Doc. No.: OMPII.DOC Rev. 2 Written By: Raj Patel Checked By: AJC Approved By: JBJ Date: 03/05/05

Size: px
Start display at page:

Download "Doc. No.: OMPII.DOC Rev. 2 Written By: Raj Patel Checked By: AJC Approved By: JBJ Date: 03/05/05"

Transcription

1 Doc. No.: OMPII.DOC Rev. 2 Written By: Raj Patel Checked By: AJC Approved By: JBJ Date: 03/05/05 PRESCIENT II GAS EXTINGUISHANT CONTROL PANEL INSTALLATION, OPERATION & MAINTENANCE MANUAL Page 1 of 27

2 CONTENTS 1. INTRODUCTION GENERAL DESCRIPTION FUNCTIONAL DESCRIPTION DETECTION ZONES (ZONE 1, ZONE 2 & AUX.ZONE) MANUAL RELEASE ZONE (MREL ZONE) ALARM CIRCUITS (ALARM 1 & ALARM 2) ACTUATOR CIRCUITS (ACT 1 & ACT 2) REPEATER OUTPUTS (REPEATER 1, 2, AZ,MZ, FLT & EV) AUXILIARY 28 VDC SUPPLY (AUX SUP + & ) STATUS LAMP UNIT REMOTE INPUTS CLEAN RELAY CONTACTS INTERNAL STANDBY BATTERIES FUNCTION ENABLE/DISABLE SWITCHES FAULT LEDS INTERNAL BUZZER DISPLAY BOARD GENERAL DISPLAY BOARD VISUAL INDICATIONS DISPLAY BOARD USER CONTROLS TECHNICAL SPECIFICATION STANDBY BATTERY REQUIREMENTS BATTERY CAPACITY CALCULATION BATTERY CHARGING DETECTOR COMPATIBILITY PANEL INSTALLATION INSTALLATION PROCEDURE COMMISSIONING PROCEDURE SYSTEM MAINTENANCE OVERVIEW WEEKLY TEST ROUTINE ELECTRONIC ENDOFLINE TERMINATORS INSTALLATION COMMISSIONING PCB LAYOUT DIAGRAM PANEL EXPLODED VIEW CONNECTION DIAGRAM...27 Page 2 of 27

3 1. Introduction Prescient II Gas Extinguishant Control Panel Installation and Operation The Prescient II Gas Extinguishant Control Panel is a standalone panel intended for use with gas extinguishing systems. The panel monitors three zones or areas for fire conditions and gives an appropriate audible and visual indication. Zones 1 & 2 are used for coincident detection and can be used to automatically release the extinguishing gas. The third zone is an auxiliary zone & only provides an alarm indication. The panel also provides a facility for initiating the release of extinguishing gas manually. 2. General Description The Panel is housed in a metal enclosure with a Manual Release facility mounted on the front. The display board provides the following functions: 1) Visual Indication of panel status via LEDs. 2) Buttons for User Control. The main control board inside the panel provides the following functions: 1) Three fully monitored Detection zones. 2) One fully monitored Manual Release zone. 3) Two fully monitored Bell circuits. 4) Two fully monitored Actuator circuits. 5) Repeater outputs for: (i) (ii) (iii) (iv) Zonal Fire Detected Manual Release Zone Activated Panel Fault Occurred Evacuate Operated 6) An Auxiliary 28VDC supply output. 7) Outputs to drive an external Status Lamp Unit. 8) Remote inputs for: (i) (ii) (iii) (iv) (v) (vi) (vii) (viii) Evacuate Silence Alarms System Reset Lockoff switch Low Pressure Pressure Switch Timer Hold Emergency Abort 9) Clean Relay contacts for: (i) (ii) (iii) (iv) (v) (vi) First Stage Operated Second Stage Operated Auxiliary Reset Auxiliary Fire Auxiliary Fault System Discharged 10) Terminals for Internal Standby Batteries 11) Function Enable/Disable Switches 12) Power Fault LED 13) Display Fault LED 14) Earth Fault LED 15) Alarm Fault LED 16) Lock Off Fault LED 17) Emergency Abort Input Fault LED Page 3 of 27

4 18) Low Pressure Fault LED 19) Mains Fault LED 20) Internal Fault LED 21) Battery Charger Fault LED 22) Output OK LED 23) Internal Buzzer 3. Functional Description Note: Please refer to Section 10 for PCB layout and Section 12 for Connection Diagram. 3.1 Detection Zones (ZONE 1, ZONE 2 & AUX.ZONE) Three detection zone circuits are provided. They are monitored for Open Circuit Fault, Short Circuit Fault and Alarm (Fire). A maximum of 20 active detectors are allowed on each zone (the actual number is dependent on the type of detector used, see section 6). Any number of passive devices may be used e.g. Manual Call Points. Zones 1 and 2 are normally used together to produce First and Second Stage fire alarms, resulting in automatic extinguishant discharge ( Double Knock Zones). Zone 3 is an auxiliary detection zone and is not used to automatically discharge the extinguishant. The Display Board has Fire and Fault LEDs for each of the zones. The Display Board also provides User Controls for disabling the monitoring of individual zones. 3.2 Manual Release Zone (MREL ZONE) The fourth detection zone is used as a Manual Release zone. It is monitored for Open Circuit Fault, Short Circuit Fault and Alarm. It is classed as a Second Stage alarm in both automatic and manual modes, and initiates the release of extinguishant when activated. This zone should only have manually operated devices connected to it e.g. Manual Call Points. The Display Board has Fire and Fault LEDs for the Manual Release Zone. The Manual Release zone cannot be disabled by the user. 3.3 Alarm Circuits (ALARM 1 & ALARM 2) Two fully monitored alarm circuits are provided. They are monitored for Open Circuit and Short Circuit faults. They are rated at 1 Amp (fused), 28 Volts DC each. An amber LED on the main Control Board is illuminated for any fault conditions an the Alarm Circuits. Note: The circuits are reversepolarity monitored. The PCB terminals are marked for the active polarity. Ensure that all connected devices are polarised. 3.4 Actuator Circuits (ACT 1 & ACT 2) Two fully monitored actuator circuits are provided. They are monitored for Open Circuit and Short Circuit faults. They are rated at 1 Amp (fused), 28 Volts DC each. An amber LED on the Display Board is illuminated for any fault conditions on the Actuator Circuits. Note: The circuits are reversepolarity monitored. The PCB terminals are marked for the active polarity. Ensure that all connected devices are polarised. 3.5 Repeater Outputs (REPEATER 1, 2, AZ, MZ, FLT & EV) Each repeater output consists of an Open Collector transistor driver capable of sinking up to 100mA. One output is provided for each of the detection zones to indicate zone alarm. In addition, one output is provided to indicate a panel fault and one output is provided to indicate the operation of manual/remote evacuate. 3.6 Auxiliary 28 VDC Supply (AUX SUP + & ) The panel provides an auxiliary d.c. power supply output for connection to ancillary equipment. The output is rated at 1 Amp (fused), 28 Volts D.C. 3.7 Status Lamp Unit The panel provides a 28 Volt D.C. output (28VS) rated at 0.5 Amp (fused) to provide power to a Remote Status Lamp Unit. Page 4 of 27

5 Outputs for AUTO (AS), MANUAL (MS) and DISCHARGED (DIS) are provided via relays on the panel. These outputs are normally open and switch to 0V. Each output is rated at 250mA. Outputs for TIMER HELD (T/H) and EMERGENCY ABORT (A) are provided via Open Collector transistor drivers, rated at 100mA each. Note: Total loading of all five outputs should not exceed 500mA. 3.8 Remote Inputs Remote Evacuate (EVAC) The panel can accept a 0V input on the Remote Evacuate terminal. This will cause the alarm circuits to operate continuously until the input is removed Silence Alarms (RSIL) The panel can accept a 0V input on the Remote Silence Alarms terminal. This will cause the alarm circuits to deactivate if they are activated for a fire condition. If the alarm circuits are activated by an Evacuate signal and no fire signals are present then this input will have no effect System Reset (RST) The panel can accept a 0V input on the Remote System Reset terminal. This will reset the panel indications to normal and remove the power supply to the zones to clear any detectors in a fire condition. This input is only accepted if the alarm circuits have already been silenced for a fire condition LockOff Switch (LOFF) The Lockoff input consists of two terminals; one input terminal and one 0V terminal. This input monitors for short circuits with a 680R endofline monitoring resistor. A short circuit fault is indicated by an amber Lock Off Fault LED on the internal control board. The input is normally closed. An open circuit condition disconnects the 680R resistor resulting in an activation of the input. In the active state the panel is placed in manual mode and the green Manual LED on the display board pulses. Operation of the Auto/Manual button on the display board has no affect while the LockOff input is active Low Pressure Fault (LP) The Low Pressure Fault input consists of two terminals; one input terminal and one 0V terminal. This is a fully monitored input with a 3K9 endofline monitoring resistor. An open or short circuit fault is indicated by an amber Low Pressure Fault LED on the internal control board. The input is normally open and requires a 680R resistor across the circuit for the active state. An active condition illuminates the amber Low Pressure Fault LED on the display board Pressure Switch (PS) The Pressure Switch input consists of two terminals; one input terminal and one 0V terminal. This is a fully monitored input with a 3K9 endofline monitoring resistor. An open or short circuit fault will be indicated by an amber Pressure Switch Fault LED on the display board. The input is normally open and requires a 680R resistor across the circuit for the active state. An active condition indicates Gas Discharged, illuminating the red Gas Discharged LED, red First Stage LED and red Second Stage LED on the display Remote Timer Hold (T/H) The Remote Timer Hold input consists of two terminals; one input terminal and one 0V terminal. This is a fully monitored input with a 3K9 endofline monitoring resistor. An open or short circuit fault is indicated by a Remote Hold Fault LED on the display board. The input is normally open and requires a 680R resistor across the circuit for the active state. An active condition illuminates the amber Timer Held LED on the display. It also resets and holds the extinguishant release timer if running. NOTE: A maximum of 3 Remote Timer Hold switches may be connected. If more than 3 switches are operated simultaneously then a short circuit fault will be detected and the Timer Hold function will be cancelled. Use only nonlatching switches which return to open contacts when the switch is released Emergency Abort Input (AI) The Emergency Abort Input consists of two terminals; one input terminal and one 0V terminal. This is a fully monitored input with a 3K9 endofline monitoring resistor. An open or short circuit fault is indicated by an Abort Input Fault LED on the internal control board. The input is normally open and requires a 680R resistor across the circuit for the active Page 5 of 27

6 state. An active condition illuminates the Emergency Abort LED on the display and prevents the release of extinguishant until the panel is reset. Page 6 of 27

7 3.9 Clean Relay Contacts First Stage (FIRST STAGE) The First Stage Relay is a double pole double throw relay and is energised whenever a First Stage Fire condition is activated. Two sets of contacts are available. The first set has Normally Open and Normally Closed changeover contacts; the second set only has Normally Closed contacts Second Stage (SECOND STAGE) The Second Stage Relay is a double pole double throw relay and is energised whenever a Second Stage Fire condition is activated. Two sets of contacts are available. The first set has Normally Open and Normally Closed changeover contacts; the second set only has Normally Closed contacts Auxiliary Reset (RESET) The Auxiliary Reset Relay is a single pole single throw relay and is energised briefly when the panel is in System Reset mode. The relay is energised for 7.5 seconds. This is to allow ancillary equipment such as Beam Detectors to be reset. Only two terminals are provided, which are normally closed Auxiliary Fire (FIRE 1 & FIRE 2) The Auxiliary fire Relay is a double pole double throw relay and is energised for any Zone Fire condition. It is deenergised only on System Reset. Two sets of three terminals are provided, giving open and closed changeover contacts Auxiliary Fault (FAULT) The Auxiliary Fault Relay is a single pole double throw relay. It is a failsafe relay and is therefore normally energised. It is deenergised for any fault condition and remains deenergised until all faults are cleared. Three terminals are provided; giving one set of open and closed changeover contacts System Discharged (DISCHARGE) The System Discharged Relay is a single pole single throw relay and is energised when the Pressure Switch input is activated or if the NO PRESSURE SWITCH function is selected and the Actuator circuits are operated. It is deenergised on System Reset. Only two terminals are provided, which are normally open Internal Standby Batteries Two terminals are provided to allow connection of one set of internal standby batteries. The Charger Circuit is monitored to ensure correct charging of any attached batteries. Incorrect charging or disconnection results in a fault indication, illuminating the amber Power Fault LED and Battery Charger Fault LED on the internal control board Function Enable/Disable Switches Three sets of DIL switches and two jumper links are available on the internal control board to allow the panel to be configured for additional sitespecific functions: Function Select Switch This consists of two sets of 8way DIL switches to provide the following options: Page 7 of 27

8 One Man Test Mode See Manual Enables onemantest during commissioning i.e. automatic reset of zones when activated. This switch has no assigned function Zone 1 Double Knock Zone 1 produces a second stage alarm in auto mode i.e. the extinguishant release timer is started if Zone 1 registers a fire condition in auto mode Zone 2 Double Knock Zone 2 produces a second stage alarm in auto mode i.e. the extinguishant release timer is started if Zone 2 registers a fire condition in auto mode Zones Intrinsically Safe Allows the use of Zener barriers (or galvanic isolators) for intrinsically safe operation of zones 1 to No Pressure Switch Gives a Gas Discharged indication when the actuator circuits are operated, for installations where the Pressure Switch input is not used. If the Pressure Switch input is not used and this switch is not enabled then operation of the actuator circuits will not produce a Gas Discharged indication on the panel Actuator Short Circuit Monitoring Disable x Delay Disables the actuator short circuit indication. This is intended for use in installations where the C1565 monitoring and suppression board has not been fitted to solenoids on the actuator circuits. Doubles the delay length set by the discharge timer delay configuration switches (see ) Alarm1 First Stage, Alarm2 Second Stage Alarm Circuit 1 operates for a 1 st stage alarm condition and a 2 nd stage alarm condition. Alarm Circuit 2 operates only for a 2 nd stage alarm condition Alarms First Stage Pulsed/Continuous Alarm Circuits 1 and 2 pulse for a 1 st stage alarm condition if this switch is OFF. Alarm Circuits 1 and 2 are continuous for a 1 st stage alarm condition if this switch is ON Alarms Second Stage Pulsed/Continuous Alarm Circuits 1 and 2 pulse for a 2 nd stage alarm condition if this switch is OFF. Alarm Circuits 1 and 2 are continuous for a 2 nd stage alarm condition if this switch is ON Manual Release gives instant discharge Disables the discharge timer for manual release, i.e. if a Manual Release device is activated the actuator circuits are operated immediately instead of after the timer has ended Inhibit Silence Alarms during Gas Imminent Prevents the alarms from being silenced during the last 15 seconds of the discharge timer Buzzer Rapid Pulse at end of delay Causes the internal Buzzer to pulse rapidly during the last 15 seconds of the discharge timer Evacuate operates Aux. Fire Relay Manual Evacuate or Remote Evacuate rings the bells and also operates the auxiliary fire relay Latching Faults Page 8 of 27

9 Discharge Timer Set Switch All fault conditions produce a general fault indication even after the fault has been cleared, until manually reset by operating Silence Buzzer and then Reset System. This is an 8way DIL switch to allow setting of the timer. The switches can be used in any combination and are additive. This gives a maximum delay of 4 minutes 15 seconds (This can be doubled up to 8 minutes 30 seconds see ) Actuator 1 Minute Cut Off Option This is a single jumper link. When present, it causes the actuator circuits to be switched off automatically after 1 minute of activation, for actuators that do not require a continuous supply Link For Earth Fault Monitoring 3.12 Fault LEDs This is a single jumper link. When present, it allows the panel to monitor for earth faults on the cables coming into the panel. If this link is REMOVED, it physically isolates the internal control board from mains earth, thus disabling the earth fault monitoring facility. Ten Amber LEDs are mounted on the control board to indicate the following faults: 1. POWER FAULT This LED illuminates for any power supply related fault. 2. DISPLAY FAULT This LED illuminates if the display is disconnected. 3. EARTH FAULT This LED illuminates for any cabletoearth fault. 4. ALARM FAULT This LED illuminates for any alarm circuit fault. 5. LOCK OFF FAULT This LED illuminates for a cable fault on the Lock Off input. 6. ABORT INPUT FAULT This LED illuminates for a cable fault on the Emergency Abort input. 7. LOW PRESSURE FAULT This LED illuminates for a cable fault on the LOW PRESSURE FAULT input. 8. MAINS FAULT This LED illuminates if the a.c. mains input voltage is lost. 9. INTERNAL FAULT This LED illuminates if the a.c. mains input voltage is lost or if there is a short circuit across the Thermistor input. 10.BATTERY CHARGER FAULT This LED illuminates if the batteries cannot be charged for any reason, e.g. faulty batteries or disconnected batteries. One Green LED is provided to indicate that the voltage from the power supply output is acceptable. The ten amber fault LEDs on the internal control board are normally OFF and illuminate continuously for the relevant fault. The General Fault LED on the Display board pulses for any of the above faults Internal Buzzer The internal buzzer provides an audible indication to compliment the visual indications provided via the LEDs on the panel. The buzzer has various modes as follows: 1. Fault Indication Pulse, 1 second On, 3 seconds OFF The buzzer can be silenced for most fault indications. Page 9 of 27

10 2. Alarm Indication Continuous The buzzer cannot be silenced. 3. Alarms Silenced Pulse, ½ second On, ½ second OFF The buzzer cannot be silenced. 4. Buzzer Pulse End Of Delay Pulse, ¼ second On, ¼ second OFF The buzzer cannot be silenced. 5. Button Press Continuous whilst any button is pressed 3.14 Display Board General The Display board is connected to the internal control board via a 50way ribbon cable and polarised ribbon socket. A latching polarised 50way header is provided on the main control board at position J1. Q O P S W R A E F G H D B I J K L C N M T V U X Y 3.15 Display Board Visual Indications LEDs on the display board provide a visual indication of the panel status, as follows: (A) Power Supply On This is a green LED that is normally illuminated continuously to indicate that the panel is supplied with power (B) General Fault This is an amber LED that is normally OFF. If a fault condition exists for which a separate LED is not provided on the display board then the general fault LED pulses (C) Processor Fault This is an amber LED which is normally OFF. It is controlled from two circuits: 1. If the microprocessor fails and is restarted by the watchdog circuit then the microprocessor illuminates the LED until the SYSTEM RESET button is pressed. 2. If the microprocessor fails and cannot be restarted by the watchdog circuit then the watchdog circuit illuminates the LED. This indication cannot be cleared unless the microprocessor restarts. Page 10 of 27

11 (D) System Disabled This is an amber LED which is normally OFF. If any disablements are present on the panel then this LED pulses until all disablements are cleared (E) Zone 1 Fire This consists of two red LEDs that are normally OFF. A fire condition on Zone 1 pulses the LEDs until the Silence Alarms function is activated. The LEDs are then steady until System Reset (F) Zone 2 Fire This consists of two red LEDs that are normally OFF. A fire condition on Zone 2 pulses the LEDs until the Silence Alarms function is activated. The LEDs are then steady until System Reset (G) Auxiliary Zone Fire This consists of two red LEDs that are normally OFF. A fire condition on the Auxiliary Zone pulses the LEDs until the Silence Alarms function is activated. The LEDs are then steady until System Reset (H) Manual Release This consists of two red LEDs that are normally OFF. An active condition on the Manual Release Zone pulses the LEDs until the Silence Alarms function is activated. The LEDs are then steady until System Reset (I) Zone 1 Fault This is an amber LED that is normally OFF. The LED pulses if there is a fault present on Zone 1. The LED is steady if Zone 1 is disabled (J) Zone 2 Fault This is an amber LED that is normally OFF. The LED pulses if there is a fault present on Zone 2. The LED is steady if Zone 2 is disabled (K) Auxiliary Zone Fault This is an amber LED that is normally OFF. The LED pulses if there is a fault present on the Auxiliary Zone. The LED is steady if the Auxiliary Zone is disabled (L) Manual Release Fault This is an amber LED that is normally OFF. The LED pulses if there is a fault present on the Manual Release Zone (M) First Stage This is a red LED that is normally OFF. If a First Stage alarm occurs the LED is illuminated until System Reset (N) Second Stage This is a red LED that is normally OFF. If a Second Stage alarm occurs the LED is illuminated until System Reset (O) System Auto This is an amber LED and is illuminated if the panel is set to automatically operate the actuator circuits (P) System manual This is a green LED that is illuminated if the actuators can only be operated manually. This LED pulses if the Lock Off input is active. Note: The System Auto and System Manual LEDs are mutually exclusive and one or the other will always be illuminated (Q) Gas Discharged This is a red LED that is normally OFF. It is illuminated when the Extinguishant is released. This is usually detected via the Pressure Switch input but may be operated when the actuator circuits are operated if the panel is configured for NO PRESSURE SWITCH (see section ). The LED will be cleared on System Reset (R) Actuator Operated This is a red LED that is normally OFF. It is illuminated when the actuator circuits are activated. The LED will be cleared on System Reset (S) Timer Held Page 11 of 27

12 This is an amber LED that is normally OFF. It pulses when the extinguishant release timer is running and is steady when the timer is held. It switches OFF after the timer has ended or on System Reset (T) Low Pressure This is an amber LED that is normally OFF. It is illuminated when the Low Pressure input is active and clears only when the input is cleared (U) Pressure Switch Fault This is an amber LED that is normally OFF. It pulses if there is a cable fault on the Pressure Switch input. It remains pulsing until the fault is cleared (V) Remote Timer Hold Fault This is an amber LED which is normally OFF. It pulses if there is a cable fault on the Remote Timer Hold input. It remains pulsing until the fault is cleared (W) Actuator Fault This is an amber LED which is normally OFF. It pulses if an open circuit or short circuit fault is detected on either of the actuator circuits. It remains pulsing until the fault is cleared (X) Emergency Abort Operated This is an amber LED and is normally OFF. It is illuminated if the Emergency Abort input is active. The indication latches until panel reset. The LED pulses if the Abort Input is active in a nonalarm condition Display Board User Controls The Display Board provides user controls via buttons behind the membrane of the display board. All buttons except for TIMER HOLD are disabled until the ACCESS CONTROLS keyswitch is rotated to position 1. Operation of any button will activate the internal buzzer until the button is released. The following functions are available: (1) Evacuate This button operates the alarm circuits continuously when operated once. It must be operated again to silence the alarm circuits. If it is operated during a fire condition then Silence Alarms must be operated to silence the alarm circuits. The Auxiliary Fire relays are not normally operated by this function but can be selected to operate via a DIL switch on the main control board (2) Silence Alarms This button allows the alarm circuits to be silenced during a fire condition. The buzzer changes from a continuous sound to a rapid pulse. A new fire or evacuate condition clears the Alarms Silenced mode, reactivating the alarm circuits and returning the buzzer to continuous (3) Reset System This button initiates a System Reset if the panel is currently in Alarms Silenced mode (as described above). During System Reset all outputs and indications are cleared. The devices on the zones are reset (i.e. the zone supply is disconnected for 1 second) and the Auxiliary Reset relay is operated for 7.5 seconds (4) Silence Fault This button silences the buzzer during a fault indication but only if that fault is allowed to be silenced. Faults that cannot be silenced are: (i) (ii) (iii) (iv) (v) (vi) (5) Auto/Manual Processor Fault when controlled by the watchdog circuit. Zone Disabled. Relay Disabled. Actuator Circuit Disabled. One Man Test Mode Active. Display Fault. Page 12 of 27

13 This button toggles the panel status between Automatic and Manual discharge mode unless the Remote LockOff input is active, in which case the panel remains in Manual mode and the button has no effect. Page 13 of 27

14 (6) Timer Hold This input is only effective when the discharge timer is running. When pressed the timer is reset to the start value and remains inactive until the button is released, at which point the timer then becomes active again (7) Test Display This button illuminates all the LEDs on the panel display and the internal control board except for MAINS FAULT, INTERNAL FAULT and BATT CH FAULT. The buzzer also sounds. The Test Display mode is active until the button is released (8) Disable Actuators This button isolates the actuator circuits and prevents them from being operated or monitored for faults. The actuator circuits can be deisolated by operating the button again (9) Disable Relay This button isolates all the auxiliary relays and prevents them from being operated. The relays can be deisolated by operating the button again. Note: The Auxiliary Fault relay is still operated (10) Disable Zone 1 This button disables fault and fire monitoring on zone 1. Full monitoring can be restored by operating the button again (11) Disable Zone 2 This button disables fault and fire monitoring on zone 2. Full monitoring can be restored by operating the button again (12) Disable Auxiliary Zone This button disables fault and fire monitoring on the Auxiliary zone. Full monitoring can be restored by operating the button again. Note: All zone disable/enable operations result in the zone power supply being disconnected for a period of 10 seconds. 4. Technical Specification Maximum power supply output: Alarm current (Mains failed): 3.0 A 200mA + 20mA to 50mA for each zone in alarm + Ancillary equipment current + Alarm circuit current + Solenoid circuit current Mains Failed current: 83mA + Ancillary equipment current Integral charger output, Quiescent: 3.0 Amps, minus mains failed current Integral charger output, Alarm: 3.0 Amps, minus Alarm current Maximum Auxiliary 28VDC supply: 1.0 A Note: The auxiliary d.c. output is not monitored for faults. Alarm circuit rating Actuator circuit rating Internal Battery size External Dimensions (mm) Weight (excluding batteries) Cable Size Accepted by Terminals 2 at 1 A each (fused) 2 at 1 A each (fused) 2 x 7 Ah Sealed lead acid 370 high x 325 wide x 130 deep 4.85 kg. Maximum Detectors Per Zone 20 Maximum Call Points Per Zone No Limit 1.0 mm to 2.5 mm CSA. (Cross Sectional Area) CIRCUIT Cable Crosssectional Area Maximum Cable Run Zone 1.0mm 350 metres Zone 1.5mm 600 metres Alarm/Actuator 1.0mm 200 metres Page 14 of 27

15 Alarm/Actuator 1.5mm 350 metres The charger output is designed for charging Valve Regulated Sealed LeadAcid batteries, which are characterised by a reducing charge current when charged from a constant potential source. It will not provide the maximum charging current when the other power supply outputs are fully loaded. The panel requires two 12V batteries connected in series to produce 24V. CONNECTING ONE 12 VOLT BATTERY OR INCORRECT CONNECTION OF THE BATTERIES WILL DAMAGE THE PANEL AND THE BATTERY. WARNING: A fuse protects the internal mains transformer; always replace this with the correct type and rating: T3AH 250V (20mm fuse, 3A, HBC, Antisurge, approved to BS EN or equivalent.) 5. Standby Battery Requirements 5.1 Battery Capacity Calculation The usual requirement for standby batteries is 24 Hours standby plus 30 Minutes in Alarm. Use the following as a guideline when calculating your requirements. 24 Hours Standby Mains Failed current X Standby Time = Battery Capacity Required in Amps in Hours in AmpHours Mains Failed current is 0.083A plus ancillary equipment e.g. if a Status Indicator draws 0.15A then the total Mains Failed current is 0.233A. Therefore over 24 Hours the Battery requirement is X 24 = Ah 30 Minutes Alarm Alarm current X Alarm Time = Battery Capacity Required in Amps in Hours in AmpHours Alarm current is 0.200A plus the detector current plus alarm and solenoid current plus ancillary equipment e.g. if one detector is in alarm and draws 30mA, and the alarm load is 1.0A, and the actuator load is 1.0A and a Status Indicator draws 0.15A then the total Alarm current is 2.38A. Therefore over 30 Minutes the Battery requirement is 2.38 X 0.5 = 1.19 Ah Therefore the total Battery requirement is = Ah Use batteries with a rating of at least 25% more than the capacity required. This is to allow for deterioration of the batteries during use. Please note that the enclosure will only accommodate two 12V batteries up to 7Ah capacity. Larger sized batteries must be housed in a separate enclosure mounted next to the panel. Where batteries are housed in a separate enclosure, the Thermistor should also be positioned in the battery enclosure to ensure correct charge control by the power supply. 5.2 Battery Charging The battery charger voltage is preset during manufacturing and should not require adjustment. The output voltage can be verified by measuring the voltage across the battery terminals on the internal control board with the batteries connected. The battery charger output should be 27.08V +/ 25 o C (Thermistor value 5K). If the charger voltage requires adjustment, use an insulated trimming tool to adjust the potentiometer VR1 (see PCB layout diagram in section 10 for location). Use a 5K resistor in place of the thermistor when setting the voltage. Care should be taken when adjusting this potentiometer, as it is located between two large heatsinks that may be hot. Page 15 of 27

16 6. Detector Compatibility The panel will operate with the following types of devices: Manufacturer Part number Description Apollo Ionisation smoke detector Optical smoke detector Grade 1 rate of rise detector Common mounting base Optical detector Ionisation detector Ionisation integrated detector Grade 1 heat detector Common mounting base Hochiki SLK E Optical smoke detector SIHE Ionisation detector DFE60 Heat detector DFE90 Heat detector DCA E Rate of rise detector DCC 1EL Grade 1 rate of rise detector DCC 2EL Grade 2 rate of rise detector DCC 1REL Range 1 rate of rise detector YBFRL\4H5 Mounting base Nittan 2KC Optical smoke detector NID 58 Ionisation smoke detector TCA70LS Heat detector RB3R Mounting base NHDG1 (4T) Grade 1 fixed temperature detector NHDG2 (4T) Grade 2 fixed temperature detector NHDG3 (4T) Grade 3 fixed temperature detector NHDG\H1 (4T) Range 1 fixed temperature heat detector 2KH 4T Photo electric detector 2IC 4T Ionisation detector RB 4 Mounting base Photain ISD P91 Ionisation smoke detector PRR P91 Grade 1 rate of rise heat detector PHD P90 Range 1 fixed temperature heat detector FSB P91 Mounting base KAC KR72 Manual call point FKI MCP/R/F Manual call point Other Types may be compatible if electrically similar to the above devices. Consult your supplier for advice. All break glass units (call points) must have a resistor fitted to them to produce an alarm condition on the panel. Any value between 470 Ohm and 680 Ohm is acceptable. Please check with your supplier if you are not sure. Page 16 of 27

17 7. Panel Installation WARNING: Read this section completely before commencing installation. Prior to commencing installation of the control panel, ensure that adequate precautions are taken to prevent damage to the sensitive electronic components on the control board due to electrostatic discharge. You should discharge any static electricity you may have accumulated by touching a convenient earthed object such as an unpainted copper radiator pipe. You should repeat the process at regular intervals during the installation process, especially if you are required to walk over carpets. The panel must be located in a clean, dry position, which is not subject to shock or vibration and at least 2 metres away from pager systems or any other radio transmitting equipment. The operating temperature range is 0ºC to 40ºC; maximum humidity is 95%. IMPORTANT NOTES ON BATTERIES: DANGER: Batteries are electrically live at all times, take great care never to short circuit the battery terminals. WARNING: Batteries are often heavy; take great care when lifting and transporting batteries. For weights above 24 kilos, lifting aids should be used. DANGER: Do NOT attempt to remove the battery lid or tamper with the internal workings of the battery. Electrolyte is a highly corrosive substance, and presents significant danger to yourself and to anything else it touches. In case of accidental skin or eye contact, flush the affected area with plenty of clean, fresh water and seek immediate medical attention. Valve Regulated Lead Acid (VRLA) batteries are low maintenance, requiring no electrolyte topup or measurement of specific gravity. WARNING: Only clean the battery case with a cloth that has been soaked or dampened with distilled water. Do not use organic solvents (such as petrol, paint thinner, benzene or mineral spirits) or other materials that can substantially weaken the case. Do not use a dry cloth as this will generate static electricity, which in turn may lead to an explosion. WARNING: Avoid operating temperatures outside the range of 15 C/5 F to +50 C/122 F for float/standby applications. The recommended normal operating temperature is 20 C. HIGH TEMPERATURE will reduce battery service life. In extreme cases this can cause Thermal Runaway, resulting in high oxygen/hydrogen gas production and battery swelling. Batteries are irrecoverable from this condition and should be replaced. LOW TEMPERATURE will prolong battery life but reduce output capacity. DANGER: Do not incinerate batteries. If placed in a fire, the batteries may rupture, with the potential to release hazardous gases and electrolyte. VRLA batteries contain substances harmful to the environment. Exhausted batteries must be recycled. Return them to the battery manufacturer or take them to your Council waste disposal site for appropriate disposal. ELECTRICAL SAFETY: The voltfree relay contacts provided within the panel must not be used to directly switch any voltage that exceeds 50VAC or 75VDC. (Please also refer to relay rating data). This equipment requires a 230V AC supply. All installation work should be carried out in accordance with the recommendations of BS5839 Part 1 and the current edition of the IEE regulations by suitably qualified and trained personnel. THIS PANEL MUST BE EARTHED Page 17 of 27

18 7.1 Installation Procedure 1. Unpack the Control panel. If the panel door is locked locate the panel keys (usually fixed to the top of the panel) and open the door. 2. Locate the small plastic bag containing the installation spares as follows: (i) (ii) (iii) (iv) End of Line Resistors (3k9 Ohms) Spare 20mm glass fuse links A set of battery leads (+ve, ve and jumper lead) Electronic End of Line Terminators 3. Disconnect the display ribbon cable from the internal control board by unlatching the ribbon socket and pulling firmly but gently on the ribbon cable connector. 4. Remove the control panel chassis and control board from the enclosure by undoing the screws located on the chassis. Do not remove the control board from the chassis. Place the chassis unit safely to one side. 5. Place the empty enclosure against the wall, mark and fix using the single hole fixing in the upper section of the enclosure back plate. Level the enclosure and complete the fixing operation using the remaining two fixing holes in the lower section of the back plate. 6. Gland the installation wiring into the enclosure using the cable entry holes provided at the top of the enclosure. Leave the plastic protection plugs in any unused holes. 7. When all installation wiring is complete, check all the wiring to ensure that it is free from short circuits, open circuits, earth faults, crossed connections etc. Connect the end of line resistor (or Electronic ELT) across the terminals of the last device in each of the zone wiring runs. The end of line resistors are to be found in the panel terminals, spares are also provided in the small plastic bag supplied with the panel. Check that each Manual Call Point is fitted with an activation resistor (in the range 470 Ohms to 680 Ohms). Note: If any zones, alarm circuits, or solenoid circuits are not being used, then the end of line resistor must be connected across the appropriate terminals in the panel. 8. Connect an end of line resistor across the terminals of the last device in each of the alarm wiring runs. 9. Connect an end of line resistor across the terminals of the last device in each of the solenoid wiring runs. If you are using the C1565 monitoring and suppression board instead of the end of line resistor, then note that only one board can be used on each circuit. 10. Reattach the chassis and control board to the enclosure by refixing the screws located on the chassis. 11. Terminate all field wiring into the relevant terminals on the control panel. Ensure that any unused zones and inputs have end of line resistors fitted in their terminals. 12. Connect 230V AC mains to the mains terminal block provided inside the enclosure, ensuring that the mains supply is isolated at the source. The mains cable must be secured to the enclosure via a Cable Tie. The cable must be protected by a 5A fuse at the source. NOTE 1 MAINS ISOLATION: An appropriate lockable double pole disconnect device shall be provided as part of the building installation. NOTE 2 MAINS CABLES: Use only mains cable compliant to BS6004, BS6500, or equivalent, within the following limits: Cable Diameter Conductor Diameter Minimum Dimensions 4.0mm 1.0mm (0.8mm 2 ) Maximum Dimensions 8.0mm 2.25mm (4.0mm 2 ) DO NOT AT THIS STAGE TURN ON THE MAINS SUPPLY TO THE CONTROL PANEL. 13. Reconnect the display board ribbon cable to the internal control board. Page 18 of 27

19 7.2 Commissioning Procedure NOTE: In order to avoid accidental operation of the solenoid valves during commissioning it is recommended that the solenoid valves remain disconnected during the commissioning process. A suitable load resistor (50 to 100 Ohm) should be connected in place of the solenoid to simulate the presence of the solenoid coil. The solenoid coil should be connected only at the end of the commissioning process. 1. Turn ON the mains supply to the panel, and observe that the control panel reacts as follows: a) The green Power Supply On LED illuminates (display) b) The amber Output OK LED illuminated (control board) c) The amber System Auto LED illuminates (display) Wait 60 seconds and check for the following additional indications: a) The amber General Fault LED flashes (display) b) The amber Power Fault LED illuminates (control board) c) The amber Battery Charger Fault LED illuminates (control board) d) The internal buzzer sounds (control board) e) The Auxiliary Fault Relay operates No other indications should be present at this time, if there are, identify the fault and rectify it by checking the following: a) That the field wiring is free from faults b) That the end of line resistors are connected correctly in the last device on each zone and alarm circuit 2. Connect the batteries to the control panel observing that the correct terminal on the batteries is connected to the correct terminal on the control panel. Observe (after 30 to 60 seconds) that the control panel reacts as follows: a) The buzzer silences and the fault indications extinguish. b) The Power Supply On LED remains lit. c) The System Auto LED remains lit. d) The Output OK LED remains lit. 3. Press the Test Display button on the display board and check that the control panel reacts as follows: a) All LEDs on the display board and the control board illuminate whilst the switch is operated (except for MAINS FAULT, INTERNAL FAULT & BATT CH FAULT). b) The internal buzzer sounds. 4. Press the Evacuate button on the display board and check that the control panel reacts as follows: a) All sounders connected to the alarm circuits operate b) The alarms continue to sound until the Evacuate switch is reoperated 5. Switch off the mains a.c. supply to the control panel and check that the control panel reacts as follows(after 30 to 60 seconds): a) The General fault LED on the display board pulses b) The Power fault LED on the control board illuminates c) The internal buzzer in the control board sounds d) The Fault Relay operates e) The Mains Fault LED on the control board illuminates f) The Internal Fault LED on the control board illuminates 6. Check that the zone detection circuits are monitoring the wiring for faults correctly. The wiring on the zone detection circuits must be placed into the following conditions: a) Open circuit (a break in the circuit wiring) b) Short circuit (a short between cores) Generate each of the above faults and check that the control panel reacts as follows: a) The appropriate amber Zone fault LED pulses Page 19 of 27

20 b) The internal buzzer on the control panel sounds c) The fault relay operates 7. Repeat step 6 on the two alarm circuits and check that the control panel reacts as follows: a) The General fault LED on the display board pulses b) The Alarm fault LED on the control board illuminates c) The internal buzzer in the control panel sounds d) The fault relay operates 8. Repeat Step 6 on the two actuator circuits and check that the control panel reacts as follows: a) The Actuator Fault LED on the display board pulses b) The internal buzzer in the control panel sounds c) The fault relay operates 9. Repeat Step 6 on each of the status inputs and check that the control panel reacts as follows: (The lockoff input is not monitored for open circuit faults) a) The General fault LED on the display board and the relevant LED on the control board pulses, or the relevant fault LED on the display board pulses b) The internal buzzer in the control panel sounds c) The fault relay operates 10. Disable each detection zone by pressing the zone disable buttons on the display board. Check that the control panel reacts as follows: a) The appropriate Zone Fault LED illuminates b) The internal buzzer in the panel sounds c) The System Disabled LED pulses 11. Press the Auto Manual button and observe the following: a) The System Auto LED extinguishes b) The System Manual LED illuminates 12. With the detection zones disabled, operate a Manual Call Point on each zone (not the Manual Release zone) in turn and check that there is no reaction from the control panel. With the Manual Call Points still operated, enable one zone and check that after a 10 second delay the control panel reacts as follows: a) The appropriate red zonal Fire LEDs flash b) The alarm circuits operate c) The auxiliary fire relays operate d) The internal buzzer in the control panel sounds 13. Press the Silence Alarms button on the display board and check that the control panel reacts as follows: a) The alarms silence b) The red zonal Fire LEDs change from pulsing to steady illumination c) The buzzer changes to a pulse 14. Enable each remaining zone in turn and check that the control panel reacts as follows: a) The appropriate red zonal Fire LEDs pulse b) The alarm circuits operate c) The auxiliary fire relays operate 15. Press the Silence Alarms button on the display board and check that the control panel reacts as follows: a) The alarms silence b) The red zonal Fire LEDs change from pulsing to steady illumination c) The buzzer changes to a pulse 16. Reset the Manual Call Points to their normal condition. Press the System Reset button on the display board. Check that the control panel returns to its normal state. 17. Operate a detector on each zone and observe that the panel reacts as follows: a) The appropriate red zonal Fire LEDs pulse Page 20 of 27

21 b) The alarm circuits operate c) The auxiliary fire relays operate 18. Silence and Reset the panel to restore it to its normal state. 19. Disconnect the cable from the actuator circuits (you will get an Actuator Fault indication on the display). Set the DIL switches in the panel to give an 8 second delay on the discharge timer. 20. Press the Disable Actuators button and observe that the System Disabled LED illuminates. Operate the Manual Call Point on the front of the panel and observe the following: a) The red Manual Release LEDs pulse b) The alarm circuits operate c) The auxiliary fire relays operate d) The First Stage & Second Stage LEDs illuminate e) The Timer Held LED pulses f) After 8 seconds the Timer Held LED extinguishes but the actuator circuits do not operate (use a voltmeter to measure the voltage across the actuator circuit terminals, you should read a negative voltage) 21. Press the Disable Actuators button again and observe that the actuator circuits operate (you should see a positive voltage of about 28V). 22. Reset the Manual Call Point unit on the front of the panel. Silence and Reset the panel to restore it to its normal state. 23. Reconnect the cables to the Actuator circuits to clear the Actuator Fault. 24. If any of the Status Inputs are being used then test for open and short circuit faults. Then test them for activation using a resistor in the range 470 Ohm to 680 Ohm. Check that the desired indications are given. See Section 3 for details on these inputs. 25. Test the Remote Evacuate feature by linking a wire from the 0v terminal to the Remote Evacuate terminal on the control board. Check that the control panel reacts as follows: a) The alarms operate b) The internal buzzer in the control panel sounds 26. Remove the link from the Remote Evacuate terminal and check that the control panel returns to its normal state. Test the Remote Silence Alarms feature by first operating a call point on the auxiliary zone and then linking the wire from the 0v terminal to the Remote Silence terminal on the control board. Check that the control panel reacts as follows: a) The alarms silence b) The pulsing red Fire LEDs change from pulsing illumination to a constant illumination c) The buzzer changes tone 27. Return the call point to its normal condition and then test the Remote Reset feature by removing the link wire from the Remote silence terminal and connecting it to the Remote Reset terminal. Check that the control panel returns to its normal state. 28. Remove the link wire from both terminals. Test the Disable Relay feature by pressing the Disable Relay button and observe the following: a) The System Disabled LED pulses b) The fault buzzer sounds 29. Simulate a fire condition on the auxiliary zone and observe that the panel indicates a fire condition but the auxiliary fire relay does not operate. 30. Press the Disable Relay button again and observe that the System Disabled LED extinguishes and the auxiliary fire relay operates. 31. Operate the Silence Alarms and then the System Reset button to return the panel to its quiescent state. 32. If Status Indicators are used then test them by carrying out the following: a) Ensure the panel is in automatic mode and observe that the desired indications are given on the Status Indicator. Page 21 of 27

22 b) Place the panel in manual mode and observe that the desired indications are given on the Status Indicator. 33. If the Status Indicators have LockOff switches then test them by carrying out the following: a) Ensure the key is indicating an automatic state and observe that the desired indications are given on both the Status Indicator and the panel. b) Turn the key to give a manual condition and observe that the desired indications are given on both the Status Indicator and the panel. Repeat tests 32 and 33 for all Status Indicators. The primary functions of the panel have now been tested. The panel can be configured for a number of optional functions via the DILswitches on the control board. See section 3.11 for more details. You should test the panel to ensure each of the options selected operate correctly. 8. System Maintenance 8.1 Overview 1. The Fire Alarm system should be tested weekly and a note made in the system logbook. 2. The operation of break glass units and detectors should be carried out on a rotational basis so that all units and alarms are checked at least once over a 3month period. Important: Make sure you disable the actuators before carrying out any tests. 3. To operate a break glass unit use the Test key provided. 4. To operate a detector, use an approved Test Smoke. 5. Check the operation of auxiliary items such as door closers. 6. Reenable any disabled circuits after completing the tests. 8.2 Weekly Test Routine 1. Press the Disable Relay button and then the Disable Actuators button. 2. Operate one break glass unit and one detector. These should be on separate zones and the zones should be varied each month (unless all zones are always tested). 3. Check that all sounders operate. 4. Press the Silence Alarms button. 5. Check that all sounders have silenced. 6. Remove the test key from all break glass units and clear all detectors of smoke. 7. Press the Reset System button. 8. Press the Evacuate button and check that all sounders operate. Press the Evacuate button again to silence the alarms. 9. Press the Disable Relay button and then the Disable Actuators button. 10. Ensure that the panel returns to normal. 11. Press each zone disable button. Check that the zone fault LED illuminates and the internal panel buzzer sounds. 12. Press each zone disable button again to enable the zones. 13. Enter details of the test in the system logbook. ENSURE THAT NO DISABLEMENTS REMAIN ON THE PANEL. Page 22 of 27

Application, Installation, Operation & Maintenance Manual

Application, Installation, Operation & Maintenance Manual APPROVED BY:JBJ PRESCIENT III FIRE ALARM & GAS EXTINGUISHING CONTROL PANEL Application, Installation, Operation & Maintenance Manual PAGE 1 of 43 CONTENTS 1. INTRODUCTION... 3 2. GENERAL DESCRIPTION...

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd OPERATIONAL NOTES FOR CONCEPT FIRE PANEL. NOTE ON NEW FIRE PANELS, POSITION 1 ON THE SIX WAY INTERNAL OPTION SWITCH IS TURNED ON, DISABLING THE ZONAL SOUNDERS. TO ENABLE ZONAL SOUNDERS TURN OFF. Operation

More information

OPERATION AND INSTALLATION MANUAL

OPERATION AND INSTALLATION MANUAL EX+Plus 2 ZONE, 1AREA EXTINGUISHANT CONTROL PANEL OPERATION AND INSTALLATION MANUAL INTRODUCTION The Premier EX Plus is a 2 zone, single area panel for controlling the release of extinguishing gases in

More information

User Operation Manual

User Operation Manual APPROVED BY: JBJ PRESCIENT III FIRE ALARM & GAS EXTINGUISHING CONTROL PANEL User Operation Manual PAGE 1 of 6 1 CONTENTS 1. FIRE - GENERAL... 3 2. FIRE - ZONES 1 OR 2 - AUTOMATIC MODE... 3 3. FIRE - ZONES

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels CF5000, MF5000 and FXP5000 Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels 16 zone panels Contents PANEL INSTALLATION...3 Installation...3 PANEL WIRING... 3 Mains power

More information

Prem1er EVACS16. Installation Manual VOICE ALARM CONTROL PANEL 4 16 ZONES

Prem1er EVACS16. Installation Manual VOICE ALARM CONTROL PANEL 4 16 ZONES Prem1er EVACS16 VOICE ALARM CONTROL PANEL 4 16 ZONES Installation Manual Approved Document No: GLT.MAN-141 PAGE 1 INDEX INDEX... 2 Summary... 3 Safety information & use of this manual... 5 Installation

More information

Operation and Maintenance Manual

Operation and Maintenance Manual (FKER Series) Repeater Panel (FKER, FKER, FKER8) Operation and Maintenance Manual Man-9EL Issue June Index Section Page. Introduction.... Safety and mounting.... Technical specification.... Control panel

More information

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel INSTALLATION, OPERATION AND MAINTENANCE MANUAL Version: CN-PM-1000.VER1.1-12/2012 EN54 INFORMATION In accordance with EN 54-2 clause 13.7, the maximum

More information

FIREBETA EXTINGUISHING CONTROL PANEL (ECP)

FIREBETA EXTINGUISHING CONTROL PANEL (ECP) F I R E D E T E C T I O N A N D C O N T R O L FIREBETA EXTINGUISHING CONTROL PANEL (ECP) Three versions: 2 areas of detection and 1 area extinguishing 4 areas of detection and 1 area extinguishing 4 areas

More information

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL USER MANUAL 1 Table of Contents 1 SAFETY INFORMATION...3 1.1 SAFETY PRECAUTIONS DURING NORMAL OPERATION OF PANEL...3 1.3 BATTERY INFORMATION...3

More information

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels Installation and user manual for the FX range of fire panels 1, 2, 4 and 8 zone panels Contents Panel installation 3 Panel connections 3 Wiring connection drawings 4 Panel facilities 6 Installation check

More information

Saffire User & Installation Manual. IMPORTANT This manual should be left with the panel after installation.

Saffire User & Installation Manual. IMPORTANT This manual should be left with the panel after installation. Saffire+ 8-12 User & Installation Manual IMPORTANT This manual should be left with the panel after installation. We reserve the right to change product specifications without prior notice. Copyright VRC

More information

Written by: A.C. Amended by G.G. Checked by: JBJ/PB Approved by:jbj

Written by: A.C. Amended by G.G. Checked by: JBJ/PB Approved by:jbj Written by: A.C. Amended by G.G. Checked by: JBJ/PB Approved by:jbj Control Equipment Limited 32 Zone, 40 Character Discovery Panel, Voyager Panel and Integra Network Repeater Installation, Commissioning

More information

USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4

USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4 PREMIER EX8 EXTINGUISHING PANEL USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN 12094 PART 1 & EN54 PARTS 2 & 4 USER MANUAL Approved Document No: GLT.MAN-132 INDEX Extinguishing

More information

Control Panel Engineering and Commissioning Instructions

Control Panel Engineering and Commissioning Instructions Twinflex - V3 Fire Detection & Alarm System Control Panel Engineering and Commissioning Instructions (TO BE RETAINED BY THE COMMISSIONING ENGINEER) 26-0338 Issue 9 Fike s policy is one of continual improvement

More information

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009 Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual Man-1048 Issue 05 October 2009 CONTENTS Contents... Page Safety & Installation...2 Installation - continued...3

More information

Conventional Fire Control Panel (FKEP2, FKEP4, FKEP8) Operation and Maintenance Manual. Man-1078EL Issue 01 February 2014

Conventional Fire Control Panel (FKEP2, FKEP4, FKEP8) Operation and Maintenance Manual. Man-1078EL Issue 01 February 2014 Conventional Fire Control Panel (FKEP2, FKEP4, FKEP8) Operation and Maintenance Manual Man-1078EL Issue 01 February 2014 B Index Page 1. Introduction... 3 1B2. Safety and mounting... 3 2B3. Technical specification...

More information

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module FIRE ALARM CONTROL EQUIPMENT Addendum October 2006 Instructions for new style EN54-4 Power supply unit module MXLK-05 Issue 2.0 June 2007 INSTALLATION Safety Suppliers of articles for use at work are required

More information

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV LC1 & 2 Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV ZIRCONLC1 One Zone Conventional Fire Panel ZIRCONLC2 Two Zone Conventional Fire Panel Compliant with EN54-2:1998 & EN54-4:1998

More information

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS QUICK USER GUIDE FOR, 2 & 4 ZONE PANELS INDICATORS COLOUR INDICATION MON FAULT Yellow On when a fault condition has occurred, or if no other fault Led is on, this indicates 24v auxiliary fuse failure.

More information

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL 3500 CONVENTIONAL FIRE ALARM CONTROL PANEL INSTALLATION AND COMMISSIONING MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax:

More information

PAT E N T System 88. COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00

PAT E N T System 88. COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00 PAT E N T System 88 COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00 Pg 1 of 12 CONTENTS 1. GENERAL 1.1 Introduction 2 1.2 System Description

More information

Precept Marine Control Panel Application Guide

Precept Marine Control Panel Application Guide Precept Marine Control Panel Application Guide Contents Page 1.0 Cabinet Specifications 2 2.0 Panel Hardware Specifications 5 3.0 Panel Configuration 8 4.0 Technical Specifications 8 5.0 Battery Sizes

More information

Surveyor Envoy-MINI 4

Surveyor Envoy-MINI 4 Surveyor Envoy-MINI 4 CONTENTS SECTION 1 INTRODUCTION Page 4 About this manual Page 4 System design and planning Page 4 Panel types Page 4 General Page 4 SECTION 2 INSTALLATION Page 5 General Page 5 ESD

More information

Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses

Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses BCU Power Supplies Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses Installation, Commissioning and Operating Manual BCU RANGE OF

More information

Technical Data Sheet

Technical Data Sheet Mx-1000 Series Technical Data Sheet Application Guide for Mx-1002, Mx-1004, Mx-1008, Mx-1016 & Mx-1032 Conventional Fire Alarm Control Panels And Mx-1108, Mx-1116 & Mx-1132 Repeater Panels Document Number:

More information

Conventional Fire Control Panel

Conventional Fire Control Panel (FKEW Series) Conventional Fire Control Panel (FKEW2, FKEW4, FKEW8) Man-1138EL Issue 01 February 2014 Contents 1. Introduction... 4 2. Safety... 4 4. Technical specification... 5 5. Control panel fascia...

More information

FSTP4-2-wire 4 Zone Conventional Fire Control Panel Operation and Maintenance Manual. Man-1078FS4 Issue 01 April 2012

FSTP4-2-wire 4 Zone Conventional Fire Control Panel Operation and Maintenance Manual. Man-1078FS4 Issue 01 April 2012 FSTP4-2-wire 4 Zone Conventional Fire Control Panel Operation and Maintenance Manual Man-1078FS4 Issue 01 April 2012 Index Page 1. Introduction... 3 2. Safety and mounting... 3 3. Technical specification...

More information

VoCALL - CFVCC5. Compact 5 Line Exchange Unit. Installation & Commissioning Manual

VoCALL - CFVCC5. Compact 5 Line Exchange Unit. Installation & Commissioning Manual VoCALL - CFVCC5 Compact 5 Line Exchange Unit Installation & Commissioning Manual Introduction A VoCALL Emergency Voice Communications System (EVCS) is a fixed, secure, bi-directional, full duplex voice

More information

FSTP2-2-wire 2 Zone Conventional Fire Control Panel Operation and Maintenance Manual. Man-1078FS2 Issue 01 April 2012

FSTP2-2-wire 2 Zone Conventional Fire Control Panel Operation and Maintenance Manual. Man-1078FS2 Issue 01 April 2012 FSTP2-2-wire 2 Zone Conventional Fire Control Panel Operation and Maintenance Manual Man-1078FS2 Issue 01 April 2012 Index Page 0B1. Introduction... 3 1B2. Safety and mounting... 3 2B3. Technical specification...

More information

BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL

BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL 26 Aug 2015 V1.8 Page 1 SECTION CONTENTS PAGE NO. 1.0 SYSTEMS DESCRIPTION 1.1 General descriptions 2 1.2 Master Alarm PCB 2 1.3 Zone Display Board 2 1.4

More information

Fire Control Panel. Installation & Programming Manual TABLE OF CONTENTS

Fire Control Panel. Installation & Programming Manual TABLE OF CONTENTS Fire Control Panel Installation & Programming Manual TBLE OF CONTENTS Page Getting Started 2 Power Supply Unit 3 Inputs 4 Outputs 4 LED Indications 4 User Keypad Functions 5 Engineer Keypad Functions 6

More information

EXTINGUISHING AGENT RELEASE MODULE

EXTINGUISHING AGENT RELEASE MODULE EXTINGUISHING AGENT RELEASE MODULE Operation, Installation & Programming Manual Revision 3.00 Distributors For: 18-20 Brookhollow Ave telephone 02 8850 2888 www.firesense.com.au Baulkham Hills NSW 2153

More information

EX8. Instruction Manual: COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 AND EN54 PARTS 2 & 4

EX8. Instruction Manual: COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 AND EN54 PARTS 2 & 4 EX8 COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN 12094 PART 1 AND EN54 PARTS 2 & 4 Instruction Manual: Approved Document No: GLT.MAN-124 PAGE 2 INDEX INDEX... 3 Introduction... 4 Indications

More information

FEC400 Series. Installation Manual

FEC400 Series. Installation Manual FEC400 Series Conventional microprocessor controlled fire detection and alarm panels with extinguishing control Installation Manual Version 2.3 / August 2004 Aritech is a GE Interlogix brand. http://www.geindustrial.com/ge-interlogix/emea

More information

FIRE ALARM CONTROL PANEL. COMPLIES WITH EN54 part 2 & part 4 MEETS THE FUNCTIONAL REQUIREMENT OF BS:EN 5839 part 1 INSTALLATION MANUAL

FIRE ALARM CONTROL PANEL. COMPLIES WITH EN54 part 2 & part 4 MEETS THE FUNCTIONAL REQUIREMENT OF BS:EN 5839 part 1 INSTALLATION MANUAL FIRE ALARM CONTROL PANEL COMPLIES WITH EN54 part 2 & part 4 MEETS THE FUNCTIONAL REQUIREMENT OF BS:EN 5839 part 1 INSTALLATION MANUAL CONTENTS 1. INTRODUCTION. 3 1.1 HANDLING THE PCBS 1.2 USING THIS MANUAL

More information

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum. September 29, 1997 Firecycle III 433 a 1. PRODUCT NAME VIKING Model E-1 Manufactured 1997 Present 2. MANUFACTURED FOR THE VIKING CORPORATION 210 N Industrial Park Road Hastings, Michigan 49058, U.S.A.

More information

Hydrosense. Vimpex Limited. Star Lane. Great Wakering. Essex SS3 0PJ. Tel: +44 (0) Fax +44 (0)

Hydrosense. Vimpex Limited. Star Lane. Great Wakering. Essex SS3 0PJ. Tel: +44 (0) Fax +44 (0) Overview of the Water Detection System 2 Components of a System 4 Design & Planning 5 System Installation Notes 7 Control Panel Installation - HSCPI-K3000 8 Control Panel Commissioning HSCPC-K3000 11 Front

More information

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

Syncro AS. Analogue Addressable Fire Control Panel. User Manual Syncro AS Analogue Addressable Fire Control Panel User Manual Man-1100 Issue 02 Nov. 2008 Index Section Page 1. Introduction...3 2. Safety...3 3. Panel Controls...4 3.1 Access Level 1...4 3.2 Access Level

More information

PREMIER EX8 INSTALLATION MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4 INSTALLATION MANUAL

PREMIER EX8 INSTALLATION MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4 INSTALLATION MANUAL PREMIER EX8 INSTALLATION MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN 12094 PART 1 & EN54 PARTS 2 & 4 INSTALLATION MANUAL Approved Document No: GLT.MAN-124 INDEX Extinguishing

More information

Conventional Fire Control Panel with Extinguishant Control Unit. Operation and Maintenance Manual SIGMA-2-M3-ECU SIGMA-4-M3-ECU SIGMA-8-M3-ECU

Conventional Fire Control Panel with Extinguishant Control Unit. Operation and Maintenance Manual SIGMA-2-M3-ECU SIGMA-4-M3-ECU SIGMA-8-M3-ECU SIGMA-CP Issue 12 October 2011 AFP-2516 Conventional Fire Control Panel with Extinguishant Control Unit Operation and Maintenance Manual SIGMA-2-M3-ECU SIGMA-4-M3-ECU SIGMA-8-M3-ECU SIGMA-XT Issue 1 October

More information

FIREPRO INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL. Approved Document No. GLT Issue: 1. 8 Author: NRPJ Date: 7/ 3/201 4

FIREPRO INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL. Approved Document No. GLT Issue: 1. 8 Author: NRPJ Date: 7/ 3/201 4 FIRE ALARM CONTROL PANEL INSTALLATION MANUAL Approved Document No. GLT -201-7-3 Issue: 1. 8 Author: NRPJ Date: 7/ 3/201 4 CONTENTS 1. INTRODUCTION... 1.1 HANDLING THE PCBS... 1.2 USING THIS MANUAL... 1.3

More information

Operating manual and Log book for the range of 1,2,4 and 8 zone fire Control and Repeat panels

Operating manual and Log book for the range of 1,2,4 and 8 zone fire Control and Repeat panels Operating manual and Log book for the range of 1,2,4 and 8 zone fire Control and Repeat panels The panels are designed in accordance with the requirements of EN54 Part 2:1997 (and include optional clauses

More information

Syncro Matrix Analogue Addressable Fire Alarm Mimic Panel Product Manual

Syncro Matrix Analogue Addressable Fire Alarm Mimic Panel Product Manual Syncro Matrix Analogue Addressable Fire Alarm Mimic Panel Product Manual Australia Issue 01 April 2012 Contents 1 Introduction 3 2 Safety 3 3 Installation 4 3.1 Mounting the Cabinet 4 4 Specifications

More information

USER MANUAL & MAINTENANCE GUIDE OG OO

USER MANUAL & MAINTENANCE GUIDE OG OO M+48. USER MANUAL & MAINTENANCE GUIDE OG OO What to do if the Fire Alarm Panel shows an Alarm (Red LED) Write down which LEDs are lit (either in the log book, or on a piece of paper for transferring to

More information

FEC403EN Installation Manual

FEC403EN Installation Manual FEC403EN Installation Manual P/N 10-4101-501-2FC1-01 ISS 22JAN15 Copyright Trademarks and patents Manufacturer 2015 UTC Fire & Security. All rights reserved. The FEC403EN name and logo are trademarks of

More information

Intruder - Fire - Water Combined Alarm

Intruder - Fire - Water Combined Alarm 65 Intruder - Fire - Water Combined Alarm Installation Manual and User Operating Instructions TALE OF CONTENTS Page First Power-Up 2 Power Supply Unit 3 Input & Detection Circuits 3 Output & Alarm Circuits

More information

Menvier Fire System MF9300

Menvier Fire System MF9300 Menvier Fire System MF9300 Eight and sixteen zone control panels Installation and User Instructions and Systems Log IMPORTANT THIS MENVIER FIRE PANEL IS DESIGNED TO BE USED WITH POLARISED AND SUPPRESSED

More information

Excel-EN Conventional Fire Control Panel

Excel-EN Conventional Fire Control Panel Available as 2, 4, 6, 8,10 or 12 zones Approved to EN54-2 & 4 Modular expansion zone cards Programmable relays and outputs Optional additional sounder circuits Optional additional programmable outputs

More information

BiWire Flexi. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI Installation Manual

BiWire Flexi. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI Installation Manual BiWire Flexi BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI Installation Manual Contents Contents 1. INTRODUCTION... 4 1.1 Purpose...4 2. THE BIWIRE FLEXI FIRE DETECTION & ALARM

More information

4 wire conventional alarm system

4 wire conventional alarm system Scimitar 4 wire conventional alarm system from Channel Safety Systems Scimitar 4 wire conventional alarm system The Scimitar Fire Alarm Control System is a comprehensive range of high specification conventional

More information

VSN-RP1r Extinguishing Control Panel. User Manual (Software version 3.x) by Honeywell. doc. MIE-MN-570I rev.008

VSN-RP1r Extinguishing Control Panel. User Manual (Software version 3.x) by Honeywell.   doc. MIE-MN-570I rev.008 www.morley-ias.es by Honeywell VSN-RP1r Extinguishing Control Panel User Manual (Software version 3.x) doc. MIE-MN-570I rev.008 Information in this document is subject to change without notice. 22 June

More information

installation & maintenance manual LPCB APPROVED CFP 2/4/8 ZONE FIRE ALARM CONTROL PANEL approved document no. DFU rev 5

installation & maintenance manual LPCB APPROVED CFP 2/4/8 ZONE FIRE ALARM CONTROL PANEL approved document no. DFU rev 5 LPCB APPROVED CFP 2/4/8 ZONE FIRE ALARM CONTROL PANEL installation & maintenance manual approved document no. DFU7004000 rev 5 CFP 2/4/8 ZONE LPCB APPROVED FIRE PANEL INSTALLATION & MAINTENANCE MANUAL

More information

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL Document No...G108WO1.DOC Serial No... Issue Date...17 th SEPTEMBER 1999 Software Version...1.4 APPROVED TO: NZS 4512:1997 AS/NZS 3548:1992 Fire Alarm

More information

GAS SUPRESSION CONTROL PANEL:

GAS SUPRESSION CONTROL PANEL: GAS SUPRESSION CONTROL PANEL: MODEL NAME: COMPANY: DELTA 437/2, Main Road, Mandwali Fazalpur, Delhi-110092 Page 1 ABOUT THE PRODUCT ASES is very proud of to introduce DELTA the completely digital microprocessor

More information

2018 Johnson Controls. Tyco Fire & Security GmbH, Victor von Bruns-Strasse 21, 8212 Neuhausen am Rheinfall, Switzerland DUO-CEL

2018 Johnson Controls. Tyco Fire & Security GmbH, Victor von Bruns-Strasse 21, 8212 Neuhausen am Rheinfall, Switzerland DUO-CEL OM_FC_DUO-CEL_APP 2018 Johnson Controls. Tyco Fire & Security GmbH, Victor von Bruns-Strasse 21, 8212 Neuhausen am Rheinfall, Switzerland DUO-CEL FIRE DETECTION/ALARM PANEL Application Guide PAGE 1 of

More information

SECURIT 700L PLUS ENGINEERING MANUAL

SECURIT 700L PLUS ENGINEERING MANUAL SECURIT 700L PLUS ENGINEERING MANUAL C & K Systems Ltd 13/03/97 C031-096-02 NEW ENHANCED FEATURE SET Securit 700L PLUS Engineering instructions INTRODUCTION The Securit 700L is a microprocessor intruder

More information

MAG2/4. AL MAG2 Soft. Version 2.1 MAG4 Soft.Version 2.0 USER MANUAL

MAG2/4. AL MAG2 Soft. Version 2.1 MAG4 Soft.Version 2.0 USER MANUAL FIRE CONTROL PANEL MAG2/4 USER MANUAL AL MAG2 Soft. Version 2.1 MAG4 Soft.Version 2.0 READ THIS MANUAL BEFORE CONNECTING THE EQUIPMENT AND KEEP IT SAFE FOR FUTURE REFERENCE. To call our technical support

More information

ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR

ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR ED820 24V MODEL fire DETECTOR INSTRUCTION MANUAL Address: Enigma House, Enigma Business Park, Malvern, Worcestershire, WR14 1GD Tel: 44 (0)1684 891500 Fax: 44 (0)1684 891600 Email: sales@electronicdevices.co.uk

More information

Sigma CP (K and T Series)

Sigma CP (K and T Series) Sigma CP (K and T Series) Conventional Fire Control Panel (K11020M2, K11040M2, K11080M2) (T11020M2, T11040M2, T11080M2) Operation and Maintenance Manual Man-1078 Issue 19 January 2014 Index Page 0B1. Introduction...

More information

Conventional Leaflets

Conventional Leaflets Conventional Leaflets Panels Last updated October 1999 Make leaflet selection by clicking on appropriate bookmark Return to Menu Installation and Basic Commissioning guide for the range of 1,2,4 and 8

More information

Sigma XT+ Extinguishant Control Panel. Operation and Maintenance Manual

Sigma XT+ Extinguishant Control Panel. Operation and Maintenance Manual Sigma XT+ Extinguishant Control Panel Operation and Maintenance Manual Man-1112 Issue 9 March 2010 Index Introduction... 5 2. Safety and mounting... 6 2.1 Safety... 6 2.2 Mounting... 7 3. Technical specification...

More information

Surveyor Excel. Fire Alarm Control Equipment Network version. Programming Manual MASTER MANUAL. VERSION 14.0 and Above

Surveyor Excel. Fire Alarm Control Equipment Network version. Programming Manual MASTER MANUAL. VERSION 14.0 and Above Surveyor Excel Fire Alarm Control Equipment Network version Programming Manual VERSION 14.0 and Above MASTER MANUAL Drawing S1606. PCB Layout guide for XLK range of control panels FCPXLK-2/4/6/8 & FCPXLK2/4/6/8TW

More information

5000 INSTALLATION GUIDE

5000 INSTALLATION GUIDE 5000 INSTALLATION GUIDE Table of Contents Section Page No 1. INTRODUCTION... 3 2. WARNINGS AND CAUTIONS... 3 3. UNPACKING... 3 4. INSTALLATION... 4 5. CONTROL PANEL - REMOVING ITEMS BEFORE MOUNTING...

More information

3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL

3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL 3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL USER MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273 Web:

More information

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER Application The unit is primarily intended for use where there is a requirement to integrate a limited fire protection function into a larger control equipment scheme, or in specialist applications where

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd full installation, commissioning and operating manuals can be downloaded from www.haes-systems.co.uk combined addressable / conventional fire alarm control panel User Guide Approved Document No. MFBU-04

More information

Installation and Operating Instructions

Installation and Operating Instructions Twinflex and Multipoint Installation and Operating Instructions Rafiki Protection Limited 55 Springvale Industrial Estate Cwmbran South Wales NP44 5BD United Kingdom Tel. (+44) 01633 865558 Fax (+44) 01633

More information

CONVENTIONAL CONTROL PANEL FL2/4/8/12 LT-XP

CONVENTIONAL CONTROL PANEL FL2/4/8/12 LT-XP FLx-LT-XP CONVENTIONAL CONTROL PANEL FL2/4/8/12 LT-XP Installation, Configuration and Operating Manual MAY 2008 MIE-MI-580I_FL rev.003 Information in this document is subject to change without notice.

More information

highline SVCS-1 INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10

highline SVCS-1 INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10 highline WINDOW CONTROLS INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM SVCS-1 * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10 CERTIFICATE OF COMPLIANCE SVCS-1 We the undersigned

More information

Operating manual and Log book for the range of 1,2,4 and 8 zone fire Control and Repeat panels

Operating manual and Log book for the range of 1,2,4 and 8 zone fire Control and Repeat panels Operating manual and Log book for the range of 1,2,4 and 8 zone fire Control and Repeat panels The panels are designed in accordance with the requirements of EN54 Part 2:1997 (and include optional clauses

More information

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS GENERAL DESCRIPTION... 2 STANDARD AND OPTIONAL PARTS LIST... 2 PARTS DIAGRAM... 3 TERMINAL DRAWING AND SPECIAL NOTES...

More information

System 800 Addressable Fire Detection & Alarm System

System 800 Addressable Fire Detection & Alarm System SECTION 5: page 1 Section 5: System 800 Addressable Fire Detection & Alarm System SECTION 5: page 3 10 reasons to specify 800 1 Plug and Play A user friendly panel not requiring special software tools

More information

SOLO Single Loop Addressable Fire Control Panel

SOLO Single Loop Addressable Fire Control Panel Solo Single Loop Analogue Addressable Fire Control Panel Apollo Protocol Installation, Commissioning & Operating Manual Issue 03 June 1999 CONTENTS Section... Page 1. Introduction...1 2. Safety...2 3.

More information

Installation and user manual for the BiWire / Conventional Repeater Panel

Installation and user manual for the BiWire / Conventional Repeater Panel Panel EFBWCV-REPEATER Contents Introduction.... 3 Purpose... 3 The Panel.... 3 Indication Equipment (IE).... 3 Power Supply Equipment (PSE).... 4 System Wiring.... 5 Status Indications.... 5 Repeater I/O....

More information

SYSTEM MANUAL FT1-SB. Single Zone Fire Alarm System

SYSTEM MANUAL FT1-SB. Single Zone Fire Alarm System SYSTEM MANUAL FT1-SB Single Zone Fire Alarm System DOCUMENT HISTORY Issue Date Description Written By Checked By Draft 0 2/9/2008 Original Document. A. Shenouda C. Orr Issue 1 4/11/2011 Update drawing

More information

FIRE ALARM CONTROL PANEL FVC01-08

FIRE ALARM CONTROL PANEL FVC01-08 FIRE ALARM CONTROL PANEL FVC01-08 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Radal Technology Limited Unit 1, Webber Court Billington Road, Burnley Lancashire, BB11 5UB Tel: +44 (0) 1282 463 770 Fax: +44

More information

BX444-Mc Gas Detector

BX444-Mc Gas Detector Installation and User Guide Rev.01. BX444-Mc Gas Detector Application Duomo is recognised within the gas industry for providing a comprehensive range of low cost, high reliability gas detection for many

More information

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

ZX1e ZX2e ZX5e. Document No Issue 01 user manual ZX1e ZX2e ZX5e Document No. 996-130 Issue 01 user manual MORLEY-IAS ZX2E/ZX5E Fire Alarm Control Panels Table of Contents 1 INTRODUCTION... 4 1.1 NOTICE... 4 1.2 WARNINGS AND CAUTIONS... 4 1.3 NATIONAL

More information

Operating manual and Log book for the range of 1,2,4 and 8 zone fire Control and Repeat panels

Operating manual and Log book for the range of 1,2,4 and 8 zone fire Control and Repeat panels Operating manual and Log book for the range of 1,2,4 and 8 zone fire Control and Repeat panels The panels are designed in accordance with the requirements of EN54 Part 2:1997 (and include optional clauses

More information

Installation, Commissioning & Operating Manual

Installation, Commissioning & Operating Manual EN54 APPROVED 2-4 ZONE ALARMSENSE CONTROL PANEL Installation, Commissioning & Operating Manual 810a/05 Approved Document UI-ALS-01 Issue 2.0 0832 Haes Systems Ltd, Columbia House, Packet Boat Lane, Cowley

More information

Fire Alarm Control Panel Installation, Commissioning & Operation MAN

Fire Alarm Control Panel Installation, Commissioning & Operation MAN DH4 ZoneSense Fire Alarm Control Panel Installation, Commissioning & Operation MAN 1531-5 Access Level 1 (Normal Operation) Responding To An Alarm Zone FIRE Alarm Indicator - flashing Common FIRE Alarm

More information

Conventional Fire Alarm System 2014 V1.2

Conventional Fire Alarm System 2014 V1.2 Conventional Fire Alarm System 2014 V1.2 Product Overview Control Panel 2 Conventional Fire Panel GST102A 2 zone Fire panel GST104A 4 zone Fire panel GST108A 8 zone Fire panel GST116A 16 zone Fire Panel

More information

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3 INTELLIGENT FIRE TECHNOLOGY Twinflex and Multipoint V3 User Guide (TO BE RETAINED BY USER) 26-0340 Issue 3 Rafiki Protection Limited Rafiki policy is one of continual improvement and the right to change

More information

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE D (OPERATION) INITIATE A DYNAMIC BATTERY TEST The system tests the back-up battery once every 24 hours. The owner can initiate a dynamic battery test at any time with the following codes while the system

More information

An introduction to... Sigma

An introduction to... Sigma An introduction to... Sigma XT+ Sigma XT+ Overview The Sigma XT+ 21000 series are the latest additions to the Sigma family of control equipment from Kentec Electronics Limited. The Sigma XT+ range combines

More information

Door Release Power Supply

Door Release Power Supply www.protectingpeople.co.uk Door Release Power Supply Engineer / Installation Manual Document: VI55.1 Protecting People Printed : 04/03/2004-1 - Ventcroft Ltd Door Release Power Supply Engineer / Installation

More information

Fire Alarm Control Panel. System Maintenance and Log Book

Fire Alarm Control Panel. System Maintenance and Log Book Fire Alarm Control Panel System Maintenance and Log Book Fire Alarm System Maintenance A fire alarm system must provide early and reliable warning of the outbreak of fire. To achieve this, the system remains

More information

Installation Manual Premier 412/816/832. Issue 10

Installation Manual Premier 412/816/832. Issue 10 Installation Manual Premier // Issue 0 Premier // Installation Manual 5. Operating the System Introduction Before attempting to operate the alarm system ensure you have familiarised yourself with all the

More information

MR-2602 Two Zone Fire Alarm Control Panel

MR-2602 Two Zone Fire Alarm Control Panel MR-2602 Two Zone Fire Alarm Control Panel Installation Manual Secutron LT-2015 Rev.3 July 2010 Table of Contents 1 Introduction 1.1 The MR-2602 Fire Alarm Control Unit... 11 1.1.1 General features...

More information

NFS Supra / VSN-2Plus / ESS-2Plus Conventional Fire Alarm Control Panel. Installation and Operating Manual

NFS Supra / VSN-2Plus / ESS-2Plus Conventional Fire Alarm Control Panel. Installation and Operating Manual / VSN-2Plus / ESS-2Plus Conventional Fire Alarm Control Panel Installation and Operating Manual HLSI-MN-025-I v.05 April 2015 Note: This manual is valid for the following control panel models: NFS-Supra

More information

Panel Functions & Indicators - Key to Icons General & Zone Fire LEDs ACCEPT SOUNDERS START/ STOP RESET BUZZER MUTE KEYSWITCH DELAY ON/OFF ITEM SELECT

Panel Functions & Indicators - Key to Icons General & Zone Fire LEDs ACCEPT SOUNDERS START/ STOP RESET BUZZER MUTE KEYSWITCH DELAY ON/OFF ITEM SELECT Islenska Français Deutsch Nederlands Svenska EN54-8 Zone Conventional Fire Control Panel User Manual 997-493-00, Issue 0 November 003 Panel Functions & Indicators - Key to Icons General & Zone Fire LEDs

More information

PRODUCT INSTRUCTIONS. Fire Door Control Panel (FDCP) Stock Code Description Doc No: PI-115. Ellard Fire Door Control Panel Ellard Slave Repeater Unit

PRODUCT INSTRUCTIONS. Fire Door Control Panel (FDCP) Stock Code Description Doc No: PI-115. Ellard Fire Door Control Panel Ellard Slave Repeater Unit PRODUCT INSTRUCTIONS Fire Door Control Panel (FDCP) Floats Rd, Wythenshawe, Manchester. M23 9WB T: 44 (0)161 945 4561 F: 44 (0)161 945 4566 Stock Code Description Doc No: PI115 00133 00134 Ellard Fire

More information

Fire Control Panel. Installation & Programming Manual TABLE OF CONTENTS

Fire Control Panel. Installation & Programming Manual TABLE OF CONTENTS Fire Control Panel Installation & Programming Manual TABLE OF CONTENTS Page Getting Started 2 Power Supply Unit 3 Remote Keypad Bus 3 Inputs & Outputs 4 User Keypad Functions 5 Engineer Keypad Functions

More information

Document No Issue 4 user manual

Document No Issue 4 user manual DX Document No. 996-148-000-4 Issue 4 user manual Dimension Series Table of Contents 1 INTRODUCTION... 5 1.1 NOTICE... 5 1.2 MODELS... 5 1.3 WARNINGS AND CAUTIONS... 7 1.4 NATIONAL APPROVALS... 7 1.5 EN54

More information

The ID51 & ID52 can be upgraded to 2 loops without the need to change back box. FEATURES. Intelligent Features

The ID51 & ID52 can be upgraded to 2 loops without the need to change back box. FEATURES. Intelligent Features 990-052, Issue 6 20 March 2006 ID50 Series Single Loop Intelligent Fire Alarm Panels Section: Intelligent Fire Alarm Panels GENERAL The NOTIFIER ID50 series single loop intelligent fire alarm panels, has

More information

Model 17A00 Expansion Enclosure

Model 17A00 Expansion Enclosure HOME AUTOMATION, INC. Model 17A00 Expansion Enclosure Installation Manual Document Number 17I00-1 Rev A March, 2002 Home Automation, Inc. Model 17A00 Expansion Enclosure Installation Manual Document Number

More information

user manual Document No , Revision 03 November 2015

user manual Document No , Revision 03 November 2015 user manual Document No. 996-202-600-3, Revision 03 November 2015 Contents 1 Introduction...1 1.1 Notice...1 1.2 Models...1 2 User Control Levels...2 2.1 Level Definition...2 2.2 User Passwords...2 3 Controls

More information

JUNO-NET. Fire Alarm Control Panel OPERATION & MAINTENANCE MANUAL

JUNO-NET. Fire Alarm Control Panel OPERATION & MAINTENANCE MANUAL Fire Alarm Control Panel & MANUAL CONTENTS SECTION -. Description of the fire control panel fascia.... Alarm.... Reset the system.... Sound and silence the alarms.... Read the Fire, Fault, Test and Disabled

More information