1 Bid No. B18-02 Fire Suppression System Bldg 1300 ***Specifications*** Bid RFI Questions Due: Friday, January 26, :00PM Gale Stevens, Buyer copy to BID DOCUMENTS: GALE STEVENS, BUYER CABRILLO COLLEGE: JON SALISBURY, DIRECTOR FACILITIES PLANNING & PLANT OPERATIONS PROJECT MANAGER: NADA MILJKOVIC, ICS,INNOVATIVE CONSTRUCTION SERVICES ARCHITECT: BILL FISHER, WILLIAM FISHER ARCHITECTURE, INC.

2

3 SECTION FIRE SUPPRESSION SYSTEMS PART 1 - GENERAL 1.1 WORK INCLUDED A. Drawings and General Provisions of the Contract, including General and Supplementary Conditions and the following other Sections, apply to work of this Section. B. Where items from the referenced Codes and Standards are repeated in this Specification, it is intended to call attention to them. It is not intended that other parts of the referenced Codes and Standards shall be assumed to be omitted if not repeated in this Specification. C. Include all labor, material, equipment and service necessary for, and reasonably incidental to the design, coordination, procurement, fabrication, and installation of the complete automatic fire protection systems as generally indicated on the Contract Drawings. D. It is the intent of these specifications to describe the complete hydraulically calculated wet pipe sprinkler system. The Contractor is responsible for carefully and critically reviewing the contract plans, specifications, and site conditions to the extent and as far as practicable. Any case of error, omission, discrepancy or lack of clarity shall be promptly identified to the College for clarification. E. In general, work shall include, but not be limited to: 1. Complete overhead automatic sprinkler system as generally indicated on the Contract Drawings. 2. Demolition and proper disposal of items and systems as generally indicated. 3. Underground fire service connection, including new valve and connection to the existing firewater piping, excavation and backfill, surface restoration, underground piping and fittings, concrete thrust blocks, riser assembly, and fire department connection. 4. Fire protection system drains as generally indicated on the Contract Drawings. 5. Installation of flexible connections and seismic bracing. 6. Systems and device testing, including preliminary air testing in accordance with NFPA 13 (2016) Section All necessary permits. F. Project Design Criteria: 1. The new fire sprinkler system protecting the Cabrillo College Building 1300 shall be a hydraulically designed wet pipe system for generally Ordinary Hazard Occupancies (Welding and Wood Shop, Mechanical, etc.). Provide a minimum design discharge of 0.20 gpm per sq ft over the hydraulically most demanding 1,950 sq ft utilizing Standard Response sprinklers. Exception: Corridors, Computer Server, Combustible Concealed Spaces and similar may be provided with Light Hazard protection. 2. Calculations shall be in accordance with NFPA requirements (as amended by the CBC). Page 1 of 7

4 3. All above-ceiling interstitial spaces shall be provided with Light Hazard fire sprinkler protection due to the presence of combustible framing assemblies. 4. Calculations shall include an outside (combined) hose stream allowance of 250 gpm. 5. Fire sprinkler hydraulic calculations shall be based upon the water supply data provided on the Contract Drawings. Hydraulic calculations shall include a minimum 10% Safety Factor (i.e. calculated demand shall not exceed 90% of the available supply). G. Pipe sizes indicated on the Contract Drawings shall not be reduced. H. The Contractor shall be responsible for establishing and implementing all safety programs and procedures and shall comply with all Federal, State and Local Safety and Health Regulations. 1.2 RELATED WORK SPECIFIED ELSEWHERE A. Division 1 - General Requirements B. Section Fire Alarm System 1.3 DRAWINGS A. The Contract Drawings are diagrammatic only. Pipe lengths shown are approximate center to center lengths between fittings. The Contractor shall determine the actual measurements and make any and all such length and offset adjustments as may be necessary to complete the installation at no change in the contract price. The Contract Drawings are not intended to relieve the Contractor of any responsibility for avoiding conflicts or obstructions, or for installing the number of sprinklers and supply piping as required to provide complete protection of the designated areas in accordance with the requirements of the referenced standards and these specifications. Written approval shall be obtained from the College Representative prior to making any major deviations from the arrangement and layout shown on the Contract Drawings. 1.4 QUALITY ASSURANCE A. All equipment shall be Listed by Underwriters Laboratories, and/or approved by Factory Mutual Approved. B. The Contractor shall be a California Licensed Fire Protection Contractor (C-16) experienced in the installation of similar automatic fire protection systems. 1.5 REFERENCES A. System, equipment, installation, and materials and methods used shall comply with the following: 1.6 SUBMITTALS 1. The requirements of Cabrillo College. 2. National Fire Protection Association (NFPA) 13 Standard for the Installation of Sprinkler Systems 2016 Edition (with California amendments). 3. California Building Code California Fire Code Manufacturer's recommendations and guidelines. A. Submit the following for approval in accordance with the General Requirements: Page 2 of 7

5 1. Working Plans as described in NFPA 13, shall be submitted within 30 days after the award of the contract. Installation shall not begin until approval has been received. 2. Shop Drawings: Submit seven prints of each shop drawing. Minimum allowable sheet size is 8-1/2 x 11-in. The Fire Marshal will retain 2 copies of the approved plans and one copy each of the approved hydraulic calculations and material submittal. 3. Product Data: Within 15 days after the award of the contract, submit for approval seven copies of manufacturer's literature, wiring diagrams, etc., for each piece of equipment used in the system. If the manufacturer's catalog sheets show more than one item, the items proposed for use shall be identified. 4. As-Built Documents: Prepare, maintain, and submit As-Built Documents for approval prior to completion and final acceptance of the Project installation. 5. Operation and Maintenance Manuals: Prior to final acceptance of the installation, submit for approval 6 sets of labeled, bound and indexed Operation and Maintenance Manuals indicating complete maintenance and operating procedures on all specialty items. Each O & M Manual shall include a copy of NFPA 25 Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems California Edition (2013), and copies of completed Contractor's Material & Test Certificate(s). Test certificates shall include the printed name and wet signature of the Contractor. 1.7 JOB CONDITIONS A. Normal building activities and uses will be maintained during the Contract period. Additionally, other trades may be working in the Buildings during the Contract period. Coordinate work schedule, material deliveries etc. with the College Representative. B. Impairments of existing fire protection systems shall be minimized, coordinated with the College Representative, and performed in accordance with NFPA 25. All existing fire protection systems shall be restored to service at the end of each working day. A detailed work plan and schedule shall be prepared and submitted to the Fire Marshal detailing necessary fire protection system shut downs. C. The work performed on this Project occurs within an existing Building. All equipment and material to be furnished and installed on the Project shall be coordinated with the existing space constraints. All equipment and material shall be fabricated such that complete systems may be broken down into sections suitable for lifting and fitting through passageways without modification to the building unless otherwise noted, or other arrangements are made with the College Representative. 1.8 WARRANTY A. Except as otherwise expressly provided in the Contract Documents, and excepting only items of routine maintenance, ordinary wear and tear and unusual abuse or neglect, Contractor guarantees all work executed by him and all supplies, materials and devices of whatsoever nature incorporated in, or attached to the work, or otherwise delivered to the College Representative as part of the work pursuant to the Contract, to be absolutely free of all defects of workmanship and materials for a period of one year after final acceptance of the entire work by the College Representative. B. All work, including parts and labor, covered under the guarantee shall be at no cost to the College. Page 3 of 7

6 PART 2 - PRODUCTS 2.1 GENERAL A. All materials and equipment furnished by the Contractor shall be new, first grade standard, current products of a manufacturer regularly engaged in the production of such materials and equipment. Where two or more pieces of equipment performing the same function are required, they shall be the product of one manufacturer and exact duplicates. 2.2 PIPING, FITTINGS, AND SPECIALTIES A. Piping shall be new, designed for 300 PSI working pressure, conforming to ASTM specifications, and have the manufacturer's name or brand along with the pipe applicable ASTM standard marked on each length of pipe. B. All new piping shall be Schedule 40 black steel pipe. Pipe shall be manufactured in accordance with specifications ASTM A 135 and A 53. C. Thin-walled piping materials (such as Schedule 5, 10, XL and BLT threadable thinwalls, etc.) will not be permitted. D. All fire protection system piping shall be provided with factory-applied antimicrobial coatings to inhibit Microbiologically-Influenced Corrosion (MIC). Allied Tube and Conduit "M-Coat", Wheatland Tube Company "MIC Shield", or equal. E. Schedule 40 black steel pipe shall be joined by screwed joints in accordance with specification ANSI B (ANSI/ASME B 2.1), by welded joints in accordance with specification ANSI/ASME B 31.1, Chap. 5, or by UL - listed mechanical grooved couplings. Grooves may be rolled or cut and they shall be dimensionally compatible with the couplings. F. Bolt-on or Strap-on branch and outlet fittings will not be not permitted. Similarly, hole cut piping system or strapless outlets will not be not permitted. G. Sprinkler piping and fittings exposed to weather, used in a corrosive atmosphere, or as noted on drawings shall be galvanized. H. Threaded fittings shall be Class 125 cast iron, black, and in accordance with ANSI B 16.4, or ductile or malleable iron, 150 lb. class, black, and in accordance with ANSI B Screwed joints shall be made up with approved Teflon joint compound or tape. I. Flanged fittings shall be cast iron, short body, Class 125, black, and in accordance with ANSI B Gaskets shall be full-face of 1/8-in. minimum thickness red sheet rubber. Flange bolts shall be hexagon head machine bolts with heavy semi-finished hexagon head nuts, cadmium plated, having dimensions in accordance with ANSI B J. Welded fittings shall be steel, standard weights, black, and in accordance with ANSI B 16.9, ANSI B 16.25, ASTM A 234, ANSI B 16.5, and ANSI B All welds shall be inspected and approved by the Authority Having Jurisdiction prior to installation. K. Grooved couplings shall be UL listed or FM approved for fire protection service. Plain-end type pipe fittings and couplings shall not be used. L. In-Building Risers shall be installed as indicated on the plans. Risers shall be composed of a single extended 90 degree fitting of fabricated 304 stainless steel tubing, maximum working pressure 200 psi. The fitting shall have a grooved-end connection on the outlet (building) side and a CIPS coupler on the inlet (underground) side. The In-Building Riser shall be an Ames Fire & Waterworks Series IBR (or approved equal). M. All sprinkler pipe passing through or crossing building seismic joints, shall contain a flexible expansion loop, designed for seismic movement. Flexible loops shall impart no thrust loads Page 4 of 7

7 2.3 VALVES to building structure. Loops shall be located at, or near, the building seismic joint. Seismic bracing shall not pass through building seismic joint and shall not connect or tie together different sides or parts of building structure. Flexible loops shall be capable of movement in the ±X, ±Y, ±Z planes. Flexible seismic loops to be Fireloop as manufactured by The Metraflex Company, Chicago, IL (no known equal). A. Above-grade fire protection control valves shall be UL Listed, slow closing, butterfly valves equipped with an integral valve-position supervisory switch. B. Check valves shall be swing type with removable faceplate, and shall have rubber or composition discs. Check valves shall not be installed in the vertically-downward position unless specifically approved for this position. C. All drain valves and test valves shall have replaceable rubber or composition discs. D. Automatic air release valve assemblies shall be Potter PAV (or approved equal) with isolation valve, mesh strainer assembly, and appurtenances. Discharge piping shall be piped as indicated. 2.4 SPRINKLERS A. Sprinklers in finished ceilings shall be 1/2" orifice Standard Response, Standard Coverage, Recessed Pendent sprinklers, k=5.6, 155 F, Viking Micromatic VK102 with white finish (or approved equal). B. Upright sprinklers (on branchline or 1-inch sprig) shall be 1/2" orifice Standard Response Standard Coverage, k=5.6, 286 F (High Temperature unless noted otherwise), Viking Micromatic VK100, black polyester finish (corrosion resistant) or approved equal. C. Sidewall sprinklers shall be 1/2" orifice Standard Response, Standard Coverage, Horizontal Sidewall sprinklers, k=5.6, 155 F, Viking Micromatic with white finish (or approved equal). D. Where indicated, finished ceiling recessed pendent sprinklers or upright sprinklers shall be equipped with SprinkGUARD ( guard assemblies. E. A minimum of 6 spare sprinklers of each type provided on the Project shall be provided in a suitable metal cabinet, along with one sprinkler wrench appropriate for each type of sprinkler installed. The metal cabinet shall be permanently mounted near the main building riser/shutoff, or as otherwise directed by the College Representative. 2.5 FIRE ALARM AND RELATED EQUIPMENT A. Waterflow switches shall have (2) SPDT contacts. They shall be installed, and adjusted under this Section. B. Valve supervisory switches shall have (2) SPDT contacts. They shall be installed, and adjusted under this Section. C. Exterior audible alarm for sprinkler waterflow shall be Potter Electric weatherproof exterior sprinkler alarm select-a-strobe/horn/sign combination, SASH-120 or approved equal. Provide 120 VAC wiring in accordance the Electric Code as generally indicated in the Wiring Schematic of Contract Drawing FS-0.0. Page 5 of 7

8 PART 3 - EXECUTION 3.1 GENERAL A. Ream all piping to remove all burrs. Pipe sections shall be cleaned inside to remove all chips and foreign materials prior to making joints. B. Install sprinklers throughout all areas of the Project. C. Welding, torch cutting, and open flames are not permitted inside the building. D. Install hangers, flexible connections, swing joints, and seismic bracing in accordance with NFPA E. System piping shall be installed such that no joints, fittings or devices occur directly over electrical equipment. Fire sprinkler piping shall not be installed in Dedicated Electrical Spaces as defined in the California Electrical Code Section. F. Install system drain valves at the locations indicated on the Drawings. All new piping shall be installed level or sloped to drain. G. Provide auxiliary drains for all trapped piping. Drains shall be installed at the bottom of the pipe being drained. All auxiliary drains shall be provided with a globe valve, nipple and cap (or plug), regardless of trapped pipe volume. H. Install permanent valve identification signs and hydraulic nameplate data as required by NFPA 13. Signs shall be attached by durable means (light duty chains will not be acceptable). Ink or felt-tipped pens shall not be used on hydraulic nameplates or signs. All markings shall be permanent. 3.2 PRODUCT HANDLING A. Deliver materials and store on site in original containers with seals unbroken and labels intact until time of use, in accordance with the manufacturer's instructions. B. All materials and equipment shall be carefully handled at all times. Only suitable and proper equipment and appliance shall be used for the safe loading, hauling, unloading, handling, and installation of material. C. All sprinklers shall be protected during installation with the protective cover provided by the manufacturer. The protective cover shall not be removed until all construction which creates a potential for damage to the sprinkler is completed, including but not limited to mechanical equipment and duct, electrical equipment and conduit, plumbing equipment and piping, wall and ceiling construction, etc. 3.3 PENETRATIONS A. The Contractor shall be responsible for all openings and penetrations required for the fire protection piping. B. Cutting structural members for passing of fire protection piping or pipe hanger fastenings will not be permitted except with approval of the College Representative. C. Suitable means shall be provided at each hole or penetration to maintain the designed fire resistance rating of the wall, ceiling or floor assembly. Submit the manufacturer s data sheet and Listing details for each through penetration fire stop to the Fire Marshal for review and approval. D. Install split wall plates or escutcheons where exposed piping passes through a finished floor, wall or ceiling. They shall fit snugly around piping. The finish of escutcheons or wall plates shall match the color of adjacent walls, ceilings or floors. Page 6 of 7

9 3.4 PAINTING A. Clean all exposed surfaces of installed piping of oil, dirt, etc. to the College Representative s satisfaction. B. Remove protective bags and wrappings after painting is completed. All sprinklers which have any paint on them shall be replaced. Cleaning of painted sprinklers is not permitted. 3.5 ACCEPTANCE INSPECTIONS AND TESTS A. Upon completion of installation and while piping is still exposed, hydrostatically test the systems at 200 psi (or 50 psi in excess of the system working pressure, whichever is greater) for a period of 2 hours. Any drop in pressure or any leak shall be cause to fail the test and a new test shall be scheduled once repairs are made. A minimum of seventy-two hours notice shall be given to the College Representative and the Fire Marshal prior to any inspection. The contractor shall have all equipment necessary for the inspection available to the Fire Marshal, including a ladder of an appropriate height. B. A pre-installation inspection of pipe, fittings, and devices is required. Prior to conducting the hydrostatic test noted above, conduct an Air Test in accordance NFPA 13 (2016) Section C. The Contractor shall be responsible for all leaks. END OF SECTION Page 7 of 7

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings. DIVISION 21 21 05 00 COMMON WORK RESULTS FOR FIRE SUPPRESSION PART 1 GENERAL 1.1 SECTION INCLUDES A. Pipe, fittings, sleeves, escutcheons, seals, and connections for sprinkler systems. 1.2 RELATED REQUIREMENTS

More information

FIRE SUPPRESSION SPRINKLER SYSTEM

FIRE SUPPRESSION SPRINKLER SYSTEM PART 1 GENERAL 1.01 DESCRIPTION A. The provisions of the General Requirements, Supplementary Requirements, and Division 1 apply to the plumbing work specified in this Division. B. The requirements of this

More information

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant. SECTION 218800 - FIRE PROTECTION 1. GENERAL A. Provisions of Division 1, GENERAL REQUIREMENTS, and Section 230000, MECHANICAL GENERAL CONDITIONS, and Section 230050, SEISMIC PROTECTION are a part of this

More information

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM SECTION 21 10 00 PART 1 - GENERAL 1.1 CODES A. Work shall conform to NFPA 13 Sprinkler Systems, 2002 Edition and NFPA 24 Outside Protection, 2002 Edition. NFPA 14 Standpipe Systems, 2000 Edition and International

More information

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE SECTION 21 1313 WET-PIPE SPRINKLER SYSTEMS PART 1 GENERAL 1.01 SECTION INCLUDES A. Wet-pipe sprinkler system. B. System design, installation, and certification. C. Fire department connections. 1.02 RELATED

More information

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions: SECTION 21 13 13 WET-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM SECTION 21 0000 AUTOMATIC FIRE SPRINKLER SYSTEM PART 1 GENERAL 1.1 QUALITY ASSURANCE A. Codes and Standards: 1. FBC (Florida Building Code 2015) 2. FBC (Florida Fire Code 2015) 3. NFPA #13R (Standard for

More information

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL SECTION 21 13 16 DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE SECTION 21 1316 DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE PART 1 GENERAL 1.01 SECTION INCLUDES A. Dry-pipe sprinkler system. B. System design, installation, and certification. C. Fire department

More information

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE SECTION 21 1316 DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE PART 1 GENERAL 1.01 SECTION INCLUDES A. Dry-pipe sprinkler system. B. System design, installation, and certification. C. Fire department

More information

THE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION

THE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION SECTION 21 1301- FIRE-SUPPRESSION SYSTEMS PART 1 - GENERAL 1.1 SUMMARY: A. This Section includes fire-suppression piping and equipment for the following building systems: 1. Wet-pipe, fire-suppression

More information

West District Library Section Campeau Drive, Ottawa SPRINKLER SYSTEMS City of Ottawa Project No. CR Page 1 of 8

West District Library Section Campeau Drive, Ottawa SPRINKLER SYSTEMS City of Ottawa Project No. CR Page 1 of 8 City of Ottawa Project No. CR006230 Page 1 of 8 PART 1 - GENERAL 1.1 Reference Standards.1 Conform to the following:.1 Provincial and municipal building and fire regulations as approved by Provincial Fire

More information

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint.

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint. (816) 373-4878 U1208-01/FAI29-029 (573) 751-2624 SECTION 2 105 17 - SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the

More information

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM SECTION 213100 WET PIPE FIRE PROTECTION SPRINKLER SYSTEM PART 1 - GENERAL 1.01 GENERAL REQUIREMENTS A. The requirements of the General Conditions and Supplementary Conditions apply to all work herein.

More information

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University.

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University. 15500 - FIRE PROTECTION PART I DESIGN GUIDELINES A. General 1. Vertical fire pumps shall not be used at the University. 2. coupling piping shall be permitted for sprinkler and standpipe systems only. B.

More information

A. Section includes wet-pipe sprinkler system, system design, installation, and certification.

A. Section includes wet-pipe sprinkler system, system design, installation, and certification. SECTION 21 13 13 WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section includes wet-pipe sprinkler system, system design, installation, and certification. 1.2 REFERENCES A. General: Comply

More information

B. Section Identification for Fire Suppression Piping and Equipment.

B. Section Identification for Fire Suppression Piping and Equipment. SECTION 211300 - FIRE SUPPRESSION SPRINKLERS PART 1 GENERAL 1.1 SECTION INCLUDES A. Dry-pipe sprinkler system. B. System design, installation, and certification. C. Fire department connections. 1.2 RELATED

More information

SECTION DRY-PIPE SPRINKLER SYSTEMS

SECTION DRY-PIPE SPRINKLER SYSTEMS Ul611-0l SECTION 211316- DRY-PIPE SPRINKLER SYSTEMS PARTl-GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions, and Division 1 Specification

More information

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements.

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements. FIRE PROTECTION GENERAL INFORMATION 1.1 Refer to Section 230000 for General Mechanical Requirements. 1.2 Refer to Section 230529 for Hangers and Supports. 1.3 Refer to Section 230553 for Pipe and Equipment

More information

DIVISION 21 - FIRE SUPPRESSION

DIVISION 21 - FIRE SUPPRESSION DIVISION 21 - FIRE SUPPRESSION DESIGN CRITERIA It is the policy of UC Davis to install fire sprinkler systems in all new construction/facilities. If the building is classified as a pole barn, shed, carport,

More information

Gas Station & C Store SECTION CWM Job No

Gas Station & C Store SECTION CWM Job No SECTION 21 1300 - PART 1 - GENERAL 1.1 WORK INCLUDED A. Provide labor, materials, equipment and services to perform operations required for the complete installation and related Work as required in Contract

More information

SECTION ADDENDUM NO. 1 FIRE SPRINKLER SYSTEM

SECTION ADDENDUM NO. 1 FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.01 GENERAL DESCRIPTION A. Furnish all materials and labor for the detailed design and installation for new fire sprinkler wet pipe systems for Buildings A through R hereafter referred

More information

MLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN

MLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN DIVISION 21 - FIRE SUPPRESSION (REFER TO SECTION 23 05 00 FOR BASIC FIRE SUPPRESSION REQUIREMENTS) 21 05 00 Common Work Results for Fire Suppression 21 13 13 Wet-Pipe Sprinkler Systems END OF SECTION FIRE

More information

DIVISION 21 - FIRE SUPPRESSION

DIVISION 21 - FIRE SUPPRESSION DIVISION 21 - FIRE SUPPRESSION DESIGN CRITERIA It is the policy of UC Davis to install fire sprinkler systems in all new construction/facilities. If the building is classified as a pole barn, shed, carport,

More information

SPRINKLERS TABLE OF CONTENTS

SPRINKLERS TABLE OF CONTENTS SPRINKLERS TABLE OF CONTENTS SECTION 21 13 13 WET PIPE SPRINKLER SYSTEMS SECTION 211313 - WET PIPE SPRINKLER SYSTEMS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract,

More information

ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1. The Curators of the University of Missouri

ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1. The Curators of the University of Missouri ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1 TO CONTRACT DOCUMENTS ENTITLED: PROJECT MANUAL FOR: Women s and Children s Hospital New Water Service Main PROJECT NUMBER: CP172631 ADVERTISEMENT DATE: July

More information

2. Welding Materials and Procedures shall conform to the ASME Code.

2. Welding Materials and Procedures shall conform to the ASME Code. PART 1 GENERAL 1.01 Scope of Standard A. The design guidelines contained herein include the requirements for systems, materials, fittings and valves utilized for fire protection systems at Sam Houston

More information

SECTION DRY-PIPE SPRINKLER SYSTEMS

SECTION DRY-PIPE SPRINKLER SYSTEMS SECTION 21 1300 S PART 1 -GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

SECTION FIRE PROTECTION. A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section

SECTION FIRE PROTECTION. A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section PART 1 - GENERAL 1.00 GENERAL PROVISIONS A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section 1.01 DESCRIPTION OF WORK A. Work Included: Provide

More information

Port of St Helens SIA Aircraft Hanger Scappoose, OR

Port of St Helens SIA Aircraft Hanger Scappoose, OR Port of St Helens SIA Aircraft Hanger Scappoose, OR AUTOMATIC FIRE SPRINKLER SYSTEM REVISION 2 MARCH 12, 2018 Scope: Furnish and install foam and water fire protection system including underground entrance

More information

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS SECTION 21 1300 S PART 1 -GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5

TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5 DOC Cremer Heating and Hot Water Plant Project Number: M 1411-04 TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION 21 30 00- WATER BASED FIRE PROTECTION SYSTEMS... 5 SECTION 22 40 00 -PLUMBING

More information

UC Santa Cruz Campus Design Guide. Includes the following sections: None DESIGN REQUIREMENTS

UC Santa Cruz Campus Design Guide. Includes the following sections: None DESIGN REQUIREMENTS DIVISION 21 - FIRE SUPPRESSION Includes the following sections: None DESIGN REQUIREMENTS It is the policy of City of Santa Cruz to install fire sprinkler systems in all new construction/facilities. If

More information

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS SECTION 21 13 13 WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SCOPE OF WORK A. Design, installation and testing shall be in accordance with NFPA 13 except for specified exceptions. B. The demolition

More information

SECTION SPRINKLER SYSTEMS

SECTION SPRINKLER SYSTEMS SECTION 13900 SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

B. Related Sections: The following Sections contain requirements that relate to this Section.

B. Related Sections: The following Sections contain requirements that relate to this Section. SECTION 211313- FIRE-SUPPRESSION PIPING PART1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general prov1s1ons of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Design & Construction Standards, Revised January

Design & Construction Standards, Revised January PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for fire-extinguishing systems other than water-based fire suppression systems.

More information

SECTION AUTOMATIC SPRINKLER PIPING

SECTION AUTOMATIC SPRINKLER PIPING SECTION 15330 AUTOMATIC SPRINKLER PIPING ****** ***** **** *** ** * ** *** **** ***** ****** NOTE TO SPECIFIER: This section contains several types of automatic sprinkler piping. Some piping is allowed

More information

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS SECTION 21 13 13 WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

ADDENDUM NO. 3 March 19, 2018

ADDENDUM NO. 3 March 19, 2018 ADDENDUM NO. 3 March 19, 2018 PROJECT: MT. VIEW ELEMENTARY CASSIA SCHOOL DISTRICT NO 151 BURLEY, IDAHO The following addenda apply to the Project Manual and / or Drawings for this project and shall be

More information

WET-PIPE SPRINKLER SYSTEMS

WET-PIPE SPRINKLER SYSTEMS SECTION 211313 - WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipes, fittings, and specialties. 2. Fire-protection valves. 3. Fire-department connections. 4. Sprinklers.

More information

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following:

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following: SECTION 21 10 00 - WATER-BASED FIRE-SUPPRESSION PART I - GENERAL 1.1 SUMMARY A. Inclusion of sprinkler and standpipe systems shall be as determined by NFPA National Fire Code pamphlet 101 and program statement.

More information

SECTION FIRE-SUPPRESSION STANDPIPES

SECTION FIRE-SUPPRESSION STANDPIPES PART 1 - GENERAL 1.1 DESCRIPTION Fire-suppression wet and manual dry standpipes. 1.2 SCOPE OF WORK SECTION 21 12 00 A. Design, installation and testing shall be in accordance with NFPA 14 except for specified

More information

SECTION SPRINKLER SYSTEMS

SECTION SPRINKLER SYSTEMS SECTION 15325 SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Wet-pipe sprinkler systems. B. Preaction sprinkler systems. C. System design, installation, and certification. D. Fire department

More information

FIRE SPRINKLER SYSTEMS POLICY

FIRE SPRINKLER SYSTEMS POLICY FIRE SPRINKLER SYSTEMS POLICY Revised 1/1/17 DESIGN AND SUBMITTAL REQUIREMENTS All new and existing fire sprinkler systems within the jurisdiction of the City Fire Department shall meet all of the applicable

More information

UMC El Paso Far East Clinic and Neighborhood Healthcare Center West Issue for Construction Page Project No and April 13, 2015

UMC El Paso Far East Clinic and Neighborhood Healthcare Center West Issue for Construction Page Project No and April 13, 2015 SECTION 211000 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Related Documents: Drawings, Notice to Bidders, General Conditions, Project Coordination, RFP Format, Requested RFP Alternatives, Cutting and

More information

Design & Construction Standards, Revised January

Design & Construction Standards, Revised January PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for the design and construction of standpipe systems to include combination standpipe

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 21 1314D - AUTOMATIC SPRINKLER SYSTEMS (DRY-PIPE) PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

DESIGN & CONSTRUCTION GUIDELINES

DESIGN & CONSTRUCTION GUIDELINES ADMINISTRATIVE SERVICES 4202 E. FOWLER AVENUE, FPC110 PHONE: (813) 974-2625 FACILITIES PLANNING & CONSTRUCTION TAMPA, FLORIDA 33620-7550 WEBSITE: USF.EDU/FPC DESIGN & CONSTRUCTION GUIDELINES DIVISION 21

More information

B. The sprinkler system shall be designed to meet the more stringent of the requirements of NFPA 13 and FM Global requirements.

B. The sprinkler system shall be designed to meet the more stringent of the requirements of NFPA 13 and FM Global requirements. SECTION 21 13 13 FIRE PROTECTION SPRINKLER SYSTEMS PART 1 - GENERAL 1.01 SUMMARY A. Section includes labor and materials for the installation of a hydraulically calculated automatic, wet-pipe sprinkler

More information

FIRE SPRINKLER SYSTEMS POLICY

FIRE SPRINKLER SYSTEMS POLICY FIRE SPRINKLER SYSTEMS POLICY VERSION 1.012/2015 FIRE SPRINKLER SYSTEMS Design and Submittal requirements All new and existing fire sprinkler systems within the jurisdiction of the City of San Mateo Fire

More information

SECTION FIRE PROTECTION

SECTION FIRE PROTECTION SECTION 15300 - FIRE PROTECTION PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, and Section 15030, ELECTRICAL REQUIREMENTS FOR

More information

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1 GENERAL: 1. All fire protection systems shall be installed in accordance with the International Fire Code and applicable NFPA standards. This guideline provides additional requirements for the design and

More information

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS SECTION 211313 WET-PIPE SPRINKLER SYSTEMS PRT 1 GENERL 1.01 RELTED DOCUMENTS. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Division 21: FIRE SUPRESSION WET-PIPE SPRINKLER PROTECTION SYSTEM. The Academy Sept Table of Contents 1 Division 21

Division 21: FIRE SUPRESSION WET-PIPE SPRINKLER PROTECTION SYSTEM. The Academy Sept Table of Contents 1 Division 21 Division 21: FIRE SUPRESSION 21 1313 WET-PIPE SPRINKLER PROTECTION SYSTEM Table of Contents 1 Division 21 SECTION 21 1313 WET-PIPE SPRINKLER PROTECTION SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A.

More information

Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040

Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040 Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040 SPRINKLER SHOP DRAWINGS 2007 NFPA 13 and 2007 NFPA 24 Project: Listed items require sprinkler

More information

SECTION (13900) - FIRE SUPPRESSION SYSTEMS

SECTION (13900) - FIRE SUPPRESSION SYSTEMS PART 1 GENERAL 1.01 SUMMARY SECTION 21 10 00 (13900) - FIRE SUPPRESSION SYSTEMS A. Section Includes: 1. Pipe and Fittings. 2. Sprinklers. B. Related Documents: 1. Marriott s Fire Protection and Life Safety

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 21 1314W - AUTOMATIC SPRINKLER SYSTEMS (WET PIPE SYSTEMS) PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

SECTION WET FIRE SPRINKLER SYSTEMS

SECTION WET FIRE SPRINKLER SYSTEMS SUNY GENESEO 211310-1 PART 1 - GENERAL 1.1 WORK INCLUDED A. Provide labor, materials, equipment and services to perform operations required for the complete installation and related Work as required in

More information

CITY OF PASADENA FIRE DEPARTMENT

CITY OF PASADENA FIRE DEPARTMENT Page 1 of 8 CITY OF PASADENA FIRE DEPARTMENT INSTALLATION OF COMMERCIAL SPRINKLERS (Revised 12/10/2014) SCOPE: This standard applies to the design and installation of automatic fire sprinkler systems in

More information

Public School Facilities Authority State of New Mexico 2019 Galisteo, Suite B Santa Fe, New Mexico 87505

Public School Facilities Authority State of New Mexico 2019 Galisteo, Suite B Santa Fe, New Mexico 87505 Public School Facilities Authority State of New Mexico 2019 Galisteo, Suite B Santa Fe, New Mexico 87505 SPECIFICATIONS FOR FIRE PROTECTION SYSTEMS NEW MEXICO PUBLIC SCHOOLS November 7, 2005 . TABLE OF

More information

North Hanover Township School District North Hanover Township, New Jersey

North Hanover Township School District North Hanover Township, New Jersey SECTION 211313 - WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipes, fittings, and specialties. 2. Fire-protection valves. 3. Fire-department connections. 4. Sprinklers.

More information

A. Standard-Pressure Piping System Component: Listed for 175-psig minimum working pressure.

A. Standard-Pressure Piping System Component: Listed for 175-psig minimum working pressure. SECTION 211313 - WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipes, fittings, and specialties. 2. Fire-protection valves. 3. Fire-department connections. 4. Sprinklers.

More information

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code Part 1 - GENERAL 1.1 DESCRIPTION OF WORK A. Design and installation of an engineered Kidde ECS Advanced Delivery Systems (ADS), clean agent/waterless fire suppression system employing 3M Novec 1230 waterless

More information

A. This section includes design and performance information for fire protection and suppression systems.

A. This section includes design and performance information for fire protection and suppression systems. SECTION 21 00 10: FIRE PROTECTION SYSTEM DESIGN 1. SUMMARY A. This section includes design and performance information for fire protection and suppression systems. 2. GENERAL A. All fire protection materials

More information

D. Reference Standards (Utilize latest editions available):

D. Reference Standards (Utilize latest editions available): 1.01 Scope of Standard A. This standard provides general requirements of The Sam Houston State University for fireextinguishing systems other than water-based fire suppression systems. This document is

More information

SECTION WET-PIPE FIRE SUPPRESSION SPRINKLERS

SECTION WET-PIPE FIRE SUPPRESSION SPRINKLERS SECTION 15932 WET-PIPE FIRE SUPPRESSION SPRINKLERS PART 1 - GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent referenced. The publications are referred

More information

Lucy s Pizza 100% CD Specification 06/22/2018

Lucy s Pizza 100% CD Specification 06/22/2018 DIVISION 21: FIRE SUPPRESSION 210500 COMMON REQUIREMENTS FOR FIRE SUPPRESSION 210548 VIBRATION & SEISMIC CONTROLS FOR FIRE SUPPRESSION PIPING & EQUIPMENT 210553 IDENTIFICATION FOR FIRE SUPPRESSION PIPING

More information

Environmental Health & Safety

Environmental Health & Safety Environmental Health & Safety Oklahoma State University FIRE SPRINKLER SYSTEM STANDARD Environmental Health and Safety University Health Services Suite 002 Stillwater, OK 74078 (405) 744-7241 www.ehs.okstate.edu

More information

NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM

NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM PART 1 - GENERAL 1.1 SUMMARY A. This section outlines the requirements for the nitrogen-generating sprinkler corrosion inhibiting system. The work

More information

SECTION WATER BASED FIRE SUPPRESSION SYSTEMS

SECTION WATER BASED FIRE SUPPRESSION SYSTEMS PART 1: GENERAL 1.01 Scope of Standard A. This standard provides general guidance concerning the specific preferences of Texas State University-San Marcos for automatic fire sprinkler and standpipe systems.

More information

SECTION WET AUTOMATIC FIRE SPRINKLER SYSTEMS

SECTION WET AUTOMATIC FIRE SPRINKLER SYSTEMS SECTION 15501 WET AUTOMATIC FIRE SPRINKLER SYSTEMS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Wet automatic fire sprinkler systems including fire pump, fire pump controller, alarms, safety devices,

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 211313 - WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

A. All Fire Suppression System design and installation shall comply with the most current and adopted version of NFPA 13.

A. All Fire Suppression System design and installation shall comply with the most current and adopted version of NFPA 13. 21 10 00 PART 1 - GENERAL 1.01 SCOPE A. The following standards and procedures apply to the design and installation of all wet pipe and dry pipe sprinkler systems. The design of fire suppression systems

More information

SECTION ELECTRIC-DRIVEN, FIRE PUMPS

SECTION ELECTRIC-DRIVEN, FIRE PUMPS SECTION 21 30 13 ELECTRIC-DRIVEN, FIRE PUMPS PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Delete between // --- // if not applicable to the project. Also delete any other item or paragraph including

More information

D. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following:

D. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following: PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of Sam Houston State University for the design and construction of standpipe systems to include combination standpipe

More information

AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations)

AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations) AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations) This standard applies to the design and installation of automatic fire sprinkler systems in conjunction with

More information

SECTION Fire Pumps

SECTION Fire Pumps SECTION 21 30 00 Fire Pumps PART 1 GENERAL 1.1 WORK INCLUDED A. Furnish, install and test a motor-driven fire pump, jockey pump, and controllers in the space provided and as shown in the contract drawings.

More information

esfr dry pendent sprinkler Vk501 (k14.0)

esfr dry pendent sprinkler Vk501 (k14.0) September 13, 2012 Sprinkler 122a 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK501 is a fast response fusible element type sprinkler designed for use in storage

More information

DARTMOUTH COLLEGE DESIGN November 15, 2007 & CONSTRUCTION GUIDELINES

DARTMOUTH COLLEGE DESIGN November 15, 2007 & CONSTRUCTION GUIDELINES SECTION 15300 FIRE PROTECTION PART 1 DESIGN DIRECTIVES 1.1 DESIGN CRITERIA A. Dartmouth College is currently insured by Factory Mutual. References to the owner s insurance company in this specification

More information

SECTION FIRE PROTECTION

SECTION FIRE PROTECTION SECTION 15300 PART I - GENERAL 1.01 WORK INCLUDED A. Furnish all labor, materials, tools, and equipment to complete the automatic fire sprinkler system as hereinafter described, ready for service to the

More information

DIVISION 21: FIRE SUPPRESSION WATER BASED FIRE SUPRESSION SYSTEMS

DIVISION 21: FIRE SUPPRESSION WATER BASED FIRE SUPRESSION SYSTEMS DIVISION 21: FIRE SUPPRESSION 21 1000 WATER BASED FIRE SUPRESSION SYSTEMS 21 1200 FIRE-SUPPRESSION DRY STANDPIPES 21 1313 WET PIPE SPRINKLER PROTECTION SYSTEM 21 1314 WET-PIPE AUTOMATIC SPRINKLER SYSTEM

More information

esfr dry pendent sprinkler Vk502 (k14.0)

esfr dry pendent sprinkler Vk502 (k14.0) Page 1 of 11 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK502 is a fast response fusible element type sprinkler designed for use in storage areas subject to freezing

More information

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD INSTALLATION OF COMMERCIAL FIRE SPRINKLER SYSTEMS STANDARD #C-001 EFFECTIVE 03-25-2009 PURPOSE: To ensure that sprinkler plans submitted for review contain

More information

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS SECTION 21 13 13 PART 1 - GENERAL 1.1 SCOPE OF WORK A. Design, installation and testing shall be in accordance with NFPA 13 except for specified exceptions. B. The design and installation of a hydraulically

More information

SECTION PREACTION SPRINKLER SYSTEMS

SECTION PREACTION SPRINKLER SYSTEMS PART 1 GENERAL SECTION 211316 - PREACTION SPRINKLER SYSTEMS 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for UL and FM Listing/Approval requirements that must be followed.

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for UL and FM Listing/Approval requirements that must be followed. Page 1 of 10 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK504 is a fast response fusible element type sprinkler designed for use in storage areas subject to freezing

More information

City of Vista Fire Department

City of Vista Fire Department City of Vista Fire Department Development Services Section 600 Eucalyptus Avenue, Vista CA 92084 Guideline: Underground Piping for Private Fire Hydrants & Fire Sprinkler Supply. Updated: January, 2008

More information

UBC Technical Guidelines Section Edition Fire Protection General Requirements Page 1 of 6

UBC Technical Guidelines Section Edition Fire Protection General Requirements Page 1 of 6 Page 1 of 6 1.0 GENERAL 1.1 Related UBC Guidelines.1 Section 20 00 05 Mechanical - General Requirements.2 Section 22 05 00 Plumbing - General Requirements.3 UBC Standard Fire Hydrant Drawings.4 Section

More information

PHYSICAL FACILITIES. 1 General. 2 Related Requirements. 5 Quality Assurance. 3 Wiring. 4 Submittals

PHYSICAL FACILITIES. 1 General. 2 Related Requirements. 5 Quality Assurance. 3 Wiring. 4 Submittals 1 General 1.1 Provide all material, labor, engineering and operations for the installation of complete and operable fire suppression systems as shown in the job scope and as specified herein. 1.2 Provide

More information

PART 1 - GENERAL SECTION FIRE PROTECTION BASIC MATERIALS AND METHODS

PART 1 - GENERAL SECTION FIRE PROTECTION BASIC MATERIALS AND METHODS FIRE PROTECTION BA SECTION 13910 - FIRE PROTECTION BASIC MATERIALS AND METHODS PART 1 - GENERAL 1.01 SECTION INCLUDES A. Pipe, fittings, valves, and connections for sprinkler, standpipe and fire hose,

More information

REFRIGERANT PIPING SYSTEM

REFRIGERANT PIPING SYSTEM PART 1 GENERAL 1.01 DESCRIPTION A. The requirements of this section apply to the refrigerant piping system connecting refrigeration and HVAC equipment specified in other sections of these specifications.

More information

SECTION WET-PIPE FIRE-SUPPRESSION SPRINKLERS

SECTION WET-PIPE FIRE-SUPPRESSION SPRINKLERS SECTION 13930 WET-PIPE FIRE-SUPPRESSION SPRINKLERS PART 1 GENERAL 1.1 SUMMARY A. Includes But Not Limited To 1. Furnish and install complete wet-pipe fire sprinkler system in new addition only as specified

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE November 2, 2007 Sprinkler 113a 1. DESCRIPTION The Viking Standard Response High Challenge Upright Large-Drop Sprinkler VK540 is a thermosensitive, glass-bulb sprinkler intended for use in protecting high

More information

Addendum No. 2 to the Contract Documents

Addendum No. 2 to the Contract Documents Addendum No. 2 to the Contract Documents Lewis County Jefferson Community College Education Center Project CONTRACT 2A: GENERAL CONSTRUCTION CONTRACT 2B: ELECTRICAL CONSTRUCTION CONTRACT 2C: MECHANICAL

More information

Mercury Plastics New Building February TABLE OF CONTENTS

Mercury Plastics New Building February TABLE OF CONTENTS DIVISION 21: FIRE SUPPRESSION 210500 COMMON REQUIREMENTS FOR FIRE SUPPRESSION 210548 VIBRATION AND SEISMIC CONTROLS FOR FIRE SUPPRESSION PIPING AND EQUIPMENT 211300 WET PIPE FIRE SUPPRESSION SPRINKLERS

More information

WET AUTOMATIC FIRE SPRINKLER SYSTEMS

WET AUTOMATIC FIRE SPRINKLER SYSTEMS SECTION 15501 WET AUTOMATIC FIRE SPRINKLER SYSTEMS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Wet automatic fire sprinkler systems including fire pump, fire pump controller, alarms, safety devices,

More information

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES DIVISION 21 FIRE SUPPRESSION PART 1 GENERAL 1.01 DESCRIPTION A. Provide UL listed, FM approved listed fire protection specialties or accessories as required by either the equipment manufacturer or the

More information

TABLE OF CONTENTS

TABLE OF CONTENTS DIVISION 21: FIRE SUPPRESSION 21 05 00 COMMON REQUIREMENTS FOR FIRE SUPPRESSION 21 05 53 IDENTIFICATION FOR FIRE SUPPRESSION PIPING AND EQUIPMENT 21 13 00 WET PIPE FIRE SUPPRESSION SPRINKLERS END TABLE

More information

DIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses

DIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses PART 1 - GENERAL 1.1 SCOPE A. Through Class III Commodity Classification, up to 12.2m of single, double or multiple row rack storage, up to 14.6m building height (VanQuish Fire Sprinkler System). Cartoned

More information