LIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE
|
|
- Adela Bailey
- 5 years ago
- Views:
Transcription
1 California Society for Healthcare Engineering SOUTHERN CALIFORNIA SEMINAR LIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE 1
2 PROGRAM AGENDA Adoption of 2012 LSC CMS Final Rule / Amendments & Clarifications LSC Chapter 43 (Building Rehab) Some Benefits of the 2012 LSC Some New Requirements of the 2012 LSC Referenced Standards 2
3 HISTORY Jan CMS Adopted 2000 LSC April 2014 CMS Proposes Adopting 2012 LSC May 2016 CMS Adopts 2012 LSC (Effective Date 7/5/2016) 3
4 CMS FINAL RULE PROVISIONS What about The Joint Commission, HFAP, DNV, AAAHC, etc.? Any Accrediting Organizations (AO) requesting Deemed Status must mirror CMS Final Rule provisions, as a minimum 4
5 CMS FINAL RULE PROVISIONS Adopts the 2012 edition of the Life Safety Code (NFPA 101) Adopts the 2012 edition of the Health Care Facilities Code (NFPA 99), except: Chapter 7 IT & Communications Chapter 8 Plumbing Chapter 12 Emergency Management Chapter 13 Security Updates various referenced codes and standards Identifies CMS amendments & clarifications 5
6 CMS FINAL RULE CLARIFICATIONS Fire Watch Agrees with the LSC / NFPA 25 Fire Watch provisions Loss of Fire Sprinkler System for more than 10 hours in a 24 hour period Previously kicked in after more than 4 hours / 24 hr. period Loss of Fire Alarm System remains at 4 hours / 24 hr. period 6
7 CMS FINAL RULE CLARIFICATIONS Requirements for Fire Watch Must be performed by dedicated staff Can have no other duties other than Fire Watch Must constantly circulate throughout facility, or portion affected by system outage Most observe for fire, fire hazards, or hazardous conditions Documentation of rounds not required 7
8 CMS FINAL RULE CLARIFICATIONS Sprinkler Protection in High Rise Buildings classified as Healthcare occupancy Required by 2012 LSC Includes a 12 year phase in period from time of Code adoption Compliance required by July 5,
9 CMS FINAL RULE CLARIFICATIONS Alcohol Hand Based Rubs (ABHR) Proposal addressed taking all appropriate precautions to secure the ABHR dispensers from inappropriate access Final Rule clarified limiting access to those who may try to harm themselves or others Examples: Dementia & Psychiatric populations 9
10 CMS FINAL RULE CLARIFICATIONS Corridor Projections 2012 LSC permits max. 6 projections ADA permits max. 4 projections CMS clarifies they will cite >4 if organization is under an ADA Action 10
11 CMS FINAL RULE CLARIFICATIONS Occupancy Definitions Healthcare = 4 or more inpatients (overnight sleeping) Ambulatory = 4 or more incapable of self preservation (no overnight sleeping) CMS requires ASC to meet Ambulatory HC Chapter (1 or more) CMS recently agreed that Emergency Departments could be classified as Ambulatory if freestanding or properly separated from Healthcare portions of building 11
12 CMS FINAL RULE CLARIFICATIONS Occupancy Definitions Business Used for transaction of business other than mercantile Dentist / Doctor Offices Office areas of Hospital (if properly separated) Outpatient Clinics (3 or less incapacitated) 12
13 CMS INTERPRETIVE GUIDELINES Emergency Preparedness S&C ALL (June 2, 2017) Life Safety Not Yet 13
14 2012 LSC CHAPTER 43 Building Rehabilitation Repair Renovation Modification Reconstruction Change of use or occupancy classification Addition 14
15 2012 LSC CHAPTER 43 Repair Renovation Replace in Kind 15
16 2012 LSC CHAPTER 43 Modification Addition or Relocation of Door Reconfiguration or Extension of Space Installation of Additional Equipment 16
17 2012 LSC CHAPTER 43 Reconstruction Reconfiguration of Space, Plus: Affects Exit or Corridor Used by More Than One Space, OR Work Area Not Permitted to be Occupied Due to Impairments OR Work Area Exceeds 50% of Building 17
18 2012 LSC CHAPTER 43 Change of Occupancy To a Building or a Portion of a Building 18
19 2012 LSC CHAPTER 43 Addition An Increase in Floor Area, Building Height, or Number of Stories 19
20 2012 LSC CHAPTER 43 Change of Use Change in Purpose (without changing the occupancy) That Affects Code Requirements Example Change in use of Room From Non Hazardous to Hazardous (Storage) Requires Sprinklers & 1 Hour Fire Rated Enclosure 20
21 2012 LSC CHAPTER 43 Change of Use Relaxation for Existing Healthcare If Room Does Not Exceed 250 sq. ft. and BUILDING is Sprinklered, 1 Hour Enclosure Not Required Put a self closer on door and call it good! 21
22 SIGNIFICANT BENEFITS OF 2012 LSC Sleeping Suite Size Increase Max sf Direct visual supervision from area such as Nurses Station OR smoke detection within sleeping rooms 5001 sf 7,500 sf Quick Response sprinklers, OR Standard Response sprinklers and complete smoke detection throughout smoke compartment 7501 sf 10,000 sf Quick Response sprinklers AND complete smoke detection throughout smoke compartment, as well as direct visual supervision from area such as Nurses Station 22
23 SIGNIFICANT BENEFITS OF 2012 LSC Suite Exiting Arrangements Clarifies one (1) exit to the exit access corridor Permits additional exits to adjacent suites, the exterior, exit passageways or exit stairwells Modifies restrictions relating to intervening rooms 23
24 SIGNIFICANT BENEFITS OF 2012 LSC Clean Waste and Records Recycling Containers Increase the size of containers to a maximum 96 gallon located outside of Hazardous area Must meet FM 6921 (Containers for Combustible Waste) Does NOT apply to trash, soiled linen, etc. 24
25 SIGNIFICANT BENEFITS OF 2012 LSC Corridor Projections for Wheeled Equipment Equip. does not reduce corridor width to less than 60 in Fire Safety Plan addresses relocation of wheeled equip. Wheeled equip. is limited to: Equipment & carts in use Medical emergency equipment not in use Patient lift & transport equipment Gurneys, wheelchairs, lifts YES Beds NO 25
26 SIGNIFICANT BENEFITS OF 2012 LSC Security Cameras / Card Readers in Stairwells LSC (10)(b) indicates electrical conduits permitted to penetrate stair enclosure if serving the enclosure TJC Contended Cameras and Card Readers Were Not Necessary to be in a Stairwell, and therefore penetrations for these were not permitted Wireless Cameras? LSC Stair Enclosure Not to be Used For Any Purpose That Has Potential To Interfere With Use as an Exit 26
27 SIGNIFICANT BENEFITS OF 2012 LSC Security Cameras / Card Readers in Stairwells 2012 LSC (10)(b) Annex Note: Penetrations for electrical wiring are permitted where the wiring serves equipment permitted by the Authority Having Jurisdiction to be located within the exit enclosure, such as security systems, public address systems, and fire department emergency communications devices. TJC has now indicated acceptance of cameras and card readers in stairwells, provided penetrations are properly protected Evac Equipment? 27
28 SIGNIFICANT BENEFITS OF 2012 LSC PERMITTED DOOR LOCKING CONCEPTS Clinical Needs Safety and Security Delayed Egress Access Control
29 DOOR LOCKING Clinical Needs of Patient (No Change) Can be unlocked by one of the following: Remote control of locks Keying of all locks to keys carried by staff at all times Other such reliable means available to staff at all times.
30 DOOR LOCKING Safety & Security (New Allowance in 2012) Door locking arrangements shall be permitted where patient special needs require specialized protective measures for their safety Pediatric Units NICU Maternity Units Emergency Departments Etc.
31 DOOR LOCKING Safety & Security, con t. All staff can unlock doors at any time Complete smoke detection system OR remote unlocking capability from constantly attended location within the space Locks release upon power loss (fail safe) Locks release upon smoke detection in the space or water flow from the space Entire building is fully sprinklered 31
32 DOOR LOCKING Delayed Egress (Requirement Relaxed) No specific justification required Removed the requirement that permitted only one delayed egress device per egress path. Building must be fully sprinklered or fully detected Be aware some building codes allow a maximum of 2 in the path of travel
33 DOOR LOCKING Access Controlled (No Change) No specific justification required Must unlock upon: Motion Sensor to Detect Approach of Person Manual Release Button (Push to Exit) Loss of Power (fail safe) Activation of Fire Alarm System Activation of Sprinkler System (if provided)
34 SIGNIFICANT BENEFITS OF 2012 LSC DOORS WITH TWO RELEASING OPERATIONS complying with (New Text): 2000 Edition 2012 Edition Area served has occupant load of 3 or less Door release does not require simultaneous operation Existing hardware only
35 SIGNIFICANT BENEFITS OF 2012 LSC SLIDING DOORS (without breakaway) WITHIN MEANS OF EGRESS complying with 18/ (New Text): 2000 Edition 2012 Edition Area served has occupant load of 10 or less Not Hazardous area Door operable from both sides without special knowledge or effort Self closing if fire rated Positive latching if opening to exit access corridor
36 NEW REQUIREMENTS OF 2012 LSC Stairwell Signage Applies to New stairwells serving three (3) or more stories Applies to Existing stairwells serving five (5) or more stories Specific text heights Specific text positions 36
37
38 NEW REQUIREMENTS OF 2012 LSC Door Inspection Program Requires annual inspection and testing of certain doors Allowance provided for a performance based program Must be performed by individuals who can demonstrate knowledge and understanding of doors and operating components No definition provided No specific certification required Applicable to ALL occupancies 38
39 ANNUAL DOOR INSPECTIONS What Doors Does This Apply To? All fire rated doors? Patient room doors that happen to be fire rated but not required to be? Traffic control / Function separation doors that happen to be fire rated? Only doors that are required to be fire rated? Doors within a smoke barrier? More confusion than anyone ever imagined! 39
40 ANNUAL DOOR INSPECTIONS What Doors Does This Apply To? 40
41 ANNUAL DOOR INSPECTIONS What Doors Does This Apply To? Inspection of Door Openings Where required by Chapters 11 through 43, the following door assemblies shall be inspected and tested not less than annually in accordance with through : (1) Door leaves equipped with panic hardware or fire exit hardware in accordance with (2) Door assemblies in exit enclosures (3) Electrically controlled egress doors (4) Door assemblies with special locking arrangements subject to Compliance with NOT required for Healthcare, Ambulatory Healthcare or Business Occupancies! 41
42 ANNUAL DOOR INSPECTIONS What Doors Does This Apply To? Inspection of Door Openings Fire rated door assemblies shall be inspected and tested in accordance with NFPA 80, Standard for Fire Doors and Other Opening Protectives. Smoke door assemblies shall be inspected and tested in accordance with NFPA 105, Standard for Smoke Door Assemblies and Other Opening Protectives. Compliance with NOT required for Smoke Door Assemblies since for Healthcare does not require these doors to be smoke leakage rated! 42
43 ANNUAL DOOR INSPECTIONS What Doors Does This Apply To? Indicated in S&C Fire door assemblies to be inspected / held to NFPA 80 requirements Not specifically called out in S&C, but don t forget rated access panels and Linen / Trash Chute door assemblies Does not specifically address fire rated doors in locations where a fire rated door is not required Both CMS & TJC have previously indicated that if a door has a label it must be held to the label, even if labeled door is not required Option Remove label if not required? Non rated doors, inc. corridor doors to patient care rooms and smoke barrier doors not required to be inspected, but should be maintained Completion date for first annual inspection extended from 7/5/2017 to 1/1/
44 ANNUAL DOOR INSPECTIONS Excessive Gaps on Fire Doors Gasketing materials to address excessive gaps on fire doors must be specifically Listed for such use Material may have a label indicating Suitable for Installation on a 90 Minute Fire Rated Door, or similar wording 44
45 ANNUAL DOOR INSPECTIONS Excessive Gaps on Fire Doors Gasketing materials to address excessive gaps on fire doors must be specifically Listed for such use Simply indicates that the material can be installed on a COMPLIANT fire door without affecting the door s rating Does not mean that the material will bring a door with excessive gaps into compliance 45
46 ANNUAL DOOR INSPECTIONS Excessive Gaps on Fire Doors Gasketing materials to address excessive gaps on fire doors must be specifically Listed for such use Must be Listed to UL R27658 as MISCELLANEOUS FIRE DOOR ACCESSORY FOR EXCESSIVE CLEARANCES OR GAPS Very few products on the market carry this Listing 46
47 INSPECTION / TESTING / MAINTENANCE OF SYSTEMS Communicate with Vendors Ensure they are Meeting the ITM Documentation Requirements for Proper Referenced Standards NFPA 25 (Water Based Fire Protection Systems) 2011 edition NFPA 72 (National Fire Alarm Code) 2010 edition 47
48 INSPECTION / TESTING / MAINTENANCE OF SYSTEMS, con t. NFPA 10 (Portable Fire Extinguishers) 2010 Edition NFPA 96 (Commercial Cooking Operations) 2011 edition NFPA 14 (Standpipe and Hose Systems) 2010 edition NFPA 13 (Sprinkler System) 2010 edition 48
49 QUESTIONS A. Richard Fasano Manager, Western Region Office
Presented by: Brad Keyes, CHSP Senior Consultant Keyes Life Safety Compliance, LLC
Presented by: Brad Keyes, CHSP Senior Consultant Keyes Life Safety Compliance, LLC Changes to Life Safety Compliance Healthcare leaders will have to deal with many changes in Life Safety compliance when
More informationNFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES
NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES Sharon S. Gilyeat, P.E., Principal Koffel Associates, Inc. www.koffel.com sgilyeat@koffel.com Expertly Engineering Safety From Fire
More informationTHE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5
THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5 AGENDA: Ambulatory Health Care & Business Occupancies Definitions / Examples Mixed & Contiguous Occupancies Ambulatory Health Care &
More informationChanges to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH)
Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH) The following represents a review of the Life Safety chapter of the new 2018 Joint Commission CAMH manual for
More informationTHE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2
THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1 QUESTIONS How To Ask a Question: POLLING There will be occasional
More informationAgency for Health Care Administration
Page 1 of 92 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0100 - General Requirements
More informationChapter 43, Building Rehabilitation allows for degrees of compliance based on the work category such as the extent of work.
3610 COMMERCE DR SUITE 817 BALTIMORE MD 21227 P 410.737.8677 F 410.737.8688 www.haifire.com May 5, 2014 Review of Regulations 42 CFR Parts 403, 416, 418, 460, 482, 483 and 485 Medicare and Medicaid Programs;
More informationNFPA 101 and NFPA 99, 2012 Editions Code Update. where art meets engineering
NFPA 101 and NFPA 99, 2012 Editions Code Update where art meets engineering Austin Dallas Denver Houston Kansas City Miami Nashville Phoenix Richmond Washington DC NFPA 101 and NFPA 99 where art meets
More informationAgency for Health Care Administration
Page 1 of 94 ST - K0000 - Initial Comments Title Initial Comments Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0100 - General
More informationFHCA 2014 Annual Conference & Trade Show
FHCA 2014 Annual Conference & Trade Show CE Session #5 Preparing for the Upcoming Code Changes Don t Look Back Tuesday, July 8 8:15 to 9:15 a.m. Canary 3 Operations/Quality Improvement Upon completion
More informationFirst Revision No NFPA [ Section No ]
of 45 10/21/2015 8:54 AM First Revision No. 3501-NFPA 101-2015 [ Section No. 3.3.190.1 ] 3.3.196.1* Ambulatory Health Care Occupancy. An occupancy used to provide services or treatment simultaneously to
More informationFIRE PROTECTION KEY DESIGN CONCEPTS IN HEALTHCARE FACILITIES Scott Twele, Aman Shah Steven Dannaway. AIA Healthcare Group
FIRE PROTECTION KEY DESIGN CONCEPTS IN HEALTHCARE FACILITIES Scott Twele, Aman Shah Steven Dannaway AIA Healthcare Group Introductions Presenters Coffman Engineers Scott M. Twele, P.E. Operations Manager,
More informationCenter for Clinical Standards and Quality /Survey & Certification Group
DEPARTMENT OF HEALTH & HUMAN SERVICES Centers for Medicare & Medicaid Services 7500 Security Boulevard, Mail Stop C2-21-16 Baltimore, Maryland 21244-1850 Center for Clinical Standards and Quality /Survey
More informationBuilding Codes & Standards for Healthcare. Healthcare Construction Certificate - Level 1
Building Codes & Standards for Healthcare Building Codes and Standards AHJs Codes Defend in Place Walls Sprinklers Fire Alarm Important Dates for Healthcare Facilities 7/5/16 NFPA Life Safety Code 101
More informationCity of South Salt Lake Fire Code Training Exiting, Egress Systems and Egress Control
City of South Salt Lake Fire Code Training Exiting, Egress Systems and Egress Control 11-27-12 This document is designed as a summary guide using IFC requirements for the provisions associated with exiting,
More informationTHE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4
THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1 QUESTIONS How To Ask a Question: POLLING There will be occasional
More informationPublic. Mike Free Health. State of Alabama Department of
State of Alabama Department of Mike Free Building Construction Specialist Technical Services Unit Office of Facilities Management Public 334-206-5221 334-206-5177 Health Fax: 334-206-5890 Web Site: www.adph.org.facmgmt
More informationPublic Health Fax: Web Site:
State of Alabama Department of Public Health Fax: 334-206-5890 Web Site: www.adph.org.facmgmt Mike Free Building Construction Specialist Technical Services Unit Office of Facilities Management 334-206-5221
More informationNFPA 101 Code Update from 2012 Edition to the 2015 Edition
NFPA 101 Code Update from 2012 Edition to the 2015 Edition Presented by: Gary Furdell AHCA Fire Protection Specialist 1 2 2012 Update to 2015 Chapter 18 New Health Care Occupancies 4 18.1.3.2 Atrium walls
More informationReport on First Revisions with Statement June 2014 NFPA 101
101 FR3002 SAF-HEA (18.1.3.2) Recommendation: 18.1.3.2 Atrium walls in accordance with 6.1.14.4.6 shall be permitted to serve as part of the separation required by 6.1.14.4.1 for creating separated occupancies
More informationEmergency Planning for Institutional Facilities
Emergency Planning for Institutional Facilities Pacific ADA Emergency Preparedness Webinars Presented by: Kimberly Paarlberg, ICC Based on the 2015 edition of the International Building Code (IBC) and
More informationAgency for Health Care Administration
Page 1 of 75 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K0100 - General Requirements - Other Title General Requirements - Other General Requirements - Other List in the REMARKS
More informationDeveloping a Healthcare Facility Fire Door Inspection Program
Developing a Healthcare Facility Fire Door Inspection Program WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio QUESTIONS How To Ask a Question: 1 POLLING There will be occasional interactive
More informationJOINT COMMISSION PREPAREDNESS / STATEMENT OF CONDITIONS DRAWINGS WSSHE SOUTHWEST CHAPTER NOVEMBER 19, 2015
JOINT COMMISSION PREPAREDNESS / STATEMENT OF CONDITIONS DRAWINGS WSSHE SOUTHWEST CHAPTER NOVEMBER 19, 2015 AGENDA INTRODUCTION OF PRESENTERS SOC VS. FIRE & LIFE SAFETY DRAWINGS HAZARDOUS AREAS VS. INCIDENTAL
More informationAgency for Health Care Administration
Page 1 of 75 ST - K0000 - Initial Comments Title Initial Comments Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0001 - OTHER
More informationSAF-BCF SECOND REVISIONS WITH STATEMENTS
Page 196 of 331 32.2.1.3 ] Second Revision No. 153-NFPA 101-2013 [ New Section after 32.2.1.4 Multiple-Level Buildings. For purposes of applying requirements of this chapter that utilize the term level
More informationNFPA 101 Life Safety Code Culture change 2012
NFPA 101 Life Safety Code Culture change 2012 Produced by Kansas Fire Marshal April, 2012 On March 9, 2012 Centers for Medicare & Medicaid Services implements a policy where they have formally adopted
More informationAgency for Health Care Administration
Page 1 of 92 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS Type Memo Tag FED - KA100 - General Requirements - Other Title
More informationFire and Smoke Door Inspections Qualified Training 02/03/17
Fire and Smoke Door Inspections Qualified Training 02/03/17 Basis of Requirements NFPA 101 requires annual fire and smoke door inspections (Section 18/19.2.2.2.1) Sections 18/19.2.2.1 require compliance
More informationTaming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes JENSEN & HALSTEAD LTD.
Taming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes Comparing the Codes: NFPA 101 Life Safety Code (2000) (NFPA) International Building Code (2012) (IBC) Chicago
More informationCompliance w/ the 2012 Life Safety Code
Compliance w/ the 2012 Life Safety Code Implications of the 2012 NFPA Code Set for Existing & New ASCs William E. Lindeman, AIA http://www.weldesigns.com Financial Interest Disclosure The presenter provides
More informationFACILITY MANAGEMENT DEFICIENCIES IN ACUTE CARE SETTINGS
FACILITY MANAGEMENT DEFICIENCIES IN ACUTE CARE SETTINGS Presented by: Alise Howlett, Assoc. AIA,CFPE, CHFM Standards Advisor, EM/PE/LS HFAP A better healthcare survey experience 1 FREQUENT PHYSICAL ENVIRONMENT
More informationBalloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition
Copyright National Fire Protection Association 2013. All rights reserved. This copy is solely for your personal, noncommercial use in connection with participation in the NFPA Standards Development Process.
More informationTHE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #6
THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #6 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1 QUESTIONS How To Ask a Question: POLLING There will be occasional
More informationThe Healthcare Environment Update
2017 The Healthcare Environment Update John Maurer, SASHE, CHFM, CHSP Engineering Department The Joint Commission Engineering Department 2017-1 Most Cited Standards Standard 2015 % Noncompliance 2016 %
More information2000 to 2012 Hospital K-tag crosswalk matrix for hospitals 2000 Tag #
P Language 0 Language 2018 IBC/IFC Section Commentary N/A N/A N/A K100 2 General Requirements Other List in the REMARKS section, any LSC Section 18.1 and 19.1 General Requirements that are not addressed
More informationReport on First Revisions with Statement June 2014 NFPA 101
101 FR6005 SAF-BCF (32.2.1.1.2) Recommendation: 32.2.1.1.2 Where there are sleeping accommodations for more than 16 residents are provided, the occupancy shall be classified as a large facility in accordance
More information2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content
Based on the 2018 International Fire Code, (IFC ) The International Fire Code (IFC ), establishes minimum regulations for fire safety. This handout will identify important changes in the IFC from 2015
More informationC. None (No sprinkler system) K3 E. NUMBER OF BEDS CERTIFIED FOR MEDICAID
DEPARTMENT OF HEALTH AND HUMAN SERVICES CENTERS FOR MEDICARE & MEDICAID SERVICES FIRE SAFETY SURVEY REPORT - 2000 LIFE SAFETY CODE Intermediate Care Facilities for the Mentally Retarded LARGE PART I Figure
More informationAgency for Health Care Administration
Page 1 of 34 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0001 - OTHER
More informationE25 (D) Automatic controls for general means of egress lighting
Adhoc Health Care MOE Study Group Study Group Report of Adhoc Meeting July 12&13, 2012 Possible Public Comments E25, E69, E74, G71, G77/G80 Study Group E25 (D) Automatic controls for general means of egress
More informationNew DATE OF BLDG. PERMIT OR PLAN APPROVAL: SURVEYOR (SIGNATURE) TITLE OFFICE DATE REVIEW AUTHORITY OFFICIAL (SIGNATURE) TITLE OFFICE DATE
DEPARTMENT OF HEALTH & HUMAN SERVICES CENTERS FOR MEDICARE & MEDICAID SERVICES FIRE SAFETY SURVEY REPORT - AMBULATORY SURGICAL CENTERS Medicare 1. (A) PROVIDER NUMBER Identifying information as shown in
More informationDEALING WITH FIRE SAFETY
DEALING WITH FIRE SAFETY Personal Care Homes And Assisted Living Facilities Presented by: Harold D. Hicks, P.E., FSFPE Fire Protection Engineer 1 Atlantic Code Consultants 2 Our Objectives Recognize the
More informationAHC Meeting #7 July 12-13, Occupancy WG Report
AHC Meeting #7 July 12-13, 2012 Part 1: CTC public comments on I-1/I-2 Condition designations..page 1 Part 2; AHC public comments on I-2 Condition designations Page 6 Part 3: Approved code change G244
More informationFACILITY MANAGEMENT DEFICIENCIES IN CRITICAL ACCESS HOSPITALS (CAH)
FACILITY MANAGEMENT DEFICIENCIES IN CRITICAL ACCESS HOSPITALS (CAH) Presented by: Alise Howlett, Assoc. AIA, CFPE, CHFM Standards Advisor, EM/PE/LS HFAP A better healthcare survey experience 1 FREQUENT
More informationAHC MEETING #4 PART I ROUND 1 ISSUES CODE CHANGES
AHC MEETING #4 MOE WORK GROUP REPORT & NOTES FROM AHC # 4 (IBC Chapters 4, 10 & 11) This appendix is based on the AHC s review of the noted Work group Report at AHC Meeting # 4. Meeting # 4 of the AHC
More informationFirst Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement
of 43 10/20/2015 4:02 PM First Revision No. 2035-NFPA 101-2015 [ Global Input ] To 14.3.4.4.1, add an item (4) to read: (4) Carbon monoxide detectors shall be installed centrally located within occupiable
More informationAgency for Health Care Administration
Page 1 of 41 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K0011 - LIFE SAFETY CODE STANDARD If the building has a common wall with a nonconforming building, the common
More informationDefend In Place 2012 IFC Overview of Institutional Occupancies
Defend In Place 2012 IFC Overview of Institutional Occupancies ICC Course No. ICC CEU s = 0.50 SCFA Course 8506-15-0 Nathan Ellis Cell: 864-812-5183 Nathan.Ellis@llr.sc.gov Institutional Occupancies Course
More informationCMS Announcement 3/27/2017. Adoption of 2012 Life Safety Code Health Care Facilities Code. Kenneth Daily, LNHA
Adoption of 2012 Life Safety Code Health Care Facilities Code Kenneth Daily, LNHA kenn@qissurvey.com CMS Announcement May 2016 Life Safety Code Health Care Code Effective July 5 th Numerous changes many
More informationFirst Aspen Federal Regulation Set: K LSC 2000 Health Existing
First Aspen Federal Regulation Set: K 01.01 LSC 2000 Health Existing K 0000 Title CFR Type INITIAL COMMENTS Memo K 0011 If the building has a common wall with a nonconforming building, the common wall
More informationAccreditation Program: Hospital
ccreditation Program: Hospital Life Safety 2008 The Joint ommission on ccreditation of Healthcare Organizations ccreditation Program: Hospital hapter: Life Safety Standard LS.0001 The [organization] designs
More informationAgency for Health Care Administration
Page 1 of 98 ST - Y0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. Based on the LSC surveyor's determination
More informationDepartment of Health Life Safety Code Update
Department of Health Life Safety Code Update Presented by: Charlie Schlegel, Director Division of Safety Inspection Overview CMS Adoption of the 2012 Life Safety Code (LSC) and 2012 Health Care Facilities
More informationAgency for Health Care Administration
Page 1 of 100 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS CFR Type Memo Tag FED - KA100 - General Requirements - Other
More informationCHAPTER 7 ALTERATIONS LEVEL
CHAPTER 7 ALTERATIONS LEVEL 2 SECTION 701 GENERAL 701.1 Scope. Level 2 alterations as described in Section 404 shall comply with the requirements of this chapter. Exception: Buildings in which the reconfiguration
More information1. Are there any annual sprinkler head inspection forms available? No, there are none available at this time.
Sprinkler 1. Are there any annual sprinkler head inspection forms available? No, there are none available at this time. 2. Does the annual sprinkler head inspection have to be done by a licensed technician
More informationLife Safety Code Common Discepancies Course# LSC102. EZpdh.com All Rights Reserved
Life Safety Code Common Discepancies Course# LSC102 EZpdh.com All Rights Reserved 1. K147 Electrical - Electrical wiring and equipment shall be in accordance with NFPA 70, National Electrical Code. 9.1.2
More informationM E M O R A N D U M. All Licensed Assisted Living Facilities. Felicia Cooper, Deputy State Fire Marshal Administrator Don Zeringue, Chief Architect
M E M O R A N D U M To: From: Approved: All Licensed Assisted Living Facilities Felicia Cooper, Deputy State Fire Marshal Administrator Don Zeringue, Chief Architect Henry Fry, Deputy Assistant Secretary
More informationJanuary 1, 2014 Mandatory Effective Date
2013 Kentucky Building Code Highlights Winnie Blythe, Technical Advisor Dept. of Housing, Buildings, and Construction winnie.blythe@ky.gov www.dhbc.ky.gov 502-573-0373 January 1, 2014 Mandatory Effective
More informationGROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES
[B] APPENDIX SR GROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES The provisions contained in this appendix are adopted by the Building Codes Division of the State of Oregon SECTION SR101
More informationFIRE SAFETY SURVEY REPORT AMBULATORY SURGICAL CENTERS (ASC) & END STAGE RENAL DISEASE (ESRD) MEDICARE
DEPARTMENT OF HEALTH AND HUMAN SERVICES CENTERS FOR MEDICARE & MEDICA SERVICE Form Approved OMB Exempt FIRE SAFETY SURVEY REPORT AMBULATORY SURGICAL CENTERS (ASC) & END STAGE RENAL DISEASE (ESRD) MEDICARE
More information<< COMPANY LETTERHEAD >>
Healthcare Facilities Accreditation Program Attn: Engineering Department 142 E. Ontario Street Chicago, IL 60611 > < Date > RE: Request for Code Equivalency ABC General Hospital,
More informationIFC Significant Changes from the 2009 to the 2015 Edition Tier 1
IFC Significant Changes from the 2009 to the 2015 Edition Tier 1 Several medical care definitions were created and revised in Chapter 2 of the 2012 IBC, as well as through the occupancy descriptions, and
More informationAgency for Health Care Administration
Page 1 of 51 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K0130 - MISCELLANEOUS Title MISCELLANEOUS OTHER LSC DEFICIENCY NOT ON 2786 FED - K9999 - FINAL OBSERVATIONS Title
More informationReview of Revisions to NFPA 1, 2015 Edition
James S Peterkin, PE, LEED AP Senior Fire Protection Engineer TLC Engineering for Architecture Anthony Apfelbeck, CFPS, CBO, CFO, FM, FIFireE, MPA Building and Fire Official City of Altamonte Springs,
More informationTop (15) Life Safety Code Deficiencies and Tips for Compliance (10/01/2011 thru 02/22/2012)
1. K62 Automatic Sprinkler Systems - Automatic sprinkler systems are continuously maintained in reliable operating condition and are inspected and tested periodically. 18.7.6, 19.7.6, 4.6.12, NFPA 13,
More informationTOPICS IN CODE ENFORCEMENT
TOPICS IN CODE ENFORCEMENT CAHED SE DISTRICT MEETING FEBRUARY 17, 2017 Mark Jelinske Cator, Ruma, and Associates mjelinske@catorruma.com 303-462-8475 TALKING POINTS Conducting Surveys on NFPA 2012 as of
More informationAgency for Health Care Administration
Page 1 of 21 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0300 - Other
More informationChanges to NFPA 101A 2013 Edition for Health Care Facilities
2017 NFPA Conference & Expo Changes to NFPA 101A 2013 Edition for Health Care Facilities Presented by: William Koffel, P.E, FSFPE Lennon Peake, P.E. Koffel Associates Koffel Associates President Manager
More informationHealth Chapter ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE
Health Chapter 420-5-22 ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE CHAPTER 420-5-22 SUBMISSION OF PLANS AND SPECIFICATIONS FOR HEALTH CARE FACILITIES TABLE OF
More information9/23/ :20 AM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification
of 4 9/23/2016 10:20 AM Second Revision No. 6501-NFPA 5000-2016 [ Section No. 17.2.2.2.4 ] 17.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked
More informationPresented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC Web: Lauzon-LSC.com
Presented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC 262-945-4567 Lauzon.lsc@gmail.com Web: Lauzon-LSC.com 2 Wis Professional Engineer Experienced Facility Director Experienced AHJ WHEA Code
More informationBarrier Management- Defending the Safety of Patients, Visitors, & Staff
Barrier Management- Defending the Safety of Patients, Visitors, & Staff About Your Speaker Rick Tinsley: 3 Years as Healthcare Construction Electrician 38 Years in Healthcare Facility Maintenance 13 Years
More informationGROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES
[B] APPENDIX SR GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES The provisions contained in this appendix are adopted by the Building Codes Division of the State of Oregon. SECTION SR101 GENERAL
More informationAgency for Health Care Administration
Page 1 of 130 ST - K0000 - Initial Comments Title Initial Comments Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. Based on the LSC
More information2007 CBC & CFC Residential Care Facility Requirements (24 hour care only)
2007 & CFC Residential Care Facility Requirements (24 hour care only) Occupancy Construction Smoke Barrier I-1 Bedridden 7+non- Ambs Or bed- Ridden R-4 7+ambs (May have 6 nonambs or 6 bedridden) R-3.1
More informationChanges to Environment of Care, Equipment Management, and Life Safety Chapters Related to Life Safety Code Updates
Issued September 20, 2017 Changes to Environment of Care, Equipment Management, and Life Safety Chapters Related to Life Safety Code Updates Environment of Care (EC) Chapter Home Care (OME) Accreditation
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT RAISA FASHIONS LTD. ACCORD ID: 11741 PLOT# B63, BSCIC INDUSTRIAL ESTATE, KANCHPUR, SONORGAON, NARAYANGANJ OTHER FACTORIES: NONE February 27, 2015 Page 2 SUMMARY was surveyed
More informationOhio Department of Health NFPA 2012 Life Safety Code Tips Sheet
Ohio Department of Health NFPA 2012 Life Safety Code Tips Sheet This document is used for frequently cited Life Safety Code violations. This is not an all-inclusive list and is intended for reference only.
More informationFire & Life Safety Code Compliance. Common Safety Deficiencies and Tips for Compliance for Long Term Care and Skilled Nursing Facilities
Fire & Life Safety Code Compliance Common Safety Deficiencies and Tips for Compliance for Long Term Care and Skilled Nursing Facilities LTC, Skilled Nursing Facilities COMMON LIFE SAFETY DEFICIENCIES
More informationAgency for Health Care Administration. Eddie Alday Life Safety Code Lead 30 th AHCA Seminar 23 September 2014
Agency for Health Care Administration Eddie Alday Life Safety Code Lead 30 th AHCA Seminar 23 September 2014 CMS S&C Letter Interpretation CMS- S&C: 13-58-LSC Dated: 08/30/2013 Several Categorical LSC
More information2017 Accreditation Updates
2017 Accreditation Updates Tennessee Healthcare Engineers Association 2017 Spring Conference Pickwick Landing State Park Counce, Tennessee 38326 Presented May 17, 2017 By Ken Gregory Vice President, Accreditation
More information4/9/2014. Life Safety Code. Nursing Facility Life Safety Code Today and Tomorrow. Kenneth Daily, LNHA.
Nursing Facility Life Safety Code Today and Tomorrow Kenneth Daily, LNHA kenn@qissurvey.com April 2014 Life Safety Code Life Safety Code 101 (2000 Ed.) Promulgated by the National Fire Protection Association
More informationCrosswalk of 2014 HFAP Standards against HFAP Standards Acute Care Hospital Manual
09.00.01 Operations Plan 11.07.01 09.00.02 Hazard Vulnerablity Analysis (HVA) 09.01.01 Safety & Security 11.00.02 New Name 09.01.02 Supplies 09.01.03 482.41(a)(2) Utilities 11.03.21; 11.03.22 09.01.04
More informationDanilo B. Concepcion, CBNT, CCHT-A Operations Manager St. Joseph Hospital Renal Services
Life Safety Code Danilo B. Concepcion, CBNT, CCHT-A Operations Manager St. Joseph Hospital Renal Services danilo.concepcion@stjoe.org 714-771-8944 The findings and conclusions in this presentation are
More informationIowa State Fire Marshal
Iowa State Fire Marshal LIFE SAFETY CODE REQUIREMENTS LONG TERM CARE Kyle R. Gorsh, Special Agent in Charge Iowa Department of Public Safety State Fire Marshal Division 2012 LSC & Applicable Standards
More informationAgency for Health Care Administration
Page 1 of 133 ST - Y0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - Y1001 - Awareness of the
More informationWritten Fire Safety Plans
Written Fire Safety Plans 2012 LSC KATHARINE ACHOR SEPTEMBER 2016 NFPA Standard: 2012 NFPA 101, 19.1.1.3.1 All health care facilities shall be designed, constructed, maintained, and operated to minimize
More informationPrepublication New Text Jan 2018 Changes to Environment of Care and Life Safety Chapters
Prepublication New Text Jan 2018 Changes to Environment of Care and Life Safety Chapters EC.01.01.01 EP3 Related to Life Safety Code Updates Hospital (HAP) Accreditation Program The hospital has a library
More informationLife Safety Code NFPA 10 NFPA 13 NFPA 25 NFPA 72 NFPA 90A NFPA 110 NFPA 99 THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #7
THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #7 AGENDA: Life Safety Code Referenced Publications Overview Life Safety Code NFPA 10 NFPA 13 NFPA 25 NFPA 72 NFPA 90A NFPA 110 NFPA 99
More informationFIRE SAFETY AND EVACUATION PLANNING FOR ASSISTED LIVING FACILITIES AND NURSING HOMES
FIRE SAFETY AND EVACUATION PLANNING FOR ASSISTED LIVING FACILITIES AND NURSING HOMES West Metro Fire Rescue Life Safety Division 433 South Allison Parkway Lakewood, Colorado 80226 (303) 989-4307 Fax (303)
More informationReport on First Revisions with Statement June 2014 NFPA 101
101 FR7040 SAF-MER (36.1.1.4) 36.1.1.4 The provisions of this chapter shall apply to life safety requirements for all new mercantile buildings. Specific requirements shall apply to suboccupancy groups,
More informationTop 8 Findings & SAFER Matrix for the 2017 ACE Summit & Expo
Top 8 Findings & SAFER Matrix for the 2017 ACE Summit & Expo February 20, 2017 Atlanta, GA Larry F. Rubin CHFM, CHSP, CPE, CEM Life Safety Code Surveyor The Joint Commission Engineering Department 2015-1
More informationASCs & LSC. Alice Epstein, DFASHRM, FNAHQ
, DFASHRM, FNAHQ Disclaimer The purpose of this presentation is to provide information, rather than advice or opinion. It is accurate to the best of the speaker's knowledge as of the date of the presentation.
More informationFIRE SAFETY SURVEY REPORT 2000 CODE - HEALTH CARE Medicare Medicaid
DEPARTMENT OF HEALTH AND HUMAN SERVICES CENTERS FOR MEDICARE & MEDICA SERVICES FIRE SAFETY SURVEY REPORT - HEALTH CARE Medicare Medicaid 2. NAME OF FACILITY 2. (A) MULTIPLE CONSTRUCTION (BLDGS) 3. SURVEY
More informationEXPLORING LIFE SAFETY COMPLIANCE FOR HEALTH CARE
2016 EXPLORING LIFE SAFETY COMPLIANCE FOR HEALTH CARE James Woodson, Engineer Engineering Department The Joint Commission HOSPITAL BREAKFAST BRIEFINGS PART 6 Disclosure Statement The following staff and
More informationHealth Care Facility Rehabilitation
2017 NFPA Conference & Expo Health Care Facility Rehabilitation Effective Application of NFPA 101 2012, Life Safety Code Chapter 43 Building Rehabilitation Ron Coté, P.E. NFPA Health Care Facility Rehabilitation
More informationICC CODE CORNER 2015 International Fire Code
PART II GENERAL SAFETY PROVISIONS CHAPTER 4 EMERGENCY PLANNING AND PREPAREDNESS SECTION 401 GENERAL 401.1 Scope. Reporting of emergencies, coordination with emergency response forces, emergency plans and
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT M.S.ATTIRES LTD. ACCORD ID: 10887 A. RAHMAN PLAZA, SHANSHONGAON, FATULLAH, NARAYANGONJ OTHER FACTORIES: AISA FASHION LTD.; PRINT GARDEN LTD.; S.M. COLLECTION LTD. February
More information