1 TECHNICAL COMMITTEE ON FIRE PUMPS MEMORANDUM TO: FROM: Technical Committee on Fire Pumps Joanne Goyette, on behalf of C. Duffy / R. P. Benedetti DATE: May 2, 2011 SUBJECT: Letter Ballot on Proposals to Amend NFPA 22 At the January 2011 NFPA 20 Report on Proposals (ROP) meeting in Orlando FL, it was agreed to submit the attached three proposals to amend NFPA 22, Standard for Water Tanks for Private Fire Protection. Since these three proposals are being submitted by the Technical Committee on Fire Pumps, the NFPA Regulations Governing Committee Projects require that there be a formal letter ballot to authorize submitting the proposals in the name of this Technical Committee. Please review the three proposals, mark your ballot accordingly, and return your ballot as directed by the deadline date of Friday, May 13, Time is of the essence. If you have any questions, please call Bob Benedetti at Attachments: Proposals Letter Ballot cc FIM Ballot Folder rpb/jmg

2 NFPA Technical Committee Document Proposal Form NOTE: All Proposals Must Be Received by 5:00 P.M. EST/EDST on the Published Proposal Closing Date. FOR OFFICE USE ONLY For further information on the standards-making process, please contact the Codes and Standards Administration at or visit Log #: For technical assistance, please call NFPA at Date Rec'd: Please indicate in which format you wish to receive your ROP/ROC electronic paper download (Note: In choosing the download option you intend to view the ROP/ROC from our Website; no copy will be sent to you.) Date April 29, 2011 Name_NFPA 20 Committee Gayle Pennel Chairman _Tel. No Company _NFPA 20 Committee Street Address 1000 Milwaukee Ave 5 th Floor City_Glenview State_IL Zip Please Indicate Organization Represented (if any) _NFPA 20 Committee 1. (a) NFPA Document Title NFPA 22 NFPA No. & Year2007 (b) Section/Paragraph Proposal recommends: (check one) new text revised text deleted text 3. Proposal (include proposed new or revised wording, or identification of wording to be deleted): (Note: Proposed text should be in legislative format; i.e., use underscore to denote wording to be inserted (inserted wording) and strike-through to denote wording to be deleted (deleted wording). Insert New definition Break Tank. A tank providing suction to a fire pump whose capacity is less than the fire protection demand (flow rate times flow duration). Resequence existing section Statement of Problem and Substantiation for Proposal: (Note: State the problem that will be resolved by your recommendation; give the specific reason for your proposal including copies of tests, research papers, fire experience, etc. If more than 200 words, it may be abstracted for publication.) Guidance for designing break tanks is needed in NFPA 22. This definition is part of the submittal for design guidelines This submittal to NFPA 22 was accepted by the NFPA 20 committee at the Jan 2011 ROP meeting in Orlando 5. Copyright Assignment (a) I am the author of the text or other material (such as illustrations, graphs) proposed in this Proposal. (b) Some or all of the text or other material proposed in this Proposal was not authored by me. Its Source is as follows: (Please identify which material and provide compete information to its source: NFPA 20 I hereby grant and assign to the NFPA all and full rights in copyright in this Comment and understand that I acquire no rights in any publication of NFPA in which this Comment in this or another similar or analogous form is used. Except to the extent that I do not have authority to make an assignment in materials that I have identified in (b) above, I hereby warrant that I am the author of this comment and that I have full power and authority to enter into this assignment. Signature (Required) PLEASE USE SEPARATE FORM FOR EACH COMMENT NFPA Fax: (617) Mail to: Secretary, Standards Council, National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02269

3 NFPA Technical Committee Document Proposal Form NOTE: All Proposals Must Be Received by 5:00 P.M. EST/EDST on the Published Proposal Closing Date. FOR OFFICE USE ONLY For further information on the standards-making process, please contact the Codes and Standards Administration at or visit Log #: For technical assistance, please call NFPA at Date Rec'd: Please indicate in which format you wish to receive your ROP/ROC electronic paper download (Note: In choosing the download option you intend to view the ROP/ROC from our Website; no copy will be sent to you.) Date April 29, 2011 Name_NFPA 20 Committee Gayle Pennel Chairman _Tel. No Company _NFPA 20 Committee Street Address 1000 Milwaukee Ave 5 th Floor City_Glenview State_IL Zip Please Indicate Organization Represented (if any) _NFPA 20 Committee 1. (a) NFPA Document Title NFPA 22 NFPA No. & Year2007 (b) Section/Paragraph Proposal recommends: (check one) new text revised text deleted text 3. Proposal (include proposed new or revised wording, or identification of wording to be deleted): (Note: Proposed text should be in legislative format; i.e., use underscore to denote wording to be inserted (inserted wording) and strike-through to denote wording to be deleted (deleted wording). Insert New Section Capacity and Elevation * The size and elevation of the tank shall be determined by conditions at each individual property after due consideration of all factors involved Wherever possible, standard sizes of tanks and heights of towers shall be as specified in 5.1.3, 6.1.2, 8.1.3, and Section For suction tanks, the net capacity shall be the number of U.S. gallons (cubic meters) between the inlet of the overflow and the level of the vortex plate A tank shall be sized so that the stored supply plus reliable automatic refill shall be sufficient to meet the demand placed upon it for the design duration A break tank shall be sized for a minimum duration of 15 minutes with the fire pump operating at 150 percent of rated capacity Liquid Sources The adequacy and dependability of the liquid source for filling the are of primary importance and shall be fully determined, with due allowance for its reliability in the future Any source of water that is adequate in quality, quantity, pressure, and reliability to fill the tank in accordance with this standard shall be permitted Where the water supply from a public service main is not adequate in quality, quantity, or pressure, an alternative water source shall be provided The adequacy of the liquid supply shall be determined and evaluated prior to the specification and installation of the tank. Resequence Existing section Statement of Problem and Substantiation for Proposal: (Note: State the problem that will be resolved by your recommendation; give the specific reason for your proposal including copies of tests, research papers, fire experience, etc. If more than 200 words, it may be abstracted for publication.) Guidance for designing break tanks is needed in NFPA 22 The text in this proposal is taken from NFPA 20 This submittal to NFPA 22 was accepted by the NFPA 20 committee at the Jan 2011 ROP meeting in Orlando

4 5. Copyright Assignment (a) I am the author of the text or other material (such as illustrations, graphs) proposed in this Proposal. (b) Some or all of the text or other material proposed in this Proposal was not authored by me. Its Source is as follows: (Please identify which material and provide compete information to its source: NFPA 20 I hereby grant and assign to the NFPA all and full rights in copyright in this Comment and understand that I acquire no rights in any publication of NFPA in which this Comment in this or another similar or analogous form is used. Except to the extent that I do not have authority to make an assignment in materials that I have identified in (b) above, I hereby warrant that I am the author of this comment and that I have full power and authority to enter into this assignment. Signature (Required) PLEASE USE SEPARATE FORM FOR EACH COMMENT NFPA Fax: (617) Mail to: Secretary, Standards Council, National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02269

5 NFPA Technical Committee Document Proposal Form NOTE: All Proposals Must Be Received by 5:00 P.M. EST/EDST on the Published Proposal Closing Date. FOR OFFICE USE ONLY For further information on the standards-making process, please contact the Codes and Standards Administration at or visit Log #: For technical assistance, please call NFPA at Date Rec'd: Please indicate in which format you wish to receive your ROP/ROC electronic paper download (Note: In choosing the download option you intend to view the ROP/ROC from our Website; no copy will be sent to you.) Date_ April 29, 2011_Name_NFPA 20 Committee Gayle Pennel Chairman _Tel. No Company _NFPA 20 Committee Street Address 1000 Milwaukee Ave 5 th Floor City_Glenview State_IL Zip Please Indicate Organization Represented (if any) _NFPA 20 Committee 1. (a) NFPA Document Title NFPA 22 NFPA No. & Year2007 (b) Section/Paragraph Proposal recommends: (check one) new text revised text deleted text 3. Proposal (include proposed new or revised wording, or identification of wording to be deleted): (Note: Proposed text should be in legislative format; i.e., use underscore to denote wording to be inserted (inserted wording) and strike-through to denote wording to be deleted (deleted wording). Insert New Section Break Tanks. Where a break tank is used to provide the pump suction water supply, the installation shall comply with this section Application. Break tanks are used for one or more of the following reasons: (1) As a backflow prevention device between the city water supply and the fire pump suction (2) To eliminate pressure fluxations in the city water supply and provide a steady suction pressure to the fire pump (3) To augment the city water supply when the volume of water available from the city is inadequate for the fire protection demand Break Tank Size. The tank shall be sized for a minimum duration of 15 minutes with the fire pump operating at 150 percent of rated capacity Refill Mechanism. The refill mechanism shall be listed and arranged for automatic operation If the break tank capacity is less than the maximum system demand for 30 minutes, the refill mechanism shall meet the requirements in through Dual automatic refill lines, each capable of refilling the tank at a minimum rate of 150 percent of the fire pump(s) capacity, shall be installed If available supplies do not permit refilling the tank at a minimum rate of 150 percent of the rated pump capacity, each refill line shall be capable of refilling the tank at a rate that meets or exceeds 110 percent of the maximum fire protection system design flow A manual tank fill bypass designed for and capable of refilling the tank at a minimum rate of 150 percent of the fire pump(s) capacity shall be provided If available supplies do not permit refilling the tank at a minimum rate of 150 percent of the rated pump capacity, the manual fill bypass shall be capable of refilling the tank at a rate that meets or exceeds 110 percent of the maximum fire protection system design flow A local visible and audible low liquid level signal shall be provided in the vicinity of the tank fill mechanism If the break tank is sized to provide a minimum duration of 30 minutes of the maximum system demand, the refill mechanism shall meet the requirements in through The refill mechanism shall be designed for and capable of refilling the tank at 110 percent of the rate required to provide the total fire protection system demand [110% (Total Demand - Tank Capacity) / Duration] A manual tank fill bypass designed for and capable of refilling the tank at 110 percent of the rate required to provide the total fire protection system demand [110% (Total Demand - Tank Capacity) / Duration] The pipe between the city connection and the automatic fill valve shall be installed in accordance with NFPA 24, Standard for the Installation of Private Fire Service Mains and Their Appurtenances The automatic filling mechanism shall be maintained at a minimum temperature of 40 F (4.4 C).

6 The automatic filling mechanism shall activate a maximum of 4 in. (152 mm) below the overflow level. Resequence existing sections after Statement of Problem and Substantiation for Proposal: (Note: State the problem that will be resolved by your recommendation; give the specific reason for your proposal including copies of tests, research papers, fire experience, etc. If more than 200 words, it may be abstracted for publication.) Guidance for designing break tanks currently provided in NFPA 20 should be in NFPA 22 This submittal to NFPA 22 was accepted by the NFPA 20 committee at the Jan 2011 ROP meeting in Orlando 5. Copyright Assignment (a) I am the author of the text or other material (such as illustrations, graphs) proposed in this Proposal. (b) Some or all of the text or other material proposed in this Proposal was not authored by me. Its Source is as follows: (Please identify which material and provide compete information to its source: NFPA 20 I hereby grant and assign to the NFPA all and full rights in copyright in this Comment and understand that I acquire no rights in any publication of NFPA in which this Comment in this or another similar or analogous form is used. Except to the extent that I do not have authority to make an assignment in materials that I have identified in (b) above, I hereby warrant that I am the author of this comment and that I have full power and authority to enter into this assignment. Signature (Required) PLEASE USE SEPARATE FORM FOR EACH COMMENT NFPA Fax: (617) Mail to: Secretary, Standards Council, National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02269

NFPA 550 ROP Meeting Minutes

NFPA 550 ROP Meeting Minutes NFPA 550 ROP Meeting Minutes NFPA Technical Committee on Fire Risk Assessment Methods (FIR-AAA) June 24, 2010 Microsoft Live Meeting 1. Call to order. The meeting was called to order at 1:00 PM on Monday,

More information

Report on Proposals F2007 Copyright, NFPA NFPA 499 Report of the Committee on

Report on Proposals F2007 Copyright, NFPA NFPA 499 Report of the Committee on Report on Proposals F2007 Copyright, NFPA NFPA 499 Report of the Committee on This list represents the membership at the time the Committee was balloted on the text of this edition. Since that time, changes

More information

National Fire Protection Association

National Fire Protection Association National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M (AMENDMENT) TO: FROM: Technical Committee on Mercantile

More information

TECHNICAL COMMITTEE ON FIRE CODE

TECHNICAL COMMITTEE ON FIRE CODE TECHNICAL COMMITTEE ON FIRE CODE M E M O R A N D U M TO: FROM: Technical Committee on Fire Code (FCC-AAA) Gregory Harrington, P.E., Staff Liaison DATE: February 3, 2011 SUBJECT: NFPA 1124 Amended CP#2

More information

MEMORANDUM. SUBJ: NFPA 72 Proposed TIA No FINAL CC BALLOT RESULTS

MEMORANDUM. SUBJ: NFPA 72 Proposed TIA No FINAL CC BALLOT RESULTS National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: NFPA Correlating Committee on Signaling Systems for

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: NFPA Technical Committee on Testing and Maintenance

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Correlating Committee on Combustible Dusts Susan

More information

MEMORANDUM. NFPA Technical Committee on Fire Code (FCC-AAA) Subject: NFPA 1 Proposed Tentative Interim Amendment (TIA) No.1045

MEMORANDUM. NFPA Technical Committee on Fire Code (FCC-AAA) Subject: NFPA 1 Proposed Tentative Interim Amendment (TIA) No.1045 National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Fire Code (FCC-AAA) Gregory

More information

Public Input No. 88-NFPA [ New Section after ] Statement of Problem and Substantiation for Public Input

Public Input No. 88-NFPA [ New Section after ] Statement of Problem and Substantiation for Public Input of 201 1/13/2014 12:51 PM Public Input No. 88-NFPA 20-2013 [ New Section after 3.3.38.10 ] Add New Defination 3.3.28.11 Multiple Stage Multiple Port Pump. A single driver pump with multiple impellers operating

More information

home smoke candles alarms electrical burns smoking medical oxygen cooking FIREFIGHTING MATCHES & LIGHTERS SPRINKLERS

home smoke candles alarms electrical burns smoking medical oxygen cooking FIREFIGHTING MATCHES & LIGHTERS SPRINKLERS FIREFIGHTING home smoke alarms REGULATIONS GOVERNING THE NFPA EDUCATIONAL MESSAGES DESK REFERENCE FOR THE FIRE SERVICE AND FIRE AND LIFE SAFETY EDUCATORS MATCHES & LIGHTERS medical oxygen cooking FIRE

More information

MEMORANDUM. Technical Committee on Board and Care Facilities. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017)

MEMORANDUM. Technical Committee on Board and Care Facilities. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Board and Care Facilities

More information

Page 1 of 198 Public Input No. 88-NFPA 20-2013 [ New Section after 3.3.38.10 ] Add New Defination 3.3.28.11 Multiple Stage Multiple Port Pump. A single driver pump with multiple impellers operating in

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle)

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) M E M O R A N D U M TO: FROM: NFPA Technical Committee on Alternative Approaches to Life Safety Linda MacKay DATE: December 28, 2010 SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) The ROP letter

More information

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Portable Fire Extinguishers

More information

Report on Comments F2006 Copyright, NFPA NFPA 560 Report of the Committee on

Report on Comments F2006 Copyright, NFPA NFPA 560 Report of the Committee on Report on Comments F2006 Copyright, NFPA NFPA 560 Report of the Committee on Nonvoting Industrial and Medical Gases Michael W. St. Clair, Chair Ostrander, OH [U] Rep. NFPA Industrial Fire Protection Section

More information

DENVER AMENDMENT PROPOSAL 2015 INTERNATIONAL CODES

DENVER AMENDMENT PROPOSAL 2015 INTERNATIONAL CODES DENVER AMENDMENT PROPOSAL 2015 INTERNATIONAL CODES NOTE: Each proposed Denver amendment to the International Codes must be justified. In order to be considered, the amendment proposal must address climate,

More information

NFPA Technical Committee on Fire Tests

NFPA Technical Committee on Fire Tests National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Fire Tests Tracy

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Merchant Vessels

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Hot Work Operations

More information

TECHNICAL COMMITTEE ON SAFETY AT MOTORSPORTS VENUES. NFPA 610 First Draft Meeting. October 17-18, 2016

TECHNICAL COMMITTEE ON SAFETY AT MOTORSPORTS VENUES. NFPA 610 First Draft Meeting. October 17-18, 2016 TECHNICAL COMMITTEE ON SAFETY AT MOTORSPORTS VENUES NFPA 610 First Draft Meeting October 17-18, 2016 Westin Kansas City at Crown Center 1 East Pershing Road Kansas City, MO, 64108 Conference Call Access:

More information

1 Batterymarch Park, Quincy, MA Phone: Fax: M E M O R A N D U M

1 Batterymarch Park, Quincy, MA Phone: Fax: M E M O R A N D U M National Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Industrial and Medical Gases Joanne

More information

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Service and Fire Protection Equipment Gregory Harrington, P.E., Staff Liaison DATE: October 1, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter

More information

1 Batterymarch Park, Quincy, MA Phone: Fax: M E M O R A N D U M

1 Batterymarch Park, Quincy, MA Phone: Fax: M E M O R A N D U M National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Fire Pumps Patti

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

560- installation of associated storage, piping, and distribution equipment; and Ostrander, OH [U]

560- installation of associated storage, piping, and distribution equipment; and Ostrander, OH [U] Report on Proposals F2006 Copyright, NFPA NFPA 560 Report of the Committee on Committee Scope: This Committee shall have primary responsibility for Industrial and Medical Gases documents on the storage,

More information

MEMORANDUM. Subject: NFPA 1124 Proposed Tentative Interim Amendment (TIA) No. 1094

MEMORANDUM. Subject: NFPA 1124 Proposed Tentative Interim Amendment (TIA) No. 1094 National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Pyrotechnics Elena Carroll,

More information

M E M O R A N D U M. Principal and Alternate Members of the Technical Committee on Commissioning Fire Protection Systems

M E M O R A N D U M. Principal and Alternate Members of the Technical Committee on Commissioning Fire Protection Systems 1 Technical Committee on Commissioning Fire Protection Systems M E M O R A N D U M DATE: March 30, 2010 TO: FROM: Principal and Alternate Members of the Technical Committee on Commissioning Fire Protection

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Building Service and

More information

Technical Committee on Fluidized Bed Boilers

Technical Committee on Fluidized Bed Boilers Technical on Fluidized Bed Boilers AGENDA Web/Teleconference 1. Chair s welcome, call to order, and opening remarks at 1:00 pm EST. 2. Self-Introduction of Members and Guests 3. Approval of Minutes from

More information

Committee on 51A M E M O R A N D U M. NFPA Technical Committee on Industrial and Medical Gases

Committee on 51A M E M O R A N D U M. NFPA Technical Committee on Industrial and Medical Gases Committee on 51A M E M O R A N D U M To: From: NFPA Technical Committee on Industrial and Medical Gases Patti Mucci, Administrative Assistant Date: June 14, 2010 Subject: NFPA 51A ROC Letter Ballot Circulation

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: DATE: Technical Committee on Handling and Conveying

More information

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Services and Fire Protection Equipment Linda MacKay DATE: November 10, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter Ballot Final Results The

More information

MEMORANDUM. NFPA Technical Committee on Fundamentals of Fire Alarm and Signaling Systems (SIG- FUN)

MEMORANDUM. NFPA Technical Committee on Fundamentals of Fire Alarm and Signaling Systems (SIG- FUN) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Fundamentals of Fire

More information

Agenda Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems June 24-25, 2013 Saint Louis, MO

Agenda Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems June 24-25, 2013 Saint Louis, MO Agenda Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems June 24-25, 2013 Saint Louis, MO Item No. Subject 13-6-1 Call to Order (8:00 A.M) 13-6-2 Roll Call 13-6-3 Approval

More information

2013 Annual Revision Cycle. Report on Proposals. A compilation of NFPA Technical Committee Reports on Proposals for public review and comment

2013 Annual Revision Cycle. Report on Proposals. A compilation of NFPA Technical Committee Reports on Proposals for public review and comment 2013 Annual Revision Cycle Report on Proposals A compilation of NFPA Technical Committee Reports on Proposals for public review and comment Public Comment Deadline: August 31, 2012 NOTE: The proposed NFPA

More information

RULES OF DEPARTMENT OF COMMERCE AND INSURANCE DIVISION OF FIRE PREVENTION CHAPTER FIRE EXTINGUISHERS TABLE OF CONTENTS

RULES OF DEPARTMENT OF COMMERCE AND INSURANCE DIVISION OF FIRE PREVENTION CHAPTER FIRE EXTINGUISHERS TABLE OF CONTENTS RULES OF DEPARTMENT OF COMMERCE AND INSURANCE DIVISION OF FIRE PREVENTION CHAPTER 0780-02-14 FIRE EXTINGUISHERS TABLE OF CONTENTS 0780-02-14-.01 Definitions 0780-02-14-.09 Restrictions 0780-02-14-.02 Standards

More information

M E M O R A N D U M. Please do not vote negatively because of editorial errors. However, please bring such errors to my attention for action.

M E M O R A N D U M. Please do not vote negatively because of editorial errors. However, please bring such errors to my attention for action. M E M O R A N D U M TO: FROM: NFPA Technical Committee on Fire Marshal Professional Qualifications Stacey Van Zandt DATE: July 13, 2010 SUBJECT: NFPA 1037 ROP TC Letter Ballot (F2011) The ROP letter ballot

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Standpipes Elena

More information

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM 1 of 213 10/20/2016 11:02 AM Committee Input No. 2505-NFPA 72-2016 [ Global Input ] Change the term visible to visual where appropriate Submitter Information Verification Submitter Full Name: SIG-NAS Organization:

More information

Report on Proposals F2007 Copyright, NFPA Report of the Committee on Dry and Wet Chemical Extinguishing Systems

Report on Proposals F2007 Copyright, NFPA Report of the Committee on Dry and Wet Chemical Extinguishing Systems Report of the Committee on Dry and Wet Chemical Extinguishing Systems Edward J. Kaminski, Chair Schirmer Engineering Corporation, NV [I] Paul E. Buchhofer, Building Inspection Underwriters, Inc., PA [E]

More information

Committee on NFPA 85

Committee on NFPA 85 Committee on NFPA 85 M E M O R A N D U M TO: FROM: NFPA Technical Committee on Single Burner Boilers Patti Mucci, Technical Assistant II DATE: August 5, 2009 SUBJECT: NFPA ROP Letter Ballot The ROP letter

More information

Guidelines Cooperation between authorities under Articles 17 and 23 of Regulation (EU) No 909/2014

Guidelines Cooperation between authorities under Articles 17 and 23 of Regulation (EU) No 909/2014 Guidelines Cooperation between authorities under Articles 17 and 23 of Regulation (EU) No 909/2014 11 July 2017 ESMA70-151-435 Table of Contents 1 Scope... 3 2 Purpose... 5 3 Compliance and reporting obligations...

More information

Public Comment No. 2-NFPA [ Section No ]

Public Comment No. 2-NFPA [ Section No ] Page 1 of 13 Public Comment No. 2-NFPA 703-2013 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, P.O. Box C700, 100 Barr Harbor Drive, West Conshohocken, PA 19428-2959. ASTM D 2898, Standard

More information

2011 Annual Revision Cycle. Report on Proposals. Public Comment Deadline: September 3, 2010

2011 Annual Revision Cycle. Report on Proposals. Public Comment Deadline: September 3, 2010 2011 Annual Revision Cycle Report on Proposals A compilation of NFPA Technical Committee Reports on Proposals for public review and comment Public Comment Deadline: September 3, 2010 NOTE: The proposed

More information

September 30, Dear Fire Suppression System Contractor/Designer:

September 30, Dear Fire Suppression System Contractor/Designer: CITY OF BOZEMAN FIRE DEPARTMENT P.O. Box 1230 Bozeman, Montana 59771-1230 Phone (406) 582-2350 CITY OF BOZEMAN BUILDING DEPARTMENT 20 E Olive St, STE 208 Bozeman, Montana 59715-4790 Phone (406) 582-2375

More information

Technical Committee on Fluidized Bed Boilers

Technical Committee on Fluidized Bed Boilers Technical Committee on Fluidized Bed Boilers AGENDA NFPA Headquarters 1 Batterymarch Park Quincy, MA 02169 1. Chair s welcome, call to order, and opening remarks at 1:00 pm EST. 2. Self-Introduction of

More information

2009 Fall Revision Cycle. Report on Proposals. A compilation of NFPA Technical Committee Reports on Proposals for public review and comment

2009 Fall Revision Cycle. Report on Proposals. A compilation of NFPA Technical Committee Reports on Proposals for public review and comment 2009 Fall Revision Cycle Report on Proposals A compilation of NFPA Technical Committee Reports on Proposals for public review and comment Public Comment Deadline: March 6, 2009 NOTE: The proposed NFPA

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: NFPA Technical Committee on Fundamentals of Fire

More information

2018 CALL FOR ENTRIES: DESIGN AWARDS

2018 CALL FOR ENTRIES: DESIGN AWARDS 2018 CALL FOR ENTRIES: DESIGN AWARDS PROFESSIONAL AWARDS Each year the Indiana Chapter of the American Society of Landscape Architects (INASLA) recognizes outstanding projects completed by individuals

More information

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved.

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved. Public Input No. 1-NFPA 557-2012 [ New Section after 1.5.3 ] 1.6 Approved Qualifications The design shall be prepared by a person with qualifications acceptable to the AHJ. The term designer is used in

More information

Tree Removal Application and Instructions

Tree Removal Application and Instructions VILLAGE OF NORTHBROOK Tree Removal Application and Instructions Why do I need to apply for a tree removal permit? Tree removal permits allow the Village to document the location, type, size and condition

More information

Page 1 of 190 Public Input No. 22-NFPA 55-2013 [ Global Input ] Throughout the document, delete ANSI from ANSI/ASME B31.3. Current Text: (multiple locations) ANSI/ASME B31.3 (found in Subsections: 2.3.2

More information

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement of 1 9/22/2014 1:38 PM Second Revision No. 104-NFPA 72-2014 [ Section No. 3.3.3 ] 3.3.3 Accessible, Readily (Readily Accessible). Capable of being reached quickly for operation, renewal, or inspections

More information

Standard Development Timeline

Standard Development Timeline Standard Development Timeline The drafting team maintained this section while developing the standard. It will be removed when the standard becomes effective. Description of Current Draft This draft is

More information

REPORT OF THE NFPA MOTIONS COMMITTEE* ON FALL 2013 REVISION CYCLE STANDARDS

REPORT OF THE NFPA MOTIONS COMMITTEE* ON FALL 2013 REVISION CYCLE STANDARDS REPORT OF THE NFPA MOTIONS COMMITTEE* ON FALL 2013 REVISION CYCLE STANDARDS I. Introduction. This is the Motions Committee Report on Standards in the Fall 2013 Revision Cycle. The report identifies Certified

More information

Public Input No. 4-NFPA [ Section No. 4.2 ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

Public Input No. 4-NFPA [ Section No. 4.2 ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification Public Input No. 4-NFPA 214-2013 [ Section No. 4.2 ] 4.2 * Fire Risk Analysis. A fire risk analysis shall be conducted. The following are some of the factors that shall be considered in determining the

More information

Public Comment No. 7-NFPA 30A-2013 [ Section No ]

Public Comment No. 7-NFPA 30A-2013 [ Section No ] Page 1 of 13 Public Comment No. 7-NFPA 30A-2013 [ Section No. 6.4.2 ] 6.4.2 Additional Proposed Changes Each pump shall have installed on the discharge side a listed leak detection device that will provide

More information

FIRE DEPARTMENT CALLS AND FALSE ALARMS

FIRE DEPARTMENT CALLS AND FALSE ALARMS FIRE DEPARTMENT CALLS AND FALSE ALARMS One-Stop Data Shop Fire Analysis and Research Division National Fire Protection Association April 2008 National Fire Protection Association, 1 Batterymarch Park,

More information

DRAFT COMBINED POSTAL BALLOT/ AUSTRALIAN / NEW ZEALAND STANDARD FOR COMMENT

DRAFT COMBINED POSTAL BALLOT/ AUSTRALIAN / NEW ZEALAND STANDARD FOR COMMENT COMMITTEE: EL-002 Safety of Household and Similar Electrical Appliances and Small Power Transformers ATTENTION: Bev Harniss DR 18926 CP DRAFT COMBINED POSTAL BALLOT/ AUSTRALIAN / NEW ZEALAND STANDARD FOR

More information

Page 1 of 5 1/29/2016 4:08 PM. First Correlating Revision No. 3-NFPA [ Section No ] Submitter Information Verification

Page 1 of 5 1/29/2016 4:08 PM. First Correlating Revision No. 3-NFPA [ Section No ] Submitter Information Verification First Correlating Revision No. 3-NFPA 101-2016 [ Section No. 6.1.8.1.1 ] 6.1.8.1.1* Definition One- and Two-Family Dwelling Unit. A building that contains not more than two dwelling units, with independent

More information

Adobe Connect - Invitation to NFPA 385 Second Draft Web Conference

Adobe Connect - Invitation to NFPA 385 Second Draft Web Conference Matthews, Diane Subject: Location: Start: End: Show Time As: Recurrence: Meeting Status: Organizer: Required Attendees: Adobe Connect - Invitation to NFPA 385 Second Draft Web Conference http://nfpa.adobeconnect.com/rpbmeet/

More information

SUWANNEE RIVER WATER MANAGEMENT DISTRICT REQUEST FOR BID NO. 15/16-003AO FIRE ALARM SYSTEM INSTALLATION AND MONITORING.

SUWANNEE RIVER WATER MANAGEMENT DISTRICT REQUEST FOR BID NO. 15/16-003AO FIRE ALARM SYSTEM INSTALLATION AND MONITORING. SUWANNEE RIVER WATER MANAGEMENT DISTRICT REQUEST FOR BID NO. 15/16-003AO FIRE ALARM SYSTEM INSTALLATION AND MONITORING Table of Contents Section Title Page 1 Introduction 2 2 Proposed Schedule 2 3 Instructions

More information

MEMORANDUM. Technical Committee on Mercantile and Business Occupancies. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017)

MEMORANDUM. Technical Committee on Mercantile and Business Occupancies. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Mercantile and Business Occupancies

More information

PASCO COUNTY, FLORIDA

PASCO COUNTY, FLORIDA PASCO COUNTY, FLORIDA Bringing Opportunities Home June 3, 205 WEST PASCO GOVERNMENT CENTER PLANNING AND DEVELOPMENT DEPARTMENT 873 CITIZENS DRIVE, SUITE 230 NEW PORT RICHEY, FL 34654 TELEPHONE: (727) 847-832

More information

Loss Prevention Standard

Loss Prevention Standard Loss Prevention Standard LPS 1196: Issue 1.2 This Loss Prevention Standard is the property of BRE Global Ltd. and is made publicly available for information purposes only. Its use for testing, assessment,

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Residential Occupancies Kelly

More information

FISHER & PAYKEL HEALTHCARE CORPORATION LIMITED

FISHER & PAYKEL HEALTHCARE CORPORATION LIMITED DIVIDEND REINVESTMENT PLAN OFFER DOCUMENT 2015 1. Introduction This document (Offer Document) contains the terms and conditions of the Fisher & Paykel Healthcare Corporation Limited (Fisher & Paykel Healthcare)

More information

NFPA s Standards Development Process

NFPA s Standards Development Process NFPA s Standards Development Process Revision Cycle 104 weeks or 141 weeks Guiding Principles Due process Openness Lack of dominance Seek society s balance between: Acceptable risk Commitment of resources

More information

M E M O R A N D U M. The Technical Correlating Committee on Boiler and Combustion Systems Hazards

M E M O R A N D U M. The Technical Correlating Committee on Boiler and Combustion Systems Hazards M E M O R A N D U M TO: FROM: The Technical Correlating Committee on Boiler and Combustion Systems Hazards Jeanne Moreau DATE: June 22, 2010 SUBJECT: NFPA 85 TCC Report on Comments Letter Ballot (F10)

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Notification Appliances

More information

Purpose : Project Manager. Professional. Contractor: devices/system. compatibility

Purpose : Project Manager. Professional. Contractor: devices/system. compatibility I. Title: Fire Alarm Systems Design, Construction and Commissioning II. Purpose : Define activities, identify stakeholders, and assign responsibilities as it relates to the installation of fire alarm devices

More information

National Fire Protection Association M E M O R A N D U M. Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems

National Fire Protection Association M E M O R A N D U M. Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Testing and Maintenance

More information

Committee on NFPA 51A

Committee on NFPA 51A Committee on M E M O R A N D U M TO: FROM: NFPA Technical Committee on Industrial and Medical Gases Patti Mucci, Administrative Assistant DATE: May 6, 2010 SUBJECT: ROC Letter Ballot The ROC letter ballot

More information

Page 1 of 9 First Revision No. 2-NFPA 99B-2012 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 10, Standard for Portable

More information

Page 1 of 37 Public Input No. 1-NFPA 30A-2012 [ New Section after 1.1.2 ] 1.1.3 This code shall not apply to aircraft fuel dispensing facilities. NFPA 30A is commonly referenced, in my opinion, incorrectly,

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: NEC Code-Making Panel 15 FROM: Kimberly Shea DATE:

More information

An Analysis of Volunteer Firefighter Injuries,

An Analysis of Volunteer Firefighter Injuries, An Analysis of Volunteer Firefighter Injuries, 2009 2011 Michael J. Karter, Jr. Fire Analysis and Research Division National Fire Protection Association January 2013 National Fire Protection Association,

More information

NFPA 101 SAF-RES PUBLIC COMMENTS

NFPA 101 SAF-RES PUBLIC COMMENTS Page 134 of 195 Public Comment No. 3-NFPA 101-2013 [ Section No. 28.7.6.1 ] 28.7.6.1 New draperies, curtains, and other similar loosely hanging furnishings and decorations shall be flame resistant as demonstrated

More information

WORKING DRAFT OF COMMITTEE MEETING OUTPUT

WORKING DRAFT OF COMMITTEE MEETING OUTPUT WORKING DRAFT OF COMMITTEE MEETING OUTPUT CONTENT NOT FINAL SUBJECT TO REVISION PRIOR TO LETTER BALLOT AND PUBLICATION OF SECOND DRAFT REPORT Document: NFPA 221 Revision Cycle: A2014 Meeting Date: 5/20/2013

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Sprinkler System

More information

MEMORANDUM. Technical Committee on Notification Appliances for Fire Alarm and Signaling Systems

MEMORANDUM. Technical Committee on Notification Appliances for Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Notification Appliances for

More information

Title 24, Part 6 Certification of Economizer Fault Detection and Diagnostics (FDD)

Title 24, Part 6 Certification of Economizer Fault Detection and Diagnostics (FDD) Title 24, Part 6 Certification of Economizer Fault Detection and Diagnostics (FDD) Title 24, Part 6 Section 120.2(i) requires that economizer FDD functions be installed on air cooled unitary air conditioning

More information

HILLSIDE BUILDING COMMITTEE PLAN REVIEW DIRECTIONS

HILLSIDE BUILDING COMMITTEE PLAN REVIEW DIRECTIONS HILLSIDE BUILDING COMMITTEE PLAN REVIEW DIRECTIONS 1 1. Review Hillside Regulations to ensure your design is in conformance with current Town Code. 2. Complete page 3 and contact Paul Mood at 480-348-3573,

More information

Egress Window. Requirements for Building Permit Application

Egress Window. Requirements for Building Permit Application Egress Window Requirements for Building Permit Application 1. Completed Building Permit application form with signature. 2. Submit two (2) copies of plans showing proposed designs and materials; plans

More information

FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE COMMITTEE

FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE COMMITTEE FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE COMMITTEE MEMORANDUM TO: FROM: NFPA 30 Technical Committee on Storage and Warehousing of Containers and Portable Tanks R. P. Benedetti DATE: September 16, 2010 SUBJECT:

More information

SAFETY CODES COUNCIL ORDER. BEFORE THE FIRE TECHNICAL COUNCIL On June 21, 2012

SAFETY CODES COUNCIL ORDER. BEFORE THE FIRE TECHNICAL COUNCIL On June 21, 2012 SAFETY CODES COUNCIL #1000, 10665 Jasper Avenue N.W., Edmonton, Alberta, Canada, T5J 389 Tel: 780-413-0099 I 1-888-413-0099 Fax: 780-424-5134 I 1-888-424-5134 www.safetycodes.ab.ca COUNCIL ORDER No. 0015423

More information

COUNTY COUNCIL OF PRINCE GEORGE'S COUNTY, MARYLAND SITTING AS THE DISTRICT COUNCIL 2010 Legislative Session. Council Members Dernoga and Olson

COUNTY COUNCIL OF PRINCE GEORGE'S COUNTY, MARYLAND SITTING AS THE DISTRICT COUNCIL 2010 Legislative Session. Council Members Dernoga and Olson DR- COUNTY COUNCIL OF PRINCE GEORGE'S COUNTY, MARYLAND SITTING AS THE DISTRICT COUNCIL 00 Legislative Session Bill No. CB--00 Chapter No. Proposed and Presented by Introduced by Co-Sponsors The Chairman

More information

NEC ROP/ROC Code Making Panel Meetings

NEC ROP/ROC Code Making Panel Meetings Phoenix AZ - December 4-16 2000 Log # 2367 2-64 - ( 210-8(b)(3) ): SUBMITTER: Monte R. Ewing State of Wisconsin The panel reaffirms its action and statement on Proposal 2-81. There is no supporting data

More information

Errata ANSI Z223.1 National Fuel Gas Code 2015 Edition

Errata ANSI Z223.1 National Fuel Gas Code 2015 Edition Errata ANSI Z223.1 National Fuel Gas Code 2015 Edition Reference: Various Errata Z223.1-2015-1 Issue Date: 3/10/16 National Fuel Gas Code user: The American Gas Association (AGA) notes the following errors

More information

Australian Standard. Degrees of protection provided by enclosures (IP Code) AS IEC Ed 2.1:2001 AS 60529

Australian Standard. Degrees of protection provided by enclosures (IP Code) AS IEC Ed 2.1:2001 AS 60529 AS 60529 2004 IEC 60529 Ed 2.1:2001 AS 60529 Australian Standard Degrees of protection provided by enclosures (IP Code) This Australian Standard was prepared by Committee EL-026, Protective Enclosures

More information

Policy for safe working on Fire Alarm Systems at Loughborough University and Loughborough University in London

Policy for safe working on Fire Alarm Systems at Loughborough University and Loughborough University in London Policy for safe working on Fire Alarm Systems at Loughborough University and Loughborough University in London Scope of document General This document sets out the procedure for the management and control

More information

FALSE ALARM ACTIVITY IN THE U.S. 2012

FALSE ALARM ACTIVITY IN THE U.S. 2012 FALSE ALARM ACTIVITY IN THE U.S. 2012 Michael J. Karter, Jr. December 2013 National Fire Protection Association Fire Analysis and Research Division Abstract In 2012, U.S. fire departments responded to

More information

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing. 9/20/2016 2:27 PM Second Revision No. 5006-NFPA 101-2016 [ Section No. 3.3.56 ] 3.3.56 Delayed Action Closer. Self-closing device that incorporates a delay prior to the initiation of closing. Mechanical

More information

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016)

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Solvent Extraction Plants

More information

Avigilon Control Center System Integration Guide

Avigilon Control Center System Integration Guide Avigilon Control Center System Integration Guide with Velocity INT-HIRSCH-A-Rev3 Copyright 2013 Avigilon. All rights reserved. No copying, distribution, publication, modification, or incorporation of this

More information

TEXAS CHAPTER AMERICAN SOCIETY OF LANDSCAPE ARCHITECTS 2019 PROFESSIONAL AWARDS GUIDELINES

TEXAS CHAPTER AMERICAN SOCIETY OF LANDSCAPE ARCHITECTS 2019 PROFESSIONAL AWARDS GUIDELINES TEXAS CHAPTER AMERICAN SOCIETY OF LANDSCAPE ARCHITECTS 2019 PROFESSIONAL AWARDS GUIDELINES The Texas Chapter of the American Society of Landscape Architects invites, from the Chapter membership, submission

More information

NFPA 79 - Second Draft Meeting July 8-10, DoubleTree Hotel, Portland, ME

NFPA 79 - Second Draft Meeting July 8-10, DoubleTree Hotel, Portland, ME National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org AGENDA NFPA TECHNICAL COMMITTEE ON ELECTRICAL EQUIPMENT OF INDUSTRIAL

More information

Design Review Commission Report

Design Review Commission Report City of Beverly Hills Planning Division 455 N. Rexford Drive Beverly Hills, CA 90210 TEL. (310) 285-1141 FAX. (310) 858-5966 Design Review Commission Report Meeting Date: Thursday, March 2, 2017 Subject:

More information