EC Standard & NFPA 110 (EPSS) Documentation Best Practice. 1: Division Team Mission
|
|
- Agnes Shepherd
- 5 years ago
- Views:
Transcription
1 EC Standard & NFPA 110 (EPSS) Documentation Best Practice 1: Division Team Mission
2 Presenters Pouyan Layegh, P.E., MBA, LEED AP Director, Campus Services Facilities Management UT MD Anderson Cancer Center Disclaimer: Although the speaker is a member of the NFPA Technical Committee on Emergency Power Supplies which is responsible for NFPA 110 Supplies, which is responsible for NFPA 110 and 111, the views and opinions expressed in this presentation are purely those of the speaker and shall not be considered the official position of NFPA or any of its Technical Committees and shall not be considered to be, nor be relied upon as a Formal Interpretation nor be relied upon as, a Formal Interpretation. Readers are encouraged to refer to the entire texts of all referenced documents. NFPA members can obtain staff interpretations of NFPA standards at Javier J Hidalgo Manager, Electrical Systems Facilities Management UT MD Anderson Cancer Center
3 Background The University of Texas MD Anderson Cancer Center is one of the largest cancer centers in the United States, we span more than 15 million square feet across 40 structures and three campuses. We serve hundreds of patients at any given time. MD Anderson Cancer Center is supported by an emergency power supply system (EPSS) consisting of: 61 backup generators, with over 50 MW capacity a sophisticated fuel system that feeds 300,000 gallons of diesel to the generators, an electrical distribution system composed of over 200 automatic transfer switches, electrical switch gears, and parallel gears supported by breakers, synchronizers, and other sophisticated controls.
4 Codes & Standards NFPA 111 Standard on Stored Electrical Energy Emergency and Standby Power Systems NFPA 110 Standard for Emergency and StandbyPower Systems NFPA 101 Life Safety Code NFPA 99 Healthcare Facility Code NFPA 70E Standard for Electrical Safety in the Workplace The Joint Commission (TJC) Centers for Medicare & Medicaid Services (CMS)
5 Codes & Standards CMS 42 CFR (e) Effective 15 November (e)(1) Emergency generator location. The generator must be located in accordance with the location requirements found in the Health Care Facilities Code (NFPA 99 and Tentative Interim Amendments TIA 12-2, TIA 12-3, TIA 12-4, TIA 12-5, and TIA 12-6), Life Safety Code (NFPA 101 and Tentative Interim Amendments TIA 12-1, TIA 12-2, TIA 12-3, and TIA 12-4), and NFPA 110, when a new structure is built or when an existing structure or building is renovated (e)(2) Emergency generator inspection and testing. The hospital must implement the emergency power system inspection, testing, and maintenance requirements found in the Health Care Facilities Code, NFPA 110, and Life Safety Code.
6 Codes & Standards Joint Commission EC , EP 4-10 Projected to become effective 9 January 2017 EP 4 - At least weekly, the hospital inspects the emergency power supply system (EPSS), including all associated components and batteries. The results and completion dates of weekly inspections are documented. Note: For additional guidance, see NFPA : 8.3.1; 8.3.3; 8.3.4; EP5 - At least monthly, the hospital tests each emergency generator under load for at least 30 continuous minutes. The cool-down period is not part of the 30 continuous minutes. The test results and completion dates are documented. EP 6 - The monthly tests for diesel-powered emergency generators are conducted with a dynamic load that is at least 30% of the nameplate rating of the generator or meets the manufacturer s recommended prime movers exhaust gas temperature. If the hospital does not meet either the 30% of nameplate rating or the recommended exhaust gas temperature during any test in EC , EP 5, then it must test the emergency generator once every 12 months using supplemental (dynamic or static) loads of 50% of nameplate rating for 30 minutes, followed by 75% of nameplate rating for 60 minutes, for a total of 1 ½ continuous hours. Note: Tests for non-diesel-powered generators need only be conducted with available load. EP 7 - At least monthly, the hospital tests all automatic transfer switches on the inventory. The test results and completion dates are documented. EP8 - At least annually, the hospital tests the fuel quality to ASTM standards. The test results and completion dates are documented. Note: For additional guidance, see NFPA : EP 9 - At least once every 36 months, hospitals with a generator providing emergency power for the services listed in EC , EPs 5 and 6, test each emergency generator for a minimum of 4 continuous hours. The test results and completion dates are documented. Note: For additional guidance, see NFPA , Chapter 8. Note that NFPA 110 requires the transferring of all ATS during the triennial test. EP 10 - The 36-month diesel-powered emergency generator test uses a dynamic or static load that is at least 30% of the nameplate rating of the generator or meets the manufacturer s recommended prime movers' exhaust gas temperature. Note: Tests for non-diesel-powered generators need only be conducted with available load.
7 NFPA 110 Suggested Operation & Testing Procedures
8 NFPA 110 Typical Multiple-Unit EPSS
9 During a recent visit by The Joint Commission surveyors, UT MD Anderson Cancer Center review of the EPSS documentation took less than 30 min. This is the culmination of code compliance, third party verification and team work. Surveyors were presented with a binder that contained all equipment required maintenance & compliance followed by detail information of corrective and proactive work. It also included pertinent EPSS institutional polices and procedures And a summarized spreadsheet that included: Test Date Frequency Compliance Applicable Readings Test duration Test Result Documentation
10 Sample Summary View
11 Sample Documentation
12 What is Demand Response? It is a program that encourages customers to reduce demand, thereby reducing the peak demand for electricity among the utility power system. Demand response allows end-use electric customers to reduce their electrical usage in a given time period, in response to a utility power system reliability and financial incentive. MD Anderson has and is participating in DR programs for both Electrical Reliability Council of Texas (ERCOT) and CenterPoint Energy CPE. Last year several generators ran for 4 hours shedding 4MW of power from the grid and proving that our EPSS is operating as intended during peak demand time. Demand Response (DR) and EPSS Proper Functioning Validation
13 TJC ECNews December 2016
14 Questions?
David Stymiest, PE, CHFM, CHSP, FASHE cell Copyright 2014, Smith Seckman Reid, Inc.; All rights reserved
AHCA 2014 Fall Conference Changes in Emergency Power Codes & Standards David Stymiest, PE, CHFM, CHSP, FASHE DStymiest@ssr-inc.com, cell 504.232.1113 Copyright 2014, Smith Seckman Reid, Inc.; All rights
More informationNFPA Updates (c) 2015 SSR, Inc. All rights reserved Florida AHCA Conf
Training presentation for: 2015 Florida AHCA Conference NFPA 110 Updates for 2016 David Stymiest, CHFM, CHSP, FASHE, (PE in LA MS MA) DStymiest@ssr-inc.com, cell 504.232.1113 Copyright 2015, Smith Seckman
More informationLife Safety Code Comparison
ASHE Monograph Life Safety Code Comparison Michael A. Crowley, PE, SASHE Jeffery E. Harper, PE ASHE Monograph Life Safety Code Comparison Michael A. Crowley, PE, SASHE Jeffery E. Harper, PE Chicago 2013
More informationBuilding Analytics and Compliance: How analytics can be used to aid in performancebased certifications. Bryant M. Kirkland Jr, PE, CCP, LEED AP
Building Analytics and Compliance: How analytics can be used to aid in performancebased certifications Bryant M. Kirkland Jr, PE, CCP, LEED AP AIA Quality Assurance The Building Commissioning Association
More informationChanges to Environment of Care, Equipment Management, and Life Safety Chapters Related to Life Safety Code Updates
Issued September 20, 2017 Changes to Environment of Care, Equipment Management, and Life Safety Chapters Related to Life Safety Code Updates Environment of Care (EC) Chapter Home Care (OME) Accreditation
More informationFACILITIES PLANNED UTILITY OUTAGES POLICY
UTMDACC INSTITUTIONAL POLICY # ADM1131 FACILITIES PLANNED UTILITY OUTAGES POLICY PURPOSE The purpose of the policy is to define roles and responsibilities for requesting, coordinating, scheduling, and
More informationCHFM, CHSP, FASHE (PE
A PRESENTATION FOR TAHFM 2013 Interlink NFPA 110 Update + Expanding the Concept of EP Reliability David Stymiest, PE, CHFM, CHSP, FASHE (PE in LA, MS, MA) DStymiest@ssr-inc.com, cell 504.232.1113 Copyright
More informationChanges to Environment of Care and Life Safety Chapters Related to Life Safety Code Updates
Issued June 28, 207 Changes to Environment of Care and Life Safety Chapters Related to Life Safety Code Updates Environment of Care (EC) Chapter Nursing Care Center (NCC) Accreditation Program Standard
More informationASHE Advocacy Team. Q4 ASHE Advocacy Liaison Webinar 12/7/16 12/7/16. Tim Adams, FASHE, CHFM, CHC Director of Leadership Development
Q4 ASHE Advocacy Liaison Webinar 12/7/16 ASHE Advocacy Team Chad E. Beebe, AIA, CHFM, CFPS, CBO, SASHE Deputy Executive Director of Advocacy cbeebe@aha.org Tim Adams, FASHE, CHFM, CHC Director of Leadership
More informationMedical Gas Inspections and Maintenance Programs. HESNI Annual Conference NIU Conference Center May 10-11, 2018 Presented by Mathis Carlson
Medical Gas Inspections and Maintenance Programs HESNI Annual Conference NIU Conference Center May 10-11, 2018 Presented by Mathis Carlson Mathis Carlson I have worked for the last 15+ years in the Medical
More informationCenter for Clinical Standards and Quality /Survey & Certification Group
DEPARTMENT OF HEALTH & HUMAN SERVICES Centers for Medicare & Medicaid Services 7500 Security Boulevard, Mail Stop C2-21-16 Baltimore, Maryland 21244-1850 Center for Clinical Standards and Quality /Survey
More informationHealthcare Emergency Power Supply Systems. Maintenance and Testing
Healthcare Emergency Power Supply Systems Maintenance and Testing Maintenance and Testing NFPA 110, 8.1.1 NFPA 110, 8.1.1 The routine maintenance and operational testing program shall be based on all of
More informationProgrammatic Policy and Procedure
Page 1 of 6 Programmatic Policy and Procedure Section Sub-section Psychiatric Health Facility (PHF) Crisis and Emergency Response Effective: Version: Policy Emergency Subsistence Management Last Revised:
More information4/18/2017. *2012 edition of NFPA 99 has gone through a major overhaul. *This document is now a Code.
Carsten Lunde, ASSE 6050 Instructor April 20, 2017 Carsten s Yearly Analysis, Inc. Any opinions expressed verbally by the speaker before you and all text in this presentation should be considered the speakers
More informationTHE HEALTHCARE ENVIRONMENT UPDATE. Anne M. Guglielmo, Engineer Engineering Department The Joint Commission. Copyright, The Joint Commission
2013 THE HEALTHCARE ENVIRONMENT UPDATE Anne M. Guglielmo, Engineer Engineering Department The Joint Commission Standard/NPSG 2012 Non Compliance 2013 Non Compliance (1 st Six Months) RC.01.01.01 61% 55%
More informationCENTRAL STATE HOSPITAL PLAN PLANT OPERATIONS UTILITIES MANAGEMENT PLAN
Page 1 of 11 CENTRAL STATE HOSPITAL PLAN SUBJECT: PLANT OPERATIONS UTILITIES MANAGEMENT PLAN ANNUAL REVIEW MONTH: RESPONSIBLE FOR REVIEW: March CSH Safety Officer LAST REVISION DATE: November 2003 I. SCOPE:
More informationGPS 140 NEC Requirements for Generators. Professional Development Seminar Series NEC Requirements for Generators
GPS 140 NEC Requirements for Generators WHAT YOU WILL LEARN NEC requirements for on-site power generation. Recent events have created increased interest in standby power This module organizes NEC requirements
More informationAre there any policies regarding outlets that contain USB ports?
Answers to the Questions Mark J. Blackburn, P.E., CFPS February, 2016 Question 1 Are there any policies regarding outlets that contain USB ports? There is no direct reference in code about these types
More informationStandards Revisions Related to Life Safety Code Update
Prepublication Issued Requirements The Joint Commission has approved the following revisions for prepublication. While revised requirements are published in the semiannual updates to the print manuals
More information16620 EMERGENCY POWER SYSTEMS
16620 EMERGENCY POWER SYSTEMS PART 1: GENERAL 1.01 SUMMARY A. This Section provides the University guidelines for the installation of Emergency Power Systems. B. This standard is developed primarily to
More informationCHFM, CHSP, FASHE (PE
A PRESENTATION FOR TAHFM 2013 Interlink NFPA 110 Update + Expanding the Concept of EP Reliability David Stymiest, PE, CHFM, CHSP, FASHE (PE in LA, MS, MA) DStymiest@ssr-inc.com, cell 504.232.1113 Copyright
More informationToday s Webcast starts at 1:00 p.m. Eastern. You will not hear audio until the Webcast begins
Today s Webcast starts at 1:00 p.m. Eastern. You will not hear audio until the Webcast begins Today's Moderator Cathy Jakicic Editor Today's Presenter Esteban Cota National Business Manager for Fire Safety
More informationStandards Revisions Related to Life Safety Code Update
Prepublication Issued Requirements The Joint Commission has approved the following revisions for prepublication. While revised requirements are published in the semiannual updates to the print manuals
More informationTop 8 Findings & SAFER Matrix for the 2017 ACE Summit & Expo
Top 8 Findings & SAFER Matrix for the 2017 ACE Summit & Expo February 20, 2017 Atlanta, GA Larry F. Rubin CHFM, CHSP, CPE, CEM Life Safety Code Surveyor The Joint Commission Engineering Department 2015-1
More informationHealthcare Electrical Reference Architecture for Large Hospitals in North America
Healthcare Electrical Reference Architecture for Large Hospitals in North America Catalog 0100CT1803 2018 schneider-electric.com/ecostruxure EcoStruxureTM Power Electrical Reference Architecture for Large
More informationThe Surveyor s Perspective. Understanding How The Joint Commission Surveyors Conducts Surveys
The Surveyor s Perspective Understanding How The Joint Commission Surveyors Conducts Surveys Tim Markijohn MBA\MHA, CHFM, CHE Field Director, Life Safety Learning Objectives At the conclusion of this presentation,
More informationPRINTED: 06/09/2017 FORM APPROVED CENTERS FOR MEDICARE & MEDICAID SERVICES OMB NO (X2) MULTIPLE CONSTRUCTION A. BUILDING 03 - A BUILDING
SUMMARY PROVER'S PLAN OF CORRECTION K 000 INITIAL COMMENTS K 000 A Life Safety Code Survey was conducted by the State Fire Marshal beginning on May 9th, 2017 and ending on May 10th, 2017. Adair Acute Care
More informationNFPA Edition Review
This is a photographic template your photograph should fit precisely within this rectangle. NFPA 70 & 99 How Recent Code Changes Effect Healthcare Facilities Sam C. Terry, P.E. Application Engineer Eaton
More informationPresented by: Brad Keyes, CHSP Senior Consultant Keyes Life Safety Compliance, LLC
Presented by: Brad Keyes, CHSP Senior Consultant Keyes Life Safety Compliance, LLC Changes to Life Safety Compliance Healthcare leaders will have to deal with many changes in Life Safety compliance when
More informationWORKING DRAFT OF COMMITTEE MEETING OUTPUT
WORKING DRAFT OF COMMITTEE MEETING OUTPUT CONTENT NOT FINAL SUBJECT TO REVISION PRIOR TO LETTER BALLOT AND PUBLICATION OF FIRST DRAFT REPORT Document: NFPA 110 (EPS-AAA) Revision Cycle: A2018 Meeting Date(s):
More informationLIFE SAFETY & FIRE PREVENTION MANAGEMENT PLAN
Title/Description: Life Safety & Fire Prevention Management Department: Facilities Management Personnel: All Effective Date: 5/97 Revised: 7/00, 7/01, 7/02, 7/03, 7/04, 7/05, 7/08 LIFE SAFETY & FIRE PREVENTION
More information2017 Accreditation Updates
2017 Accreditation Updates Tennessee Healthcare Engineers Association 2017 Spring Conference Pickwick Landing State Park Counce, Tennessee 38326 Presented May 17, 2017 By Ken Gregory Vice President, Accreditation
More informationEMERGENCY POWER SYSTEMS
263213 EMERGENCY POWER SYSTEMS PART 1: GENERAL 1.01 SUMMARY A. Section includes: 1. University guidelines for the installation of Emergency Power Systems (EPS). 2. Addresses the design and installation
More informationHeathcare Interpretations Task Force
Healthcare Interpretations Task Force MEMORANDUM TO: FROM: Heathcare Interpretations Task Force Robert Solomon DATE: May 30, 2014 SUBJ: HITF Meeting Agenda and Meeting Room Location Information Attached
More informationTHE HEALTHCARE ENVIRONMENT UPDATE. George Mills, Director Engineering Department The Joint Commission. Copyright, The Joint Commission
2013 THE HEALTHCARE ENVIRONMENT UPDATE George Mills, Director Engineering Department The Joint Commission Standard/NPSG 2012 Non Compliance 2013 Non Compliance (1 st Six Months) RC.01.01.01 61% 55% LS.02.01.20
More informationINITIAL FIRE SAFETY ASSESSMENT
INITIAL FIRE SAFETY ASSESSMENT Factory Mouza Chandra, Shafipur, Kaliakoir, Gazipur Gazipur Dhaka 24 Mar 2014 The Alliance for Worker Safety Page 1/12 24 Mar 2014 Introduction to the Report The following
More informationThe Healthcare Environment Update
2017 The Healthcare Environment Update John Maurer, SASHE, CHFM, CHSP Engineering Department The Joint Commission Engineering Department 2017-1 Most Cited Standards Standard 2015 % Noncompliance 2016 %
More informationU.S. Codes & Standards for Energy Storage Systems. Joe Cain, P.E. Chair, SEIA Codes & Standards Working Group
U.S. Codes & Standards for Energy Storage Systems Joe Cain, P.E. Chair, SEIA Codes & Standards Working Group Regulatory Update: U.S. Codes & Standards Agenda NFPA 70 (NEC) UL 1973 & 9540 Fire Codes NFPA
More informationToday s Webcast starts at 1:00 p.m. Eastern. You will not hear audio un=l the Webcast begins
Today s Webcast starts at 1:00 p.m. Eastern. You will not hear audio un=l the Webcast begins Today's Moderator Cathy Jakicic Editor Today's Presenter Esteban Cota Na#onal Business Manager for Fire Safety
More informationOUR MISSION. OUR MISSION is to promote secure
OUR MISSION OUR MISSION is to promote secure and safe openings that enhance life safety through outreach efforts that include awareness and education within the building design, code authority and facility
More informationPage 1 of 6 10/19/2016 9:49 AM. Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input
Public Input No. 4-NFPA 111-2016 [ Section No. 1.1.4.1 ] 1.1.4.1 * This standard shall not cover the following: (1) Application of the SEPSS (2) Distribution wiring (3) Systems having total outputs less
More informationSummary of Chapters NFPA 1911: Standard for the Inspection, Maintenance, Testing, and Retirement of In- Service Automotive Fire Apparatus
Summary of Chapters NFPA 1911: Standard for the Inspection, Maintenance, Testing, and Retirement of In- Service Automotive Fire Apparatus Applicable to any public or private organization that uses fire
More information2018 Joint Commission Standards What s New in the EC/LS/UM GASHE Annual March Meeting Lake Blackshear Resort
2018 Joint Commission Standards What s New in the EC/LS/UM GASHE Annual March Meeting Lake Blackshear Resort Presented March 9, 2018 By Ken Gregory, CHSP President Ken Gregory Consulting 1 2018 Joint Commission
More informationSECTION GENERATOR PARALLELING CONTROLS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 23 13 GENERATOR PARALLELING CONTROLS SPEC WRITER NOTE: Delete between // -- // if not applicable to project. Also delete any other item or paragraph not applicable
More informationTHE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #6
THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #6 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1 QUESTIONS How To Ask a Question: POLLING There will be occasional
More informationAgency for Health Care Administration. Eddie Alday Life Safety Code Lead 30 th AHCA Seminar 23 September 2014
Agency for Health Care Administration Eddie Alday Life Safety Code Lead 30 th AHCA Seminar 23 September 2014 CMS S&C Letter Interpretation CMS- S&C: 13-58-LSC Dated: 08/30/2013 Several Categorical LSC
More informationEC 5.10 FIRE PREVENTION MANAGEMENT
EC 5.10 FIRE PREVENTION MANAGEMENT The organization manages fire safety risks. 1 The organization develops and maintains a written management plan describing the processes it implements to effectively
More informationNEC Requirements for Standby Power Systems. New England Building Officials Education Association Annual Conference October 5, 2015
NEC Requirements for Standby Power Systems New England Building Officials Education Association Annual Conference October 5, 2015 Emergency & Standby Power Systems Alternative power sources are utilized
More informationSurviving the Survivable Cable Crunch
Fire Alarm Notebook by Dean K. Wilson. P.E. Page 1 Surviving the Survivable Cable Crunch by Dean K. Wilson, P.E. Question: I am a fire inspector in a mid-western city. We have recently received preliminary
More informationUNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY
Revision No.: 6 Page 1 of 5 I. PURPOSE This procedure provides guidance to EH&S office staff to coordinate notifications of appropriate internal staff who will need to respond to an unannounced Joint Commission
More informationChapter 17, Initiating Devices
Chapter 17, Initiating Devices Summary. Chapter 17 was Chapter 5 in NFPA 72-2007. The term authority having jurisdiction is replaced in some sections by the term other governing laws, codes, or standards.
More information3M Personal Safety Division. Standards Update. NFPA 1981/1982, 2018 Edition. March 30, 2018
3M Personal Safety Division Standards Update NFPA 1981/1982, 2018 Edition March 30, 2018 Standards Update NFPA 1981/1982, 2018 Edition The purpose of this presentation is to provide an update on the status
More informationNEW ENERGY IN THE BATTERY INFRASTRUCTURE
NEW ENERGY IN THE BATTERY INFRASTRUCTURE Maurice H. Johnson Business Development Engineer UL LLC Northbrook, IL Paper Overview Over the past several years, there has been a significant effort to address
More informationField Guide for Healthcare Facilities
Field Guide for Healthcare Facilities Jennifer L. Frecker James K. Lathrop Written by industry experts Jennifer L. Frecker and James K. Lathrop and using an easy-to-digest format, The New Life Safety Code
More informationCompliance w/ the 2012 Life Safety Code
Compliance w/ the 2012 Life Safety Code Implications of the 2012 NFPA Code Set for Existing & New ASCs William E. Lindeman, AIA http://www.weldesigns.com Financial Interest Disclosure The presenter provides
More informationWelcome DISCLAIMER. Testing Electric Fire Pumps You Need to Understand the Arc Flash Hazard 5/1/ NFPA Conference & Expo
2017 NFPA Conference & Expo Testing Electric Fire Pumps You Need to Understand the Arc Flash Hazard Presented by: Tracey D. Bellamy, PE, CFPS Chief Engineering Officer Telgian Corporation Welcome Instructor
More informationCopyright Information
1 Copyright Information Copyright 2013 HCPro, Inc. The Adopting the 2012 Life Safety Code : Prepare for Fire Safety Equipment Testing and Inspection Changes materials package is published by HCPro, Inc.
More information10/25/2018. Facilitators. Emergency Preparedness &Life Safety Code for Administrators. Participant Guide
Emergency Preparedness &Life Safety Code for Administrators 1 Participant Guide Emergency PreparednessHandouts Graphic Organizer Sample Checklist for Emergency Preparedness Regulation Compliance Crosswalk
More informationWHAT S NEW IN NFPA
WHAT S NEW IN NFPA 99-2012 North Carolina Hospital Engineers Association Fall Conference Grove Park Inn Asheville, NC Presented August 24, 2017 By Ken Gregory, CHSP Who Regulates Hospitals? Congress Healthcare
More informationWHAT S NEW IN NFPA
WHAT S NEW IN NFPA 99-2012 North Carolina Hospital Engineers Association Fall Conference Grove Park Inn Asheville, NC Presented August 24, 2017 By Ken Gregory, CHSP Who Regulates Hospitals? Congress Healthcare
More informationMotion Controlled Apartment Building Corridor Lighting
STAFF REPORT ACTION REQUIRED Motion Controlled Apartment Building Corridor Lighting Date: October 19, 2009 To: From: Wards: Reference Number: Licensing and Standard Committee Executive Director, Municipal
More informationINITIAL FIRE SAFETY ASSESSMENT
INITIAL FIRE SAFETY ASSESSMENT Dhanpur, Chapapur, Kotwali, Comilla COMILLA Chittagong The Alliance for Worker Safety Page 1/16 Introduction to the Report The following report contains a site profile and
More informationHEALTHCARE INTERPRETATIONS TASK FORCE AGENDA
HEALTHCARE INTERPRETATIONS TASK FORCE AGENDA 1. Call to order 8:30 A.M. DECEMBER 5, 2007 Greenberg Traurig Law Firm 800 Connecticut Avenue N.W., Suite 500, Washington, DC 20006 Tel: 202.331.3100 Fax: 202.331.3101
More informationObjectives. NFPA Dust Specific Documents. Combustible Dust Process Hazard Safety Overview of NFPA Standards for Combustible Dusts
Combustible Dust Process Hazard Safety Overview of NFPA Standards for Combustible Dusts Guy R. Colonna, PE Division Manager, NFPA Combustible Dust Symposium Detroit, MI September 20, 2011 1 Objectives
More informationCode Technology Committee Meeting #31 March 31-April 1, 2015 Care_WTC Recommendations/Elevators
Code Technology Committee Meeting #31 March 31-April 1, 2015 Care_WTC Recommendations/Elevators This list is a compilation of 2015 Cycle code changes related to the above CTC Area of Study. E 42-15 Page
More informationFacility Sourcing Practices and Joint Commission Update
Facility Sourcing Practices and Joint Commission Update Presenters: John Brownrigg Director, Pre-Construction Services FX Facility Group Larry Rubin Life Safety Code Surveyor The Joint Commission ACE 2018
More informationChanges to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH)
Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH) The following represents a review of the Life Safety chapter of the new 2018 Joint Commission CAMH manual for
More informationPublic Safety in the Healthcare Facility
CABMET Study Group Public Safety in the Healthcare Facility Matt Baretich Baretich Engineering Fort Collins, Colorado mfb@baretich.com Slide 1 Public Safety: 15% of CBET Exam Electrical Chemical Radiation
More informationThe Physical Environment Portal: Module 5, LS Leadership
The Physical Environment Portal: Module 5, LS.02.01.10 - Leadership Fire Safety: Background Fire safety impacts both the lives of the occupants and the physical structures. In the early 1900 s many buildings
More informationWHEA FSE inspections.
WHEA FSE inspections www.jfahern.com FEC.02.03.05 Features of Fire Safety Buildings are protected from fire by a series of detection, notification and suppression devices Each feature of fire safety must
More informationASCO PowerQuest Power Monitoring and Control Systems
ASCO PowerQuest Power Monitoring and Control Systems THE POWER TO KNOW It s all about the need to know... Your need to know what s happening with your facility s on-site power and distribution system.
More informationEQUIVALENT INITIAL FIRE SAFETY ASSESSMENT
EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Plot # 33-36 Sector # 07, Chittagong Chittagong Chittagong 08 Jun 2014 The Alliance for Worker Safety Page 1/18 08 Jun 2014 Introduction to the Report
More informationCMS Regulatory Update & Survey Trends: Life Safety Code
CMS Regulatory Update & Survey Trends: Life Safety Code CMS Physical Environment Compliance Challenges William E. Lindeman, AIA http://www.weldesigns.com Financial Interest Disclosure The presenter provides
More informationJOINT COMMISSION PREPAREDNESS / STATEMENT OF CONDITIONS DRAWINGS WSSHE SOUTHWEST CHAPTER NOVEMBER 19, 2015
JOINT COMMISSION PREPAREDNESS / STATEMENT OF CONDITIONS DRAWINGS WSSHE SOUTHWEST CHAPTER NOVEMBER 19, 2015 AGENDA INTRODUCTION OF PRESENTERS SOC VS. FIRE & LIFE SAFETY DRAWINGS HAZARDOUS AREAS VS. INCIDENTAL
More informationINITIAL FIRE SAFETY ASSESSMENT
INITIAL FIRE SAFETY ASSESSMENT Factory Bashtoli, Sinabah, Sofipur, Kaliakoir, Gazipur Gazipur Dhaka 08 Sep 2014 The Alliance for Worker Safety Page 1/10 Factory 08 Sep 2014 Introduction to the Report The
More informationWhy Selective Coordination is Mandatory -- It Fills the Reliability Hole --
Why Selective Coordination is Mandatory -- It Fills the Reliability Hole -- The NEC has mandatory selective coordination requirements for the following systems. Emergency Systems- Article 700 700.27 Legally
More information2016 Joint Commission Update
2016 Joint Commission Update Bert M. Gumeringer, MBA, CHFM, FASHE Asst. Vice President-Facilities Operations Texas Children s Hospital August 12, 2016 11:30am-12:30pm Top 10 Findings Comparison-2015 vs.2016
More information1.0 Purpose of a Secondary Plan for the Masonville Transit Village
Report to Planning and Environment Committee To: Chair and Members Planning & Environment Committee From: John M. Fleming Managing Director, Planning and City Planner Subject: Masonville Transit Village
More informationHome Fires Involving Heating Equipment
Home Fires Involving Heating Equipment December 2017 Richard Campbell December 2017 National Fire Protection Association Abstract In 2011-2015, U.S. fire departments responded to an estimated average of
More informationThe Impact the Reference Standards in the 2012 Edition of NFPA 101 have on the Operation of Health Care Facilities: NFPA 80 and 99
The Impact the Reference Standards in the 2012 Edition of NFPA 101 have on the Operation of Health Care Facilities: NFPA 80 and 99 Sharon S. Gilyeat, P.E. Lauren Schrumpf August 8, 2018 Expertly Engineering
More informationMaryland State Fire Marshals Office Rep. International Fire Marshals Association (IFMA)
MINUTES HEALTHCARE INTERPRETATIONS TASK FORCE Tuesday June 14, 2011 BOSTON CONVENTION & EXHIBITION CENTER (BCEC) ROOM 104C 415 Summer Street Boston, MA 1. The meeting was called to order at 8:40 AM. (See
More informationBeth Israel Deaconess Medical Center BIDMC Manual
Beth Israel Deaconess Medical Center BIDMC Manual Title: Life Safety/Fire Safety Management Plan Policy #: EOC-04 Purpose: The BIDMC Life Safety Management Plan defines the program to minimize the probability
More informationM E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot
M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Service and Fire Protection Equipment Gregory Harrington, P.E., Staff Liaison DATE: October 1, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter
More informationElement Z General Design Requirements Owner Standards and Other Requirements
Codes and Applicable PART 1 - INTRODUCTION 1.01 OVERVIEW A. This Section addresses minimum codes, guidelines, regulations and standards that must be appropriately applied in designing facility systems
More informationPlanning and Growth Management Committee
STAFF REPORT ACTION REQUIRED By-law to Require and Govern the Construction of Green Roofs in Toronto Date: October 29, 2008 To: From: Wards: Reference Number: Planning and Growth Management Committee Chief
More informationLife Safety Code NFPA 10 NFPA 13 NFPA 25 NFPA 72 NFPA 90A NFPA 110 NFPA 99 THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #7
THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #7 AGENDA: Life Safety Code Referenced Publications Overview Life Safety Code NFPA 10 NFPA 13 NFPA 25 NFPA 72 NFPA 90A NFPA 110 NFPA 99
More information2.07 Permit Application Checklist for Diesel Generators, Diesel Fire Pumps, and Fuel Tanks Serving Generators and Fire Pumps (2016)
2.07 Permit Application Checklist for Diesel Generators, Diesel Fire Pumps, and Fuel Tanks Serving Generators and Fire Pumps (2016) Reference: Documents referenced for this bulletin are as follows: San
More informationEPSS Monitoring for Total Compliance
EPSS Monitoring for Total Compliance A Lawyer s Playground PRESENTED BY Dan Chisholm, Sr. Chairman of NFPA 110 Technical Committee Dan.Chisholm@mgi-epss.com Learning Objectives What CMS surveyors are looking
More informationNational Grid Residential Active Demand Reduction Demonstration Project. MA EEAC Demand Reduction Sub-Committee February 23, 2017
National Grid Residential Active Demand Reduction Demonstration Project MA EEAC Demand Reduction Sub-Committee February 23, 2017 What are we testing? Impact of calling DR events using Direct Load Control
More informationEXPLORING LIFE SAFETY COMPLIANCE FOR HEALTH CARE
2016 EXPLORING LIFE SAFETY COMPLIANCE FOR HEALTH CARE James Woodson, Engineer Engineering Department The Joint Commission HOSPITAL BREAKFAST BRIEFINGS PART 6 Disclosure Statement The following staff and
More informationCHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS
CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS 61G15-32.001 61G15-32.002 61G15-32.003 61G15-32.004 61G15-32.005 61G15-32.006 61G15-32.007
More informationCourse Outline. Course Introduction Purpose of the course Course Overview Program Outline Instructor Information
The main focus of the ASSE 6040 Medical Gas Systems Maintenance Personnel Course is to provide individuals, who are responsible for the proper inspection, testing, and maintenance of medical gas systems,
More informationBuilding Fire Safety in New York City s Existing Office Buildings
www.goldmancopeland.com Building Fire Safety in New York City s Existing Office Buildings Daniel Colombini, PE, LEED AP Principal, Director of Plumbing/Fire Protection Director of Plumbing and Fire Protection
More informationMeasures (ILSM) Process
Managing the Interim Life Safety Measures (ILSM) Process 1 A Program for The Texas Association of Healthcare Facility Management Monday, April 30, 2012 Robert H. Bartels, CHFM CHSP CHEP SASHE President,
More informationOther EC and LS documents may be requested by surveyors, as needed, throughout the survey.
Documentation required by the Hospital Accreditation program Life Safety (LS) and selected Environment of Care (EC) standards is presented in the following pages. These documents will be reviewed by the
More informationEQUIVALENT INITIAL FIRE SAFETY ASSESSMENT
EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Address: Plot # 59-87, Adamjee Export Processing ZONE, Adamjee Nagar, Siddergonj, Narayangonj, Siddirgonj, Narayangonj Dhaka Bangladesh 09 Jun 2014 The
More informationLife Safety Code Potpourri
Life Safety Code Potpourri JAMES P. LOVELAND P.E. MINNESOTA DEPARTMENT OF HEALTH Engineering Services Section FEDERAL MONITORING SURVEYS 2007 2008 2009 No. of FMSs 20 20 20 No. of Deficiencies 332 252
More informationBUSINESS PLAN CEN/TC 121 WELDING AND ALLIED PROCESSES EXECUTIVE SUMMARY
Page: 1 BUSINESS PLAN CEN/TC 121 WELDING AND ALLIED PROCESSES EXECUTIVE SUMMARY Business Environment Standardization of welding by all processes, as well as allied processes; these standards include terminology,
More informationCalifornia Fire Code (CFC) Part III contains requirements. Building and Equipment Design Features PART. Chapters 5 through 19
PART 3 Building and Equipment Design Features Chapters 5 through 19 Chapter 5 Fire Service Features No changes addressed Chapter 6 Building Services and Systems Chapter 7 Fire-Resistance-Rated Construction
More informationAutomation and Energy Efficiency of Industrial Refrigeration Systems
Automation and Energy Efficiency of Industrial Refrigeration Systems E360 Forum Chicago, IL October 5, 2017 Mike Micak Director of Sales Logix Controls Introduction Management thinker Peter Drucker was
More information