRUCTIONS INSTALLER MUST READ PAGE 3 CONTAINS WIRING HARNESS AND BLOWER CONNECTION INSTRUCTIONS FOR ALL APPLICATIONS
More information50A Integrated Furnace Control
50A56-956 Integrated Furnace Control INSTALLATION INSTRUCTIONS FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY
More informationOperator: Save these instructions for future use!
031-01284-000/50A55-241 Integrated Furnace Control INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR
More informationEclipse Self-Check UV Scanner
856 Instruction Manual 10/18/2010 Eclipse Self-Check UV Model 5602-91 Version 1 Introduction The self-check UV is used for continuous gas or oil flames. A mechanical shutter in the scanner closes briefly
More informationC1210ES Tankless Water Heater
Engineering Submittal Sheet Dimensions and Connections B C D C Combustion air inlet Exhaust outlet Optional combustion air inlet Top view Top view A E Hot water outlet Cold water inlet F H J C I K G Front
More informationLFL Series Burner Flame Safeguard Control
LFL Series Burner Flame Safeguard Control Technical Instructions Document No. 74US LFL Rev. 2 November, 2004 The LFL is a compact electro-mechanical primary flame safeguard control designed to provide
More informationOperator: Save these instructions for future use!
WHITE-RODGERS 50A55-286 Integrated Furnace Control INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR
More informationC1050ES Tankless Water Heater
Engineering Submittal Sheet Dimensions and Connections B C D C Combustion air inlet Exhaust outlet Optional combustion air inlet Top view Top view A E F Hot water outlet Cold water inlet Inlet water filter
More informationMMI (40-34) Gas burner safty control
certified Qualitysystem ISO 9001 / EN 29001 A Honeywell Company Reg. Nr. 10529 (40-34) Gas burner safty control 0708.22-01-e/12/98 INTRODUCTION The Mod 40-34 gas burner safety control is suitable for fully
More informationFlame Safeguards LFE10. Building Technologies HVAC Products
7 71 Flame Safeguards LAE LFE Flame safeguards for burners with intermittent operation The LAE is used for the supervision and indication of oil flames The LFE is used for the supervision and indication
More informationITC 2000 HEATING CONTROL CABINET. Installation & Operation Manual
ITC 2000 HEATING CONTROL CABINET Installation & Operation Manual VTI, Incorporated 24 McMillan Way Newark, DE 19713 Phone (302) 738 0500 FAX (302) 738 6594 Revision Level 0.03 Manual No. 90003314 June,
More informationFlame Safeguards LFE10. Building Technologies HVAC Products
7 71 Flame Safeguards LAE LFE Flame safeguards for burners with intermittent operation The LAE is used for the supervision and indication of oil flames The LFE is used for the supervision and indication
More informationCATALOGUE PRODUITS - CSA - CSI - CSM - CSS - CSS2 - P16 - P19 - P20 - P25 - UV DETECTOR
CATALOGUE PRODUITS - CSA - CSI - CSM - CSS - CSS2 - P16 - P19 - P20 - P25 - UV DETECTOR CSA Range Full Sequence Control in an IP40 enclosure technology factfile The Pactrol CSA range of full sequence controls
More informationMMG Gas burner safety control
A Honeywell Company Gas burner safety control INTRODUCTION gas burner safety controls are suitable for fully automatic forced and induced draught gas burners which have an intermittent (expanding flame)
More informationMBCE-110/230FR Flame Sensor Module
MBCE-1001 FEBRAURY 6, 2017 MBCE-110/230FR Flame Sensor Module exida FMEDA SIL2 SEE NOTE 1 ON PAGE 4 DESCRIPTION The MBCE-110/230FR modules provide visual indication and electrical outputs that signal the
More informationelite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems
5/25/16 rev 6 elite Model ELN General Specification 550 W to 1.5 KW elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems 1.0 General General Specification This specification
More informationsouthbend A MIDDLEBY COMPANY INSTALLATION AND OPERATION MANUAL CG214 (E) CG314 (E) CG414 (E) CG220 (E) CG320 (E) CG325 (E) GAS BOILERS MODELS:
INSTALLATION AND OPERATION MANUAL GAS BOILERS MODELS: CG214 (E) CG314 (E) CG414 (E) CG220 (E) CG320 (E) CG325 (E) southbend A MIDDLEBY COMPANY 1100 Old Honeycutt Road Fuquay-Varina, NC 27526 (919) 552-9161
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS PROFESSIONAL COOKTOP MODELS 48 GAS COOKTOP WITH SEALED BURNERS** 48 NATURAL GAS MODEL *TN047-7 **THIS MODEL IS NOT FIELD CONVERITBLE FOR LP/PROPANE GAS. IT MUST BE ORDERED FROM
More informationMBCE-110/230UV Flame Sensor Module
MBCE-1002 FEBRUARY 3, 2017 MBCE-110/230UV Flame Sensor Module DESCRIPTION The MBCE-110/230UV modules provide visual indication and electrical outputs that signal the user regarding flame presence in a
More informationTECHNICAL SUPPORT: SERVICE BULLETIN #4 (v ) AB2017 HOT SURFACE IGNITION MODULE OVERVIEW
TECHNICAL SUPPORT: 1-800-403-3279 SERVICE BULLETIN #4 (v 1.80405) AB2017 HOT SURFACE IGNITION MODULE OVERVIEW WARNING Installation of this ignition control module may only be performed by a qualified and
More informationNew features make cooking a greater pleasure than
Small 9,200 Btu/hr (2.7 kw) burners Two-tiered control knobs Model CT36G Low-profile continuous grates Illuminated control panel Medium 12,000 Btu/hr (3.5 kw) burner Seamless drawn pan Large 15,000 Btu/hr
More informationIRIS IP65 IRIS UNISCAN APPLICATION MANUAL
IRIS IP65 IRIS UNISCAN APPLICATION MANUAL 01/08/05 DESCRIPTION TABLE OF CONTENTS PAGE IRIS - UNISCAN... 1 SPECIFICATION... 1 SUPPLY VOLTAGE: -... 1 OUTPUTS: -... 1 TRANSMISSION: -... 1 CABLE: -... 1 FLAME
More informationLGA... Gas Burner Controls. Siemens Building Technologies HVAC Products
7 418 Gas Burner Controls LGA... The LGA... are used for the startup and supervision of atmospheric gas burners of small to medium capacity (without fan) in intermittent operation. The LGA... and this
More informationIntermittent Pilot Ignition (IPI) and Direct Spark Ignition (DSI) Applications with Flame Current Probes
Application Note Issue Date February 22, 2018 Intermittent Pilot Ignition (IPI) and Direct Spark Ignition (DSI) Applications with Flame Current Probes Application This document is intended to aid the appliance
More informationINDEX APPLIANCE GAS WATER HEATER CONTROLS 150 ELECTRIC WATER HEATER THERMOSTATS 151 SNAP DISC CONTROLS/LIMITS/SWITCHES 152 GAS DRYER VALVES 153
INDEX GAS WATER HEATER CONTROLS 150 ELECTRIC WATER HEATER THERMOSTATS 151 SNAP DISC CONTROLS/LIMITS/SWITCHES 152 Model(s) Page(s) Flush Mount Fan/Limit/Attic Fan Control... 152 GAS DRYER VALVES 153 Model(s)
More informationBosch Greentherm T9800 SE 199 Gas Tankless Water Heater
Engineering Submittal Sheet Product Overview & Certifications Engineering Specifications The system shall consist of gas tankless water heater model Greentherm T9800 SE 199 as manufactured by Bosch Thermotechnology.
More informationGAS COOKTOP INSTALLATION INSTRUCTIONS BEFORE YOU BEGIN. IMPORTANT Save these instructions for local electrical inspector s use.
GAS COOKTOP INSTALLATION INSTRUCTIONS Please read this guide thoroughly before installation. To contact LG Electronics, 24 hours a day, 7 days a week: 1-800-243-0000 (U.S.A.) 1-888-542-2623 (Canada) Or
More informationInternet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #
INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #238-39387-00 THIS INSTRUCTION SUPPLEMENT IS ONLY INTENDED TO GIVE INSTALLATION INSTRUCTIONS AND INFORMATION RELATED TO THE INDUCED
More informationOld documentation - Only for your information! Product is not available anymore!
ControlBloc Control and safety combination with directconnected automatic burner control MPC Printed in Germany ösler Druck Edition 0.01 Nr. 229 481 1 6 Technical description The ControlBloc is the combination
More informationLGA... Gas Burner Controls. Siemens Building Technologies Landis & Staefa Division
7 418 ISO 9001 Gas Burner Controls LGA... The LGA... are used for the startup and supervision of atmospheric gas burners of low to medium capacity, without fan assistance, in intermittent operation. The
More informationELECTRONIC FIREPLACE DAMPER
ELECTRONIC FIREPLACE DAMPER Model: FSE Series The Flue Sentinel Electronic Fireplace Damper is designed to increase the comfort and energy efficiency of residential homes with gas-fired fireplaces. Consisting
More informationFIREYE M4RT1 FLAME SAFEGUARD CONTROLS DESCRIPTION
M-4000 JANUARY 29, 200 FIREYE M4RT1 FLAME SAFEGUARD CONTROLS WARNING: Selection of this control for a particular application should be made by a competent professional, licensed by a state or other government
More informationEUROBOX SERIES TYPES CM...N SM...N MM...N
EUROBOX SERIES TYPES CM...N SM...N MM...N AUTOMATIC CONTROL SYSTEMS FOR GAS BURNERS AND GAS BURNING APPLIANCES WITH OR WITHOUT FAN (MANUAL RESET) DESCRIPTION This series of electronic systems is suitable
More informationLAE10 LFE10. Use. Series 02
ISO 00 Flame Safeguards 7 7 LAE L Series 02 Supplementary data sheets 772 and 773 Flame safeguards for burners with intermittent operation. For safety reasons - self-test of flame supervision circuit,
More informationC1210ESC Tankless Water Heater
Engineering Submittal Sheet Overview and ertifications L W LOW-LEAD U P US Massachusetts Plumbing Board Approved Engineering Specifications Water heater shall be a Model Therm 1210 ES. Plant shall consist
More informationInstallation Instructions If you have questions, call 800-GE-CARES or visit our website at:
Installation Instructions If you have questions, call 800-GE-CARES or visit our website at: www.monogram.com 36" Stainless Steel Gas Cooktops Natural Gas Model: ZGU375NS LP Gas Model ZGU375LS Monogram.
More informationELECTRONIC FIREPLACE DAMPER
ELECTRONIC FIREPLACE DAMPER Model: FSE Low Profile Series The Flue Sentinel Electronic Fireplace Damper is designed to increase the comfort and energy efficiency of residential homes with gas-fired fireplaces.
More informationASGE NATIONAL TECHNICAL CONFERENCE AMERICAN SOCIETY OF GAS ENGINEERS
ASGE NATIONAL TECHNICAL CONFERENCE AMERICAN SOCIETY OF GAS ENGINEERS MGM GRAND HOTEL LAS VEGAS JUNE 7 9, 2010 BOB JACKSON 1 REFERENCES 1. Household Cooking Gas Appliances, American National Standard ANSI
More informationtcm100, tcm101 Series Temperature Control Modules and PTS100, PTS100/3 Pipe Temperature Sensors Operations Manual
tcm100, tcm101 Series Temperature Control Modules and PTS100, PTS100/3 Pipe Temperature Sensors Operations Manual This manual covers operation of the tcm100 and tcm101 Series Temperature Control Modules.
More informationCat. N. Cat. N (s) 1. DESCRIPTION - USE 3. OVERALL DIMENSIONS. Technology : 4. PREPARATION - CONNECTION 2. PRODUCT RANGE
Cat. N STOP & GO automatic resetting 87045 LIMOGES Cedex - FRANCE Telephone : + 33 5 55 06 87 87 Fax: + 33 5 55 06 88 88 Cat. N (s) : 4 062 88 / 4 062 89 CONTENTS PAGE 1. Description - Use... 1 2. Product
More informationModel LTN-3R Outdoor Rated Uninterruptible Power System Single Phase
Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase General Specification 550 VA/Watts 1300 VA/Watts 1.0 GENERAL This specification defines the electrical and mechanical characteristics
More informationLight oil - kerosene burner
Installation, use and maintenance instructions Light oil - kerosene burner One stage operation CODE MODEL TYPE 374374 G3B 437T 90 (4) - 05/0 TECHNICAL FEATURES TYPE 437T Thermal power output 9 35 kw.6
More informationForced draught gas burner
Installation, use and maintenance instructions Forced draught gas burner Code Model Type 3751982 GAS 3 519T80 291 (3) - 02/2010 DECLARATION Declaration of conformity in accordance with ISO / IEC 17050-1
More information24 VAC SYSTEM CONTROL KIT
24 VAC SYSTEM CONTROL KIT Model: CK-92F and CK-92FG Designed for use with the SWG Series Power Venter for controlling Natural Gas or L.P. Gas appliances with a 24 VAC Gas Valve and a 30-millivolt controlled
More informationPART 4 ELECTRICAL STANDARDS
PART 4 ELECTRICAL STANDARDS 1.0 INTRODUCTION AND SCOPE: These standards reflect the general requirements and recommendations of elevator contractors, with respect to the power distribution system to achieve
More informationInstallation/Operating Instructions for: The Equator. H.I. Series Indoor/Outdoor Infrared Patio Heaters
E asy R adiant W orks 12288 S id e R oa d 22, W ain fleet, O n ta rio, C anad a L 0S 1V 0 P h on e 905 89 9 3473 F ax 905 899 2262 w w w.easy rad iantw orks.co m em ail erw @ vaxxine.com Installation/Operating
More informationG34M Bulletin #69/ August 2003
ENGINEERING DATA G34M MULTI POSITION GAS FURNACE 12.4 to 31.0 kw Output 52.7 to 131.9 Mj Input 3.5 to 17.6 kw Nominal Add-on Cooling GAS FURNACES 50 Hz G34M Bulletin #69/490045 August 2003 Typical Applications
More information2 BURNER STOVE WITH GRILL
9 OWNERS MANUAL OWNERS MANUAL 2 BURNER STOVE WITH GRILL Part No. COMP546 IMPORTANT: Read these instructions for use carefully. Familiarise yourself with the appliance before connecting it to a gas container.
More informationPilot Burner and Direct Spark Ignition (DSI) Applications with Flame Rectification Sensing
Application Note Issue Date September 25, 2017 Pilot Burner and Direct Spark Ignition (DSI) Applications with Flame Rectification Sensing Application This document is intended to aid the appliance engineer
More informationIEC60601_1K. Medical electrical equipment Part 1: General requirements for basic safety and essential performance
Page 1 of 165 Report No.: E309264-D1028-1/A0/C0-UL Test Report issued under the responsibility of: IEC 60601-1 Medical electrical equipment Part 1: General requirements for basic safety and essential performance
More informationUV Scanner. Model Specification. Introduction. 854 Instruction Manual
854 Instruction Manual 10/11/010 UV Model 5600-91 C US Introduction This sensor features a high temperature and high sensitivity ultraviolet (UV) tube for monitoring gas or oil flames in applications that
More informationInstruction manual. WMCR-2, WMCR-3, WMCR-4 and WMCR-6 Circulator Zone Controllers WMCR-1E and WMCR-4E Expansion Modules
Instruction manual WMCR-2, WMCR-3, WMCR-4 and WMCR-6 Circulator Zone Controllers WMCR-1E and WMCR-4E Expansion Modules This manual must only be used by a qualified heating installer/service technician.
More informationQ - Series Boiler. Troubleshooting Manual
Q - Series Boiler Troubleshooting Manual WARNING There are a number of live tests that are required when fault finding this product. Extreme care should be used at all times to avoid contact with energized
More informationOPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVN/P-400 INDIRECT FIRED SPACE HEATERS
OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) For FVN/P-400 INDIRECT FIRED SPACE HEATERS CERTIFIED FOR USE IN CANADA AND U.S.A. As per Standard ANSI Z83.7/CSA 21.4 2000 Gas Fired Construction
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS PROFESSIONAL RANGE MODELS 24 ALL GAS, CONVECTION WITH OPEN BURNERS** 24 NATURAL GAS MODEL *TN480-7BW **THESE MODELS ARE FIELD CONVERITBLE FOR LP/PROPANE GAS.** 24 LP/PROPANE GAS
More informationPower Supply Display Module PSDM. Installation and Operation Manual
Power Supply Display Module PSDM Installation and Operation Manual Read this manual before using this product. Failure to follow the instructions and safety precautions in this manual can result in serious
More informationINTRODUCTION THIS MANUAL INCLUDES IMPORTANT SAFETY INFORMATION
INSTALLATION AND OPERATING INSTRUCTIONS FOR THE HARDY Fuel Oil Furnace Models D-140 & D-350 HARDY MANUFACTURING COMPANY, INC. 12345 ROAD 505 PHILADELPHIA, MS 39350 PHONE: (601) 656-5866 FAX: (601) 656-4559
More informationS9360, S9361, S9370, S9371 Integrated Boiler Controllers
S9360, S9361, S9370, S9371 Integrated Boiler Controllers INSTALLATION INSTRUCTIONS SPECIFICATIONS IMPORTANT: The specifications given in this publication do not include normal manufacturing tolerances.
More informationLine Pressure ( w.c.) Gas Supply Min. Max. Pressure ( w.c.) Natural Gas Propane Gas
HVAC Guideline Specifications WHISPER-JET: SET SERIES Two Stage Positive Pressure Gas-Fired Infrared Radiant Tube Type Heater Commercial/Industrial Applications Technical Summary Input Range: 80,000/60,000
More informationDATASHEET. Burner control unit FDA 601x
EN 298 / EN 230 2012 19 PCB 100x160mm 3HE/8TE socket DIN 41612 2-channel microprocessor controlled program air valve control for heating / cooling preventilation continuous operation with ionisation intermittent
More informationprestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE TSG-SOLO-9/04
prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE 2004-28 TSG-SOLO-9/04 Table of Contents INTRODUCTION Page 1 SERVICING TIPS AND INSTRUCTIONS Page 3 CONTROL MODULE DISPLAY -
More informationSECTION SAMPLE SPECIFICATION FOR BOILER CONTROLLER CONVERSION KIT
SECTION 23 09 33 SAMPLE SPECIFICATION FOR BOILER CONTROLLER CONVERSION KIT HARSCO INDUSTRIAL, PATTERSON-KELLEY NURO CONTROL CONVERSION KIT Part 1 - GENERAL 1.01 RELATED DOCUMENTS A. ANSI Z21.13 / CSA 4.9
More informationWARNING CAUTION 50T INSTALLATION INSTRUCTIONS DESCRIPTION PRECAUTIONS. Integrated Furnace Control
50T35-743 Integrated Furnace Control INSTALLATION INSTUCTIONS FAILUE TO EAD AND FOLLO ALL INSTUCTIONS CAEFULLY BEFOE INSTALLIN O OPEATIN THIS CONTOL COULD CAUSE PESONAL INJUY AND/O POPETY DAMAE. DESCIPTION
More informationFlame Safeguard Fault Code Diagnostics
Vino s Vine Tech Tips Series 02/2013 Flame Safeguard Fault Code Diagnostics As manager of Tech Services, it probably comes as no surprise I spend some time discussing fault codes and corresponding corrective
More informationNAVIEN AMERICA INC FITCH AVENUE IRVINE, CALIFORNIA, USA
Navien America Inc. Specification Details for the Navien models: CR-210 CR-210A For Indoor Installation Only For Potable Water Heating and Space Heating NAVIEN AMERICA INC. 17855 FITCH AVENUE IRVINE, CALIFORNIA,
More informationInstallation Instructions Horizon Natural Draft Electronic Ignition Gas Fireplaces
Installation Instructions Horizon Natural Draft Electronic Ignition Gas Fireplaces Installation Instructions Horizon Natural Draft Electronic Ignition 3 Sided Gas Fireplaces Natural Draft Electronic Ignition
More informationUltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW
12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes
More informationEKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING. Manual
EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING Manual Contents Introduction...3 Valve compatibility...3 Features...3 Application examples...3 Ordering...3 Operating the EKC 347...4-5
More informationInstallation Instructions
WARNING! INSTALLATION SAFETY INSTRUCTIONS Read these instructions completely and carefully. Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer
More information