1 Service Bulletin No MODEL TYPE SECTION/GROUP DATE E / J Series Coaches Service Information 8--Engine Mar. 30, 2006 SUBJECT AMEREX FIRE SUPPRESSION SYSTEM CONDITIONS Service Information Only Description: Effective with unit number 63495, MCI began installing the provision for the Amerex fire suppression system on E and J model coaches. The AMEREX fire suppression system is a completely automatic system which continuously monitors the engine compartment for any fire hazards. The system utilizes strategically located thermostats which are connected to an electronic control panel module. The control module features an engine shutdown circuit to minimize the fire hazard. This suppression system utilizes an electronic triggering device for release of the dry chemical compound ( ABC ) extinguishing agent. Attached to this bulletin are Supplement pages for the AMEREX fire suppression system, that can be inserted into the MCI E4500 / J4500. Printed in Canada

2 Date December 2005 Page 8D-1 E4500 & J4500 Series SECTION 8D AMEREX FIRE SUPPRESSION SYSTEM CONTENTS OF THIS SECTION SUBJECT PAGE General Description... 8D-2 Components... 8D-2 Operation... 8D-2 Maintenance... 8D-4 Specifications... 8D-5 Resettable Fire Alarm Sensors... 8D-6 General Description... 8D-6 Maintenance... 8D-6 Specifications... 8D-7

3 E4500 & J4500 Series Date December 2005 Page 8D-2 GENERAL DESCRIPTION The AMEREX fire suppression system is a completely automatic system which continuously monitors the engine compartment for any fire hazards. The system utilizes strategically located thermostats which are connected to an electronic control panel module. The control module features an engine shutdown circuit to minimize the fire hazard. This suppression system utilizes an electronic triggering device for release of the dry chemical compound (ABC) extinguishing agent. COMPONENTS The suppression system installation is made up of several major components, which are mounted at various locations throughout the coach. Control Module The control module is responsible for auto function and fault detection of the system. The control module is mounted on the driver s side A-post, and incorporates both audible and visual alarms to warn of any hazard. System status is displayed with red and green LEDs in conjunction with the audible alarm. This unit is wired directly to the batteries for continuous duty and interconnects with the thermostats and manual actuator. Thermostats Three normally-open thermostats are mounted inside the engine compartment to monitor temperature heat levels. The high temperature trigger thermostat (350_F) is located directly over the engine turbocharger assembly. There are two low temperature thermostats [280_F (138_C)]. One is located on the rear cross seat in front of engine over the AC compressor and alternator. The other is located on the crossmember to the right of the engine over the exhaust manifold. The sensors are connected directly to the control panel module. The 350_F (177_C) sensor is required in the high temperature area above the turbo to prevent an inadvertent discharge. Manual Actuator The manual actuator switch is mounted to the left of the driver on the console. with easy access to the ring pin and FIRE button. To activate the switch, the operator must pull the safety ring pin, breaking the plastic lockwire seal, and press the red FIRE button. This action signals the electronic control module, which sounds the audible alarm, discharges the agent cylinder and shuts down the engine (15 seconds). Chemical Cylinder A 25 pound pressurized chemical cylinder is mounted in a special bracket and located in the #3 LH baggage compartment. This tank is fitted with a discharge valve and electronic control head assembly. The release valve is connected by hose to a central distribution block. OPERATION When the thermostats mounted in the engine compartment sense a fire, a signal is sent to the control head on the agent cylinder. The system can also be manually activated by pressing the manual actuation button in the driver s area. The electric actuator opens the discharge valve on the agent cylinder, allowing the pressurized dry chemical to flow through the distribution holes and through the four spray nozzles located in the engine compartment, extinguishing the fire. CONTROL PANEL MODULE Normal Operation During normal operations, a green System OK LED is illuminated on the front of the control panel to indicate that all circuits are intact and functioning properly. Fire Condition When either of the normally-open thermostats heat up to their preset temperature, their contacts close and actuate a ground to energize the panel alarm mode circuit. During hazard conditions, the control panel s green SYSTEM OK LED goes out and a red FIRE LED illuminates. Simultaneously, the control panel s engine shutdown timer begins its countdown, and energizes the control head on the agent cylinder valve. The audible buzzer continually sounds during hazard events (see Figure 1). This alarm will continue to operate until the PUSH TO SILENCE button on the control panel is actuated. When the silence button has been pushed, a SILENCE ENGAGED LED is illuminated. The alarm must sound before the silence button becomes operational. The alarm cannot be set to silence prior to a fire or a fault condition.

4 Date December 2005 Page 8D-3 E4500 & J4500 Series NOTE: As a safety provision, the engine shutdown RELAY RESET button may be activated at any time before the countdown time reaches zero. This resets the time to its original pre--set time. This may be done as many times as necessary to safely bring the coach to a controlled stop. When the timer reaches zero, the RELAY RESET switch shuts the engine down, and the RELAY ENGAGED LED remains on. Figure 1. Control Panel When the fire is extinguished and the thermostat cools, its contacts reopen. The red LEDs remain illuminated until the system is serviced and the control panel is reset. Fault Condition If a fault condition occurs in the electrical actuator circuit, both red FIRE LEDs illuminate, the audible alarm sounds, and the shutdown time will start. The red FIRE LED will remain on until the fault condition is repaired. ACTUATOR Automatic Operation When a thermostat closes, current passes through the actuator and electrically fires it. The detonation of the cartridge produces enough force to drive the actuator stem through the nitrogen cylinder s rupture disc. When the stem punctures the nitrogen cylinder s seal, it releases pressure into the trigger line. Manual Operation The manual function is used when a fault exists that could inhibit auto/electrical detonation of the electric actuator via the circuit monitor or if fire is noticed before the the preset temperature sensor is reached. During a fire emergency, the driver would manually pull the disarming pin press the red FIRE button.

5 E4500 & J4500 Series Date December 2005 Page 8D-4 The automatic fire protection system has specific maintenance requirements regarding the scheduled replacement of components and the testing of the automatic alarm mode circuits. TESTING Semi-annual testing of the fire suppression system s automatic firing and triggering components should be performed to assure that they work correctly. The AMEREX squib simulator module is used to properly test the alarm mode circuit. NOTE: The Test button (below the Amerex Diamond) may be depressed to quickly check proper operation of all circuit monitor/control panel features. Holding the button down until the timer reaches zero will cause engine shut down. Alarm Mode Circuit Do not perform the following test with the electric actuator installed and electrically connected. A system discharge will result. 1. Clean all thermo sensors and the circuit monitor to remove dirt, grease and other foreign materials. Check sensors for dents, punctures or other damage and replace, if necessary. Check all power connection and wiring harnesses for cuts, abrasions or heat damage and repair or replace as needed. 2. Remove the electric actuator lead from the electric control head and attach it to the simulator module. 3. Depress the reset button on the simulator. The circuit monitor should indicate a normal condition with the green System OK LED illuminated. Exercise extreme care when performing this procedure. Assure that no hazards exist that could be ignited by the heat source. 4. Apply a suitable heat source near the thermo sensor until the contacts close. Test the function of each sensor individually. 5. When the sensor contacts close, the circuit monitor should enter alarm mode. The green System OK MAINTENANCE LED goes out and a red FIRE LED illuminates as described earlier. 6. Remove the heat source and allow the sensor to cool. The red FIRE LED should remain lit and the audible alarm will continue to operate. NOTE: During the test, the alarm can be silenced, however, the LED will remain illuminated until the system is reset. 7. Depress the reset button on the Test Module and the monitor will return to normal mode. Repeat this test for each of the thermo sensors. 8. Verify that all thermo sensors have cooled as indicated by the green System OK LED on front of circuit monitor. 9. Reconnect the electric actuator lead. REPLACEMENT Dry Chemical Cylinder & Discharge Valve 1. Remove the fired electric actuator from the control head. Replace the electric actuator. Reset electric control head following instructions included with the electric actuator. 2. Disconnect the discharge hose, fitting and retaining flange from the valve body. Install the anti-recoil plate. 3. Remove the two padded straps that secure the agent cylinder by removing the four 1/2 inch bolts, washers, and locknuts. 4. Replace the spent dry chemical cylinder and discharge valve assembly with a fully charged cylinder. 5. Resecure the cylinder into its mounting straps and reinstall the retaining flange, discharge hose fitting and connect hose. 6. Reattach the electric control head onto the discharge valve. Electric Actuator NOTE: Electric actuators have a maximum field service life of 6 years and a shelf storage life of 12 years. 1. Disconnect the electric actuator connector lead. 2. Connect the actuator simulator module to the connector lead. Push the reset button. The status of the fire suppression system should indicate normal. 3. Disconnect the simulator module. 4. Unfasten and remove the electric actuator from the control head.

6 Date December 2005 Page 8D-5 E4500 & J4500 Series 5. Install a new actuator into the control head. 6. Verify that the green SYSTEM OK LED is illuminated and the red FIRE LED is OFF on circuit monitor. Control Panel Module 1. Place battery disconnect switch OFF. 2. Disconnect the electric actuator. 3. Remove four mounting screws from the control panel. 4. Disconnect the wiring harness from control panel and remove. 5. Replace with new control panel and reconnect harness. 6. Perform an alarm mode circuit test as described earlier in this section. 7. Reinstall the control panel in the same location. 8. Reconnect the electric actuator. 9. Place battery disconnect switch ON. 10. Verify that the green SYSTEM OK LED is illuminated and the red FIRE LED is OFF on circuit monitor. SPECIFICATIONS Thermostats 1. Place battery disconnect switch OFF. 2. Disconnect the electric actuator and connect the squib simulator. 3. Disconnect the thermostat wire harness. 4. Unfasten and remove the thermostat from its mounting position. NOTE: Install the correct temperature thermostat in the proper location. 5. Reconnect the thermostat wire harness. 6. Check to see if the System OK LED is on. 7. Reconnect the electric actuator. 8. Disconnect the squib simulator. 9. Perform an alarm mode circuit test as described earlier in this section. 10. Place battery disconnect switch ON. 11. Verify that the green SYSTEM OK LED is illuminated and the red FIRE LED is OFF on circuit monitor. DRY CHEMICAL CYLINDER & DISCHARGE VALVE S/A Part Number... 3L THERMO SENSOR Part Number [280_F (138_C)]... 3L Part Number [350_F (177_C)]... 3L CIRCUIT MONITOR/CONTROL PANEL Part Number... 7L AMEREX SQUIB SIMULATOR Part Number

7 E4500 & J4500 Series Date December 2005 Page 8D-6 RESETTABLE FIRE ALARM SENSORS GENERAL DESCRIPTION The resettable fire alarm protection system provides audible and visual warning if a fire occurs in the engine compartment area. COMPONENTS The system consists of two automatically self-resetting alarm sensors, warning light and bell. The sensors mount to the rear cross seat panel, directly above the engine. The warning bell is located in the parcel rack junction box. This system is energized through the parcel rack junction box and connects by wire harness to the sensors (see Figure 2). ALARM SENSOR OPERATION If a fire occurs, the normally-open alarm sensors reach activating temperature and close and complete ground for the circuit. The circuit remains energized during the fire, and resets to the open position after the bimetal sensor cools. NOTE: The alarm sensor s activating temperature is preset at 360F (182 C). HARNESS Figure 2. Fire Detection Sensors C0651 MAINTENANCE LAMP REPLACEMENT 1. Turn disconnect switch to OFF position. 2. Unfasten and remove telltale cluster containing warning lamp from instrument panel. 3. Disconnect lamp from housing and replace.

8 Date December 2005 Page 8D-7 E4500 & J4500 Series SENSOR REPLACEMENT 3. Unfasten and remove sensor from panel and 1. Turn disconnect switch to OFF position. 2. Disconnect sensor harness from rear junction box harness. discard. 4. Attach new sensor and reconnect harnesses. SPECIFICATIONS SENSOR Manufacturer... Fenwal Part Number

9 E4500 & J4500 Series Date December 2005 Page 8D-8 THIS PAGE INTENTIONALLY LEFT BLANK

Basic Vehicle Fire Protection Manual

Basic Vehicle Fire Protection Manual Basic Vehicle Fire Protection Manual Basic Vehicle Fire Protection Manual TABLE OF CONTENTS Introduction... 3 System Operation...... 5 Component Overview.... 7 Operator Controls Control Panel.........

More information

SECTION AUXILIARY HEATER

SECTION AUXILIARY HEATER 14-301.03/ 1 2010MR12 SECTION 14-301.03 GENERAL DESCRIPTION The Thermo 300 auxiliary heating system is used in conjunction with the vehicle s heating system, in order to heat the passenger compartment

More information

Service Bulletin No. 241

Service Bulletin No. 241 Service Bulletin No. 241 MODEL TYPE SECTION/GROUP DATE E4500 / J4500 Series Coaches Field Change Program 16-- HVAC Apr. 27, 2005 SUBJECT SPORLAN WATER VALVE FLOW WASHER CONDITIONS Description: MCI is informing

More information

Ventless Operation Supplement GBF-D-VH

Ventless Operation Supplement GBF-D-VH Operations & Service Manual GBF-5D-VH GBF-50D-VH Ventless Operation Supplement GBF-D-VH Giles Enterprises, Inc. An ISO900 Registered Company Committed to Quality 750 Gunter Park Drive West Montgomery,

More information

Kiddie After Discharge Clean-Up

Kiddie After Discharge Clean-Up Kiddie After Discharge Clean-Up 1 All information provided is intended for informational purposes only and should not be used to replace either technical documents, manuals, guides, manufacturer information

More information

SERVICE MANUAL VC3ED FULL SIZE ELECTRIC CONVECTION OVEN - NOTICE -

SERVICE MANUAL VC3ED FULL SIZE ELECTRIC CONVECTION OVEN - NOTICE - SERVICE MANUAL VC3ED FULL SIZE ELECTRIC CONVECTION OVEN VC3ED ML-137013 - NOTICE - This Manual is prepared for the use of trained Vulcan Service Technicians and should not be used by those not properly

More information

Installation Instructions

Installation Instructions Installation Instructions Page 1 of 10 January 2009 Audio, Alarm Ver 4.0 Accessory Development These installation instructions supersede all previous versions. SUBJECT ALARM RETROFIT - P/N 65 73 0 427

More information

TECHNICAL INFORMATION Touchtronic Clothes Dryers

TECHNICAL INFORMATION Touchtronic Clothes Dryers TECHNICAL INFORMATION Touchtronic Clothes Dryers Includes: T1302, T1303, T1322, T1329ci T1403 & T1405 2004 Miele This page intentionally left blank. Table of Contents GENERAL INFORMATION A. Warning and

More information

ANSUL AUTOMAN II-C EXPLOSION PROOF RELEASING DEVICE Installation, Operation, and Maintenance Manual

ANSUL AUTOMAN II-C EXPLOSION PROOF RELEASING DEVICE Installation, Operation, and Maintenance Manual ANSUL AUTOMAN II-C EXPLOSION PROOF RELEASING DEVICE Installation, Operation, and Maintenance Manual 001799 This manual is intended for use with the ANSUL AUTOMAN Il-C Explosion-Proof Releasing Device.

More information

User Operation Manual

User Operation Manual APPROVED BY: JBJ PRESCIENT III FIRE ALARM & GAS EXTINGUISHING CONTROL PANEL User Operation Manual PAGE 1 of 6 1 CONTENTS 1. FIRE - GENERAL... 3 2. FIRE - ZONES 1 OR 2 - AUTOMATIC MODE... 3 3. FIRE - ZONES

More information

TECHNICAL INFORMATION T1500 Series Clothes Dryers

TECHNICAL INFORMATION T1500 Series Clothes Dryers TECHNICAL INFORMATION T1500 Series Clothes Dryers 2003 Miele - Table of Contents 1.0 CONSTRUCTION & DESIGN 1.1 Appliance Overview - Vented 1 1.2 Appliance Overview Condenser Models 2 1.3 Controls Overview

More information

Bombardier Challenger Fire Protection

Bombardier Challenger Fire Protection GENERAL The fire protection system is divided into two separate subsystems: Fire and overheat detection system; and Fire extinguishing system. The fire and overheat detection system includes components

More information

GAS RACK OVENS WITH ELECTRONIC OVEN CONTROL

GAS RACK OVENS WITH ELECTRONIC OVEN CONTROL GAS RACK OVENS WITH ELECTRONIC OVEN CONTROL MODELS DRO2G DRO2GH GAS GAS 701 S. RIDGE AVENUE TROY, OHIO 45374-0001 937-332-3000 www.hobartcorp.com FORM 19202 Rev. D (Dec. 2003) IMPORTANT FOR YOUR SAFETY

More information

CHECKFIRE 110 DETECTION AND ACTUATION SYSTEM

CHECKFIRE 110 DETECTION AND ACTUATION SYSTEM CHECKFIRE 110 DETECTION AND ACTUATION SYSTEM PLANNING, INSTALLATION, Operation, and Maintenance Manual One Stanton Street / Marinette, WI 54143-2542, USA / +1-715-735-7411 / www.ansul.com Copyright 2014

More information

Lightning Warning System: LWS MK-II. User's Guide. KOREA EMI Technologies Co.,Ltd , Jangam-ri, Majang-myeon, Icheon-si, Gyeonggi-do, Korea

Lightning Warning System: LWS MK-II. User's Guide. KOREA EMI Technologies Co.,Ltd , Jangam-ri, Majang-myeon, Icheon-si, Gyeonggi-do, Korea User's Guide CONTENTS FEATURES WHAT YOU NEED TO GET STARTED INSTALLATION DETAILS Installing the Antenna Installing the External Alert Siren The main console OPERATING PROCEDURE Power On Routine Push Buttons

More information

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.01 SUMMARY SECTION 15371 KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM A. Section Includes: A complete wet chemical automatic fire suppression system for the exhaust hood, including necessary

More information

Water Distiller Service Manual

Water Distiller Service Manual Water Distiller Service Manual Water Distiller Service Manual L70478WT 2008 Regal Ware, Inc. Table of Contents RECOMMENDED TOOLS... 2 GENERAL INSPECTION...3 BOILING CHAMBER TROUBLESHOOTING & REPAIRS Description...

More information

Types of Detection. Fusible Link Detection - Most Common

Types of Detection. Fusible Link Detection - Most Common Types of Detection Fusible Link Detection - Most Common Types of Detection Electric Detection Types of Detection Pneumatic Detection-Tubing Pneumatic Tubing 3 Year Service life Survey Hazard 1) List all

More information

DISTRIBUTION > HOUSING, HVAC > INSTALLATION > AIR INLET HOUSING

DISTRIBUTION > HOUSING, HVAC > INSTALLATION > AIR INLET HOUSING Page 1 of 6 Service Manual: HEATING & AIR CONDITIONING - Print Date: SERVICE INFORMATION - 2500 HD & 3500 HD DISTRIBUTION > HOUSING, HVAC > INSTALLATION > AIR INLET HOUSING Fig 1: Front Of Air Inlet Housing

More information

CHECKFIRE 110 DETECTION AND ACTUATION SYSTEM

CHECKFIRE 110 DETECTION AND ACTUATION SYSTEM CHECKFIRE 110 DETECTION AND ACTUATION SYSTEM OWNERS GUIDE 2017 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject

More information

MODEL A-316 CARBON MONOXIDE (CO) MONITOR AND ALARM FOR COMPRESSED AIR TESTING

MODEL A-316 CARBON MONOXIDE (CO) MONITOR AND ALARM FOR COMPRESSED AIR TESTING MODEL A-316 CARBON MONOXIDE (CO) MONITOR AND ALARM FOR COMPRESSED AIR TESTING FOR OPERATION FROM 115 AC POWER Andersen Medical Gas 12 Place Lafitte Madisonville, LA 70447 http://www.themedicalgas.com 1-866-288-3783

More information

HVAC Module Assembly Replacement. Tools Required. J A Halogen Leak Detector. Removal Procedure

HVAC Module Assembly Replacement. Tools Required. J A Halogen Leak Detector. Removal Procedure 2005 Pontiac Grand AM V6-3.4L VIN E Page 1 Housing Assembly HVAC: Service and Repair The content of this article reflects the changes identified in TSB Bulletin No. #06-01-37-002 dated January 18, 2006.

More information

CIRRUS AIRPLANE MAINTENANCE MANUAL

CIRRUS AIRPLANE MAINTENANCE MANUAL EXTINGUISHING 1. DESCRIPTION The airplane is equipped with a liquefied-gas type fire extinguisher mounted within a quick-release bracket assembly. The extinguishing agent is Halon 1211/101 blend and is

More information

URBAN CRUISER AIR CONDITIONING (RHD) ENGLISH EUROPE

URBAN CRUISER AIR CONDITIONING (RHD) ENGLISH EUROPE URBAN CRUISER (RHD) AIR CONDITIONING ENGLISH EUROPE - 0 - IMPORTANT NOTICE DEFINITION OF TERMS INTRODUCTION This manual has been designed for technicians who are qualified and educated in the proper procedures

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS Accessory Application Publications No. AII 30320 ENGINE BLOCK 2006 CIVIC HYBRID P/N 08T44-SVB-100 Issue Date SEP 2005 PARTS LIST Engine block heater Aluminium washer Heater harness

More information

SECTION TOTAL FLOODING ECARO-25 CLEAN AGENT FIRE EXTINGUISHING SYSTEM

SECTION TOTAL FLOODING ECARO-25 CLEAN AGENT FIRE EXTINGUISHING SYSTEM SECTION 13966 TOTAL FLOODING ECARO-25 CLEAN AGENT FIRE EXTINGUISHING SYSTEM Display hidden notes to specifier by using Tools / Options / View / Hidden Text. PART 1 GENERAL 1.1 SECTION INCLUDES A. Total

More information

Product Support Bulletin

Product Support Bulletin MODEL: SUBJECT: CONVENTIONAL, W/ C7 CAT ENGINE WEBASTO TSL-17 HEATER Body DATE: APRIL 13, 2004 INDEX: 6 PAGE: 1 OF 16 Before you start this procedure, perform Freightliner Service Bulletin #20-7 first.

More information

OWNERS SERVICE MANUAL NO INSTALLATION, OPERATING & SERVICING INSTRUCTIONS

OWNERS SERVICE MANUAL NO INSTALLATION, OPERATING & SERVICING INSTRUCTIONS STORED PRESSURE, WHEELED & STATIONARY 50 POUND DRY CHEMICAL FIRE EXTINGUISHERS ABC (AMMONIUM PHOSPHATE BASE), REGULAR (SODIUM BICARBONATE BASE), PURPLE K (POTASSIUM BICARBONATE BASE) OWNERS SERVICE MANUAL

More information

Amerex Fire Suppression Systems. Because Operators and the Environment are NOT Disposable Quality is Behind the Diamond.

Amerex Fire Suppression Systems. Because Operators and the Environment are NOT Disposable Quality is Behind the Diamond. Amerex Fire Suppression Systems Because Operators and the Environment are NOT Disposable Quality is Behind the Diamond. Quality is Behind the Diamond. Diamonds have long been a symbol for quality. At Amerex

More information

SFC-200 SERIES LED FIRE ALARM PANEL

SFC-200 SERIES LED FIRE ALARM PANEL SFC-200 SERIES LED FIRE ALARM PANEL USER GUIDE LT-953SUM SFC-200 Series LED Version User Guide Contents Contents... i Introduction... 1 About this Manual... 1 Technical Support... 1 Main Display... 2

More information

WHEELED STORED PRESSURE

WHEELED STORED PRESSURE OWNERS SERVICE MANUAL NO. 19795 INSTALLATION, OPERATING & SERVICING INSTRUCTIONS All fire extinguishers should be installed, inspected and maintained in accordance with the National Fire Protection Association

More information

3500 SERIES CONVECTION STEAM COOKER PARTS AND SERVICE MANUAL

3500 SERIES CONVECTION STEAM COOKER PARTS AND SERVICE MANUAL 3500 SERIES CONVECTION STEAM COOKER PARTS AND SERVICE MANUAL EFFECTIVE JULY 30, 2014 Superseding All Previous Parts Lists. The Company reserves the right to make substitution in the event that items specified

More information

PAT E N T System 88. COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00

PAT E N T System 88. COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00 PAT E N T System 88 COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00 Pg 1 of 12 CONTENTS 1. GENERAL 1.1 Introduction 2 1.2 System Description

More information

PURPLE K POWDER EXTINGUISHERS INSTALLATION, OPERATION, MAINTENANCE AND RECHARGE MANUAL

PURPLE K POWDER EXTINGUISHERS INSTALLATION, OPERATION, MAINTENANCE AND RECHARGE MANUAL PURPLE K POWDER EXTINGUISHERS INSTALLATION, OPERATION, MAINTENANCE AND RECHARGE MANUAL NO. 05602 FOR AMEREX STORED PRESSURE, HAND PORTABLE DRY CHEMICAL FIRE EXTINGUISHERS. ABC (Ammonium Phosphate Base)

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with automatic detection and control. The work described in

More information

KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.01 SUMMARY SECTION 15371 KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM A. Section Includes: A complete automatic fire suppression system for the exhaust hood, including necessary accessories.

More information

Lubrication cycle IP Enclosure Rating. 110 VAC, 220/230 VAC (50/60 Hz) Alarm Fault Relay Contacts. IP-55 (Liquid tight connector)

Lubrication cycle IP Enclosure Rating. 110 VAC, 220/230 VAC (50/60 Hz) Alarm Fault Relay Contacts. IP-55 (Liquid tight connector) SMAC Controller Industrial Lubrication Systems Operation The SMAC Controller is a multi-purpose programmable controller used with industrial lubrication systems. Controller settings are saved whenever

More information

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM SECTION 1 - GENERAL CONDITIONS SPECIFICATION FOR A TOTAL FLOOD I. SCOPE: This specification outlines the requirements for a Total Flood ECARO-25 TM clean agent fire suppression system utilizing HFC-125

More information

Part Number Rev. B May 2011 Page 1 INSTALLATION, OPERATION AND MAINTENANCE MANUAL. No Revision B May SafetyNet

Part Number Rev. B May 2011 Page 1 INSTALLATION, OPERATION AND MAINTENANCE MANUAL. No Revision B May SafetyNet Part Number 16601 Rev. B May 2011 Page 1 INSTALLATION, OPERATION AND MAINTENANCE MANUAL No. 16601 Revision B May 2011 SafetyNet VEHICLE FIRE SUPPRESSION SYSTEM CONTROL COMPONENTS Amerex Corporation Post

More information

TOP AND CABINET PARTS For Models: LSQ9659LW1, LSQ9659LG1 (White/Grey) (Biscuit/Gold)

TOP AND CABINET PARTS For Models: LSQ9659LW1, LSQ9659LG1 (White/Grey) (Biscuit/Gold) TOP AND CABINET PARTS AUTOMATIC WASHER 5 03 Litho in U.S.A.(drd) 1 Part No. TOP AND CABINET PARTS 1 Literature Parts LIT3956025 Installation Instructions LIT3955869 Use & Care Guide LIT3955903 Feature

More information

tcm100, tcm101 Series Temperature Control Modules and PTS100, PTS100/3 Pipe Temperature Sensors Operations Manual

tcm100, tcm101 Series Temperature Control Modules and PTS100, PTS100/3 Pipe Temperature Sensors Operations Manual tcm100, tcm101 Series Temperature Control Modules and PTS100, PTS100/3 Pipe Temperature Sensors Operations Manual This manual covers operation of the tcm100 and tcm101 Series Temperature Control Modules.

More information

CIRRUS AIRPLANE MAINTENANCE MANUAL

CIRRUS AIRPLANE MAINTENANCE MANUAL COOLING 1. DESCRIPTION On aircraft serials 183 and subsequent, an optional air condition system is available. This section contains the maintenance practices pertinent to this system. Cabin ventilation

More information

Heating and ventilation system,

Heating and ventilation system, Page 1 of 24 87-151 Heating and ventilation system, servicing Instrument panel air outlets and air guide ducts CAUTION! Before working on the electrical system: Obtain security code for anti-theft radio.

More information

UNDERCOUNTER DISHWASHER

UNDERCOUNTER DISHWASHER CORPORATION UNDERCOUNTER DISHWASHER MODEL DU8500XX3 Almond/Black 7 92 Litho In U.S.A. c 1992 WHIRLPOOL CORPORATION Part No. FRAME AND CONSOLE PARTS 1 3370310 Console (Includes Item 2) 2 3370309 Insert,

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE October 10, 2008 Deluge Devices 281a 1. PRODUCT DESCRIPTION The Viking Model C-1 is a rate-of-rise releasing device for use on hydraulic and pneumatic release systems controlling operation of Viking deluge

More information

TT /97. Features INSTALLATION INSTRUCTIONS. Horn. Lamps

TT /97. Features INSTALLATION INSTRUCTIONS. Horn. Lamps TT-1023 1/97 INSTALLATION INSTRUCTIONS Original Issue Date: 2/94 Model: 6-2000 kw Market: Industrial Subject: Flush- or Surface-Mount Remote Annunciator Kits PA-293991 and PA-293991-SD The remote annunciator

More information

Data/ Specification Sheet

Data/ Specification Sheet Data/ Specification Sheet MONARCH Dry Chemical Automotive Paint Spray Booth Fire Suppression System TM 1. Fixed temperature mechanical or thermal detectors 2. Electrical conduit protecting stainless steel

More information

SPECIFICATION: DRY CHEMICAL FIRE SUPPRESSION SYSTEM FOR INDUSTRIAL APPLICATIONS MODEL IND

SPECIFICATION: DRY CHEMICAL FIRE SUPPRESSION SYSTEM FOR INDUSTRIAL APPLICATIONS MODEL IND 1. GENERAL SPECIFICATION 1.1 A pre-engineered, fixed pipe, automatic dry chemical fire suppression system shall be provided and installed for the hazard including work area, plenums and all exhaust ventilation

More information

MODEL 5800A CARBON MONOXIDE (CO) MONITOR AND ALARM SAMPLE-DRAWING TYPE

MODEL 5800A CARBON MONOXIDE (CO) MONITOR AND ALARM SAMPLE-DRAWING TYPE MODEL 5800A CARBON MONOXIDE (CO) MONITOR AND ALARM SAMPLE-DRAWING TYPE 11//07 A153-021500-1 INSTRUCTION MANUAL - MODEL 5800A CO ALARM I INTRODUCTION This MST Model 5800A Carbon Monoxide (CO) Alarm is a

More information

FRAME AND CONSOLE PARTS

FRAME AND CONSOLE PARTS FRAME AND CONSOLE PARTS UNDERCOUNTER DISHWASHER 1 3375275 Console (Includes Item 2) 2 3376026 Insert, Console 3 3376029 Switch, 5 Pushbutton 4 3369529 Follower, Cam 5 3373626 Timer 6 3369415 Cam 7 304231

More information

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY...................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS.......................... 2 INTERMITTENT IGNITION DEVICE..........

More information

Please read this manual completely before attempting to install, operate or service this equipment.

Please read this manual completely before attempting to install, operate or service this equipment. Service Manual POWER OVEN OFF COOL DOWN COOK LIGHT OFF OVEN READY TEMPERATURE GAS CONVECTION OVEN TIME GAS SHUTOFF ON OFF MODELS 6/13 THE OVEN E SERIES Please read this manual completely before attempting

More information

ANSUL ANSUL AUTOMAN II-C RELEASING DEVICE

ANSUL ANSUL AUTOMAN II-C RELEASING DEVICE ANSUL INSTALLATION OPERATION AND MAINTENANCE MANUAL ANSUL AUTOMAN II-C RELEASING DEVICE 001799 This manual is intended for use with the ANSUL AUTOMAN II-C Releasing Device. Those who install, inspect,

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with a Cheetah Xi 50 addressable detection and control system.

More information

Products documentation (REVISION DATE: 03/10/2011) OMFP6010 (60cm PIROLITIC OVEN)

Products documentation (REVISION DATE: 03/10/2011) OMFP6010 (60cm PIROLITIC OVEN) Products documentation (REVISION DATE: 03/10/2011) OMFP6010 (60cm PIROLITIC OVEN) Ovens Service Manual Models OMFP6010 CONTENTS This document has been published to be used for service only. The contents

More information

APU FIRE EXTINGUISHING SYSTEM - DESCRIPTION AND OPERATION

APU FIRE EXTINGUISHING SYSTEM - DESCRIPTION AND OPERATION 1.General APU FIRE EXTINGUISHING SYSTEM - DESCRIPTION AND OPERATION A.The APU fire extinguishing system has controls in two locations that release one application of fire extinguishing agent to a fire

More information

WASHER/DRYER CONTROL PANEL PARTS For Models: LTE6234DQ2, LTE6234DZ2, LTE6234DT2 (Designer White) (Designer Almond) (Biscuit)

WASHER/DRYER CONTROL PANEL PARTS For Models: LTE6234DQ2, LTE6234DZ2, LTE6234DT2 (Designer White) (Designer Almond) (Biscuit) WASHER/DRYER CONTROL PANEL PARTS WASHER/DRYER LAUNDRY SYSTEM 1 Literature Parts Installation Instructions LIT3397616 English LIT3397634 Arabic Use & Care Guide LIT3401097 English LIT3405528 Arabic LIT8299786

More information

Full Size Canister Service Manual Riccar Models 1700 / 1800 Power Nozzles RPB-100 / RPB-220 / RPB-224 / RPB-250

Full Size Canister Service Manual Riccar Models 1700 / 1800 Power Nozzles RPB-100 / RPB-220 / RPB-224 / RPB-250 Full Size Canister Service Manual Riccar Models 1700 / 1800 Power Nozzles RPB-100 / RPB-220 / RPB-224 / RPB-250 Table of Contents I. General Full Size Canister Issues...2 A. Full Bag Indicator...2 1. General

More information

2002 Dodge Caravan SE

2002 Dodge Caravan SE EVAPORATOR (FRONT) Removal 1. Remove the HVAC housing from the vehicle. See HVAC HOUSING (FRONT). Remove the heater hoses from the heater core. 2. Remove and discard the foam seal from the HVAC housing

More information

Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses

Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses BCU Power Supplies Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses Installation, Commissioning and Operating Manual BCU RANGE OF

More information

OPERATION & INSTALLATION MANUAL FOR ALARM PANEL M2AP01

OPERATION & INSTALLATION MANUAL FOR ALARM PANEL M2AP01 OPERATION & INSTALLATION MANUAL FOR ALARM PANEL M2AP01 Table of Contents Safety Instructions 4 Owner/Operator Responsibility 4 Specifications 5 Introduction 6 Installation Instructions 7 Setup 7 Wiring

More information

SECTION air supply system + WARNING: + NOTE: GENERAL DESCRIPTION COMPRESSED AIR RESERVOIRS / 1.

SECTION air supply system + WARNING: + NOTE: GENERAL DESCRIPTION COMPRESSED AIR RESERVOIRS / 1. 08-000.02/ 1 2011JA14 SECTION 08-000.02 GENERAL DESCRIPTION See Figure 1 for a schematic diagram of the. See the Nova LFS parts manual for a detailed schematic of the. The function of the vehicle s is

More information

CORE Protection Fire System Specification

CORE Protection Fire System Specification CORE Protection Fire System Specification The CORE restaurant fire suppression system is a pre-engineered, duct and plenum water spray system in conjunction with a wet chemical, cartridge-operated, regulated

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph

More information

OPERATION MANUAL. Move it. Hang it. Rack it. Stack it. MaxPower Corporation 230 Yuma Street Denver, CO

OPERATION MANUAL. Move it. Hang it. Rack it. Stack it. MaxPower Corporation 230 Yuma Street Denver, CO OPERATION MANUAL Complete Instructions for and Operation MaxPower Corporation 230 Yuma Street Denver, CO 80223 800-576-3966 www.coolcube10.com Move it. Hang it. Rack it. Stack it. 05/05 P/N: 5-TC600-2510

More information

EXTINGUISHING AGENT RELEASE MODULE

EXTINGUISHING AGENT RELEASE MODULE EXTINGUISHING AGENT RELEASE MODULE Operation, Installation & Programming Manual Revision 3.00 Distributors For: 18-20 Brookhollow Ave telephone 02 8850 2888 www.firesense.com.au Baulkham Hills NSW 2153

More information

WASHER/DRYER CONTROL PANEL PARTS

WASHER/DRYER CONTROL PANEL PARTS WASHER/DRYER CONTROL PANEL PARTS WASHER/DRYER LAUNDRY SYSTEM 1 3398879 Harness, Console Wiring (Automatic) (Includes Illus. 1A, 1B & 1C) 1A 3350130 Plug, Terminal (2 Way) (Connects With Main Dryer Harness)

More information

Air Heater. Air Top 3500 Diesel. Supplemental Installation Instructions for: Van Body Vehicles

Air Heater. Air Top 3500 Diesel. Supplemental Installation Instructions for: Van Body Vehicles Air Heater Air Top 3500 Diesel Supplemental Installation Instructions for: Van Body Vehicles Table of Contents 1. Introduction 1.1 General Information.............................................. 2 2.

More information

FA-300 Series. LED Fire Alarm Control Panel. User Guide. FA-300 SERIES Fire Alarm Control Panel. FA-300 SERIES Fire Alarm Control Panel

FA-300 Series. LED Fire Alarm Control Panel. User Guide. FA-300 SERIES Fire Alarm Control Panel. FA-300 SERIES Fire Alarm Control Panel LAMP TEST REMOTE CPU FAULT GROUND FAULT SIGNAL SILENECE FIRE DRILL BUZZER SILENCE INFO AC ON ALARM SUPERVISORY BATTERY SYSTEM RESET AUXILIARY DISCONNECT LAMP TEST MENU LAMP TEST REMOTE CPU FAULT GROUND

More information

ENGINE COOLING 14-1 CONTENTS THERMOSTAT... 3 SERVICE SPECIFICATIONS... 2 LUBRICANT... 2 WATER PUMP... 5 ON-VEHICLE SERVICE... 2

ENGINE COOLING 14-1 CONTENTS THERMOSTAT... 3 SERVICE SPECIFICATIONS... 2 LUBRICANT... 2 WATER PUMP... 5 ON-VEHICLE SERVICE... 2 14-1 ENGINE COOLING CONTENTS SERVICE SPECIFICATIONS.............. 2 LUBRICANT............................. 2 ON-VEHICLE SERVICE.................. 2 Coolant Replacement...................... 2 THERMOSTAT...........................

More information

Customer Service...1. Calibration...8. Inspection...9. Lighting Cleaning Features Control Box Digital Timers...

Customer Service...1. Calibration...8. Inspection...9. Lighting Cleaning Features Control Box Digital Timers... Table of Contents MIRACLEAN GRIDDLE Customer Service...1 Keating of Chicago Web Site...4 Miraclean Griddle Features...7 Calibration...8 Inspection...9 Installation...10-12 Leveling...10 Gas Pressure...11

More information

Badger Universal Control Head

Badger Universal Control Head Badger Universal Control Head P/N: 60-120099-002 FEATURES For Use in: Range Guard Commercial Cooking Fire Suppression Systems Industry Guard Industrial Fire Suppression Systems Pneumatic Release of up

More information

ModulAir Air Dryer with External Purge Tank - Changeover from Bendix AD-IS for Peterbilt Installation. Air Dryer Mounting Bracket (Item 1)

ModulAir Air Dryer with External Purge Tank - Changeover from Bendix AD-IS for Peterbilt Installation. Air Dryer Mounting Bracket (Item 1) Instruction Guide L31259 11/10 ModulAir Air Dryer with External Purge Tank - Changeover from Bendix AD-IS for Peterbilt Installation Air Dryer Mounting Bracket (Item 1) Tank Mounting Bracket (Item 19)

More information

TECH SHEET - DO NOT DISCARD PAGE

TECH SHEET - DO NOT DISCARD PAGE TECH SHEET - DO NOT DISCARD PAGE 1 3. If this test mode has been entered successfully, all indicators on the console are illuminated for 5 seconds with 8:88 showing in the Estimated Time Remaining three-digit

More information

Thermo 230 / 231 / 300 / 301 / Troubleshooting

Thermo 230 / 231 / 300 / 301 / Troubleshooting Thermo 230 / 231 / 300 / 301 / 350 5 Troubleshooting 5 Troubleshooting 5.1 General This section describes troubleshooting procedures for the heaters Thermo 230, 231, 300, 301 and 350. CAUTION Troubleshooting

More information

Installation, Operation, and Maintenance Manual RTE14S & RTE14S-2. For the Taco Bell "Rethermalizer" Model Numbers

Installation, Operation, and Maintenance Manual RTE14S & RTE14S-2. For the Taco Bell Rethermalizer Model Numbers Installation, Operation, and Maintenance Manual For the Taco Bell "Rethermalizer" Model Numbers RTE14S & RTE14S-2 NOTICES There are three different types of notices that you should be familiar with, a

More information

P0032-O2 SENSOR 1/1 HEATER CIRCUIT HIGH

P0032-O2 SENSOR 1/1 HEATER CIRCUIT HIGH 8 - ND - DODGE DAKOTA -.7L MAGNUM V8 P-O SENSOR / HEATER CIRCUIT HIGH S6 K9 BR/DG - LEFT FRONT K99 Z K K9 8 8 BR/TN BK/LB DB/LB BR/DG G8 8 C C C O / O / O RETURN HEATER SIGNAL (UPSTREAM) CONTROL CONTROL

More information

Home Stack Washer/Dryers

Home Stack Washer/Dryers Home Stack Washer/Dryers Refer to Page 3 for Model Numbers Parts SWD456C_806093 www.alliancelaundry.com Part No. 806093R1 December 2016 Table of Contents Title Page Parts Ordering Information... 2 Serial

More information

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPUSLE VALVE, Fike FK AGENT & SHP PRO CONTROL PANEL

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPUSLE VALVE, Fike FK AGENT & SHP PRO CONTROL PANEL SECTION 1 GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Total Flood Clean Agent Fire Suppression System utilizing FK-5-1-12 as the fire extinguishing agent and with a

More information

bc14g combi oven serial numbers with iw/ix/iz/jg/jo

bc14g combi oven serial numbers with iw/ix/iz/jg/jo bcg combi oven REPLACEMENT PARTS LIST serial numbers with iw/ix/iz/jg/jo Effective february 0, 05 Superseding All Previous Parts Lists. The Company reserves the right to make substitution in the event

More information

Fire Extinguisher Use. Fire Extinguisher Review. and Fire Safety

Fire Extinguisher Use. Fire Extinguisher Review. and Fire Safety Fire Extinguisher Use Fire Extinguisher Review and Fire Safety Topics to be discussed Fire Safety Fire Extinguisher Use Inspections and Maintenance Simulator Training Fire Safety The ABC s of Fire In order

More information

TOP AND CABINET PARTS

TOP AND CABINET PARTS TOP AND CABINET PARTS AUTOMATIC WASHER 3 00 Litho in U.S.A. (awm) 1 Part No. TOP AND CABINET PARTS 1 Literature Parts Installation Instructions LIT3952817 English LIT3951578 French Use & Care Guide LIT3953953

More information

IMR IX176 Portable Gas Detector User Manual

IMR IX176 Portable Gas Detector User Manual IMR Portable Gas Detector User Manual Read this manual carefully before using this device. (727) 328-2818 / (800) RING-IMR Fax: (727) 328-2826 www.imrusa.com Ver. 1.0A4 CONTENTS SERVICE GUIDELINES... 3

More information

CellarSafe. Carbon Dioxide and Oxygen Safety Monitor

CellarSafe. Carbon Dioxide and Oxygen Safety Monitor CellarSafe Carbon Dioxide and Oxygen Safety Monitor Installation and operating instructions for the CellarSafe Monitor and the CellarSafe Calibration Unit M07234 May 2008 Issue 6 Warning Please take care

More information

TABLE OF CONTENTS PART 4 - HAND TOOLS AND POWER DRIVEN PORTABLE TOOLS

TABLE OF CONTENTS PART 4 - HAND TOOLS AND POWER DRIVEN PORTABLE TOOLS TABLE OF CONTENTS PART 4 - HAND TOOLS AND POWER DRIVEN PORTABLE TOOLS Page DEFINITIONS...4-1 GENERAL...4-1 CHAIN SAWS...4-3 BRUSH SAWS...4-4 POWDER ACTUATED TOOLS...4-5 PORTABLE CIRCULAR SAWS...4-5 PART

More information

Chapter 26 FIRE PROTECTION

Chapter 26 FIRE PROTECTION Chapter 26 FIRE PROTECTION 26-Title Page 1 INTENTIONALLY LEFT BLANK 26-Title Page 2 LIST OF EFFECTIVE PAGES Chapter Section Page No. Date 26 26-Title 1 2 26-LOEP 1 2 26-TOC 1 2 26-20 1 July 28, 2008 2

More information

Specification/ Data Sheet

Specification/ Data Sheet Specification/ Data Sheet TRITON RP Agent Release Control Panel FEATURES Agent Release Control Panel designed specifically for suppression release operation with: Four initiating device circuits (IDCs)

More information

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels CF5000, MF5000 and FXP5000 Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels 16 zone panels Contents PANEL INSTALLATION...3 Installation...3 PANEL WIRING... 3 Mains power

More information

O PE R AT I ON HO851G REVOLVING TRAY OVEN. MODEL HO851G GAS ML Pan ML Pan ML Pan ML Pan

O PE R AT I ON HO851G REVOLVING TRAY OVEN. MODEL HO851G GAS ML Pan ML Pan ML Pan ML Pan O PE R AT I ON HO851G REVOLVING TRAY OVEN MODEL HO851G GAS ML-132160 24 Pan ML-132161 18 Pan ML-132258 36 Pan ML-132259 30 Pan 701 S. RIDGE AVENUE TROY, OHIO 45374-0001 937-332-3000 www.hobartcorp.com

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS Accessory Application Publications No. ENGINE BLOCK P/N 08T44-SNA-100 2007 CIVIC 2 AND 4-DOOR (DX, LX, EX) AII 33542 Issue Date AUG 2006 PARTS LIST Engine block heater Aluminum

More information

HEAT/ COOL/ DEFROST FORD THUNDERBIRD

HEAT/ COOL/ DEFROST FORD THUNDERBIRD specializing in AIR CONDITIONING, PARTS AND SYSTEMS for your classic vehicle PERFECT FIT IN-DASH HEAT/ COOL/ DEFROST 1964-66 FORD THUNDERBIRD CONTROL & OPERATING INSTRUCTIONS The controls on your new Perfect

More information

DISHWASHER - PART RECOGNITION GUIDE

DISHWASHER - PART RECOGNITION GUIDE DISHWASHER - PART RECOGNITION GUIDE SPRAY ARM HOLDER UPPER SPRAY ARM FILTER ASSEMBLY LOWER SPRAY ARM ASSEMBLY SUMP DISHWASHER - PART RECOGNITION GUIDE DISPENSER DOOR SPRING DOOR HINGE INNER DOOR DOOR THERMOSTAT

More information

Owner's Manual TABLE OF CONTENTS

Owner's Manual TABLE OF CONTENTS 40MAQ High Wall Ductless System Sizes 09 to 36 Owner's Manual TABLE OF CONTENTS PAGE A NOTE ABOUT SAFETY... 2 GENERAL... 2 PART NAMES... 3 FUNCTION BUTTONS... 4 DISPLAY PANELS... 5 REMOTE CONTROL... 6

More information

ECOJET EJ-10E & EJ-7E ELECTRIC CONVECTION STEAMER W/TWIN GENERATORS PARTS AND SERVICE MANUAL

ECOJET EJ-10E & EJ-7E ELECTRIC CONVECTION STEAMER W/TWIN GENERATORS PARTS AND SERVICE MANUAL ECOJET EJ-10E & EJ-7E ELECTRIC CONVECTION STEAMER W/TWIN GENERATORS PARTS AND SERVICE MANUAL EFFECTIVE JULY 31, 2014 Superseding All Previous Parts Lists. The Company reserves the right to make substitution

More information

Mazda North American Operations Irvine, CA

Mazda North American Operations Irvine, CA Service Bulletin Mazda North American Operations Irvine, CA 92618-2922 Subject: AIR CONDITIONING MUSTY / MILDEW ODOR Bulletin No: 07-002/13 MULTI-MODEL - AIR CONDITIONING MUSTY / MILDEW ODOR BULLETIN NOTE

More information

G-TECTA Cellaguard Carbon Dioxide and Oxygen Fixed Monitors

G-TECTA Cellaguard Carbon Dioxide and Oxygen Fixed Monitors G-TECTA Cellaguard Carbon Dioxide and Oxygen Fixed Monitors UK Installation & Calibration Manual 2 Contents Safety and Warning information 2 Installation 2 Mounting 3 Cabling Requirements 4 External Alarm

More information

Dexter Commercial Vended Stack Washer Dryer. Dryer Troubleshooting, Fault Codes, And Schematics. Starting serial number (12/13)

Dexter Commercial Vended Stack Washer Dryer. Dryer Troubleshooting, Fault Codes, And Schematics. Starting serial number (12/13) Dexter Commercial Vended Stack Washer Dryer Dryer Troubleshooting, Fault Codes, And Schematics Starting serial number 481983 8533-070-001 (12/13) Dryer Trouble Shooting Electronic Control Diagnostic Lights

More information

This site is based on a but applies to all 1971-on Saab 99 and Saab 900.

This site is based on a but applies to all 1971-on Saab 99 and Saab 900. by Mark Jeter updated: December 8, 2004 originally web-published June 27, 2001 This document shows how the original waterpump in a Saab "B" engine can be eliminated and replaced with a reliable, efficient

More information

PERFECT FIT SERIES IN-DASH HEAT/ COOL/ DEFROST CHEVROLET NOVA

PERFECT FIT SERIES IN-DASH HEAT/ COOL/ DEFROST CHEVROLET NOVA specializing in AIR CONDITIONING, PARTS AND SYSTEMS for your classic PERFECT FIT SERIES IN-DASH HEAT/ COOL/ DEFROST 1966-67 CHEVROLET NOVA CONTROL & OPERATING INSTRUCTIONS The controls on your new Perfect

More information

OWNERS SERVICE MANUAL NO

OWNERS SERVICE MANUAL NO OWNERS SERVICE MANUAL NO. 05608 INSTALLATION, OPERATING AND SERVICING INSTRUCTIONS for AMEREX STORED PRESSURE WHEELED & STATIONARY 125/150 POUND DRY CHEMICAL FIRE EXTINGUISHERS WHEELED STATIONARY Model

More information