Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments
|
|
- Hector George
- 5 years ago
- Views:
Transcription
1 Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments Jason Huczek a, Marc Janssens a, Kentaro Onaka b, Stephen Turner c a SwRI, 6220 Culebra Road, San Antonio, TX 78238, USA b TEPCO, 1 Chome-1-2 Uchisaiwaicho, Chiyoda, Tokyo , Japan c Leidos, Inc., 301 Laboratory Road, Oak Ridge, TN 37830, USA ABSTRACT Southwest Research Institute (SwRI) recently conducted a research program focused on the effect of mechanical ventilation on smoke layer height for two geometric configurations (corridor and tee) and two fire sources. The primary objective of the research was to define performance metrics related to smoke layer height for relevant fire scenarios in order to specify a smoke extraction system suitable for a specific configuration in a building. A test enclosure was constructed, which consisted of a first floor that was 3 m wide, 10-m long and 3-m tall, and a second floor that was 3-m wide, 4-m long and 4-m tall. The first and second floor compartments were connected by a single hatch measuring 1 1-m. Mechanical exhaust was connected to the second floor compartment and exhaust flow rates between 0 and 1.11 m 3 /s were evaluated in the tests. Thermocouple trees, each outfitted with seven thermocouples at various elevations, were positioned at three locations in the test enclosure. The smoke layer height was calculated based on the vertical temperature measurements at the three locations. It was also estimated based on video documentation of visibility of an array of exit signs at the same nominal locations. These measurements are discussed and compared in detail in this paper. INTRODUCTION To meet the fire safety requirements in an industrial corridor-like structure, the building owner had to ensure that, in the event of a fire, the smoke layer will not descend below 1.5 m above the floor. To comply with this requirement, the building owner decided to provide mechanical ventilation through a ceiling hatch at one end of the structure and use Fire Dynamics Simulator (FDS) to determine the extraction rate that would be needed to meet the performance-based requirement. The FDS validation guide [1] indicates that, on average, the model slightly over-predicts the smoke layer depth (layer depth = ceiling height minus layer height) by only 3% (bias δ 1.03), with an uncertainty of ± 5% (relative standard deviation σ 0.05). However, these estimates are based for a large part on a comparison between model predictions and layer height measurements in naturally vented compartments. Moreover, the flow rates in the mechanically vented experiments were relatively low (1 10 air changes per hour). The building owner therefore decided to conduct a series of fourteen full-scale experiments to expand the validation range of the model to include high ventilation rates (15 29 air changes per hour).
2 FULL-SCALE EXPERIMENTAL DESIGN Fire Source Development Two different fire sources were specified by the client. The specified fire sizes had heat release rate (HRRs) of 106 kw (simulating a small cable fire ) and 317 kw (simulating a class A combustible fire ). Each fire source consisted of a propane burner with the center removed and through that opening a liquid spray of toluene was injected into the propane flame. A series of 25 tests were conducted to refine the two fire sources in terms of the propane/toluene ratio, nozzle size, etc. and a final eight tests were conducted to obtain repeatable soot yield and heat release rate values for each fire source. Table 1 summarizes the final parameters of the fire sources and Table 2 provides a few selected photographs of the test setup and burners. Fire HRR (kw) Soot Yield (g/g) Table 1. Fire Source Parameters Relative Effective Smoke Radiative Heat of Production Fraction Combustion Rate (m 2 (kj/g) (-) /MJ) Propane Mix Fraction (%) Toluene Mix Fraction (%) Fire HRR (kw) Table 2. Fire Source Testing Selected Photographs. Overall Test Setup Close-Up View of Fire Source Close-Up View of Test in Progress
3 For the 106-kW fire source, the spray nozzle used to discharge toluene was a Hago, 2.00 GPH, 80º, Hollow Cone. The discharge pressure was 9.6 bar and the mass flow rate was 1.91 g/s. For the 317-kW fire source, the spray nozzle used to discharge toluene was a Monarch, 0.65 GPH, 90º, Hollow Cone. The discharge pressure was 8.6 bar and the mass flow rate was 0.55 g/s. For the 106-kW fire source, the propane mass flow rate was 0.71 g/s and the heat release rate was 33 kw. For the 317-kW fire source, the propane mass flow rate was 6.46 g/s and the heat release rate was 300 kw. A more detailed discussion of the ignition source characterization can be found in [2]. Experimental Configuration The experiments were performed in two configurations, referred to as corridor and tee and shown in Figures 1 and 2, respectively. Figure 1. Corridor Configuration
4 Instrumentation Figure 2. Tee Configuration Three measurement stations were positioned downstream from the fire source location. At each station, there was a thermocouple tree (Type K, 20 AWG wire) and two sets of exits signs (illuminated and non-illuminated) at two heights, which were viewed by cameras through glass windows. The cameras were set up to view the exit signs as well as the length of the corridor(s). The camera locations are depicted in Figure 3. In the hatch corridor, two types of optical density measurements were taken. A set of seven commercial beam detectors (System Sensor Model 1224S) and four laser detectors (Edmund Optics components) were installed to measure optical density, and to a lesser extent, smoke layer height, in each experiment. The layout of each thermocouple tree as well as the beam and laser detectors is depicted in Figure 4. Figure 3. Camera Port Locations (Plan View)
5 Figure 4. Instrumentation Layout (Elevation View) The lasers were transmitted across the nominal 10 meters of the hatch corridor and the intensity was measured with a photodiode receiver that converts intensity to voltage. The laser sources are red in color and have a wavelength of 635 nm ± 5 nm. The photodiode receivers are 5-mm diameter Si photodiode detectors with an operating wavelength of µm and responsivity of / 10 7 Volts/Watt (depending on gain position). An in-situ, end-to-end calibration of the laser detector system was completed and the results are shown in Figure 5. The transmittance was measured after placing neutral density filters ranging from 0.5 to 3.0 OD at each laser beam height. The percent error between average measurements and neutral density filters is provided in the table and ranges from approximately 4 to 14%, but is very low over the range of interest for the compartment test measurements. Figure 5. Calibration of Laser Detector System in Hatch Corridor (10-m Pathlength)
6 Compartment Test Matrix Table 3 provides the details of the compartment test matrix. Test ID HRR (kw) Table 3. Compartment Test Matrix Flow Configuration m 3 /s (ACH*) Preliminary Tests Discussion Corridor 0.56 (15) Initial Tests to checkout Corridor 0.56 (15) instrumentation S Corridor S Corridor S Corridor S Corridor FS Corridor FS Corridor FS Corridor FS Tee FS Tee FS Tee FS Tee FS Tee FS Tee (0-22) 0.56 (15) (15-29) 1.11 (29) Final Tests 0.56 (15) 1.11 (29) 0 m 3 /s,0.28 m 3 /s, 0.56 m 3 /s, 0.83 m 3 /s, 7-10 minutes each Picked two flows from S-1, 15 minutes each 0.56 m 3 /s, 0.83 m 3 /s, 1.11 m 3 /s, 10 minutes each Pick two flows from S-3, 15 minutes each FS Tee Rerun of FS (15) *ACH=air changes per hour, based on total volume of test structure FULL-SCALE TEST RESULTS Cable fires, 106 kw Corridor and Tee Ventilation based on S-2, two flows, 15 minutes each Class A fires, 317 kw, Tee Ventilation based on S-4, two flows, 15 minutes each Table 4 provides a summary of the results for a few of the final tests (FS-1, FS-4, and FS7), including temperatures and optical densities measured at 12.5 minutes after flow is set for each test. Tables 5-7 provide selected graphical results for test FS-1, FS-4 and FS7, respectively.
7 Test ID FS-1 FS-4 FS-7 Table 4. Summary of Selected Final Test Results (FS-1, FS-4 and FS-7). Flow Amb. Tree Temp, 2.7m Duct Optical Density at m 3 /s Temp. ( C) Temp height in meters (ACH) ( C) Tr 1 Tr 2 Tr 3 C (15) (15) (29) ACH=Air Changes per Hour, Amb=Ambient, Temp=Temperature, Tr=Tree Table 5. Test FS-1 Results
8 Table 6. Test FS-4 Results Table 7. Test FS-7 Results
9 A few general test observations can be made from the data. At higher ventilation rates, a clear layer was observed in both corridors. At lower ventilation rates, a clear layer was observed in the fire corridor, but mixing was observed in the hatch corridor. At lower ventilation rates, multiple layers of smoke were observed: an area of darker smoke at the top above approximately m, a layer of lighter smoke with a depth of approximately m, and a clear layer below that elevation. This was consistently observed for all the tests. The measured optical densities for the simulated cable fires were higher than for the simulated class A combustible fires, as expected due to the higher soot yield for the former. The upper layer gas temperature for the simulated cable fires were lower than for the simulated class A fires, as expected due to the higher HRR for the latter. Test Photograph Arrays and Exit Sign Comparisons Still images from the cameras used during testing were collected for comparison to the FDS visualizations in Smokeview. Figure 6 shows an example of this type of photograph array for FS-1. Table 8 provides a comparison between FS-1 and FDS calculations for the same scenario and Tables 9-10 provide comparison images between the FS-1 and FS-4 experiments and FDS output. The details of the FDS modeling for this project are discussed in [3]. Figure 6. FS-1 Photo Array (Top: 0.83 m 3 /s, Bottom: 0.56 m 3 /s).
10 Table 8. FS-1 Visibility and FDS Results for Exit Sign Position No. 3 Test Series FDS Result Parameter FS1 (S2, FS1-FS3) Estimated Smoke Layer Height (m) at 0.83 m 3 /s Estimated Smoke Layer Height (m) at 0.56 m 3 /s m Illuminated Exit Sign Visible at 0.83 m 3 /s? Yes OD = /m 2.3-m Reflective Exit Sign Visible at 0.83 m 3 /s? No OD = /m 2.3-m Illuminated Exit Sign Visible at 0.56 m 3 /s? No OD = /m 2.3-m Reflective Exit Sign Visible at 0.56 m 3 /s? No OD = /m 1.5-m Illuminated Exit Sign Visible at 0.83 m 3 /s? Yes OD = /m 1.5-m Reflective Exit Sign Visible at 0.83 m 3 /s? Yes OD = /m 1.5-m Illuminated Exit Sign Visible at 0.56 m 3 /s? Yes OD = /m 1.5-m Reflective Exit Sign Visible at 0.56 m 3 /s? Yes OD = /m Test ID Table 9. FS-1 and FS-4 Visibility and FDS Results for Exit Sign Position No. 3 Test Result FDS Calculation 0.83 m 3 /s FS-1 FS-4
11 Test ID Table 10. FS-1 and FS-4 Visibility and FDS Results for Exit Sign Position No. 3 Test Result FDS Calculation 0.56 m 3 /s FS-1 FS-4 Comparison of Observed Smoke Layer Heights and FDS Calculations Figure 7 shows an example of layer height comparisons between experiments and FDS for both configurations and one of the fire sources. The first 900 seconds of each graph corresponds to an exhaust rate of 0.83 m 3 /s and the second 900 seconds of each graph corresponds to an exhaust rate of 0.56 m 3 /s. Figure 7. Selected Smoke Layer Comparison Results.
12 CONCLUSIONS The main conclusions from this research are as follows: The agreement between observed layer heights and calculated layer heights is better in the fire compartment, than in the adjoining compartments, which are closer to the mechanical exhaust extraction point. The mechanical exhaust introduces significant mixing between the layers, which greatly impairs the ability to use the thermocouple tree data to estimate the layer height close to the extraction point. The mixing effects appear to be more significant for the corridor configuration than the tee configuration. This is likely due to the closer proximity to the exhaust hatch of the fire in the tee configuration, as compared to the corridor configuration. The smoke layer height based on visual observations is generally and often significantly higher than the HGL height determined from vertical temperature profile data. ACKNOWLEDGEMENT The authors would like to express their gratitude to TEPCO for the financial support that made the work described in this paper possible. REFERENCES 1. McGrattan, Kevin, et. al., Fire Dynamics Simulator Technical Reference Guide Volume 3: Validation, NIST Publication 1018, National Institute of Standards and Technology, September 30, Huczek, J., et al., Full-Scale Fire Tests to Obtain Optical Density Data for Validation of Compartment Fire Models, Interflam 2016, London, England, July 4-6, Janssens, M., et al., Use of FDS to Comply with Performance-Based Requirements Based on Smoke Layer Height, 11 th Conference on Performance-Based Codes and Fire Safety Design Methods, Warsaw, Poland, May 23-25, 2016.
1.0 INTRODUCTION. Shaw Industries Group 2 SwRI Project No c
1.0 INTRODUCTION This report presents the results of a fire performance evaluation in accordance with the 2011 Edition of National Fire Protection Association (NFPA) Standard 265, Standard Methods of Fire
More informationSmoke Layer Height and Heat Flow through a Door
Smoke Layer Height and Heat Flow through a Door 2018 Smoke Layer Height and Heat Flow through a Door In this tutorial you will simulate a growing fire in the corner of a 5m x 5m room. The room has a 1m
More informationFIRE DYNAMICS IN FAÇADE FIRE TESTS: Measurement, modeling and repeatability
Proceedings of the International Conference in Dubrovnik, 15-16 October 2015 FIRE DYNAMICS IN FAÇADE FIRE TESTS: Measurement, modeling and repeatability Johan Anderson a, Lars Boström a, Robert Jansson
More informationZONE MODEL VERIFICATION BY ELECTRIC HEATER
, Volume 6, Number 4, p.284-290, 2004 ZONE MODEL VERIFICATION BY ELECTRIC HEATER Y.T. Chan Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China ABSTRACT Selecting
More informationAdvantages and Disadvantages of Fire Modelling
Advantages and Disadvantages of Fire Modelling Dr Guillermo Rein School of Engineering University of Edinburgh & Imperial College London Dr Guillermo Rein 9 May 2012 Chief Fire Officers Association Annual
More informationRADIATION BLOCKAGE EFFECTS BY WATER CURTAIN
, Volume 6, Number 4, p.248-254, 04 RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN C.L. Choi Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China ABSTRACT Water
More informationPREDICTING SMOKE DETECTOR ACTIVATION USING THE FIRE DYNAMICS SIMULATOR
PREDICTING SMOKE DETECTOR ACTIVATION USING THE FIRE DYNAMICS SIMULATOR VIJAY T. D SOUZA, JASON A. SUTULA, STEPHEN M. OLENICK*, WEI ZHANG and RICHARD J. ROBY Combustion Science & Engineering, Inc. Columbia,
More informationPolarized Light Scattering of Smoke Sources and Cooking Aerosols
Polarized Light Scattering of Smoke Sources and Cooking Aerosols Thomas Cleary, Amy Mensch National Institute of Standards and Technology, Gaithersburg, MD, USA Abstract Light scattering data was gathered
More informationSTUDY REPORT SR 292 (2013) B-RISK 2013 Software Benchmarking Examples. C.A. Wade
STUDY REPORT SR 292 (213) B-RISK 213 Software Benchmarking Examples C.A. Wade The work reported here was funded by BRANZ from the Building Research Levy. BRANZ 213 ISSN: 1179-6197 Preface This report presents
More informationCase Study 1 Underground Car Park
Case Study 1 Underground Car Park Dorota Brzezińska 1, Janusz Paliszek 2, Piotr Smardz 2, Renata Ollesz 1, Karol Kaczor 2 1 Lodz University of Technology, GRID - Lodz, 2 INBEPO Wroclaw, Poland Building
More informationValidation of a Smoke Detection Performance Prediction Methodology. Volume 3. Evaluation of Smoke Detector Performance
Validation of a Smoke Detection Performance Prediction Methodology Volume 3. Evaluation of Smoke Detector Performance Prepared by: James A. Milke and Frederick W. Mowrer University of Maryland Pravinray
More informationHealthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland
Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Paper ID 0141 ISBN: 978-83-7947-232-1 Prediction of exhaust gas stagnation in common corridor of apartments with gas water heater Takuro Nakamura
More informationAn experimental study of the impact of tunnel suppression on tunnel ventilation
An experimental study of the impact of tunnel suppression on tunnel ventilation Yoon J. Ko and George Hadjisophocleous Civil and Environmental Engineering, Carleton University 1125 Colonel By Drive, Ottawa,
More informationValidation of a Smoke Detection Performance Prediction Methodology. Volume 2. Large-scale room fire tests
Validation of a Smoke Detection Performance Prediction Methodology Volume 2. Large-scale room fire tests Prepared by: Frederick W. Mowrer and James A. Milke University of Maryland Pravinray Gandhi Underwriters
More informationSmoke Layer Height and Heat Flow through a Door
Smoke Layer Height and Heat Flow through a Door 2017 Smoke Layer Height and Heat Flow through a Door In this tutorial you will simulate a growing fire in the corner of a 5m x 5m room. The room has a 1m
More informationTest One: The Uncontrolled Compartment Fire
The University of Edinburgh BRE Centre for Fire Safety Engineering One Day Symposium on The Dalmarnock Fire Tests: Experiments & Modelling Test One: The Uncontrolled Compartment Fire Cecilia Abecassis
More informationSOUTHWEST RESEARCH INSTITUTE
SOUTHWEST RESEARCH INSTITUTE 6220 CULEBRA ROAD 78238-5166 P.O. DRAWER 28510 78228-0510 SAN ANTONIO, TEXAS, USA (210) 684-5111 WWW.SWRI.ORG CHEMISTRY AND CHEMICAL ENGINEERING DIVISION FIRE TECHNOLOGY DEPARTMENT
More informationTech Notes. TESTING PROTOCOL Fire Retardant Gel Coats. INTERPLASTIC CORPORATION Thermoset Resins Divison ISSUE 5
INTERPLASTIC CORPORATION Thermoset Resins Divison ISSUE 5 5 Tech Notes TESTING PROTOCOL Fire Retardant Gel Coats Issue Date: 4/22/2010 Document ID: TN-TS-05A 2010 Interplastic Corporation Testing Protocol
More informationSmoke Transport and FDS Validation
Smoke Transport and FDS Validation DANIEL GOTTUK, CHRISTOPHER MEALY and JASON FLOYD Hughes Associates, Inc. 361 Commerce Drive, Suite 817 Baltimore, Maryland 21227 ABSTRACT A 26 Fire Protection Research
More informationWATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS
WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS Jukka Vaari 1, Amit Lior 2 1 2 VTT Technical Research Centre of Finland, Espoo, Finland Marioff Corporation Oy, Vantaa,
More informationOverview of the PRISME project Technical Description and Main Outcomes
OECD PRISME Project on Fire Propagation Final Seminar Overview of the PRISME project Technical Description and Main Outcomes Audouin L., Rigollet L., Pretrel H., Le Saux W. IRSN / ETIC Summary (1) Context
More informationIntertek. REPORT NUMBER: SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: November 19, 2008
Intertek I 0:: o D.. W 0:: I en w I REPORT NUMBER: 3161466SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: EVALUATION CENTER Intertek Testing Services NA Inc. 16015 Shady Falls Rd. Elmendorf,
More informationPERFORMANCE-BASED FIRE PROTECTION OF NUCLEAR PLANTS
Hong Kong Polytechnic University CPD Lecture, August 29, 2014 PERFORMANCE-BASED FIRE PROTECTION OF NUCLEAR PLANTS Marc L. Janssens, Ph.D., FSFPE Senior Engineer Southwest Research Institute 6220 Culebra
More informationA Comparison of Aspirated Smoke Detectors
A Comparison of Aspirated Smoke Detectors Honeywell FAAST Detectors and Xtralis VESDA VLF (Laserfocus) Conducted by Packer Engineering, Inc And The Fire Testing and Evaluation Center at The University
More informationAspirating Gas Detection CFD Modelling Predicts Application Performance
Aspirating Gas Detection CFD Modelling Predicts Application Performance Yun Jiang Xtralis, Bentleigh East, Australia Claudio Groppetti Xtralis, Avon, MA, USA Abstract Historically gas detection has utilized
More informationFire Scenario Influence of Material of Boundary Condition on Results
Fire Scenario Influence of Material of Boundary Condition on Results HUGHES ASSOCIATES EUROPE, srl FIRE SCIENCE & ENGINEERING Luciano Nigro Andrea Ferrari Elisabetta Filippo Hughes Associates Europe srl
More informationMethod for testing the suppression performance of fire suppression systems installed in engine compartments of buses and coaches
2014-09-19 SP Method 4912 Method for testing the suppression performance of fire suppression systems installed in engine compartments of buses and coaches 2014-09-19 page 2 (17) Copyright This test method
More informationRESEARCH TECHNICAL REPORT. SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale Fire Tests in Rack Storage
RESEARCH TECHNICAL REPORT SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale Fire Tests in Rack Storage SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale
More informationCAN THE CONE CALORIMETER BE USED TO PREDICT FULL SCALE HEAT AND SMOKE RELEASE CABLE TRAY RESULTS FROM A FULL SCALE TEST PROTOCOL?
CAN THE CONE CALORIMETER BE USED TO PREDICT FULL SCALE HEAT AND SMOKE RELEASE CABLE TRAY RESULTS FROM A FULL SCALE TEST PROTOCOL? Marcelo M. Hirschler GBH International, USA ABSTRACT The results of three
More informationThe first tunnel fire. Benefits of fire
Benefits of fire suppression Quantifying the effects of suppression on energy release. This article by Fathi Tarada, managing director of fire safety, risk management, ventilation and CFD consultant Mosen
More informationInvestigating the Effects of Sprinkler Sprays on Fire-Induced Doorway Flows: A Two-Part Study. Jeremiah Crocker and Dr. Bin Xiao New Technology Team
Jeremiah Crocker and Dr. Bin Xiao New Technology Team Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved. The products and specifications published herein are for general evaluation
More informationUsing FDS Modelling to Establish Performance Criteria for Water Mist Systems on Very Large Fires in Tunnels
Using FDS Modelling to Establish Performance Criteria for Water Mist Systems on Very Large Fires in Tunnels Jack R. Mawhinney, P. Eng., FSFPE Javier J. Trelles, Ph.D. Authors & acknowledgement J. R. Mawhinney
More informationValidation of a Smoke Detection Performance Prediction Methodology. Volume 4. Evaluation of FDS Smoke Detection Prediction Methodology
Validation of a Smoke Detection Performance Prediction Methodology Volume 4. Evaluation of FDS Smoke Detection Prediction Methodology Prepared by: Frederick W. Mowrer and James A. Milke University of Maryland
More informationClemens Felsmann 1, Jean Lebrun 2, Vincent Lemort 2 and Aad Wijsman 3 ABSTRACT INTRODUCTION METHODOLOGY
Eleventh International IBPSA Conference Glasgow, Scotland July 27-30, 2009 TESTING AND VALIDATION OF SIMULATION TOOLS OF HVAC MECHANICAL EQUIPMENT INCLUDING THEIR CONTROL STRATEGIES. PART II: VALIDATION
More informationRecent BRANZFIRE enhancements and validation
Recent BRANZFIRE enhancements and validation Michael Spearpoint University of Canterbury Summary BRANZFIRE is a multi-compartment fire zone model that has been under development since 1996 predominately
More informationLink loss measurement uncertainties: OTDR vs. light source power meter By EXFO s Systems Engineering and Research Team
Link loss measurement uncertainties: OTDR vs. light source power meter By EXFO s Systems Engineering and Research Team INTRODUCTION The OTDR is a very efficient tool for characterizing the elements on
More informationA STUDY ON THE BEHAVIOR OF STEAM CONDENSATION IN U-SHAPED HEAT TUBE
A STUDY ON THE BEHAVIOR OF STEAM CONDENSATION IN U-SHAPED HEAT TUBE Satoru Ito 1, Keisuke Tsukada 1, Nobuyoshi Tsuzuki 2, Takao Ishizuka 3 and Hiroshige Kikura 3 1 Department of nuclear Engineering, Graduate
More informationLaser Safety and Classification Full Version (CA-1110) Advanced Version (CA-1111) Basic Version (CA-1112)
Laser Safety and Classification Full Version (CA-1110) Advanced Version (CA-1111) Basic Version (CA-1112) The spectral range of lasers vary from a few nanometer up to some hundred micrometers and is mostly
More informationSmoke Alarm Research at NIST
Smoke Alarm Research at NIST Thomas G. Cleary Fire Research Division National Institute of Standards and Technology Smoke Alarm Summit March 31, 2015 Outline Supporting ANSI/UL 217 268 Task Group on adding
More informationSmoke Alarm Research at NIST
Smoke Alarm Research at NIST Thomas G. Cleary Fire Research Division National Institute of Standards and Technology March 27, 2014 Outline Kitchen fire and nuisance alarm experiments (CPSC funded) New
More informationCFD Model of a Specific Fire Scenario
16 th Australasian Fluid Mechanics Conference Crown Plaza, Gold Coast, Australia 2-7 December 27 CFD Model of a Specific Fire Scenario D. Mackay, T. Barber and E. Leonardi School of Mechanical and Manufacturing
More informationFigure 1. Structure Used For the Simulations.
OVERVIEW: Vent, Enter, Search (VES) is one of the most talked about tactics in the fire service today. When used correctly, its positive impact can be measured by the lives it saves. The VES method is
More information5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea
5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea PRACTICAL APPLICATIONS OF FIRE MODELING IN INDUSTRIAL APPLICATIONS By James M. Dewey, Advisor Risk Management
More informationRESEARCH TECHNICAL REPORT. SMART Sprinkler Protection for Highly Challenging Fires Phase 1: System Design and Function Evaluation
RESEARCH TECHNICAL REPORT SMART Sprinkler Protection for Highly Challenging Fires Phase : System Design and Function Evaluation SMART Sprinkler Protection for Highly Challenging Fires Phase : System Design
More informationIndicative hoarding fire experiment. Prepared for: London Fire Brigade. 21 May 2014 Client report number
Indicative hoarding fire experiment Prepared for: London Fire Brigade 21 May 2014 Client report number 292366 1 Hoarding fire demonstration Prepared on behalf of BRE Fire and Security by Name Dr Sung-Han
More informationNUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM
, Volume 11, Number 2, p.43-48, 2012 NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM Q. Kui Institute of Building Fire Research, China Academy of Building Research, Beijing,
More informationChapter 17, Initiating Devices
Chapter 17, Initiating Devices Summary. Chapter 17 was Chapter 5 in NFPA 72-2007. The term authority having jurisdiction is replaced in some sections by the term other governing laws, codes, or standards.
More informationABSTRACT. Stephen Kerber, Master of Science, Dr. James Milke, Fire Protection Engineering
ABSTRACT Title of Document: EVALUATION OF THE ABILITY OF FIRE DYNAMICS SIMULATOR TO SIMULATE POSITIVE PRESSURE VENTILATION IN THE LABORATORY AND PRACTICAL SCENARIOS Stephen Kerber, Master of Science, 2005
More informationHeat and Smoke Release of a Ceiling-Installed Speaker
WFCi Project #12051 Heat and Smoke Release of a Ceiling-Installed Speaker Indicative testing conducted in accordance with the test methodology described in UL 2043, Fire test for heat and visible smoke
More informationFire and smoke management in a uni-directional road tunnel for a congested traffic condition
Fire and smoke management in a uni-directional road tunnel for a congested traffic condition Y Liu, J Munro Parsons Brinckerhoff Australia B Dandie Thiess Pty Ltd., Australia ABSTRACT Emergency smoke ventilation
More informationResults from a Full-Scale Smoke Alarm Sensitivity Study
Results from a Full-Scale Smoke Alarm Sensitivity Study Thomas Cleary Building and Fire Research Laboratory National Institute of Standards and Technology Gaithersburg, MD (301) 975-6858 thomas.cleary@nist.gov
More informationCOSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN
COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN Presented by Ian Levine June, 2016 Photo courtesy of Google Maps PRESENTATION OVERVIEW BUILDING
More informationRecent Advances in Fire Suppression Modeling Issues & Perspectives of Fire Safety Engineering Applications
Recent Advances in Fire Suppression Modeling Issues & Perspectives of Fire Safety Engineering Applications Pianet Grégoire Studies and modelling section manager Fire and Environmental Department, CNPP
More informationExperiments to Validate the NRCC Smoke Movement Model for Fire Risk-Cost Assessment
Experiments to Validate the NRCC Smoke Movement Model for Fire Risk-Cost Assessment AKIHIKO HOKUGO Building Research Institute Ministry of Construction Tatehara I, Tsukuba-City 305, Japan DAVID YUNG and
More informationSprinkler Protection for Cloud Ceilings Phase 2: Small Area Clouds
Sprinkler Protection for Cloud Ceilings Phase 2: Small Area Clouds Final Report Prepared by: Dr. Jason Floyd Steve Strege Matt Benfer Hughes Associates, Inc. Baltimore, MD August 214 Fire Protection Research
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Internal Combustion Engines
More informationFire Investigation in Italian Waste Treatment Plant: lessons learned and future development
Fire and Evacuation Modeling Technical Conference (FEMTC) 2018 Gaithersburg, Maryland, October 1-3, 2018 Fire Investigation in Italian Waste Treatment Plant: lessons learned and future development Ing.
More informationEnergy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates
Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2014 Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for
More informationSTUDY ON THE REACTION TO FIRE OF MEDIUM VOLTAGE CABLES SYSTEMS
STUDY ON THE REACTION TO FIRE OF MEDIUM VOLTAGE CABLES SYSTEMS Neus GENERÓ, Juan de Dios MARTÍNEZ, Jacint ROVIRA, Grupo General Cable Sistemas, (Spain), ngenero@generalcable.es, jdmartinez@generalcable.es,
More informationAnnex B Plenum Spaces
Annex B Plenum Spaces Introduction Considerable work has been undertaken in characterising fire travel through plenum spaces via cables. In the context of this study the term plenum has been used to describe
More informationAC : A COLLECTIVE UNDERGRADUATE CLASS PROJECT RECONSTRUCTING THE SEPTEMBER 11, 2001 WORLD TRADE CENTER FIRE
AC 2007-2770: A COLLECTIVE UNDERGRADUATE CLASS PROJECT RECONSTRUCTING THE SEPTEMBER 11, 2001 WORLD TRADE CENTER FIRE Andre Marshall, University of Maryland James Quintiere, University of Maryland American
More informationNew European Cable Testing and Classification
New European Cable Testing and Classification THE BENCHMARK IN FIRE TESTING New European Cable Testing and Classification Cables will be tested using 5 test methods, and classified by extending the provisions
More informationTHEORY OR OPERATION 2 SENSOR UNIT - MECHANICAL 6 SENSOR UNIT - ELECTRICAL 8 CONTROL UNIT - MECHANICAL 9 CONTROL UNIT - ELECTRICAL 9 OPTIONS 11
Table of Contents INTRODUCTION 1 THEORY OR OPERATION 2 DESCRIPTION 5 SENSOR UNIT - MECHANICAL 6 SENSOR UNIT - ELECTRICAL 8 CONTROL UNIT - MECHANICAL 9 CONTROL UNIT - ELECTRICAL 9 SPECIFICATIONS 10 OPTIONS
More informationFULL-SCALE FIRE TESTS OF A TWO-STORY CROSS-LAMINATED TIMBER STRUCTURE
FULL-SCALE FIRE TESTS OF A TWO-STORY CROSS-LAMINATED TIMBER STRUCTURE Laura E. Hasburgh 1, Samuel L. Zelinka 1, Keith J. Bourne 1, David R. Tucholski 2, Jason P. Ouellette 2 ABSTRACT: There is a current
More informationFire propagation over combustible exterior facades exposed to intensified flame in Japan
MATEC Web of Conferences 46, 02002 (2016) DOI: 10.1051/matecconf/20164602002 C Owned by the authors, published by EDP Sciences, 2016 Fire propagation over combustible exterior facades exposed to intensified
More informationJ. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441
J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441 Response-Time Comparisons of Ionization and Photoelectric/Heat Detectors 1. Introduction Despite
More informationCOMPARISON OF CFD MODELLING WITH FIRE TESTS Comparison of CFD Modelling with Results of Full Scale Compartment Fire Tests in a Residential Unit
Application of Structural Fire Engineering, 19-20 April 2013, Prague, Czech Republic COMPARISON OF CFD MODELLING WITH FIRE TESTS Comparison of CFD Modelling with Results of Full Scale Compartment Fire
More informationCLT Adhesive Tests in Support of Mass Timber Buildings
CLT Adhesive Tests in Support of Mass Timber Buildings DES604 Jason Smart, P.E. Manager, Engineering Technology American Wood Council Sam Francis, C.B.O. Senior Director, National Programs American Wood
More informationHow to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs
How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs 1 ABSTRACT Noureddine Benichou and Ahmed H. Kashef * Institute for Research in Construction National Research Council of Canada
More informationA Priori Modelling of Fire Test One
A Priori Modelling of Fire Test One Authorship: Brave Users Guillermo Rein, José L. Torero, Wolfram Jahn, Jamie Stern-Gottfried, Noah L. Ryder, Sylvain Desanghere, Mariano Lázaro, Frederick Mowrer, Andrew
More information1.0 INTRODUCTION 2.0 CLASSIFICATION CRITERIA
1.0 INTRODUCTION This report presents the results of an investigation of the external fire resistance characteristics of the VELUX FCM Deck Mounted Skylight roof covering system in general accordance with
More informationSBI. Single Burning Item - EN THE BENCHMARK IN FIRE TESTING
SBI Single Burning Item - EN 13823 THE BENCHMARK IN FIRE TESTING FTT Single Burning Item (SBI) The importance of the SBI The European Construction Products Directive requires that all European Member states
More informationWildland fire phenomenology experiments:
Wildland fire phenomenology experiments: 2001-2002 RIT: Bob Kremens Stef VanGorden Andy Fordham Bryce Nordgren Dave Pogolarza Adam Cisz RMSC: Dan Latham Colin Hardy Brett Butler We plan to measure unknown
More informationFire Suppression Performance of Manually Applied CAF and Other Water Based System
Fire Suppression Performance of Manually Applied CAF and Other Water Based System Andrew Kim and George Crampton Fire Suppression Research and Applications A Technical Working Conference (SUPDET2012) Outline
More informationNUMERICAL SIMULATION OF THE NEW SOUTH WALES FIRE BRIGADE COMPARTMENT FIRE BEHAVIOUR TRAINING TEST CELL
, Volume 9, Number 4, p.154-162, 7 NUMERICAL SIMULATION OF THE NEW SOUTH WALES FIRE BRIGADE COMPARTMENT FIRE BEHAVIOUR TRAINING TEST CELL D. Mackay and T. Barber School of Mechanical and Manufacturing
More informationNEXT GENERATION OF ELECTRICAL LADLE HEATERS: A CASE STORY. Marcus Andersson. Sandvik Heating Technology, Hallstahammar, Sweden ABSTRACT
NEXT GENERATION OF ELECTRICAL LADLE HEATERS: A CASE STORY Marcus Andersson Sandvik Heating Technology, Hallstahammar, Sweden ABSTRACT Sandvik is now introducing its next generation of Kanthal electrical
More informationPotential Impact of New UL Fire Test Criteria
Potential Impact of New UL Fire Test Criteria Thomas G. Cleary Fire Research Division National Institute of Standards and Technology March 7, 2014 Outline Background Recent History Task Group Progress
More informationLow Global Warming Refrigerants For Commercial Refrigeration Systems
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Low Global Warming Refrigerants For Commercial Refrigeration Systems Samuel
More informationAn Analysis of Compartment Fire and Induced Smoke Movement in Adjacent Corridor
2C-1 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea An Analysis of Compartment Fire and Induced Smoke Movement in Adjacent Corridor Soo-Young Kim *, Eung-Sik
More informationASSESSING THE FIRE PERFORMANCE OF ELECTRIC CABLES (FIPEC)
ASSESSING THE FIRE PERFORMANCE OF ELECTRIC CABLES (FIPEC) P. Van Hees and J. Axelsson, SP Sweden, S. J. Grayson and A. M. Green, Interscience Communications UK, H Breulet, ISSeP Belgium and U Vercellotti,
More informationStudy of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke Exhaust Fan
Open Journal of Fluid Dynamics, 2017, 7, 205-218 http://www.scirp.org/journal/ojfd ISSN Online: 2165-3860 ISSN Print: 2165-3852 Study of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke
More information"HC" AIRFLO. In-duct firing line burner
"HC" AIRFLO In-duct firing line burner -.- High heat release up to.5 MW per unit of burner length (05 mm) Clean combustion with low CO and NO x emission levels Minimal process air pressure drops locally
More informationBuilding and Characterizing 14GHz InGaAs Fiber Coupled Photodiodes
Building and Characterizing 14GHz InGaAs Fiber Coupled Photodiodes Gabrielle Inglis Advisor: Robert Boni Laboratory for Laser Energetics University of Rochester Summer High School Research Program 200
More informationCALIBRATION HOW IT WORKS
HIGH POWER SOLUTIONS POWER DETECTORS ENERGY DETECTORS At Gentec-EO, we understand that the essence of our business since over 45 years has been delivering accuracy. There are no half measures: it either
More informationConceptual Design of a Better Heat Pump Compressor for Northern Climates
Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 1976 Conceptual Design of a Better Heat Pump Compressor for Northern Climates D. Squarer
More informationSIMULATION OF A COMPARTMENT FLASHOVER FIRE USING HAND CALCULATIONS, ZONE MODELS AND A FIELD MODEL
Reference : Spearpoint M J, Mowrer F W, McGrattan K. Simulation of a single compartment flashover fire using hand calculations, zone models and a field model. Proc. 3 rd International Conference on Fire
More informationTEST REPORT. Report No.: D Rendered to: 3M COMPANY St. Paul, Minnesota
Architectural Testing TEST REPORT Report No.: D7913.05-121-24 Rendered to: 3M COMPANY St. Paul, Minnesota PRODUCT TYPE: Window Film SERIES/MODEL: 3M Scotchshield Ultra 800 TEST METHOD: ASTM E 84-11a, Standard
More informationHealthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland
Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Paper ID 0320 ISBN: 978-83-7947-232-1 The Analysis of the Air Velocity Distribution above the Trench Heater with Natural Convection Mariusz
More informationMeasurements Conducted Heat release rate (HRR) was measured in all tests. HRR measurements were conducted under the 3 m by 3 m calorimeter
Table A-1. Tests Conducted and Ambient Conditions at Beginning of Each Test Notes: PAL stands for pallet and CRA ( Community Risk Assessment ) is the designator for the configuration of pallets burned
More informationFABRITRAK SYSTEMS, INC. FIRE TEST REPORT
FABRITRAK SYSTEMS, INC. FIRE TEST REPORT SCOPE OF WORK ASTM E84 TESTING ON POLYESTER INFILL REPORT NUMBER H5200.01-121-24 TEST DATE 08/31/17 ISSUE DATE 09/20/17 RECORD RETENTION END DATE 08/31/21 PAGES
More informationUsing Smoke Obscuration to Warn of Pre-Ignition Conditions of Unattended Cooking Fires
Using Smoke Obscuration to Warn of Pre-Ignition Conditions of Unattended Cooking Fires Erik Johnsson, Mariusz Zarzecki National Institute of Standards and Technology, Gaithersburg, MD, USA Abstract A series
More informationMINISTERIO DE FOMENTO
Dirección General de Servicios de Alta Velocidad - Larga Distancia Real Scale Fire Tests in High-Speed Trains Convocatoria de Concesión de Ayudas a Agrupaciones o Consorcios de Investigación para la realización
More informationSTACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING
STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING H. Kotani, R. Satoh, T. Yamanaka Dept. of Architectural Engineering, School of Engineering, Osaka University, Osaka, Japan ABSTRACT The purpose
More informationSome Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps
More informationASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER
, Volume 9, Number 1, p.38-58, 2007 ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER C.W. Leung and W.K. Chow Department of Building Services Engineering, The Hong Kong
More informationA Study on the 2-D Temperature Distribution of the Strip due to Induction Heater
, pp.1-5 http://dx.doi.org/10.14257/astl.2015.90.01 A Study on the 2-D Temperature Distribution of the Strip due to Induction Heater Jong-Hyun Lee 1, Jin-Taek Kim 1, Sung-Hyuk Lim 2, Do-Gyun Jung 2, Hyeong-Jin
More informationConsiderations in the Design of Smoke Management Systems for Atriums
Construction Technology Update No. 48 Considerations in the Design of Smoke Management Systems for Atriums by G.D. Lougheed This Update discusses the use of an engineered approach to the design of smoke
More informationctbuh.org/papers Fire Engineering the Tallest Building in the Historic City of Manchester, UK Title:
ctbuh.org/papers Title: Authors: Subjects: Keywords: Fire Engineering the Tallest Building in the Historic City of Manchester, UK Dean McGrail, Associate Director, WSP Group Simon Lay, Technical Director,
More informationDeveloping a Fire Test Strategy for Storage Protection Under Sloped Ceilings
Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings Justin A. Geiman, Noah L. Ryder Fire & Risk Alliance, Rockville, MD, USA André W. Marshall Custom Spray Solutions, Silver Spring,
More informationUnderstanding total measurement uncertainty in power meters and detectors
Understanding total measurement uncertainty in power meters and detectors Jay Jeong, MKS Instruments. Inc. INTRODUCTION It is important that users of calibrated power meters and detectors understand and
More information