Sheetz Inc. Fire Protection Service Guidelines

Size: px
Start display at page:

Download "Sheetz Inc. Fire Protection Service Guidelines"

Transcription

1 Sheetz Inc. Fire Protection Service Guidelines Overview The following are guidelines for Sheetz Fire Protection Services for the 2016/2018 contract year. Each key area is listed below with the appropriate details. Upon arrival at the site, Provider MUST check in with Store manager on duty. The manager will assign the work to be done. Upon completion of work, the manager on duty will inspect the work, and, if satisfied, provide a receipt showing the work performed. The receipt is the Provider s proof of service and all payment will be made based solely on POS receivings. Payment will be issued weekly at 2%, 15 day terms and will be deposited directly to Provider s account. For example, services provided in the first week of a month will be paid (less a 2% discount) on the second Thursday following the first week. NO PAPER INVOICES WILL BE ACCEPTED FROM PROVIDER. Provider must furnish their Bank information for Direct Deposit of payments. Fire alarm panel testing scope of work (NFPA-72) (Monitored fire alarm panels) Quarterly requirements Visual inspection of all fire sprinkler devices connected to the alarm. This includes water flow switches and valve tamper switches. Test of fire pump monitored points (loss of phase, phase reversal, pump running etc.) Semi-annual requirements Test of sprinkler waterflow switches (flow water or manually trip flapper) Test of sprinkler valve tamper switches (operate valves) Visual inspection lead-acid battery (swelling of loose connections) Test batteries-load voltage Annual requirements Test and visual inspection of panel functionality, LED s, fuses, etc. Test panel battery charger Battery discharge test Test & visual inspection of horns, strobes, chimes, & bells, etc. Test & visual inspection of smoke detectors Test & visual inspection of heat detectors Test & visual inspection of duct smoke detectors Test & visual inspection of electromechanical releasing devices (solenoid) Test & visual inspection of voice evacuation equipment Other Replace sealed leac-acid batteries every 5 years or as test results require Smoke detector cleaning: as test results require. Many newer fire alarm panels are capable of issuing maintenance alerts and adjusting sensitivity as the detector becomes dirtier. Both of these features reduce false alarms. Smoke & heat detector replacement recommended after 10 years of service Any and all parts used may NOT be priced separately, but must be included in the bid price Any deficiencies found must be reported to the store manager on duty immediately

2 (Unmonitored fire alarm panels) Quarterly requirements Test of panel lamps & led s, fuses, primary power supply, and interface equipment Visual inspection of all fire sprinkler devices connected to the alarm. This includes water flow switches and valve tamper switches Test of fire pump monitor points (loss of phase, phase reversal, pump running etc.) Semi-annual requirements Test of sprinkler water flow switches (by flowing water) Test of sprinkler valve tamper switches Visual inspection lead-acid battery (swelling or loose connections) Test batteries-load voltage Annual requirements Battery discharge test (30 minutes) Test & visual inspection of horns, strobes, chimes, & bells, etc. Test & visual inspection of smoke detectors Test & visual inspection of duct smoke detectors Test & visual inspection of electromechanical releasing devices (solenoid) Test & visual inspection of voice evacuation equipment Other Replaced sealed lead-acid batteries every 5 years or as test results require Smoke detector cleaning: as test results require. Many newer fire alarm panels are capable of issuing maintenance alerts and adjusting sensitivity as the detector becomes dirtier. Both of these features reduce false alarms. Smoke & heat detector replacement recommended after 10 years of service Any and all parts used may NOT be priced separately, but must be included in the bid price Any deficiencies found must be reported to the store manager on duty immediately Please be aware that the above listed is abbreviated for clarity. Please refer to NFPA-72 for the complete list of devices, test frequencies, and procedures. Kitchen fire suppression inspection and test scope of work (NFPA 17A, 2009 Edition, Chapter 7 and in accordance with the manufacturer s listed installation and maintenance manual) Inspections shall be performed twice per year. The initial inspection must be completed no sooner than 5 months, and no later than 6 months from the date of last inspection, which will be provided by Sheetz corp. office. Inspections may not be performed during the hours of 11am to 1pm. Contractor must check in with store management prior to initiating service. All fusible links shall be replaced during every inspection.

3 Contractor shall: test all remote pulls test automatic (trip test) and manual release of system verify mechanical operation of system. verify gas shutoff (where applicable). verify electrical shutoff. check system components for cleanliness. test grease build up levels using the International Kitchen Exhaust Cleaning Association (IKECA) grease depth gauge comb (see pictures below). Any system found to be at critical or at the maximum depth must be reported to Sheetz corporate office. Contractor will provide photo validation of depth test. restore system to normal operation. reset system. install new tamper seals. remove cylinder, verify agent weight, and hydrostatic test dates. verify piping to manufacturers specifications (piping/bracing). verify that nozzle caps are intact (for metal caps only). Inspect nozzles to assure that they are properly adjusted for cooking surface coverage and free of obstructions and debris so that they will perform correctly. Install record tag. Verify that owner s manual is on site. Any and all parts used may NOT be priced separately, but included in the bid price. This includes, nozzle caps, fusible links, Co2 cartridge, inspection tag, tamper seal(s), etc. Portable Fire Extinguisher Inspection and Test Scope of Work (NFPA 10, 2010 edition, Chapter 7) Inspection shall occur annually Extinguisher inspections shall be performed at the same time as one of the Kitchen Inspection listed above. Contractor shall: Ensure that facility meets current NFPA guidelines. Remove extinguisher from hanger. Check gauge pressure. Check gauge condition and compatibility. Check weight. Visually inspect for external damage. Check date of manufacture. Check last hydro test date (12 years). Check last 6 year maintenance inspection. Check valve and shell for damage or corrosion Remove nozzle. Check nozzle condition for cracks or splits. Check nozzle threads. Check conditions of horn (if applicable).

4 Check for obstructions. Break seal and remove pin. Check upper and lower handles. Check valve opening for powder or any foreign matter. Replace locking pin and replace with new tamper seal. Clean shell with spray. Replace nozzle. Check band assembly. Tag extinguisher with new annual certification tag. View hazard. Verify that the units correspond with the hazard. Verify that the unit is properly hung with the manufacturer s hanger. Ensure that the unit is properly placed with the normal path of travel. Ensure the unit use is properly defined with class decal. Verify that the unit operation instructions are clear and visible. Ensure that the unit is visible and unobstructed. Replace on hanger. Any and all parts used may NOT be priced separately, but included in the bid price. This includes pull pins, tags, tamper seals, etc. Portable Fire Extinguisher Service and Repair Service calls for portable fire extinguishers and components (cabinets, covers, hangers, etc) will be scheduled by Sheetz corporate office. Contractor must check in with store management prior to initiating service. Each service must be priced separately. Travel charges must be priced separately. Contact Numbers: Contractor must have the capability to provide twenty-four hour emergency service. Contractor must furnish Sheetz with a list of contact telephone and cell phone numbers. Damages: Should the contractor be unwilling or unable to repair or restore damages, contractor shall be invoiced for, and obligated to pay, all actual costs associated with use of an alternative repair contractor. All charges will be invoiced to the contractor responsible for damages. Pricing: All prices must be listed in dollar amounts and be in effect through August 31, Service Expectations and Procedures: Upon arrival at store, store management will assign services that are needed. After the work is completed to the satisfaction of the manager on duty, these services will be entered in to the store POS and a receipt will be given to contractor. Receipt will list services and time of service and will serve as proof that service was provided. No work orders are to be signed by store personnel. Payment: Sheetz will pay contractor based solely on services received at store POS. Payment will be issued weekly at 2%, 15 day terms and will be deposited directly to contractor s account. For

5 example, services provided in the first week of a month will be paid (less a 2% discount) on the second Thursday following the first week. NO PAPER INVOICES WILL BE ACCEPTED FROM CONTRACTOR. Insurance: At all times during the term, the Contractor shall maintain comprehensive general liability insurance written on a comprehensive basis to provide all major divisions of coverage. The insurance shall be in the minimum amount of $2,000,000 general aggregate limit; $2,000,000 products/completed operations aggregate limit; $1,000,000 personal injury and advertising injury limit; $1,000,000 per occurrence and $1,000,000 fire damage per fire. Worker s compensation insurance in compliance with all applicable statutory requirements, including employer s liability in the minimum amount of $1,000,000 each accident, $1,000,000 disease-policy limit and $1,000,000 disease-each employee. All-risk property insurance to cover full replacement value of Contractor s personal property, improvements and betterments and Sheetz property in Contractor s care, custody, or control. Automobile liability insurance covering owned, non-owned, and hired vehicles in a minimum amount of $1,000,000 for each accident-combined single limit for bodily injury and property damage. All policies shall name Sheetz Inc. and its subsidiaries as additional insured. Contractor shall be obligated to furnish a properly executed original Certificate of Insurance prior to execution of the agreement. No work shall be undertaken by the contractor until a contract has been properly executed.

MERAMEC VALLEY R-III SCHOOL DISTRICT 126 North Payne Street Pacific, MO

MERAMEC VALLEY R-III SCHOOL DISTRICT 126 North Payne Street Pacific, MO MERAMEC VALLEY R-III SCHOOL DISTRICT 126 North Payne Street Pacific, MO 63069 636-271-1400 REQUEST FOR PROPOSAL FIRE EXTINGUISHER/KITCHEN HOOD INSPECTIONS FOR ADDITIONAL INFORMATION CONTACT: Joel Cracchiolo,

More information

*** Inspection *** Please identify yourself as a Cintas representative when arriving onsite.

*** Inspection *** Please identify yourself as a Cintas representative when arriving onsite. Tech Clock-In/Out IVR: 1-877-349-2906 Job #: Tech ID #: 2902 FP Service Instructions Job #: *** Inspection *** You must clock in and out of this job through Cintas's IVR phone system! Call 1-877-349-2906

More information

June 2018 Safety Meeting Fire Extinguishers Part I

June 2018 Safety Meeting Fire Extinguishers Part I June 2018 Safety Meeting Fire Extinguishers Part I The portable fire extinguisher, one of the most common fire protection appliances in use today, is found in fixed facilities and on propane vehicles.

More information

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment February 2017 Alberta Fire Code safety equipment maintenance requirements: The Black Diamond Fire Department has

More information

COUNTY OF ROCKLAND Department of General Services Purchasing Division

COUNTY OF ROCKLAND Department of General Services Purchasing Division Department of General Services Purchasing Division Title: Contract Period: Fire Extinguishers and Suppression Systems-Inspection, Testing, Maintenance, Repair and Recharging 3/1/18 through 2/28/19 with

More information

Revised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required*

Revised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required* 1.0 Description of Services Required: Revised March 2015 Fire Alarm Systems Verification Schedule I(A) Services *Manditory Site visit required* Perform the annual fire alarm system and sprinkler system

More information

Winnipeg Fire Department Fire Prevention Branch

Winnipeg Fire Department Fire Prevention Branch Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of

More information

Model Policy On Portable Fire Extinguishers (Ontario Version)

Model Policy On Portable Fire Extinguishers (Ontario Version) Model Policy On Portable Fire Extinguishers (Ontario Version) Every workplace needs a policy ensuring the appropriate selection, use, storage and maintenance of fire extinguishers. OHS managers in any

More information

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Plan Review

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Plan Review MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Plan Review Minooka Fire Protection District Maintaining Your Fire Safety Systems Fire continues to be a major threat

More information

OWNER'S OPERATION AND MAINTENANCE MANUAL

OWNER'S OPERATION AND MAINTENANCE MANUAL OWNER'S OPERATION AND MAINTENANCE MANUAL P/N 15064 Amerex Industrial Dry Chemical Fire Suppression System MODELS IS18ABC (18 lb. ABC) / IS35ABC (35 lb. ABC) / IS45ABC (45 lb. ABC) / Manufactured by: AMEREX

More information

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY Revision No.: 3 Page 1 of 6 I. PURPOSE This policy establishes the steps required for performing the monthly fixed systems inspections and the semi-annual systems testing. Fixed systems include; wet chemical

More information

INSPECTION AND TESTING FORM

INSPECTION AND TESTING FORM INSPECTION AND TESTING FORM Date: Time: SERVICE ORGANIZATION Name: Address: Representative: License No.: MONITORING ENTITY Contact: Monitoring Account Ref. No.: TYPE TRANSMISSION McCulloh Multiplex Digital

More information

2-SUPPRESSION REQUIREMENTS - CODE REQUIRED INSPECTIONS TEST Page 1 of 7

2-SUPPRESSION REQUIREMENTS - CODE REQUIRED INSPECTIONS TEST Page 1 of 7 WET SPRINKLER Monthly Wet Sprinkler 2-SUPPRESSION REQUIREMENTS - CODE REQUIRED INSPECTIONS TEST Page 1 of 7 VISUALS [per NFPA 25-1998 ed] 1. Gauge (Ck for Condition, Normal Pressure) [per 2-2.4.1] 2. Valves

More information

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL SECTION 21 13 16 DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

Building Self-Inspection Program

Building Self-Inspection Program Building Self-Inspection Program www.tridentinsurance.net Lines of Business: Property, General Liability, Worker s Compensation, Public Official Liability Risk Control Strategy/Key Issues: Reduce physical

More information

SPE Exhibitor Appointed Contractor Manual

SPE Exhibitor Appointed Contractor Manual SPE Exhibitor Appointed Contractor Manual What is an Exhibitor Appointed Contractor? An Exhibitor-Appointed Contractor (EAC) is any person or company other than the designated official or exclusive contractors

More information

109-B Concord Drive Casselberry, FL DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72. Owner s Address: Owner's Phone Number:

109-B Concord Drive Casselberry, FL DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72. Owner s Address: Owner's Phone Number: 109-B Concord Drive Casselberry, FL 32707 407.830.6500 DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72 Pg 1 of 4 Equity One 11180600 Owner/Representative: WO#: _Customer#: 1550 NE Miami Garden Dr

More information

NASSAU COUNTY FIRE PROTECTION PERMIT APPLICATION

NASSAU COUNTY FIRE PROTECTION PERMIT APPLICATION BUILDING PERMIT# Revised 6/30/15 AP# PERMIT # Cost $ Check# Receipt# NASSAU COUNTY FIRE PROTECTION PERMIT APPLICATION 5 TH EDITION (2014) OF THE FLORIDA BUILDING CODE IS IN EFFECT THE 2012 FLORIDA FIRE

More information

Global Property. SEMIANNUAL FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:

Global Property. SEMIANNUAL FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location: Global Property SEMIANNUAL FIRE PROTECTION EQUIPMENT INSPECTION REPORT Plant: Date of Inspection Location: Inspected By: Reviewed By CONTROL VALVES (If Valves are Not Locked Open or Electronically Supervised

More information

FIRE & LIFE SAFTEY STANDARD

FIRE & LIFE SAFTEY STANDARD Title: Effective Date: 01/01/14 Revised Date: 1/1/14 Code References: Title 16, Chapter 16.16 of the Roseville Municipal Code, NFPA 72 Note: This standard is a summary of Fire Department clarifications

More information

Types of Detection. Fusible Link Detection - Most Common

Types of Detection. Fusible Link Detection - Most Common Types of Detection Fusible Link Detection - Most Common Types of Detection Electric Detection Types of Detection Pneumatic Detection-Tubing Pneumatic Tubing 3 Year Service life Survey Hazard 1) List all

More information

New Construction Fire Inspection Process

New Construction Fire Inspection Process New Construction Fire Inspection Process This document is intended to provide the Owner, Designer, and/or Contractor of new construction with an outline of required fire inspections and with the specific

More information

Facilities Management

Facilities Management Facilities Management Policy Number: 700.4 Title: Fire Protection & Life Safety Inspection Policy Implementation Date: August 1 st, 2008 Last Revised: September 14 th, 2017 Last Audited: August, 2017 Introduction

More information

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE GENERAL INDUSTRY SAFETY STANDARDS PART 8. PORTABLE FIRE EXTINGUISHERS

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE GENERAL INDUSTRY SAFETY STANDARDS PART 8. PORTABLE FIRE EXTINGUISHERS DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE GENERAL INDUSTRY SAFETY STANDARDS (By authority conferred on the director of the department of licensing and regulatory affairs by sections

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST FIRE AND LIFE SAFETY SYSTEMS FOR STRUCTURES FIVE OR MORE STORIES IN HEIGHT AND LESS THAN 75 FEET IN HEIGHT FROM THE POINT

More information

Checklist For Building Inspection & Fire Safety

Checklist For Building Inspection & Fire Safety INSPECTION CHECKLIST Date of Inspection: Location/Address: Weather Condition: Inspector: AFTER COMPLETING YOUR INSPECTION, TRANSFER YOUR CONCERNS/OBSERVATIONS TO THIS AREA Facility: Name: Staff Contact:

More information

FIRE SAFETY AND PREVENTION POLICY

FIRE SAFETY AND PREVENTION POLICY Effective Date: July 26, 2011 Supersedes /Amends: VRS-49/April 2006 Originating Office: Office of the Vice-President, Services Policy Number: VPS-49 PREAMBLE Concordia University (the University ) has

More information

Service Requirements SEMI- ANNUAL ANNUALLY OTHER REF. REQUIREMENT

Service Requirements SEMI- ANNUAL ANNUALLY OTHER REF. REQUIREMENT 58 Fire protection equipment requires care and maintenance at scheduled intervals to assure it will operate properly and safely when needed. Only personnel who are trained and qualified to maintain the

More information

Evaluating Your Property and Work for Safety Hazards

Evaluating Your Property and Work for Safety Hazards Evaluating Your Property and Work for Safety Hazards One of the best ways to reduce the potential for insurable losses arising on or from your premises is to ensure that unsafe conditions and practices

More information

PURPLE K POWDER EXTINGUISHERS INSTALLATION, OPERATION, MAINTENANCE AND RECHARGE MANUAL

PURPLE K POWDER EXTINGUISHERS INSTALLATION, OPERATION, MAINTENANCE AND RECHARGE MANUAL PURPLE K POWDER EXTINGUISHERS INSTALLATION, OPERATION, MAINTENANCE AND RECHARGE MANUAL NO. 05602 FOR AMEREX STORED PRESSURE, HAND PORTABLE DRY CHEMICAL FIRE EXTINGUISHERS. ABC (Ammonium Phosphate Base)

More information

Basic Vehicle Fire Protection Manual

Basic Vehicle Fire Protection Manual Basic Vehicle Fire Protection Manual Basic Vehicle Fire Protection Manual TABLE OF CONTENTS Introduction... 3 System Operation...... 5 Component Overview.... 7 Operator Controls Control Panel.........

More information

Skilled Healthcare Documentation Requirements Life Safety and Fire Protection

Skilled Healthcare Documentation Requirements Life Safety and Fire Protection DATE OF EVALUATION: FACILITY NAME: FACILITY ADDRESS: ADMINISTRATOR: MAINTENANCE DIRECTOR: All required documentation must be written and saved for at least 2 years and some documentation may be required

More information

SERVICE MANUAL (v1) UL / ULC. WET CHEMICAL HAND PORTABLE RESTAURANT KITCHEN FIRE EXTINGUISHERS Model: SF-6LK / WBDL-6LK

SERVICE MANUAL (v1) UL / ULC. WET CHEMICAL HAND PORTABLE RESTAURANT KITCHEN FIRE EXTINGUISHERS Model: SF-6LK / WBDL-6LK STRIKE FIRST CORPORATION AKC SERVICE MANUAL (v1) UL / ULC WET CHEMICAL HAND PORTABLE RESTAURANT KITCHEN FIRE EXTINGUISHERS Model: SF-6LK / WBDL-6LK All fire extinguishers should be installed, inspected

More information

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting life and

More information

Fire Safety Plan FOR. Business/Property Name: Address: Phone Number: Occupancy Classification. Approved by Fire Inspector: Date:

Fire Safety Plan FOR. Business/Property Name: Address: Phone Number: Occupancy Classification. Approved by Fire Inspector: Date: Fire Safety Plan FOR Business/Property Name: Address: Phone Number: Occupancy Classification Approved by Fire Inspector: Date: Table of Contents Part 1 Building Resources Audit Page 3 Part 2 Human Resources

More information

Checklist For Life Safety

Checklist For Life Safety INSPECTION CHECKLIST Date of Inspection: Location/Address: Weather Condition: Inspector: AFTER COMPLETING YOUR INSPECTION, TRANSFER YOUR CONCERNS/OBSERVATIONS TO THIS AREA Facility: Name: Staff Contact:

More information

a) Establishment of emergency procedures to be followed at the time of an emergency;

a) Establishment of emergency procedures to be followed at the time of an emergency; 5.10 Fire Safety 5.10.1 Introduction The Corporation is responsible for carrying out the provisions of the Ontario Fire Code. This section outlines our responsibilities as well as inspections and testing

More information

Fire Suppression Installation (R-102) for AVI Hoods & XLT Ovens

Fire Suppression Installation (R-102) for AVI Hoods & XLT Ovens XD 9011E ABGKSWBGHAE 10/16/2017 Fire Suppression Installation (R-102) for AVI Hoods & XLT Ovens CAUTION This appliance is for professional use by qualified personnel. This appliance must be installed by

More information

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Fire Alarm Systems Plan Review Checklist Date: Permit Number: Business Name: Address: Fire Alarm System Submittal

More information

EMLC Academy Trust. Fire Safety Policy 2017/19. Every child deserves to be the best they can be

EMLC Academy Trust. Fire Safety Policy 2017/19. Every child deserves to be the best they can be EMLC Academy Trust Fire Safety Policy 2017/19 Every child deserves to be the best they can be 1 Scope: EMLC Academy Trust & Academies within the Trust Version: 2 Filename: EMLC Academy Trust Fire Safety

More information

Fire Alarm Testing and Inspection Report

Fire Alarm Testing and Inspection Report Fire Alarm Testing and Inspection Report Property Name: Property Address: Property Manager: Contact: Phone Number: Central Station: Phone Number: PELICAN ISLE II 35 DOCKSIDE RD. NAPLES, FLORIDA 3110 BILL

More information

Global Property. QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:

Global Property. QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location: Global Property QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Plant: Date of Inspection Location: Inspected By: Reviewed By CONTROL VALVES (If Valves are Not Locked Open or Electronically Supervised

More information

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions: SECTION 21 13 13 WET-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

ISLE OF WIGHT FIRE & RESCUE SERVICE

ISLE OF WIGHT FIRE & RESCUE SERVICE ISLE OF WIGHT FIRE & RESCUE SERVICE Record of Fire Safety Equipment Testing Fire Drills & Training CONTENTS 1. MEANS OF ESCAPE 2. FIRE WARNING AND AUTOMATIC FIRE DETECTION 3. FIRE EXTINGUISHERS AND HOSEREELS

More information

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course Florida Building Code 2010 Chapter 9 Fire Protection Systems Advanced Course 1 Introduction This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors

More information

Commercial Remodel/ Add On Rules and Regulations

Commercial Remodel/ Add On Rules and Regulations Commercial Remodel/ Add On Rules and Regulations Public Works and Community Development Department City of Shenandoah 29955 I-45 North Shenandoah, Texas 77381 281-298-5522 www.shenandoahtx.us Construction

More information

Other EC and LS documents may be requested by surveyors, as needed, throughout the survey.

Other EC and LS documents may be requested by surveyors, as needed, throughout the survey. Documentation required by the Hospital Accreditation program Life Safety (LS) and selected Environment of Care (EC) standards is presented in the following pages. These documents will be reviewed by the

More information

D. Reference Standards (Utilize latest editions available):

D. Reference Standards (Utilize latest editions available): 1.01 Scope of Standard A. This standard provides general requirements of The Sam Houston State University for fireextinguishing systems other than water-based fire suppression systems. This document is

More information

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.01 SUMMARY SECTION 15371 KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM A. Section Includes: A complete wet chemical automatic fire suppression system for the exhaust hood, including necessary

More information

Design & Construction Standards, Revised January

Design & Construction Standards, Revised January PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for fire-extinguishing systems other than water-based fire suppression systems.

More information

Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems

Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems Your Presenter: Merton Bunker, PE Inspections and tests are intended to reduce or limit: Loss of life

More information

NFPA CODE TESTING & INSPECTION. Requirements & Recommendations for. Licensed Florida Hospitals, Ambulatory Surgery Centers,

NFPA CODE TESTING & INSPECTION. Requirements & Recommendations for. Licensed Florida Hospitals, Ambulatory Surgery Centers, NFPA CODE TESTING & INSPECTION Requirements & Recommendations for Licensed Florida Hospitals, Ambulatory Surgery Centers, ICF/IID Healthcare, & In-patient Hospice Facilities per NFPA Life Safety Code 101

More information

Allfire Site No. a division of Allsaved Ltd. Fire Safety Log Book. Premises Address: Responsible Person:

Allfire Site No. a division of Allsaved Ltd. Fire Safety Log Book. Premises Address: Responsible Person: Site No. a division of Allsaved Ltd. Fire Safety Log Book Premises Address: Responsible Person: Introduction An Introduction to Your Fire Safety Log Book The Regulatory Reform (Fire Safety) Order 2005

More information

St. Vincent s Health System Page 1 of 6

St. Vincent s Health System Page 1 of 6 St. Vincent s Health System Page 1 of 6 TITLE: Fire Plan Code Red FACILITY: St. Vincent s East FUNCTION: ORIGINATING DEPT: HOSPITAL SHARED POLICY? EFFECTIVE DATE: _X Yes No DOCUMENT NUMBER: 801 ORIGINATION

More information

Southaven Fire Department Fire Marshal s Office 8710 Northwest Drive Southaven, Mississippi Phone: Fax:

Southaven Fire Department Fire Marshal s Office 8710 Northwest Drive Southaven, Mississippi Phone: Fax: Southaven Fire Department Fire Marshal s Office 8710 Northwest Drive Southaven, Mississippi 38671 Phone: 662-393-7466 Fax: 662-280-6521 Fire Alarm Maintenance Guide The City of Southaven enforces the 2012

More information

March 27, ADDENDA No. 1. VARIOUS FIRE SERVICES Richland County, Ohio

March 27, ADDENDA No. 1. VARIOUS FIRE SERVICES Richland County, Ohio March 27, 2019 ADDENDA No. 1 Subject: Richland County, Ohio Enclosed herewith is a copy of Addenda No. 1 for the subject project. This material will be included in the final agreement and will become a

More information

WHEA FSE inspections.

WHEA FSE inspections. WHEA FSE inspections www.jfahern.com FEC.02.03.05 Features of Fire Safety Buildings are protected from fire by a series of detection, notification and suppression devices Each feature of fire safety must

More information

FIRE SAFETY PLAN. BUILDING NAME: Pathobiology / AHL BUILDING NUMBER: 089. DATE: 15-August-10 FPO #2

FIRE SAFETY PLAN. BUILDING NAME: Pathobiology / AHL BUILDING NUMBER: 089. DATE: 15-August-10 FPO #2 FIRE SAFETY PLAN BUILDING NAME: Pathobiology / AHL BUILDING NUMBER: 089 DATE: 15-August-10 FPO #2 INDEX Introduction 2 Locations of Fire Safety Plans 3 Forward 4 Audit of Building Data 5-6 Fire Fighting

More information

Fort Bragg Fire and Emergency Services Division Fire Safety Survey For use of this form, see FB Reg 420-1, the proponent agency for this form is DES.

Fort Bragg Fire and Emergency Services Division Fire Safety Survey For use of this form, see FB Reg 420-1, the proponent agency for this form is DES. Fort Bragg Fire and Emergency Services Division Fire Safety Survey For use of this form, see FB Reg 420-1, the proponent agency for this form is DES. Date of Survey: Building Number: UNIT / Organization:

More information

Self Inspection Program

Self Inspection Program Self Inspection Program Munich Re Self Inspection Program Inspection and testing of fire protection systems Introduction Engineered fire protection systems are a vital factor in the reduction of potential

More information

Unified Fire Authority - Fire Prevention Bureau

Unified Fire Authority - Fire Prevention Bureau Unified Fire Authority - Fire Prevention Bureau FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance

More information

SMALL WORKS PROJECT REQUEST FOR SEALED BIDS

SMALL WORKS PROJECT REQUEST FOR SEALED BIDS SMALL WORKS PROJECT REQUEST FOR SEALED BIDS PIERCE COUNTY FIRE PROTECTION DISTRICT #22 18421 OLD BUCKLEY HIGHWAY BONNEY LAKE, WA 98391 (253) 863-1800 (253) 863-1848 (FAX) Date Bid Requested: 5/24/2012

More information

AM Retail Group, Inc.

AM Retail Group, Inc. AM Retail Group, nc. Health & Safety The employer shall ensure all applicable laws, regulations, and rules that pertain to health and safety in the workplace are followed. The employer, bearing in mind

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-21 21 03.00 10 February 2009) ---------------------------------- Preparing Activity: USACE Superseding UFGS-21 21 03.00 10 (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

Project Name: Project Address: Installer Name: Installer Address: Date of Inspection:

Project Name: Project Address: Installer Name: Installer Address: Date of Inspection: FIRE DEPARTMENT Kitchen Range Hood Fire Suppression System Acceptance Test Project Name: Project Address: Installer Name: Installer Address: Date of Inspection: DOCUMENTATION NO Plans have been reviewed

More information

GUILFORD COUNTY SCHOOLS

GUILFORD COUNTY SCHOOLS GUILFORD COUNTY SCHOOLS Fire Extinguisher Plan Policy In accordance with the regulations established by the United States Department of Labor pursuant to the Occupational Safety and Health Act and the

More information

Fire/Life Safety Policy

Fire/Life Safety Policy Fire/Life Safety Policy On Campus Student Housing A. Purpose The University supports and maintains a strong commitment to the safety and health of each student living in On Campus Student Housing. The

More information

Fire Alarm Control Panel. System Maintenance and Log Book

Fire Alarm Control Panel. System Maintenance and Log Book Fire Alarm Control Panel System Maintenance and Log Book Fire Alarm System Maintenance A fire alarm system must provide early and reliable warning of the outbreak of fire. To achieve this, the system remains

More information

Hot Work Policy. Department of Risk Management. 1. Purpose. 2. Authority. 3. Scope

Hot Work Policy. Department of Risk Management. 1. Purpose. 2. Authority. 3. Scope 1. Purpose The purpose of the University of Denver Hot Work policy is to protect personnel and property from a fire caused by hot work. The DU Hot Work policy defines the responsibilities and requirements

More information

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard

More information

ARKANSAS FIRE PROTECTION LICENSING BOARD ACT 743 OF 1977

ARKANSAS FIRE PROTECTION LICENSING BOARD ACT 743 OF 1977 ARKANSAS FIRE PROTECTION LICENSING BOARD ACT 743 OF 1977 As Amended July 1, 1999 20-22-601. LEGISLATIVE INTENT FIRE PROTECTION LICENSING BOARD It is the purpose and intent of this subchapter to provide

More information

A.C.A. Tit. 20, Subtit. 2, Ch. 22, Subch. 6 Note

A.C.A. Tit. 20, Subtit. 2, Ch. 22, Subch. 6 Note A.C.A. Tit. 20, Subtit. 2, Ch. 22, Subch. 6 Note Arkansas Code of 1987 Annotated Official Edition 1987-2014 by the State of Arkansas All rights reserved. *** Legislation is current through the 2013 Regular

More information

GENERAL AREAS OF INSPECTION

GENERAL AREAS OF INSPECTION This information is intended to assist you in preparation for the annual high-rise inspection. This is not a complete list and the Inspector may identify other conditions or issues in the building that

More information

EC 5.10 FIRE PREVENTION MANAGEMENT

EC 5.10 FIRE PREVENTION MANAGEMENT EC 5.10 FIRE PREVENTION MANAGEMENT The organization manages fire safety risks. 1 The organization develops and maintains a written management plan describing the processes it implements to effectively

More information

C i t y o f G r o v e r B e a c h ADMINISTRATIVE SERVICES DEPARTMENT

C i t y o f G r o v e r B e a c h ADMINISTRATIVE SERVICES DEPARTMENT C i t y o f G r o v e r B e a c h ADMINISTRATIVE SERVICES DEPARTMENT BUSINESS TAX CERTIFICATE NEW AND RENEWALS Frequently Asked Questions The following are answers to some commonly asked questions regarding

More information

False Sense of Security???

False Sense of Security??? IS YOUR SPRINKLER SYSTEM GIVING YOU A FALSE SENSE OF SECURITY? Best Practices in Fire Safety An ASSE Virtual Symposium March 1 & 2, 2011 Walter S. Beattie CSP, CFPS, CSHM False Sense of Security??? Fire

More information

MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS

MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS FIRE CODE BULLETIN December 2004 97 FCB 018 (R1) Page 1 of 5 BACKGROUND: MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS Fire protection service companies are

More information

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY Revision No.: 11 Page 1 of 12 I. PURPOSE This procedure establishes a tool to help maintain a safe environment for all patients, visitors and staff by evaluating the loss of a life safety feature during

More information

TEXAS DEPARTMENT OF TRANSPORTATION PORTABLE FIRE EXTINGUISHER SERVICES ANNUAL INSPECTION MAINTENANCE, REPAIR, AND RECHARGING

TEXAS DEPARTMENT OF TRANSPORTATION PORTABLE FIRE EXTINGUISHER SERVICES ANNUAL INSPECTION MAINTENANCE, REPAIR, AND RECHARGING TEXAS DEPARTMENT OF TRANSPORTATION SPECIFICATION NO. * PORTABLE FIRE EXTINGUISHER SERVICES ANNUAL INSPECTION MAINTENANCE, REPAIR, AND RECHARGING PUBLICATION This specification is a product of the Texas

More information

USAutomatic Sprinkler Corporation

USAutomatic Sprinkler Corporation Inspection Report Information For CITY OF WESTFIELD - PUBLIC SAFETY Prepared by: T.Hughes, C.Gibbs a fire protection company Sheet 1 of 2 Phone: (317) 573-8160 Fax: (317) 573-8161 110370 REPORT OF INSPECTION

More information

Fire Safety Plan (Single-Stage Fire Alarm System) (Small Establishment):

Fire Safety Plan (Single-Stage Fire Alarm System) (Small Establishment): Fire Safety Plan (Single-Stage Fire Alarm System) (Small Establishment): Fire Safety Plan Single-Stage Fire Alarm System for: (Business Name) (Business Address) Submission Date - Submitted by - Signature

More information

Commercial Rules and Regulations

Commercial Rules and Regulations Commercial Rules and Regulations Public Works and Community Development Department City of Shenandoah 29955 I 45 North Shenandoah, Texas 77381 281 298 5522 www.shenandoahtx.us Construction Documents Submit

More information

CITY OF PASADENA FIRE DEPARTMENT

CITY OF PASADENA FIRE DEPARTMENT Page 1 of 8 CITY OF PASADENA FIRE DEPARTMENT INSTALLATION OF COMMERCIAL SPRINKLERS (Revised 12/10/2014) SCOPE: This standard applies to the design and installation of automatic fire sprinkler systems in

More information

MAINTENANCE AND SERVICE OF AUTOMATIC FIRE EXTINGUISHING SYSTEMS

MAINTENANCE AND SERVICE OF AUTOMATIC FIRE EXTINGUISHING SYSTEMS FIRE DEPARTMENT Bureau of Fire Protection and Life Safety www.cityofsanmateo.org 1040 East Hillsdale Blvd Foster City, CA 94404 (650) 522-7940 FAX: (650) 522-7941 MAINTENANCE AND SERVICE OF AUTOMATIC FIRE

More information

SUWANNEE RIVER WATER MANAGEMENT DISTRICT REQUEST FOR BID NO. 15/16-003AO FIRE ALARM SYSTEM INSTALLATION AND MONITORING.

SUWANNEE RIVER WATER MANAGEMENT DISTRICT REQUEST FOR BID NO. 15/16-003AO FIRE ALARM SYSTEM INSTALLATION AND MONITORING. SUWANNEE RIVER WATER MANAGEMENT DISTRICT REQUEST FOR BID NO. 15/16-003AO FIRE ALARM SYSTEM INSTALLATION AND MONITORING Table of Contents Section Title Page 1 Introduction 2 2 Proposed Schedule 2 3 Instructions

More information

CITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM. Bid # Addendum #1

CITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM. Bid # Addendum #1 CITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM Bid #56-09 Addendum #1 This Addendum forms part of the original document marked Bid #56-09 MUNICIPAL COMPLEX FIRE ALARM. Device

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with automatic detection and control. The work described in

More information

Item No. Description 1. BID PROPOSAL FORM Make the following revisions: a. Replace the BID PROPOSAL FORM with the attached BID PROPOSAL FORM.

Item No. Description 1. BID PROPOSAL FORM Make the following revisions: a. Replace the BID PROPOSAL FORM with the attached BID PROPOSAL FORM. City of Raleigh, Fire Station No. 11 Renovation September 28, 2018 274-CM2018-15A Page 1 HUFFMAN ARCHITECTS, PA 632 PERSHING ROAD RALEIGH, NORTH CAROLINA 27608 PHONE (919) 740-5669 TO: ALL PRIME BIDDERS

More information

Final EC Inspection Report 03/2010

Final EC Inspection Report 03/2010 2491 Alluvial Avenue, Suite 59 Clovis, California 93611 Tel: (559)392-2838 - Fax: (559)325-7599 Contractor License #933910 (C-10/C-16) Final EC.02.03.05 Inspection Report 03/2010 This Final Report Covers

More information

Fire Precautions, Evacuation and Emergency Control Procedure Denmead Scouts HQ

Fire Precautions, Evacuation and Emergency Control Procedure Denmead Scouts HQ Fire Precautions, Evacuation and Emergency Control Procedure Denmead Scouts HQ Document Details Originator: Craig Thompson February 2012 CONTENTS 1 Introduction 3 2 Scope 3 3 Roles and Responsibilities

More information

FIRE SUPPRESSION SPRINKLER SYSTEM

FIRE SUPPRESSION SPRINKLER SYSTEM PART 1 GENERAL 1.01 DESCRIPTION A. The provisions of the General Requirements, Supplementary Requirements, and Division 1 apply to the plumbing work specified in this Division. B. The requirements of this

More information

School Fire Safety Checklist

School Fire Safety Checklist Community Risk Reduction The (SFSC) includes many of the most common fire prevention and life safety issues found in schools. The SFSC is not intended to be an all inclusive list, but rather highlights

More information

Name of Establishment 123 Anywhere Street Anytown, Ontario A1A-1A1 Approved By:

Name of Establishment 123 Anywhere Street Anytown, Ontario A1A-1A1 Approved By: FIRE SAFETY PLAN Name of Establishment 123 Anywhere Street Anytown, Ontario A1A-1A1 Approved By: INTRODUCTION A FIRE SAFETY PLAN IS DESIGNED TO PROVIDE OCCUPANT SAFETY IN THE EVENT OF FIRE, TO PROVIDE

More information

"This is only the scope of work for the project. For more information, interested parties should contact Procurement at

This is only the scope of work for the project. For more information, interested parties should contact Procurement at "This is only the scope of work for the project. For more information, interested parties should contact Procurement at purchasing@stpgov.org to ensure receipt of a full bid package, to be listed as a

More information

Jefferson Cocke County Utility District Marketing Plan (July 1, 2008 through June 30, 2019) Revised effective July 01, 2016 A) Identify commercial

Jefferson Cocke County Utility District Marketing Plan (July 1, 2008 through June 30, 2019) Revised effective July 01, 2016 A) Identify commercial ` Jefferson Cocke County Utility District Marketing Plan (July 1, 2008 through June 30, 2019) Revised effective July 01, 2016 A) Identify commercial and home development before construction has begun (or

More information

OWNER'S SERVICE MANUAL NO INSPECTION, MAINTENANCE AND RECHARGE

OWNER'S SERVICE MANUAL NO INSPECTION, MAINTENANCE AND RECHARGE FOAM FIRE EXTINGUISHERS MODEL 254-6 LITER AFFF FOAM WITH SPRAY NOZZLE Model 250 2 ½ GAL.LON AFFF FOAM WITH ASPIRATED NOZZLE MODEL 252 2 ½ GAL.LON FFFP (ALCOHOL RESISTANT) FOAM WITH ASPIRATED NOZZLE OWNER'S

More information

I. Scope: II. Environmental Health and Safety Fire Alarm System Impairment Program - Guideline Revision Date: April, 2018

I. Scope: II. Environmental Health and Safety Fire Alarm System Impairment Program - Guideline Revision Date: April, 2018 Environmental Health and Safety Fire Alarm System Impairment Program - Guideline Revision Date: April, 2018 Prepared by: EH&S The probability of casualties and major structural damage increases when fire

More information

Functional Performance Test

Functional Performance Test Fire Alarm Control Panel & Fire Alarm Annunciator Panel Notify all building occupants that testing will be conducted. Fire alarm contractor shall have personnel with 2-way radios at the fire alarm control

More information

LIFE SAFETY TRAINING Nebraska Health Care Association Chris Moran November 1, 2017

LIFE SAFETY TRAINING Nebraska Health Care Association Chris Moran November 1, 2017 LIFE SAFETY TRAINING Nebraska Health Care Association Chris Moran November 1, 2017 WHO WE ARE We are a global company offering specialty engineering and consulting services for the built environment. We

More information

Florida Building Code 2010

Florida Building Code 2010 Introduction Florida Building Code 2010 Chapter 9 Fire Protection Systems This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors are familiar with

More information