SERVICE INSTRUCTIONS FOR. Fire Alarm System MINI-2000

Size: px
Start display at page:

Download "SERVICE INSTRUCTIONS FOR. Fire Alarm System MINI-2000"

Transcription

1 SERVICE INSTRUCTIONS FOR Fire Alarm System MINI-2000 Version Jari Ollila Tom Brunberg Oy Esmi Ab Copyright Oy ESMI Ab, The copyright to the documentation herein is the property of Oy ESMI Ab, Espoo, Finland. The contents may be used and / or copied only with the written permission from Oy ESMI Ab or in accordance with the terms and conditions stipulated in the agreement / contract under which the documentation has been supplied. f:\upi90\customer\maint\servman1.doc

2 Page 2 CONTENTS 1 BLOCK DIAGRAMS MONITORINGS (WITH FAULT EXPLANATIONS) MONITORINGS OF ZONES Normal state Fire State Line Broken Line Fault Short Circuit Monitor Fault During Zone Test During System Test Zones used in Explosive Atmospheric Environment ALARM DEVICE LINE MONITORING Normal state Test State INPUT MONITORING (INPUTS IN1 - IN3 AND AM) EARTH LEAKAGE MONITORING FUSE MONITORING MONITORING OF FIRE AND FAULT ROUTING EQUIPMENT Fire Relay (RL8) Fault Relay (RL9) BATTERY AND CHARGER AND MAINS MONITORING PROGRAM MONITORING SERVICE STATE SYSTEM SETTINGS EXTENSION OF ZONES EXTENSIONS FROM 4 TO 8 (also 12 > 16 or 20 > 24 or 28 > 32 ) EXTENSION FROM 8 TO 12 (also 16 > 20 or 24 > 28) REPLACEMENT OF PROGRAM MEMORY (ROM) RESTARTING THE SYSTEM POWER SUPPLY REPLACEMENT APPENDIX 1 - Layouts of Boards APPENDIX 2 - Fuses... 23

3 Page 3 1 BLOCK DIAGRAMS Zone board Zone board Power supply Data Power supply Disblay board Data Controller board Power supply Fast Charge control Mains monitoring Power supply unit Mains Battery Figure Error! Unknown switch argument. Units in MINI-2000 Zone boards Display board Microprocessor and its peripheral circuits (memory etc.) Serial port Power unit Battery Charger and battery circuit Input, output and monitoring circuits Alarm devices Routing relays Clean relays Inputs. Figure Error! Unknown switch argument. Controller board

4 Page 4 Controller board 8 Zones Zone selection and monitoring circuit Zonal output selection circuit 8 Zonal outputs Figure Error! Unknown switch argument. Zone board LCD-Display Led display Key board Controller board Figure Error! Unknown switch argument. Display board

5 Page 5 2 MONITORINGS (WITH FAULT EXPLANATIONS) All fault warnings are indicated on the display with an optical and an audible signal. Fault warning origins are specified, either by means of a monitor specific LED, or by means of a fault explanation, displayed on the alphanumeric display. This section describes the operation of the monitorings in various situations in order to assist the service personnel to determine the reason for a fault warning. The best way to clarify the reason for faults is to silence first the common fault warning, to disconnect those faulty objects from keyboard, to reset fault warning. Then the faulty object can be selected and set to test state from keyboard. 2.1 MONITORINGS OF ZONES Each zone is terminated by an Active Terminator (AT), which creates a current pulse every 70 ms. The 1 ms pulse is created by changing the input resistance of the terminator from the normal 7.4 kohm to 50 ohm. Maximum cable resistance of a zone may be 100 ohms (not including the terminator). Maximum total leak current of the detectors may be 3 ma. Zone voltage is measured over two resistors between the negative terminal ( Zone(-) ) of the zone and ground ( Gnd ) (ie. the negative terminal of the 24V supply on the Controller board). The resistors are a 220 ohm and a 80 ohm in series. The measuring circuit is shown in Error! Unknown switch argument.. The signals AD, SC and RU are connected to the Controller Board. AD is dc voltage level with range 0-5 V. SC is digital pulse detection signal (Fault or OK, OK = pulse detected). RU is digital pulse detection signal (Fault or OK, OK = pulse detected). Supply (24Vdc) Zone DC voltage level AD 120 ohm 80 ohm Pulse voltage level Pulse voltage level SC RU Figure Error! Unknown switch argument. Monitoring circuit on Zone board

6 2.1.1 Normal state Page 6 Monitoring: In normal state the dc voltage level between Zone(-) and Gnd is 0.8V - 3V (normally approx. 1.2V) depending on supply voltage level and amount of detectors in zone. Pulse voltage level (measured from same point) is higher than 11V ± 1V (normally approx. 16V). Normal state = [(0.8V < AD < 3V) and (SC = OK) and (RU = OK)] Fire State Evaluation of Fire State is depending on jumper settings on the Zone Board (see Error! Unknown switch argument. ). If the jumper setting implies that a short circuit is to be indicated as a fault, both the AD signal and the SC signal are used for fire state evaluation, otherwise only the AD signal. Short circuit detection (with fault indication) requires that the resistance of detectors and other zone components (when in fire alarm state) are 250 ohms ohms. (Eg. resistance in manual call point is 470 ohms). Monitoring: Dc voltage level (AD) between Zone(-) and Gnd is over 3 V and the difference between the pulse voltage level and dc voltage level is > 2.8 V. If short circuit is detected as fire (depending on configuration) pulse voltage level has no meaning. Fire State = [(AD > 3V) and (SC = OK)] Fire State = [(AD > 3V)] if short circuit is fault if short circuit is fire Line Broken Cable resistance of zone has radically increased (over 3 kohms with 27V supply) (terminator not included). Monitoring: Dc voltage level between Zone(-) and Gnd is lower than 0.8V. Pulse voltage level is not measured. Line Broken = [(AD < 0.8V)] Line Fault Cable resistance of zone is over the fault limit ( ohms). (If cable resistance is in normal area (resistance is lower than 100 ohms) and this fault is indicated, monitoring circuit on zone board or/and on controller board is out of order) Monitoring: Dc voltage level between Zone(-) and Gnd is normal (0.8V - 3V), but pulse voltage level (measured from same point) is lower than 11V ± 1V. Line Fault = [(0.8V < AD < 3V) and (SC = OK) and (RU = Fault)]

7 2.1.5 Short Circuit Page 7 Evaluation of Short Circuit is depending on jumper settings on the Zone Board (see Error! Unknown switch argument. ). If the jumper setting does not imply that a short circuit is to be indicated as a fault, a fire alarm will be indicated. Monitoring: Dc voltage level between Zone(-) and Gnd is over 3V and pulse voltage level (measured from same point) minus dc voltage level is lower than 2.8V. Short Circuit = [(AD > 3V) and (SC = Fault)] Monitor Fault This fault is detected if zone is in order (no above mentioned faults) but monitoring circuit on zone board or/and on controller board is out of order. Monitoring: Constantly: Dc voltage level between Zone(-) and Gnd is normal (0.8V - 3V), and pulse voltage level (measured from same point) is normal (higher than 11V ± 1V), but part of pulse detection circuit is out of order. Monitor Fault = [(0.8V < AD < 3V) and (SC = Fault) and (RU = OK)] Every 24h: The supply of all zones is turned off for 1 second. During that time the values of the zone interfaces are measured. If the circuit is in order, all measured values ought to be in fault state. Monitor fault = [(AD > 0.8V) or (SC = OK) or (RU = OK)] During Zone Test When Zone Test is active, fire alarms or fault warnings for that zone are not activated. The state (Normal, Fire, Break, Short or Line fault) of the zone under test, is indicated on the display only. The monitoring limits of each state are the same as in normal state During System Test The zone interface circuits of all zones are tested during system test. Monitoring First the supply of all zones is turned off for 1 second. During that time the values of the zone interfaces are measured. If the circuit is in order, all measured values ought to be in fault state. After that, the zones are shown one by one on the display. If a fault was detected in any zone interface circuit the type of the nonworking circuit is indicated when that zone is on the display. Codes on the display (see also figure ): "B" if AD is not < 0.8 "L" if RU is not Fault "S" if SC is not Fault Comparable codes with "BLS" (english) in different country versions:

8 Finnish: "KLO" Norwegian: "ALK" Swedish: "ALK" Danish: "LSK" Page Zones used in Explosive Atmospheric Environment Zone(s) 1 and/or 2 can be configured to operate in EX-environment. In this case the active terminator (AT-1) is replaced by an end of line resistor (4.7 kohm). Only AD value (see Error! Unknown switch argument.) is measured. Short circuit is always indicated as fire. Fire threshold is a fixed value. Fault thresholds are floated with level of the supply voltage. Monitoring: Fault = [(AD < (1.1 V * Vsupply/26.5V))] IN Normal = [((1.5 V * Vsupply/26.5V) < AD < 3 V)] Fire = [(AD > 3 V)] Deleted: Fault = [(AD < (1.5 V * V supply /26.5V))] 2.2 ALARM DEVICE LINE MONITORING A fault is indicated if there is short circuit or break in the lines. During fault warnings, numbers 1-4 on the display refer to numbers of the alarm device line terminals. Number 5 on the display refer to AM input on Controller Board (see section 2.3 Input monitoring) Normal state Alarm device lines (AL) are monitored with reversed polarity ( AL(-) is positive and AL(+) is negative). Therefore, all alarm devices are provided with diodes and the lines with End-Of-Line resistors (4.7 kohm). The fuses of these lines (F1 - F4) are monitored by the same circuit. Thus, a blown fuse is indicated as alarm device line fault. Monitoring Fault is detected if voltage level between AL(+) and Gnd is < 1.8 V (resistance in line is < 1 kohm) or voltage level is > 8.9 V (resistance in line is > 13 kohm (end of line resistor 4.7 kohm included). Normally the measured value is 4 V. These voltage levels are floated by a factor Vsupply/26.5V where Vsupply is voltage level measured from the 24 V supply terminals on the Controller Board. Fault = [(AL(+) < 1.8V) or (AL(+) > 8.9V)] Test State The fault limits: Lower limit is 2.5 V (resistance in line is 2 kohm). Upper limit is 6.7 V (resistance in line is 9 kohm (end of line resistance 4.7 kohm included). These voltage levels are floated by a factor Vsupply/26.5V where Vsupply is voltage level measured from the 24 V supply terminals on the Controller Board Measured values of lines 1-4 are indicated on the display. Fault = [( AL(+) < 2.5V) or ( AL(+) > 6.7V)]

9 Page INPUT MONITORING (INPUTS IN1 - IN3 AND AM) At normal state the input is closed (ie. the terminals are shorted). An input is activated by opening the input line. The input lines IN1 - IN3 activate corresponding leds on the display panel. The AM input activates an alarm device fault (line number 5). Monitoring: Lines are activated if voltage level between terminals is > 6.7 V (resistance is > 5 kohm). 2.4 EARTH LEAKAGE MONITORING Earth leakage is monitored with respect to both the positive and the negative supply voltage poles. The cabinet (earth) is connected to the monitor circuit via the two mounting screws in the lower corners of the Controller Board. Fault warning is indicated if the resistance from either pole to the earth is less than 22 kohms (30 kohms during system test). The faults are indicated as "FAULT -" or "FAULT +". Monitoring in normal state: Normally the voltage level between cabinet and Gnd (ie. negative of 24V supply on the Controller board) is 9.4 V. "FAULT -" is indicated if voltage level is < 5.3 V FAULT +" is indicated if voltage level is > 16.5 V These voltage levels are floated by factor Vsupply/26.5V where Vsupply is voltage level measured from eg. 24 V supply terminals on the Controller Board Monitoring during system test: "FAULT -" is indicated if voltage level is < 6.0 V "FAULT +" is indicated if voltage level is > 15.5 V (These levels are also floated.) Monitoring in test state: Measured voltage level is indicated on the display. The fault limits are same as in normal state.

10 2.5 FUSE MONITORING Page 10 All fuses are monitored. The indication of a blown fuse varies depending on which circuit it protects: Controller Board fuses: F1 - F4 protects the alarm device lines. Breaks of these fuses are indicated as alarm device fault. F5, F8, F9 protects the three 24 V supply outputs on the Controller Board. Breaks of these fuses are indicated as fuse fault. F6 and F7 protects the battery circuit. Breaks of these fuses are indicated as battery fault. Zone Board fuse: Fuse on Zone Board protects the zone circuits of that board. Break of this fuse is indicated as "zone fault - line broken" (faults in all eight zones of that board). Power supply: Break of fuse located in the power supply is indicated as charger fault (with fault code 6). Monitoring of fuses F5, F8 and F9 in all states: Fuse fault is indicated if the voltage measured over any of the fuses is over 1.7 V. 2.6 MONITORING OF FIRE AND FAULT ROUTING EQUIPMENT Fire Relay (RL8) The coil circuit of the fire routing relay is monitored. A break in the coil circuit or a fault in the control circuit is indicated as fire routing equipment fault. The relay is normally de-energized. Monitoring in normal state: The coil resistance is measured and if it is over approx. 150 kohm it is indicated as a fault in the coil circuit. (Co8 < 1.2V; normally approx 4.2V) Every 60 seconds, the relay is energized for a few microseconds. During this short activation time the relay will not operate but the control circuit and coil can be measured for breaks or short circuits. Monitoring in test state: The same measuring and temporary activation as in normal state are performed. As the result of the test, the digits "1" and "0" (corresponding to successfull test) are shown on the display. The first ("1" = OK) indicates the result of the resistance measurement, and the second ("0" = OK) indicates the result of the temporary activation Fault Relay (RL9) The coil circuit of the fault routing relay is monitored. A break in the coil circuit or a fault in the control circuit is indicated as a fault routing equipment fault. The relay is normally energized. Monitoring in normal state: The coil resistance is measured and if over approx. 2 Mohm, it is indicated as a fault in the coil circuit. (0.6V < Co9 < 4.0V; normally approx 1.0V) Every 60 seconds, the relay is de-energized for a few microseconds. During this short activation time the relay will not operate but the control circuit and coil can be measured for breaks or short circuits.

11 Page 11 Monitoring in test state: The same measurements and temporary activation as in normal state are performed. As a result of the measurements two values are displayed. The first value is measured when the relay is in normal state and is normally 1.0, fault limit is 0.6. The second value is measured during the temporary activation (de-energization) and is normally 5, fault limit is BATTERY AND CHARGER AND MAINS MONITORING The battery is monitored with respect to: low voltage battery capacity fuse blown or circuit broken The battery charger is monitored with respect to: high voltage, regulator fault forced charge activation lack of current supply even if main supply is OK test discharge circuit faults charge current control circuit The main supply is monitored for absence. Each of these monitor functions has its own identificator, which is displayed at fault warning. Battery fault 1 Battery fault 2 Battery fault 3 Charger fault 4 Charger fault 5 Charger fault 6 Charger fault 7 Charger fault 8 Mains fault 9 If voltage level of battery is < 23.5 V. (For example during a long mains break). If the battery circuit is broken (eg. blown fuse or loose connectors). If capacity of battery is too low. If voltage level of battery is too high or the regulation in power unit or control circuit of forced charge is out-of-order If voltage level of battery doesn't increase during forced charge control. If mains is on and Control Panel doesn't get supply voltage from power unit. If the test discharge circuit is not in order. If charge current control circuit between power unit and battery is shorted. If mains is off. (The time interval between start of mains break and fault warning depends on country version: norwegian version: 0.5 h, danish version: 10 h, swedish version: 3 h, finnish version: this fault is not indicated). Monitorings in normal state: Voltage level of battery and charger are measured every 100 ms. Running average values are calculated and stored in system memory. Short (20 ms) discharge test of battery and evaluation of measured values are done every 10 s. Forced charge test and battery capacity test are activated 1 min. after start up of the system and then after every 24 h. (Duration of these tests is 20 s)

12 Page 12 Power unit Uc Control circuit Ub F4A F4A Load resistor located in power unit The power supply tests are done as follows (see Error! Unknown switch argument. ): Ubm = average battery voltage in memory (measured every 100 ms.) Ucm = average charger voltage in memory (measured every 100 ms.) Ub = battery voltage (measured during current test) Uc = charger voltage (measured during current test) Ufc = forced charge voltage (measured during forced charge test) Fc = forced charge state Test Indication if fault Possible reason a) Ubm < 23.5 V battery fault 1 b) Ubm > 28.0 V and not Fc charger fault 4 Charger is turned off and the short (20 ms) discharge test is activated. c) Ub < 21.0 V battery fault 2 break in battery fuses or loosened contacts d) Uc < Ub charger fault 6 system doesn't get supply from power unit altough mains is on e) Uc < (Ucm V) charger fault 8 circuit between power unit and battery is shorted If time to make forced charge test and long discharge test: - Forced charge is activated (duration is 20 sec.) f) Ub < (Ubm V) charger fault 5 voltage level of battery doesn't increase enough - Ufc is measured (in preparation for the next test) - The charger circuit is opened (but charger output is kept on the forced charge level) and 20 sec. load test is activated g) Ub < 21.0 V battery fault 3 the capacity of battery is too low h) Uc < (Ufc V) charger fault 8 circuit between power unit and battery is shorted i) Ub > (Ubm V) charger fault 7 discharge test circuit is out-of-order End of test Figure Error! Unknown switch argument. Charger and Battery circuits on Controller Board

13 Page 13 Tests a) and b) are done every 10 sec.. Tests c)... e) are done every 10 sec. if mains is on. Tests f)... i) are done every 24 h and 1 min. after system start up, provided that Ubm > 26.5V and forced charge is off. In addition these tests are also performed after a reset of faults 3, 5, 8 and 7. Only test a) is done if charger monitoring is disabled or charger is in fault state. Only test b) is done if battery monitoring is disabled or battery circuit is in fault state. Forced charge is activated if Ubm < 23.5 V or voltage level of discharged battery < 21.0 V. Forced charge is deactivated when voltage level of battery has been over 28.0 V for 5 h. Maximum time for continuous forced charge is 72 h (in case the battery voltage doesn't increase over 28.0 V). The long discharge test is always performed after deactivation of forced charge Battery monitoring in test state: Measured battery voltage is indicated on the display. If the Control Panel is not in service state the actual battery/charger circuit voltage is displayed. However, before the voltage is displayed, a short (20 ms) discharge test is performed (with the charger disconnected) and if the test givs a result < 23.5V, that voltage is displayed instead of the 'charger connected' voltage. If the Control Panel is in service state (see section Service state) the discharge test is activated and the measured battery voltage is displayed. The discharge test continues until the test is terminated manually, or by a time limit of 5 min. Charger monitoring in test state: Measured value of charger is indicated on the display. If the Control Panel is not in service state the charger circuit is opened and the measured charger voltage is displayed. If the Control Panel is in service state (see section Service state) the forced charge control is activated and the measured charger voltage is displayed. 2.8 PROGRAM MONITORING The internal system is supervised by the processor. System faults are indicated on the display with steady "GENERAL FAULT" and "SYSTEM FAULT" indicators and with an audible signal. If a system fault is detected during start up, only fault routing equipment control is activated, otherwise also other configured fault controls are activated. Fault origin is specified by means of a fault code, displayed on the alphanumeric display: 1 = program memory corrupted 2 = data memory access fault 3 = Alphanumeric display response fault (or no information at display) 4 = AD-converter response fault 5 = data structure of timeout queue fault 6 = data structure of communication queue fault 9x = unexpected interrupt x=interrupt number WARNING! Normal operation of the fire control panel is stopped when a system fault is detected. The execution of the running program is monitored by a HW-watch-dog, located on the Controller Board. The watch-dog will reset the system, if not updated by the program every 200 ms.

14 Page 14 3 SERVICE STATE The Control Panel is set into service state by shorting (for a moment) the "service jumper" on the Controller Board (see Error! Unknown switch argument.). Control Panel returns to normal state when the front door is closed. Functions in service state: In normal state (except the Norwegian version) the Control Panel gives an acoustic fault warning and activates the fault alarm device relay for 3 s every 5th min if the front door is open. In service state this warning is disabled. In normal state a selection is cancelled and the display returns to the state before the selection, after 15 seconds of no keypresses. In service state the time limit is 5 minutes. During battery monitor test the battery is discharged. During charger test the forced charge is activated. During system test the zone interface test result is displayed 0.3 seconds per zone. (Normally the time is 2 sec./zone). 4 SYSTEM SETTINGS Outputs are configured with DIL switch S and jumper field J on the controller board (see Error! Unknown switch argument.). Selections are shown in Error! Unknown switch argument. and Error! Unknown switch argument.. Zone outputs and characteristics are configured with jumpers J1.. J6 on the zone interface board to which the zones are connected. Selections are shown in Error! Unknown switch argument.. CAUTION CAUTION Do not change the settings of jumpers J1.. J4 on the zone interface boards unless you have ensured that all detectors and manual call points connected to the zone do not short-circuit the zone when alarming. Manual call points must be equipped with an internal 470 ohm resistor and PI type detectors must be of the right type. Do not change the settings of jumpers J5 and J6 on the zone interface boards unless you have a written (and signed) specification of the pairwise dependency of the respective zone pairs. J9 J10 COMBINATION ZONES J ON OFF J5 J6 SHORT CIRCUIT MONITORED ON / OFF J4 J3 J2 J ON ON S OFF = switch position Controller Board default setting Zone Board default setting Figure Error! Unknown switch argument. Switch and jumper settings

15 Page 15 Table Error! Unknown switch argument. Settings and functions of DIL switch S on the controller board. Default settings in boldface Switch Position Function 1 ON Alarm device line 1 uses continuous signalling OFF Alarm device line 1 uses pulsed signalling 2 ON Alarm device line 2 uses continuous signalling OFF Alarm device line 2 uses pulsed signalling 3 ON Alarm device line 3 uses continuous signalling OFF Alarm device line 3 uses pulsed signalling 4 ON Alarm device line 4 uses continuous signalling OFF Alarm device line 4 uses pulsed signalling 5 ON Alarm device line 4 = fault warning device line OFF Alarm device line 4 = fire alarm device line 6 ON Fire transmitter connected OFF Fire transmitter not connected 7 ON Fault transmitter connected OFF Fault transmitter not connected 8 ON Serial port uses Esmi protocol OFF Serial port uses ACII protocol Table Error! Unknown switch argument. Settings and functions of jumper field J on the controller board. Default settings in boldface Jumpers Position Output Function 1 2 ON ON fire alarm output, activ. at detection of fire, deactivated at reset OFF ON CO1 fault warning output, activated at detection of fault, deact. at reset ON OFF control alarm output See note 1) below OFF OFF fire door control See note 2) below 3 4 ON ON fire alarm output, activ. at detection of fire, deactivated at reset OFF ON CO 2 fault warning output, activated at detection of fault, deact. at reset ON OFF fire alarm output See note 3) below OFF OFF door open output, activated when the door of the panel is open 5 6 ON ON fire alarm output, activ. at detection of fire, deactivated at reset OFF ON CO 3 fault warning output, activ. at detection of fault, deact. at reset ON OFF disablement output, activated when there s a disablement OFF OFF country specific function See note 4) below 7 8 ON ON Baud rate of serial port = 9600 bps OFF ON Baud rate of serial port = 4800 bps ON OFF Baud rate of serial port = 2400 bps OFF OFF Baud rate of serial port = 1200 bps 9 OFF Zone 1 operating in normal environment ON Zone 1 operating in explosive atmospheric env. 10 OFF Zone 2 operating in normal environment ON Zone 2 operating in explosive atmospheric env. Note Fire alarm and fault warning outputs are activated in the SE version only if the door of the panel is closed at the moment of fire or fault detection. Note 1) Activated when the panel indicates fire alarm and the door of the panel is open. Note 2) Activated in the FI, IT, RU and EE versions when the panel indicates fire alarm or fault in any of the loops. Deactivated at fire alarm reset or at fault alarm reset. Activated in the SE, DK, EN54 and LV versions when the door of the panel is closed and the panel simultaneously indicates fire alarm or fault in any of the loops. Deactivated when the door of the panel is opened or when the fire alarm or fault alarm is reset. Activated in the NO version when the panel indicates fire alarm or fault in any of the loops or the main power supply (230Vac) is off. Deactivated when the fire alarm or the fault alarm is reset or when the main power supply is on. Note 3) Activated if the door of the panel is closed at the moment of fire detection. Deactivated at fire alarm reset.

16 Page 16 Note 4) Extinguisher control output. Activated in the EN54, DK and LV versions when the panel indicates fire alarm. Deactivated at fire alarm reset. The output can be disabled / re-enabled from the menu. Table Error! Unknown switch argument. Settings and functions of jumpers J1.. J6 on the zone interface board. Default settings in boldface Jumper Position Function J1 OFF Short-circuit in zones 1 or 2 = fire alarm ON Short-circuit in zones 1 or 2 = fault warning J2 OFF Short-circuit in zones 3 or 4 = fire alarm ON Short-circuit in zones 3 or 4 = fault warning J3 OFF Short-circuit in zones 5 or 6 = fire alarm ON Short-circuit in zones 5 or 6 = fault warning J4 OFF Short-circuit in zones 7 or 8 = fire alarm ON Short-circuit in zones 7 or 8 = fault warning J5 OFF Zones 1, 2, 3 and 4 are independent ON Zones 1/2 and 3/4 are pairwise depending J6 OFF Zones 5, 6, 7 and 8 are independent ON Zones 5/6 and 7/8 are pairwise depending New settings are valid after the control unit is restarted.

17 Page 17 5 EXTENSION OF ZONES In control panel MINI-2000 batteries are located to same cabinet with electrical units and there is room for two zone boards. Maximum number of zones in this type is 16. In control panel MINI-2100 batteries are located to external battery cabinet and there is room for four zone boards in main cabinet. Maximum number of zones in this type is 32. If a zone board is provided with one zone hybrid, four zones can be connected to that board. If a zone board is provided with two zone hybrids, eight zones can be connected to that board. See Error! Unknown switch argument EXTENSIONS FROM 4 TO 8 (also 12 TO 16 or 20 TO 24 or 28 TO 32 ) De-energize the system by first disconnecting the battery connector from the controller board and then mains plug from the mains socket. Install the zone hybrid (24 pin SIL-package) carefully to socket so that component side of zone hybrid is on the same side as zone hybrid already located on the board. See also Error! Unknown switch argument.. Figure Error! Unknown switch argument. Zone Board After installation check that each pin of hybrid is properly in socket. Connect four active terminators to corresponding zone terminals. Start up the system by first inserting the mains plug into the mains socket and then connecting the battery connector to the controller board. If extension is in order the new total zone number is indicated on display panel. After this test the active terminators can be connected to their final sites and extended zones can be connected normally to corresponding terminals.

18 Page EXTENSION FROM 8 TO 12 (also 16 TO 20 or 24 TO 28) De-energize the system by first disconnecting the battery connector from the controller board and then mains plug from the mains socket. Install the new zone board above zone board(s) already located in the cabinet. See also Error! Unknown switch argument.. Connect the flat cable to the connectors of zone boards. Mark the terminal numbers on the zone board with pen (permanent ink) as shown in figure (eg. markings in second zone board are: TE 6 for zone terminals and TE 7 for zonal output terminals). Connect four active terminators to corresponding zone terminals. Start up the system by first inserting the mains plug into the mains socket and then connecting the battery connector to the controller board. If extension is in order the new zone number is indicated on display panel. After this test the active terminators can be connected to their final sites and extended zones can be connected normally to corresponding terminals. Figure Error! Unknown switch argument. Order of Zone Boards

19 Page 19 6 REPLACEMENT OF PROGRAM MEMORY (ROM) Program memory (32-pin PLCC-package) is circuit IC3 on the controller board. See Error! Unknown switch argument., Error! Unknown switch argument.. Program version has to be labeled on the memory package. That label must not be removed. De-energize allways the system by disconnecting the battery cable and the mains plug before replacing the memory. To change the memory circuit: remove the memory from the socket with a special tool or with some pin (eg. bended paper clip). Install the new memory into the socket so that bevelled corner of package is in the lower right corner as shown in figure. Start up the system by connecting the mains plug and the battery cable. During five seconds after start up the program version is displayed on the display panel. Check that displayed version number is same as number labeled on the memory package. CPU IC 1 Hole for removal tool IC 3 Bevelled corner Figure Error! Unknown switch argument. Replacement of program memory 7 RESTARTING THE SYSTEM The system is allways restarted automatically after power up of the system. The system can be restarted without power up by pushing restart button on the Controller Board (see Error! Unknown switch argument., Error! Unknown switch argument.) or by simultaneously pushing the "DISABLE + SELECT_UP + TEST + SILENCE" keys.

20 Page 20 8 POWER SUPPLY REPLACEMENT The system has to be de-energized before replacing the power supply by disconnecting the battery cable and the mains plug. The power supply is removed by first loosening (two turns) four screws through four holes in each corner of the power supply by screw driver (type: pozidrive nr. 1, minimum lenght 80 mm, maximum diameter 4.5 mm) and then moving the power supply up 1 cm and then pulling it out from cabinet. See Error! Reference source not found.. The new power supply is installed in opposite order as removing. Charger voltage adjustment NTC RESISTOR 27.2V J1 J2 X4 X4 GND

21 Page 21 REPLACING THE CPU-BOARD IN MINI-2000 WHICH HAS THE OLD POWER UNIT: - Cut the "short circuit"-wires on the right side of the CPU-board (see figure). - Check that the resistor R64 (47 k) has been installed to the board. REPLACING AN OLD POWER UNIT WITH THE NEW ONE: - Add the "short circuit"-wires over the resistor R64 and diode D24 on the right side of the CPU-board ( see figure). - Check the new power unit, J2 (short circuit piece) has to be installed and J1 has to be removed (cutted wire). - Replace the NTC resistor with 10 kiloohms resistor. (in old power unit there is not temperature compensation and the program cannot monitor the new power unit with compensation). - Check the voltage level of power unit (before connecting the cabel between CPU and power unit.) The level should be /- 0.1 V measured between two pins of connector X4 (see figure) in power unit. Adjust that level if needed. - Attach the cable (ESMI code , to be ordered separately) to the connector X4 on the new power unit and to the connector CO3 on the CPU-board. ADJUST VOLTAGE LEVEL NTC RESISTOR 27.2V GND J1 J2 X4 X4

22 Page 22 9 APPENDIX 1 - Layouts of Boards Figure Error! Unknown switch argument. Zone Board Figure Error! Unknown switch argument. Controller Board

23 Page APPENDIX 2 - Fuses Fuses on the controller board: Fuse Type Protects F1 T500mA Alarm device line 1 F2 T500mA Alarm device line 2 F3 T500mA Alarm device line 3 F4 T500mA Alarm device line 4 F5 T500mA General power supply (upper) F6 F4A Battery + F7 F4A Battery - F8 T500mA Alarm transmitter power supply F9 T500mA General power supply (upper) Fuses F1.. F4 cause an ALARM DEVICES FAULT indication and a 'fault n' display message when blowing. Fuses F6 and F7 cause a BATTERY FAULT 2 indication when blowing. Fuses F5, F8 and F9 cause a FUSE FAULT indication when blowing. Fuse on the zone interface board(s): Fuse Type Protects F1 T1A Power supply for the zones connected to the board Fuse F1 on the Zone board causes a zone fault (LINE BROKEN) indication from all zones connected to that zone board when blowing. Fuse in the Power Unit: Fuse Type Protects F1 T500mA The power unit internally Fuse F1 in the Power Unit causes a CHARGER FAULT (fn 6) when blowing.

User Manual. Dryer Controller M720

User Manual. Dryer Controller M720 User Manual Dryer Controller M720 Hardware version 1.00 Software version 1.00 Preliminary version Manual M720 Dryer controller Page 1 of 42 Document history Preliminary version: - Created in April, 2009

More information

Dryer Controller M720

Dryer Controller M720 User Manual Dryer Controller M720 Hardware version 2.00 Software version 2.00 Manual M720 Dryer controller Page 1 of 60 Document history Preliminary version: - Created in April, 2009 Hardware Version 2.00,

More information

La Marche Manufacturing Company Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual

La Marche Manufacturing Company   Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual La Marche Manufacturing Company www.lamarchemfg.com Option 46 Series Digital Combined Accessory Package Installation and Operation Manual This manual is subject to change without notice. You may obtain

More information

Fire Control Panel FS4000

Fire Control Panel FS4000 Fire Control Panel FS4000 INSTRUCTION MANUAL Revision 4/02.11 Contents 1. Introduction... 4 2. Terminology... 4 3. Function... 5 4. Technical features... 5 4.1 Fire alarm lines... 5 4.2. Current thresholds

More information

Application, Installation, Operation & Maintenance Manual

Application, Installation, Operation & Maintenance Manual APPROVED BY:JBJ PRESCIENT III FIRE ALARM & GAS EXTINGUISHING CONTROL PANEL Application, Installation, Operation & Maintenance Manual PAGE 1 of 43 CONTENTS 1. INTRODUCTION... 3 2. GENERAL DESCRIPTION...

More information

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63 Fire Extinguishing Control Panel FS5200Е INSTRUCTION MANUAL Revision 8/01.17 Instruction Manual Page 1 1. 2. 3. 4. 4.1. 4.2. 4.2.1. 4.2.2. 4.2.3. 4.2.4. 4.2.5. 4.2.6. 4.2.7. 4.2.8. 4.2.9. 4.2.10. 4.2.11.

More information

Fire Control Panel FS4000

Fire Control Panel FS4000 Fire Control Panel FS4000 INSTRUCTION MANUAL Revision 11/01.17 Contents 1. Introduction... 3 2. Terminology... 3 3. Function... 4 4. Technical features... 4 4.1 Fire alarm lines... 4 4.2. Current thresholds

More information

LEAKMONITOR MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND USER OPERATION MANUAL

LEAKMONITOR MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND USER OPERATION MANUAL LEAKMONITOR MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND USER OPERATION MANUAL The LeakMonitor alarm panel is a microprocessor controlled fully adjustable alarm system suitable for multizone

More information

La Marche Manufacturing Company Option 16 Series. Digital Combined Accessory Package. Installation and Operation Manual

La Marche Manufacturing Company   Option 16 Series. Digital Combined Accessory Package. Installation and Operation Manual La Marche Manufacturing Company www.lamarchemfg.com Option 16 Series Digital Combined Accessory Package Installation and Operation Manual This manual is subject to change without notice. You may obtain

More information

Fire Control Panel FS5100

Fire Control Panel FS5100 Fire Control Panel FS5100 INSTRUCTION MANUAL Revision 6/02.11 Contents 1. Introduction... 5 2. Terminology... 5 3. Function... 7 4. Technical data... 7 4.1. Modules... 7 4.1.1. Type of modules... 7 4.1.2.

More information

GE Security. FP1200, FP2000 and KSA1200 series fire panels, repeaters and emulators Interconnection and wiring

GE Security. FP1200, FP2000 and KSA1200 series fire panels, repeaters and emulators Interconnection and wiring GE Security FP1200, FP2000 and KSA1200 series fire panels, repeaters and emulators Interconnection and wiring Version v2-2 / September 2005 Aritech and Kilsen are GE Security brands. http://www.geindustrial.com/ge-interlogix/emea

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

REPEATER FS5200R INSTRUCTION MANUAL

REPEATER FS5200R INSTRUCTION MANUAL REPEATER FS5200R INSTRUCTION MANUAL Instruction Manual Page1 CONTENTS 1. Introduction... 3 2. Function... 3 3. Technical data... 3 4. Contents of delivery... 4 5. General information... 5 6. Duty Mode...

More information

Planning Instructions MEW01090 Revision 4

Planning Instructions MEW01090 Revision 4 Planning Instructions MEW01090 Revision 4 Fire Alarm System EBL128 V1.1.x Author: Jan Pettersson Date of issue: 2008-07-11 Date of rev: 2011-04-08 This page has deliberately been left blank. Table of contents

More information

ACCURATE ELECTRONICS INC

ACCURATE ELECTRONICS INC ACCURATE ELECTRONICS INC Page 1 of 7 Model 108078 2 Sept 09 WWW.ACCURATE.ORG PO BOX 1654 97075-1654 8687 SW Hall Blvd 97008 BEAVERTON OR USA 503.641.0118 FAX 503.646.3903 Practice Section 108078 Rev A

More information

BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL

BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL 26 Aug 2015 V1.8 Page 1 SECTION CONTENTS PAGE NO. 1.0 SYSTEMS DESCRIPTION 1.1 General descriptions 2 1.2 Master Alarm PCB 2 1.3 Zone Display Board 2 1.4

More information

Fire Control Panel. Installation & Programming Manual TABLE OF CONTENTS

Fire Control Panel. Installation & Programming Manual TABLE OF CONTENTS Fire Control Panel Installation & Programming Manual TBLE OF CONTENTS Page Getting Started 2 Power Supply Unit 3 Inputs 4 Outputs 4 LED Indications 4 User Keypad Functions 5 Engineer Keypad Functions 6

More information

Snifter ATEX22 VERSION. User Manual. Distributor

Snifter ATEX22 VERSION. User Manual. Distributor Snifter ATEX22 VERSION User Manual Distributor Version 1.4 09/09/2009 Table of Contents 1. INTRODUCTION... 3 1.1. Safety... 3 1.2. Product overview... 4 1.3. How does it work?... 4 2. INSTALLATION... 5

More information

FEC400 Series. Installation Manual

FEC400 Series. Installation Manual FEC400 Series Conventional microprocessor controlled fire detection and alarm panels with extinguishing control Installation Manual Version 2.3 / August 2004 Aritech is a GE Interlogix brand. http://www.geindustrial.com/ge-interlogix/emea

More information

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE General Description This guide provides a summary for installing and configuring the Centaur TM Cube Slave Alarm Signalling Equipment

More information

Saffire User & Installation Manual. IMPORTANT This manual should be left with the panel after installation.

Saffire User & Installation Manual. IMPORTANT This manual should be left with the panel after installation. Saffire+ 8-12 User & Installation Manual IMPORTANT This manual should be left with the panel after installation. We reserve the right to change product specifications without prior notice. Copyright VRC

More information

CONTROL DEVICE SLIDETRONIC HD

CONTROL DEVICE SLIDETRONIC HD CONTROL DEVICE SLIDETRONIC HD to control gravity self-closing fire gates Producer: Somati system s.r.o. Jihlavská 510/2c 664 41 Troubsko, okr.brno - venkov Tel.: 547 427 011 Fax: 547 427 013 E-mail: export@somati-system.cz

More information

UNC100 Integra Manual

UNC100 Integra Manual UNC100 Integra Manual New Generation Building Security July 30, 2014 V1.2 Copyright Notice Copyright 1995-2014 by All rights reserved Worldwide. Printed in Canada. This publication has been provided pursuant

More information

A36D/TPSD Modbus RTU (Serial) SCADA INTERFACE INSTRUCTIONS

A36D/TPSD Modbus RTU (Serial) SCADA INTERFACE INSTRUCTIONS SCADA INTERFACE INSTRUCTIONS - OPTION 21S - FOR A36D/TPSD SYSTEMS with option 500 and 550. A36D/TPSD Modbus RTU (Serial) SCADA INTERFACE OPTION 21S INSTRUCTIONS This manual is valid for A36D/TPSD Chargers

More information

FX FIRE DETECTION SYSTEM

FX FIRE DETECTION SYSTEM FX FIRE DETECTION SYSTEM Installation and commissioning manual Read this manual carefully before installation and commissioning! Installation and commissioning must be performed according to this manual.

More information

TECHNICAL DATA SHEET CONVENTIONAL FIRE ALARM SYSTEMS Conventional Fire Alarm Control Panel

TECHNICAL DATA SHEET CONVENTIONAL FIRE ALARM SYSTEMS Conventional Fire Alarm Control Panel CVENTIAL ALARM S Features: Description: The LF-CP Series Fire Alarm Control Panel is manufactured based on advanced technology while maintaining high quality during assembly. It is of solid state circuitry

More information

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel INSTALLATION, OPERATION AND MAINTENANCE MANUAL Version: CN-PM-1000.VER1.1-12/2012 EN54 INFORMATION In accordance with EN 54-2 clause 13.7, the maximum

More information

EXTINGUISHING CONTROL PANEL PX2 SERIES

EXTINGUISHING CONTROL PANEL PX2 SERIES EXTINGUISHING CONTROL PANEL PX2 SERIES AE/PX2 AE/SA-PX2 AE/94-PX2 USER MANUAL VERSION 1.0 APR/2007 CONTENT PAGE 1 INTRODUCTION...3 1.1 PURPOSE OF THE MANUAL... 3 1.2 REMARKS... 3 1.3 WARNINGS AND PRECAUTIONS....

More information

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL USER MANUAL 1 Table of Contents 1 SAFETY INFORMATION...3 1.1 SAFETY PRECAUTIONS DURING NORMAL OPERATION OF PANEL...3 1.3 BATTERY INFORMATION...3

More information

BSR Addressable Fire Detection control panel. Installation operation manual

BSR Addressable Fire Detection control panel. Installation operation manual BSR-1116 Addressable Fire Detection control panel Installation operation manual ATTENTION!!! READ THE MANUAL BEFORE THE INSTALLATION AND PAY ATTENTION TO PARAGRAPH 2.6.3 AND 2.6.4. Page 2 from 36 Contents

More information

Control box FSTronic DES-FS

Control box FSTronic DES-FS Control box FSTronic DES-FS Designed for drives of rolling fire shutters and sectional fire gates CONTENT: TECHNICAL REPORT 1. POWER SUPPLY 2. CONFIGURATION 3. INSTALLATION AND SETTING 4. DESCRIPTION OF

More information

ZIOU/230 - MAINS IO INSTRUCTION MANUAL

ZIOU/230 - MAINS IO INSTRUCTION MANUAL Description ZIOU/230 - MAINS IO INSTRUCTION MANUAL The Mains IO Modules are fully monitored loop powered devices which permit the interfacing of third party equipment with the Fire Alarm Control panel

More information

Public Safety DAS Annunciator Panel

Public Safety DAS Annunciator Panel Public Safety DAS Annunciator Panel 120 VAC Models: 1221-A, 1221-B, 1221-C Revision D 91117 48 VDC Models: 1221-A-48, 1221-B-48, 1221-C-48 24 VDC Models: 1221A-24, 1221-B-24, 1221-C-24 CAUTION: (Read This

More information

BS-316. Gas detection control panel up to 16 inputs. Installation operation manual

BS-316. Gas detection control panel up to 16 inputs. Installation operation manual BS-316 Gas detection control panel up to 16 inputs Installation operation manual Page 1 from 21 Contents 1 Operation instructions--------------------------------------------------------------------------------------------------------------------3

More information

M2500 Engine Controller Installation Manual

M2500 Engine Controller Installation Manual M2500 Engine Controller Installation Manual Revision: 23-04-2012 Page 1 Contents 1 Preface... 4 2 Installation... 5 3 Terminal Connections... 6 4 Inputs... 7 4.1 Power Supply... 7 4.2 Mode/ Control Inputs...

More information

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117 Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel Revision E 61117 CAUTION: (Read This First) This panel has been designed to make it nearly bullet proof to mistakes made when wiring

More information

MO n : 12JMC rév A

MO n : 12JMC rév A CTT8 MO n : rév A Page 2 / 18 MODIFICATIONS Rev. Description Date Checked by Approuved by Z Creation 2012/02/12 JMC LA A First issue 2012/02/14 JMC LA INDEX Page 3 / 18 GENERALITY 4 INTRODUCTION 4 ACCESSORIES

More information

Installation Instructions 4 Zone Fire Panel

Installation Instructions 4 Zone Fire Panel Installation Instructions 4 Zone Fire Panel General Features Four fully controlled zones with test / disable capability per zone. Two full controlled alarm lines with disable capability per line. 4V/800mA

More information

ECO N DATE DESCRIPTION OF CHANGE CHG

ECO N DATE DESCRIPTION OF CHANGE CHG Model Number: M21E-24-DIN Description: The product is a loop powered device which controls an unsupervised dual pole output channel suitable to manage 24VAC loads. The M21E-24-DIN is micro-controller operated,

More information

MODEL B2 INSTALLATION MANUAL

MODEL B2 INSTALLATION MANUAL RELEASE DEVICES GENERAL DESCRIPTION MODEL B2 INSTALLATION MANUAL S/N: The B2 Series Time Delay Release Devices are UL Listed, Canadian Listed, and CSFM Listed for use on rolling doors, single-slide and

More information

AL800ULADA. NAC Power Extender. Installation Guide

AL800ULADA. NAC Power Extender. Installation Guide AL800ULADA NAC Power Extender Installation Guide Rev. 122000 AL800ULADA - NAC Power Extender Overview: The Altronix AL800ULADA is an extremely cost effective 8 amp voltage regulated remote power supply/battery

More information

CTT8 TEMPERATURE MONITOR DEVICE

CTT8 TEMPERATURE MONITOR DEVICE INSTRUCTION MANUAL IM302-U v2.3 CTT8 TEMPERATURE MONITOR DEVICE GENERALITY The device of control temperatures CTT8 is used in the control of electric machine, transformer, motor, etc. where it s possible

More information

CONVENTIONAL CONTROL PANEL FL2/4/8/12 LT-XP

CONVENTIONAL CONTROL PANEL FL2/4/8/12 LT-XP FLx-LT-XP CONVENTIONAL CONTROL PANEL FL2/4/8/12 LT-XP Installation, Configuration and Operating Manual MAY 2008 MIE-MI-580I_FL rev.003 Information in this document is subject to change without notice.

More information

Operation and Maintenance Manual

Operation and Maintenance Manual (FKER Series) Repeater Panel (FKER, FKER, FKER8) Operation and Maintenance Manual Man-9EL Issue June Index Section Page. Introduction.... Safety and mounting.... Technical specification.... Control panel

More information

Added password for IP setup page : Password must be in IP format!

Added password for IP setup page : Password must be in IP format! NETWORK POWER MONITOR Release : 21 August 2014 Hardware Version : Version 7 Firmware version 1.00 PC Application Software : Version (latest)...2 Added password for IP setup page : Password must be in IP

More information

AL600ULADA. NAC Power Extender. Installation Guide

AL600ULADA. NAC Power Extender. Installation Guide AL600ULADA NAC Power Extender Installation Guide Rev. 122000 AL600ULADA - NAC Power Extender Overview: The Altronix AL600ULADA is an extremely cost effective 6.5 amp voltage regulated remote power supply/battery

More information

User manual and installation instruction Control for Fire Ventilation RV / RV 24-32

User manual and installation instruction Control for Fire Ventilation RV / RV 24-32 User manual and installation instruction Control for Fire Ventilation RV 24-24 / RV 24-32 Fire ventilation Comfort ventilation 24VDC max. 24/32A 2 Actuator outputs 1 Fire ventilation group, 2 comfort groups

More information

Technical Manual. Level Alarm Unit CARLA & WIDS

Technical Manual. Level Alarm Unit CARLA & WIDS CARLA & WIDS Technical Manual SAS au Capital de 2 158 244-444 871 933 R.C.S. Bourges - APE : 2651B Headquarter : 9, rue Isaac Newton - 18000 Bourges - France Technical Manual CARLA for Tankers Cargo Tanks

More information

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3 INTELLIGENT FIRE TECHNOLOGY Twinflex and Multipoint V3 User Guide (TO BE RETAINED BY USER) 26-0340 Issue 3 Rafiki Protection Limited Rafiki policy is one of continual improvement and the right to change

More information

OVEN INDUSTRIES, INC.

OVEN INDUSTRIES, INC. OVEN INDUSTRIES, INC. OPERATING MANUAL Model 5C7-252 TEMPERATURE CONTROLLER With PLC Inputs Introduction Thank you for purchasing our controller. The Model 5C7-252 is an exceptionally versatile unit and

More information

Danfoss gas detection units

Danfoss gas detection units Data sheet Danfoss gas detection units Types GD Premium, Premium+, Premium Duplex, Premium Remote, Premium Flex and Premium Uptime The Premium line gas detection units are used for monitoring and warning

More information

ABOUT THIS DOCUMENT AND THE DOCUMENT STRUCTURE WE USE

ABOUT THIS DOCUMENT AND THE DOCUMENT STRUCTURE WE USE ABOUT THIS DOCUMENT AND THE DOCUMENT STRUCTURE WE USE isocket Smart Relay is a complex Smart House system which is installed in the fuse cabinet (electric cabinet) in the house. We therefore assume that

More information

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 031703 Overview: The Altronix AL802ULADA is an extremely cost effective 8 amp voltage regulated

More information

CASS9000 Standalone FingerPrint Door Access System. User Manual

CASS9000 Standalone FingerPrint Door Access System. User Manual CASS9000 Standalone FingerPrint Door Access System User Manual CASS9000 COPYRIGHT Information furnished by Cass Technology Sdn. Bhd. is believed to be accurate and reliable. Cass Technology Sdn. Bhd. have

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd full installation, commissioning and operating manuals can be downloaded from www.haes-systems.co.uk combined addressable / conventional fire alarm control panel User Guide Approved Document No. MFBU-04

More information

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL Document No...G108WO1.DOC Serial No... Issue Date...17 th SEPTEMBER 1999 Software Version...1.4 APPROVED TO: NZS 4512:1997 AS/NZS 3548:1992 Fire Alarm

More information

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm Operating & Maintenance Manual Alert-4 Ethernet LCD Master Alarm w w w. a m i c o. c o m Contents User Responsibility 4 Introduction 4 Features 5 Description of the Alarm 5 Shipment Details 5 The Alarm

More information

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE D (OPERATION) INITIATE A DYNAMIC BATTERY TEST The system tests the back-up battery once every 24 hours. The owner can initiate a dynamic battery test at any time with the following codes while the system

More information

Tempco Part Number PCT30006 Temperature Control Enclosure with Relay Output for Tote Tank Heating Applications

Tempco Part Number PCT30006 Temperature Control Enclosure with Relay Output for Tote Tank Heating Applications Instruction Manual Tempco Part Number PCT30006 Temperature Control Enclosure with Relay Output for Tote Tank Heating Applications Manual PCT30006, Revision 9/20/2016 The PCT30006 control enclosure incorporates

More information

Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual

Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual Revision 4/01.17 Contents 1. Introduction... 6 2. Terminology... 6 3. Function... 8 4. Technical data... 8 4.1. Physical configuration...

More information

Operating instructions Page 14. Refrigerator Read the operating instructions before switching on for the first time

Operating instructions Page 14. Refrigerator Read the operating instructions before switching on for the first time Operating instructions Page 14 Refrigerator Read the operating instructions before switching on for the first time 7085 039-00 LKv 5710 Content Disposal notes... 14 Description of the appliance... 14 Safety

More information

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009 Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual Man-1048 Issue 05 October 2009 CONTENTS Contents... Page Safety & Installation...2 Installation - continued...3

More information

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS GENERAL DESCRIPTION... 2 STANDARD AND OPTIONAL PARTS LIST... 2 PARTS DIAGRAM... 3 TERMINAL DRAWING AND SPECIAL NOTES...

More information

Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual

Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual Revision 6/01.17 Contents 1. Introduction... 6 2. Terminology... 6 3. Function... 8 4. Technical data... 8 4.1. Physical configuration...

More information

S2000-ASPT. Fire Alarm and Extinguishing Control Panel. Engineer s and User s Manual

S2000-ASPT. Fire Alarm and Extinguishing Control Panel. Engineer s and User s Manual S2000-ASPT Fire Alarm and Extinguishing Control Panel Engineer s and User s Manual FIRE ALARM AND EXTINGUISHING CONTROL PANEL ATTENTION! To modify the panel configuration parameters use the program UProg.exe

More information

Matrix2000. User Guide - CPD Advanced Analog Fire Alarm Control Panel 4 24 Zones. Version: 2.0 Revision: 1

Matrix2000. User Guide - CPD Advanced Analog Fire Alarm Control Panel 4 24 Zones. Version: 2.0 Revision: 1 Matrix2000 User Guide - CPD Advanced Analog Fire Alarm Control Panel 4 24 s Version: 2.0 Revision: 1 IMPORTANT INFORMATION Limitation of liability It is mandatory, Matrix2000 panel to be installed in accordance

More information

Air Comfort. Installation instructions (English) A

Air Comfort. Installation instructions (English) A Air Comfort Installation instructions (English) WWW.BRINKAIRFORLIFE.NL 614788-A This appliance may be used by children as of 8 years of age, persons of reduced mental or physical capacities and those of

More information

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev Installation Guide for AL800UL-ADA NAC Power Extender Rev. 090500 Overview: The Altronix AL800UL-ADA is an extremely cost effective 8 amps voltage regulated remote power supply /battery charger. The AL800UL-ADA

More information

Control Panel Engineering and Commissioning Instructions

Control Panel Engineering and Commissioning Instructions Twinflex - V3 Fire Detection & Alarm System Control Panel Engineering and Commissioning Instructions (TO BE RETAINED BY THE COMMISSIONING ENGINEER) 26-0338 Issue 9 Fike s policy is one of continual improvement

More information

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description MODUL-R FIRE ALARM CONTROL PANELS MR-2900/MR-2920 Addressable Fire Alarm Control Panels Description MR-2900 Fire Alarm Control Panel The MR-2900 fire alarm system control unit is the heart of a sophisticated

More information

Entwicklung + Fertigung + Service: Heerweg 15 D, Denkendorf Tel.: / Fax.: /

Entwicklung + Fertigung + Service: Heerweg 15 D, Denkendorf Tel.: / Fax.: / Planungsbüro + Service: Esteraustr. 10, 56379 Holzappel Tel.: 0 64 39 / 90 19 90 Fax.: 0 64 39 / 90 19 91 E-Mail: u.ramakers@umsitec.de Entwicklung + Fertigung + Service: Heerweg 15 D, 73770 Denkendorf

More information

FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL

FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL THE GAMEWELL COMPANY PN: 71981 60 PLEASANT STREET ISSUE A ASHLAND, MA 01721 3/22/2001 This page intentionally blank ii

More information

The supplier and installer of the system should be approved by the local civil defence authority.

The supplier and installer of the system should be approved by the local civil defence authority. ANALOGUE ADDRESSABLE FIRE ALARM SYSTEM 1. Scope of Work The contractor shall supply, install, test and commission a modern Analogue Addressable Fire Detection and Alarm System of an approved manufacturer

More information

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL MADE IN THE U.S.A. U.L. LISTED CANADIAN LISTED CSFM: 7300-1418:100 GENERAL DESCRIPTION SERIAL NUMBER The Cookson Company FIREFLY II PLUS Time Delay Release

More information

Serial-No. / date. Electric: / May 2007

Serial-No. / date. Electric: / May 2007 CE & UL Version Error messages & Troubleshooting Electric and Gas Combi Model Serial-. / date from thru Electric: ESC 65 72584 / May 27 ESC 62 72584 / May 27 ESC 5 72584 / May 27 ESC 2 72584 / May 27 ESC

More information

Tempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications

Tempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications Instruction Manual Tempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications Manual PCT-3000 Revision 9/2014 The PCT-3000 series control console incorporates

More information

SET Installation and Operating Instructions. Level switch for one sensor

SET Installation and Operating Instructions. Level switch for one sensor Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel.: +358 29 006 260 Fax: +358 29 006 1260 7.11.2013 Internet: www.labkotec.fi 1/14 SET-1000 Level switch for one sensor Copyright 2013 Labkotec Oy

More information

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08 Beacon 200 Gas Monitor Operator s Manual Part Number: 71-2102RK Released: 6/6/08 Table of Contents Chapter 1: Introduction.................................................3 Overview.............................................................3

More information

How to modify Volvo Alarm Siren after it has given Message: Alarm system Service Required Ver. 1.2

How to modify Volvo Alarm Siren after it has given Message: Alarm system Service Required Ver. 1.2 How to modify Volvo Alarm Siren after it has given Message: Alarm system Service Required Ver. 1.2 We will show how to modify the Alarm Siren Unit without using Battery. If you are not sure or do not know

More information

OilSET Installation and Operating Instructions. Oil Separator Alarm Device

OilSET Installation and Operating Instructions. Oil Separator Alarm Device Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel: +358 29 006 260 Fax: +358 29 006 1260 18.11.2010 Internet: www.labkotec.fi 1/10 OilSET-1000 Oil Separator Alarm Device Copyright 2010 Labkotec

More information

Halton SAFE / 7.14 user guide and installation instructions

Halton SAFE / 7.14 user guide and installation instructions Halton SAFE / 7.14 user guide and installation instructions VERIFIED SOLUTIONS BY H A LTO N Enabling Wellbeing Table of contents 1 System description 3 2 User Accounts 4 3 Main menu 7 3.1 Main menu - Change

More information

Conventional Fire Alarm System 2014 V1.2

Conventional Fire Alarm System 2014 V1.2 Conventional Fire Alarm System 2014 V1.2 Product Overview Control Panel 2 Conventional Fire Panel GST102A 2 zone Fire panel GST104A 4 zone Fire panel GST108A 8 zone Fire panel GST116A 16 zone Fire Panel

More information

Constant voltage 3-phase rectifier.

Constant voltage 3-phase rectifier. 11750a Constant voltage 3-phase rectifier. Page 1 of 11 11750a Mechanical assembly The rectifier is assembled in a cabinet intended for indoor wall mounting. The cabinet has ventilation holes on both sides

More information

21-light Remote Annunciator. Owner s Manual

21-light Remote Annunciator. Owner s Manual 21-light Remote Annunciator Owner s Manual Annunciator Description... Inside Font Cover Detailed Specifications... 1 Environmental Specifications... 1 Power Supply Requirements... 1 Communication With

More information

ENV 06. Update Electronics Service Mode and Alarms

ENV 06. Update Electronics Service Mode and Alarms ENV 06 Update Electronics Service Mode and Alarms ENV 06 Introduction ENV 06 = Electrolux New Vision 2006 New electronic platform for washing machines and tumble dryers New design for all Electrolux household

More information

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual CONTENTS Installation Precautions... 1 EN 54 Information... 2 Chapter 1 Product Overview... 3 1.1 Features... 3 1.2 Technical Specifications... 3 1.2.1 Operating Voltage... 3 1.2.2 Batteries... 3 1.2.3

More information

SUPERINTEND VRE-08/16/32/64

SUPERINTEND VRE-08/16/32/64 SUPERINTEND VRE-08/16/32/64 Residual Current Monitoring System (RCM) for Grounded Electrical Systems 8/16/32/64 supervision points Operator Manual v2.00 Superintend VRE-08/16/32/64 operator manual v2.00

More information

RELEASE DEVICE CONTROLS

RELEASE DEVICE CONTROLS RELEASE DEVICE CONTROLS RELEASE DEVICE MODEL C+ INSTALLATION MANUAL UL LISTED CANADIAN LISTED CSFM: 7300-48:00 GENERAL DESCRIPTION: MADE IN THE U.S.A. S/N: The LM0-C+ Release Device/Control Panel is a

More information

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge Replaceable LED modules 11 Alarm Sequences as per ISA-18.1 standard Each channel/window fully field programmable RS232 or RS485 MODBUS-RTU communication Repeat relay for each window and multifunction relays

More information

On the job around the clock 24/7: Fire detection systems

On the job around the clock 24/7: Fire detection systems On the job around the clock 24/7: Fire detection systems Version 02.2010 Version: 02.2010 Product catalogue Fire detection systems This product catalogue is intended for sales purposes only. For planning,

More information

OPERATION AND INSTALLATION MANUAL

OPERATION AND INSTALLATION MANUAL EX+Plus 2 ZONE, 1AREA EXTINGUISHANT CONTROL PANEL OPERATION AND INSTALLATION MANUAL INTRODUCTION The Premier EX Plus is a 2 zone, single area panel for controlling the release of extinguishing gases in

More information

RMS-I-DE-01 Smoke Detector

RMS-I-DE-01 Smoke Detector RMS-I-DE-01 Smoke Detector 2012 CONTEG, spol. s r.o. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted or stored in any retrieval system of any nature,

More information

Discovery 1-4 Loop 96 Zone, 40-Character Analogue Addressable Control Panel. Application Guide

Discovery 1-4 Loop 96 Zone, 40-Character Analogue Addressable Control Panel. Application Guide Discovery 1-4 Loop 96 Zone, 40-Character Analogue Addressable Control Panel Application Guide Contents Page 1.0 Introduction and Typical System Illustration 2 2.0 Cabinet Specifications 4 3.0 Hardware

More information

Fire Control Panel. Installation & Programming Manual TABLE OF CONTENTS

Fire Control Panel. Installation & Programming Manual TABLE OF CONTENTS Fire Control Panel Installation & Programming Manual TABLE OF CONTENTS Page Getting Started 2 Power Supply Unit 3 Remote Keypad Bus 3 Inputs & Outputs 4 User Keypad Functions 5 Engineer Keypad Functions

More information

PERMACONN PM1030 Includes DI300. Installation Manual

PERMACONN PM1030 Includes DI300. Installation Manual PERMACONN PM1030 Includes DI300 Installation Manual Radio Data Comms Unit 5/20-30 Stubbs Street Silverwater NSW 2128 Telephone: 02 9352 1777 Facsimile: 02 9352 1700 Introduction The PERMACONN system provides

More information

Fire and Gas Monitoring Panel ST7-HV

Fire and Gas Monitoring Panel ST7-HV Fire and Gas Monitoring Panel ST7-HV INTRODUCTION TO THE ST7-HV SYSTEM The ST7-HV system is a programmable PLC suitable for safety and security installations with a high technological and economic content

More information

OPERATION AND MAINTENANCE MANUAL

OPERATION AND MAINTENANCE MANUAL OPERATION AND MAINTENANCE MANUAL Prg Sel line alarm on on/off alarm enter Clear EMIpro MICROPROCESSOR CONTENTS 1 GENERAL CHARACTERISTICS Page 2 1.1 General description Page 2 2 EMIPRO USER INTERFACE Page

More information

Discovery 1-4 Loop 32 Zone, 40 Character Analogue Addressable Control Panel. Application Guide

Discovery 1-4 Loop 32 Zone, 40 Character Analogue Addressable Control Panel. Application Guide Discovery 1-4 Loop 32 Zone, 40 Character Analogue Addressable Control Panel Application Guide Contents Page 1.0 Introduction and Typical System Illustration 2 2.0 Cabinet Specifications 4 3.0 Hardware

More information

OilSET-1000 (12 VDC)

OilSET-1000 (12 VDC) Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel: +358 29 006 260 Fax: +358 29 006 1260 Internet: www.labkotec.fi 20.03.2009 1/11 OilSET-1000 (12 VDC) Oil Separator Alarm Device Copyright 2009

More information

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum. September 29, 1997 Firecycle III 433 a 1. PRODUCT NAME VIKING Model E-1 Manufactured 1997 Present 2. MANUFACTURED FOR THE VIKING CORPORATION 210 N Industrial Park Road Hastings, Michigan 49058, U.S.A.

More information