Fire Protection Coffee Break Training August 2016
|
|
- Adam Cook
- 5 years ago
- Views:
Transcription
1 Fire Protection Coffee Break Training August 2016
2 Agenda Introduction - Phelan NFPA 13 versus NFPA 13R systems for Residential Occupancies - Homa NFPA 72 Record of Completion - Homa Questions and Answers
3 Overview How did you get to NFPA standards? Ordinances IBC & IFC Differences between the residential applications within NFPA 13 and NFPA 13R Densities Sprinklers in a design area Outside the dwelling unit. Omissions of sprinklers NFPA 72 Completion Documents Completion of documents and location Intelligibility testing
4 Ordinances Dmgov.org, municipal code on the bottom right hand corner. This redirects to d=muco_ch46fiprpr Chapter 46: Fire Prevention and Protection ARTICLE III. CODE Sec Adoption of the 2012 Edition of International Fire Code.
5 International Codes International Building and Fire Code 2012 Adoption of the 2015 International Codes in process expected effective date of January 1, 2017 in Des Moines. Chapter 9 of both IFC and IBC contain Fire Protection requirements based upon occupancy including sprinkler requirements.
6 International Codes IBC International Building Code (Table ) Section 102.4, states reference codes, standards, and code thereof is an enforceable extension. IBC references: Section 420; Groups I-1 R-1 R-2 R-3 Section 508; Mixed Use & Occupancy Section 509; Incidental Use
7 International Codes IFC International Fire Code (Table ) To determine which standard to use consult the International Fire Code, 903 which addresses Automatic Sprinkler Systems When required by code, buildings or portions thereof shall be equipped with an automatic sprinkler system, sprinklers shall be installed throughout in accordance with NFPA 13 except in (Exempt Locations.)
8 IFC- NFPA 13R NFPA 13R sprinkler systems shall be permitted to be installed throughout Group R occupancies up to and including four stories in height. If Type V construction is used, sprinklers shall be provided for exterior balconies and decks. This is to insure life safety. If a mixed occupancy building contains a Group R occupancy but one of the other occupancies requires a sprinkler system throughout the building in accordance to NFPA 13, NFPA 13R would not be allowed.
9 IFC- NFPA 13D NFPA 13D sprinkler systems shall be permitted in one or two family dwellings, also in group R-3 and R-4 living facilities and townhomes. Prevents flashover in the room of origin, and improves the chance for occupants to escape or be evacuated.
10 IFC Sprinkler Requirements for Residential Occupancies Sprinklers required in any building that contains a Group R fire area. Hotels Apartment Buildings Group homes Dormitories
11 NFPA Standards The 2012 IBC and IFC reference the 2010 versions of NFPA 13 and 13R NFPA 13 Standard for the Installation of Sprinkler Systems, addresses both property protection and life safety. NFPA 13 permits residential sprinklers in high rise apartments. NFPA 13R Standard for the Installation of Sprinkler Systems in Residential Occupancies up to and Including Four Stories in Height (limit 60 ) Address life safety concerns in residential occupancies.
12 NFPA 13 Vs. 13R NFPA 13R applications should consist of dwelling units, multi-family dwellings or dormitories, in which are under 60ft in height. With accessory and incidental residential occupancy's only 10% of a given floor is allowed nonresidential. Example: Laundry room, mechanical closest, swimming pool. Once you go past the 60ft limit or exceed the limitations on accessory or incidental spaces your building is declared a mixed use. If one of the mixed use occupancies would require a sprinkler system throughout the building in accordance with NFPA 13, then a 13R system would not be allowed.
13 NFPA 13 Density NFPA 13 Light Hazard 0.10 GPM Ordinary Hazard (1) 0.15 GPM Ordinary Hazard (2) 0.20 GPM Extra Hazard (1) 0.30 GPM Extra Hazard (2) 0.40 GPM
14 NFPA 13R Density NFPA 13R: A minimum of 0.05 GPM for, excludes QR and EC. In accordance to NFPA 13R; Quick Response and Extended Coverage sprinklers are required to be 0.10 GPM over the entire dwelling unit.
15 Inside Dwelling Units NFPA 13 NFPA 13 requires 4 adjacent sprinklers, without regard to boundaries. These 4 hydraulically most demanding sprinklers shall be: 1) In accordance with minimum flow rate indicated in individual listings. 2) Calculated based on delivering a minimum of 0.1 gpm/ft2 over the design area.
16 Inside Dwelling Units NFPA 13R NFPA 13R, all sprinklers within a compartment, a maximum of 4 adjacent sprinklers, with the greatest hydraulic demand. Compartment, a space completely enclosed by walls and a ceiling. Each wall in the compartment is permitted to have openings to an adjoining space if the openings have a minimum lintel depth of 8 in. from the ceiling and the total width of the openings in a single wall does not exceed 8 ft in width. A single opening of 36 in. or less in width without a lintel is permitted when there are no other openings to adjoining spaces. MINIMUM OPERATING PRESSURE OF 7 PSI FOR BOTH STANDARDS.
17 Outside Dwelling Unit NFPA 13 NFPA 13, When using the room design method or the area under consideration is a corridor; maximum of 5 adjacent sprinklers with a single line of sprinklers or 75 linear ft. which ever is greater. NFPA 13, If a corridor is present, the designer has to calculate the largest room, as well as the 5 sprinklers in the corridor. To determine the greatest demand.
18 Outside Dwelling Unit NFPA 13R NFPA 13R, A corridor shall include up to 4 most hydraulically demanding adjacent sprinklers..in accordance to Sprinklers outside the dwelling units shall be quickresponse, and selection shall be based on the requirements of NFPA 13, except where permitted by , which allows the use of residential sprinklers in corridors leading to the dwelling units.
19 The number of design sprinklers for a corridor or breezeway outside the dwelling unit shall include up to the four most hydraulically demanding adjacent sprinklers.
20 Hose Allowance & Water Supply Duration. NFPA 13 Light hazard Hose 100 gpm Duration 30 minutes Ordinary Hazard Hose 250 gpm Duration minutes Extra Harzard Hose 500 gpm Duration minutes NFPA 13R Hose 100 gpm Duration 30 minutes.
21 IFC 905 & NFPA 14 Standpipes Standpipes are required in buildings to provide quick, convent water source for the fire department. There are three classes of standpipes in which depend on building height, area, occupancy, and extent of automatic sprinkler system. Class 3 standpipes systems shall be installed throughout buildings where the floor level of the highest story is located more than 30ft above the lowest level of the fire department vehicle access. NFPA 14; where two or more standpipes are installed in the same building or section of building, they shall be interconnected. NFPA 14; Class I and Class III standpipes shall be at least 4 in. in size. One or more fire department connections shall be provided for each zone of each Class I or Class III standpipe system.
22 NFPA 13 Combustible Concealed Spaces NFPA 13 requires combustible concealed spaces including attics, floor/ceiling assemblies exterior balconies, and bathrooms to be sprinklered. NFPA 13 does allow certain sprinkler omissions, including, concealed spaces formed by studs or joist with less than 6 between the inside or near edges of the studs, joists, roof, or floor deck; these shall not require sprinkler protection. Concealed spaces filled with noncombustible insulation shall not require sprinkler protection. Concealed spaces over isolated small rooms not exceeding 55ft in area shall not require sprinkler protection. For more omissions refer to chapter 8 of NFPA 13.
23 NFPA 13R Combustible Concealed Spaces NFPA 13R specifies that sprinklers are not required in combustible concealed spaces which are not used for living, storage, or fuel fired equipment. An attic is an example of a combustible concealed space. NFPA 13 requires combustible concealed spaces to be protected by sprinklers. NFPA 13R does not.
24 Residential Building Designed to NFPA 13 Density of.10 GPM Hose Allowance 100 GPM
25 Residential Building Designed to NFPA 13R In accordance to NFPA 13R all sprinklers within a compartment, up to maximum of four adjacent sprinklers, that requires the greatest hydraulic demand. A compartment is a space completely enclosed by walls and a ceiling. Each wall in the compartment is permitted to have openings to an adjoining space if the openings have a minimum lintel depth of 8 in. from the ceiling and the total width of the openings in a single wall does not exceed 8ft in width. A single opening of 36 in. or less in width without lintel is permitted when there are no other openings to adjoining spaces.
26 Residential Building Designed to NFPA 13R
27 Handout & Questions?
28 NFPA 72 Completion Documents The system installer is responsible for record completion. Record of completion is due at least 24 hours prior to inspection. Record of completion forms include: Type of system Name of installer Locations of record drawings Owners manual Test reports Also provides a confirming record of acceptance tests and gives details about the components and wiring of the systems. Fire Alarm and Emergency Communication System Record of Completion
29 NFPA 72 Record of Completion Documents & Intelligibility If you design a voice system you have to test for intelligibility. The testing of a voice system includes intelligibility testing. Record of the intelligibility testing should be submitted with the Record of Completion.
30 NFPA 72 Intelligibility Refresher NFPA , defines intelligibility as the quality or condition of being intelligible. It further states intelligible is capable of being understood; comprehensible; clear. Speech Transmission Index (STI) is a measure of speech transmission quality. The STI measures some physical characteristics of a transmission channel and expresses the ability of the channel to carry across the characteristics of a speech signal. The Common Intelligibility Scale (CIS) was created to map all quantitative intelligibility measurement methods to the same scale so that all different results can be compared. In order to help achieve the needed intelligibility, it is important to ensure the speaker sound output is 15 db over ambient noise. For voice evacuation, speakers ideally should have a frequency range between 150 and 11,000 Hertz (Hz) because this is the frequency range that an adult voice produces.
31 NFPA 72 Intelligibility Average STI of not less than 0.50 (0.70 CIS) Intelligibility meters, which measure either STI or CIS scores, are the most accurate and practical means of conducting intelligibility testing.
32 NFPA 72 Intelligibility Factors that effect intelligibility test results Tolerance of the message generator and amplifier. Loading of the audio amplifiers. Mechanical Excessive voltage drop in the speaker circuit. Vibration Damaged speakers Finishing's in the area. Size of room Distance between speakers.
33 What to Include for Intelligibility Testing You can document the intelligibility test many ways, but must include the following: Scale CIS STI Intelligibility readings for at least all of the test locations identified on the approved fire alarm plans. You can record them on a plan or in a list. Average reading if all of the readings do not meet the minimum.
34 Thank you! Questions?
Committee Input No. 28-NFPA 13R-2013 [ Global Input ]
Page 1 of 6 Committee Input No. 28-NFPA 13R-2013 [ Global Input ] 6.2.2 Outside Dwelling Units. 6.2.2.1 All sprinklers used outside of the dwelling units shall be in accordance with 6.2.2 7.2 and 7.3.
More informationWhat Builders Need to Know about Residential Sprinkler Design
What Builders Need to Know about Residential Sprinkler Design Melisa Rodriguez, P.E., NICET IV Design Services Supervisor, Fire Safety melisa.rodriguez@uponor.com www.uponor-usa.com Agenda Brief history
More informationWhat You Need to Know about Residential Sprinkler Design
What You Need to Know about Residential Sprinkler Design Melisa Rodriguez, P.E., NICET IV Design Services Supervisor, Fire Safety melisa.rodriguez@uponor.com www.uponor-usa.com The Residential Sprinkler
More informationCenter for Life Safety Education
Center for Life Safety Education Fire Sprinklers 101 Introduction, Building Codes, and Water Supplies Reprinted with permission from NFPA 13, Installation of Sprinkler Systems, Copyright 2007, National
More informationFire Prevention Coffee Break Training. May 2017
Fire Prevention Coffee Break Training May 2017 Agenda Introduction Submittals - Phelan Changes to NFPA 13 - Phelan Questions and Answers Open Forum Please welcome our S ummer Intern Charlie Poppe Small
More informationSPRINKLER PROTECTION OF COMBUSTIBLE CONCEALLED SPACES WITH LESS THAN 6 BETWEEN OPPOSITE FACES IN CAVITY.
STATE OF LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS OFFICE OF STATE FIRE MARSHAL CODE ENFORCEMENT AND BUILDING SAFETY 8181 INDEPENDENCE BOULEVARD, BATON ROUGE, LA 70806 800-256-5452 225-925-4920
More informationAUTOMATIC FIRE SPRINKLER SYSTEMS
MCKINNEY FIRE DEPARTMENT FIRE MARSHAL S OFFICE AUTOMATIC FIRE SPRINKLER SYSTEMS These guidelines are to be followed when a business, facility or organization installs an automatic fire sprinkler system
More informationSprinkler Permit Applications
REQUIREMENTS FOR NFPA 13 SYSTEM Building Inspections Sprinkler Permit Applications A complete application for a Sprinkler Permit will comply with the requirements of Chapter 8 of NFPA 13. Hydraulic calculations
More informationPLAN REVIEW CHECKLIST
PLAN REVIEW CHECKLIST Date Documents Submitted: Log No.: File No.: Property Information Building Name: Building Address: Owner s Name: Owner s Address: Owner s Phone: Fax: E-mail: System Designer/Contractor
More informationBuilding & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome!
Building & Fire Code Academy Building Better With Our Greatest Resource Education Welcome! Understanding the Sprinkler System Design Alternatives in the 2015 International Why inspect, test and maintain?
More informationZurn Pex, Inc. Residential Fire Protection Presentation. PEX Plumbing, Radiant Heating and Residential Fire Protection Systems
Residential Fire Protection Presentation Zurn Pex, Inc PEX Plumbing, Radiant Heating and Residential Fire Protection Systems Matt Lawrence BDM-North Central Region 1 Presentation Outline I. IRC Mandate
More informationSingle Room Occupancy Hotel Safety & Stabilization Task Force
Page 1 of 6 Graphics Version Skip to Content Single Room Occupancy Hotel Safety & Stabilization Task Force sfgov residents business government visitors online serviceshelp Single Room Occupancy (SRO) Hotel
More informationAmerican Fire Sprinkler Association. An Introduction to the IBC and IFC
American Fire Sprinkler Association Presents An Introduction to the IBC and IFC October 13, 2005 Speaker Roland Huggins, P.E. Vice President of Engineering and Technical Services American Fire Sprinkler
More informationVILLAGE OF DOWNERS GROVE Report for the Village Council Meeting
ORD 2017-7420 Page 1 of 8 VILLAGE OF DOWNERS GROVE Report for the Village Council Meeting SUBJECT: Adoption of 2015 ICC Building and Fire Codes SUBMITTED BY: Stan Popovich, AICP Director of Community Development
More informationSprinklers in Wood-Frame Construction:
Sprinklers in Wood-Frame Construction: What Architects and Engineers Need to Know Presented by: Brian D. Kuhn Jr., P.E. (MA, CA, DC, 6 others), LEED Green Associate Please add relevant logo here Disclaimer:
More informationWORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES
1 WORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES TABLE 2.1 CONSTRUCTION OF STRUCTURAL MEMBERS AND FLOOR AND ROOF (1) ASSEMBLIES (Applies to each fire zone)
More informationMINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry
MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Fire Alarm Systems Plan Review Checklist Date: Permit Number: Business Name: Address: Fire Alarm System Submittal
More informationInterim Amendments to Ontario s 2012 Building Code Retirement Homes. August 17, 2017
Interim Amendments to Ontario s 2012 Building Code Retirement Homes August 17, 2017 Notice This presentation is intended for general information purposes only. It is not intended as legal or technical
More informationPROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE
PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE Developed by the Midwestern Regional Work Group CONTENTS Item 15 Limited area sprinkler systems Item 20 Scope of IFC Ch 7 Item 21 Fire-resistance-rated
More informationFire Prevention Coffee Break Training. February 2017
Fire Prevention Coffee Break Training February 2017 Agenda FDC s - Lund Standpipes - Phelan Fire Alarm Testing Phelan/Dooley Questions and Answers Open Forum Standpipe requirement Standpipes are required
More informationMontgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040
Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040 SPRINKLER SHOP DRAWINGS 2007 NFPA 13 and 2007 NFPA 24 Project: Listed items require sprinkler
More informationFire Alarm Intelligibility. Chris Nolan
Fire Alarm Intelligibility Chris Nolan chris.nolan@honeywell.com 416-525-9898 Fire Alarm Intelligibility Agenda Definition Codes Factors Design Test 2 What is Voice Intelligibility Definition: A measure
More informationFire Protection Coffee Break Training May 2016
Fire Protection Coffee Break Training May 2016 Introduction High-Rise Requirements Questions and Answers Agenda Overview Site Fire Access Aerial Access Power/Back-up Power Elevators and Access Sprinklers
More informationFIRE SAFETY REQUIREMENTS FOR PRE RESIDENTIAL BUILDINGS OF THREE OR MORE STORIES (DOROTHY MAE ORDINANCE - NO. 158,963)
INFORMATION BULLETIN / PUBLIC - MECHANICAL CODE REFERENCE NO.: LAMC 91.8604 Effective: 6-20-84 DOCUMENT NO. P/MC 2002-005 Revised: 6-15-00 Previously Issued As: MGD #74 FIRE SAFETY REQUIREMENTS FOR PRE-
More informationReview of Residential Fire Sprinkler Systems for One- and Two-Family Dwellings
Review of Residential Fire Sprinkler Systems for One- and Two-Family Dwellings Reprinted with permission from NFPA 13D Installation of Sprinkler Systems in One- and two-family Dwellings and Manufactured
More informationCHAPTER 7 ALTERATIONS LEVEL
CHAPTER 7 ALTERATIONS LEVEL 2 SECTION 701 GENERAL 701.1 Scope. Level 2 alterations as described in Section 404 shall comply with the requirements of this chapter. Exception: Buildings in which the reconfiguration
More informationFire Sprinkler System Design and Installation Requirements
Fire Sprinkler System Design and Installation Requirements The Park City Fire Service District (PCFD) and Park City Municipal Corporation (PCMC) have made the following amendments to the State of Utah
More informationSECTION (13900) - FIRE SUPPRESSION SYSTEMS
PART 1 GENERAL 1.01 SUMMARY SECTION 21 10 00 (13900) - FIRE SUPPRESSION SYSTEMS A. Section Includes: 1. Pipe and Fittings. 2. Sprinklers. B. Related Documents: 1. Marriott s Fire Protection and Life Safety
More informationRecommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region
Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region The following sections, paragraphs, and sentences of the 2015 International Existing
More informationGROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES
[B] APPENDIX SR GROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES The provisions contained in this appendix are adopted by the Building Codes Division of the State of Oregon SECTION SR101
More informationFIRE PROTECTION SYSTEMS
CHAPTER 9 FIRE PROTECTION SYSTEMS > SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall specify where fire protection systems are required and shall apply to the design, installation,
More informationGROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES
[B] APPENDIX SR GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES The provisions contained in this appendix are adopted by the Building Codes Division of the State of Oregon. SECTION SR101 GENERAL
More informationRESIDENTIAL FIRE SPRINKLER SYSTEMS POLICY
RESIDENTIAL FIRE SPRINKLER SYSTEMS POLICY Plan Submittal and Inspection Requirements Revised 01/18/18 All residential fire sprinkler systems within the jurisdiction of the Fire Department shall meet all
More informationEl Reno Fire Department Fire Alarm Plan Review Worksheet
El Reno Fire Department Fire Alarm Plan Review Worksheet This Fire Alarm Plan Review Checklist is provided as a guide to assist with your Fire Alarm Plan Review Submittal requirements. Please contact us
More informationORDINANCE NO
ORDINANCE NO. 2016-14 AN ORDINANCE AMENDING THE CODE OF ORDINANCES, CITY OF BOERNE, TEXAS, BY AMENDING CHAPTER 5 - BUILDINGS AND BUILDING REGULATIONS, ARTICLE VIII, LIFE & SAFETY CODE, SECTION 5-236; AND
More informationNFPA Siemens Industry, Inc. All rights reserved. usa.siemens.com/infrastructure-cities
Fire Alarm and Signaling Code Overview NFPA 72-2010 usa.siemens.com/infrastructure-cities Siemens Building Technologies, Inc. is a Registered Provider with The American Institute of Architects Continuing
More informationSCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL /
SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL 60202 fpeschulte@aol.com 847/866-7479 SPRINKLER PROTECTION BASICS: TYPES OF : SPRAY - standard response - quick response -
More informationNFPA Edition. NFPA 13 (2016 Edition) Hot Topics and NFPA 13 FAQ s. Highlights of 2016 Changes. Storage Commodity Classification 4/29/2014
NFPA 13 2016 Edition NFPA 13 (2016 Edition) Hot Topics and NFPA 13 FAQ s Committees created the First Draft at meetings between July 2013 and December 2013 Balloting ended in early 2014 First Draft decisions
More information2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content
Based on the 2018 International Fire Code, (IFC ) The International Fire Code (IFC ), establishes minimum regulations for fire safety. This handout will identify important changes in the IFC from 2015
More informationTABLE OF CONTENTS ADOPTED FIRE CODES... 3 AFPD SERVICE AREA... 3 SITE AND DEVELOPMENT SUBMITTAL REQUIREMENTS... 4 PLAN REVIEW FEES...
TABLE OF CONTENTS ADOPTED FIRE CODES... 3 AFPD SERVICE AREA... 3 SITE AND DEVELOPMENT SUBMITTAL REQUIREMENTS... 4 PLAN REVIEW FEES... 4 SITE AND DEVELOPMENT PLAN REVIEW TURNAROUND TIMES... 4 DEVELOPMENT
More informationHeathcare Interpretations Task Force
Healthcare Interpretations Task Force MEMORANDUM TO: FROM: Heathcare Interpretations Task Force Robert Solomon DATE: May 30, 2014 SUBJ: HITF Meeting Agenda and Meeting Room Location Information Attached
More informationNFPA 45 NFPA 211 NFPA 1600
NFPA 45 NFPA 211 NFPA 1600 Prepared by: William E. Koffel, P.E., FSFPE Expertly Engineering Safety From Fire 1 Objectives Overview of the NFPA process Understand the scope and application of NFPA 45, NFPA
More informationFIRE INSPECTION GUIDELINES FOR FOSTER GROUP HOME PARENTS Effective June 1, 2002, Update September 2011
HCFMO Harris County Fire Marshal M.S. Montgomery Fire Marshal FIRE INSPECTION GUIDELINES FOR FOSTER GROUP HOME PARENTS Effective June 1, 2002, Update September 2011 EFFECTIVE JANUARY 1, 2007 These guidelines
More informationTaming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes JENSEN & HALSTEAD LTD.
Taming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes Comparing the Codes: NFPA 101 Life Safety Code (2000) (NFPA) International Building Code (2012) (IBC) Chicago
More informationSTANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT UPRIGHT SPRINKLER VK535 (K11.2) TECHNICAL DATA
Page of 5. DESCRIPTION Viking EC/QREC Ordinary Hazard ELO Fusible Element Sprinkler VK535 is a thermosensitive spray sprinkler available in several different finishes and temperature ratings to meet varying
More informationFire Prevention Coffee Break Training November 2014
Fire Prevention Coffee Break Training November 2014 Agenda Introduction/ What do we want? - Fire Marshal Lund FAQ s and Alternative Design FPE Phelan Permit to Inspect, Maintain, & Service FP Appliances
More informationBurnsville Fire Department 100 Civic Center Pky, Burnsville, MN Fire Marshal: FAX:
Burnsville Fire Department 100 Civic Center Pky, Burnsville, MN 55337 Fire Marshal: 952-895-4579 FAX: 952-895-4512 2018 FIRE SUPPRESSION PERMIT APPLICATION PERMIT Wet System Dry System Cooking Hood Clean
More informationSENJU SPRINKLER CO.,LTD. Residential Flush Pendent Sprinkler Model ZN-RES,K=4.2 (SIN / SS4421) (PTFE gasketed orifice seal design) General Description
Page:1 of 5 SENJU SPRINKLER CO.,LTD. Residential Flush Pendent Sprinkler Model ZN-RES,K=4.2 (SIN / SS4421) (PTFE gasketed orifice seal design) General Description The Model ZN-RES Residential Flush Pendent
More information2012 International Fire Code Significant Changes. IFC Background. Purpose IBC and 2012 NFPA 101 Significant Means of Egress Changes
2012 International Fire Code Significant Changes Andrew M. Schneider, P.E. Senior Fire Protection Engineer aschneider@koffel.com Koffel Associates, Inc. www.koffel.com Expertly Engineering Safety From
More informationResidential Flush Horizontal Side-Wall Sprinkler Model HF-RES,K=4.2 (SIN / SS4423) (PTFE gasketed orifice seal design)
Page:1 of 5 Residential Flush Horizontal Side-Wall Sprinkler Model HF-RES,K=4.2 (SIN / SS4423) (PTFE gasketed orifice seal design) General Description The Model HF-RES Residential Flush Horizontal Side-Wall
More informationBy: Russell Bainbridge March 18th, 2016 FPE 596
By: Russell Bainbridge March 18th, 2016 FPE 596 Egress Analysis and Design California Polytechnic State University's Engineering IV building Fire Detection, Alarm and Communication Systems A warehouse
More informationRetain. Retain. Retain. Board Advisory. Board Advisory. Retain. Disposition. (Statute, Rule, FBC, Industry)
Florida Specific Amendment Code Reference NFPA 101 Anytime a reference is made to NFPA 1 or NFPA 101 within this Code, it shall be 1.1.1.1 the Florida specific version of NFPA 1 and NFPA 101. The Florida
More informationAPPENDIX A International Building Code Amendments
APPENDIX A 2012 International Building Code Amendments The following sections, paragraphs, and sentences of the 2012 International Building Code are hereby amended as follows: Standard type is text from
More informationFIRE PREVENTION AND PROTECTION*
Chapter 30 (Replaced old ordinance September10, 2012) FIRE PREVENTION AND PROTECTION* * Cross References: Buildings and building regulations, ch. 14; environment, ch. 26; manufactured homes and trailers,
More information2018 NICET Code Transition Changes
2018 NICET Code Transition Changes NICET will be transitioning to newer codes accepted in their exams in mid-october 2018, specifically: NFPA 72 2016 NFPA 70 2014 IBC 2015 NFPA 101 2015 Here are some changes
More informationstandard/quick response extended coverage light and ordinary hazard elo sprinklers
January 27, 2012 Sprinkler 83a 1. DESCRIPTION Viking EC/QREC Light and Ordinary Hazard Extra-Large Orifice Sprinklers VK532 and VK534 are thermosensitive spray sprinklers available in several different
More informationBUILDING CODE OF THE CITY OF NEW YORK. New York City Department of Buildings 4 June 2007
BUILDING CODE OF THE CITY OF NEW YORK New York City Department of Buildings 4 June 2007 Fatma Amer, PE, Deputy Commissioner, Technical Affairs James Colgate, RA, Executive Architect John Lee, RA Keith
More informationMECKLENBURG COUNTY FIRE MARSHAL S OFFICE
Effective Date: 11/01/02 Purpose: MECKLENBURG COUNTY To establish a set of guidelines for performance testing of all newly installed or upgraded fire alarm systems in order to ensure that all devices and
More informationLarge Family Daycare Guideline
Moreno Valley Fire Department Fire Prevention Bureau Large Family Daycare Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: April 10, 2017 Large Family Daycare Guideline Purpose
More informationSite Plans. Fire Code Requirements
Site Plans Fire Code Requirements Outline Before you start Critical building information drives requirements Access Requirements Access, aerial access, road design, remoteness, fire lanes, residential
More informationLaboratories and Hazardous Materials. Company Overview
Laboratories and Hazardous Materials Don E. Contois, P.E. Sam Sinapi Company Overview R.W. Sullivan Engineering (RWS) was established in 1945 and currently has 95 employees. RWS is a full service engineering
More informationNFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES
NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES Sharon S. Gilyeat, P.E., Principal Koffel Associates, Inc. www.koffel.com sgilyeat@koffel.com Expertly Engineering Safety From Fire
More informationec/qrec ordinary hazard upright and pendent sprinklers vk570 and vk572 (k14.0)
Sprinkler 83h 1. DESCRIPTION Viking Standard/Quick Response Extended Coverage Ordinary Hazard (ECOH) Upright Sprinkler VK570 and Pendent Sprinkler VK572 are thermosensitive glass bulb spray sprinklers
More informationS000 SITE REVIEW APPR NO. FIRE CODE COMPLIANCE ITEM
APPR NO. FIRE CODE COMPLIANCE ITEM S000 S001 S005 (Automobile Access Aisle) shall be a minimum of 5 ft wide, a common access aisle may be shared by 2 vehicles. Surface slopes shall not exceed 1:50(2%)
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD STANDPIPE SYSTEMS PURPOSE This standard outlines the general requirements for the installation of standpipe systems. CODE REFERENCES
More informationORDINANCE NUMBER
ORDINANCE NUMBER 2010-2 AN ORDINANCE AMENDING THE ORDINANCE 2007-4 REQUIRING THE INSTALLATION OF AUTOMATIC FIRE SUPPRESSION SYSTEMS IN CERTAIN STRUCTURES IN THE CITY OF STARKVILLE, OKTIBBEHA COUNTY, MISSISSIPPI
More informationPlan Submittal Checklist
City of Aurora Public Works Department HIGH-PILED COMBUSTIBLE STORAGE Plan Submittal Checklist Building Division 15151 E. Alameda Parkway, Ste 2400 Aurora, CO 80012 303-739-7420 Fax: 303-739-7551 Project
More informationFire Suppression Introduction Contact Information
Contact Information Jeffrey Mayers Fire Safety Engineering Manager Georgia State Fire Marshal s Office 404-617-8515 E-mail: jmayers@sfm.ga.gov 1 Goal of This Seminar: Hierarchy of Codes List reference
More informationSECTION 915 CARBON MONOXIDE DETECTION
SECTION 915 CARBON MONOXIDE DETECTION 915.1. General. Carbon monoxide alarms and carbon monoxide detectors shall be installed in buildings as required in accordance with Section 915.2 for residential buildings
More informationFire Sprinklers The Ultimate Fire Fighters Eric Skare
Fire Sprinklers The Ultimate Fire Fighters Eric Skare Presentation Description The residential fire problem has changed over the last several decades. Although some aspects have improved, fires in newly
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved
More informationTable OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS
901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.
More informationFIRE PROTECTION SYSTEMS
CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall specify where fire protection systems are required and shall apply to the design, installation and
More informationELEVATORS. Integration of Codes between Fire Alarm, Sprinklers, and Elevators 12/5/2017
12/5/2017 1 ELEVATORS Integration of Codes between Fire Alarm, Sprinklers, and Elevators Encore Electric Inc. Prepared By John McGovern and Jeffrey Engelstad 12/5/2017 Encore Electric Inc. 2 Agenda Basics
More informationSignificant Changes to the 2012 IFC Semiconductor Fabrication Facilities. Scott Stookey Senior Technical Staff International Code Council, Austin TX
Significant Changes to the 2012 IFC Semiconductor Fabrication Facilities Scott Stookey Senior Technical Staff International Code Council, Austin TX Introduction This presentation reviews the significant
More information2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.
2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is
More informationORDINANCE NUMBER~-07
ORDINANCE NUMBER~-07 AN ORDINANCE AMENDING TITLE 14 (BUILDINGS AND CONSTRUCTION) OF THE MASON COUNTY CODE ADDING CHAPTER 14.18 ENTITLED INTERIM FIRE FLOW STANDARDS FOR GROUP A WATER SYSTEMS AN ORDINANCE
More informationHIGH-RISE RETROFIT ORDINANCES - NO and NO
INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: LAMC 91.8604 Effective: 9-06-90 DOCUMENT NO. P/BC 2002-054 Revised: 4-15-03 Previously Issued As: MGD 88 HIGH-RISE RETROFIT ORDINANCES - NO.
More informationJanuary 1, 2014 Mandatory Effective Date
2013 Kentucky Building Code Highlights Winnie Blythe, Technical Advisor Dept. of Housing, Buildings, and Construction winnie.blythe@ky.gov www.dhbc.ky.gov 502-573-0373 January 1, 2014 Mandatory Effective
More information4/13/2015. Everything a firefighter wants to tell a design professional or building code official, in one hour.
Everything a firefighter wants to tell a design professional or building code official, in one hour. 1 2 3 1 4 The job of the fire department is to put the wet stuff on the red stuff. 5 Job #1. of the
More informationSprinkler Standards Proposed Technical Changes
Sprinkler Standards 2002-2007 Proposed Technical Changes Featuring Speaker Bob Caputo Consolidated FireProtection, Inc August 9, 2006 1 1 SPEAKER Bob Caputo Consolidated FireProtection, Inc Bob Caputo
More informationEC/QREC ORDINARY HAZARD PENDENT SPRINKLER VK572 (K14.0) TECHNICAL DATA
Page 1 of 6 1. DESCRIPTION Viking Standard/Quick Response Extended Coverage Ordinary Hazard (ECOH) Pendent Sprinkler VK572 is a thermosensitive glass bulb spray sprinkler with a 14.0 (202 metric*) nominal
More informationE x t E N d e d Co v e r ag e S p r i n k l e r s. Office Buildings Hotels Hospitals Libraries. High-Piled Storage Big-Box Retailing
Extended Coverage Sprinklers Extended Coverage Sprinklers are intended for the protection of areas larger than those specified in standard installation rules and for specific light, ordinary, or extra
More informationModule 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements
Module 3 Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements 1 WATER-BASED SUPPRESSION SYSTEMS-PART TWO This module covers: 1. Ohio Building Code requirements and when and why
More informationFire Prevention Coffee Break Training. February 2016
Fire Prevention Coffee Break Training February 2016 Agenda Flow Tests Phelan Submittals - Phelan Inspection & Testing Dooley Questions and Answers Open Forum Change in Flow Test Policy The responsible
More informationRESIDENTIAL CARE USER GUIDE UPDATES TO MANITOBA BUILDING/FIRE CODE:
RESIDENTIAL CARE USER GUIDE UPDATES TO MANITOBA BUILDING/FIRE CODE: Manitoba Regulation 221/2015 and Manitoba Regulation 222/2015 DATE: MARCH 17, 2016 1. INTRODUCTION On April 1, 2016, new building and
More informationMOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Alarm System Plan Review 2009 International Fire Code and 2010 NFPA 72 Date of Review // BLD201 - Project Address: Project Name: _ Professional
More informationRichard B. Alpert, P.E. Senior FPE, Clark Nexsen
Richard B. Alpert, P.E. Senior FPE, Clark Nexsen Clark Nexsen is a Registered Provider with The American Institute of Architects Continuing Education Systems (AIA/CES). Credit(s) earned on completion of
More informationLOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION
CHAPTER 23.45 Sections LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION 23.45.100 Local amendments to the International Fire Code, 2006 Edition... 2 23.45.102.1 Construction and design provisions...
More informationCalifornia Fire Code (CFC) Part III contains requirements. Building and Equipment Design Features PART. Chapters 5 through 19
PART 3 Building and Equipment Design Features Chapters 5 through 19 Chapter 5 Fire Service Features No changes addressed Chapter 6 Building Services and Systems Chapter 7 Fire-Resistance-Rated Construction
More informationFire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY
Fire Department HEADQUARTERS 4410 Cathedral Oaks Road Santa Barbara, CA 93110-1042 (805) 681-5500 FAX: (805) 681-5563 Michael W. Dyer Fire Chief County Fire Warden Eric Peterson Deputy Fire Chief CODE
More informationMAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS
FIRE CODE BULLETIN December 2004 97 FCB 018 (R1) Page 1 of 5 BACKGROUND: MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS Fire protection service companies are
More informationThe Use of Public Address System to Improve Tunnel Safety - Current Practices. Lim Hock Tay
The Use of Public Address System to Improve Tunnel Safety - Current Practices Lim Hock Tay Content 1 Introduction 2 3 Overview of Survey Responses Discussion 4 Conclusion PIARC International Conference
More informationEC/QREC ORDINARY HAZARD UPRIGHT SPRINKLER VK570 (K14.0) TECHNICAL DATA
Page 1 of 5 1. DESCRIPTION Viking Standard/Quick Response Extended Coverage Ordinary Hazard (ECOH) Upright Sprinkler VK570 is a thermosensitive glass bulb spray sprinkler with a 14.0 (202 metric*) nominal
More informationCOMPLIANCE ALTERNATIVES
CHAPTER 12 COMPLIANCE ALTERNATIVES SECTION 1201 GENERAL 1201.1 Scope. The provisions of this chapter are intended to maintain or increase the current degree of public safety, health, and general welfare
More informationPERFORMANCE COMPLIANCE METHODS
CHAPTER 13 PERFORMANCE COMPLIANCE METHODS SECTION 1301 GENERAL 1301.1 Scope. The provisions of this chapter shall apply to the alteration, repair, addition and change of occupancy of existing structures,
More informationTHE PEOPLE OF THE CITY OF LOS ANGELES DO ORDAIN AS FOLLOWS:
ORDINANCE N0. 1_8_-1_7_5_7 An ordinance amending Article 4 of Chapter IX of the Los Angeles Municipal Code and incorporating by reference the 2010 Edition of the California Plumbing Code (C.P.C.) with
More informationCODE TECHNOLOGIES COMMITTEE NURSING CARE FACILITIES WORK GROUP APPROVED CODE CHANGE DRAFTS CODE GROUP B
CODE TECHNOLOGIES COMMITTEE NURSING CARE FACILITIES WORK GROUP APPROVED CODE CHANGE DRAFTS CODE GROUP B This report includes 3 code change proposal from the CTC Nursing Care Facilities Coordination committee
More informationAgency for Health Care Administration
Page 1 of 92 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS Type Memo Tag FED - KA100 - General Requirements - Other Title
More informationFlorida Building Code 2010
Introduction Florida Building Code 2010 Chapter 9 Fire Protection Systems This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors are familiar with
More information