First Revision No. 158-NFPA [ Global Input ] Submitter Information Verification. Committee Statement

Size: px
Start display at page:

Download "First Revision No. 158-NFPA [ Global Input ] Submitter Information Verification. Committee Statement"

Transcription

1 of /21/2013 1:03 PM First Revision No. 158-NFPA [ Global Input ] Revise to update UL 864 to "2003, revised 2012" and upate ANSI/ASME A17 to Submittal Date: Wed Sep 11 11:08:52 EDT 2013 : Updated references used in SIG-PRO chapters

2 1 of /21/2013 1:03 PM First Revision No. 124-NFPA [ Section No ] * Emergency Control Functions. Building, fire, and emergency control elements or systems that are initiated by the fire alarm or emergency communications signaling system and either increase the level of life safety for occupants or control the spread of the harmful effects of fire or other dangerous products. (SIG-PRO) Submittal Date: Tue Sep 10 08:33:19 EDT 2013 The change makes the definition more generic to allow other NFPA documents (such as NFPA 720) to extract the definition. Public Input No. 284-NFPA [Section No ]

3 4 of /21/2013 1:03 PM First Revision No. 220-NFPA [ Section No ] * Dedicated Function Fire Alarm Control Unit. A protected premises fire alarm control unit which that is intended to provide operation of a operate specifically identified emergency control function(s). (SIG-PRO) Submittal Date: Wed Sep 18 15:23:40 EDT 2013 A dedicated function control unit can be used for multiple dedicated functions. The change cleans up the ambiguity in the current language. Public Input No. 177-NFPA [Section No ]

4 9 of /21/2013 1:03 PM First Revision No. 151-NFPA [ Section No ] Low-Power Radio Transmitter. /Transceiver. Any device that communicates with associated control/receiving equipment or other transceivers by low-power radio signals. (SIG-PRO) Submittal Date: Wed Sep 11 09:13:59 EDT 2013 Wireless systems incorporate two-way communications. The terms transceiver added to reflect the two-way aspect of this communication.

5 9 of /21/2013 1:03 PM First Revision No. 127-NFPA [ New Section after ] Performance-based design documentation for signaling line circuit zoning shall be in accordance with and (SIG-PRO) Submittal Date: Tue Sep 10 09:18:07 EDT 2013 The text provides the link to sections and where documentation is required when designing a fire alarm system with signaling line circuit zoning. See FR 120 and 121. Public Input No. 365-NFPA [New Section after ]

6 27 of /21/2013 1:03 PM First Revision No. 89-NFPA [ Section No ] The designation of the pathways shall be permitted to also include the performance of the pathway (interconnection) to survivability from attack by fire. Submittal Date: Mon Sep 09 10:01:14 EDT 2013 The purpose of this change is to eliminate potential conflicts between sections and Also see FR 211. Public Input No. 195-NFPA [Section No ]

7 28 of /21/2013 1:03 PM First Revision No. 92-NFPA [ Section No ] All non-power-limited and power-limited signaling system circuits entering a building shall be provided with transient protection. (SIG-FUN) Submittal Date: Mon Sep 09 11:25:18 EDT 2013 This new requirement added in 2013 is incomplete, unclear and potentially dangerous. The NEC recognizes that not all outside circuits require special transient suppression. There are two reasons for this. The first is that not all circuits that enter or exit a building are prone to lightning or other surge events. Therefore, the NEC qualifies which circuits require transient protection. The second reason that not all circuits that enter or exit a building are required to have transient protection is that adding surge suppression can actually attract lightning if not properly installed and may actually defeat protection that is built into the control units. Listing requirements for control panels already require some measure of transient protection for all circuits. Where additional transient protection is installed on both ends of a circuit which extends between two buildings, unless the grounding is to the same point or at the same potential there will be ground loops that will attract surges and damage systems. Additional transient protection beyond that required by the product listing should only be required in areas that are prone to lightning - as already required by the NEC. In addition, the requirement does not specify whether the transient protection should be of the parallel type or the serial type, which affects whether the circuit will continue to operate upon catastrophic failure of the protection device. For example, in most cases a parallel type should be used for initiating device circuits and signaling line circuits. This will permit those circuits to continue to operate if the device has been destroyed by the first strike. This can be important if that same lightning strike actually started a fire which could be detected if the detection or signaling circuit continued to operate. If a serial type had been used, the circuit might no longer be operational and would fail to detect the fire even though the panel would be protected against a second potential strike. There is a lot more thought, planning and design needed to properly specify transient protection. This 2013 requirement goes beyond the minimum requirements of a code or standard such as NFPA 72. NFPA 72 already requires compliance with the appropriate sections of the NEC. Public Input No. 514-NFPA [Section No ]

8 29 of /21/2013 1:03 PM First Revision No. 156-NFPA [ New Section after ] * Where operational capability is required to be maintained or continued during the application of a fault, the operational capability required in Section and shall be restored within 200 seconds from the time the fault is introduced. Supplemental Information File Name A _for_FR_156_EC_edits.docx Description Submittal Date: Wed Sep 11 10:38:55 EDT 2013 Paragraphs , (2), (4), (4), (2), (3), (4), and (6) require operational capability to be maintained or continued during the application of various identified faults single open, single ground, wire to wire (short) etc. This is to clarify when the operational capability is to begin after the introduction of the fault condition. The issue is the application of two events fault and alarm in rapid succession. The Code permits each event to have a different response time. Faults = 200 s and alarms = 10 s. Because a fault affects the circuit performance until detected and the circuit is automatically reconfigured, this is a hardware issue rather than just a software issue. Systems technology needed to process these two events in the order of occurrence. Where a fault is applied first, the system is permitted up to 200 s to detect and automatically reconfigure. Any alarm applied after 200 s is required to be annunciated and to actuate required signals within 10 s. This is a minimum requirement and systems may process the signals faster. The change will correlate with proposed changes to ANSI/UL 864. This change also adds new annex material - A

9 A In the event of an introduction of a fault and subsequent alarm condition, operational ability should be restored within 200 seconds, and the alarm condition received at the fire alarm control unit is to be within 10 seconds after the expiration of the 200 seconds. Any subsequent alarms initiated after the initial 200 second window should be actuated in accordance with Section and

10 30 of /21/2013 1:03 PM First Revision No. 107-NFPA [ Section No [Excluding any Sub-Sections] ] Pathways shall be designated as Class A, Class B, Class C, Class D, Class E, Class N, or Class X, depending on their performance. Submittal Date: Mon Sep 09 15:58:55 EDT 2013 : Class N circuits were added to this section under FR 99.

11 31 of /21/2013 1:03 PM First Revision No. 96-NFPA [ Section No ] * Class C. A pathway shall be designated as Class C when it performs as follows: (1) It includes one or more pathways where operational capability is verified via end-to-end communication, but the integrity of individual paths is not monitored. (2) A loss of end-to-end communication is annunciated as a trouble signal. Submittal Date: Mon Sep 09 12:28:00 EDT 2013 The purpose of this change is to clarify that section requires a trouble signal and make it consistent with the other paragraphs in this section. Public Input No. 196-NFPA [Section No ]

12 32 of /21/2013 1:03 PM First Revision No. 99-NFPA [ New Section after ] Global FR-101 Hide Deleted Global FR-103 Hide Deleted Class N. Global FR-103 Hide Deleted Global FR-101 Hide Deleted Global FR-103 Hide Deleted A pathway shall be designated as Class N when it performs as follows: Global FR-103 Hide Deleted (1) * It includes two or more pathways where operational capability of the primary pathway and a redundant pathway to each device shall be verified through end-to-end communication. Exception: When only one device is served, only one pathway shall be required. (2) A loss of intended communications between endpoints shall be annunciated as a trouble signal. (3) A single open, ground, short, or combination of faults on one pathway shall not affect any other pathway. (4)* Conditions that affect the operation of the primary pathway(s) and redundant pathway(s) shall be annunciated as a trouble signal when the system s minimal operational requirements cannot be met. (5) * Primary and redundant pathways shall not be permitted to share traffic over the same physical segment. Submittal Date: Mon Sep 09 14:06:18 EDT 2013 Questions concerning the acceptability of using Ethernet and other non-fire or non-mns networks for fire alarm and signaling systems applications are being raised more and more. Because of these questions and the rapidly changing technology, the Task Group on Networks in FA/ECS was formed by the Correlating to address the risk analysis, design, application, installation, and performance of networks and networking equipment used in fire alarm systems, fire EVACS and mass notification systems. This change is a result of that effort. Some of the concerns that were raised during related discussions for the 2013 edition included: ground detection, system management, availability, and software control. Also see FR 101 and FR 103 for related annex material and associated figures.

13 33 of /21/2013 1:03 PM Public Input No. 270-NFPA [New Section after ]

14 34 of /21/2013 1:03 PM First Revision No. 105-NFPA [ Section No ] * Global FR-106 Hide Deleted Global FR-106 Hide Deleted Class A, Class N, and Class X circuits using physical conductors (e.g., metallic, optical fiber) shall be installed such so that the primary and redundant, or outgoing and return conductors, exiting from and returning to the control unit, respectively, are routed separately. The outgoing and return (redundant) circuit conductors shall be permitted in the same cable assembly (i.e., multi-conductor multiconductor cable), enclosure, or raceway only under the following conditions: (1) For a distance not to exceed 10 ft (3.0 m) where the outgoing and return conductors enter or exit the initiating device, notification appliance, or control unit enclosures (2) For single raceway drops Single drops installed in raceway to individual devices or appliances (3)* For single raceway drops to multiple devices or appliances installed within In a single room not exceeding 1000 ft 2 (93 m 2 ) in area, a drop installed in raceway to multiple devices or appliances that does not include any emergency control function devices Submittal Date: Mon Sep 09 15:15:25 EDT 2013 Changes are made for clarity. Class N circuits were added to correlate with other FRs. Sections (3) now excludes primary and secondary conductors to emergency control function devices from being permitted in the same cable assembly, enclosure or raceway. Changes to subparagraphs (2) and (3) were made to clarify the intent that only single drops in raceway are acceptable. Where a circuit enters a room that contains emergency control function interface devices (i.e., control modules/relays connected to and programmed to shutdown HVAC units and other fire and life safety control functions), loss of both "legs" of this circuit could disable important fire and life safety control functions that might be essential for prevention of circulation of smoke or some other required operation, such as elevator recall functions.

15 First Revision No. 212-NFPA [ Section No ] 12.4* Pathway Survivability. All pathways shall comply with NFPA 70, National Electrical Code Pathway Survivability Level 0. Level 0 pathways shall not be required to have any provisions for pathway survivability Pathway Survivability Level 1. Pathway survivability Level 1 shall consist of pathways in buildings that are fully protected by an automatic sprinkler system in accordance with NFPA 13, Standard for the Installation of Sprinkler Systems, with any interconnecting conductors, cables, or other physical pathways installed in metal raceways * Pathway Survivability Level 2. Pathway survivability Level 2 shall consist of one or more of the following: (1) 2-hour fire-rated circuit integrity (CI) or fire-resistive cable (2) 2-hour fire-rated cable system [electrical circuit protective system(s)] (3) 2-hour fire-rated enclosure or protected area (4)* 2-hour performance Performance alternatives approved by the authority having jurisdiction Pathway Survivability Level 3. Pathway survivability Level 3 shall consist of pathways in buildings that are fully protected by an automatic sprinkler system in accordance with NFPA 13, Standard for the Installation of Sprinkler Systems, and one or more of the following: (1) 2-hour fire-rated circuit integrity (CI) or fire-resistive cable (2) 2-hour fire-rated cable system [electrical circuit protective system(s)] (3) 2-hour fire-rated enclosure or protected area (4)* 2-hour performance Performance alternatives approved by the authority having jurisdiction Supplemental Information File Name Annex_Material_for_FR_212.EC_edits docx Description Submittal Date: Wed Sep 18 11:36:03 EDT 2013 There is no intention to recommend a certain hierarchical ranking. Also text has been revised to indicate that any performance analysis accepted by the AHJ is acceptable in lieu of the prescriptive requirements for level 2 and 3. Annex material has been added to further clarify these issues. 35 of /21/2013 1:03 PM

16 A.12.4 The intent of the pathway survivability designation is to provide options for the protection of the pathway circuits and not to create a hierarchical ranking. Other chapters within NFPA 72 or other codemaking jurisdictions can select the survivability option that best meets their needs. A Methods of survivability protection might alternate within a protected premise. For example, 2 hour resistive cable might extend from a 2 hour fire rated enclosure. A (4) A performance based alternative is needed because it is possible to construct a nonsprinklered, Type V(000) building that employs relocation or partial evacuation (e.g., a single story ambulatory health care occupancy) that would not warrant either a 2 hour fire resistance rated enclosure or 2 hour cable. Examples of performance alternatives that might be considered in a design for survivability are a strategic application of Class A, Class X, or Class N segments and also wireless communication pathways. A (4) A performance based alternative is needed because it is possible to construct a sprinklered single story Type V(111) or multistory Type II(111) building that employs relocation or partial evacuation (e.g., a health care occupancy) that would not warrant either a 2 hour fire resistance rated enclosure or 2 hour cable (a 1 hour enclosure would suffice). Examples of performance alternatives that might be considered in a design for survivability are a strategic application of Class A, Class X, or Class N segments and also wireless communication pathways.

17 37 of /21/2013 1:03 PM First Revision No. 213-NFPA [ Section No ] Unless otherwise permitted or required by through and by through , all means of interconnecting equipment, devices, and appliances and wiring connections shall be monitored for the integrity of the interconnecting conductors or equivalent path so that the occurrence of a single open or a single ground-fault condition in the installation conductors or other signaling channels is automatically indicated within 200 seconds. Submittal Date: Wed Sep 18 13:22:59 EDT 2013 Several of the classes defined allow for operation without monitoring for some of the faults. The changes in this paragraph make it consistent with those paragraphs.

18 38 of /21/2013 1:03 PM First Revision No. 111-NFPA [ Section No ] Unless otherwise permitted or required by through and by through , all means of interconnecting equipment, devices, and appliances and wiring connections shall be monitored for the integrity of the interconnecting conductors or equivalent path so that the restoration to normal of a single open or a single ground-fault condition in the installation conductors or other signaling channels is automatically indicated within 200 seconds. (SIG-FUN) Submittal Date: Mon Sep 09 17:11:30 EDT 2013 Several of the classes defined allow for operation without monitoring for some the faults. The changes in this paragraph make it consistent with those paragraphs. Public Input No. 199-NFPA [Section No ]

19 39 of /21/2013 1:03 PM First Revision No. 112-NFPA [ Section No ] Monitoring for integrity shall not be required for central station circuits serving notification appliances within a central station. Submittal Date: Mon Sep 09 17:15:36 EDT 2013 : All fire alarms system notification appliance circuits should be monitored for integrity. Public Input No. 322-NFPA [Section No ]

20 40 of /21/2013 1:03 PM First Revision No. 214-NFPA [ Section No ] Monitoring for integrity of the installation conductors for a ground-fault condition shall not be required for the communications and transmission channels extending from a supervising station to a subsidiary station(s) or protected premises, or both, that comply with the requirements of Chapter 26 and are electrically isolated from the fire alarm system (or circuits) by a transmitter(s), provided that a single ground-fault condition does not affect the required operation of the fire alarm system and/or signaling system. Submittal Date: Wed Sep 18 13:35:30 EDT 2013 This change cleans up the wording of to clarify the meaning and eliminate redundant requirements. Public Input No. 200-NFPA [Section No ]

21 41 of /21/2013 1:03 PM First Revision No. 114-NFPA [ Section No ] Where two or more systems are interconnected, the systems shall be connected using Class A, B, N, or X circuits as described in Section Submittal Date: Mon Sep 09 17:30:36 EDT 2013 Class N circuits were added under other FRs and are acceptable for this type of application. Public Input No. 277-NFPA [Section No ]

22 42 of /21/2013 1:03 PM First Revision No. 211-NFPA [ Section No ] 12.7* Nomenclature. Global FR-91 Hide Deleted Global FR-91 Hide Deleted To The following nomenclature shall be used to identify the required properties of the system(s) interconnections and survivability requirements, the following identification nomenclature shall be used : (1) System(s) interconnections (2) Survivability levels (not required if Level 0) (3) Shared pathway levels (not required if Level 0) Submittal Date: Tue Sep 17 11:47:03 EDT 2013 The purpose of this change is to clean up the wording of 12.7 and include the optional language formerly found in Also see FR 89. Public Input No. 201-NFPA [Section No. 12.7]

23 First Revision No. 222-NFPA [ Section No ] 21.1* Application. The provisions of Chapter 21 shall cover the minimum requirements and methods for emergency control function interfaces to fire alarm systems and emergency communications systems in accordance with this chapter The requirements of Chapters 7, 10, 17, 18, 23, 24, and 26 shall also apply, unless they are in conflict with this chapter The requirements of Chapter 14 shall apply The requirements of this chapter shall not apply to Chapter 29 unless otherwise noted stated. Supplemental Information File Name Figure_for_FR_222_Integrated_Systems_rev_5_.png A.21.1_text_for_FR_222.EC_edits.docx Description Submittal Date: Wed Sep 18 16:05:09 EDT 2013 New Annex text introduces the concepts of individual systems and integrated systems. The proposed figure is a revision of one that has made it through the first draft of NFPA 4. Although NFPA 4 is not yet been approved as a standard it is in cycle one year ahead of NFPA 72. It will be voted on before NFPA 72 technical committees second draft meetings. It is easier to put in the reference now and make adjustments later than it would be to do the opposite. New A.21.1 is also added (see attached). Public Input No. 566-NFPA [Section No. 21.1] 66 of /21/2013 1:03 PM

24 A.21.1 Fire alarm systems, signaling systems, and emergency communications systems are often part of a large, integrated system serving a building or area. Figure A.21.1 shows examples of individual systems that might be part of an integrated system. A fire alarm system might monitor the status of one of the other individual systems or provide a form of output to control another individual system, such as a smoke control system or an elevator controller. In some cases, the fire alarm system shares information and control in two directions with another individual system. NFPA 72 covers only the fire alarm or signaling system in the circuits powered by it, not any part of the other individual systems. See NFPA 4, Standard for Integrated Fire Protection and Life Safety System Testing, for additional information on integrated systems.

25

26 67 of /21/2013 1:03 PM First Revision No. 223-NFPA [ Section No ] The installation wiring between the fire alarm control unit and the emergency control function interface device shall be Class A, Class B, Class N, Class D, or Class X in accordance with Chapter 12. Submittal Date: Thu Sep 19 07:53:38 EDT 2013 : The change is made to add Class N to the list of classes. See FR 99. Public Input No. 278-NFPA [Section No ]

27 of /21/2013 1:03 PM First Revision No. 224-NFPA [ Global Input ] Revise the title of 21.3 to read: "Elevator Phase I Emergency Recall Operation." Submittal Date: Thu Sep 19 07:58:02 EDT 2013 The change is made to correlate with the terminology changes made in FRs affecting 21.3 sub-paragraphs.

28 68 of /21/2013 1:03 PM First Revision No. 225-NFPA [ Section No ] All fire alarm initiating devices used to initiate fire fighters service recall elevator Phase I Emergency Recall Operation shall be connected to the required building fire alarm system. Submittal Date: Thu Sep 19 08:06:07 EDT 2013 This change corrects the inconsistencies in the language between NFPA 72 and ASME A17.1. Public Input No. 65-NFPA [Section No ]

29 69 of /21/2013 1:03 PM First Revision No. 226-NFPA [ Section No ] * In facilities without a required building fire alarm system, fire alarm initiating devices used to initiate fire fighters' service recall elevator Phase 1 Emergency Recall Operation shall be connected to either a nonrequired building fire alarm system or a dedicated function fire alarm control unit that shall be designated as elevator recall control and supervisory control unit, permanently identified on the dedicated function fire alarm control unit and on the record drawings. Submittal Date: Thu Sep 19 08:12:10 EDT 2013 The revised text will allow fire alarm initiating devices to be connected to either the dedicated function fire alarm control unit or to a non-required building fire alarm control unit. Public Input No. 81-NFPA [Section No ]

30 70 of /21/2013 1:03 PM First Revision No. 227-NFPA [ Section No ] Unless otherwise required by the authority having jurisdiction, only the elevator lobby, elevator hoistway, and elevator machine room, elevator control room, and elevator control space smoke detectors, or other automatic fire detection as permitted by , shall be used to recall elevators for fire fighters service initiate elevator Phase I Emergency Recall Operation. Exception: A waterflow switch shall be permitted to initiate elevator recall Phase I Emergency Recall Operation upon activation of a sprinkler installed at the bottom of the elevator hoistway (the elevator pit), provided the waterflow switch and pit sprinkler are installed on a separately valved sprinkler line dedicated solely for protecting the elevator pit, and the waterflow switch is provided without time-delay capability. Submittal Date: Thu Sep 19 08:20:53 EDT 2013 This change correlates terminology used in NFPA 72 to be consistent with that used in the referenced published edition of ASME A17.1. Public Input No. 193-NFPA [Section No ]

31 71 of /21/2013 1:03 PM First Revision No. 138-NFPA [ New Section after ] Fire Alarm Initiating Device(s) Inside Elevator's Hoistway. Fire alarm initiating device(s) required to be installed inside an elevator's hoistway by other sections of this Code or by other codes and standards shall be required to be accessible for repair, service, testing, and maintenance from outside the elevator's hoistway. Submittal Date: Tue Sep 10 15:15:21 EDT 2013 In California, the Elevator Safety Order has a requirement that all hoistway FAIDs must be accessible from outside the hoistway. However, this requirement only applies in the State of California but it is not a national code requirement. This will significantly reduce the life-safety risk for FA installers and service personnel, and cost to owners due to the great deal of required coordination Public Input No. 221-NFPA [New Section after ]

32 72 of /21/2013 1:03 PM First Revision No. 228-NFPA [ Section No ] Smoke detectors shall not be installed in unsprinklered elevator hoistways unless they are installed to activate the elevator hoistway smoke relief equipment. or to protect elevator control spaces or elevator machinery spaces as required in (2) and (2). Submittal Date: Thu Sep 19 08:37:52 EDT 2013 This change was for correlation with the requirements in ASME A17.1. Because of new technology, elevator machinery and elevator control spaces can now be located in elevator hoistways and as such, smoke detectors, or other automatic fire detection as permitted by would be required in the hoistway. Public Input No. 53-NFPA [Section No ]

33 73 of /21/2013 1:03 PM First Revision No. 229-NFPA [ Section No ] * If ambient conditions prohibit installation of automatic smoke detection used to initiate elevator Phase I Emergency Recall Operation, other automatic fire detection initiating devices shall be permitted. Submittal Date: Thu Sep 19 08:45:00 EDT 2013 : This change clarifies this section and to be consistent with ASME A17.1. Public Input No. 249-NFPA [Section No ]

34 74 of /21/2013 1:03 PM First Revision No. 140-NFPA [ Section No ] When actuated, any detector fire alarm initiating device that has initiated fire fighters recall elevator Phase 1 Emergency Recall Operation shall also be annunciated at the building fire alarm control unit, or other at the fire alarm control unit as described in , and at required remote annunciators. Submittal Date: Tue Sep 10 15:59:54 EDT 2013 The term "and at any required remote annunciators" was vague and removed for clarity. Terms were changed to be consistent with the terms used in ASME A17.1. Public Input No. 250-NFPA [Section No ]

35 75 of /21/2013 1:03 PM First Revision No. 157-NFPA [ Section No ] Actuation from the elevator hoistway, elevator machine room, elevator machinery space, elevator control space, or elevator control room smoke detectors, or other automatic fire detection as permitted by , shall cause separate and distinct visible annunciation at the building fire alarm control unit, or at the fire alarm control unit described in , and at required annunciators to alert fire fighters and other emergency personnel that the elevators are no longer safe to use. Submittal Date: Wed Sep 11 10:57:06 EDT 2013 The phrase "and at required annunciators" is removed to be consistent with the action on FR 140.

36 76 of /21/2013 1:03 PM First Revision No. 141-NFPA [ Section No [Excluding any Sub-Sections] ] Global FR-142 Hide Deleted Separate outputs from the building fire alarm systems control unit or the fire alarm control unit described in to the elevator controller(s) shall be provided to implement elevator Phase I Emergency Recall Operation in accordance with Section 2.27 of ANSI/ASME A17.1/CSA B44, Safety Code for Elevators and Escalators, as required in through Submittal Date: Tue Sep 10 16:58:24 EDT 2013 : This change correlates and Public Input No. 260-NFPA [Section No [Excluding any Sub-Sections]]

37 77 of /21/2013 1:03 PM First Revision No. 230-NFPA [ Section No ] Designated Level Recall. For each elevator or group of elevators, an output shall be provided to signal elevator recall to the designated level in response to the following: (1) Activation of smoke detectors, or other automatic fire detection as permitted by , located at any elevator lobby served by the elevator(s) other than the lobby at the designated level (2) Activation of smoke detectors, or other automatic fire detection as permitted by , located at any elevator machine room, elevator machinery space, elevator control space, or elevator control room serving the elevator(s), except where such rooms or spaces are located at the designated level (3) Activation of smoke detectors, or other automatic fire detection as permitted by , located in the elevator hoistway serving the elevator where sprinklers or elevator control spaces or elevator machinery spaces are located in the hoistway, unless otherwise specified in (3) Submittal Date: Thu Sep 19 08:59:20 EDT 2013 This change for correlation with the requirements in ASME A17.1. Because of new technology, elevator machinery and elevator control spaces can now be located in elevator hoistways and as such, smoke detectors, or other automatic fire detection as permitted by would be required in the hoistway. Public Input No. 54-NFPA [Section No ]

38 78 of /21/2013 1:03 PM First Revision No. 231-NFPA [ Section No ] * Visual Warning. For each elevator or group of elevators, an output(s) shall be provided to the elevator controller for the purpose of causing the elevator visual warning signal to operate in response to the following: (1) Activation of the elevator machine room, elevator machinery space, elevator control space, or elevator control room initiating devices identified in (2) or (2) (2) Activation of the elevator hoistway initiating devices identified in (3) or (3) Submittal Date: Thu Sep 19 11:26:49 EDT 2013 : This change clarifies the purpose of the output signal to the elevator controller. Public Input No. 274-NFPA [Section No ]

39 79 of /21/2013 1:03 PM First Revision No. 232-NFPA [ Section No ] * Control circuits to shut down elevator power shall be monitored for the presence of operating voltage. Loss of voltage to the control circuit for the disconnecting means shall cause a supervisory signal to be indicated at the building fire control unit and required remote annunciators or at the control unit described in Submittal Date: Thu Sep 19 11:32:45 EDT 2013 The term "and at any required remote annunciators" was vague and removed for clarity. The revised text will require the loss of voltage to be reported at the either the dedicated function fire alarm control unit or to a non-required building fire alarm control unit. Public Input No. 283-NFPA [Section No ]

40 80 of /21/2013 1:03 PM First Revision No. 233-NFPA [ Section No ] * If connected to the fire alarm system serving the protected premises, all detection devices used to cause the operation of HVAC systems, smoke dampers, fire dampers, fan control, smoke doors, and or fire doors shall be monitored for integrity in accordance with and Section Submittal Date: Thu Sep 19 11:51:21 EDT 2013 Changes are made for grammatical correction to the compound sentence, and deletion of reference to Section which is not relevant to the paragraph/requirement. Public Input No. 373-NFPA [Section No ]

41 81 of /21/2013 1:03 PM First Revision No. 234-NFPA [ Section No ] All door and shutter hold-open release and integral door and shutter release and closure devices used for release service shall be monitored for integrity in accordance with Section Exception: Pathways installed as Class D circuits in accordance with Submittal Date: Thu Sep 19 13:08:00 EDT 2013 The reference to 21.2 was changed to 12.6 in order to appropriately reference requirements for performance. The exception clarifies that a fail safe installation is permitted. Public Input No. 359-NFPA [Section No ]

42 82 of /21/2013 1:03 PM First Revision No. 235-NFPA [ Section No ] For all means of egress doors connected in accordance with where secondary power supplies of fire alarm control unit batteries units are used, they shall comply with Submittal Date: Thu Sep 19 13:14:22 EDT 2013 The term fire alarm control unit batteries is misleading (battery as group of devices). It should be made clear here that the second power supply of the FACU is meant. A second power supply could also come from a separate emergency power supply, a fuel cell or other independent sources. Public Input No. 367-NFPA [Section No ]

43 83 of /21/2013 1:03 PM First Revision No. 236-NFPA [ Section No ] * Fire Secondary power supplies of fire alarm control unit batteries units shall not be utilized to maintain means of egress doors in the locked condition unless the fire alarm control unit is arranged with circuitry and sufficient secondary power to ensure that the means of egress doors will unlock within 10 minutes of loss of primary power. Submittal Date: Thu Sep 19 13:18:47 EDT 2013 The term fire alarm control unit batteries is misleading (battery as group of devices). It should be made clear here that the second power supply of the FACU is meant. A second power supply could also come from a separate emergency power supply, a fuel cell or other independent sources. Public Input No. 368-NFPA [Section No ]

44 84 of /21/2013 1:03 PM First Revision No. 128-NFPA [ Section No [Excluding any Sub-Sections] ] A record of installed software and firmware version numbers shall be maintained at the location of the fire alarm control unit. prepared and maintained in accordance with Sections 7.5 and 7.7. Submittal Date: Tue Sep 10 09:25:38 EDT 2013 Documentation requirements for NFPA 72 are located in Chapter 7. The revised language in section will require the software and firmware versions to be documented and retained in accordance with Chapter 7. Specifically, section 7.5 outlines the requirements for Completion Documentation and 7.7 the requirements for Records, Records Retention, and Records Maintenance. Public Input No. 624-NFPA [Section No [Excluding any Sub-Sections]]

45 6 of /21/2013 1:03 PM First Revision No. 365-NFPA [ Global Input ] 23.6 The assignment of class designations to signaling line circuits shall be based on their performance capabilities under abnormal (fault) conditions in accordance with the requirements for Class A, Class B, Class N, or Class X pathways specified in Chapter 12. Submitter Full Name: Lee Richardson Organization: National Fire Protection Assoc Submittal Date: Mon Nov 18 14:33:07 EST 2013 The proposed Class N pathways will address the issue of Ethernet being utilized for signaling line circuits in fire alarm and signaling systems. Public Input No. 279-NFPA [Section No [Excluding any Sub-Sections]]

46 7 of /21/2013 1:03 PM First Revision No. 366-NFPA [ Global Input ] * A single fault on a pathway connected to the addressable devices shall not cause the loss of the devices in more than 50 addressable devices one zone. Supplemental Information File Name A _for_FR_237.docx Description Updated annex text Submitter Full Name: Lee Richardson Organization: National Fire Protection Assoc Submittal Date: Mon Nov 18 14:48:19 EST 2013 The change was made to migrate away from a maximum of 50-devices to limiting the loss of devices to one zone because 50-devices is not appropriate for all applications. The annex material gives additional guidance on how to approach the zoning of the system during the design stage. Annex A material is also revised - see attached.

47 A The intent of applies to both short-circuit faults and open-circuit faults. Fire alarm and signaling system communications technologies have evolved to the point that SLCs are now the prevalent means of monitoring initiation devices, controlling output devices, and communicating between panels, annunciators, and controllers. The extent of coverage of traditional IDCs is inherently limited based on the quantity of powered initiation devices or code limitations. Similarly, the extent and coverage of NACs also are limited by the power required to operate the devices. SLCs, unlike IDCs and NACs, have few limitations, and it is now common that a single SLC can monitor and control more than 250 devices. In addition, a single SLC can be the only pathway by which alarms are initiated, emergency control functions are controlled, and audible and visual notification appliances are activated. A total catastrophic failure of a fire alarm and life safety system due to a single open or short on an SLC can negate most, if not all, of this Code s requirements for specifying an acceptable minimum level of performance and reliability for the protection of life and property from fire. Designers should carefully consider the potential that a single SLC short or open caused by a fire or inadvertent damage to the SLC could disable an entire SLC prior to the activation of an alarm condition along with the subsequent alarm signaling and emergency control functions. With traditional IDCs and NACs, a single open, ground, or short fault on one circuit could not affect the performance of other IDCs, NACs, and emergency control circuits. As such, the occurrence of a single short or open limited the extent of the failure to a particular zone or area. One method for providing an acceptable level of performance and reliability of SLCs is to limit the potential catastrophic failure to one zone, in a way similar to how traditional IDCs and NACs have been and are now required to do. A single zone could be designated in the following ways: (1) By floor where an SLC would not span multiple floors (2) By floor area, where a large floor would be split into multiple zones based on a maximum floor area size (e.g., 22,500 ft 2 ) (3) By fire barrier or smoke barrier compartment boundaries, which an SLC would not cross (4) By maximum length or circuit, where an SLC would not be longer than a predetermined length (e.g., 300 ft) See the definition of zone ( ) for additional clarification.

48 85 of /21/2013 1:03 PM First Revision No. 117-NFPA [ New Section after ] For the purpose of this section, each floor of the building shall be considered a separate zone. Submittal Date: Mon Sep 09 18:41:51 EDT 2013 This change better defines a zone is in terms of an SLC and the intended scope of FR 237. Public Input No. 355-NFPA [New Section after ]

49 86 of /21/2013 1:03 PM First Revision No. 118-NFPA [ New Section after ] For the purpose of this section, if a floor of the building is subdivided into multiple zones by fire or smoke barriers and the fire plan for the protected premises allows relocation of occupants from the zone of origin to another zone on the same floor, each zone on the floor shall be considered a separate zone. Submittal Date: Mon Sep 09 18:48:19 EDT 2013 This change better defines a zone in terms of an SLC and clarifies the intended scope of FR 237. Public Input No. 356-NFPA [New Section after ]

50 First Revision No. 122-NFPA [ New Section after ] No area or zone shall be serviced solely by a single device where Class N pathways are deployed, such that a single device failure would render an area or zone incapable of initiating input signals or receiving output signals. Exception: When a risk analysis is performed to determine areas where a single device is sufficient and acceptable to the authority having jurisdiction Where a device as referenced by is serviced by only a single pathway, it shall terminate that pathway with no capability to connect additional endpoint devices to the pathway Class N pathways shall be required to use Shared Pathway Level 3 as specified in Section A single fault on a Class N pathway connected to the addressable devices shall not cause the loss of more than one addressable device. Submittal Date: Mon Sep 09 19:41:45 EDT 2013 The creation of requirements for Class N pathways and their permitted use for signaling line circuits are necessary to ensure a safe and reliable installation. Public Input No. 285-NFPA [New Section after ] Public Input No. 286-NFPA [New Section after ] Public Input No. 287-NFPA [New Section after ] Public Input No. 288-NFPA [New Section after ] 90 of /21/2013 1:03 PM

51 87 of /21/2013 1:03 PM First Revision No. 119-NFPA [ New Section after ] * The requirements in shall not apply to the following: (1) Circuits between enclosures containing transponders and control units regardless of the number of initiating devices, notification appliances, or control relays that might be connected to those control units. (2) Circuits connecting short-circuit fault isolation modules to enclosures containing transponders and control units where the conductors are installed in metallic raceway or equivalently protected against mechanical injury and where the circuit does not exceed 3 ft (1 m) in length. Supplemental Information File Name A _for_FR_119.EC_edits.docx Description Submittal Date: Mon Sep 09 19:01:55 EDT 2013 The installations referenced in this change should not be subject to the restrictions in FR 237.The annex material serves to better clarify what is intended by the new language. New annex text is also added - see attached. Public Input No. 360-NFPA [New Section after ] Public Input No. 361-NFPA [New Section after ] Public Input No. 364-NFPA [New Section after A ]

52 A The intent is to clarify that the requirement identified in applies only to SLCs that connect to addressable devices and not to SLCs that interconnect fire alarm control units (FACU) or transponders.

53 88 of /21/2013 1:03 PM First Revision No. 120-NFPA [ New Section after ] The loss of more than one zone shall be permitted on a documented performance-based design approach in accordance with Submittal Date: Mon Sep 09 19:25:23 EDT 2013 A performance based alternative to the requirements of the newly revised 23.6 will still provide a safe design when the conditions of this change are followed. Public Input No. 357-NFPA [New Section after ]

54 First Revision No. 121-NFPA [ New Section after ] * Performance-based designs submitted to the authority having jurisdiction for review and approval shall include documentation, in an approved format, of each performance objective and applicable scenario, together with technical substantiation used in establishing the proposed zone performance. Supplemental Information File Name a _for_fr_121.ec_edits.docx Description Submittal Date: Mon Sep 09 19:31:16 EDT 2013 The change provides better clarity as to what will be required for designers to exercise the performance based alternative to FR 237, which has been adopted as a new The annex material gives some examples of how this alternative may be utilized. New annex material is also added - see attached. Public Input No. 358-NFPA [New Section after ] Public Input No. 363-NFPA [New Section after A ] 89 of /21/2013 1:03 PM

55 A Possible scenarios in which a designer might choose to permit loss of more than one zone include a multistory building with a small floor plan footprint where a limited number of addressable devices are located on the floor (e.g., one manual fire alarm box and two automatic fire detection devices). In this scenario, the designer might choose to include multiple floors of devices on the same signaling line circuit because the loss of such devices due to a single SLC short or open would disable a limited number of devices. Another scenario could include buildings with a small vestibule at the top of a stair that exits onto the roof of a building. The vestibule might contain one manual fire alarm box and one or two automatic fire detection devices that could be connected to the signaling line circuit on the floor below and considered the same zone. Designers providing documents for upgrades to an existing building where the control units and all fire alarm system devices are being replaced but some portion of the existing circuits are being reused might, because of constructability reasons, opt for combining zones and the associated risk of the loss of those devices due to a single SLC short or open. The intent of is not to impose an unnecessary burden on building owners with existing systems undergoing renovations, upgrades, or replacements. In these scenarios as well as others, the designer would be required to provide a documented, performance based design approach to justify why the loss of more than one zone is acceptable. Documentation must be composed in accordance with and be submitted in accordance with

56 91 of /21/2013 1:03 PM First Revision No. 129-NFPA [ Section No ] * Actuation Time. Actuation of alarm notification appliances or emergency voice communications, emergency control function interface devices, and annunciation at the protected premises shall occur within 10 seconds after the activation of an initiating device. Supplemental Information File Name Attachment_for_FR_129.docx Description Submittal Date: Tue Sep 10 10:10:09 EDT and related annex text is deleted because the subject matter will be addressed in under the responsibility of the Fundamentals committee. The related annex material is also deleted - see attached. The following text is suggested for and A.10.11: * Actuation Time. Actuation of alarm notification appliances or emergency voice communications, emergency control function interface devices, and signal annunciation at the protected premises fire alarm control unit and other designated locations shall occur within 10 seconds after the activation of an initiating device. A Other locations could include the following: (1) Building fire command center for in-building fire emergency voice/alarm communications systems (2) Fire alarm control unit for network fire alarm systems Actuation of an initiating device is usually the instant at which a complete digital signal is achieved at the device, such as a contact closure. For smoke detectors or other automatic initiating devices, which can involve signal processing and analysis of the signature of fire phenomena, actuation means the instant when the signal analysis requirements are completed by the device or fire alarm control unit software. A separate fire alarm control unit contemplates a network of fire alarm control units forming a single large system as defined in Section For some analog initiating devices, actuation is the moment that the fire alarm control unit interprets that the signal from an initiating device has exceeded the alarm threshold programmed into the fire alarm control unit. For smoke detectors working on a system with alarm verification, where the verification function is performed in the fire alarm control unit, the moment of actuation of smoke detectors is sometimes determined by the fire alarm control unit. It is not the intent of this paragraph to dictate the time frame for the local fire safety devices to complete their function, such as fan wind-down time, door closure time, or elevator travel time.

Page 1 of 40 First Correlating Revision No. 15-NFPA 72-2014 [ Global Input ] 10.5.4 Plans Examiners and Inspectors. 10.5.4.1 Fire alarm system and emergency communications system plans and specifications

More information

Fire Alarm System Fundamentals

Fire Alarm System Fundamentals Fire Alarm System Fundamentals Mircom is the largest and oldest privately owned fire alarm and life safety manufacturer in North America and 5th largest overall with 50 years of industry experience. Mircom

More information

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement of 1 9/22/2014 1:38 PM Second Revision No. 104-NFPA 72-2014 [ Section No. 3.3.3 ] 3.3.3 Accessible, Readily (Readily Accessible). Capable of being reached quickly for operation, renewal, or inspections

More information

NFPA Changes

NFPA Changes Chapter 21, Emergency Control Functions and Interfaces Summary. Chapter 21 is new. These requirements were formerly found in Chapter 6, Protected Premises Fire Alarm Systems. The term fire safety function

More information

Changes in NFPA

Changes in NFPA Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration

More information

Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN)

Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN) 4 of 326 11/21/2013 1:03 PM First Revision No. 161-NFPA 72-2013 [ Section No. 3.3.11 ] 3.3.11 Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN)

More information

NFPA Changes

NFPA Changes Chapter 12, Circuits and Pathways Summary. Chapter 12, Circuits and Pathways, is a new chapter. It brings together requirements that were formerly found in SIG-FUN, Fundamentals of Fire Alarm Systems regarding

More information

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions. 11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

More information

26 of 128 9/23/2014 9:25 AM

26 of 128 9/23/2014 9:25 AM 26 of 128 9/23/2014 9:25 AM Second Revision No. 105-NFPA 72-2014 [ Global Comment ] Revise the Annex F figures that include a smoke detector symbol (hexagon with a whisp of smoke) so that the new smoke

More information

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM 1 of 213 10/20/2016 11:02 AM Committee Input No. 2505-NFPA 72-2016 [ Global Input ] Change the term visible to visual where appropriate Submitter Information Verification Submitter Full Name: SIG-NAS Organization:

More information

First Revision No. 339-NFPA [ Section No. 2.2 ]

First Revision No. 339-NFPA [ Section No. 2.2 ] 8 of 326 11/21/2013 1:03 PM First Revision No. 339-NFPA 72-2013 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 10, Standard

More information

STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018

STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018 STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018 STANDARD INFORMATION Standard Number: NFPA 72 Standard Name: National Fire Alarm and Signaling Code Standard Edition and Issue Date: 2016 Edition

More information

9/23/ :47 AM. Second Revision No NFPA [ New Section after ] Submitter Information Verification. Committee Statement

9/23/ :47 AM. Second Revision No NFPA [ New Section after ] Submitter Information Verification. Committee Statement Second Revision No. 5501-NFPA 5000-2016 [ New Section after 29.2.1.2 ] 29.2.1.3 Bathtubs, bathtub-shower combinations, and nonemergency showers shall be provided with grab bars in accordance with the provisions

More information

NFPA Siemens Industry, Inc. All rights reserved. usa.siemens.com/infrastructure-cities

NFPA Siemens Industry, Inc. All rights reserved. usa.siemens.com/infrastructure-cities Fire Alarm and Signaling Code Overview NFPA 72-2010 usa.siemens.com/infrastructure-cities Siemens Building Technologies, Inc. is a Registered Provider with The American Institute of Architects Continuing

More information

Fire Alarm Wiring. Circuit types, styles and limitations

Fire Alarm Wiring. Circuit types, styles and limitations Fire Alarm Wiring Circuit types, styles and limitations What we will cover Types Classes Notification Appliance Circuits (NAC) Initiating Device Circuits (IDC) Signaling Line Circuits (SLC) Class A, B,

More information

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course Florida Building Code 2010 Chapter 9 Fire Protection Systems Advanced Course 1 Introduction This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors

More information

MEMORANDUM. Technical Committee on Protected Premises Fire Alarm and Signaling Systems

MEMORANDUM. Technical Committee on Protected Premises Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Protected Premises Fire Alarm

More information

Florida Building Code 2010

Florida Building Code 2010 Introduction Florida Building Code 2010 Chapter 9 Fire Protection Systems This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors are familiar with

More information

NFPA 72 Code Changes vs 2013

NFPA 72 Code Changes vs 2013 NFPA 72 Code Changes - 2010 vs 2013 AFAA-NE Westborough, MA February 7, 2018 Richard Roux NFPA 72 National Fire Alarm and Signaling Code Overview and 2013 Changes NFPA 72 1993 Edition Aug 20, 1993 1996

More information

rpsa FIRE PROTECTION ENGINEERS

rpsa FIRE PROTECTION ENGINEERS FIRE PROTECTION ENGINEERS R.P. SCHIFILITI ASSOCIATES, INC. P.O. Box 297 Reading, Massachusetts 01867-0497 USA 781.944.9300 Fax / Data 781.942.7500 Telephone Elevator Fire Safety: Elevator Recall and Elevator

More information

SAF-BCF SECOND REVISIONS WITH STATEMENTS

SAF-BCF SECOND REVISIONS WITH STATEMENTS Page 196 of 331 32.2.1.3 ] Second Revision No. 153-NFPA 101-2013 [ New Section after 32.2.1.4 Multiple-Level Buildings. For purposes of applying requirements of this chapter that utilize the term level

More information

Proposed Changes to NFPA

Proposed Changes to NFPA 2017 NFPA Conference & Expo Proposed Changes to NFPA 72-2019 Presented by: Manuelita David (SIG-FUN), Jensen Hughes Warren Olsen (SIG-SSS), Fire Safety Consultants, Inc. Merton Bunker (SIG-AAC), EYP Architecture

More information

2018 NICET Code Transition Changes

2018 NICET Code Transition Changes 2018 NICET Code Transition Changes NICET will be transitioning to newer codes accepted in their exams in mid-october 2018, specifically: NFPA 72 2016 NFPA 70 2014 IBC 2015 NFPA 101 2015 Here are some changes

More information

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Service and Fire Protection Equipment Gregory Harrington, P.E., Staff Liaison DATE: October 1, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter

More information

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Services and Fire Protection Equipment Linda MacKay DATE: November 10, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter Ballot Final Results The

More information

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard

More information

Unified Fire Authority - Fire Prevention Bureau

Unified Fire Authority - Fire Prevention Bureau Unified Fire Authority - Fire Prevention Bureau FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR6005 SAF-BCF (32.2.1.1.2) Recommendation: 32.2.1.1.2 Where there are sleeping accommodations for more than 16 residents are provided, the occupancy shall be classified as a large facility in accordance

More information

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement of 43 10/20/2015 4:02 PM First Revision No. 2035-NFPA 101-2015 [ Global Input ] To 14.3.4.4.1, add an item (4) to read: (4) Carbon monoxide detectors shall be installed centrally located within occupiable

More information

Chapter 2: Definitions

Chapter 2: Definitions FLORIDA BUILDING CODE Existing Buildings 6 TH Edition (2017) Code Changes based on the document provided by DBPR - 2014 and 6th Edition (2017) Florida Building Code Comparison JUMP TO CHAPTER (click chapter

More information

Questions/Comments for Richard Roux from Webinar on 7/11/13

Questions/Comments for Richard Roux from Webinar on 7/11/13 Questions/Comments for Richard Roux from Webinar on 7/11/13 Below are the questions and comments from the July 11, 2013 webinar 2013 NFPA 72: Design and Installation Requirements for Mass Notification

More information

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification Second Revision No. 2011-NFPA 101-2016 [ Section No. 14.2.2.2.4 ] 14.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked to prevent unwanted entry

More information

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. 2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Protected Premises

More information

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement 10/20/ :03 AM

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement 10/20/ :03 AM of 496 10/20/2016 11:03 AM First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value 0.0375 lumens/ft 2 is used the metric equivalent shall be

More information

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing. 9/20/2016 2:27 PM Second Revision No. 5006-NFPA 101-2016 [ Section No. 3.3.56 ] 3.3.56 Delayed Action Closer. Self-closing device that incorporates a delay prior to the initiation of closing. Mechanical

More information

MNEC NFPA 72 WHITE PAPER

MNEC NFPA 72 WHITE PAPER MNEC NFPA 72 WHITE PAPER In 2010, the National Fire Protection Assocation (NFPA), significantly changed their code # 72 (National Fire Alarm Code) and has forever improved the importance of communicating

More information

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM 1 of 14 6/22/2016 3:15 PM Second Revision No. 1-NFPA 17A-2016 [ Section No. 4.3.3 ] 4.3.3 All discharge nozzles shall be provided with caps or other suitable devices to prevent the entrance of grease vapors,

More information

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition Copyright National Fire Protection Association 2013. All rights reserved. This copy is solely for your personal, noncommercial use in connection with participation in the NFPA Standards Development Process.

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved

More information

Minutes of the Pre-ROP Meeting of the T/C on Protected Premises Signaling September 22-23, 2010 Indianapolis, IN

Minutes of the Pre-ROP Meeting of the T/C on Protected Premises Signaling September 22-23, 2010 Indianapolis, IN Minutes of the Pre-ROP Meeting of the T/C on Protected Premises Signaling September 22-23, 2010 Indianapolis, IN Mr. Merton Bunker, Committee Chair, called the meeting to order at 8:05 on Wednesday September

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR7040 SAF-MER (36.1.1.4) 36.1.1.4 The provisions of this chapter shall apply to life safety requirements for all new mercantile buildings. Specific requirements shall apply to suboccupancy groups,

More information

First Revision No. 82-NFPA [ Section No ] Submitter Information Verification. Committee Statement. 2 of /21/2013 1:03 PM

First Revision No. 82-NFPA [ Section No ] Submitter Information Verification. Committee Statement. 2 of /21/2013 1:03 PM 2 of 326 11/21/2013 1:03 PM First Revision No. 82-NFPA 72-2013 [ Section No. 2.3.4 ] 2.3.4 ISO Publications. International Organization for Standardization, 1, ch. de la Voie-Creuse, Case postale 56, CH-1211

More information

9/23/ :20 AM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

9/23/ :20 AM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification of 4 9/23/2016 10:20 AM Second Revision No. 6501-NFPA 5000-2016 [ Section No. 17.2.2.2.4 ] 17.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked

More information

Interfacing Fire Alarm, Sprinkler and Elevator Systems

Interfacing Fire Alarm, Sprinkler and Elevator Systems 1 Interfacing Fire Alarm, Sprinkler and Elevator Systems Rodger Reiswig, SET Director, Industry Relations SimplexGrinnell November 17, 2010 Interfacing to Elevators 2 ASME A17.1 Safety Code for Elevators

More information

Report on First Revision November 2013 NFPA 731

Report on First Revision November 2013 NFPA 731 Report on First Revision November 2013 NFPA 731 731- Log #FR1 Final Action: (2.3.3) Submitter: Technical Committee Premises Security Recommendation: 2.3.3 UL Publications. Underwriters Laboratories Inc.,

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Notification Appliances

More information

El Reno Fire Department Fire Alarm Plan Review Worksheet

El Reno Fire Department Fire Alarm Plan Review Worksheet El Reno Fire Department Fire Alarm Plan Review Worksheet This Fire Alarm Plan Review Checklist is provided as a guide to assist with your Fire Alarm Plan Review Submittal requirements. Please contact us

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Alarm System Plan Review 2009 International Fire Code and 2010 NFPA 72 Date of Review // BLD201 - Project Address: Project Name: _ Professional

More information

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax) FIRE DEPARTMENT SANTA CLARA COUNTY 14700 Winchester Blvd., Los Gatos, CA. 95032-1818 (408) 378-4010 (408) 378-9342 (fax) www.sccfd.org STANDARD DETAILS & SPECIFICATIONS Spec No C-4 Rev. Date 03/10/10 SUBJECT:

More information

Second Revision No. 102-NFPA [ Global Comment ] Submitter Information Verification. Committee Statement

Second Revision No. 102-NFPA [ Global Comment ] Submitter Information Verification. Committee Statement of 1 9/22/2014 12:54 PM Second Revision No. 102-NFPA 72-2014 [ Global Comment ] 10.12.2 Visible notification appliances, textual visible notification appliances, and speaker notification appliances located

More information

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline Moreno Valley Fire Department Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 8, 2017 Alarm & Signaling Systems PURPOSE Fire alarm and signaling systems are designed to

More information

2. HVAC and smoke control systems; fire, smoke, and combination fire/smoke dampers. 5. Central control and monitoring system.

2. HVAC and smoke control systems; fire, smoke, and combination fire/smoke dampers. 5. Central control and monitoring system. PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible.. This

More information

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety Div B 3.2.1.1.(4), (5) & (6) Exceptions in Determining Building Height BCBC1998-3.2.1.1.(4), (5) & (7) replace (harmonize with NBC) - NBC 2005 has significant revisions to provisions for mezzanines. These

More information

First Revision No NFPA [ Section No ]

First Revision No NFPA [ Section No ] of 45 10/21/2015 8:54 AM First Revision No. 3501-NFPA 101-2015 [ Section No. 3.3.190.1 ] 3.3.196.1* Ambulatory Health Care Occupancy. An occupancy used to provide services or treatment simultaneously to

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 8/2004 Fire Chief Lee Koontz Fire Marshal Paul Smith EFD-FMO 3-1 2003 International Fire & Building Code as Amended NFPA Standards

More information

1.3 REFERENCE STANDARDS

1.3 REFERENCE STANDARDS SECTION 28 4600 FIRE DETECTION AND ALARM PART 1 -GENERAL 1.1 SECTION INCLUDES A. Fire alarm system design and installation, including all components, wiring, and conduit. B. Circuits from protected premises

More information

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used. PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire alarm and signaling systems at Sam Houston State University provide the highest level of life safety possible. This

More information

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS SECTION 907 FIRE ALARM AND DETECTION SYSTEMS 907.1 General. This section covers the application, installation, performance and maintenance of fire alarm systems and their components in new and existing

More information

Addressing Sound Masking Requirements in the National Fire Alarm and Signaling Code and UL Standards

Addressing Sound Masking Requirements in the National Fire Alarm and Signaling Code and UL Standards Addressing Sound Masking Requirements in the National Fire Alarm and Signaling Code and UL Standards Wayne D. Moore, P.E., CFPS, SET Vice President JENSEN HUGHES 117 Metro Center Boulevard, Suite 1002

More information

M E M O R A N D U M. Technical Committee on Supervising Station Fire Alarm and Signaling Systems

M E M O R A N D U M. Technical Committee on Supervising Station Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Supervising Station

More information

Type of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number:

Type of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number: DATE OF SUBMISSION TO: Department of Licenses and Inspections Commercial and Industrial Fire Inspection Unit 990 Spring Garden Street, 3 rd Floor, Philadelphia, PA 19123 AP# CITY OF PHILADELPHIA FIRE ALARM

More information

The 2013 National Fire Alarm and Signaling Code

The 2013 National Fire Alarm and Signaling Code ARE YOU A MEMBER OF AFAA? WHY SHOULD YOU BE A MEMBER BECAUSE YOUR BUSINESS IS IMPORTANT James Mongeau The 2013 National Fire Alarm and Signaling Code 1 NFPA 72 Organization Be*er organiza2on Easier to

More information

HCD DSA OSHPD 1 2 1/AC AC SS SS/CC

HCD DSA OSHPD 1 2 1/AC AC SS SS/CC CALIFORNIA BUILDING CODE MATRIX ADOPTION TABLE CHAPTER 30 ELEVATORS AND CONVEYING SYSTEMS (Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter 1 for state agency

More information

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Rancho Cucamonga Fire Protection District Prevention Bureau Standard Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Updated: December 2016 for consistency

More information

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM of 25 7/30/2015 1:35 PM First Revision No. 49-NFPA 17A-2015 [ Detail ] Make the following change to 5.2.1.10.2: 5.2.1.10.2* The manual actuation device shall clearly identify the hazard protected and provide

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Protected Premises

More information

Report on First Revision June 2014 NFPA 5000

Report on First Revision June 2014 NFPA 5000 5000- Log #12 BLD-BSF Final Action: (55.2 (New) ) NOTE: This proposal appeared as Comment 5000-168 (Log #86) which was held from the A11 ROC on Proposal 5000-239. Submitter: Technical Correlating Committee

More information

MD-DC-VA Automatic Fire Alarm Association, Inc. Interfacing Fire Alarm, Sprinkler and Elevator Systems In Maryland, DC and Virginia

MD-DC-VA Automatic Fire Alarm Association, Inc. Interfacing Fire Alarm, Sprinkler and Elevator Systems In Maryland, DC and Virginia , Inc. Interfacing Fire Alarm, Sprinkler and Elevator Systems In Maryland, DC and Virginia Presented by: Andrew Roe, SET Alarm Tech Solutions, LLC Scope: The Purpose of Elevator Controls History of Elevator

More information

First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 4/15/ :08 AM

First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 4/15/ :08 AM First Revision No. 1-NFPA 1403-2015 [ Section No. 1.2.1 ] 1.2.1 The purpose of this standard shall be to provide a process for conducting live fire training evolutions to ensure that they are conducted

More information

ALARM SYSTEMS AND EVACUATION PLANS SELF INSPECTION CHECKLIST

ALARM SYSTEMS AND EVACUATION PLANS SELF INSPECTION CHECKLIST OPTIONAL INFORMATION Name of School: Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: ALARM SYSTEMS AND EVACUATION PLANS Guidelines: This checklist covers regulations issued

More information

FIRE & LIFE SAFTEY STANDARD

FIRE & LIFE SAFTEY STANDARD Title: Effective Date: 01/01/14 Revised Date: 1/1/14 Code References: Title 16, Chapter 16.16 of the Roseville Municipal Code, NFPA 72 Note: This standard is a summary of Fire Department clarifications

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Notification

More information

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE Effective Date: 11/01/02 Purpose: MECKLENBURG COUNTY To establish a set of guidelines for performance testing of all newly installed or upgraded fire alarm systems in order to ensure that all devices and

More information

Public Input No. 4-NFPA [ Section No. 4.2 ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

Public Input No. 4-NFPA [ Section No. 4.2 ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification Public Input No. 4-NFPA 214-2013 [ Section No. 4.2 ] 4.2 * Fire Risk Analysis. A fire risk analysis shall be conducted. The following are some of the factors that shall be considered in determining the

More information

1 Exam Prep Fire Alarm Signaling Systems Tabs and Highlights

1 Exam Prep Fire Alarm Signaling Systems Tabs and Highlights 1 Exam Prep Fire Alarm Signaling Systems Tabs and Highlights These 1 Exam Prep Highlights are based on the Fire Alarm Signaling Systems, 4th Edition. Each Tabs sheet has five rows of tabs. Start with the

More information

The Technical Committee on Commissioning and Integrated Testing

The Technical Committee on Commissioning and Integrated Testing National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org TO: FROM: The Technical Committee on Commissioning and Integrated Testing

More information

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input of 280 2/6/2015 12:06 PM Public Input No. 1-NFPA 58-2013 [ Global Input ] NOTE: This public input originates from Tentative Interim Amendment 58-14-1 (TIA 1079) issued by the Standards Council on August

More information

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE Developed by the Midwestern Regional Work Group CONTENTS Item 15 Limited area sprinkler systems Item 20 Scope of IFC Ch 7 Item 21 Fire-resistance-rated

More information

Brighton Area Fire Authority

Brighton Area Fire Authority 615 W. Grand River Ave. Brighton, MI 48116 o: 810-229-6640 f: 810-229-1619 January 14, 2019 Fire Alarm Contractors RE: Fire Alarm Credential & Submittal Requirements To Whom It May Concern: The following

More information

CERTIFICATION BULLETIN

CERTIFICATION BULLETIN File: ULC-S527-11 ULC-G5.2 June 1, 2012 CERTIFICATION BULLETIN 2012-04 Effective Date Announcement CAN/ULC-S527-11, 3 rd Edition of the Standard for Control Unit for Fire Alarm Systems To: Subscribers

More information

AGENDA NFPA TECHNICAL COMMITTEE ON NOTIFICATION APPLIANCES. Report on Comments Meeting, October 13-14, Richmond Marriott, Richmond, VA

AGENDA NFPA TECHNICAL COMMITTEE ON NOTIFICATION APPLIANCES. Report on Comments Meeting, October 13-14, Richmond Marriott, Richmond, VA National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org AGENDA NFPA TECHNICAL COMMITTEE ON NOTIFICATION APPLIANCES Report on Comments

More information

National Fire Protection Association M E M O R A N D U M. Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems

National Fire Protection Association M E M O R A N D U M. Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Testing and Maintenance

More information

Full Service Central Station Fire Alarm Listing Evaluation

Full Service Central Station Fire Alarm Listing Evaluation Full Service Central Station Fire Alarm Listing Evaluation Listing Evaluation A UL Listing project includes: 1. Evaluating the central station facility for compliance with UL 827, Central-Station Alarm

More information

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement of 47 10/21/2015 9:37 AM First Revision No. 5041-NFPA 101-2015 [ Global Input ] Throughout the document, change electrically controlled egress door assemblies to door hardware-release of electrically locked

More information

NEC Requirements for Standby Power Systems. New England Building Officials Education Association Annual Conference October 5, 2015

NEC Requirements for Standby Power Systems. New England Building Officials Education Association Annual Conference October 5, 2015 NEC Requirements for Standby Power Systems New England Building Officials Education Association Annual Conference October 5, 2015 Emergency & Standby Power Systems Alternative power sources are utilized

More information

Page 1 of 12 Input No. 62-NFPA 409-2013 [ Section No. 3.3.9 ] 3.3.9 Hangar Building Cluster. A group of buildings with more than one area for the storage and servicing of aircraft and all attached or contiguous

More information

ELEVATORS. Integration of Codes between Fire Alarm, Sprinklers, and Elevators 12/5/2017

ELEVATORS. Integration of Codes between Fire Alarm, Sprinklers, and Elevators 12/5/2017 12/5/2017 1 ELEVATORS Integration of Codes between Fire Alarm, Sprinklers, and Elevators Encore Electric Inc. Prepared By John McGovern and Jeffrey Engelstad 12/5/2017 Encore Electric Inc. 2 Agenda Basics

More information

Surviving Survivability A User s Guide to Survivable Fire Alarm Circuits Larry D. Rietz, SET 23 May 2018

Surviving Survivability A User s Guide to Survivable Fire Alarm Circuits Larry D. Rietz, SET 23 May 2018 Surviving Survivability A User s Guide to Survivable Fire Alarm Circuits Larry D. Rietz, SET 23 May 2018 Automatic FireAlarm Association SURVIVING SURVIVABILITY - A USER S GUIDE TO Larry D. Rietz, SET

More information

SECTION DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM SECTION 283111 DIGITAL, ADDRESSABLE FIRE ALARM PART 1 - GENERAL 1.1 GENERAL A. This Section includes the following: 1. Fire-alarm control panel. 2. Manual fire-alarm boxes. 3. Smoke detectors. 4. Heat

More information

Idaho Surveying & Rating Bureau, Inc South Cobalt Point Way Tel: (208) Meridian, Idaho FAX: (208)

Idaho Surveying & Rating Bureau, Inc South Cobalt Point Way Tel: (208) Meridian, Idaho FAX: (208) Idaho Surveying & Rating Bureau, Inc. 1871 South Cobalt Point Way Tel: (208) 343-5483 Meridian, Idaho 83642 FAX: (208) 895-8059 www.isrb.com e-mail info@isrb.com Joseph C. Harbacheck, CIC Secretary - General

More information

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016 1. Introduction The intent of this document is to establish minimum standards for the practice of fire protection engineering within the State of Oklahoma as conducted by licensed professional engineers.

More information

Review of Revisions to NFPA 1, 2015 Edition

Review of Revisions to NFPA 1, 2015 Edition James S Peterkin, PE, LEED AP Senior Fire Protection Engineer TLC Engineering for Architecture Anthony Apfelbeck, CFPS, CBO, CFO, FM, FIFireE, MPA Building and Fire Official City of Altamonte Springs,

More information

Functional Performance Test

Functional Performance Test Fire Alarm Control Panel & Fire Alarm Annunciator Panel Notify all building occupants that testing will be conducted. Fire alarm contractor shall have personnel with 2-way radios at the fire alarm control

More information

Division 28 - Electronic Safety and Security

Division 28 - Electronic Safety and Security Division 28 - Electronic Safety and Security 28 31 11 Fire Alarm Systems Fire alarm systems shall be installed in buildings when required by this section. 1. Purpose: The primary purpose of a fire alarm

More information

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2

More information

Advanced Fire Alarm Systems Training Program Outline (5 Day)

Advanced Fire Alarm Systems Training Program Outline (5 Day) Advanced Fire Alarm Systems Training Program Outline (5 Day) Day 1 Prescriptive and Performance-Based Design Understand the methodology in accessing the threat of fire within a structure. Know the difference

More information

MODULE 8. Tying the Systems Together: Emergency Control Functions and Interfaces

MODULE 8. Tying the Systems Together: Emergency Control Functions and Interfaces MODULE 8 Tying the Systems Together: Emergency Control Functions and Interfaces 1 OVERVIEW OF MODULE 8 In this module we will: Describe all components, their arrangements and how the systems work Describe

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 92 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS Type Memo Tag FED - KA100 - General Requirements - Other Title

More information