Salamander User Guide

Size: px
Start display at page:

Download "Salamander User Guide"

Transcription

1 SYSTEM USER GUIDE

2

3 Introduction Salamander User Guide Salamander is a radio-controlled, battery-powered system for holding open fire doors. Before installation, a thorough radio survey will have been conducted using the purpose made Salamander Survey Kit. This document includes information to assist in the use of the Salamander system. Contents Introduction... 3 Documentation... 3 The System... 4 Enrolling Door Holders and Closers... 4 The Weekly Fire Test... 4 Closing All the Doors... 4 Trouble Shooting... 5 At the Controller... 5 System Configuration... 7 During Use... 7 Command Codes... 8 Locking the Keypad... 8 Display Unit Statistics... 9 Door Holders and Closers... 9 Boosters... 9 Changing Batteries Door Holders Door Closers Adding New Units Un-enrolling Units from a Controller Documentation Before and during installation of the system, the survey results and door locations should have been recorded by the installer(s) to assist the user during the life of the system. It will prove useful to add and retain further information about the system as it is used, altered and/or expanded. At the end of this document is an example change record sheet. Additional to this User Guide is the Installer Guide that goes with the Salamander system controller which contains further details on the technical aspects of installing and using the system. This is available from Geofire under part number issue B 3

4 The System The controller will normally display OP and the green power LED will be illuminated. This shows the system is OPerating properly. If no green LED is lit then there is no mains power and the controller is working on backup battery only. After 1 minute, the number display will switch off to conserve power. To indicate that the controller is still transmitting, a t will be displayed every 30 seconds. If the controller displays AL or FA and flashes all LEDs, it is sensing an ALarm / FAult signal from the fire panel. Clear the alarm / fault signal or check the wiring to the panel. Once the alarm / fault signal to the controller is cleared, press Activate on the Salamander controller to resume normal operation. Enrolling Door Holders and Closers Each door holder and closer has to be introduced to the controller so that they recognise each other. We call this enrolling. Enrol each unit at the controller before fitting. To enrol, insert the batteries into the unit while holding down the black release button. Once you hear the motor running you can release the button. Wait for the motor to complete its test cycle (around 10 seconds) then press the Enrol button on the controller. AU is displayed on the controller. Wait for up to 15 seconds. When the enrol process is complete, the controller allocates the unit a number. Note the number shown on the display and write it on the back of the unit in the case of the door holder. The magnet will not turn on until the battery cover is fitted and the screw fully inserted. If enrol is not successful, the controller will display EE and light all three LEDs. Remove the batteries and try again. Repeat this until all the units are enrolled. Once a unit is enrolled the batteries can be removed ready for fitting. The Weekly Fire Test When the weekly fire alarm test is performed an alarm signal is sent from the fire panel to the controller. The controller will display AL and all doors will release within 30 seconds. Leave the fire panel in alarm mode, even if you silence the sounders, for at least 1 minute to ensure that all units release their door. Clear the alarm in the fire panel then press Activate to reset the controller. The controller will now display OP. Check the units all turn on again after a further 30 seconds. Closing All the Doors Press the * RELEASE button on the controller. All units should release their doors within 30 seconds. After a further 30 seconds the units will turn on again issue B 4

5 Trouble Shooting At the Controller The display shows AL, all 3 LEDs are flashing, and the units will not turn on The controller is registering an alarm signal from the fire panel. Check whether your fire panel is in a fire alarm state. Consult your Salamander system installer / maintainer. The display shows FA, all 3 LEDs are flashing, and the units will not turn on The controller is registering a fault signal from the fire panel. Check whether your fire alarm panel is registering a fault. Consult your Salamander system installer / maintainer. All 3 LEDs are flashing, the 2 digit display is blank, and the units will not turn on The controller is registering a fault signal or a fire signal from the fire panel and the controller is running on back-up battery only. Check whether your fire alarm panel is registering a fire or fault state. Consult your Salamander system installer / maintainer. The 2 digit display is blank, and the units will not turn on The controller has no mains supply and has exhausted its backup battery. Once mains power is restored to the unit the backup battery will be recharged automatically. If there is no obvious cause for the repeater to be on battery backup, consult your Salamander system installer / maintainer. The number display on the controller is flashing The controller is in command mode. If no buttons are pressed the controller will time-out after 5 minutes and return to normal mode. Alternatively, use the up arrow (Enrol button) or down arrow (Activate button) to display 9 then press * RELEASE. The display will show the channel number being used by the controller and then exit command mode. There are no lights on the controller except a t every 30 seconds on the number display The mains power has failed and the controller is running on its backup battery. AL is not shown when I trigger a fire condition in the fire alarm panel There is either something wrong with the trigger wiring from the fire alarm panel, or the fire alarm is not going into a fire mode where the auxiliary supply / relay is being switched. Consult your Salamander system installer / maintainer. There is a LOW BATTERY warning If the display shows a two digit number, one of the units has reported a low battery to the controller. This unit will function for a further 1-2 months, but the batteries should be replaced when convenient. If the display shows a number prefixed by an r, one of the boosters has reported that it is on battery backup as there has been a failure in the mains supply. This unit will operate for ~ issue B 5

6 hours before the backup battery is discharged. Once mains power is restored to the unit the backup battery will be recharged automatically. If there is no obvious cause for the repeater to be on battery backup, consult your Salamander system installer / maintainer. There is a LOW BATTERY warning and the LOW SIGNAL LED is flashing If the display shows a two digit number, one of the units has reported a low battery to the controller before then not responding to the controller. This indicates that the unit has stopped working due to low battery. Remove the old batteries, wait for 10 seconds while the electronics discharge, then insert new cells without pressing the black button. If the display shows a number prefixed by an r, one of the boosters has reported to the controller that it is on battery backup before then not responding to the controller. This indicates that the unit has stopped working due to a fully discharged backup battery. Once mains power is restored to the unit the backup battery will be recharged automatically. If there is no obvious cause for the repeater to be on battery backup, consult your Salamander system installer / maintainer. There is a static LOW SIGNAL warning The unit number on the display is receiving messages at a lower than expected signal strength. This is a warning only and will, with time, disappear as whatever temporary impairment is removed. Low signals can be produced by moveable obstacles in corridors or rooms impeding the signal path to the unit. Trolleys, people, and other objects can all produce this effect. If this warning persists, consult your Salamander system installer / maintainer. There is a flashing LOW SIGNAL warning The unit number on the display has not replied to the controller. If the unit continues to operate correctly, and the warning eventually clears by itself, there is no cause for concern. Pressing the black button to release the door, or performing the weekly fire test, will confirm if this unit is still operating. If it seems unresponsive, unscrew the battery cover the take the batteries out. Wait 10 seconds for the electronics to discharge before then replacing the batteries and refitting the battery cover. Check that the unit turns on to hold the door; this may take up to 30 seconds. If this warning appears or the unit becomes unresponsive regularly, consult your Salamander system installer / maintainer. Units will not enrol to the controller, it just displays EE If you are enrolling a door unit, be sure to hold down the black button on the unit when inserting the batteries. Wait for the motor to finish running before then pressing Enrol. All units should be enrolled at the controller before fitting. When I try to un-enrol a unit, the controller displays EE There are no units of this type enrolled to the system issue B 6

7 When I press a button on the controller it displays Cd The keypad has been locked and the controller is prompting you to enter the security code. To unlock, refer to the Locking the Keypad section further on. If you do not know what code has been set, use the preset code Once the keypad is active, select command code option 00 and enter a new code 00 to disable the lock function. System Configuration I want to connect a timer to release all doors during the night time This can be done using the fault input to the controller if it is spare. Please consult your Salamander system installer / maintainer. Note that in the controller default setting there will be a 30 minute delay before the doors switch back on unless the Activate button is pressed. To remove the 30 minute reset delay, enter command mode, select option 08 and press release. This toggles the reset delay between 60 (30 minute delay, default setting) or 01 (no delay). With a 01 delay, once the timer contacts close, the controller will reset at the next 32 second broadcast. When this method is used to retain the doors, a fire alarm state triggered by the fire alarm panel will override a period of door release and will show as AL on the control panel display. If this state is cleared before the time for holding the doors again, FA will again be displayed on the control panel and the doors will re-hold correctly at the end of the door release period. During Use After a fire test or false alarm, the controller displays AL, and the doors will not hold Press Activate to clear the alarm on controller, otherwise the alarm will automatically clear after 30 minutes. If this is inconvenient, the reset time can be reduced to zero by selecting command option 8 on the controller. Some doors keep releasing for no reason The units in question are not receiving a consistent radio signal and are failing safe. This will also lead to premature battery failure. Consult your Salamander system installer / maintainer. The controller is flashing the Low Signal LED but the door holder indicated is still working The unit number on the display has not replied to the controller. If the unit continues to operate correctly, and the warning eventually clears by itself, there is no cause for concern. Pressing the black button to release the door, or performing the weekly fire test, will confirm if this unit is still operating. If it seems unresponsive, unscrew the battery cover then take the batteries out. Wait 10 seconds for the electronics to discharge before then replacing the batteries and refitting the battery cover. Check that the unit turns on to hold the door; this may take up to 30 seconds. If this warning appears or the unit becomes unresponsive regularly, consult your Salamander system installer / maintainer issue B 7

8 Command Codes Press the * RELEASE and Un Enrol buttons at the same time to enter command codes. Once the buttons are released, the number display flashes 00 to indicate command mode. Use the up and down arrows to select the code number then press * RELEASE. The codes are as follows: 00 Set key-lock code, see over page 01 lock keypad now 02 (Consult Salamander system installer / maintainer) 03 (Consult Salamander system installer / maintainer) 04 (Consult Salamander system installer / maintainer) 05 (Consult Salamander system installer / maintainer) 06 door holder statistics, see the Display Unit Statistics section 07 (Consult Salamander system installer / maintainer) 08 fire/fault reset delay : 60 (30 minutes default) / 01 (30 seconds) 09 display channel number 10 toggle poll frequency: 1h (1 hour frequency) / 2h (2 hours - default) 11 un-enrol a booster 12 (Consult Salamander system installer / maintainer) 13 booster statistics, see the Display Unit Statistics section 14 display back-up battery condition 15 toggle status query of boosters Pr = Poll Repeaters (default) / np = No Poll Locking the Keypad 1. Select command code 00 and press * RELEASE 2. A static 00 is now displayed 3. Decide on a security code number for unlocking the keypad (4 or more digits recommended) 4. Use the up and down arrows to select the first digit 5. Press Un Enrol and then select the second digit. Repeat as necessary 6. After entering the last digit press * RELEASE instead of Un-enrol. The keypad will now lock Any press of the buttons other than Activate will show Cd on the display. Enter the security code as in 4 to 6 above using the up and down arrows, Un Enrol and * RELEASE. OP will be displayed. The keypad will lock again after 5 minutes of no use, or if command option 1 is selected. If the security code is lost or set by mistake, use the engineers unlock code To switch off key locking proceed as if to set a locking code and enter the new security code 00, i.e. complete steps 1 and 2 then press * RELEASE again issue B 8

9 Display Unit Statistics Door Holders and Closers Enter command code 06. Use the up and down arrows to select the door holder number and press * RELEASE. First the received signal strength at the door holder is displayed (63 maximum) Press *. Now the signal strength received at the controller is displayed (63 maximum) Press *. The battery strength is displayed (39 = max, 32 = min) Press *. The node with which it is synchronised (0 = controller, 1-8 = booster number) Press *. The top 2 digits of the holder serial number Press *. The middle 2 digits of the serial number Press *. The last 2 digits of the serial number are displayed Then either select another door holder or press Un Enrol to return to OP If the first display is nc, this means that there are no valid statistics for this unit (the unit did not reply to the last query). Un here means that there is no unit enrolled in this slot. If nc is displayed, the serial number will still be displayed when pressing * RELEASE for this unit to allow for troubleshooting. Boosters Enter command code 13. r1 is displayed. Use the up and down arrows to select the booster number and press * RELEASE. First the received signal strength at the booster is displayed (63 maximum) Press *. Now the signal strength received at the controller is displayed (63 maximum) Press *. The power state is displayed (01 mains / 00 battery backup) Press *. The node with which it is synchronised (0 = controller, 1-8 = booster number) Press *. The top 2 digits of the holder serial number Press *. The middle 2 digits of the serial number Press *. The last 2 digits of the serial number are displayed Then either select another booster or press Un Enrol to return to OP If the first display is nc, this means that there are no valid statistics for this unit (the unit did not reply to the last query). Un here means that there is no unit enrolled in this slot. If nc is displayed, the serial number will still be displayed when pressing * RELEASE for this unit to allow for troubleshooting issue B 9

10 Changing Batteries The batteries in door holders and closers will last for up to 2 years provided that the unit is receiving good quality, consistent, radio signals. For planned maintenance we recommend replacing the batteries annually. Door Holders Remove the battery cover and take out the old batteries Wait for 10 seconds Install the fresh batteries referring to the battery label for the orientation without pressing the black button Replace the battery cover N.B. If the black button is held by accident when putting the batteries in, remove the batteries, wait 10 seconds for the electronics to discharge, and reinsert the batteries again without pressing the black button. Door Closers Unscrew and remove the main cover Remove the battery cover and take out the old batteries. Wait for 10 seconds Install the fresh batteries referring to the battery label for the orientation without pressing the black button. Replace the battery cover Replace and screw on the main cover N.B. If the black button is held by accident when putting the batteries in, remove the batteries, wait 10 seconds for the electronics to discharge, and reinsert the batteries again without pressing the black button. Use only good quality C size alkaline batteries, not rechargeable batteries. We recommend Duracell Procell; these are available direct from Geofire and may be ordered by quoting part number issue B 10

11 Adding New Units Further units may be added to an installed and operating system with no disruption to the operation of the existing units. Up to 99 door holders and up to 8 boosters may be enrolled to a single controller. Before adding units into an installation, seek advice from the installer or maintainer of your system; Where units will lie within the bounds of, or be very near to, the existing system, it may be possible to add them without surveying the radio environment at the new locations. Where there is any doubt, perform a survey Where units significantly extend the reach of the system, the extra locations must be surveyed to assess whether additional boosters will be required to cover the new locations Un-enrolling Units from a Controller To un-enrol a door holder or closer from the controller; press the Un Enrol button. The display will show the lowest enrolled unit number scroll up and down using the top two buttons to select the unit to un-enrol press * RELEASE To un-enrol a booster from the controller; select command option 11 (see the section) scroll up and down using the top two buttons to select the unit to un-enrol press * RELEASE Once the unit to be un-enrolled is selected, all the LEDs will be lit until the process is complete. Help Desk Tel: / salamander@geofire.co.uk issue B 11

12 Salamander System Change Record Sheet Date Changes / Additions Made Unit Number Location e.g. 31/03/14 Batteries changed in unit due to low battery warning 12 Room 17 DC Initials Medguard Professional Healthcare Supplies Tel: +353 (01) service@medguard.ie Fax: +353 (01) Web:

Acoustic door holder fitting instructions

Acoustic door holder fitting instructions Acoustic door holder fitting instructions Fitting the holder Decide where the door holder will be mounted (at least 650 mm from the door hinge). For doors fitted with overhead closers, a position towards

More information

Control Panel User Guide

Control Panel User Guide Fire Detection & Alarm System Control Panel V4.14 Control Panel User Guide (TO BE RETAINED BY USER) 26-0397 Issue 6 Fike s policy is one of continual improvement and the right to change a specification

More information

DCS2000 DEMENTIA CARE SYSTEM USER GUIDE. For Software Version 1.2 1

DCS2000 DEMENTIA CARE SYSTEM USER GUIDE. For Software Version 1.2 1 DCS2000 DEMENTIA CARE SYSTEM USER GUIDE For Software Version 1.2 1 Contents 1. INTRODUCTION...3 2. TYPICAL ROOM LAYOUT...4 3. DCS 2000 CONTROL PANEL...5 4. ON / OFF...6 5. SELECTING PROFILES...7 6. STATUS

More information

Security System. User s Guide for the Text Command Center

Security System. User s Guide for the Text Command Center User s Guide for the Text Command Center MY ALARM COMPANY IS: CALL BEFORE TEST: THIS SECURITY SYSTEM IS CONNECTED TO TELEPHONE NUMBER: THE SECURITY CONTROL PANEL IS CONNECTED TO THE PHONE JACK LOCATED:

More information

2000 SERIES DIAGNOSTIC ALARM CONTROL SYSTEM

2000 SERIES DIAGNOSTIC ALARM CONTROL SYSTEM 2000 SERIES DIAGNOSTIC ALARM CONTROL SYSTEM OPERATING INSTRUCTIONS MODELS: 2300 2500 2700 This information is relevant to systems fitted with Issue 4.1 (or later) Master Keypad Software, also to Networked

More information

Testing the System. Battery Test. Dialer Test. Fire Drill Test (Code + [#] + 69) One-Man Fire Walk-Test (Code + [#] + 68)

Testing the System. Battery Test. Dialer Test. Fire Drill Test (Code + [#] + 69) One-Man Fire Walk-Test (Code + [#] + 68) F A 1 7 0 0 c Testing the System Battery Test When AC power is present, the FA1700C runs a brief battery test every 60 seconds to determine if there is a battery connected, and runs an extended battery

More information

WLS900 Wireless Security System. Table of Contents. Your installing company is, Name: Address: Phone: Your monitoring station is, Name: Phone:

WLS900 Wireless Security System. Table of Contents. Your installing company is, Name: Address: Phone: Your monitoring station is, Name: Phone: Table of Contents WLS900 Wireless Security System 1 Introduction 2 2 Using the Keypad 3 3 Arming the System 4 3A - Arming Levels; 4 3B - Arming the System in the Away Mode 4 3C - Improper Arming Warning

More information

Operating Guide. English Version 3.3

Operating Guide. English Version 3.3 Operating Guide English Version 3.3 Keep this Guide in a safe place. Contents Page What is Deafgard? 2 First Check 3 Important Safety Information Prior to Use 4 LCD & Keypad 5 The LEDs - Strobe and Status

More information

Contents. Glossary

Contents. Glossary Contents Glossary ------------------------------------------------------------------------------------------------------ 6 1. Introduction to the IDS 1632 -------------------------------------------------------------

More information

U ser's Guide PC6010

U ser's Guide PC6010 User's Guide PC6010 Quick Reference Guide This manual is for Basic and Advanced users. Each of these types of user can access a different set of functions. The and symbols next to the title of each procedure

More information

DYGIZONE GJD910 Lighting Controller & Enunciator

DYGIZONE GJD910 Lighting Controller & Enunciator DYGIZONE GJD910 Lighting Controller & Enunciator MASTER WIRING IDENTIFICATION Power up to the DygiZone and you will see: All the LED s (red,yellow,green and blue buttons) will flash All the LCD icons will

More information

Security System. User Guide for the LED Command Center

Security System. User Guide for the LED Command Center Security System User Guide for the LED Command Center National Security Systems Inc (800)457-1999 MY SECURITY COMPANY IS: CALL BEFORE TEST: THIS SECURITY SYSTEM IS CONNECTED TO TELEPHONE NUMBER: THE SECURITY

More information

User Guide. HTM Nurse Call. In the event of requiring assistance, please contact your Installer/Supplier.

User Guide. HTM Nurse Call. In the event of requiring assistance, please contact your Installer/Supplier. HTM 08-03 Nurse Call User Guide In the event of requiring assistance, please contact your Installer/Supplier. Alarm Radio Monitoring Ltd Brunel Road, Leominster, Herefordshire. HR6 0LX tel: 01568 610 016

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd full installation, commissioning and operating manuals can be downloaded from www.haes-systems.co.uk combined addressable / conventional fire alarm control panel User Guide Approved Document No. MFBU-04

More information

2200 and 2200L ALARM CONTROL SYSTEMS

2200 and 2200L ALARM CONTROL SYSTEMS 2200 and 2200L ALARM CONTROL SYSTEMS OPERATING INSTRUCTIONS MODELS: 2200 (fitted software 3.4 or later) 2200L (fitted software 3.9L or later) Castle Care-Tech Ltd. 2200/2200L Alarm System Operating Manual

More information

New Silent Alert Fire Safe System

New Silent Alert Fire Safe System 1 New Silent Alert Fire Safe System TECHNICAL MANUAL This manual covers the FSTX-2225-EU - Fire Alarm Interface PG3A-2204-EU - Pager Unit - Fire Safe Compatible FSCH-2226-IN - Fire Safe Charger or CH3A-2205-IN

More information

HARDWIRED CONTROL PANELS

HARDWIRED CONTROL PANELS USER'S GUIDE HARDWIRED CONTROL PANELS Cooper Security Limited 2007 Every effort has been made to ensure that the contents of this book are correct. However, neither the authors nor Cooper Security Limited

More information

FIRERAY 5000 range USER GUIDE

FIRERAY 5000 range USER GUIDE FIRERAY 5000 range USER GUIDE 0044-003-04 IMPORTANT PLEASE NOTE: The beam path MUST be kept clear of obstructions at all times! Failure to comply may result in the Detector initiating a Fire or Fault signal.

More information

DSC PowerSeries NEO Quick Start Guide

DSC PowerSeries NEO Quick Start Guide DSC PowerSeries NEO Quick Start Guide WE DO NOT RECOMMEND BEING IN ANY PROGRAMMING SECTION THAT IS NOT IN THIS GUIDE UNLESS YOU FULLY UNDERSTAND THE FUNCTION OF THAT SECTION. Doing so may cause problems

More information

HARDWIRED CONTROL PANELS

HARDWIRED CONTROL PANELS USER GUIDE 9651 HARDWIRED CONTROL PANELS Contents 1. Introduction...3 The Alarm System...3 The Keypad...3 About This Guide...5 2. Everyday Operation...6 How Do I Know if the System is Working?...6 Setting

More information

M800, M800iD Plus, M1000 and M3000. User's Guide

M800, M800iD Plus, M1000 and M3000. User's Guide M800, M800iD Plus, M1000 and M3000 User's Guide Cooper Security Limited 2005 Every effort has been made to ensure that the contents of this book are correct. However, neither the authors nor Cooper Security

More information

REPEATER FS5200R OPERATION MANUAL

REPEATER FS5200R OPERATION MANUAL REPEATER FS5200R OPERATION MANUAL 1. Function Repeater FS5200R receives and transmits data for Fire condition and Fault condition from remote fire control panels (repeaters) and provides information about

More information

Silent Alert Fire Safe System

Silent Alert Fire Safe System Silent Alert Fire Safe System Technical Manual This manual covers the FSTX-2225-EU Fire alarm interface PG3A-2204-EU Pager FSCH-2226-IN Fire Safe Charger or CH3A-2205-IN Alarm clock charger SW3A-2208-EU

More information

Control Panel User Guide

Control Panel User Guide Fire Detection & Alarm System Control Panel (Suitable for TWINFLEX pro control panels from V1.00) Control Panel User Guide (TO BE RETAINED BY THE USER) 26-1028 Issue 2 Fike s policy is one of continual

More information

C2 Compact Range Installation & Programming Manual

C2 Compact Range Installation & Programming Manual C2 Compact Range Installation & Programming Manual Page 1 Onsite training is available and telephone technical support with optional remote access for further assistance is all part of the support we can

More information

169MHz Telecare Devices Sensor Controller

169MHz Telecare Devices Sensor Controller 169MHz Telecare Devices Sensor Controller Compatible with Reach at home alarms, Advent xt warden call, Altec Response and Touchsafe Pro Nursecall systems Can be used for bed or chair occupancy monitoring

More information

Operating instructions SENTRI4 Control panel based Fire detection and alarm system

Operating instructions SENTRI4 Control panel based Fire detection and alarm system 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32 Zones Healthy 15:45 Fault Power Fault System Fault SenTRI 4 Fire System Designed to EN54 Pt 2 & 4 Operating instructions

More information

Intruder alarm system Operating Instructions

Intruder alarm system Operating Instructions Intruder alarm system Operating Instructions 0 2 3 4 5 6 7 8 9 CHIME OMIT RESET PROG SET S Power 0 2 3 5 6 7 8 Chime Omit Prog 4 9 Set AccentaG3 mini Servicing organisation details Servicing organisation

More information

To operate the 5207 you can use either the built-in touchpad or the Model 5230 Remote Annunciator.

To operate the 5207 you can use either the built-in touchpad or the Model 5230 Remote Annunciator. Section 5 Operation To operate the 5207 you can use either the built-in touchpad or the Model 5230 Remote Annunciator. Figure 5-1 Built-in Touchpad (Seven-Segment Display) Figure 5-2 Model 5230 Remote

More information

Installation & Operation

Installation & Operation Integrated Area Monitor IAM Integrated Area Monitor Control Panel IAM-C Installation & Operation Content Page 1- IAM Sensor -Installation Instructions 2 2- IAM Sensor -Location Instructions 2 3- IAM Sensor

More information

USER MANUAL & MAINTENANCE GUIDE OG OO

USER MANUAL & MAINTENANCE GUIDE OG OO M+48. USER MANUAL & MAINTENANCE GUIDE OG OO What to do if the Fire Alarm Panel shows an Alarm (Red LED) Write down which LEDs are lit (either in the log book, or on a piece of paper for transferring to

More information

NX-148 LCD CODE PAD TABLE OF CONTENTS

NX-148 LCD CODE PAD TABLE OF CONTENTS NX-148 LCD CODE PAD TABLE OF CONTENTS Glossary Of Terms... 4 Understanding The Lights... 5 Code Pad Functions Arming In The ON Mode... 6 Making The System Ready To Arm... 7 Using Quick Arm... 7 Arming

More information

5000 SERIES 8 ZONE INSTRUCTION MANUAL

5000 SERIES 8 ZONE INSTRUCTION MANUAL 5000 SERIES 8 ZONE INSTRUCTION MANUAL NESS SECURITY PRODUCTS 4/167 PROSPECT HIGHWAY SEVEN HILLS. 2147 NSW AUSTRALIA SYDNEY Phone: (02) 8825 9222 (Head Office) BRISBANE Phone: (07) 3343 7744 MELBOURNE Phone:

More information

User manual AG-WT10. Indoor unit air/air heat pump UHB GB LEK

User manual AG-WT10. Indoor unit air/air heat pump UHB GB LEK LEK User manual Indoor unit air/air heat pump UHB GB 1715-3 331557 Table of Contents 1 Important information Installation data Safety information Serial number an excellent choice Safety instructions

More information

USER GUIDE WIRE-FREE HOME PROTECTION SYSTEM AG100+ CONTENTS

USER GUIDE WIRE-FREE HOME PROTECTION SYSTEM AG100+ CONTENTS CONTENTS USER GUIDE WIRE-FREE HOME PROTECTION SYSTEM AG00 Section Getting started. General system overview. Introduction to the system. Items included with the system. Introduction to the Smart Panel.5

More information

ZERIO PLUS EDA-Z5008, Z5020 & Z5100

ZERIO PLUS EDA-Z5008, Z5020 & Z5100 ZERIO PLUS EDA-Z5008, Z5020 & Z5100 USER MANUAL Revision 1.00 EDA-Z5008, Z5020 & Z5100 User Manual 0359 Electro Detectors Limited Electro House Edinburgh Way Harlow, Essex CM20 2EG, UK 14 0359 CPR 00226

More information

User s Guide. SUB-MA7240O-0001.OG.Solution doc. Created: 6/05/03. Last Updated: 23/09/03. MA7240AO-0001 Version 1.0

User s Guide. SUB-MA7240O-0001.OG.Solution doc. Created: 6/05/03. Last Updated: 23/09/03. MA7240AO-0001 Version 1.0 User s Guide SUB-MA7240O-0001.OG.Solution40-111.doc Created: 6/05/03 Last Updated: 23/09/03 MA7240AO-0001 Version 1.0 2 Table Of Contents User List...6 Quick Reference..7 Features...7 Keypad User's Guide...8

More information

Fire Command Keypad. XR5 User s Guide

Fire Command Keypad. XR5 User s Guide Fire Command Keypad XR5 User s Guide Silencing an Alarm While the fire alarm horns, strobes, or sirens are sounding use one of the following methods to silence the alarm depending on which type of keypad

More information

To activate using remote control: press [ ] key once. To activate using keyboard: on panel keyboard [ ] keys once.

To activate using remote control: press [ ] key once. To activate using keyboard: on panel keyboard [ ] keys once. Table of Content 1.1General Description----------------------------------------------------------------------2 2.2System Setup-----------------------------------------------------------------------------3

More information

ZITON RADIO LOOP MODULE

ZITON RADIO LOOP MODULE ZITON RADIO LOOP MODULE PROGRAMMING MANUAL Table of Contents Section Page No 1.0 INTRODUCTION...3 1.1 System Design...3 1.2 Handling Precautions...3 1.3 Packaging:...3 2.0 MENU STRUCTURE...4 2.1 Menu Structure

More information

Challenger Series Users Manual

Challenger Series Users Manual Challenger Series Users Manual P/N MAUSER-TS1016 05 20AUG15 Copyright Trademarks and patents Manufacturer 2015 UTC Fire & Security Australia Pty Ltd. All rights reserved. The Challenger name and logo are

More information

Peak Partners Web-Programmable Thermostat Homeowner s Manual. Look inside for a complete guide to the setup and operation of your new thermostat.

Peak Partners Web-Programmable Thermostat Homeowner s Manual. Look inside for a complete guide to the setup and operation of your new thermostat. Peak Partners Web-Programmable Thermostat Homeowner s Manual Look inside for a complete guide to the setup and operation of your new thermostat. Table of Contents Step 1: Getting Started...4-6 A. Thermostat

More information

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE General Description This guide provides a summary for installing and configuring the Centaur TM Cube Slave Alarm Signalling Equipment

More information

6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL

6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL 6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL USER MANUAL Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0)

More information

GSM Alarm System. User s Manual. Profile. MOBILE CALL GSM Alarm System

GSM Alarm System. User s Manual. Profile. MOBILE CALL GSM Alarm System MOBILE CALL GSM Alarm System GSM Alarm System System disarmed 11/26/2013 User s Manual Profile For a better understanding of this product, please read this user manual thoroughly before using it. CONTENTS

More information

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08 Beacon 200 Gas Monitor Operator s Manual Part Number: 71-2102RK Released: 6/6/08 Table of Contents Chapter 1: Introduction.................................................3 Overview.............................................................3

More information

WIRELESS ALARM SYSTEM WITH TELEPHONE AUTO DIALER

WIRELESS ALARM SYSTEM WITH TELEPHONE AUTO DIALER BAT.LOW AC WIRELESS ALARM SYSTEM WITH TELEPHONE AUTO DIALER THE SYSTEM THAT CALLS YOU! Our WIRELESS ALARM SYSTEM WITH TELEPHONE AUTO DIALER is designed to allow you to create your own security system.

More information

Memcom Emergency Telephone

Memcom Emergency Telephone Memcom Emergency Telephone Installation Guide Ref No. 450 900 (GB) Version 2 + + Simple wiring for quick installation + + Integrated LCD display shows you what you have programmed + + All code based programming

More information

Solution-6 Operators Manual Page 1 Preface Congratulations on selecting the Solution-6 security control system for your installation. So that you can obtain the most from your unit, we suggest that you

More information

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide System Reset Trou ble Silence Ala rm Silence Manual Ala rm ENTER NO YES Letters Numb ers Keyword Radionics System Reset Trouble Silence Alarm Silence Manual Alarm ENTER NO YES Le ters Numbers Keyw ord

More information

TS400 & TS410. Intruder Alarm Control Panels. Operating Instructions

TS400 & TS410. Intruder Alarm Control Panels. Operating Instructions TS400 & TS410 Intruder Alarm Control Panels Operating Instructions Zone Location Home Set Chime 1 Armed / Omitted 2 Armed / Omitted 3 Armed / Omitted 4 Armed / Omitted 5 Armed / Omitted F. Exit Always

More information

Product Recall Notification TX-4200 Wireless Personal Panic Device

Product Recall Notification TX-4200 Wireless Personal Panic Device Product Recall Notification TX-4200 Wireless Personal Panic Device October, 2016 Interlogix announces voluntary recall of TX-4200 Personal Panic devices Interlogix recently discovered an issue with a small

More information

Area Systems While the alarm bell or siren is sounding, enter your user code. The system silences the alarm bell or siren.

Area Systems While the alarm bell or siren is sounding, enter your user code. The system silences the alarm bell or siren. XR20 User s Guide Silencing an Alarm All/Perimeter and Home/Away Systems While the alarm bell or siren is sounding, enter your user code. The keypad displays DISARM SILENCE. Press the Select key under

More information

CA5000 Liquid CO 2 Freezer Backup System

CA5000 Liquid CO 2 Freezer Backup System CA5000 Liquid CO 2 Freezer Backup System OPERATING INSTRUCTIONS MANUAL HAMPSHIRE CONTROLS CORPORATION ONE GROVE STREET / P.O. BOX 516, DOVER, NEW HAMPSHIRE USA 03821 TEL. (603) 749-9424 FAX (603) 749-9433

More information

Surveyor Excel. Fire Alarm Control Equipment Network version. Programming Manual MASTER MANUAL. VERSION 14.0 and Above

Surveyor Excel. Fire Alarm Control Equipment Network version. Programming Manual MASTER MANUAL. VERSION 14.0 and Above Surveyor Excel Fire Alarm Control Equipment Network version Programming Manual VERSION 14.0 and Above MASTER MANUAL Drawing S1606. PCB Layout guide for XLK range of control panels FCPXLK-2/4/6/8 & FCPXLK2/4/6/8TW

More information

Fire Alarm Control Panel. System Maintenance and Log Book

Fire Alarm Control Panel. System Maintenance and Log Book Fire Alarm Control Panel System Maintenance and Log Book Fire Alarm System Maintenance A fire alarm system must provide early and reliable warning of the outbreak of fire. To achieve this, the system remains

More information

The most user friendly Security Alarm System L S Section 1 Overview of System Section 2 Planning your Installation

The most user friendly Security Alarm System L S Section 1 Overview of System Section 2 Planning your Installation The most user friendly Contents Section 1 Overview of System 1.1 Kit Contents 1.2 Tools Required 1.3 System Features Security Alarm System L S 4 0 0 Section 2 Planning your Installation 2.1 Location of

More information

Zerio Plus EDA-D6000 Radio Combined Heat Detector and Sounder Installation Instructions

Zerio Plus EDA-D6000 Radio Combined Heat Detector and Sounder Installation Instructions Zerio Plus EDA-D6000 Radio Combined Heat Detector and Sounder Installation Instructions EN54-3:2001+A1:2002+A2:2006 EN54-5:2000+A1:2002 EN54-25:2008 0359 Electro Detectors Ltd. Electro House Edinburgh

More information

USER GUIDE HARDWIRED CONTROL PANELS

USER GUIDE HARDWIRED CONTROL PANELS USER GUIDE HARDWIRED CONTROL PANELS Contents 1. Introduction... 3 The Alarm System... 3 The Keypads... 3 The 725r Telecommand (Remote Setting Device)... 5 About This Guide... 5 2. Everyday Operation...

More information

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

ZX1e ZX2e ZX5e. Document No Issue 01 user manual ZX1e ZX2e ZX5e Document No. 996-130 Issue 01 user manual MORLEY-IAS ZX2E/ZX5E Fire Alarm Control Panels Table of Contents 1 INTRODUCTION... 4 1.1 NOTICE... 4 1.2 WARNINGS AND CAUTIONS... 4 1.3 NATIONAL

More information

IT801 Thermostat. User s Manual. The complete guide to the set up and operation of your new smart Wi-Fi thermostat.

IT801 Thermostat. User s Manual. The complete guide to the set up and operation of your new smart Wi-Fi thermostat. IT801 Thermostat User s Manual The complete guide to the set up and operation of your new smart Wi-Fi thermostat. The smart Wi-Fi thermostat system learns your comfort preferences, then finds opportunities

More information

TS2500. Intruder Alarm Control Panel. SYSTEM OPEN 17:30 01 Jan ENT ESC. Setting the System. Unsetting the System RE SET

TS2500. Intruder Alarm Control Panel. SYSTEM OPEN 17:30 01 Jan ENT ESC. Setting the System. Unsetting the System RE SET E n t er y ou r pa s s c o de X X X X th en l ea v e th e p r o tec t e d a re a. G o dir e ct ly to t h e k e yp ad an d en te r y ou r p as s c o d e X X X X. E n t er y ou r pa s s c o de X X X X f

More information

REMOTE CONTROL FAN SPEED ECONOMY BATTERY LOW. owner s manual

REMOTE CONTROL FAN SPEED ECONOMY BATTERY LOW. owner s manual REMOTE CONTROL AUTO FAN SPEED COOL PM ECONOMY BATTERY LOW owner s manual Hello and congratulations on purchasing a Breezair Ducted Cooler for your home. Breezair coolers have been designed to provide quiet,

More information

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL 3500 CONVENTIONAL FIRE ALARM CONTROL PANEL USER MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273 Web:

More information

Keep this guide in a safe place. Contents

Keep this guide in a safe place. Contents Operating Guide This is an important document detailing the correct usage of the Deafgard device. These instructions must be read and fully understood before using the device This guide must be kept in

More information

Using Your. Security System With LED Keypad S5030, S5031, S5032

Using Your. Security System With LED Keypad S5030, S5031, S5032 Using Your Security System With LED Keypad S5030, S5031, S5032 Contents 1 Overview Your Security System... 1 How Your Security System Works... 2 Your System's Programming... 3 Getting Used to Your System...

More information

OWNER S MANUAL. Evaporative Cooler. (English) (EXH, EZH) ILL239-D ILL1140-A FAN SPEED REMOTE CONTROL ECONOMY

OWNER S MANUAL. Evaporative Cooler. (English) (EXH, EZH) ILL239-D ILL1140-A FAN SPEED REMOTE CONTROL ECONOMY OWNER S MANUAL Evaporative Cooler REMOTE CONTROL AUTO COOL FAN SPEED PM ECONOMY ILL239-D ILL1140-A (English) (EXH, EZH) Introduction...4 Remote Thermostat Control...5 Wall Mounted Thermostat Control...11

More information

CW9000 Wireless Fire System. Installation Manual

CW9000 Wireless Fire System. Installation Manual CW9000 Wireless Fire System Installation Manual CONTENTS 1 PROJECT PROCESS...4 1.1 PLANNING...4 1.2 SITE SURVEY...4 1.3 EQUIPMENT INSTALLATION...4 1.4 COMMISSIONING / CONFIGURATION...4 2 SYSTEM INSTALLATION...5

More information

BENTEL SECURITY reserves the right to modify the technical features of this product without prior notice.

BENTEL SECURITY reserves the right to modify the technical features of this product without prior notice. BENTEL SECURITY reserves the right to modify the technical features of this product without prior notice. via Florida Z.I. Valtesino - 63013 GROTTAMMARE (AP) - ITALY Installation and Quick guide: DUAL

More information

3 ZONE WIREFREE BURGLAR ALARM INSTALLATION & OPERATING INSTRUCTIONS

3 ZONE WIREFREE BURGLAR ALARM INSTALLATION & OPERATING INSTRUCTIONS WIREFREE PIRs WIREFREE KEYPAD AND CASE WIREFREE REMOTE WIREFREE DOOR CONTACT ukpanels.com Please note: Before you start to install this Micromark Alarm, we advise that you should take adequate safety precautions

More information

Simon XTi Quick Operation Guide

Simon XTi Quick Operation Guide Simon XTi Quick Operation Guide This is the Quick Operation Guide for the Simon XTi system (models 600-1054-95R-12 & 600-1054-95R-12-CN). The Simon XTi provides a graphical user interface for programming

More information

USER GUIDE HARDWIRED CONTROL PANELS

USER GUIDE HARDWIRED CONTROL PANELS USER GUIDE HARDWIRED CONTROL PANELS Scantronic Contents 1. Introduction... 3 The Alarm System... 3 The Keypads... 3 The 725r Remote Setting Device... 6 About This Guide... 6 2. Everyday Operation... 7

More information

USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4

USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4 PREMIER EX8 EXTINGUISHING PANEL USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN 12094 PART 1 & EN54 PARTS 2 & 4 USER MANUAL Approved Document No: GLT.MAN-132 INDEX Extinguishing

More information

Cellular Monitoring System

Cellular Monitoring System Cellular Monitoring System Wireless Temperature Monitoring Installation and Operation User s Manual Temperature Monitoring System used in: Temperature-controlled storage rooms and facilities Medical and

More information

V1.0. Smart Home Alarm System. User Manual. APP download via QR Code scanning. Please read the manual carefully before using.

V1.0. Smart Home Alarm System. User Manual. APP download via QR Code scanning. Please read the manual carefully before using. V1.0 Smart Home Alarm System User Manual APP download via QR Code scanning Please read the manual carefully before using. Content FUNCTION PROFILE 2 THE SCHEMATIC GRAPH OF HOST 3 PROCESS OF BOOTING 6 OPERATION

More information

Radio fire warning panel SRC 3000

Radio fire warning panel SRC 3000 Radio fire warning panel SRC 3000 6 zone radio fire warning panel Operating instructions Version 1.2 Art. 32487 detectomat GmbH Headquarter: Phone: +49 (0) 4102-2114-60 An der Strusbek 5 Fax: +49 (0) 4102-2114-670

More information

Scimitar user manual & log book. Petersfield Business Park, Bedford Rd, Petersfield, Hampshire GU32 3QA Tel: Fax:

Scimitar user manual & log book. Petersfield Business Park, Bedford Rd, Petersfield, Hampshire GU32 3QA Tel: Fax: Petersfield Business Park, Bedford Rd, Petersfield, Hampshire GU32 3QA Tel: 01730 268 231. Fax: 01730 265 552 Scimitar user manual & log book SCIMITAR USER MANUAL Approved Document No. DFU7001001 Rev 2

More information

PERMACONN PM1030 Includes DI300. Installation Manual

PERMACONN PM1030 Includes DI300. Installation Manual PERMACONN PM1030 Includes DI300 Installation Manual Radio Data Comms Unit 5/20-30 Stubbs Street Silverwater NSW 2128 Telephone: 02 9352 1777 Facsimile: 02 9352 1700 Introduction The PERMACONN system provides

More information

Touchpad Exit Controller Administration Guide

Touchpad Exit Controller Administration Guide Touchpad Exit Controller Administration Guide 2018 RF Technologies, Inc. All specifications subject to change without notice. All Rights Reserved. No Part of this work may be reproduced or copied in any

More information

User manual AG-WT10. Indoor unit air/air heat pump UHB GB

User manual AG-WT10. Indoor unit air/air heat pump UHB GB User manual Indoor unit air/air heat pump UHB GB 1516-1 331557 Table of Contents 1 Important information Installation data Safety information Serial number an excellent choice Safety instructions Recovery

More information

WARNING FIRE DOOR CLOSING

WARNING FIRE DOOR CLOSING PRODUCT INSTRUCTIS Stock Code: 088 FCP - Lite Floats Road, Wythenshawe Manchester, M 9WB Tel: + (0) 9 Fax: + (0) 9 Doc No PI - 88 Iss:.0 WARNING FIRE DOOR CLOSING STOP Contents ) Blank ) Features and

More information

Digital Electronic Thermostat With RF

Digital Electronic Thermostat With RF RT300RF Manual:89 6/7/10 12:52 Page 1 Digital Electronic Thermostat With RF Instruction Manual Model No RT300RF 2 RT300RF Manual:89 6/7/10 12:52 Page 2 2 RT300RF INSTRUCTION MANUAL RT300RF Manual:89 6/7/10

More information

Version 1.03 January-2002 USER S MANUAL

Version 1.03 January-2002 USER S MANUAL Version 1.03 January-2002 1 USER S MANUAL 2 Version 1.03 January-2002 System Details CUSTOMER:...... PHONE:... FAX:... INSTALLED BY:...... PHONE:... FAX:... MAINTENANCE & SERVICE:...... PHONE:... FAX:...

More information

ST325. Thermostat. The ST325TX can be used with any of these receivers RXBC605 RXST625 RXRT505 RXVBC605 RXWBC MHz

ST325. Thermostat. The ST325TX can be used with any of these receivers RXBC605 RXST625 RXRT505 RXVBC605 RXWBC MHz ST325TX Manual Version 008_Layout 1 16/05/2013 09:02 Page 1 ST32 ST S T325 32 25 5TX TX ST3 T3 325T 32 25TX ST T3 325 25TX ST S T32 25T TX TX ST325TX Digital Room ST325 T3 5 5TX T X Thermostat RXBC605

More information

XR401. Comfort Control TCONT401AN21MA. Owner s Manual. your local dealer (distributor) For more information contact. Tyler, Texas 75711

XR401. Comfort Control TCONT401AN21MA. Owner s Manual. your local dealer (distributor) For more information contact. Tyler, Texas 75711 XR401 Comfort Control $ Fan Mode TCONT401AN21MA Comfort Control Owner s Manual Trane 6200 Troup Highway Tyler, Texas 75711 For more information contact your local dealer (distributor) Table Of Contents

More information

System. For a better understanding of this product, please read this user manual thoroughly before using it.

System. For a better understanding of this product, please read this user manual thoroughly before using it. GSM Alarm System User s Manual For a better understanding of this product, please read this user manual thoroughly before using it. Chapter 1. Features Chapter 2. Control Panel Introduction Chapter 3.

More information

Control Panel User Guide (TO BE RETAINED BY THE USER)

Control Panel User Guide (TO BE RETAINED BY THE USER) Fire Detection & Alarm System Control Panel V3 (Suitable for Quadnet control panels from V2.00) Control Panel User Guide (TO BE RETAINED BY THE USER) 26-0585 Issue 7 Fike s policy is one of continual improvement

More information

NetworX Series. NX-8 Commercial Fire Panel Installation and Startup

NetworX Series. NX-8 Commercial Fire Panel Installation and Startup NetworX Series NX-8 Commercial Fire Panel Installation and Startup 2004 GE Security All rights reserved. Printed in the United States of America. These instructions do not purport to cover all details

More information

IDS816 User Manual H Issued January 2009

IDS816 User Manual H Issued January 2009 1 Contents Glossary-------------------------------------------------------------------------------------------------------------------6 1. Introduction to the IDS 816---------------------------------------------------------------------------7

More information

Memcom + Emergency Telephone

Memcom + Emergency Telephone Memcom + Emergency Telephone Installation Guide Ref No. 453 901AU (GB) Version 4 + + Simple wiring for quick installation + + Integrated LCD display shows you what you have programmed + + All code based

More information

169MHz Telecare Devices Enuresis Sensor & Plastic Bed Mat

169MHz Telecare Devices Enuresis Sensor & Plastic Bed Mat 169MHz Telecare Devices Enuresis Sensor & Plastic Bed Mat Compatible with Reach at home alarms, Advent xt warden call, Altec Response and Touchsafe Pro Nursecall systems Interface unit complete with plastic

More information

CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3

CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3 CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3 2.1 Electrical Specifications... 3 2.2 Communication Loop Parameters... 3 2.3 Dimensions...

More information

OWNER S MANUAL. Evaporative Cooler. (English) (EA, EXH, EZH) ILL239-D ILL1140-A FAN SPEED REMOTE CONTROL ECONOMY

OWNER S MANUAL. Evaporative Cooler. (English) (EA, EXH, EZH) ILL239-D ILL1140-A FAN SPEED REMOTE CONTROL ECONOMY OWNER S MANUAL Evaporative Cooler REMOTE CONTROL AUTO COOL FAN SPEED PM ECONOMY ILL239-D ILL1140-A (English) (EA, EXH, EZH) Hello and congratulations on purchasing a Breezair Ducted Cooler for your home.

More information

XRSuper6. User s Guide

XRSuper6. User s Guide XRSuper6 User s Guide Silencing an Alarm All/Perimeter and Home/Away Systems While the alarm bell or siren is sounding, enter your user code. DISARM SILENCE. Select SILENCE to stop the bell or siren. This

More information

Contents. Glossary Introduction to the IDS Notes Understanding the Keypad Indicators Operation of the Keypad...

Contents. Glossary Introduction to the IDS Notes Understanding the Keypad Indicators Operation of the Keypad... 2 Contents Glossary...7 1. Introduction to the IDS805...8 1.1 Notes...8 2. Understanding the Keypad Indicators...8 3. Operation of the Keypad...9 4. System Information...10 4.1 Programmed Functions...10

More information

Elite 16D Version 16 Zone Controller Arrowhead Alarm Products Ltd. Operating Guide. Proudly Designed and Manufactured in New Zealand

Elite 16D Version 16 Zone Controller Arrowhead Alarm Products Ltd. Operating Guide. Proudly Designed and Manufactured in New Zealand 6 Elite 16D Version 16 Zone Controller Arrowhead Alarm Products Ltd Operating Guide 1 Proudly Designed and Manufactured in New Zealand CONTENTS Page No. INTRODUCTION 3 About your Alarm 3 OPERATING YOUR

More information

USER GUIDE HARDWIRED CONTROL PANELS

USER GUIDE HARDWIRED CONTROL PANELS USER GUIDE HARDWIRED CONTROL PANELS Contents 1. Introduction... 3 The Alarm System... 3 The Keypads... 4 The 725r Telecommand (Remote Setting Device)... 5 About This Guide... 5 2. Everyday Operation...

More information

Watchguard WGAP864 User Manual

Watchguard WGAP864 User Manual Watchguard WGAP864 User Manual v1.0 Issued September 2016 1 2 Table of Contents Glossary... 5 1. Introduction to your Watchguard WGAP864... 6 2. Before Operating your Alarm System... 6 3. Understanding

More information

Operating instructions Vigilon panel and Network node Fire detection and alarm system

Operating instructions Vigilon panel and Network node Fire detection and alarm system Healthy 15:45 Fault Power Fault Vigilon Fire System GENT 2015 Designed to EN54 Pt 2 & 4 System Fault Operating instructions Vigilon panel and Network node Fire detection and alarm system Test Fire Fault/Dis

More information

USER S MANUAL HOME ENERGY SAVINGS REMOTE CAMERA INTERNET USER INTERFACE TEMPERATURE ALARMS BURGLARY PROTECTION DOOR SECURITY FIRE SAFETY

USER S MANUAL HOME ENERGY SAVINGS REMOTE CAMERA INTERNET USER INTERFACE TEMPERATURE ALARMS BURGLARY PROTECTION DOOR SECURITY FIRE SAFETY + USER S MANUAL 1.0 HOME ENERGY SAVINGS REMOTE CAMERA INTERNET USER INTERFACE TEMPERATURE ALARMS BURGLARY PROTECTION DOOR SECURITY FIRE SAFETY SECURITY KEYPAD WITH PROXIMITY TAGS PREVENTION OF WATER DAMAGES

More information