Barrier Management- Defending the Safety of Patients, Visitors, & Staff
|
|
- Pearl Mathews
- 5 years ago
- Views:
Transcription
1 Barrier Management- Defending the Safety of Patients, Visitors, & Staff
2 About Your Speaker Rick Tinsley: 3 Years as Healthcare Construction Electrician 38 Years in Healthcare Facility Maintenance 13 Years as a Director of Facility Management/Safety/Security 7 Years combined service as President, Secretary/Treasurer, and Education Chairman for the Tennessee Healthcare Engineering Association Lifetime THEA Board Consultant Member of numerous Engineering Societies and Associations AHA Certified Healthcare Facility Manager (CHFM) IBFCSM Certified Healthcare Emergency Professional (CHEP) WIFE Certified Crazy Train Engineer (CCTE)
3 What is Barrier Management? Barrier Management is ongoing testing and inspections to ensure fire and smoke barriers are functioning properly and meeting designed ratings to protect occupants and infrastructure during a fire. Components of conducting Barrier Management include the following: Physical testing of fire/smoke dampers every 6 years in Hospitals and every 4 years in facilities not classified as a hospital using CMS Conditions of Participation occupancy classifications At least annual inspections of fire doors in rated walls At least annual inspections of rated walls Codes requiring Barrier Management include the following: Dampers NFPA 101, NFPA 80, & NFPA 105 Doors NFPA 101, NFPA 80, & NFPA 105 Walls NFPA 101 & IFC
4 Components of a Barrier There are many components that create a fire, smoke, or combination barrier. The construction material type: Sheetrock, Concrete, Cinder Blocks, Wood, Steel, etc. Type of material to fill cracks, holes, piping/cable penetrations, fireproofing steel, etc. Fire, smoke, or combination dampers Fire, smoke, or combination doors
5 Why is Barrier Management Important? Proper Barrier Management along with suppression and alarm systems help protect occupants and structures during the event of a fire. Below are a few examples of how this works: Properly constructed and maintained barriers help contain fire and smoke to a specific area (Compartmentation) Compartmentation gives more time to extinguish the fire and evacuate if needed Compartmentation helps to limit structural and/or contents damage and saves lives Isolating the fire helps to lessen the risk of firefighters getting hurt or killed
6 Why do I need Smoke Barriers, I have Fire Barriers? Almost 70% of all building deaths are associated with Smoke Inhalation. (Source NFPA) Most victims are not located in the same room as the fire s origin. (Source NFPA) Smoke Travels feet per minute under fire conditions. (Source NFPA) Fire creates positive pressure due to the expansion of air from the heat forcing smoke through the smallest hole like air from a compressor. Improper smoke barrier construction/maintenance can result in smoke filling an otherwise survivable space into a deadly area in just minutes.
7 Why Defend in Place? Healthcare Hospitals, Nursing Homes, Assisted Living Facilities Patients tied to life saving machines or in surgery can t be easily evacuated. Many patients are too sick or non-ambulatory and can t be moved quickly. Multi-story buildings create transportation issues between floors for these patients when elevators can t be used.
8 Code References Facilities are constructed and maintained using many different codes. Many AHJ s use different editions and/or writers of the codes to inspect your facility. Examples: The State may use a different edition of NFPA 101 for CMS Surveys than they use for a State Survey even though it s the same person doing the survey or the local Fire Marshall may inspect using the IFC, IBC, and IMC codes. So, how do you win? Find out what codes the AHJ s that inspect your facility use and maintain the facility to the most strict code when there is a discrepancy. CMS funded facilities are surveyed by the 2012 Edition of NFPA 101 Life Safety Code, 2012 Edition of NFPA 99 Healthcare Facilities Code, and other associated NFPA codes that are referenced. Architects normally design buildings using the latest State adopted NFPA, IBC, and IMC codes.
9 Fire & Smoke Dampers
10 Code Required Testing of Dampers NFPA requirements for damper testing and inspecting are : Each damper shall be tested and inspected 1 year after installation. (NFPA: 105, 6.5.2, NFPA 80: ) Each damper shall be tested and inspected every 4 years thereafter, except in hospitals where the frequency shall be every 6 years. (NFPA 105: , , NFPA 80: )
11 Fusible link melts when temperature exceeds the designed rating. Gravity damper Fire shutter Dampers: drops down, closing How the opening. do they Spring loaded damper closes when tension is released. Fire dampers work? do not seal against smoke migration unless rated as a Combination Fire & Smoke Damper. Typical Fusible Link Curtain Fire Damper Multi-Blade Fire Damper
12 Smoke Dampers: How do they work? Dampers are controlled by an external force either by pneumatic or electrical voltage and activated by an alarm system. The dampers will either open or close according to the type of the designed system using actuator motors. Usually dampers are designed to close and seal the opening from smoke migration. Smoke evacuation systems may either keep the damper open and/or open normally closed dampers to evacuate the smoke from the building.
13 Smoke Dampers Fail Position: Fail Open vs. Fail Closed Determined by System Actuator Location: External Internal Internal Actuator External Actuator Defective actuators are the #1 source of damper deficiencies.
14 Combination Fire/Smoke Dampers Perform the dual role of both Fire Dampers and Smoke Dampers Used in locations that are designated as both fire barriers and smoke barriers to prevent the passage of flame and smoke They are activated by heat and/or an alarm system
15 Smoke Control System Dampers Chapter 9 of the IBC regulates engineered smoke control systems 2 types of Smoke Control Systems: Dedicated and Non-Dedicated Dedicated systems are only activated during an alarm Non-dedicated systems can be used for daily air handling but may function differently as programmed during an alarm
16 Smoke Control Damper Testing Each damper shall be tested and inspected 1 year after installation. After initial commissioning and testing, dedicated smoke control systems must be tested semi-annually. Non-dedicated systems must be tested annually. Chapter 9 dampers do not fall under the 4 & 6 year rule.
17 Difference of Passive & Active Smoke Control Systems Passive systems when activated are designed to seal the duct going through a smoke barrier to keep the smoke contained to that area. Active systems use engineered designs to open or close dampers when activated to either evacuate the smoke or to keep smoke out of other areas by adjusting pressures.
18 What s Wrong With This Picture?
19
20
21 Fire & Smoke Doors
22 Fire Door Doing Its Job: Non-Fire Side Photo courtesy of NFPA
23 Fire Door Doing Its Job: Fire Side Photo courtesy of NFPA
24 2012 LSC 101 Fire & Smoke Door Inspection Requirements Inspection of Door Openings Where required by Chapters 11 through 43, the following door assemblies shall be inspected and tested not less than annually in accordance with through (1) Door leaves equipped with panic hardware or fire exit hardware in accordance with (2) Door assemblies in exit enclosures (3) Electrically controlled egress doors (4) Door assemblies with special locking arrangements subject to Fire-rated door assemblies shall be inspected and tested in accordance with NFPA 80, Standard for Fire Doors and Other Opening Protectives. Smoke door assemblies shall be inspected and tested in accordance with NFPA 105, Standard for Smoke Door Assemblies and Other Opening Protectives.
25 2012 LSC 101 Fire & Smoke Door Inspection Requirements The inspection and testing interval for fire-rated and nonrated door assemblies shall be permitted to exceed 12 months under a written performance-based program in accordance with of NFPA 80, Standard for Fire Doors and Other Opening Protectives A written record of the inspections and testing shall be signed and kept for inspection by the authority having jurisdiction Functional testing of door assemblies shall be performed by individuals who can demonstrate knowledge and understanding of the operating components of the type of door being subjected to testing Door openings not in proper operating condition shall be repaired or replaced without delay.
26 Top Fire and Smoke Door Deficiencies Improper clearances between door, frame, and floor Missing or illegible labels on doors & frames Missing, incorrect type, and/or malfunctioning hardware Incorrect type, size, broken, or improper installation of vision panels Damaged door and/or frame (Holes, Warped/Dented, Delamination) Field modifications of door and/or frames Improper size or items attached to doors (Kick Plates, Decorations, Signage, Wall Pockets) Doors propped open (Wedges, Kick Down Holders, Items Placed in Front of Doors) Doors not latching or closing properly (Strikes, Latches, Closers, Coordinators, Tape over latch bolt or strike plate) Doors dragging, rubbing, or binding on floors, each other, and/or frame Improper latching devices (Deadbolts, Hooks, Slide Bolts, Non Rated-Panic Hardware that do not meet fire exit specifications) Electronic latching/releasing devices not working properly
27 So What Do I Do With The Extra Parts That Come With The New Door Closer?
28 What Do You Mean By Improper Field Modification?
29 What Are The 5 Issues With This Fire Rated Door?
30 What Are The 4 Issues With This Fire Rated Door?
31 MANAGING FIRE & SMOKE BARRIERS IN TODAY S HEALTHCARE ENVIRONMENT
32 In the world above the ceiling tiles Out of sight can be out of mind!
33 Healthcare Specific Issues Key Firestop Compliance Issues: A large % of findings are firestop related. Of those the overwhelming % are cable penetrations Penetrations allow smoke to migrate to other areas Infection Control, specifically related to unsealed penetrations can be a significant issue in critical areas such as isolation rooms, ICU, NICU, etc. Fire Barrier Management over time is a significant challenge for HC facilities if not constantly monitored
34 Even when we have made the effort Openings that once were sealed may no longer be
35 I think it looks pretty!
36 What else can I find to put in here?
37 I just need to get to the other side!
38 What Sign?
39 The System Must Meet The Application Rating Of The Barrier Proper Barrier Construction Proper Sealant Type Annular Space Requirements Meet Approved Testing Lab Installation Requirements More Than Just Red Caulk!!!
40 What is a Barrier Management Program??? Proactive Approach to Maintaining Rated Wall Integrity. Documentation!!!! Provide Paths for Future Cable Pulls. (Listed Cable Management Systems) Enforce Accountability! Meet or Exceed Inspection/Accreditation Requirements.
41 Why Do I Need A Barrier Management Program? Regulatory Compliance Insure Proper Installation Exhibit a Proactive Approach Prevent Property Loss Life Safety
42 A BMP At A Minimum Should Accomplish Four Things: 1. Ensure the delivery of a compliant building 2. Adopt procedures to keep it in compliance 3. Inspections/Testing by code requirements 4. Documentation (Evidence of Compliance)
43 Barrier Management Program Above Ceiling Permit Form This permit will be given with a designated start and finish date which will be determined by the facility. The permit will allow access above the ceiling. This permit will be displayed at all times.
44 Firestop Installer Training Should be a requirement for anyone working in barriers Detailed training on the proper installation of firestop manufacturers approved systems & products Testing program requiring annual review Infection Control Training Patient Privacy (HIPAA) Training BMP Protocol Training
45 Proper Products For Application Insuring the products selected for the applications are correct for the type of penetration, type of object to be sealed around, size of the repair, and testing lab approved installation. What s good for the contractor may not be what s good for the facility. Specialized products for specific testing lab applications are available from firestop manufacturers.
46 Through-Penetrations
47 Most Firestop Manufactures Have A Cable Management Solution Products like these provide a long term solution to cable issues by allowing multiple runs to be pulled at different times without making new holes.
48 Construction Joints Movement Is The Issue: Elastomeric Firestop Required To Ensure Caulk Flexes With The Building Movement
49 USING YOUR BARRIERS FOR EMERGENCY PREPAREDNESS
50 How Does Barrier Management & Emergency Preparedness Work Together? Properly maintained barriers can be used for other purposes than to slow the migration of fire and smoke. Smoke dampers can be closed to prevent airflow from a contaminated area to other parts of the facility. Properly sealed walls and floors will prevent airborne viruses and chemical vapors from spreading. Properly latching doors when closed will help protect occupants during violent weather. Properly latching doors when closed will also slow down someone intending to commit violent acts by limiting their line of site and physically having to stop and open doors.
51 How Can I Make Barrier Management & Emergency Preparedness Work Together? Perform an HVA to determine what your internal vulnerabilities are and what can be done to mitigate. Write Policies & Procedures to Maintain Barriers. Write Policies & Procedures to detail how to implement steps for handling the event. Include HVA and P&P s in your Emergency Operations Plans. Smoke dampers can be set up to manually close with the fire alarm system in zones or stand-alone switching for individual control on passive systems. Cannot be used with smoke evacuation systems. Doors can be manually closed or set up through the fire alarm system to close from a remote location when violent weather is approaching or during an intruder event.
52 Summary & Conclusion: Initiate a Barrier Management Program including an Above Ceiling Work Permit and give a copy to each contractor. Follow up on contractors to make sure they are properly sealing penetrations before they are paid. Ensure inspections and tests are conducted by qualified individuals/companies and performed on schedule. Repair issues ASAP and perform ILSM s and PFI s if needed. Perform an HVA on Internal Risks Including Fire, Storms, Intruders, and Chemical Spills/Release. Include Internal HVA and BMP in EOC and Emergency Operations Plans. Notify AHJ s that you have a BMP during inspection. Remember that you are responsible for the safety of the occupants and infrastructure of your facility.
53 Have You Ever Had One Of Those Days?
54 Questions? Thank you for your time. Contact Info: Rick Tinsley CHFM, CHEP Life Safety Consultant LSS Life Safety Services
WHAT TO EXPECT DURING A FIRE DOOR INSPECTION
WHAT TO EXPECT DURING A FIRE DOOR INSPECTION Basic Fire Door Inspections 1. Fire door basic function 2. Understanding codes 3. Responsibility of end user 4. Common fire door deficiencies 5. What your door
More information1-300 Fire and/or Smoke Dampers to Inspect $ Fire and/or Smoke Dampers to Inspect $34.30
Life Safety Services, LLC TXMAS Schedule Contract Number: TXMAS-12-03FAC030 Passive Fire Protection Services Authorized Federal Supply Schedule Price List Quantity of Dampers to Inspect Per Damper to Survey
More informationLIFE SAFETY & FIRE PREVENTION MANAGEMENT PLAN
Title/Description: Life Safety & Fire Prevention Management Department: Facilities Management Personnel: All Effective Date: 5/97 Revised: 7/00, 7/01, 7/02, 7/03, 7/04, 7/05, 7/08 LIFE SAFETY & FIRE PREVENTION
More informationFire and Smoke Door Inspections Qualified Training 02/03/17
Fire and Smoke Door Inspections Qualified Training 02/03/17 Basis of Requirements NFPA 101 requires annual fire and smoke door inspections (Section 18/19.2.2.2.1) Sections 18/19.2.2.1 require compliance
More informationDeveloping a Healthcare Facility Fire Door Inspection Program
Developing a Healthcare Facility Fire Door Inspection Program WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio QUESTIONS How To Ask a Question: 1 POLLING There will be occasional interactive
More informationBuilding Codes & Standards for Healthcare. Healthcare Construction Certificate - Level 1
Building Codes & Standards for Healthcare Building Codes and Standards AHJs Codes Defend in Place Walls Sprinklers Fire Alarm Important Dates for Healthcare Facilities 7/5/16 NFPA Life Safety Code 101
More information2012 Life Safety and Health Care Facility Codes - Door Inspections and Other Critical Inspection, Testing and Maintenance
2012 Life Safety and Health Care Facility Codes - Door Inspections and Other Critical Inspection, Testing and Maintenance Will begin at 1 pm Housekeeping Announcements Problems during the call? Press *0
More informationLIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE
California Society for Healthcare Engineering SOUTHERN CALIFORNIA SEMINAR LIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE 1 PROGRAM AGENDA Adoption of 2012 LSC CMS Final Rule / Amendments
More informationEC 5.10 FIRE PREVENTION MANAGEMENT
EC 5.10 FIRE PREVENTION MANAGEMENT The organization manages fire safety risks. 1 The organization develops and maintains a written management plan describing the processes it implements to effectively
More informationAbout the Instructor & Presenter:
About the Instructor & Presenter: Paul G. Baillargeon, AHC, FDAI Vice President, Technical Consulting Door Security & Safety Foundation A noted veteran in the door and hardware industry, Mr. Baillargeon
More informationDanilo B. Concepcion, CBNT, CCHT-A Operations Manager St. Joseph Hospital Renal Services
Life Safety Code Danilo B. Concepcion, CBNT, CCHT-A Operations Manager St. Joseph Hospital Renal Services danilo.concepcion@stjoe.org 714-771-8944 The findings and conclusions in this presentation are
More informationFACILITY MANAGEMENT DEFICIENCIES IN ACUTE CARE SETTINGS
FACILITY MANAGEMENT DEFICIENCIES IN ACUTE CARE SETTINGS Presented by: Alise Howlett, Assoc. AIA,CFPE, CHFM Standards Advisor, EM/PE/LS HFAP A better healthcare survey experience 1 FREQUENT PHYSICAL ENVIRONMENT
More informationMeasures (ILSM) Process
Managing the Interim Life Safety Measures (ILSM) Process 1 A Program for The Texas Association of Healthcare Facility Management Monday, April 30, 2012 Robert H. Bartels, CHFM CHSP CHEP SASHE President,
More informationThe Physical Environment Portal: Module 5, LS Leadership
The Physical Environment Portal: Module 5, LS.02.01.10 - Leadership Fire Safety: Background Fire safety impacts both the lives of the occupants and the physical structures. In the early 1900 s many buildings
More informationFACILITY MANAGEMENT DEFICIENCIES IN CRITICAL ACCESS HOSPITALS (CAH)
FACILITY MANAGEMENT DEFICIENCIES IN CRITICAL ACCESS HOSPITALS (CAH) Presented by: Alise Howlett, Assoc. AIA, CFPE, CHFM Standards Advisor, EM/PE/LS HFAP A better healthcare survey experience 1 FREQUENT
More informationFire Rated Door Assemblies: Compliant Designs
Fire Rated Door Assemblies: Compliant Designs Steel Door Institute www.steeldoor.org AIA Provider #G389 Course #: SDIFIRE 1 HSW CE hour 1 Credit(s) earned on completion of this course will be reported
More informationUNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY
Revision No.: 11 Page 1 of 12 I. PURPOSE This procedure establishes a tool to help maintain a safe environment for all patients, visitors and staff by evaluating the loss of a life safety feature during
More informationInterim Life Safety Measures (ILSM)
1 Interim Life Safety Measures (ILSM) Frank D. Rudilosso P.E., M.Eng, CHSP Manager Facilities Regulatory Life Safety Compliance frr9035@nyp.org Tom Singh MPH, MHA, CHSP Field Director Facilities Regulatory
More informationIowa State Fire Marshal
Iowa State Fire Marshal LIFE SAFETY CODE REQUIREMENTS LONG TERM CARE Kyle R. Gorsh, Special Agent in Charge Iowa Department of Public Safety State Fire Marshal Division 2012 LSC & Applicable Standards
More informationEmergency Planning for Institutional Facilities
Emergency Planning for Institutional Facilities Pacific ADA Emergency Preparedness Webinars Presented by: Kimberly Paarlberg, ICC Based on the 2015 edition of the International Building Code (IBC) and
More informationTaming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes JENSEN & HALSTEAD LTD.
Taming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes Comparing the Codes: NFPA 101 Life Safety Code (2000) (NFPA) International Building Code (2012) (IBC) Chicago
More informationTHE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5
THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5 AGENDA: Ambulatory Health Care & Business Occupancies Definitions / Examples Mixed & Contiguous Occupancies Ambulatory Health Care &
More informationCity of South Salt Lake Fire Code Training Exiting, Egress Systems and Egress Control
City of South Salt Lake Fire Code Training Exiting, Egress Systems and Egress Control 11-27-12 This document is designed as a summary guide using IFC requirements for the provisions associated with exiting,
More informationNFPA 80 Overview January 21, 2016
NFPA 80 Overview January 21, 2016 Kristin Bigda, P.E. Senior Fire Protection Engineer National Fire Protection Association Presenter Kristin Bigda, P.E. Senior Fire Protection Engineer, NFPA Building Fire
More informationCompliance w/ the 2012 Life Safety Code
Compliance w/ the 2012 Life Safety Code Implications of the 2012 NFPA Code Set for Existing & New ASCs William E. Lindeman, AIA http://www.weldesigns.com Financial Interest Disclosure The presenter provides
More informationNFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES
NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES Sharon S. Gilyeat, P.E., Principal Koffel Associates, Inc. www.koffel.com sgilyeat@koffel.com Expertly Engineering Safety From Fire
More informationJOINT COMMISSION PREPAREDNESS / STATEMENT OF CONDITIONS DRAWINGS WSSHE SOUTHWEST CHAPTER NOVEMBER 19, 2015
JOINT COMMISSION PREPAREDNESS / STATEMENT OF CONDITIONS DRAWINGS WSSHE SOUTHWEST CHAPTER NOVEMBER 19, 2015 AGENDA INTRODUCTION OF PRESENTERS SOC VS. FIRE & LIFE SAFETY DRAWINGS HAZARDOUS AREAS VS. INCIDENTAL
More informationInterim Life Safety Measures. Healthcare Construction Certificate - Level 1
Interim Life Safety Measures Purpose of Interim Life Safety Management BASIC SAFETY: During renovations projects in healthcare occupancies, the basic level of protection for the occupants must be maintained
More informationH BUTCH BROWNING FIRE MARSHAL BUILDING REHABILITATION
STATE OF LOUISIANA Department of Public Safety and Corrections Office of State Fire Marshal Code Enforcement and Building Safety 8181 Independence Boulevard Baton Rouge, Louisiana 70806 225-925-4920 H
More informationFIRE PROTECTION KEY DESIGN CONCEPTS IN HEALTHCARE FACILITIES Scott Twele, Aman Shah Steven Dannaway. AIA Healthcare Group
FIRE PROTECTION KEY DESIGN CONCEPTS IN HEALTHCARE FACILITIES Scott Twele, Aman Shah Steven Dannaway AIA Healthcare Group Introductions Presenters Coffman Engineers Scott M. Twele, P.E. Operations Manager,
More informationInterim Life Safety Assessments and Infection Prevention Assessments
Interim Life Safety Assessments and Infection Prevention Assessments 1 Healthcare Construction ILSM and ICRAs PRESENTED BY Bob Dubiel, CHFM, CHC -Mayo Clinic Health System NWWI -Projects and Construction
More informationGENERAL FIRE PROCEDURES
GENERAL FIRE PROCEDURES C O D E R E D IN THE EVENT OF FIRE: PASS If you use a fire extinguisher on a small fire, remember to PASS in order to use the fire extinguisher properly: P Pull the pin. A Aim at
More informationTHE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #6
THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #6 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1 QUESTIONS How To Ask a Question: POLLING There will be occasional
More information2016 Joint Commission Update
2016 Joint Commission Update Bert M. Gumeringer, MBA, CHFM, FASHE Asst. Vice President-Facilities Operations Texas Children s Hospital August 12, 2016 11:30am-12:30pm Top 10 Findings Comparison-2015 vs.2016
More informationRenovation Program. Renovation Program GENERAL
Renovation Program GENERAL This program provides guidance and protocols for renovation projects in occupied, operational acute hospitals. Team building is essential to quality control and HFD Services
More informationOther EC and LS documents may be requested by surveyors, as needed, throughout the survey.
Documentation required by the Hospital Accreditation program Life Safety (LS) and selected Environment of Care (EC) standards is presented in the following pages. These documents will be reviewed by the
More informationWritten Fire Safety Plans
Written Fire Safety Plans 2012 LSC KATHARINE ACHOR SEPTEMBER 2016 NFPA Standard: 2012 NFPA 101, 19.1.1.3.1 All health care facilities shall be designed, constructed, maintained, and operated to minimize
More informationTable OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS
901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.
More informationNFPA 101 Life Safety Code Culture change 2012
NFPA 101 Life Safety Code Culture change 2012 Produced by Kansas Fire Marshal April, 2012 On March 9, 2012 Centers for Medicare & Medicaid Services implements a policy where they have formally adopted
More information1. Are there any annual sprinkler head inspection forms available? No, there are none available at this time.
Sprinkler 1. Are there any annual sprinkler head inspection forms available? No, there are none available at this time. 2. Does the annual sprinkler head inspection have to be done by a licensed technician
More informationSURREY FIRE SERVICE. Construction Fire Safety Plan Bulletin
SURREY FIRE SERVICE Construction Fire Safety Plan Bulletin The B.C. Fire Code requires building owners/contractors to comply with the requirements of the BC Fire Code 5.6 Construction and Demolition Sites
More informationNFPA 101 and NFPA 99, 2012 Editions Code Update. where art meets engineering
NFPA 101 and NFPA 99, 2012 Editions Code Update where art meets engineering Austin Dallas Denver Houston Kansas City Miami Nashville Phoenix Richmond Washington DC NFPA 101 and NFPA 99 where art meets
More informationChanges to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH)
Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH) The following represents a review of the Life Safety chapter of the new 2018 Joint Commission CAMH manual for
More informationProcedure DESCRIPTION/OVERVIEW
Applies To: UNMH Responsible Department: Life Safety Revised: 07.08.16 Procedure Patient Age Group: (X ) N/A ( ) All Ages ( ) Newborns ( ) Pediatric ( ) Adult DESCRIPTION/OVERVIEW To assure the safety
More informationTennessee Department of Health Bureau of Health Licensure and Regulations Division of Health Care Facilities
Tennessee Department of Health Bureau of Health Licensure and Regulations Division of Health Care Facilities 1 Colby Henson Fire Safety Supervisor 665 Mainstream Drive 2nd floor 615-806-4798 Colby.Henson@tn.gov
More informationNFPA CODE TESTING & INSPECTION. Requirements & Recommendations for. Licensed Florida Hospitals, Ambulatory Surgery Centers,
NFPA CODE TESTING & INSPECTION Requirements & Recommendations for Licensed Florida Hospitals, Ambulatory Surgery Centers, ICF/IID Healthcare, & In-patient Hospice Facilities per NFPA Life Safety Code 101
More informationPRINTED: 06/09/2017 FORM APPROVED CENTERS FOR MEDICARE & MEDICAID SERVICES OMB NO (X2) MULTIPLE CONSTRUCTION A. BUILDING 03 - A BUILDING
SUMMARY PROVER'S PLAN OF CORRECTION K 000 INITIAL COMMENTS K 000 A Life Safety Code Survey was conducted by the State Fire Marshal beginning on May 9th, 2017 and ending on May 10th, 2017. Adair Acute Care
More informationLife Safety Code Common Discepancies Course# LSC102. EZpdh.com All Rights Reserved
Life Safety Code Common Discepancies Course# LSC102 EZpdh.com All Rights Reserved 1. K147 Electrical - Electrical wiring and equipment shall be in accordance with NFPA 70, National Electrical Code. 9.1.2
More informationThis policy may also be used for routine work orders that are Life Safety in nature and cannot be completed within 45-days.
Policy: It is the policy of the St. Joseph Mercy Health System (SJMHS- Ann Arbor, Oakland, Livingston, Brighton, Chelsea and St. Mary Mercy Hospital- Livonia) and associated satellite facilities to assure
More informationE25 (D) Automatic controls for general means of egress lighting
Adhoc Health Care MOE Study Group Study Group Report of Adhoc Meeting July 12&13, 2012 Possible Public Comments E25, E69, E74, G71, G77/G80 Study Group E25 (D) Automatic controls for general means of egress
More informationMinimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016
1. Introduction The intent of this document is to establish minimum standards for the practice of fire protection engineering within the State of Oklahoma as conducted by licensed professional engineers.
More informationAgency for Health Care Administration
Page 1 of 94 ST - K0000 - Initial Comments Title Initial Comments Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0100 - General
More informationPresented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC Web: Lauzon-LSC.com
Presented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC 262-945-4567 Lauzon.lsc@gmail.com Web: Lauzon-LSC.com 1 Wis Professional Engineer Experienced Facility Director Experienced AHJ WHEA Code
More informationFIRE AND SAFETY PROJECT REVIEW REPORT
1. A001 2. A001 3. A001 4. D102/103 5. A102/103 *VA enforces/applies the National Fire Protection Association (NFPA) 101 (current edition is 2015) and not the International Building Code (IBC). Ideally
More informationSECTION INSPECTION AND TESTING OF WORK
SECTION 01455 PART I - GENERAL 1.01 SECTION INCLUDES A. Project Inspections and Procedures B. Scheduling Inspectors Notification requirements 1.02 RELATED SECTIONS A. Section 01310 COORDINATION B. Section
More informationInternational Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures
International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures Please note this is not an all-inclusive list. The type and complexity of your project
More informationWEST VIRGINIA UNIVERSITY
WEST VIRGINIA UNIVERSITY Environmental Health and Safety (SOP) WV State Fire Marshal (SFM) Project Plans Review Process & Procedures West Virginia University Environmental Health & Safety Page 1 of 10
More informationSwinging Egress and Fire Doors
Presented by: AHCA Seminar: Inspecting and Maintaining Swinging Egress and Fire Doors Current State CMS Memorandum July 28, 2017 Tuesday May, 3, 2016 CMS issued the final rule adopting the 2012 Life Safety
More informationThe Impact the Reference Standards in the 2012 Edition of NFPA 101 have on the Operation of Health Care Facilities: NFPA 80 and 99
The Impact the Reference Standards in the 2012 Edition of NFPA 101 have on the Operation of Health Care Facilities: NFPA 80 and 99 Sharon S. Gilyeat, P.E. Lauren Schrumpf August 8, 2018 Expertly Engineering
More informationAgency for Health Care Administration
Page 1 of 92 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0100 - General Requirements
More informationNFPA 101 Code Update from 2012 Edition to the 2015 Edition
NFPA 101 Code Update from 2012 Edition to the 2015 Edition Presented by: Gary Furdell AHCA Fire Protection Specialist 1 2 2012 Update to 2015 Chapter 18 New Health Care Occupancies 4 18.1.3.2 Atrium walls
More informationReport on First Revisions with Statement June 2014 NFPA 101
101 FR3002 SAF-HEA (18.1.3.2) Recommendation: 18.1.3.2 Atrium walls in accordance with 6.1.14.4.6 shall be permitted to serve as part of the separation required by 6.1.14.4.1 for creating separated occupancies
More informationPresented by: Brad Keyes, CHSP Senior Consultant Keyes Life Safety Compliance, LLC
Presented by: Brad Keyes, CHSP Senior Consultant Keyes Life Safety Compliance, LLC Changes to Life Safety Compliance Healthcare leaders will have to deal with many changes in Life Safety compliance when
More informationCMS Announcement 3/27/2017. Adoption of 2012 Life Safety Code Health Care Facilities Code. Kenneth Daily, LNHA
Adoption of 2012 Life Safety Code Health Care Facilities Code Kenneth Daily, LNHA kenn@qissurvey.com CMS Announcement May 2016 Life Safety Code Health Care Code Effective July 5 th Numerous changes many
More informationAgency for Health Care Administration
Page 1 of 34 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0001 - OTHER
More informationFire Sprinkler Plan Submittal Form
Contents Fire Sprinkler Plan Submittal Form... 2 Standpipe Plan Review Submittals... 4 Fire Pump Plan Submittal Requirements... 6 Fire Alarm Plan Submittal Form... 8 Kitchen Hood Wet Chemical Submittal...10
More informationFirst Aspen Federal Regulation Set: K LSC 2000 Health Existing
First Aspen Federal Regulation Set: K 01.01 LSC 2000 Health Existing K 0000 Title CFR Type INITIAL COMMENTS Memo K 0011 If the building has a common wall with a nonconforming building, the common wall
More information<< COMPANY LETTERHEAD >>
Healthcare Facilities Accreditation Program Attn: Engineering Department 142 E. Ontario Street Chicago, IL 60611 > < Date > RE: Request for Code Equivalency ABC General Hospital,
More informationSchool Fire Safety Checklist
Community Risk Reduction The (SFSC) includes many of the most common fire prevention and life safety issues found in schools. The SFSC is not intended to be an all inclusive list, but rather highlights
More informationYORK COUNTY DEPARTMENT OF FIRE SAFETY BUILDING PLAN REVIEW REQUIREMENTS
YORK COUNTY DEPARTMENT OF FIRE SAFETY BUILDING PLAN REVIEW REQUIREMENTS The York County Department of Fire Safety reviews all commercial building plan submittals for compliance with the 2015 International
More informationBuilding & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome!
Building & Fire Code Academy Building Better With Our Greatest Resource Education Welcome! Understanding the Sprinkler System Design Alternatives in the 2015 International Why inspect, test and maintain?
More informationAmerican Fire Sprinkler Association. An Introduction to the IBC and IFC
American Fire Sprinkler Association Presents An Introduction to the IBC and IFC October 13, 2005 Speaker Roland Huggins, P.E. Vice President of Engineering and Technical Services American Fire Sprinkler
More informationConstruction Requirements and the Ontario Building Code
Construction Requirements and the Ontario Building Code Thomas Pepper, P. Eng. October 20, 2017 OSBIE Toronto The Evolution of Construction Laws Building Regulations date back as far as 1900 B.C. to Babylonian
More informationJanuary 1, 2014 Mandatory Effective Date
2013 Kentucky Building Code Highlights Winnie Blythe, Technical Advisor Dept. of Housing, Buildings, and Construction winnie.blythe@ky.gov www.dhbc.ky.gov 502-573-0373 January 1, 2014 Mandatory Effective
More informationMaintaining Building and Fire Safety During Active Assailant Events and Other Terrorist Events
Position Statement Maintaining Building and Fire Safety During Active Assailant Events and Other Terrorist Events Maintaining school safety in light of recent terrorist events is challenging for everyone,
More informationUNIVERSITY OF TOLEDO
UNIVERSITY OF TOLEDO SUBJECT: INTERIM LIFE SAFETY MEASURES AND INFECTION Procedure No: LS-08-008 CONTROL PROCEDURE STATEMENT Interim life safety and infection control measures will be implemented to protect
More informationReport on First Revisions with Statement June 2014 NFPA 101
101 FR6005 SAF-BCF (32.2.1.1.2) Recommendation: 32.2.1.1.2 Where there are sleeping accommodations for more than 16 residents are provided, the occupancy shall be classified as a large facility in accordance
More informationLife Safety Code NFPA 10 NFPA 13 NFPA 25 NFPA 72 NFPA 90A NFPA 110 NFPA 99 THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #7
THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #7 AGENDA: Life Safety Code Referenced Publications Overview Life Safety Code NFPA 10 NFPA 13 NFPA 25 NFPA 72 NFPA 90A NFPA 110 NFPA 99
More informationEstablished /10/2015. Doran Pruisner Dan Wood
Established 1911 Doran Pruisner Dan Wood The International Fire Code, 2009 Edition shall apply to all occupancies except for those that are explicitly excluded by these provisions. 1 Buildings built between
More informationTo provide the requirements needed for Care Facilities Having 6 or Fewer Clients. This occupancy is classified as an R-3.1.
EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD STANDARD #F-003 EFFECTIVE 06-03-2009 PURPOSE To provide the requirements needed for Care Facilities Having 6 or Fewer Clients. This occupancy is classified
More informationLaura Frye, AHC, CSI, CCS, FDAI Technical Director, DSSF Director of Certification, DHI
Laura Frye, AHC, CSI, CCS, FDAI Technical Director, DSSF Director of Certification, DHI Inspecting Swinging Fire Doors with Builders Hardware A Practical Guide for AHJs and Facility Management Personnel
More informationFire, Smoke, and Combination Fire Smoke Dampers
Fire, Smoke, and Combination Fire Smoke Dampers Mark Belke Director Damper Products-Greenheck Chairman of Code Action Review Committee (CARC) California Building Code work group NFPA 80A, 90A, 92B, 101,
More informationEnhancing K-12 Security
The official publication of ALOA SPAI, an international association of security professionals October 2016 SECURING YOUR SUCCESS Enhancing K-12 Security Recent code proposals may shake up safety practices
More informationFire & Life Safety Code Compliance. Common Safety Deficiencies and Tips for Compliance for Long Term Care and Skilled Nursing Facilities
Fire & Life Safety Code Compliance Common Safety Deficiencies and Tips for Compliance for Long Term Care and Skilled Nursing Facilities LTC, Skilled Nursing Facilities COMMON LIFE SAFETY DEFICIENCIES
More informationLife Safety Damper Installation ASHRAE St Louis Chapter Feb. 9,2015. Peter McDonnell, PE, LEED AP BD+C McClure Engineering
Life Safety Damper Installation ASHRAE St Louis Chapter Feb. 9,2015 Peter McDonnell, PE, LEED AP BD+C McClure Engineering UL DAMPER TEST STANDARDS UL 555 - FIRE DAMPERS UL555S SMOKE DAMPERS UL555C CEILING
More informationTop (15) Life Safety Code Deficiencies and Tips for Compliance (10/01/2011 thru 02/22/2012)
1. K62 Automatic Sprinkler Systems - Automatic sprinkler systems are continuously maintained in reliable operating condition and are inspected and tested periodically. 18.7.6, 19.7.6, 4.6.12, NFPA 13,
More informationINSPECTOR I SKILLS ADMINISTRATION
INSPECTOR I SKILLS ADMINISTRATION 1- Prepare inspection reports so that the report is clear and concise and reflects the findings of the inspection in accordance with the applicable codes and standards..
More informationM E M O R A N D U M. All Licensed Assisted Living Facilities. Felicia Cooper, Deputy State Fire Marshal Administrator Don Zeringue, Chief Architect
M E M O R A N D U M To: From: Approved: All Licensed Assisted Living Facilities Felicia Cooper, Deputy State Fire Marshal Administrator Don Zeringue, Chief Architect Henry Fry, Deputy Assistant Secretary
More informationUNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY
Revision No.: 6 Page 1 of 5 I. PURPOSE This procedure provides guidance to EH&S office staff to coordinate notifications of appropriate internal staff who will need to respond to an unannounced Joint Commission
More informationProperties that are determined to be architecturally and/or historically significant may be designated as one of the following:
Preparation for disasters, both natural and manmade, is essential for the protection of your building. This is particularly true of historic resources, which often consist of unique and often irreplaceable
More informationAre there any policies regarding outlets that contain USB ports?
Answers to the Questions Mark J. Blackburn, P.E., CFPS February, 2016 Question 1 Are there any policies regarding outlets that contain USB ports? There is no direct reference in code about these types
More informationFire Alarm System Fundamentals
Fire Alarm System Fundamentals Mircom is the largest and oldest privately owned fire alarm and life safety manufacturer in North America and 5th largest overall with 50 years of industry experience. Mircom
More informationShut Down The Fan: A Reprise by Dean K. Wilson, P.E.
Fire Alarm Notebook by Dean K. Wilson. P.E. Page 1 Shut Down The Fan: A Reprise by Dean K. Wilson, P.E. Question: My grandfather passed away last summer. He had spent many years as a fire fighter. Among
More informationNFPA 914 CODE FOR FIRE PROTECTION OF HISTORIC STRUCTURES
NFPA 914 CODE FOR FIRE PROTECTION OF HISTORIC STRUCTURES Jack Watts Cultural Heritage and Fire Protection Issues Siena 23 May 2008 NFPA 914 Thinking outside the box Building Regulations Developers Safety
More informationAgency for Health Care Administration
Page 1 of 41 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K0011 - LIFE SAFETY CODE STANDARD If the building has a common wall with a nonconforming building, the common
More informationFirst Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] Submitter Information Verification. Committee Statement and Meeting Notes
First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] 4.3.11.5.5 Materials within a raised floor plenum exposed to the airflow shall be (a) noncombustible or (b) exhibit a maximum flame spread index of 25
More informationDefend In Place 2012 IFC Overview of Institutional Occupancies
Defend In Place 2012 IFC Overview of Institutional Occupancies ICC Course No. ICC CEU s = 0.50 SCFA Course 8506-15-0 Nathan Ellis Cell: 864-812-5183 Nathan.Ellis@llr.sc.gov Institutional Occupancies Course
More information2017 Accreditation Updates
2017 Accreditation Updates Tennessee Healthcare Engineers Association 2017 Spring Conference Pickwick Landing State Park Counce, Tennessee 38326 Presented May 17, 2017 By Ken Gregory Vice President, Accreditation
More informationGoals of a Fire Prevention Program Fire Prevention Strategy Housekeeping Issues Flammable and Combustible Liquids Electrical Fire Hazards
Goals of a Fire Prevention Program Fire Prevention Strategy Housekeeping Issues Flammable and Combustible Liquids Electrical Fire Hazards Compartmentalization Life Safety The primary goal of fire safety
More informationLOS ANGELES UNIFIED SCHOOL DISTRICT OFFICE OF ENVIRONMENTAL HEALTH AND SAFETY PROCEDURE
TITLE: ISSUER: Occupancy Inspections for New Schools and Modernization Projects John Sterritt, Director Office of Environmental Health and Safety ROUTING Office of Environmental Health & Safety Staff DATE:
More information