DET-TRONICS SPECIFICATION DATA. Eagle Quantum EQ2200UVHT For Use With C7050B Continuous Duty High Temperature UV Flame Detector DESCRIPTION

Size: px
Start display at page:

Download "DET-TRONICS SPECIFICATION DATA. Eagle Quantum EQ2200UVHT For Use With C7050B Continuous Duty High Temperature UV Flame Detector DESCRIPTION"

Transcription

1 DET-TRONICS SPECIFICATION DATA Eagle Quantum EQ2200UVHT For Use With C7050B Continuous Duty High Temperature UV Flame Detector DESCRIPTION The EQ2200UVHT UV Flame Detector is used with the Eagle Quantum system to provide UV flame protection in continuous duty high temperature applications, such as turbine compartments, enclosures, generator rooms, etc. where ambient temperatures can continuously exceed +75 C (+167 F). The EQ2200UVHT is an electronic module assembly that is used in conjunction with a high temperature rated C7050B UV detector (with DE1888K3 high temperature rated UV sensor tube). The two devices are mounted in separate explosion-proof, watertight enclosures. The UV detector is rated for continuous duty in environments up to +125 C (+257 F). The electronic module is rated up to +75 C (+167 F). The electronic module cannot be located in the high temperature area. The UV detector and electronic module assembly can be separated up to 165 feet (50 meters) using high temperature rated 4 core shielded cable. In accordance with NFPA 72, the maximum separation distance is 20 feet (6 meters) using conduit or equivalent protection against mechanical damage. The detector is equipped with both automatic and manual optical integrity (oi) test capability. LED Detector status is indicated by a red LED that is visible through the viewing window on the cover of the electronic module junction box. Table 1 indicates the condition of the LED for each detector status. OUTPUT The output of the device is a status message that is sent to the gateway and logic controller in the Local Control Unit along the communication loop. System response to the message is determined at the time of configuration. The device supports ANSI/NFPA 72 Class A, Style 7 communication with the LCU. *oi is Detector Electronics' Trademark for its patented Optical Integrity Systems, U.S. Patent 3,952,196, United Kingdom Patent 1,534,969, Canada Patent 1,059,598. Detector Electronics Corporation /

2 Table 1 Detector Status/Indications Status Normal with automatic oi selected Normal with manual oi selected Fault Fire LED Blinks every 5 seconds Blinks every 10 seconds Off On ADDRESSABILITY Device identification is accomplished by setting switches on a DIP switch assembly located on the electronic module (valid address range is 5 to 250). ALARM LOG The detector maintains an alarm log in non-volatile memory. The time and date for the last eight alarms are logged. TERMINAL WIRING BOARD External wiring is connected to plug-in screw terminal connectors on the terminal wiring board located inside the electronic module junction box. ENCLOSURE The explosion-proof NEMA/Type 4X enclosure is designed for use in a variety of hazardous locations. SOFTWARE SELECTABLE OPTIONS The following software selectable options are available using a PC running Det-Tronics configuration software. Operating Mode The operating mode determines the type of logic that the UV flame detector will use for processing fire signals. (Arc rejection mode is the recommended setting). Arc Rejection Mode (Factory Recommended). The arc rejection mode enables the detector to prevent nuisance fire alarms caused by UV from short-duration electrical arcs or electrostatic discharge, while maintaining the ability to reliably detect the UV given off by a flame. The arc rejection mode is not recommended unless these false alarm sources are present within the application to be protected. Typical applications that benefit from arc rejection logic include electrostatic coating processes and uncontrolled environments where transient UV sources can be present, such as many typical outdoor applications. The arc rejection algorithm examines the radiant energy level detected within a specified unit of time (timed gate). The output of the detector is determined by three variables: sensitivity level gate length number of consecutive gates required. Different combinations of these variables allow for various levels of transient arc rejection capability. There are four arc rejection levels (very high, high, medium, and low) that are selectable for the detector through the PC. Refer to Table 2. The proper arc rejection setting for a given application must be determined through testing. For indoor applications with known electrostatic energy fields within 15 feet of the detector, an arc rejection setting of very high or high is typical. For outdoor applications, medium or low arc rejection settings are typical. It is recommended that each detector be thoroughly tested at the programmed arc rejection setting within the ambient conditions that will be present during normal operation. This will help to ensure that the selected arc rejection setting is proper for the application. Standard Mode. In the standard processing mode, the detector output (measured in counts per second) is compared to the fire threshold (the sensitivity setting as described below). If the radiant energy level from the fire exceeds the selected alarm threshold level, the time delay begins (if a time delay is selected). If the radiant energy level from the fire remains above the selected sensitivity level for the duration of the time delay, the fire alarm output is activated. In every application, it is crucial to ensure that the radiant ultraviolet energy level from the expected fire at the required distance from the detector will exceed the selected sensitivity level. Standard signal processing is recommended for controlled indoor applications only. 2

3 Table 2 Arc Rejection Levels for UV Detector Arc Rejection Level Consecutive Gates Gate Length Sensitivity* Min. Processing Time Very High 8 1/16 Second Very High (8 CPS) 0.5 Second High 4 1/16 Second Very High (8 CPS) 0.25 Second Medium 4 1/8 Second Very High (8 CPS) 0.5 Second Low 4 1/4 Second Very High (8 CPS) 1.0 Second * CPS = counts per second Sensitivity Whether the Standard or Arc Rejection mode is selected, the sensitivity setting must always be programmed. The selected sensitivity level determines the fire alarm threshold setpoint. The higher the sensitivity level, the greater the detection range, but the possibility of false alarms will be increased. Four sensitivity levels are selectable. Refer to Table 3. The sensitivity setting must be appropriate for the anticipated fire size at the required distance from the detector. Time Delay Arc rejection mode If the fire signal meets the programmed arc rejection requirements, the time delay begins. A fire output is generated if the fire signal continues for the duration of the time delay. Standard mode A fire output is generated only if the fire signal exceeds the sensitivity setting for the entire duration of the programmed time delay. Automatic or Manual oi The oi system uses an internally generated UV test signal to determine the relative condition of the detector and its optical surfaces. If automatic oi testing is selected, the oi test is automatically performed once every minute. The automatic oi test does not generate an alarm output or interfere with normal detector operation. The manual oi test is initiated using a button on the point display screen on the PC. The manual oi test can be used in addition to automatic oi to test UV detector sensitivity. FEATURES UV detector rated for +125 C continuous duty Long detection range to gasoline fires LED indicates normal operation, fire and fault conditions Microprocessor based circuitry Selectable automatic or manual oi Adjustable sensitivity and time delay for fire output Selectable latching or non-latching for fire and fault outputs Programmable for arc rejection or standard signal processing method Fire overrides fault for safety No calibration required Operates under adverse weather conditions and in dirty environments Field addressable Fault isolation Pass through communication circuitry on power loss Non-volatile memory for configuration and logging of alarms Screw terminal connectors RFI / EMI hardened Swivel mounting bracket for ease of installation and positioning FMR, CSA, CENELEC and CE Mark Certifications FMR performance verified per ANSI/NFPA 72 and FM Table 3 Sensitivity Levels for UV Detector Sensitivity Level Equivalents Sensitivity Level Selected Nominal Fire Alarm Threshold In Counts per Second (CPS) Very High 8 High 24 Medium 48 Low

4 SPECIFICATIONS INPUT VOLTAGE 24 vdc nominal, 18 to 30 vdc. 10% overvoltage will not cause damage to the equipment. INPUT POWER 2.0 watts typical, 4.0 watts maximum during oi test. TEMPERATURE RANGE Electronic Module: 40 F to +167 F ( 40 C to +75 C). UV Detector: 40 F to +257 F ( 40 C to +125 C). Storage: 67 F to +185 F ( 55 C to +85 C). HUMIDITY RANGE 5 to 95% relative humidity, can withstand 100% condensing humidity for short periods of time. WIRING REQUIREMENTS Wiring to the UV detector must be between 12 and 18 AWG (approximate metric equivalent = 4 and 1.0 mm 2 ) with a minimum voltage rating of 600 volts rms and a minimum temperature rating of 125 C. The use of shielded cable is highly recommended to provide maximum protection from RFI/EMI interference. Consult Eagle Quantum system manual for communication network wiring requirements. VIBRATION Meets MIL SPEC 810C, method 514.2, curve AW. DIMENSIONS See Figures 2, 3 and 4. 5/16-18 UNC SPECTRAL SENSITIVITY RANGE UV radiation over the wavelength of 1850 to 2450 angstroms (solar blind). CONE OF VISION The detector has a 90 degree cone of vision with the highest sensitivity lying along its central axis. See Figure 1. DETECTOR LOCK NUT 1 3/8 INCH GLAND NUT USED TO ROTATE SWIVEL/DETECTOR ASSEMBLY TO DESIRED POSITION 2.5 (6.4) FLAME SENSITIVITY The detector has four adjustable sensitivity settings plus transient arc rejection capabilities. MOUNTING BASE 2.5 (6.4) RESPONSE TIME The detector is selectable for a 0 to 7 second time delay. 2.0 (5.08) DIA. 120 ±2 (2) OUTPUTS Digital communication, transformer isolated (78.5 kbps). 100% REPRESENTS THE MAXIMUM DETECTION DISTANCE FOR A GIVEN FIRE. THE SENSITIVITY INCREASES AS THE ANGLE OF INCIDENCE DECREASES (6.4) DIA. A (0.64) DIA. (3) Figure 2 Q9001B Swivel Mounting Bracket Dimensions in Inches (Centimeters) /2 INCH NPT OR 20 MM 4.75 (12.06) DETECTION DISTANCE (PERCENT) (6.35) 10 A1987 Figure 1 Cone of Vision of UV Detector D573 Figure 3 UV Detector Dimensions in Inches (Centimeters) 4

5 CERTIFICATION FMR/CSA: Electronic Module: Class I, Div. 1, Groups B, C and D. Class I, Div. 2, Groups A, B, C, and D (T4A). Class II, Div. 1, Groups E, F, and G. Class II, Div. 2, Groups F and G (T4A). Class III. NEMA/Type 4X. Ambient temperature limits: 40 C to +75 C (0.71) 3.39 (8.6) 4.66 (11.8) UV Detector: Class I, Div. 1, Groups B, C and D (T4). Class I, Div. 2, Groups A, B, C, and D (T4). Class II, Div. 1 & 2, Groups E, F, and G (T4). Class III (T4). NEMA/Type 4X. Ambient temperature limits: 40 C to +125 C (13.21) 2.69 (6.83) CENELEC: Electronic Module EEx d IIC T4 (Tamb = 60 C to +75 C) EEx d IIC T5 (Tamb = 60 C to +65 C) EEx d IIC T6 (Tamb = 60 C to +50 C) IP (0.81) OVAL SLOT MOUNTING (TYPICAL FOUR PLACES) UV Detector EEx d IIB +H 2 T4 (Tamb = 55 C to +125 C) EEx d IIB +H 2 T5 (Tamb = 55 C to +90 C) EEx d IIB +H 2 T6 (Tamb = 55 C to +75 C) IP66. CE: Conforms to all relevant European Directives. SHIPPING WEIGHT UV Detector Aluminum: 1.2 pounds (0.6 kg) Stainless Steel: 2.2 pounds (1.0 kg) (16.8) 3/4 INCH NPT OR 25/20 MM 1.28 (3.25) Electronic Module Aluminum: 4.0 pounds (1.8 kg). Stainless Steel: 9.5 pounds (4.3 kg). B1988 Figure 4 EQ2200UVHT Junction Box Dimensions in Inches (Centimeters)

6 INSTALLATION LOOSEN TWO SCREWS TO REMOVE TERMINAL WIRING BOARD Refer to the Eagle Quantum system manual, form number , for complete instructions regarding wiring and installation. WARNING Do not open any junction box or device enclosure when power is applied without first de-classifying the hazardous area. ELECTRONIC MODULE ASSEMBLY 1. Mount the device on a solid surface that is free of vibration. 2. Remove the cover from the junction box. 3. Loosen the three captive screws that hold the electronic module to the terminal wiring board and remove the module. See Figure Loosen (do not remove) the two captive screws that secure the terminal wiring board inside the junction box, and remove the terminal wiring board. See Figure 6. (The terminal blocks are located on the bottom side of the terminal wiring board.) Figure 6 Terminal Wiring Board with Electronic Module Removed IMPORTANT Insulate the shields to prevent shorting to the device housing or to any other conductor. Terminals 4 and 9 (shield) are connected internally, as are terminals 5 and 8 (24 vdc +) and terminals 6 and 7 (24 vdc ). 6. Re-install the terminal wiring board inside the junction box. A Connect the UV detector wires to the appropriate points on the P3 terminal. Connect the 24 vdc power wires and the communication network cable to the appropriate points on the P2 terminal. See Figure 7 for terminal identification. Note that the plug-in terminals can be removed to facilitate wiring. P2 1 2 SHIELD A COM 1 3 B 4 SHIELD LOOSEN THREE SCREWS TO REMOVE ELECTRONIC MODULE 5 + ELECTRONIC MODULE UV FLAME DETECTOR TERMINAL BLOCK P VDC TERMINAL WIRING BOARD A B 2 9 SHIELD C 3 10 A D 4 11 B COM 2 A1992 A SHIELD Figure 5 Electronic Module Installed on Terminal Wiring Board Figure 7 EQ2200UVHT Wiring Terminal 6

7 BINARY VALUE OPEN OPEN } LEAVE IN OPEN POSITION TERMINAL CAP BLIND HOLE NODE ADDRESS EQUALS THE ADDED VALUE OF ALL CLOSED ROCKER SWITCHES Figure 8 Field Device Address Switches OPEN = OFF CLOSED = ON A1557 CATCH CATCH SCREW COVER LOCKING ASSEMBLY STRAP 7. Set the rocker switches for the desired address. Each device on the LON/SLC must be assigned a unique address. This is accomplished by setting DIP switches on the module s circuit board. See Figure 8. Each rocker switch has a specific binary value. The node address is equal to the added value of all closed rocker switches. All open switches are ignored. The valid address range is from 5 to 250. Refer to the Eagle Quantum system manual (form ) for additional information. 8. Re-install the electronic module, ensuring that the connector is aligned correctly. Tighten the three captive screws that hold the electronic module in place. 9. Replace the junction box cover and hand tighten to ensure proper sealing. UV FLAME DETECTOR Wiring to the UV detector must be between 12 and 18 AWG with a minimum voltage rating of 600 volts rms and a minimum temperature rating of 125 C. The use of shielded cable is highly recommended to provide maximum protection from RFI/EMI interference. 1. Mount the Swivel Mounting Bracket using 1/4 inch (M6) screws with a length of at least 1 inch (25 mm). The mounting surface should be free of BARREL WINDOW CAP Figure 10 Detector with Cover Locking Assembly vibration. Allow adequate space around the swivel to facilitate aiming and wiring of the detector. Armored flexible conduit should be used for the final 3 feet (one meter) of the cable run to allow for aiming and alignment of the detector. 2. Attach the detector to the Swivel Mounting Bracket. 3. Disassemble the detector enclosure by turning the housing cover counterclockwise. See Figure 9. If the detector is equipped with a cover locking device, it must be loosened using a hexagonal (Allen) wrench (see Figure 10). 4. Connect the wires to the appropriate screw terminals on the detector terminal block. See Figure 7 for terminal identification. Do not ground the shield to the detector housing. (Tape off the shield and leave it disconnected.) B0769 TERMINAL BLOCK INDEX PIN UV SENSOR TUBE MODULE A1994 HOUSING COVER Figure 9 High Temperature UV Detector

8 F oi RING UV TEST LAMP* OPENING 10. Aim the detector at the potential hazard and tighten the nut on the swivel mounting bracket. 11.Install any optional accessories (such as air shields). ORDERING INFORMATION When ordering, please specify: SPLIT IN oi RING (MUST BE POSITIONED ON THE DOWNWARD SIDE OF UNIT WHEN MOUNTED) EQ2200UVHT C7050B ( Series) Electronic Module High Temperature UV Detector * UV TEST LAMP OPENING MUST NOT BE ALIGNED WITH SPLIT IN oi RING Figure 11 Viewing Window of UV Detector B1991 One electronic module assembly and one high temperature UV detector are required for each detection point. Specify: Material: Aluminum or Stainless Steel 5. Remove the UV sensor tube module from its shipping package. When handling the sensor tube module, be careful not to touch the sensor tube, since oil from the skin can attenuate UV radiation, reducing the sensitivity of the tube. Conduit entry size: 3/4 inch NPT or 25/20 MM for electronic module 1/2 inch NPT or 20 MM for UV Detector 6. Using the index pin as a guide, install the sensor module on the detector terminal block. 7. Re-assemble the detector housing. If the detectors are equipped with cover locking devices, loosen the clamp sufficiently so that the catch can be seated in the blind hole provided on the terminal cap. See Figure 10. The clamp must then be fastened securely around the detector barrel by tightening with the proper tool. 8. Clean the viewing window and oi ring. 9. Check the viewing window surface (Figure 11) and ensure that: A) The oi source (UV test lamp opening) is located on top. B) The split in the oi reflective ring is not aligned with the UV test lamp opening on the detector module. C) The split in the oi ring is directed downward to prevent a buildup of contaminants between the oi ring and the viewing window. Replacment Parts: Part Number Description Electronic Module Assembly Only DE1888K3 UV Sensor Module with oi Oi Reflector Ring For additional information or for assistance in designing a system to meet the needs of a specific application, please contact: Detector Electronics Corporation 6901 West 110th Street Minneapolis, Minnesota USA Operator: (952) or (800) 765-FIRE Customer Service: (952) Fax: (952) Web site: detronics@detronics.com REGISTERED BY UL AND BSI ISO 9001 REGIS T E RE D FIR M REGIS T E RED IRM NO. A2305 NO Detector Electronics Corporation 6901 West 110th Street Minneapolis, Minnesota Operator (952) or (800) 765-FIRE Customer Service (952) Fax (952) detronics@detronics.com

DET-TRONICS. SPECIFICATION DATA Eagle Quantum Premier Fire and Gas Detection / Releasing System APPLICATION FEATURES

DET-TRONICS. SPECIFICATION DATA Eagle Quantum Premier Fire and Gas Detection / Releasing System APPLICATION FEATURES DET-TRONICS SPECIFICATION DATA Eagle Quantum Premier Fire and Gas Detection / Releasing System APPLICATION Eagle Quantum Premier is a configurable, distributed, intelligent safety system providing flame

More information

Instructions Protect ir Multispectrum IR Flame Detector with Pulse Output X3300

Instructions Protect ir Multispectrum IR Flame Detector with Pulse Output X3300 Instructions 95-8517 Protect ir Multispectrum IR Flame Detector with Pulse Output Detector Electronics Corporation 6901 West 110th Street Minneapolis, Minnesota 55438 USA Tel: 952.941.5665 or 800.765.3473

More information

Instructions

Instructions Instructions 95-8465-03 Unitized Ultraviolet Flame Detector/Controller U7602E Detector Electronics Corporation 6901 West 110th Street Minneapolis, Minnesota 55438 USA Tel: 952.941.5665 or 800.765.3473

More information

Multi-Spectral, Digital, Infrared Electro-Optical. FSC Model No. s. Unitized, Two Stage, Quick Response Flame Detectors.

Multi-Spectral, Digital, Infrared Electro-Optical. FSC Model No. s. Unitized, Two Stage, Quick Response Flame Detectors. Fire Sentry Corporation (FSC) 593 Apollo Street Tel.: 714-671-1100 Brea, California 92821 Fax: 714-671-5821 Multi-Spectral, Digital, Infrared Electro-Optical FSC Model No. s FS10-R and FS10-A Unitized,

More information

Instructions

Instructions Instructions 9--0 Infrared Fire Detection System R/C09B Detector Electronics Corporation 90 West 0th Street Minneapolis, Minnesota USA Tel: 9.9. or 00.. Fax: 9.9.0 /0 9--0 Table of Contents APPLICATION...

More information

ADDENDUM. xwatch Explosion-Proof Camera with X-Series Flame Detectors DESCRIPTION GENERAL APPLICATION INFORMATION

ADDENDUM. xwatch Explosion-Proof Camera with X-Series Flame Detectors DESCRIPTION GENERAL APPLICATION INFORMATION ADDENDUM xwatch Explosion-Proof Camera with X-Series Flame Detectors DESCRIPTION The xwatch Explosion-Proof Camera is available as a factory installed option with any of the Det Tronics X Series line of

More information

INSTRUCTIONS. Eagle Quantum Premier (EQP) Addressable Smoke & Heat (ASH) Module EQ3750ASH. 5.1 Rev: 4/

INSTRUCTIONS. Eagle Quantum Premier (EQP) Addressable Smoke & Heat (ASH) Module EQ3750ASH. 5.1 Rev: 4/ INSTRUCTIONS Eagle Quantum Premier (EQP) Addressable Smoke & Heat (ASH) Module EQ3750ASH 5.1 Rev: 4/17 INSTRUCTIONS Eagle Quantum Premier (EQP) Addressable Smoke & Heat (ASH) Module EQ3750ASH DESCRIPTION

More information

SAFETY MANUAL. X2200 UV, X9800 IR, X5200 UVIR SIL 2 Certified Flame Detectors

SAFETY MANUAL. X2200 UV, X9800 IR, X5200 UVIR SIL 2 Certified Flame Detectors SAFETY MANUAL X2200 UV, X9800 IR, X5200 UVIR SIL 2 Certified Flame Detectors SAFETY-CERTIFIED Flame DETECTORs This manual addresses the specific requirements and recommendations applicable to the proper

More information

Instructions xwatch Explosion-Proof Camera X /

Instructions xwatch Explosion-Proof Camera X / Instructions xwatch Explosion-Proof Camera X7050 2.1 6/09 Table Of Contents Description............................................ 1 features............................................... 1 General Application

More information

Instructions. Explosion Proof Smoke Detector U Rev: 9/

Instructions. Explosion Proof Smoke Detector U Rev: 9/ Instructions Explosion Proof Smoke Detector U0. Rev: 9/ 9-7 Table of Contents OVERVIEW... FEATURES... BENEFITS... SPECIFICATIONS... OPERATION... Warm Up... Outputs... Integral Wiring Compartment... LED...

More information

Instructions Protect ir Multispectrum IR Flame Detector X3300 9/

Instructions Protect ir Multispectrum IR Flame Detector X3300 9/ Instructions 95-8502 Protect ir Multispectrum IR Flame Detector X3300 Detector Electronics Corporation 6901 West 110th Street Minneapolis, Minnesota 55438 USA Tel: 952.941.5665 or 800.765.3473 Fax: 952.829.8750

More information

Instructions

Instructions Instructions 95-8331-02 UVIR Flame Detection System R7495 Dual Channel Controller C7052J Detector Detector Electronics Corporation 6901 West 110th Street Minneapolis, Minnesota 55438 USA Tel: 952.941.5665

More information

Instructions. Multispectrum IR Flame Detector X Rev: 1/

Instructions. Multispectrum IR Flame Detector X Rev: 1/ Instructions Multispectrum IR Flame Detector X3301 Rev: 1/16 Table of Contents DESCRIPTION....1 Outputs...1 LED...2 oi (Optical Integrity)...2 Communication....3 Data Logging....3 Integral Wiring Compartment...3

More information

Instructions. Duct Mount Accessory Q Rev: 11/

Instructions. Duct Mount Accessory Q Rev: 11/ Instructions Duct Mount Accessory Q5016 Rev: 11/16 95-8752 Table of Contents DESCRIPTION...1 FEATURES...1 OPERATION...1 SPECIFICATIONS.... 2 INSTALLATION... 2 Detector Location...2 Tools for Assembly...4

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES SECTION 26 36 23 AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Model 3300 Technical Support and Installation Manual

Model 3300 Technical Support and Installation Manual Model 3300 Technical Support and Installation Manual Manual # T15011 Document Revision: A1 1. OVERVIEW 1 2. BASIC OPERATION 1 2.1 General 1 2.2 Field-of-View 2 2.3 Range 2 2.4 Environment 2 2.5 Configuration

More information

Instructions

Instructions Instructions 95-8440-02 PointWatch Infrared Hydrocarbon Gas Detector PIR9400 Detector Electronics Corporation 6901 West 110th Street Minneapolis, Minnesota 55438 USA Tel: 952.941.5665 or 800.765.3473 Fax:

More information

Instructions R8471J Gas Controller for use with Model OPECL Open Path Eclipse IR Gas Detector 1.1 1/

Instructions R8471J Gas Controller for use with Model OPECL Open Path Eclipse IR Gas Detector 1.1 1/ Instructions R8471J Gas Controller for use with Model OPECL Open Path Eclipse IR Gas Detector 1.1 1/08 Table Of Contents Section I Installation and Startup.................. 1 INSTALLATION............................................

More information

Instructions. IR Flame Detector X Rev: 1/

Instructions. IR Flame Detector X Rev: 1/ Instructions IR Flame Detector X9800 Rev: 1/16 95-8554 Table of Contents DESCRIPTION....1 Outputs...1 LED...2 oi (Optical Integrity)...2 Communication...3 Data Logging...3 Integral Wiring Compartment...3

More information

Instructions IR Flame Detector X Rev: 6/

Instructions IR Flame Detector X Rev: 6/ Instructions 95-8554 IR Flame Detector X9800 Rev: 6/13 95-8554 Table of Contents Description.... 1 Outputs... 1 LED... 2 oi (Optical Integrity)... 2 Communication... 3 Data Logging... 3 Integral Wiring

More information

INSTRUCTIONS. PointWatch Infrared Hydrocarbon Gas Detector PIR9400

INSTRUCTIONS. PointWatch Infrared Hydrocarbon Gas Detector PIR9400 To navigate through this document, click on the Bookmarks and Page button and use the bookmarks to access information. INSTRUCTIONS PointWatch Infrared Hydrocarbon Gas Detector PIR9400 11/96 Form 95-8440

More information

MODEL SS4-A/-A2 (CENELEC)

MODEL SS4-A/-A2 (CENELEC) Model SS4-A/-A2 Optical Fire Detector Page i Fire Sentry Corporation (FSC) 23311 La Palma Avenue Tel.: 714-694-2700 Yorba Linda, California 92887 Fax: 714-694-2701 Multi-Spectrum Digital Electro-Optical

More information

RED1. Technical Support And Installation Manual. Models ST, E1, E2, E3, E4, and 420. Approved

RED1. Technical Support And Installation Manual. Models ST, E1, E2, E3, E4, and 420. Approved RED1 Models ST, E1, E2, E3, E4, and 420 Technical Support And Installation Manual 210111 FM Approved 1. OVERVIEW 1 2. BASIC OPERATION 3 2.1 General 3 2.2 Field-of-View 4 2.3 Range 4 2.4 Environment 4 2.5

More information

Instructions. Det-Tronics SmokeWatch Explosion Proof Smoke Detector U Rev: 3/

Instructions. Det-Tronics SmokeWatch Explosion Proof Smoke Detector U Rev: 3/ Instructions Det-Tronics SmokeWatch Explosion Proof Smoke Detector U5015 Rev: 3/17 95-8723 Table of Contents OVERVIEW...1 FEATURES...1 BENEFITS...1 SPECIFICATIONS...2 OPERATION...3 Warm Up...3 Outputs...3

More information

SAFETY MANUAL. Multispectrum IR Flame Detector X3301

SAFETY MANUAL. Multispectrum IR Flame Detector X3301 SAFETY MANUAL Multispectrum IR Flame Detector X3301 SAFETY-CERTIFIED MODEL X3301 MULTISPECTRUM INFRARED DETECTOR This manual addresses the specific requirements and recommendations applicable to the proper

More information

S200Plus Triple Infra Red Flame Detector Triple Waveband Infra-Red Flame Detection

S200Plus Triple Infra Red Flame Detector Triple Waveband Infra-Red Flame Detection DATASHEET S200Plus Triple Infra Red Flame Detector Triple Waveband Infra-Red Flame Detection Features: Unrivalled black body rejection over a wide range of source temperatures Triple waveband infra-red

More information

Instructions Multispectrum IR Flame Detector with Pulse Output X Rev: 12/

Instructions Multispectrum IR Flame Detector with Pulse Output X Rev: 12/ Instructions 95-8578 Multispectrum IR Flame Detector with Pulse Output 6.1 Rev: 12/13 95-8578 Table of Contents DESCRIPTION... 1 Outputs... 2 LED... 2 oi (Optical Integrity)... 2 Communication... 3 Data

More information

MINERVA S200Plus. Fire Detection. Triple Waveband Infra-Red Flame Detection. Features: Minerva S200PLUS

MINERVA S200Plus. Fire Detection. Triple Waveband Infra-Red Flame Detection. Features: Minerva S200PLUS MINERVA S200Plus Triple Waveband Infra-Red Flame Detection Features: Unrivalled black body rejection over a wide range of source temperatures Triple waveband infra-red solar blind flame detection for optimum

More information

Instructions Dual Spectrum Infrared Flame Detector PM-5MPX. 4.1 Rev: 8/

Instructions Dual Spectrum Infrared Flame Detector PM-5MPX. 4.1 Rev: 8/ Instructions 95-8562 Dual Spectrum Infrared Flame Detector Rev: 8/13 95-8562 Table of Contents Application... 1 Detector use in hazardous areas... 2 Electrical Characteristics.... 2 Environmental Characteristics...

More information

Instructions Infrared Hydrocarbon Gas Detector PointWatch Eclipse Model PIRECL /

Instructions Infrared Hydrocarbon Gas Detector PointWatch Eclipse Model PIRECL / Instructions 95-8526 Infrared Hydrocarbon Gas Detector PointWatch Eclipse Model PIRECL 11/06 95-8526 Table of Contents APPLICATION.............................. 1 OPERATION OVERVIEW.....................

More information

The Most Versatile Flame Detectors in the World. Optical Flame Detection Solutions

The Most Versatile Flame Detectors in the World. Optical Flame Detection Solutions The Most Versatile Flame Detectors in the World Optical Flame Detection Solutions The Global Leader in Flame Detection Superior Performance and Reliability Flame detection is the very essence of the proud

More information

Addendum HART Communication with the X2200 UV Flame Detector 1.1 4/

Addendum HART Communication with the X2200 UV Flame Detector 1.1 4/ Addendum HART Communication with the X2200 UV Flame Detector 1.1 4/09 Table Of Contents Interconnecting the HART Communicator with the Detector.... 1 HART Device Description Language.... 3 Detector Wiring.......................................

More information

Instructions IR Flame Detector with Pulse Output X Rev: 6/

Instructions IR Flame Detector with Pulse Output X Rev: 6/ Instructions 95-8555 IR Flame Detector with Pulse Output 5.1 Rev: 6/13 95-8555 Table of Contents DESCRIPTION....1 Outputs...2 LED...2 oi (Optical Integrity)...2 Communication...3 Data Logging...3 Integral

More information

Instructions. Multispectrum IR Flame Detector with Pulse Output X Rev: 10/

Instructions. Multispectrum IR Flame Detector with Pulse Output X Rev: 10/ Instructions Multispectrum IR Flame Detector with Pulse Output Rev: 10/15 95-8736 Table of Contents DESCRIPTION....1 Outputs...2 LED...2 oi (Optical Integrity)...2 Communication....3 Data Logging....3

More information

Dräger Flame 2500 Flame Detection

Dräger Flame 2500 Flame Detection Dräger Flame 2500 Flame Detection Working in areas with combustible gases, vapours or materials requires fire/ flame detection as a life-saving necessity. The best solutions must combine state-of-the-art

More information

SharpEye 20/20I. Triple IR (IR 3 ) Flame Detector. User's and Maintenance Manual

SharpEye 20/20I. Triple IR (IR 3 ) Flame Detector. User's and Maintenance Manual SharpEye 20/20I Triple IR (IR 3 ) Flame Detector User's and Maintenance Manual Doc. No. TM 20/20I, Rev. (4)-99 July 1999 Factory Mutual Approved Class I Div. 1 Groups B, C, D Class II Div. 1 Groups E,

More information

DESIGN MANUAL. The information in this doucment is applicable to sensors built in September, 2009 or later (Firmware 3.0)

DESIGN MANUAL. The information in this doucment is applicable to sensors built in September, 2009 or later (Firmware 3.0) DESIGN MANUAL MODEL GIR910 INFRARED CARBON DIOXIDE (CO 2 ) GAS SENSOR 70091 The information in this doucment is applicable to sensors built in September, 2009 or later (Firmware 3.0) The information and

More information

ICS Regent. Fire Detector Input Modules PD-6032 (T3419)

ICS Regent. Fire Detector Input Modules PD-6032 (T3419) ICS Regent Fire Detector Input Modules (T3419) Issue 1, March, 06 Fire detector input modules provide interfaces for 16 fire detector inputs such as smoke detectors, flame detectors, temperature detectors,

More information

The Most Versatile Flame Detectors in the World. Optical Flame Detection Solutions

The Most Versatile Flame Detectors in the World. Optical Flame Detection Solutions The Most Versatile Flame Detectors in the World Optical Flame Detection Solutions The Global Leader in Flame Detection Superior Performance and Reliability Flame detection is the very essence of the proud

More information

Dräger Flame 2100 Flame Detection

Dräger Flame 2100 Flame Detection Dräger Flame 2100 Flame Detection Working in areas with combustible gases, vapors, or materials requires fire/ flame detection as a life-saving necessity. The best solutions must combine state-of-the-art

More information

Instructions. PointWatch TM Infrared Hydrocarbon Gas Detector Model PIR Rev: 9/

Instructions. PointWatch TM Infrared Hydrocarbon Gas Detector Model PIR Rev: 9/ Instructions PointWatch TM Infrared Hydrocarbon Gas Detector Model PIR9400 Rev: 9/15 95-8440 Table Of Contents APPLICATION...1 FEATURES...1 SPECIFICATIONS...2 DESCRIPTION...5 Detection Method...5 Current

More information

COMPACT FLAME CONTROLLER CFC 2000

COMPACT FLAME CONTROLLER CFC 2000 COMPACT FLAME CONTROLLER CFC 2000 TECHNICAL DESCRIPTION EDITION: TB_CFC2000_EN_REV09_20150408 Important: Please note, that all mounting and wiring as well as all changing or adjustment at the flame monitoring

More information

Nanotechnology Metal Oxide Semiconductor (NTMOS) H 2 S Gas Sensor

Nanotechnology Metal Oxide Semiconductor (NTMOS) H 2 S Gas Sensor INSTRUCTIONS Nanotechnology Metal Oxide Semiconductor (NTMOS) H 2 S Gas Sensor APPLICATION The Det-Tronics Nanotechnology Metal Oxide Semiconductor (NTMOS) Hydrogen Sulfide (H 2 S) stand-alone gas sensor

More information

SEC 2000 Millenium Infrared Gas Detector

SEC 2000 Millenium Infrared Gas Detector SEC 2000 Millenium Infrared Gas Detector Instruction and Operation Manual Sensor Electronics Corporation 5500 Lincoln Drive Minneapolis, Minnesota 55436 USA (952) 938-9486 Fax (952) 938-9617 Email: sales@sensorelectronic.com

More information

Design Manual Installation Operation Maintenance

Design Manual Installation Operation Maintenance Design Manual Installation Operation Maintenance Model F120 Triple-Mode UV/IR Flame Detector 70053 23282 Mill Creek Drive, Suite 215 Laguna Hills, CA 92653 USA +1.949.583.1857 Phone +1.949.340.3343 Fax

More information

INFRARED PRODUCTS FOR MONITORING SMOKELESS FLARES, PILOTS, AND FLAME INTENSITY

INFRARED PRODUCTS FOR MONITORING SMOKELESS FLARES, PILOTS, AND FLAME INTENSITY INFRARED PRODUCTS FOR MONITORING SMOKELESS FLARES, PILOTS, AND FLAME INTENSITY >OLYL >H]LSLUN[O 4H[[LYZ SMOKELESS FLARE MONITOR Smokeless Flare Monitor (FM) Smokeless flares incinerate flammable hazardous

More information

UNITIZED ULTRAVIOLET FIRE DETECTOR

UNITIZED ULTRAVIOLET FIRE DETECTOR MODEL #: UVU-140-A & UVU-140-AR UNITIZED ULTRAVIOLET FIRE DETECTOR REVISED: DECEMBER, 1999 REV. uvu140a-aroct99.wpd WARRANTY POLICY Net Safety Monitoring Inc. products are carefully designed and manufactured

More information

Instructions Model MIR MSHA Approved IR Gas Detector 3.1 7/

Instructions Model MIR MSHA Approved IR Gas Detector 3.1 7/ Instructions Model MIR MSHA Approved IR Gas Detector 3.1 7/08 Table Of Contents Application............................................. 1 Features............................................... 1 Specifications..........................................

More information

Dräger Polytron Pulsar 2 Open Path Gas Detector

Dräger Polytron Pulsar 2 Open Path Gas Detector Dräger Polytron Pulsar 2 Open Path Gas Detector The Dräger Polytron Pulsar 2 represents the latest infrared technology in open path gas detection. Equipped with all the same functions as the standard Dräger

More information

DESIGN MANUAL MODEL GIR900 INFRARED COMBUSTIBLE GAS SENSOR

DESIGN MANUAL MODEL GIR900 INFRARED COMBUSTIBLE GAS SENSOR DESIGN MANUAL MODEL GIR900 INFRARED COMBUSTIBLE GAS SENSOR 70086 The information in this doucment is applicable to sensors built in September, 2008 or later (Firmware 3.0) The information and technical

More information

Instructions Oxygen Controller R8471C 2.1 8/

Instructions Oxygen Controller R8471C 2.1 8/ Instructions 95-8405 Oxygen Controller R8471C 8/07 95-8405 Table Of Contents Section I - General Information APPLICATION...1 FEATURES...1 DESCRIPTION...1 SPECIFICATIONS...2 Controller...2 C7052C O2 Detector...2

More information

FIREYE C9707A ALL FUEL SCANNER

FIREYE C9707A ALL FUEL SCANNER 65-8065 APRIL 11, 2013 FIREYE C9707A ALL FUEL SCANNER The C9707A All Fuel Scanner is used with the FIREYE R9107A Flame Controller to provide continuous monitoring of burner flames in industrial and utility

More information

COMPACT FLAME CONTROLLER CFC 1000

COMPACT FLAME CONTROLLER CFC 1000 COMPACT FLAME CONTROLLER CFC 1000 TECHNICAL DESCRIPTION EDITION: TB CFC1000- REV.6 2012-03-07 Important: Please note, that all mounting and wiring as well as all changing or adjustment at the flame monitoring

More information

RAZOR RZR SERIES DIE CAST ALUMINUM LED EXIT SIGNS INSTALLATION AND OPERATING INSTRUCTIONS IMPORTANT SAFEGUARDS READ AND FOLLOW ALL SAFETY INSTRUCTIONS

RAZOR RZR SERIES DIE CAST ALUMINUM LED EXIT SIGNS INSTALLATION AND OPERATING INSTRUCTIONS IMPORTANT SAFEGUARDS READ AND FOLLOW ALL SAFETY INSTRUCTIONS RAZOR RZR SERIES DIE CAST ALUMINUM LED EXIT SIGNS INSTALLATION AND OPERATING INSTRUCTIONS IMPORTANT SAFEGUARDS When using electrical equipment, basic safety precautions should always be followed including

More information

FlexPS. Architectural & Engineering. Specification for FlexPS. Architectural/Engineering Specification for a

FlexPS. Architectural & Engineering. Specification for FlexPS. Architectural/Engineering Specification for a Architectural/Engineering Specification for a Fence-Mounted Perimeter Intrusion Detection System FlexPS Disclaimer Senstar, and the Senstar logo are registered trademarks, and FlexPS, Silver Network and

More information

Instructions Toxic Gas Controllers R8471D/F/G Chlorine/Sulfur Dioxide/Nitrogen Dioxide 1.1 8/

Instructions Toxic Gas Controllers R8471D/F/G Chlorine/Sulfur Dioxide/Nitrogen Dioxide 1.1 8/ Instructions 95-8529 Toxic Gas Controllers R8471D/F/G Chlorine/Sulfur Dioxide/Nitrogen Dioxide 1.1 8/07 95-8529 Table of Contents Section I - General Information DESCRIPTION...1 FEATURES...1 SPECIFICATIONS...2

More information

IPES-IR3 Flame Detector Operating Manual R02

IPES-IR3 Flame Detector Operating Manual R02 IPES-IR3 Flame Detector Operating Manual 80031-001 R02 Table of Contents INTRODUCTION 3 RELAYS INCLUDED AS A STANDARD FEATURE 3 APPLICATIONS 3 IPES IR3 FLAME SPECIFICATIONS 4 FLAME RESPONSE SENSITIVITY

More information

UV Flame Detector. User's and Maintenance Manual TM20/20UB Rev E, August 2004

UV Flame Detector. User's and Maintenance Manual TM20/20UB Rev E, August 2004 UV Flame Detector Model 20/20U, 20/20UB User's and Maintenance Manual TM20/20UB Rev E, August 2004 Factory Mutual Approved Class I Div. 1 Groups B, C, D Class II Div. 1 Groups E, F, G ATEX Approved Ex

More information

Dräger Polytron Fixed Gas Detector. Dräger Polytron 5700 Infrared DrägerSensor PIR 7000 to detect combustible gases and vapors

Dräger Polytron Fixed Gas Detector. Dräger Polytron 5700 Infrared DrägerSensor PIR 7000 to detect combustible gases and vapors Dräger Polytron 5700 Fixed Gas Detector Dräger Polytron 5700 Infrared DrägerSensor PIR 7000 to detect combustible gases and vapors Dräger Polytron 5700 Including e-box for increased safety wiring The Dräger

More information

Instructions Infrared Hydrocarbon Gas Detector PointWatch Eclipse Model PIRECL Rev.10/

Instructions Infrared Hydrocarbon Gas Detector PointWatch Eclipse Model PIRECL Rev.10/ Instructions 95-8526 Infrared Hydrocarbon Gas Detector PointWatch Eclipse Model PIRECL Rev.10/12 95-8526 Table of Contents application... 1 OPERATION OVERVIEW.... 1 Theory of Operation... 1 Detectable

More information

Movement Detector GJD 300

Movement Detector GJD 300 Movement Detector GJD 300 Installation & Set Up Guide Introduction A CCTV event trigger utilising two independent passive infrared detectors combined in a T05 package. Both sensors have to trigger before

More information

Fiber Optic Cable Fence Disturbance Sensor

Fiber Optic Cable Fence Disturbance Sensor Architectural & Engineering Specification for Fiber Optic Cable Fence Disturbance Sensor Purpose of document This document is intended to provide performance specifications and operational requirements

More information

Dräger Polytron Pulsar 2 Detection of flammable gases and vapours

Dräger Polytron Pulsar 2 Detection of flammable gases and vapours Dräger Polytron Pulsar 2 Detection of flammable gases and vapours The Dräger Polytron Pulsar 2 is the latest infrared technology in open path gas detection. Equipped with all the same functions as the standard

More information

LTFX Electric Tank Immersion Heaters Installation Instructions

LTFX Electric Tank Immersion Heaters Installation Instructions LTFX Electric Tank Immersion Heaters Installation Instructions 1 PN403-5 161-049178-101 March 2017 LTFX Electric Tank Immersion Heater Installation Instructions General The Chromalox Electric Tank Immersion

More information

MBCE-110/230UV Flame Sensor Module

MBCE-110/230UV Flame Sensor Module MBCE-1002 FEBRUARY 3, 2017 MBCE-110/230UV Flame Sensor Module DESCRIPTION The MBCE-110/230UV modules provide visual indication and electrical outputs that signal the user regarding flame presence in a

More information

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual MANUAL Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual Model FPT 130 Single Point Freeze Protection Heat Trace Control Table of Contents SCFP-CO-F130 Overview... 3 Installation...

More information

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual We manage heat MANUAL Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual 1850 N Sheridan Street South Bend, Indiana 46628 (574) 233-1202 or (800) 234-4239

More information

Multi-Spectrum Digital Electro-Optical Fire Detectors

Multi-Spectrum Digital Electro-Optical Fire Detectors Installation Guide and Operating Manual Multi-Spectrum Digital Electro-Optical Fire Detectors Model SS4-AUV/-AUV2 Stand-Alone Relay Mode or 4-20 ma Output Option OPERATOR MANUAL // NOTICES AND TRADEMARKS

More information

Instructions FlexVu Universal Display Unit Model UD10 DCU Emulator. 4.2 Rev: 9/

Instructions FlexVu Universal Display Unit Model UD10 DCU Emulator. 4.2 Rev: 9/ Instructions 95-8656 FlexVu Universal Display Unit Model UD10 DCU Emulator 4.2 Rev: 9/12 95-8656 Table of Contents application... 1 DESCRIPTION... 1 Magnetic Switches... 2 Device Enclosure... 3 Device

More information

SEC Signature Process Gas Analyzer

SEC Signature Process Gas Analyzer SEC Signature Process Gas Analyzer Instruction and Operation Manual Sensor Electronics Corporation 5500 Lincoln Drive Minneapolis, Minnesota 55436 USA (952) 938-9486 Fax (952) 938-9617 email sensor@minn.net

More information

Rosemount 752 Fieldbus Remote Indicator

Rosemount 752 Fieldbus Remote Indicator Product Data Sheet Rosemount 752 Rosemount 752 Fieldbus Remote Indicator ROSEMOUNT 752 DELIVERS: Two-wire segment powered device Displays up to 8 values Link Master Capability Optional PID, Characterizer,

More information

DET-TRONICS INSTRUCTIONS. Infrared Hydrocarbon Gas Detector PointWatch Eclipse Model PIRECL APPLICATION OPERATION OVERVIEW

DET-TRONICS INSTRUCTIONS. Infrared Hydrocarbon Gas Detector PointWatch Eclipse Model PIRECL APPLICATION OPERATION OVERVIEW DET-TRONICS INSTRUCTIONS Infrared Hydrocarbon Gas Detector PointWatch Eclipse Model PIRECL IMPORTANT Be sure to read and understand the entire instruction manual before installing or operating the gas

More information

Instructions. Infrared Hydrocarbon Gas Detector PointWatch Eclipse Model PIRECL Rev: 3/

Instructions. Infrared Hydrocarbon Gas Detector PointWatch Eclipse Model PIRECL Rev: 3/ Instructions Infrared Hydrocarbon Gas Detector PointWatch Eclipse Model PIRECL 19.2 Rev: 3/17 95-8526 Table of Contents APPLICATION... 1 OPERATION OVERVIEW... 1 Theory of Operation.... 1 Detectable Gases...

More information

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL TRACON MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL TABLE OF CONTENTS FPT 130 Overview... 2 Installation... 3 Power Source and Load Connections... 4 Temperature Sensor... 5 External

More information

Description. Applications

Description. Applications CVEP PDS CVEP Convection for Hazardous Heater For Locations Hazardous Locations Convection Heater 1.8 to 9.0kW (T-2A) 280 C (536 F) 1.6 to 4.0kW (T-3A) 180 C (356 F) 1.8 to 9.0kW (T-2) 1.8 300 C to 9.0kW

More information

D-TECT Introduction. Connecting the Unit. Quick Installation. Multi Beam Alignment & Masking. Mounting the Unit

D-TECT Introduction. Connecting the Unit. Quick Installation. Multi Beam Alignment & Masking. Mounting the Unit D-TECT 2 GJD300 Quad PIR Movement Detector Package Contents Package Contains: 1 x D-Tect 2 1 x Drilling template for fixing holes 3 x 31.75mm wall plugs 3 x 31.75mm screws 2 x Spare Sliding Curtains 2

More information

INSTRUCTIONS. Duct Mount Kit Q900. Description. Operation

INSTRUCTIONS. Duct Mount Kit Q900. Description. Operation INSTRUCTIONS Duct Mount Kit Q900 Description The Detector Electronics Model Q900 Duct Mount Kit is used with the Model PIRECL PointWatch Eclipse IR gas sensor to detect combustible hydrocarbon gases within

More information

APPLICATION BULLETIN COMBUSTION TURBINE FACILITIES. Overview

APPLICATION BULLETIN COMBUSTION TURBINE FACILITIES. Overview Overview Modern combustion (or gas) turbine packages typically include an axial compressor, a combustion section and a turbine. Both compressor and turbine sections consist of one or more sets of fixed

More information

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117 Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel Revision E 61117 CAUTION: (Read This First) This panel has been designed to make it nearly bullet proof to mistakes made when wiring

More information

Single IR Flame Detector. User and Maintenance Manual TM 20/20R, Rev. A January 2005

Single IR Flame Detector. User and Maintenance Manual TM 20/20R, Rev. A January 2005 Single IR Flame Detector Model 20/20R User and Maintenance Manual TM 20/20R, Rev. A January 2005 ATEX Approved Ex II 2G EExd IIB + H 2 T5 EExde IIB + H 2 T5 GasTech Australia Pty Ltd 24 Baretta Rd Wangara

More information

MODEL: O ELECTROCHEMICAL O2 DETECTOR (Used with ST1400 O2 Sensor) Part Number: MAN Rev. 0

MODEL: O ELECTROCHEMICAL O2 DETECTOR (Used with ST1400 O2 Sensor) Part Number: MAN Rev. 0 MODEL: O2-25-24 ASSEMBLY CONSISTS OF: XP-O2 housing (supersedes PE-EX-O2) ST1400-500-24 sensor (supersedes PE1400-500-24) JB2 junction box CB2 connector board ELECTROCHEMICAL O2 DETECTOR (Used with ST1400

More information

D-Tect 2 GJD300 Quad PIR Movement Detector

D-Tect 2 GJD300 Quad PIR Movement Detector D-Tect GJD0 Quad PIR Movement Detector Package Contents 3. Package Contains: x D-Tect x Drilling template for fixing holes x Allen Key 3 x 3.75mm wall plugs 3 x 3.75mm screws x Spare Sliding Curtains x

More information

IR FLAME DETECTOR RIV-601/F

IR FLAME DETECTOR RIV-601/F IR FLAME DETECTOR EN 54-10 class 2 VdS approval G 205044 application manual CONTROL LOGIC rev. 4 DEC07 MAFE DEC07 IR FLAME DETECTORS SUMMARY Page general notions...3 description...4. Electrical and general

More information

Apollo Intelligent Auto Aligning Beam Detector. User Guide

Apollo Intelligent Auto Aligning Beam Detector. User Guide Apollo Intelligent Auto Aligning Beam Detector User Guide EN 1. General Information 50cm 50cm 8-100m Ensure clear line of sight from Detector to Reflector Mount on solid surfaces (structural wall or girder)

More information

Certificate of Compliance

Certificate of Compliance FF0 001 Certificate of Compliance Certificate: 70116284 (LR 064969_0_00) Issued to: Mine Safety Appliances Company North American Division 1000 Cranberry Woods Dr Cranberry Township, Pennsylvania 16066-5296

More information

Model 144H. Product Data Sheet , Rev DB February Content

Model 144H. Product Data Sheet , Rev DB February Content Rosemount 144 PC-Programmable Temperature Transmitter Provides an installation-ready solution for temperature monitoring applications using Complete Point Solutions (CPS) Increases measurement accuracy

More information

FRP HEATING SYSTEM INSTALLATION, OPERATION & MAINTENANCE MANUAL FRP.IOM.R1

FRP HEATING SYSTEM INSTALLATION, OPERATION & MAINTENANCE MANUAL FRP.IOM.R1 FRP HEATING SYSTEM INSTALLATION, OPERATION & MAINTENANCE MANUAL FRP.IOM.R1 Hotfoil, Inc. Robbinsville, New Jersey Phone: 609.259.4118 Fax: 609.259.4119 http:\\hotfoil.com INDEX Section I Product Specification

More information

Multi-Spectrum Digital Electro-Optical Fire Detector

Multi-Spectrum Digital Electro-Optical Fire Detector Installation Guide and Operating Manual Multi-Spectrum Digital Electro-Optical Fire Detector Model SS4-A/-A2 (CENELEC) Stand-Alone Relay Mode or 4-20 ma Output Option OPERATOR MANUAL // NOTICES AND TRADEMARKS

More information

Ultra Fast UV/IR Flame Detector

Ultra Fast UV/IR Flame Detector Ultra Fast UV/IR Flame Detector Model 20/20F User and Maintenance Manual TM756100 Rev A, July 2005 ATEX Approved Ex II 2G EExd IIB + H2 T5 EExde IIB + H 2 T5 218 Little Falls Rd., Cedar Grove, NJ 07009

More information

Dependable Solutions for Gas Detection

Dependable Solutions for Gas Detection Dependable Solutions for Gas Detection Combustibles/Flammables Standard & Exotic Toxics Oxygen Enrichment/Deficiency Introduction to Sensidyne Established in 1983 - acquired by Schauenburg GmbH in April

More information

Certificate of Compliance

Certificate of Compliance FF0 001 Certificate of Compliance Certificate: 70116279 (LR 025993_0_000) Issued to: General Monitors, Incorporated 26776 Simpatica Circle Lake Forest, California 92630 USA Attention: Larry Vlagea The

More information

Instructions. Infrared Hydrocarbon Gas Detector Open Path Eclipse Model OPECL Rev: 12/

Instructions. Infrared Hydrocarbon Gas Detector Open Path Eclipse Model OPECL Rev: 12/ Instructions Infrared Hydrocarbon Gas Detector Open Path Eclipse Model OPECL Rev: 12/13 95-8556 Table of Contents application...1 OPERATION OVERVIEW...2 Theory of Operation...2 Detectable Gases...2 Standard

More information

Dräger Flame 3000 Visual Flame Detector Instructions for Use

Dräger Flame 3000 Visual Flame Detector Instructions for Use D en Instructions for Use Dräger Flame 3000 Visual Flame Detector Instructions for Use WARNING Strictly follow the Instructions for Use. The user must fully understand and strictly observe the instructions.

More information

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection Technical Bulletin Arc Fault Monitor 4 Zones, 8 Sensors Features Four independent arc fault tripping zones 1 or 2 arc fault sensors per zone allowing up to 8 arc fault sensors per module Trip indication

More information

Intrinsically Safe, NEMA 4, Type 4X, IP67 Loop-Powered Meter

Intrinsically Safe, NEMA 4, Type 4X, IP67 Loop-Powered Meter PD685 Intrinsically Safe, NEMA 4, Type 4X, IP67 Loop-Powered Meter Actual Size Digits C US Intrinsically Safe 3½ Digits LARGE DISPLAY NEMA 4, Type 4X, IP67 Loop-Powered Field-Mount Process Meter 4-20 ma

More information

Architectural and Engineering Specification for a Fence-Mounted Perimeter Intrusion Detection System. FlexZone

Architectural and Engineering Specification for a Fence-Mounted Perimeter Intrusion Detection System. FlexZone Architectural and Engineering Specification for a Fence-Mounted Perimeter Intrusion Detection System FlexZone April 15, 2014 Page 1 of 14 G6DA0115-001 This document is intended to provide performance specifications

More information

DET-TRONICS INSTRUCTIONS. Infrared Hydrocarbon Gas Detector. PointWatch Eclipse Model PIRECL APPLICATION OPERATION OVERVIEW

DET-TRONICS INSTRUCTIONS. Infrared Hydrocarbon Gas Detector. PointWatch Eclipse Model PIRECL APPLICATION OPERATION OVERVIEW DET-TRONICS INSTRUCTIONS Infrared Hydrocarbon Gas Detector PRELIMINARY Specifications Subject to Change 8/19/02 PointWatch Eclipse Model PIRECL IMPORTANT Be sure to read and understand the entire instruction

More information

SEC Millenium Carbon Dioxide Gas Detector

SEC Millenium Carbon Dioxide Gas Detector SEC Millenium Carbon Dioxide Gas Detector Instruction and Operation Manual Sensor Electronics Corporation 5500 Lincoln Drive Minneapolis, Minnesota 55436 USA (952) 938-9486 Fax (952) 938-9617 Email sales@sensorelectronic.com

More information

AnaLASER II Detector. Protection Systems. A UTC Fire & Security Company. High-Sensitivity Smoke Detector (HSSD ) FEATURES DESCRIPTION

AnaLASER II Detector. Protection Systems. A UTC Fire & Security Company. High-Sensitivity Smoke Detector (HSSD ) FEATURES DESCRIPTION AnaLASER II Detector High-Sensitivity Smoke Detector (HSSD ) F-89-250 FEATURES Air Sampling Smoke Detector for Early Warning Applications Two Versions Available: Standard Detector and Ultra Detector STANDARD

More information

INSTRUCTION MANUAL. D1xB2XH2 Xenon Beacon For use in Hazardous Locations. 2) Rating & Marking Information

INSTRUCTION MANUAL. D1xB2XH2 Xenon Beacon For use in Hazardous Locations. 2) Rating & Marking Information INSTRUCTION MANUAL D1xB2XH2 Xenon Beacon For use in Hazardous Locations 2) Rating & Marking Information 2.1 Public Mode Fire Alarm Ratings The D1xB2XH2 is certified for use as public mode visual alarm

More information