Sequence of operation

Size: px
Start display at page:

Download "Sequence of operation"

Transcription

1 Sequence of operation IPS 4000 secondary variable speed control File No: Date: february 21, 2013 Supersedes: new Date: new

2 sequence of operation ips list of abbreviations: adj: Field Adjustable ai/ao: Analog Input/Analog Output di/do: Digital Input/Digital Output bas: Building Automation System dp: Differential Pressure Sensor hmi: Human Machine Interface ips 4000 automation system The ips 4000 has one (1) control panel with the following functionality: One ai per zone dp/t/flow transmitter 4-20 ma One ai for dp or Flow transmitter 4-20 ma for pump run-out protection One di per dp switch One di for remote connection for start/stop One di per pump for fault signal One di per vfd for fault signal One d0 for alarm horn (buzzer) One di for alarm silencer One a0 per vfd for speed signal One d0 per pump for status One d0 for pump/motor/vfd alarm One d0 for zone dp/t/fow transmitter alarm One d0 for general system alarm One d0 per vfd automatic bypass One digital communication port for bms One digital communication port for graphical hmi One digital communication port for vfd communication. operation All pumps must be set in auto mode for the plant to work properly. However, any individual pumps can be set to hand or off mode. Any pump in hand or off mode won t be operated by the automatic sequencing of the plant in any mode of operation. Any pump placed in hand mode will start immediately as long as the ips is on. 1 general sequence 1.1 The standard ips 4000 is supplied with a 4" pgd touch Human Machine Interface (hmi). 1.2 When the ips 4000 system is set to local start, the ips will turn on as soon as the ips switch is set to enable. 1.3 During both settings (remote and local start), the ips will turn off when the ips switch is set to off. 1.4 The schematic of the system is displayed on the hmi showing all secondary pumps variables on the screen. 1.5 Monitor single zone differential pressure transmitter (up to 12 transmitters as an option remotely installed by contractor). 1.6 Compare each value to its set-point. The zone that has deviated the most from its set-point shall be set as the controlling zone (see detailed specifications for multizone control). 1.7 pid control algorithm for pump speed control in plc. 1.8 Automatically disable any zone differential pressure signals that are not within limits and alert the operator of a possible transmitter failure. 1.9 Motor speed will be switched to manual at speed set by the operator if all transmitters fail Manual vfd bypass or auto bypass option Manual and automatic alternation of secondary pumps based on hours of operation Alarms shall include transmitters failure, pump/motor/ drive failure, pump fatal alarms, and general system failure Run-out protection on pumps based on dp or flow sensor Three levels of password protection on operator interface. 2 zone sensor control for secondary pumps 2.1 The ips 4000 can operate up to six pumps. One pump can be selected as stand-by. 2.2 When the ips is on, the shall start the lead pump. 2.3 If lead pump fails to start, the next lag pump shall automatically start and an alarm will be displayed showing pump fault. The alarm is sent to the bas as well. 2.4 The ips 4000 shall be capable of alternating the lead and lag variable pumps manually (at hmi), and automatically based on hours of operation. 2.5 The ips can monitor the dp or temperature of up to 12 zones. If there is only one zone enabled, it becomes the active zone. When there are two or more zones and all of them are enabled, the zone with the most negative error becomes the active zone (if all the errors are positive, the zone with the smallest error). The zone dp or temp is referred as zone present value (pv). Each zone has an adjustable setpoint (sp). Zone error is defined as: error = pv - sp. If a zone is disabled, its error will default to

3 ips 4000 sequence of operation When the system valves control is enabled, the ips 4000 shall obtain the opening (in %) of the system valve with the maximum opening from the bas. The control will modulate the active zone setpoint in order to maintain the system valve with the maximum opening at the system valve opening setpoint (adj.). If the valve s opening is less than the setpoint, reduce the active zone setpoint and vice versa. 2.7 The speed of the pumps is controlled to maintain the active zone differential pressure at setpoint. If the active zone pv is under the setpoint, the speed of the pumps shall increase. If the pv is over the setpoint, the speed shall decrease. 2.8 Automatically disable any zone differential pressure or temperature signals that are not within limits and alert the operator of a possible transmitter failure. Should all sensors fail, the pump speed will be set to 95% (adj.). 2.9 The ips 4000 shall be capable of staging and de-staging pumps based on adjustable bep speeds. If the pump speed is over the bep stage-on speed for the duration of the stage-on delay (adj.), start the next lag pump. Similarly, if the pump speed is under the bep stage-off for the duration of the stage-off delay (adj.), stop the last lag pump The lag pumps shall run for a minimum of 15 minutes (adj.) once started ips 4000 shall have run out (eoc) protection of the pumps using either a dp sensor or a flow meter (user selectable). When the eoc protection is enabled, the ips 4000 will start the next lag pump if the differential pressure from the dp sensor is greater than the eoc dp (adj.) or if the value from the flow meter is greater than the eoc flow (adj.) multiplied by the number of pumps running. If the selected sensor is out of range, disable the eoc protection and display the alarm on the hmi If the pump dp switches are enabled, the ips will use their signals (di) as pump operation confirmation. If the dp switches are not enabled, the vfd feedback is used as pump run confirmation Shall the plc loose the pump run feedback (whether dp switch as digital input or vfd signal) the ips will generate a Pump Run Feedback Alarm and lock the pump out of operation until 2.14 The ips will continuously monitor the vfd status, shall the vfd raise its fault signal, the ips will generate a Pump vfd Fault Alarm and lock the pump out of operation until 2.15 Shall the plc loose communication with a pump vfd (due to loose or broken wire, vfd not properly configured or powered off), the ips will generate a Pump Communication Alarm and lock the pump out of operation until 2.16 The pump auto bypass can be enabled or disabled. If it is enabled, when a pump fails (due to no run feedback, vfd fault or communication), the ips will determine if there is another pump available to replace the faulty pump. If there is no pump available, a digital output will mechanically bypass the vfd and energize the pump motor directly. All pumps running at that moment will be bypassed. The bypass condition will remain until manually reset at the hmi. 3 sensorless control for secondary pumps 3.1 The ips 4000 can operate up to six pumps. One pump can be selected as stand-by. 3.2 When the operator selects sensorless control, the hmi hides the zone setup screens and shows the sensorless control setup screen with the following additional adjustable parameters: Design Head, Design Flow, Zero Flow Head, Head bep, Flow bep, Dead Band, Sensorless Map Adjustment Factor. 3.3 The ips 4000 reads Head and Flow from each vfd, in addition to current, power, and speed feedback. 3.4 When the ips is turned On all the duty pumps are started. 3.5 The ips calculates the total flow (Q) as the addition of the flow read from each running pump. The IPS uses the head read from the lead pump as the system head (H). 3.6 The pump speed and best efficiency staging points are controlled by embedded Armstrong algorithm to maintain the operation point (system head & flow) on the system control curve. 3.7 The lag pumps shall run for a minimum of 15 minutes (adjustable) once started. 3.8 If eoc is enabled, use Q instead of flow sensor. 3.9 The control monitors the flow of each running pump and if it deviates more than 20% off the average the system will issue an alarm If the pump dp switches are enabled, the ips will use their signals (di) as pump operation confirmation. If the dp switches are not enabled, the vfd feedback is used as pump run confirmation Shall the plc loose the pump run feedback (whether dp switch as digital input or vfd signal) the ips will generate a Pump Run Feedback Alarm and lock the pump out of operation until

4 sequence of operation ips The ips will continuously monitor the vfd status, shall the vfd raise its fault signal, the ips will generate a Pump vfd Fault Alarm and lock the pump out of operation until 3.13 Shall the plc loose communication with a pump vfd (due to loose or broken wire, vfd not properly configured or powered off), the ips will generate a Pump Communication Alarm and lock the pump out of operation until 3.14 The pump auto bypass can be enabled or disabled. If it is enabled, when a pump fails (due to no run feedback, vfd fault or communication), the ips will determine if there is another pump available to replace the faulty pump. If there is no pump available, a digital output will mechanically bypass the vfd and energize the pump motor directly. All pumps running at that moment will be bypassed. 5.2 alarm screens a Alarms with time stamp b Alarm help c Alarm history d Diagnostic indicating status (ok or bad) of plc, memory, network and communication e hmi and plc software version 5.3 setup screens (three levels of access) a Level 0 - No password, allows view only access b Level 1 - Allows modification of all parameters, except pump pid and bas setup. Allows restoring previously saved values c Level 2 - Allows modification of all parameters. Allows saving and restoring of all parameters 4 temperature control of modulating valve 4.1 If the temperature control is enabled, the ips 4000 will use one of the zone sensor analog inputs for a temperature sensor, and pump four analog output to control the modulating valve. 4.2 The valve position is controlled by pid to maintain the temperature at a setpoint specified by the user. 4.3 The valve output is selectable between 0-10 VDC or 2-10 VDC. 5 hmi screens 5.1 operator screens a Source of control: Local or remote b ips status: On/off c System overview graphic. This display adjusts to the selected configuration (i.e. number of pumps, piping configuration, number of zones) d Pump information: Running/Off/Alarm, hoa, Duty 1, Duty 2, Stand-by, etc. e Pump vfd information: Speed, amps, power, volts ac f All enabled zones present value, set-point, error and indication of which one is the active zone g Pump hours of operation 6 bas 6.1 The ips 4000 shall be capable of serial communication with the bas with any of the following protocols: Modbus RTU, BACnet MS/TP, BACnet IP, BACnet Ethernet and LonWorks. 6.2 The following points will be available through all protocols: a Remote Start/Stop b ips On/Off status c Pump information: Running/Off/Alarm, hoa, Duty 1, Duty 2, Stand-by, etc. d Pump vfd information: Speed, Amps, power, volts ac, Flow and Head. e All zones present value, setpoint and error. f Pump hours of operation. 6.3 The ips has the following signals available as hard wired: a Remote Start/Stop (di). b Pump alarm (do). c Sensor alarm (do). d General alarm (do).

5 ips 4000 sequence of operation 5

6 toronto 23 bertrand avenue toronto, ontario canada m1l 2p buffalo 93 east avenue north tonawanda, new york u.s.a birmingham heywood wharf, mucklow hill halesowen, west midlands united kingdom b62 8dj +44 (0) manchester wenlock way manchester united kingdom m12 5jl +44 (0) bangalore #59, first floor, 3rd main margosa road, malleswaram bangalore, india (0) shanghai no hu hang road, xi du township feng xian district, shanghai p.r.c armstrong integrated established 1934 armstrongintegrated.com tm

Installation and operating instructions. E.2 Series high efficiency circulator

Installation and operating instructions. E.2 Series high efficiency circulator Installation and operating instructions E.2 Series high efficiency circulator File No: 10.84 Date: august 16, 2012 Supersedes: 10.84 Date: july 20, 2010 contents 1.0 Operating limits 4 2.0 Electrical

More information

Condensing boiler plant (vp)

Condensing boiler plant (vp) Condensing boiler plant (vp) Design Envelope File No: 9.565uk Date: january 23, 2015 Supersedes: new Date: new design envelope s performance improvements are among the top priorities of many building professionals

More information

Astro 2 circulator models. Installation and operating instructions

Astro 2 circulator models. Installation and operating instructions Astro 2 circulator models Installation and File No: 10.89 Date: august 05, 2013 Supersedes: 10.89 Date: june 26, 2013 contents 1.0 Introduction 4 2.0 Installing 4 2.1 Terminal box 4 2.2 Electrical wiring

More information

ASTRO 2 SERIES HOT WATER RE-CIRCULATION SYSTEM INSTALLATION AND OPERATING INSTRUCTIONS

ASTRO 2 SERIES HOT WATER RE-CIRCULATION SYSTEM INSTALLATION AND OPERATING INSTRUCTIONS ASTRO 2 SERIES HOT WATER RE-CIRCULATION SYSTEM INSTALLATION AND OPERATING INSTRUCTIONS File No: 10.812 Date: february 24, 2017 Supersedes: 10.812 Date: july 23, 2015 1.0 Typical application 1 2.0 How it

More information

ASTRO 2 SERIES HOT WATER RE-CIRCULATION SYSTEM INSTALLATION AND OPERATING INSTRUCTIONS

ASTRO 2 SERIES HOT WATER RE-CIRCULATION SYSTEM INSTALLATION AND OPERATING INSTRUCTIONS ASTRO SERIES HOT WATER RE-CIRCULATION SYSTEM INSTALLATION AND OPERATING INSTRUCTIONS File No: 10.81 Date: july 11, 018 Supersedes: 10.81 Date: february 4, 017 1.0 Typical application 1.0 How it works 1

More information

opti-visor ultra-efficient chiller plant automation Typical specification

opti-visor ultra-efficient chiller plant automation Typical specification opti-visor ultra-efficient chiller plant automation Typical File No: 90.893 Date: february 9, 2015 Supersedes: 90.893 Date: april 20, 2012 contents 1.0 Chilled water plant 4 1.1 General system requirements

More information

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers. ModSync Sequencing System Installation & Operation Manual For use with Fulton Steam Boilers. Revision 3.0 8/21/2008 - 2 - Table of Contents Introduction Page 4 Features Page 4 Sequence of Operation Page

More information

E.2 series high efficiency circulator. Installation and operating instructions

E.2 series high efficiency circulator. Installation and operating instructions E.2 series high efficiency circulator Installation and operating instructions File No: 10.84 Date: august 16, 2012 Supersedes: 10.84 Date: july 20, 2010 contents 1.0 Operating limits 4 2.0 Electrical

More information

SCC Inc. Master Panel. Specifications. Document No. TS 2010 February 11, Product Description. Sample Specification

SCC Inc. Master Panel. Specifications. Document No. TS 2010 February 11, Product Description. Sample Specification February 11, 2019 Master Panel Product Description The Master Panel shall provide lead/lag control and time based, automatic rotation of up to eight (8) boilers, when used in conjunction with LMV3 or LMV5

More information

I/O ZONE 560/583 USERS GUIDE

I/O ZONE 560/583 USERS GUIDE I/O ZONE 560/583 USERS GUIDE 641-224 641-242 641-237 1 Table of Contents Hot Gas Re-Heat Valve On/Off:... 15 THE ZONE CONTROLLER...4 Modulating Re-Heat Valve:... 16 SPECIFICATIONS...5 CONTROLLER COMPONENTS...6

More information

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas User s Manual TIGER S EYE E-Series Mark V Jockey TIGERFLOW Systems, Inc. 4034 Mint Way Dallas, Texas 75237 214-337-8780 www.tigerflow.com TABLE OF CONTENTS Introduction... 4 Sequence of Operation... 5

More information

K-Controller Brochure.qxp_ Controller Brochure 2/27/17 3:03 PM Page 4 Versa IC Platform

K-Controller Brochure.qxp_ Controller Brochure 2/27/17 3:03 PM Page 4 Versa IC Platform Versa IC Platform VERSA IC Integrated Control Platform Raypak s VERSA IC combines modulating temperature control, safety limits, and ignition programming into one user- friendly Integrated Control Platform.

More information

3750 Pulpress pressurisation unit. Installation and operating instructions

3750 Pulpress pressurisation unit. Installation and operating instructions 3750 Pulpress pressurisation unit Installation and File No: 37.858uk Date: september 02, 2016 Supersedes: 37.858uk Date: october 05, 2015 contents 1.0 ce conformities 4 2.0 Preface 4 3.0 Introduction

More information

SEQUENCE OF OPERATIONS

SEQUENCE OF OPERATIONS SEQUENCE OF OPERATIONS DDC CONTROLLER: Controller with integral LCD readout for changing set points and monitoring unit operation. Provided with required sensors and programming. Factory programmed, mounted,

More information

Tri-Stack Smart System

Tri-Stack Smart System Tri-Stack Smart System TM Notes & Warnings - The protection provided by this equipment may be impaired if it is not used in the manner specified herein. - Ensure all wiring meets applicable national and

More information

SCC Inc. TS Series. Technical Instructions. Document No. TS 1000 June 25, TS Touchscreen Kits. Description. Touchscreen

SCC Inc. TS Series. Technical Instructions. Document No. TS 1000 June 25, TS Touchscreen Kits. Description. Touchscreen TS Touchscreen Kits for use with LMV3, LMV5 and RWF Controls June 25, 2018 Touchscreen Description Plate Kit Enclosure TS series touchscreen kits provide a human machine interface (HMI) with a Siemens

More information

EOS INTERFACE GUIDE AND POINTS LIST For EOS BTCII Firmware Version J1239D-570 and newer

EOS INTERFACE GUIDE AND POINTS LIST For EOS BTCII Firmware Version J1239D-570 and newer Installation and interface must be performed by a qualified controls technician. IMPORTANT: THIS MANUAL CONTAINS INFORMATION REQUIRED FOR INSTALLATION, INTERFACE AND CONFIGURATION OF THIS EQUIPMENT. READ

More information

Operational Overview and Controls Guide

Operational Overview and Controls Guide DOCUMENT: ECSEQ2-2 EFFECTIVE: 02/26/10 SUPERSEDES: 02/14/07 Operational Overview and Controls Guide Standard Two or Three Pump Type VFD Booster Controls 6700 Best Friend Road. Norcross, GA 30071. (770)

More information

Lift Station Level Controller

Lift Station Level Controller Lift Station Level Controller Installation and Operation Manual 1 California Motor Controls, Inc. Benicia, CA Table of Contents 1. Features Product Overview... 4-6 Access Security... 7 Optional Features...

More information

MYRIAD DPC DUPLEX PUMP CONTROLLER INSTRUCTION MANUAL VERSION 3.7

MYRIAD DPC DUPLEX PUMP CONTROLLER INSTRUCTION MANUAL VERSION 3.7 MYRIAD DPC DUPLEX PUMP CONTROLLER INSTRUCTION MANUAL VERSION 3.7 VISIT OUR WEBSITE SIGMACONTROLS.COM MYRIAD DPC MANUAL 013114 1 2 TABLE OF CONTENTS INTRODUCTION 3 Ordering Information Specifications Features

More information

Carbon Monoxide Transmitter

Carbon Monoxide Transmitter Introduction The CO Transmitter uses an electrochemical sensor to monitor the carbon monoxide level and outputs a field-selectable 4-20 ma or voltage signal. The voltage signal may also be set to 0-5 or

More information

LMV52 Control. Specifications. Document No. LV February 3, Product Description. Sample Specification

LMV52 Control. Specifications. Document No. LV February 3, Product Description. Sample Specification LMV52 Control Product Description February 3, 2017 The LMV52 is a microprocessor-based burner management system with matching system components for the control and supervision of forced draft burners.

More information

MYRIAD TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL

MYRIAD TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL MYRIAD TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL MYRIAD TPC VISIT OUR WEBSITE SIGMACONTROLS.COM MYRIADI&O062705 2 TABLE OF CONTENTS INTRODUCTION 3 Ordering Information Specifications Features WIRING 7,8

More information

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA 99336 www.jmcvr.com 1-509-586-9893 Table of Contents TABLE OF FIGURES...1 OVERVIEW OF THE HRC CAPABILITIES...2 INSTALLATION AND

More information

New Versa IC Platform

New Versa IC Platform New Versa IC Platform Electronic Temperature Controllers Engineered for Raypak Boilers & Water Heaters Leading-Edge Controllers For over 60 years, Raypak s low-mass, high-recovery designs have set the

More information

GeneSys Air-Cooled Screw Compressor Chiller

GeneSys Air-Cooled Screw Compressor Chiller Operation Manual OM AGSB-5 Group: Chiller Part Number: 331373201 Date: June 2005 Supersedes: OM AGSB-4 GeneSys Air-Cooled Screw Compressor Chiller AGS 230A/B through AGS 475A/B, 60 Hertz AGS 206A/B through

More information

PLC / HMI Modbus (Slave) Addressing

PLC / HMI Modbus (Slave) Addressing Made in the USA PLC / HMI Modbus (Slave) Addressing Legacy - HMI touch screen with built in Legacy - Pentra PLC with Expandable I/O Legacy Chiller Systems, Inc. General Information IMPORTANT READ BEFORE

More information

DACC - NMDA BUILDINGS

DACC - NMDA BUILDINGS A PROJECT FOR: LAS CRUCES, NEW MEXICO PROJECT LOCATION LOCATION MAP INDEX OF DRAWINGS: CV001 - COVER SHEET M101 - OVERALL CAMPUS STEAM UTILITY PLAN M102 - DACC DAMA 341 PLAN M103 - DACC LRC & CLASSROOM

More information

LMV51 Control. Specifications. Document No. LV February 7, Product Description. Sample Specification

LMV51 Control. Specifications. Document No. LV February 7, Product Description. Sample Specification SCC Inc. LMV51 Control Product Description February 7, 2017 The LMV51 is a microprocessor-based burner management system with matching system components for the control and supervision of forced draft

More information

C-TRAC3 COMMUNICATION MANUAL FOR. BACnet NOVEMBER 2010 TO JANUARY 2014 USA HEAD OFFICE AND FACTORY

C-TRAC3 COMMUNICATION MANUAL FOR. BACnet NOVEMBER 2010 TO JANUARY 2014 USA HEAD OFFICE AND FACTORY A C-TRAC3 COMMUNICATION MANUAL FOR BACnet NOVEMBER 2010 TO JANUARY 2014 UNIT MODEL NO. UNIT SERIAL NO. SERVICED BY: TEL. NO: CANADIAN HEAD OFFICE AND FACTORY 1401 HASTINGS CRES. SE CALGARY, ALBERTA T2G

More information

CELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL

CELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL Operation Manual Celltrol II Bioreactor Control System Page 1 of 33 Table of Contents 1) Introduction... 3 1.1) Scope of Document... 3 1.2) Control System Overview... 3 1.3) Introduction to Celltrol II...

More information

CLEANROOM MONITOR CR3A Network - Installation Instructions

CLEANROOM MONITOR CR3A Network - Installation Instructions CLEANROOM MONITOR CR3A Network - Installation Instructions INTRODUCTION The CR3 Series Cleanroom Monitor, was developed specifically to allow for monitoring of confined spaces with accuracy and reliability.

More information

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL SECTION 15910 SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division

More information

SECTION PACKAGED HEAT TRANSFER SYSTEM

SECTION PACKAGED HEAT TRANSFER SYSTEM PACKAGED HEAT TRANSFER SYSTEM Page 1 of 6 SECTION PACKAGED HEAT TRANSFER SYSTEM 1 GENERAL 1.1 SUMMARY A. Packaged steam-to-water heat transfer system 1.2 REFERENCES A. ASHRAE American Society of Heating,

More information

PWM. Solar Charge controller with Ethernet. Solar Smart PWM 20Amp. Hardware Description : Release : 19 June 2014

PWM. Solar Charge controller with Ethernet. Solar Smart PWM 20Amp. Hardware Description : Release : 19 June 2014 Solar Charge controller with Ethernet Release : 19 June 2014 Hardware Version : Version 1 Firmware version 1 PC Application Software : Version 1.0.0.0 Hardware Description : The Solar Smart regulator was

More information

WATER HEATER ELECTRONIC CONTROLLER USER MANUAL

WATER HEATER ELECTRONIC CONTROLLER USER MANUAL WATER HEATER ELECTRONIC CONTROLLER USER MANUAL UPPER LED READOUT LED ICONS LOWER LED READOUT PVI INDUSTRIES, LLC - Fort Worth, Texas 76111 - Web www.pvi.com - Phone 1-800-433-5654 Page 1 / 7 PV500-40 03/17

More information

Suggested Specification: Benchmark 1.5 Low NOx Gas-Fired Hydronic Boiler(s)

Suggested Specification: Benchmark 1.5 Low NOx Gas-Fired Hydronic Boiler(s) Furnish and install as shown on AERCO International plans and operation and maintenance manuals, with all applicable codes and authorities having local, state and federal jurisdiction, Benchmark Series

More information

CAREL heatersteam Electric Element Steam Humidifiers

CAREL heatersteam Electric Element Steam Humidifiers Suggested Engineering Specifications Section 23 84 13 CAREL heatersteam Electric Element Steam Humidifiers 1. GENERAL SCOPE 1. Furnish and install as indicated on the drawings and plans, in-duct [space]

More information

Micro-VPAC IIT LSC - Lift Station Controller. User Manual. Version 1.0.2

Micro-VPAC IIT LSC - Lift Station Controller. User Manual. Version 1.0.2 Micro-VPAC IIT LSC Micro-VPAC IIT LSC - Lift Station Controller User Manual Version 1.0.2 Table of Contents ii CHAPTER: Table of Contents Contents Introduction 5 General 6 Control Description 6 Manual

More information

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER This manual must be left with owner and should be hung on or adjacent to the boiler for reference. US HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER MODELS CHS-85 through CHS-399 APPENDIX A CONTROLLER

More information

Analog Room Pressure Monitor RPC Series

Analog Room Pressure Monitor RPC Series Description The Room Pressure Monitor is used to measure differential pressure in the range of 0.125 to 1"wc or 30 to 250 Pa. It combines precision high sensitivity silicon sensing capabilities and the

More information

Lift Station Monitoring & Control The process begins here

Lift Station Monitoring & Control The process begins here Lift Station Monitoring & Control The process begins here Standards Certification Education & Training Publishing Conferences & Exhibits Speakers: Alan Vance E+H Industry Mgr W/WW Terry Sages Rockwell

More information

Table of Contents 1. OVERVIEW SYSTEM LAYOUT SPECIFICATIONS FUNCTION... 11

Table of Contents 1. OVERVIEW SYSTEM LAYOUT SPECIFICATIONS FUNCTION... 11 Table of Contents 1. OVERVIEW... 3 2. SYSTEM LAYOUT... 4 3. SPECIFICATIONS... 8 3.1 SYSTEM COMPONENTS...9 3.2 PLC INPUTS AND OUTPUTS...9 3.3 FUNCTION KEYS...10 3.4 DEFAULT SET POINTS AND TIMERS...10 4.

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

READ AND SAVE THESE INSTRUCTIONS

READ AND SAVE THESE INSTRUCTIONS XXXXXXX-0 EN 1904 READ AND SAVE THESE INSTRUCTIONS BASIC-PLC CONTROLLER MANUAL For all Condair desiccant dryer with equipped with Basic- PLC valid from version: PLC-35/PLC-45 18.04.03 Dehumidification

More information

OnTrac Boiler Management System

OnTrac Boiler Management System OnTrac Boiler Management System CS-4 & CS-8 Setup and Operation Manual 3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918 Page 1 Table of Contents Caution... 5 Specifications:... 5 Overview...

More information

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment. SECTION 23 09 93 - SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1 WORK INCLUDES A. Base Bid: Heating Contractor provide: Control sequences for HVAC systems, subsystems, and equipment. B. Alternate

More information

Table of Contents. W2W Open

Table of Contents. W2W Open W2W Open Points and Properties CARRIER CORPORATION 2013 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-457-01 3/27/2013 Table of Contents Introduction... 1

More information

LaserRobot. Controller s User Manual. Hotline: Add: 1500xinfei Road No.72, Shanghai, China

LaserRobot. Controller s User Manual. Hotline: Add: 1500xinfei Road No.72, Shanghai, China LaserRobot Controller s User Manual Hotline: +86 400-670-1510 Email: sales@empower.cn Add: 1500xinfei Road No.72, Shanghai, China Version: V1.0 Date: 2017/12/22 Historical Version: Historical Version Date

More information

MicroTech Series-200 Flooded Screw Chiller

MicroTech Series-200 Flooded Screw Chiller Open Protocol Data Infomation Packet Version 1.0 Group: Controls Date: February 1997 MicroTech Series-200 Flooded Screw Chiller Open Protocol Data Communications 2002 McQuay International - C O N F I D

More information

B-40/B-41 Modulating Temperature Controller

B-40/B-41 Modulating Temperature Controller INSTALLATION & OPERATING INSTRUCTIONS B-40/B-41 Modulating Temperature Controller For Raytherm Boilers & Water Heaters H2 514-4001 WH2 2100-4001 Catalog No. 5000.70 Effective: 12-21-11 Replaces: NEW P/N

More information

Reference Guide for Microprocessor Controller

Reference Guide for Microprocessor Controller Document 483586 Microprocessor Controller for Dedicated Outdoor Air System Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before

More information

Two-Channel Gas Controller

Two-Channel Gas Controller Two-Channel Gas Controller Specifications subject to change without notice. USA 09 Page of DESCRIPTION Highly configurable, UL 0 performance-tested and -certified, and wall-mounted gas monitor; continuously

More information

Wilo CO-Helix Booster Systems. Product Presentation July, 2017

Wilo CO-Helix Booster Systems. Product Presentation July, 2017 Wilo CO-Helix Booster Systems Product Presentation July, 2017 Pioneering for You Intelligent Pumps Save energy & optimize performance Technological innovation focus largest R&D development facility in

More information

RPM1600 Series Room Pressure Monitors

RPM1600 Series Room Pressure Monitors RPM1600 Series Room Pressure Monitors Technical Bulletin LB-RPM1611-0, LB--0 Code No. LIT-12012228 Issued October 2017 Refer to the QuickLIT website for the most up-to-date version of this document. How

More information

Process & TeMPerATUre UniversAl input DigiTAl MeTers

Process & TeMPerATUre UniversAl input DigiTAl MeTers Process & TeMPerATUre UniversAl input DigiTAl MeTers nova PD56 series Thermocouple, rtd, & Process inputs Universal Power supply 1-24 va c Up to 3 Alarm relays retransmitting 4-2 ma output input Max/Min

More information

S F IT 6" / 8"HES. Quick Installation Guide. franklinwater.eu

S F IT 6 / 8HES. Quick Installation Guide. franklinwater.eu GB D S F IT 6" / 8"HES Quick Installation Guide franklinwater.eu Summary Page English 5-19 Deutsch 25-39 Svenska 44-60 French 63-81 Italian 84-101 GB 6" / 8"HES Quick Installation Guide franklinwater.eu

More information

Trinity Lx400 High Efficiency Gas Condensing Boiler & Water Heater

Trinity Lx400 High Efficiency Gas Condensing Boiler & Water Heater Part I - General Part II - Product Part III - Installation Project Name: Location: Engineer: Contractor: I. GENERAL Rep: Date: A. Supply and install modulating and condensing boiler(s)/water heater(s)

More information

Control manual. Series. Gas-fired direct vent Cast iron boilers. Control adjustment and Operation instructions

Control manual. Series. Gas-fired direct vent Cast iron boilers. Control adjustment and Operation instructions KNCT2-808 KN Series Gas-fired direct vent Cast iron boilers Models KN-6, -10, -20 only (HeatNet control firmware edition 45 ) Control manual Control adjustment and Operation instructions Also read and

More information

MODEL 4100-LEV. Level Monitor. User Manual

MODEL 4100-LEV. Level Monitor. User Manual MODEL 4100-LEV Level Monitor User Manual Technical Support Continental North America Toll Free 1-(800) 387-9487 Ph: +1 (905) 829-2418 Fx: +1 (905) 829-4701 A Product of Arjay Engineering Ltd. Oakville,

More information

Modbus RTU RS485 Manual

Modbus RTU RS485 Manual Modbus RTU RS485 Manual AUTOMATED FUEL MAINTENANCE SYSTEMS FTI-5A, FTI-10A, FTI-20A FUEL TECHNOLOGIES INTERNATIONAL 06/10/2014 Rev B - Fuel Technologies - Modbus The Modbus Communications Setup Button

More information

LC150 VIEW-AT-A-GLANCE PUMP CONTROL-TELEMETRY UNIT

LC150 VIEW-AT-A-GLANCE PUMP CONTROL-TELEMETRY UNIT LC150 VIEW-AT-A-GLANCE PUMP CONTROL-TELEMETRY UNIT Simply Features In Brief Telemetry Ready Security 2 or 3 Pump Control UL Listed Alarm/Event Log Volumetric Flow Calculator VFD Control Optional Dialer

More information

Trinity Lx200 High Efficiency Gas Condensing Boiler & Water Heater

Trinity Lx200 High Efficiency Gas Condensing Boiler & Water Heater Part I - General Part II - Product Part III - Installation Project Name: Location: Engineer: Contractor: I. GENERAL Rep: Date: A. Supply and install modulating and condensing boiler(s)/water heater(s)

More information

SCC Inc. TS Series. Technical Instructions. Document No. TS 5000 February 12, TS CE Combustion Enclosures with LMV3.

SCC Inc. TS Series. Technical Instructions. Document No. TS 5000 February 12, TS CE Combustion Enclosures with LMV3. TS CE Combustion Enclosures with LMV3 February 12, 2019 Description TS CE series combustion enclosure with Siemens LMV3 linkageless controller sets the new standard for combustion control and monitoring

More information

MicroTech Unit Ventilator

MicroTech Unit Ventilator Open Protocol Data Information Packet Version 2.2 Group: Controls Date: April 1996 MicroTech Unit Ventilator Open Protocol Data Communications 2002 McQuay International - C O N F I D E N T I A L - This

More information

Ventilation in balance

Ventilation in balance Ventilation in balance control and operation Airlinq IF 2013 The Airlinq AM L control panel has won two design awards at if 2013 for its innovative design one award for if product design and if communication

More information

Trinity Tft High Efficiency Gas Condensing Boiler & Water Heater

Trinity Tft High Efficiency Gas Condensing Boiler & Water Heater Part I - General Part II - Product Part III - Installation Project Name: Location: Engineer: Contractor: I. GENERAL Rep: A. Supply and install modulating and condensing boiler(s) as specified herein. Date:

More information

SmartVFD HVAC and BYPASS

SmartVFD HVAC and BYPASS SmartVFD HVAC and BYPASS The Smart Choice for Energy Savings. Saving Energy the Smart Way Buildings consume more than 70 percent of the electricity produced in North America and roughly half of that is

More information

PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS

PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS NOVA PD56 Series Thermocouple, RTD, & Process Inputs Universal Power Supply 1-24 VAC Up to 3 Alarm Relays Retransmitting 4-2 ma Output Input Max/Min

More information

Installation, Operation, and Maintenance Manual

Installation, Operation, and Maintenance Manual Installation, Operation, and Maintenance Manual RECEIVING AND INSPECTION Upon receiving unit, check for any interior and exterior damage, and if found, report it immediately to the carrier. Also check

More information

CM3500 Controller - ClimateMaster DOAS Water-Source Heat Pumps - Rev.: 7 Oct, 2008B

CM3500 Controller - ClimateMaster DOAS Water-Source Heat Pumps - Rev.: 7 Oct, 2008B 2 CM3500 Controller - ClimateMaster DOAS Water-Source Heat Pumps - Rev.: 7 Oct, 2008B CAUTION CAUTION - ONLY TRAINED, QUALIFIED PERSONNEL SHOULD INSTALL AND/OR SERVICE CLIMATEMASTER EQUIPMENT. SERIOUS

More information

AIS750 Series Alarm Annunciator

AIS750 Series Alarm Annunciator Unparallel, modular, multipoint design with Integrated controllers Two Operation Modes (Stand-alone & Serial) All sizes confi gurable up to 440 Alarm Points RS485 / RS232 Serial Communication Manual &

More information

Specification , July 2015

Specification , July 2015 Technical Information PrecisionLine Controllers EDC21 / EDC22 / EDC23 EASYSET DIGITAL CONTROLLERS Specification 51-52-3-48, July 215 Introduction The EDC21, EDC22 and EDC23 controllers provide precise

More information

WaterFurnace FX10 Application Guide Reversible Chiller

WaterFurnace FX10 Application Guide Reversible Chiller 2011 WaterFurnace FX10 Application Guide Reversible Chiller Introduction This manual provides information about the FX10 Water Source Heat Pump (WSHP) controller as it relates to dual compressor water

More information

OPERATING MANUAL Enertronic Control System 2

OPERATING MANUAL Enertronic Control System 2 OPERATING MANUAL Enertronic Control System 2 The integrated control system for Lennox chillers in the Ecologic range Manufacturer: Lennox Benelux B.V. Postbus 1028, 3860 BA NIJKERK Watergoorweg 87, 3861

More information

Open Protocol Data Communications

Open Protocol Data Communications MicroTech Series-100 Centrifugal Chiller Open Protocol Data Communications Information Packet Version 3.2 April, 1996 - C O N F I D E N T I A L - This Document may not be copied or reproduced in any way

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas 67357 Telephone: 620-421-0480,

More information

Temperature + Humidity (%RH) Control & Recording System with 8 / 16 Channel Mapping. Touch Panel PPI

Temperature + Humidity (%RH) Control & Recording System with 8 / 16 Channel Mapping. Touch Panel PPI HumiTherm Ultra Temperature + Humidity (%RH) Control & Recording System with 8 / 16 Channel Mapping Mapping Unit Micro PLC Control Unit Touch Panel Touch Operation Panel PPI HumiTherm Ultra GSM Module

More information

SmartVFD HVAC and BYPASS

SmartVFD HVAC and BYPASS SmartVFD HVAC and BYPASS The Smart Choice For Energy Savings Energy Savings Are Smart For You. And Smart For The World. About three-quarters of the energy consumed by commercial buildings is in the form

More information

DAP III Zone Master User s Guide

DAP III Zone Master User s Guide DAP III Zone Master User s Guide Data Aire, Inc. 230 West BlueRidge Avenue Orange, California 92865 Document Number 600-000-788 March 2010 Revision 1.0 Document # 600-000-788 1 Overview The Data Aire DAP

More information

RS485 MODBUS Module 8AI

RS485 MODBUS Module 8AI Version 1.4 15/04/2013 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have

More information

Wiser Air User Interface Guide. Thermostat

Wiser Air User Interface Guide. Thermostat Wiser Air User Interface Guide Thermostat 2 User Guide Wiser Air Scope This document outlines the user interface features of the Wiser Air smart thermostat. It is intended to support individual users and

More information

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products Document 475595 Microprocessor Controller for Tempered Air Products Reference Guide for the Microprocessor Controller Please read and save these instructions. Read carefully before attempting to operate

More information

1 INTRODUCTION SYSTEM DESCRIPTION... 3

1 INTRODUCTION SYSTEM DESCRIPTION... 3 1 INTRODUCTION... 1 2 SYSTEM DESCRIPTION... 3 3 INSTALLATION... 5 3.1 INPUT/OUTPUT POSITIONING... 5 3.2 CONTROLLER WIRING... 6 3.2.1 Dual Fuel... 6 Single Fuel... 7 3.3 BUILT-IN ANALOG INPUTS...8 4 GENERAL

More information

2017 products.koer.com Page 1 of 14

2017 products.koer.com Page 1 of 14 VAV Parameters 2017 products.koer.com Page 1 of 14 INTRODUCTION Learn how to setup various VAV parameters and configurations, PID calculation elements, EC motor voltages, wall type etc. 2017 products.koer.com

More information

OVEN INDUSTRIES, INC.

OVEN INDUSTRIES, INC. OVEN INDUSTRIES, INC. OPERATING MANUAL Model 5C7-252 TEMPERATURE CONTROLLER With PLC Inputs Introduction Thank you for purchasing our controller. The Model 5C7-252 is an exceptionally versatile unit and

More information

Oxygen (O2) Single-Point Gas Detection System

Oxygen (O2) Single-Point Gas Detection System Oxygen (O) Single-Point Gas Detection System DESCRIPTION Wall-mounted gas monitor with built-in oxygen (O) sensor, accepts one analog remote device such as a secondary gas sensor, temperature or humidity

More information

Added password for IP setup page : Password must be in IP format!

Added password for IP setup page : Password must be in IP format! NETWORK POWER MONITOR Release : 21 August 2014 Hardware Version : Version 7 Firmware version 1.00 PC Application Software : Version (latest)...2 Added password for IP setup page : Password must be in IP

More information

Updated: 17/03/2010 ELECTROLUX. CAREL ir33. Quick reference Handbook. Ver. 1.1 Eng. Pag.1/12

Updated: 17/03/2010 ELECTROLUX. CAREL ir33. Quick reference Handbook. Ver. 1.1 Eng. Pag.1/12 CAREL ir33 Quick reference Handbook Pag.1/12 MAIN FEATURES OF THE INSTRUMENT USER INTERFACE 1. ON/OFF switch button UP button to increase temperature values 2. DOWN button to decrease values - Activates/deactivates

More information

Dryer Master DM510 Commissioning Guide

Dryer Master DM510 Commissioning Guide COMMISSIONING GUIDE Dryer Master DM510 Dryer Moisture Systems Inc. 640 Superior Drive Waterloo, Ontario Phone 519.725.4700 Fax 519.885.4300 USA & Canada Toll Free 1-888-318-0009 E-mail: info@dryermaster.com

More information

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

Nitrogen Dioxide (NO2) Single-Point Gas Detection System Nitrogen Dioxide (NO) Single-Point Gas Detection System DESCRIPTION Wall-mounted gas monitor with built-in nitrogen dioxide (NO)/diesel fume gas sensor, accepts one analog remote device such as a secondary

More information

I/A Series 716C 1/16 DIN Temperature Controller

I/A Series 716C 1/16 DIN Temperature Controller Product Specifications I/A Series 716C 1/16 DIN Temperature Controller PSS 2C-1B5 A The Foxboro 716C is a powerful compact, 1/16 DIN, microprocessor-based temperature controller that offers a variety of

More information

TYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM

TYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM 2 Line, 16 Characters/row LCD Display Temperature Input Range -50 C to +500 C -58 F to + 932 F Enclosure NEMA Type 4X Current Rating 30A max (resistive load only) Ambient Temperature -40 C to + 40 C -40

More information

UDC1000 and UDC1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS

UDC1000 and UDC1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS UDC1000 and UDC1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS EN0I-6041 4/01 PRODUCT SPECIFICATION SHEET OVERVIEW The UDC1000 and UDC1500 are microprocessor-based 1/16 DIN and 1/8 DIN controllers

More information

MODEL 4100-OWS. Oil/Water Separator Level Monitor. User Manual

MODEL 4100-OWS. Oil/Water Separator Level Monitor. User Manual MODEL 4100-OWS Oil/Water Separator Level Monitor User Manual Technical Support Continental North America Toll Free 1-(800) 387-9487 Ph: +1 (905) 829-2418 Fx: +1 (905) 829-4701 A Product of Arjay Engineering

More information

American University Design Standards

American University Design Standards 25 95 00 CONTROL SEQUENCES FOR HVAC PART 1. GENERAL 1.01 SECTION INCLUDES A. Description of Work B. Control Sequences General Requirements C. System Specific Control Sequences 1.02 RELATED DOCUMENTS A.

More information

Project Name: Location: Engineer: Contractor: I. GENERAL

Project Name: Location: Engineer: Contractor: I. GENERAL Part I - General Part II - Product Part III - Installation Project Name: Location: Engineer: Contractor: I. GENERAL I. PRODUCT Rep: Date: A. Supply and install modulating and condensing boiler(s) as specified

More information

OPERATION AND MAINTENANCE MANUAL. Electrode Steam Humidifier Nortec EL Series

OPERATION AND MAINTENANCE MANUAL. Electrode Steam Humidifier Nortec EL Series 2582954_C_EN_1611 IMPORTANT! Read and save these instructions. This manual to be left with the equipment. OPERATION AND MAINTENANCE MANUAL Electrode Steam Humidifier Nortec EL Series Humidification and

More information

Pre-Cool and Free- Cool Fan Control

Pre-Cool and Free- Cool Fan Control 5/26/2014 Pre-Cool and Free- Cool Fan Control ArcticCool Chillers ArcticCool Chillers Limited Authored by: Casey Smith ArcticCool Chillers Limited Pre-Cool and Free-Cool Fan Control Sequence of Operations

More information

APPLICATION DATA SHEET

APPLICATION DATA SHEET APPLICATION DATA SHEET Control Systems Transmitters Sensors Accessories Wall, 19 Rack or Panel Mounting Units 110/230V 50/60Hz AC operation 250 Addressable devices as: Relays, 4-20 Inputs or Gas Detectors

More information