1 Flair 500 Series s
2 Basics Flair Multi-Zone s (MZAs) are fully functional, flexible, programmable micro controller based alarm control panels. They can be used independently d or in conjunction with other control panels and access control systems. Typical applications i include alarm systems where there are guards, officers, nurses or other personnel who need to monitor doors, rooms, objects or people quickly without having to scroll through LCD screens or computers FEATURES 8 Zone Modular Design Micro Controller Based Highly Visible Display Single Touch Control Easily Programmable
3 User Interface The Basic 8 Zone Module consists of 8 each, Yellow, Green, Red LEDs, and 8 Tactile Switches. Yellow LED Green LED Red LED Tactile Switch Indicates if the corresponding Zone is Bypassed. ON = Bypassed Indicates the Status of the Zone Input in real-time. ON = Zone Secure OFF = Zone Faulted Flashing = Zone Trouble Indicates a Zone Alarm. Flashing = New Alarm Steady = Acknowledged Alarm Provides for Individual Zone Control Acknowledge (Press Once) Reset (Press Once after Ack.) Bypass (Hold for 1 ½ seconds) Typical 8 Zone Display
4 Inputs of the MZA Zone Inputs Consist of eight Supervised Loop Inputs with one Common. Zone Inputs may be independently programmed for any one of five Input Types. N.C./N.O. N.C. N.O. Fire High Security Back of MZA Zone Inputs Cont trol In Control Inputs Consist of four Digital Control Inputs with one Common. Control Inputs may be independently programmed for any one of six Control Types Individual Out Com. Out Acknowledge Reset Shunt Disable Shunt Disable w/ Memory Arm/Disarm Lamp Test Serial Port 12 Vdc
5 N.C./N.O - Zone Input Configuration For use with N.C. and or N.O. contacts. N.C/N.O. EOL Zones must have a 1000 Ohm resistor across them. If the Zone is Shorted or Open, it will Alarm, there is no Trouble condition. Resistors should always be placed at the end of the wire run.
6 N.C. - Zone Input Configuration For use with N.C. contacts. N.C. EOL Zones must have a 1000 Ohm resistor across them. An Open Zone will generate an Alarm condition. A Shorted Zone will generate a Trouble condition.
7 N.O./Fire - Zone Input Configuration For use with N.O. Contacts. N.O. EOL Zones must have a 1000 Ohm resistor across them. A Shorted Zone will generate an Alarm condition. An Open Zone will generate a Trouble condition.
8 High Security - Zone Input Configuration High Security EOL Zones monitor for 7 different Loop Resistance Ranges. Secure Loop = 2000 Ohms Alarm Loop = 5300 Ohms Magnetic Tamper = 1000 Ohms Loop Tamper = Short Open and Loop Tamper = Short, Open and ranges above and below the Secure Loop Resistance
9 Individual Outputs Consist of eight Open Collector Transistor Outputs, each with a maximum switch current of 100mA 24VDC. Individual Outputs may be programmed for any one of five Output Types Non-Latch Latched Pulsed Timed Sounder Outputs of the MZA Back of MZA Zone Inputs Cont trol In Common Outputs Consist of two Open Collector Transistor Outputs, each with a maximum switch current of 100mA 24VDC, typically factory wired to an Audible Sounder and Common Relay Output. Common Outputs may be programmed for any one of six Output t Types Non-Latch Latched Pulsed tpulsed Timed Sounder System Arm Serial Port Individual Out Com. Out 12 Vdc
10 Zone Output Configurations The 8 Individual Outputs act as a switch to ground and may be connected to a small audible device, LED lamp, low current relay w/ surge diode, input of a digital device (PLC, Digital it Dialer, Alarm Panel, or PC) etc Non-Latch Follows the Status of the Zone Input, automatically resetting when the Zone Input is Secure. Latched Output will remain activated upon Alarm until the Zone Input is Secure and the Zone has been Acknowledged and Reset. Pulsed Output will activate upon Alarm for a 3 Second Period, each time the Zone Input is Alarmed. Timed Output will activate upon Alarm for a pre-programmed Time Period, then Automatically Reset. Sounder Output will activate upon Alarm and remain on until the Zone has been Acknowledged.
11 Configuring the MZA Characteristics of the Inputs and Outputs of each MZA Module are easily configured with the use of the Flair one page MZA Configuration software. Input Types Entry/Exit Delays Door Prop Delays Output Types Output Mapping
12 Input to Output Mapping Any Outputs may be configured to operate with any individual Input or combination of Inputs. Connect Multiple Zones to a Single Output for control of: Digital Dialers Camera Switchers DVR s Voice s Lighting Sirens Output Mapping
13 Communication Module Communication Status LEDs Operation Status LEDs ICSP Port 12 Vdc PC Serial Port Output Expansion Port Relay Drivers RS485 Port 1 RS485 Port 2 RS485 Port 3 RS485 Port 4 Link Port
14 Communication Module Basics The Communication Module (CM) is an accessory to the that controls and routes RS485 Serial Communication between two or more Cabinets Local/Remote The CM can be used to connect a Local Cabinet to one or more Remote Cabinets, each with complete display and control of the Local Zones. Multiplex up to 512 Zones FEATURES Micro Controller o Based Easily Programmable Individual Status LEDs
15 RS485 Ports Each CM has four RS485 Ports to connect up to four Cabinets in Local/Remote Configuration, with one Cabinet on each of the four RS485 Ports. Local Cabinets are typically hard wired to sensors in the surrounding building and display the status of those inputs. Remote Cabinets provide visual display and control of a Local Cabinet at one or more other locations. Each RS485 Port can be configured as either Local or Remote. A Local Cabinet may be routed to several Remote Cabinets. A Remote Cabinet may only be routed to one Local Cabinet.
16 CM Link Port The CM Link Port can be used to connect two Communication Modules together, in order to expand the number of Local/Remote Cabinets multiplexed to eight and/or to Link Local/Remote Cabinets over the Internet or a wireless transceiver. PC Serial Port The PC Serial Port is used to Configure the CM using a standard PC with an RS232 Serial Port.
17 Configuring the CM The Communication Module is easily configured with a standard PC, via the PC Serial Port, using the Flair one page CM Configuration Software. Configurable Features: Routing of Local Cabinet to one or more Remote Cabinets. Output Expansion Port Features Virtual MZA CM Link Port Routing
18 Application Profiles Social Services Duress Alarm School/University Alarm Estate Upgrade/Retro-fit Existing Alarm Panel Access Control
19 Social Services Duress Alarm 503A-24 Local Telecom Room 3 rd Floor 503A-24 Local RS485 RS485 PORT CM COMMUNICATION MODULE RS485 PORT 2 Telecom Room 2 nd Floor 561R-72 Remote 503A-24 Local Telecom Room 1 st Floor Guard Station 1 st Floor Lobby
20 School/University Alarm 503A-12 Local Mathematics/Science Building 503A-12 Local Technology Building 503A-12 Local Liberal Arts Building 503A-12 Local Performing Arts Building RS485 RS485 PORT CM COMMUNICATION MODULE Local Sensors Door Window PIR RS485 PORT 2 561BC-72 Local/Remote Security Office Administration Building
21 Estate Security Zone Inputs 503A-48 Local Door Window PIR Sensors Tele-Com Utility Room 550A-48 Remote Graphic Office RS485 PORT 1 500CM Communication Module RS485 PORT 2 RS485 PORT 3 RS485 PORT 4 550A-48 Remote Graphic Master Bedroom 550A-48 Remote Graphic
22 Upgrade/Retro-fit Existing Alarm Panel Existing Sensors Door Window PIR Existing Field Wiring Existing Zone Inputs Existing Local Alarm Panel Zone Inputs Guard Station 1 st Floor Lobby 550A-48 Local Graphic RS485 PORT 1 500CM Communication Module Individual Outputs CM Link Port Ethernet to RS485 Converter LAN WAN RS485 to Ethernet Converter CM Link Port Remote Site 500CM Communication Module RS485 PORT 1 561BC-48 Remote
23 Access Control Card Reader KeyPad Door Sensor Door Control Access Control Panel Guard Station 1 st Floor Lobby Zone Inputs 561R-48 Local RS485 PORT 1 Remote Site 561BC-48 Remote RS485 PORT 1 500CM Communication Module CM Link Port RS485 CM Link Port 500CM Communication Module
24 Simple Access Control Card Reader KeyPad DPST Door Sensor Door Control Guard Station 1 st Floor Lobby Zone Inputs 561R-48 Local
System Introduction. 1.1 PC5015 Specifications S E C T I O N 1
1.1 PC5015 Specifications System Introduction S E C T I O N 1 Flexible Zone Configuration: 8 Fully Programmable Zones 38 Access Codes: 32 User, 1 System Master, 2 Partition Master, 2 Duress and 1 maintenance
More informationPROGRAMMING GUIDE SPECTRA CONTROL PANELS V , 1725EX, 1728 AND 1728EX 1755, 1755EX, 1758, AND 1758EX
PROGRAMMING GUIDE SPECTRA CONTROL PANELS V1.2 1725, 1725EX, 1728 AND 1728EX 1755, 1755EX, 1758, AND 1758EX TABLE OF CONTENTS HOW DO I PROGRAM THE SYSTEM?... 4 Single Digit Data Entry Method (Hexadecimal
More informationP Zone Expandable Hybrid Security System
Page 1 of 11 up to 8 hardwired keypads and 4 wireless keypads 4 hardwired keypads available with zone input PWLS910 wireless handheld keypad added wireless control is provided by - PWLS908 wireless panic
More informationSystem Introduction. Digital Communicator Specifications: Supports all Major Formats including SIA and Contact ID Event Initiated Personal Paging
1.1 Specifications System Introduction S E C T I O N 1 Control Panel Specifications Flexible Zone Configuration: 8 Fully Programmable Zones 38 Access Codes: 32 User, 1 System Master, 2 Partition Master,
More informationSystem Introduction. 1.1 Specifications S E C T I O N 1
System Introduction S E C T I O N 1 1.1 Specifications Control Panel Specifications Flexible Zone Configuration: 8 Fully Programmable Zones 37 Access Codes: 32 User, 1 System Master, 2 Partition Master
More informationControl/Communicator Installation Manual
DAS NETWORX NX-12 Control/Communicator Installation Manual General Description...2 Ordering Information...2 Option Definitions...3 Programming the LED Code Pads...5 Programming the NX-12...9 Types of Programming
More informationRANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL
RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS GENERAL DESCRIPTION... 2 STANDARD AND OPTIONAL PARTS LIST... 2 PARTS DIAGRAM... 3 TERMINAL DRAWING AND SPECIAL NOTES...
More informationHEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING
-961212-0004 SOFTWARE VERSION 3.10 CONTROL PANEL RESET: Installer lock must be unlocked. ( 058: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (2) Connect
More informationDS7400Xi Addressable Control/ Communicator
DS7400Xi Addressable Control/ Communicator DS7400Xi DS7400Xi-EXP 110VAC operation 220VAC operation Remotely Programmable WDSRP (Windows Detection Systems Remote Programming Software), allows the systems
More informationMG Partition 64-Zone Wireless Console with GPRS/GSM Version 1.6. Section Programming Guide
MG6250 2-Partition 64-Zone Wireless Console with GPRS/GSM Version.6 Section Programming Guide Things You Need to Know About this Programming Guide The MG6250 All-in-one Wireless Console can be programmed
More informationVAP304 PRO INSTALLATION & OPERATION MANUAL
VAP304 PRO INSTALLATION & OPERATION MANUAL Panic Fire Duress Program Bypass Report Chime Test Memory B A D C Program Chime Panic Duress Exit Fire Report Bypass Memory Test Reset Password Exit Reset Password
More informationTABLE OF CONTENTS TABLE OF CONTENTS 1
TABLE OF CONTENTS TABLE OF CONTENTS 1 FEATURES 2 Keypad Programmable... 2 EEPROM Memory... 2 Static/Lightning Protection... 2 Supervision... 2 Operation... 2 SPECIFICATIONS 2 PC1550 Control Panel... 2
More informationHEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING
-961212-0004 SOFTWARE VERSI 3.10 CTROL PANEL RESET: Installer lock must be unlocked. (Address 058: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (2)
More informationAll-In-One Wireless Security System V3.2 Programming Guide. Model # MG6130 / MG6160
All-In-One Wireless Security System V3.2 Programming Guide Model # MG6130 / MG6160 We hope this product performs to your complete satisfaction. Should you have any questions or comments, please visit www.paradox.com
More information4-PGM Expansion Module
4-PGM Expansion Module APR3-PGM4 = Default setting SECTION [001] : General Options SECTION [002] : PGM Options Option OFF ON Option OFF ON [1] Future Use N/A N/A [1] PGM1 Deactivation After Deactivation
More informationDS3MX-E-I. Installation Guide. 3 Zone Mini Control Panel
DS3MX-E-I EN Installation Guide 3 Mini Control Panel DS3MX-E-I Installation Guide 1.0 General Information EN 2 1.0 General Information The DS3MX is a three zone mini control panel, which can be installed
More informationEngineer Reference. EN :2006+A1:2009 EN :2009 EN :2008 EN :2005+A1:2008 Security Grade 2 Environmental Class II
EN50131-1:2006+A1:2009 EN50131-3:2009 EN50131-6:2008 EN50131-5-3:2005+A1:2008 Security Grade 2 Environmental Class II Engineer Reference INTERNAL SIREN WARNING The Enforcer 32-WE control panel contains
More informationAll-In-One Wireless Security System V1.0. Model #: MG-6060
All-In-One Wireless Security System V1.0 Model #: MG-6060 Reference and Installation Manual DRAFT Table of Contents Introduction... 5 About Magellan and this Manual... 5 Conventions... 5 Specifications...
More informationHEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING
48ESEP-01 SOFTWARE VERSION 3.10 CONTROL PANEL RESET: Installer lock must be unlocked. (Address 058: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (2)
More informationTABLE OF CONTENTS. FOR THE RECORD 15 PROGRAMMING WORK SHEETS 16 CONTROL PANEL WIRING DIAGRAM inside back cover
TABLE OF CONTENTS FEATURES 2 SPECIFICATIONS 2 INSTALLATION 3 Mounting the Panel... 3 Mounting the Keypad... 3 Auxiliary Power Connection... 3 PGM Terminal Connections... 3 Bell/Siren Connection... 3 Keypad
More informationOJD ITB No Attachment E Duress Alarm Equipment Specifications
Duress Alarm Equipment Specifications PART 1 GENERAL 1.1 SECTION INCLUDES A. Duress devices. B. Alarm control panel. C. Signaling devices. 1.2 REFERENCE STANDARDS A. NFPA 70 - National Electrical Code;
More informationExcel-EN Conventional Fire Control Panel
Available as 2, 4, 6, 8,10 or 12 zones Approved to EN54-2 & 4 Modular expansion zone cards Programmable relays and outputs Optional additional sounder circuits Optional additional programmable outputs
More informationTABLE OF CONTENTS. General Description Standard and Optional Parts List Feature Definitions Comments about the 8600E...
5$1*(5( DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS General Description... 2 Standard and Optional Parts List... 2 Feature Definitions... 3 Comments about the 8600E... 4 Terminal
More informationInstallation Manual IMPORTANT. PC5020 Version 3.1 DLS-3 v1.3 and higher
IMPORTANT WARNING:This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be
More informationInstallation, Operating and Maintenance Manual
STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS
More informationSECTION INTRUSION DETECTION
(NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) SECTION 28 16 00 INTRUSION
More informationUnderstanding the Code Pad lights...4. Code Pad tones...5. Fully arming the system On MODE...6. Fully arming the system - Quick Arm MODE...
TABLE OF CONTENTS...Glossary of terms...2...code Pad Diagram...3 Understanding the Code Pad lights...4 Code Pad tones...5 Fully arming the system On MODE...6 Fully arming the system - Quick Arm MODE...6
More informationRANGER 8980E DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL
RANGER 8980E DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS GENERAL DESCRIPTION...2 STANDARD AND OPTIONAL PARTS LIST...2 FEATURE DEFINITIONS...3 TERMINAL DRAWING AND SPECIAL NOTES...4
More informationSOFTWARE VERSION 2.20 CONTROL PANEL RESET: Installer lock must be unlocked. (Address 255: enter any value other than 147)
-961112-0003 SOFTWARE VERSI 2.20 CTROL PANEL RESET: Installer lock must be unlocked. ( 255: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (4) Wait 3
More informationINSTALLATION MANUAL PC56O. Version 1.OA
INSTALLATION MANUAL PC56O Version 1.OA TABLE OF CONTENTS INTRODUCTION 3 Features... 3 Specifications... 3 INSTALLATION 4 Mounting the Control Panel... 4 Mounting the Keypad... 4 Wiring... 5 Burglary Zone
More informationR A D I O N I C S. READYKEY K2015A Alarm Event Manager. Installation Data Sheet. Description
R A D I O N I C S READYKEY K2015A Alarm Event Manager Installation Data Sheet READER CONTROLLER INPUTS INPUTS RLY 8 RLY 7 RLY 6 RLY 5 RLY 4 RLY 3 RLY 2 RLY 1 8 Supervised Inputs (Normally Open or Normally
More informationAddressable Fire Alarm Control Panel
PRODUCT SPECIFICATION XR2400F Addressable FACP Addressable Fire Alarm Control Panel Description The DMP XR2400F Addressable Fire Alarm Control Panel is an expandable Fire Alarm Control with built-in DACT
More informationINSTALLATION AND PROGRAMMING MANUAL
INSTALLATION AND PROGRAMMING MANUAL Contents Section 0. Section 1. Section 2. Section 3. Section 4. Section 5. Section 6. Section 7. Section 8. Section 9. Section 10. Section 11. Section 12. Section 13.
More informationTraining Manual with Bi-directional Wireless
Training Manual with Bi-directional Wireless Installer Training Firmware Version 2.7x X16 Stock Code: 860-1-473-X16 X64 Stock Code: 860-1-864-XS 2 IDS X-Series Training v2.7 Contents Contents 3 X-Series
More informationSystem Introduction. 1.1 Specifications
System Introduction S E C T I O N 1 1.1 Specifications Downloading Software Support PC585 uses DLS-1 v6.5 and up. Flexible Zone Configuration Four fully programmable zones; system expandable to eight zones
More informationPower Wave Zone Alarm Panel V8.5. Installation Manual
Power Wave - 8 8 Zone Alarm Panel V8.5 Installation Manual 7 December 2001 Crow (Aust) Electronic Engineering Pty Ltd Corporate Head Office: 429 Nepean Hwy, Brighton East, Vic., 3187 Australia Phone: +61
More informationSOFTWARE VERSION 2.20 CONTROL PANEL RESET:
-961112-0002 SOFTWARE VERSI 2.20 CTROL PANEL RESET: Installer lock must be unlocked. ( 255: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (4) Wait 3
More information21-light Remote Annunciator. Owner s Manual
21-light Remote Annunciator Owner s Manual Annunciator Description... Inside Font Cover Detailed Specifications... 1 Environmental Specifications... 1 Power Supply Requirements... 1 Communication With
More informationType 8001 PRIME MOVER CONTROLS INC. ALARM ANNUNCIATOR TYPE8001 FEATURES SB 8001B
PRODUCT BULLETIN SB 8001B Type 8001 ALARM ANNUNCIATOR TYPE8001 FEATURES 16 or 32 alarm points per flush mount enclosure Displays are backlit with long life LEDs and engraved to suit Dimmer controls built
More informationKT-100 Door Controller
WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully
More information8-zone Expansion Module
8-zone Expansion Module APR3-ZX8 SECTION [001] : General Options Option OFF ON [1] Tamper Recognition ON = Input 8 (Z8) becomes tamper input = Default setting Disabled Enabled [2] PGM Deactivation After
More informationEVO192 v3.0 Fire and Burglary What s New
EVO192 v3.0 Fire and Burglary What s New Compatibility: EVO192 v3.0 TM50 v1.31 K641 v2.41 Overview: CP-01 Compliancy Wiring Diagram The following sections/options have been added to the EVO192 panel. They
More informationDigiplex System V2.14 / V2.2ACC. Control Panel Programming Guide
Digiplex System V2.14 / V2.2ACC Control Panel Programming Guide Table of Contents Getting Started...2 What Do I Do First?...2 How Do I Program the Control Panel?...2 Single Digit Entry Method...2 Multiple
More informationFire Burglary Instruments Inc. XL-2G Gold Control/Communicator Installation Training Seminar Rev. 5/96
Fire Burglary Instruments Inc. XL-2G Gold Control/Communicator Installation Training Seminar Rev. 5/96 XL-2G Gold Product Overview 7 Zones (6 programmable + panic or keyswitch zone) Fast Loop Response
More informationPower Wave. 8 Zone Control Communicator. Crow Electronic Engineering P/L. Ver:8.54. Installation & Programming Guide.
Power Wave 8 8 Zone Control Communicator Crow Electronic Engineering P/L Ver:8.54 Installation & Programming Guide 8 November 2000 Crow ( Aust ) Electronic Engineering Pty Ltd Corporate Head Office: 429
More informationFIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200
FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200 1.0 General 1.1 Manufacturer Manufacturer of the Fire Alarm Control Panel (FACP) equipment shall be: Digital Monitoring Products, Incorporated 2500 N.
More informationMG5000 V2.4 MG5050 V2.4 SP5500 V2.4 SP6000 V2.4 SP7000 V2.4. Programming Guide
MG5000 V2.4 MG5050 V2.4 SP5500 V2.4 SP6000 V2.4 SP7000 V2.4 Programming Guide We hope this product performs to your complete satisfaction. Should you have any questions or comments, please visit www.paradox.com
More informationNX-148 LCD CODE PAD TABLE OF CONTENTS
NX-148 LCD CODE PAD TABLE OF CONTENTS Glossary Of Terms... 4 Understanding The Lights... 5 Code Pad Functions Arming In The ON Mode... 6 Making The System Ready To Arm... 7 Using Quick Arm... 7 Arming
More informationHoneywell Control Panels FOR RESIDENTIAL AND COMMERCIAL INSTALLATIONS. Feature Charts
Honeywell Control Panels FOR RESIDENTIAL AND COMMERCIAL INSTALLATIONS Feature Charts Control Panels FEATURE CHART LYNX Plus (L3000) (Supported Feature) (Not Supported) N/A (Not Applicable) LYNX Touch (L5210)
More informationPNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel
PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel INSTALLATION, OPERATION AND MAINTENANCE MANUAL Version: CN-PM-1000.VER1.1-12/2012 EN54 INFORMATION In accordance with EN 54-2 clause 13.7, the maximum
More informationAll-In-One Wireless Security System V1.0. Model #: MG Reference and Installation Manual
All-In-One Wireless Security System V1.0 Model #: MG-6060 Reference and Installation Manual Table of Contents Introduction... 3 About Magellan and this Manual... 3 Conventions... 3 Specifications... 3
More informationControl Panels. Control Panels for Commercial Applications. Control panels provide the central processing
Control Panels Control Panels for Commercial Applications Control panels provide the central processing and logic for an integrated system. In a typical system, there are four major functions: inputs,
More informationConventional Releasing Control Panel
s Data Sheet Fire Safety Products Conventional Releasing Control Panel Pre-Action Deluge Agent-Releasing Fire System Model TXR-320 Remote configurable Up to two (2) hazard areas Operable with the following:
More informationEasyLoader AV-2005 & AV-2008
EasyLoader AV-2005 & AV-2008 Integrated Alarm Control/Communicator Year 2000 ready Installation and Operation Manual Version 2.17C Edition IIII This product is subject to continuous enhancements and therefore
More informationInstallation Manual Premier 412/816/832. Issue 10
Installation Manual Premier // Issue 0 Premier // Installation Manual 5. Operating the System Introduction Before attempting to operate the alarm system ensure you have familiarised yourself with all the
More informationProduct Data Sheet. Remote Terminals. Features:
Remote Terminals Product Data Sheet Features: Based around two core products, the Mx- 4010 Remote Display Terminal (RDT) and the fully functional Mx-4020 Remote Control Terminal (RCT). Both remote terminals
More informationDigiplex Control Panel (DGP-848) - V4.0
Digiplex Control Panel (DGP-848) - V4.0 DGP-848 Reference and Installation Manual TABLE OF CONTENTS INTRODUCTION... 4 1.0 1.1 Features... 4 1.2 Specifications... 4 INSTALLATION... 5 2.0 2.1 Location &
More informationUNC100 Integra Manual
UNC100 Integra Manual New Generation Building Security July 30, 2014 V1.2 Copyright Notice Copyright 1995-2014 by All rights reserved Worldwide. Printed in Canada. This publication has been provided pursuant
More informationInstallation & Programming Guide
Alert Version 8 Zone Control Arrowhead Alarm Products Ltd Installation & Programming Guide Proudly Designed and Manufactured in New Zealand Arrowhead Alarm Products Ltd PHONE: (09) 579 7506 FAX: (09) 579
More informationNGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3 PRODUCT OVERVIEW
NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM Local configuration and monitoring with Raychem Touch 1500 touch screen display PRODUCT OVERVIEW The nvent RAYCHEM NGC-40 is a multipoint
More informationFMR Installation Instructions. Addressable Fire System Controller
FMR-7033 EN Installation Instructions Addressable Fire System Controller EN 2 FMR-7033 Installation Instructions Contents Contents Contents...2 1.0 Introduction...3 2.0 Description...3 3.0 Device Mounting...3
More informationDL-250 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL
DL-250 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS 1. GENERAL DESCRIPTION...P.2 2. STANDARD AND OPTIONAL PARTS LIST...P.2 3. FEATURE DEFINITIONS...P.3 4. TERMINAL DRAWING AND
More informationDL150 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL
DL150 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS 1. GENERAL DESCRIPTION... 2 2. STANDARD AND OPTIONAL PARTS LIST... 2 3. FEATURE DEFINITIONS... 3 4. TERMINAL DRAWING AND SPECIAL
More informationProperty of Monitronics Inc
Enter Program Program Location 1. Hold 8 key for 3 seconds, keypad will beep 2. Enter 4 5 6 7 8 9, display should show dash on display 1. Press [B/A] key display will show 3 dashs 2. Enter 3-digit location
More informationSystem Manual W A R N I N G. PC6O1O Software Version 2.1
System Manual W A R N I N G This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual
More informationAlarm Control Panel WIC-16Z4P WIC-5Z2P. Installation & Operation User Manual
WIC-16Z4P WIC-5Z2P Installation & Operation User Manual Page : 1/34 INDEX # Function Page 1 Abort Current Communication and Clear Reporting Queue (*59) 13 2 Abort Current Communications (*59) 10 3 Account
More informationTW-8000 TAUT WIRE FENCE
TW-8000 TAUT WIRE FENCE www. rbtec. com Email: info@rbtecom GENERAL TW-8000 Product information INTRUDALERT is a powerful electronic system specifically designed for total perimeter protection of critical
More informationARCHITECTURAL DOOR HARDWARE KEY PADS & CARD READERS CATALOG
ARCHITECTURAL DOOR HARDWARE KEY PADS & CARD READERS CATALOG January 1, 2017 v3 West Coast Office (800) 544-4422 East Coast Office (800) 225-6737 intldoorclosers.com Index KEY PADS & CARD READERS Heavy
More informationMODEL KP-200 VANDAL RESISTANT & WEATHERPROOF FLUSH MOUNT DIGITAL KEYPAD DESIGNED FOR ACCESS CONTROL APPLICATIONS
MODEL KP-200 VANDAL RESISTANT & WEATHERPROOF FLUSH MOUNT DIGITAL KEYPAD DESIGNED FOR ACCESS CONTROL APPLICATIONS OPERATES ON 12 OR 24 VOLTS AC/DC, AUTO VOLTAGE SENSING FULLY PROGRAMMABLE FROM THE KEYPAD
More informationNGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3
NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM Local configuration and monitoring with Raychem Touch 1500 touch screen display PRODUCT OVERVIEW The Raychem NGC-40 is a multipoint electronic
More informationHMS 1100 Installation Manual
HMS 1100 Installation Manual OnQ OnQ HMS 1100 INSTALLATION MANUAL Document Number 1307593 Rev. 2.3 February, 2003 Copyright Y 2002-2003 HAI All Rights Reserved CONTENTS INTRODUCTION...1 PLANNING...1 INSTALLATION...2
More informationD720 and D1255 Command Centers
Command Centers and Keypads D720 and D1255 Command Centers 33704G The D720 and D1255 Command Centers are low profile, surface mount units that can annunciate events from the 9000 Series Control/Communicators
More informationRANGER 7600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL
RANGER 7600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS 1. TABLE OF CONTENTS... P.1 2. GENERAL DESCRIPTION... P.2... 3. STANDARD AND OPTIONAL PARTS LIST... P.2... 4. FEATURE
More informationElite Version. 8 Zone Control Communicator. Installation & Programming Guide. Proudly Designed and Manufactured in New Zealand
Elite Version 8D 8 Zone Control Communicator Installation & Programming Guide Proudly Designed and Manufactured in New Zealand This Elite Version 8D alarm control panel has been designed to provide the
More informationINSTALLATION MANUAL & PROGRAM RECORD SHEET
INSTALLATION MANUAL & PROGRAM RECORD SHEET TABLE OF DESCRIPTION CONTENTS PAGE WIRING MANUAL 2-6 MENU CHART 7 INSTALLER FUNCTIONS 8 MENU 1 SYSTEM TIMES 9 MENU 2 ZONE CONFIGURATION 10-14 MENU 3 SYSTEM OPTIONS
More informationINTRODUCTION. The use of any power source other than a PC4204 to repower the Combus will result in a system malfunction.
INTRODUCTION The PC4020 is a highly flexible and versatile control which will enable the installer to meet the most demanding security requirements. The heart of the system is the main control panel, designated
More informationTHIS GUIDE SUPPORTS MATRIX 424 & 832 CONTROL PANELS
THIS GUIDE SUPPORTS MATRI 424 & 832 CONTROL PANELS Software Version V1 08 RINS 295 ISSUE 4 DECEMBER 2001 WARRANTY This product is sold subject to our standard warranty conditions and is warranted against
More informationWIRELESS CONTROLS & DETECTORS
WIRELESS CONTROLS & DETECTORS WLS908 Panic Pendant Press 2 buttons for 2 seconds to initiate a panic alarm Water-resistant Pendant test function Supervised for low battery Each pendant is a wireless zone
More informationMODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description
MODUL-R FIRE ALARM CONTROL PANELS MR-2900/MR-2920 Addressable Fire Alarm Control Panels Description MR-2900 Fire Alarm Control Panel The MR-2900 fire alarm system control unit is the heart of a sophisticated
More informationIntegrated Security Solutions
Integrated Security Solutions Table of Contents Control Panels 4 Keypads 8 Communication Modules 16 I/O Expanders 20 Door Control 24 Home Automation 25 RF Receivers 26 3 Our integrated security solutions
More informationINSTALLATION GUIDE XTLN-WIFI PANEL
INSTALLATION GUIDE XTLN-WIFI PANEL MODEL XTLN-WiFi INSTALLATION GUIDE FCC NOTICE This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of
More informationAXI LED USER MANUAL (REV. 1.0)
Security & Home Automation System AXI LED USER MANUAL (REV. 1.0) CONTENTS PREFACE FEATURES LED KEYPAD OUTLOOK 1.0 LIGHT INDICATION 1 2 4 6 CHAPTER 1: ALARM SYSTEM CONTROL 1.0 USING LED KEYPAD 1.0.1 ARMING
More informationInstallation & Programming Guide
S series (8/16 Zone Control Communicator) Installation & Programming Guide Proudly Designed and Manufactured in New Zealand (NZS:4301/93) Security Merchants Australia P/L VIC 03 9558 8455 NSW 02 9890 5300
More informationACP10 & ACP50 Security Systems
ACP10 & ACP50 Security Systems System Configuration LCD Keypad LCD Keypad LED Keypad LED Keypad 4-wire Bus ACP10 & ACP50 AEX10* AEX10* AEX10* AEX10* * ACP50 Only Control Panels The ACP10 control panel
More informationEasyLoader. Integrated Alarm Control/Communicator. Year 2000 ready. Express Installation and Operation Manual. Edition II
EasyLoader AV-2004, AV-2048 Integrated Alarm Control/Communicator Year 2000 ready Express Installation and Operation Manual Version 3.06 (with very slow zone) Edition II This product is subject to continual
More informationFire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63
Fire Extinguishing Control Panel FS5200Е INSTRUCTION MANUAL Revision 8/01.17 Instruction Manual Page 1 1. 2. 3. 4. 4.1. 4.2. 4.2.1. 4.2.2. 4.2.3. 4.2.4. 4.2.5. 4.2.6. 4.2.7. 4.2.8. 4.2.9. 4.2.10. 4.2.11.
More informationFor a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.
Power Supply/Chargers Installation Guide Models Include: eflow4na8d - 4A @ 12VDC or 24VDC - Eight (8) PTC Outputs eflow6na8d - 4A @ 12VDC or 24VDC - Eight (8) PTC Outputs eflow102na8d - 10A @ 12VDC - Eight
More informationLaptop / PC Programming Manual
Laptop / PC Programming Manual Doc. # Fire PC Program rev B 01.07 This Document is property of Evax Systems, Inc. The Evax Fire Solutions Programmer Components 2 1.0 System Setup 4 1.1 Interface Setup
More informationMatrix Installation Manual. Software Version 4. EN Security Grade 2 Environmental Class 2 RINS918-1
Matrix 424 832 832+ Installation Manual Software Version 4 RINS918-1 EN50131-1 Security Grade 2 Environmental Class 2 CONTENTS 1. INSTALLATION & CABLING RULES...1 1.1 Tools Required... 1 1.2 Mains Wiring...
More informationDL100 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL
DL100 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS 1. GENERAL DESCRIPTION...P.2 2. STANDARD AND OPTIONAL PARTS LIST...P.2 3. FEATURE DEFINITIONS...P.3 4. TERMINAL DRAWING AND
More informationCC408. Quick Reference Guide Solution 880
CC408 EN Quick Reference Guide Solution 880 CC408 Quick Reference Guide Notices EN 2 Copyright Notice Unless otherwise indicated, this publication is the copyright of Bosch Security Systems Pty Ltd ( Bosch
More informationM1000 Alarm Annunciator
Data Sheet Alarm Annunciator Reliable Supervision and Control 10 inputs with LED indications Supports both NO/NC input contacts 10 open collector outputs Built-in siren relay Text label for alarm descriptions
More informationFor a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.
Power Supply/Chargers Installation Guide Models Include: eflow4na8-4a @ 12VDC or 24VDC - Eight (8) Fused Outputs eflow6na8-4a @ 12VDC or 24VDC - Eight (8) Fused Outputs eflow102na8-10a @ 12VDC - Eight
More information(Updated Defaults) (Covers Ver: 8.64 and above)
Power Wave - 8 8 Zone Alarm Panel V8.71 / 8.72 (Updated Defaults) (Covers Ver: 8.64 and above) Installation Manual 10-December-2003 Crow (Aust) Electronic Engineering Pty Ltd Corporate Head Office: 429
More informationALARM... CONTROL... PANELS... AND... KEYPADS...- WIRED...
ALARM... CONTROL..... PANELS... AND... KEYPADS....- WIRED........ Securi-Prod 4 Zone Perimeter Alarm 4 x EOL zone alarm panel 2K2 Zone EOL resistance value Multiple Arm/Disarm functions Built in receiver
More informationProtégé EliteSuite Eclipse LED Keypad Installation Manual ELT-KLES
Protégé EliteSuite Eclipse LED Keypad Installation Manual ELT-KLES The specifications and descriptions of products and services contained in this manual were correct at the time of printing. Integrated
More informationSI120 Guarto Easy I. Alarm system. Fire & Security Products
Alarm system SI120 Guarto Easy I Central alarm control unit with integrated communicator Simple to program Simple and reliable to operate Flexible Extensive communications Simple to install Alarm receiving
More informationIntelligent addressable fire alarm control panel
Intelligent addressable fire alarm control panel Input current consumption: Panel rating: Batteries: Networking and Interfaces Panel to panel communication: Number of panels: Interface port: System capacity
More informationCONTACT ID REPORT CODES
CONTACT ID REPORT CODES PREFIX - E - ACTIVATION PREFIX - R - RESTORAL 100 Medical Zone 101 Personal Emergency Zone 102 Fail to report in Zone Fire Alarms 110 110 Fire Zone 111 Smoke Zone 112 Combustion
More informationM2M Services Ltd. RControl Alarm - Installer Manual V 1.0
M2M Services Ltd. RControl Alarm - Installer Manual V 1.0 Content Content... 2 Wiring the power supply module... 3 Wiring a siren... 3 SMARTEnroll self-learning zones... 3 Wireless keyfobs... 3 Supported
More information