1 , Inc. Interfacing Fire Alarm, Sprinkler and Elevator Systems In Maryland, DC and Virginia Presented by: Andrew Roe, SET Alarm Tech Solutions, LLC

2 Scope: The Purpose of Elevator Controls History of Elevator Controls & Sprinklers Elevator Recall and Power Shutdown Relevant Codes What our local AHJ s are enforcing Discussion of issues Where we appear to be headed 2

3 Purpose: 1973 ASME A17.1b (supplement to the 1971 Code) Purpose: Prevent people from using elevators during a fire scenario To Allow for Responding Firefighters to Account for all Elevators Stage Equipment (Hose lines, air tanks, etc.) Evacuate Occupants with Mobility Restrictions Prevent Car from being called to the Fire Floor 3

4 4

5 History - Controls: 1973 ASME A17.1b (supplement to the 1971 Code): Identified Designated Level Both Manual and Automatic Recall Key Switch (only by firefighters) Smoke Detectors in Lobbies Travel of 25 above or below designated level 1981 introduced the Alternate Level 5

6 History - Controls: 1984 introduced only lobby and machine detectors were to initiate recall A17.1 referred users to NFPA 72E, Automatic Fire Detectors NFPA first mentions A17.1 requirements in 1987 edition of NFPA 72A, Installation, Maintenance and use of Local Protective Signaling Systems Elevator Recall for Firefighters Service 1993 edition of NFPA 72, National Fire Alarm Code addressed cases where there was no required building fire alarm system Elevator Recall and Supervisory Panel 6

7 History - Controls: 1996 edition of NFPA 72 introduced other fire detection as being permissible if environment was not appropriate for a smoke detector. A third control circuit was added to provide a warning of fire in the hoistway or elevator machine room The 2000 A17.1 was harmonized with the Canadian B44 Elevator Safety Standard NFPA 72 [2002] and A17.1 [2004] now both address new technology elevators machine room-less elevators 7

8 History - Controls: First introduced in ASME A Purpose: Remove Main-line Power prior to sprinkler activation Prevent Elevator from Moving/Operating dangerously Note: the requirement does not include circuits for ventilation, in-car lights and communication, pit receptacles and lights, etc. 8

9 History - Controls: A17.1 applies to all new elevator installations A17.3 (where adopted) applies to existing elevators A17.3 re: Firefighters Service Firefighters Service Elevators shall conform to the requirements of ASME/ANSI A Rules through (see Appendix C) unless at the time of installation or alteration it was required to comply with a later edition of A

10 History - Sprinklers: Sprinklers in elevator machine rooms and hoistways have been recognized by the Safety Code for Elevators and Escalators, ASME A17.1 since the 1955 Edition. The building codes at first did not require buildings to be sprinkled but encouraged their use by allowing tradeoffs (fire resistance ratings, distances to exits & area and height limitations) which reduced the cost of construction. This tradeoff worked well and now the building codes require most buildings to be fully sprinkled. 10

11 History - Sprinklers: In the early 1980 s the ASME A17.1 Committee became aware of this trend and initiated a study of the hazards of water being discharged on elevator equipment. Some of the reported hazards include cars operating with car and/or hoistway doors opened, loss of brakes and loss of traction. There are numerous cases of elevators leaving a floor with the doors open which have been traced back to wet interlocks and control circuits. 11

12 History - Sprinklers: The ASME A17.1 Committee could not blindly prohibit sprinklers in elevator machine rooms and hoistways since if a building code or fire code required sprinklers in all areas of a building, that code would be enforced regardless of any contrary requirement that would be in the elevator code. The Committee did approach the building and fire code community with a proposal that sprinklers not be required in elevator spaces in fully sprinkled buildings but this was rejected. 12

13 History - Sprinklers: The ASME A17.1 Committee, aware of its responsibility to ensure the safety if the elevator user, in early 1982 asked Edward Donoghue, a member of the ASME A17.1 Hoistway Committee, to contact the National Fire Sprinkler Association and discuss the issue. They came up with 3 recommendations: shields and raintight covers was impractical as they would over a period of time, be removed or become ineffective and how would you test them anyway? 13

14 History - Sprinklers: Another recommendation was to use gaseous extinguishing agents in lieu of sprinklers but this was also discarded as its ability to provide the required level of protection was questionable. The third recommendation to disconnect main line power to the elevator before sprinkler activation, was acceptable, was reworded in performance language, balloted, approved by the ASME A17 Main Committee and published as Rule 102.2(c)(4) in ANSI/ASME A

15 International Building Code : Referenced codes and standards. The codes and standards referenced in this code shall be considered part of the requirements of this code to the prescribed extent of each such reference. Where differences occur between provisions of this code and referenced codes and standards, the provisions of this code shall apply. 15

16 Elevator Controls (A ): Firefighters' Emergency Operation: Automatic Elevators Firefighters' Emergency Operation shall apply to all automatic elevators except a) where the hoistway or a portion thereof is not required to be fire-resistive construction (see ), the travel does not exceed mm (80 in.), and the hoistway does not penetrate a floor Where Firefighters' Emergency Operation is provided voluntarily these requirements shall also apply. 16

17 Elevator Controls (A ): Phase I Emergency Recall Operation A three-position key-operated switch shall be a) provided only at the designated level for each single elevator or for each group of elevators. b) labeled "FIRE RECALL' and its positions marked "RESET," "OFF," and "ON (in that order), with the "OFF" position as the center position. 17

18 Elevator Controls (A ): Phase I Emergency Recall Operation by Fire Alarm Initiating Devices In jurisdictions not enforcing the NBCC, fire alarm initiating devices used to initiate Phase I Emergency Recall Operation shall be installed in conformance with the requirements of NFPA 72, and shall be located a) at each floor served by the elevator b) in the associated elevator machine room c) in the elevator hoistway, when sprinklers are located in those hoistways 18

19 Elevator Controls (A ): Phase I Emergency Recall Operation to the designated level shall conform to the following: a) The activation of a fire alarm initiating device specified in (a) at any floor, other than at the designated level, shall cause all elevators that serve that floor, and any associated elevator of a group automatic operation, to be returned nonstop to the designated level. b) The activation of a fire alarm initiating device specified in (b) shall cause all elevators having any equipment located in that machine room, and any associated elevators of a group automatic operation, to be returned nonstop to the designated level. If the machine room is located at the designated level, the elevator(s) shall be returned nonstop to the alternate level. c) The activation of a fire alarm initiating device specified in (c) shall cause all elevators having any equipment in that hoistway, and any associated elevators of a group automatic operation, to be returned nonstop to the designated level, except that initiating device installed at or below the lowest landing of recall shall cause the car to be sent to the upper recall level. 19

20 Elevator Controls (A ): Summary of Phase I: The detection of smoke or heat causes the elevators to be recalled to the ground floor, unless this is where smoke was detected. The doors open, and the elevators are locked out of service. Responding fire fighters may use the elevators under manual control of a fire fighter in the car using a special fire fighter key in what is called Phase-II operation. 20

21 Elevator Controls (A ): Phase II Emergency In-Car Operation. A three-position ("OFF," "HOLD," and "ON," in that order) key-operated switch shall be labeled "FIRE OPERATION; provided in an operating panel in each car; and shall be readily accessible. 21

22 Elevator Controls (A ): Summary of Phase II: Phase II operation is used to evacuate people with mobility impairments, some fire department standard operating procedures for high-rise fire fighting rely on stairs for access, staging, and operations. ASME A17.4, Guide for Emergency Personnel, contains detailed instructions for fire fighters' service operation. 22

23 Elevator Power Shutdown (A /2005): In jurisdictions not enforcing the NBCC, means shall be provided to automatically disconnect the main line power supply to the affected elevator upon or prior to the application of water from sprinklers located in the machine room or in the hoistway more than 600 mm (24 in.) above the pit floor. a) This means shall be independent of the elevator control and shall not be self-resetting. b) Heat detectors and sprinkler flow switches used to initiate main line elevator power shutdown shall comply with the requirements of NFPA 72. c) The activation of sprinklers outside of the hoistways or machine room shall not disconnect the main line elevator power supply. 23

24 Elevator Power Shutdown (IBC 2006 & 2009): Shunt trip. Where elevator hoistways or elevator machine rooms containing elevator control equipment are protected with automatic sprinklers, a means installed in accordance with NFPA 72, Section , Elevator Shutdown, shall be provided to disconnect automatically the main line power supply to the affected elevator prior to the application of water. This means shall not be self-resetting. The activation of sprinklers outside the hoistway or machine room shall not disconnect the main line power supply. 24

25 Elevator Recall (NFPA ): Elevator Recall for Fire Fighters Service System-type smoke detectors, or other automatic fire detection as permitted by , located in elevator lobbies, elevator hoistways, and elevator machine rooms including machine space, control room, and control space used to initiate fire fighters service recall, shall be connected to the building fire alarm system * In facilities without a building fire alarm system, these smoke detectors, or other automatic fire detection as permitted by , shall be connected to a dedicated function fire alarm control unit that shall be designated as elevator recall control and supervisory control unit, permanently identified on the dedicated function fire alarm control unit and on the record drawings Unless otherwise required by the authority having jurisdiction, only the elevator lobby, elevator hoistway, and the elevator machine room smoke detectors, or other automatic fire detection as permitted by , shall be used to recall elevators for fire fighters service Each elevator lobby, elevator hoistway, and elevator machine room smoke detector, or other automatic fire detection as permitted by , shall be capable of initiating elevator recall when all other devices on the same initiating device circuit have been manually or automatically placed in the alarm condition. 25

26 Elevator Recall (NFPA ): * A lobby smoke detector shall be located on the ceiling within 6.4 m (21 ft) of the centerline of each elevator door within the elevator bank under control of the detector. Exception: For lobby ceiling configurations exceeding 4.6 m (15 ft) in height or that are other than flat and smooth, detector locations shall be determined in accordance with Chapter Smoke detectors shall not be installed in unsprinklered elevator hoistways unless they are installed to activate the elevator hoistway smoke relief equipment * If ambient conditions prohibit installation of automatic smoke detection, other automatic fire detection shall be permitted When actuated, any detector that has initiated firefighters recall shall also be annunciated at the building fire alarm control unit, or other fire alarm control unit as described in , and required remote annunciators Actuation from elevator hoistway and elevator machine room smoke detectors or other automatic fire detection as permitted by shall cause separate and distinct visible annunciation at the building fire alarm control unit or the fire alarm control unit described in and required annunciators to alert fire fighters and other emergency personnel that the elevators are no longer safe to use. 26

27 Elevator Recall (NFPA ): Where approved by the authority having jurisdiction, the detectors used to initiate elevator recall shall be permitted to initiate a supervisory signal in lieu of an alarm signal Where lobby detectors are used for other than initiating elevator recall, the signal initiated by the detector shall also initiate an alarm signal * Separate outputs from the fire alarm systems to the elevator controller(s) shall be provided to implement elevator Phase I Emergency Recall Operation in accordance with Section 2.27 of ASME A17.1, Safety Code for Elevators and Escalators, as required in through

28 Elevator Power Shutdown (NFPA ): Elevator Shutdown * Where heat detectors are used to shut down elevator power prior to sprinkler operation, the detector shall have both a lower temperature rating and a higher sensitivity as compared to the sprinkler If heat detectors are used to shut down elevator power prior to sprinkler operation, they shall be placed within 610 mm (2 ft) of each sprinkler head and be installed in accordance with the requirements of Chapter 5. Alternatively, engineering methods, such as specified in Annex B, shall be permitted to be used to select and place heat detectors to ensure response prior to any sprinkler head operation under a variety of fire growth rate scenarios * If pressure or waterflow switches are used to shut down elevator power immediately upon or prior to the discharge of water from sprinklers, the use of devices with time-delay switches or timedelay capability shall not be permitted * Control circuits to shut down elevator power shall be monitored for presence of operating voltage. Loss of voltage to the control circuit for the disconnecting means shall cause a supervisory signal to be indicated at the control unit and required remote annunciators The initiating devices described in and shall be monitored for integrity by the fire alarm control unit required in and

29 Relevant Codes 29

30 Out of Sync Codes 30

31 Confused Yet? Must use A17.1, NFPA 72, NFPA 13 and IBC together to correctly apply the required elevator controls! Here s where to find them: 31

32 ASME A Section 2.27 Emergency Operation and Signaling Devices Phase I Emergency Recall Operation by Fire Alarm Initiating Devices Note: Section 2.27 applies to Electric Elevators and section 3.27 applies to Hydraulic Elevators section 3.27 says refer to

33 ASME A Section 2.8 Equipment in Hoistways, Machinery Spaces, Machine Rooms, Control Spaces and Control Rooms (Shunt Trip / Power Disconnect requirement) 33

34 NFPA Protected Premises Fire Safety Functions Emergency Elevator Operations Emergency elevator operations shall meet the requirements of Sections 21.3, 21.4, 21.5, and

35 NFPA Chapter 21 Emergency Control Functions and Interfaces 21.3* Elevator Recall for Firefighter Service 21.4 Elevator Shutdown 21.5 First Responders Use Elevators 21.6 Elevators for Occupant-Controlled Evacuation 35

36 NFPA Chapter 8 Installation Requirements 8.15 Special Situations Elevator Hoistways and Machine Rooms. 36

37 37

38 38

39 39

40 40

41 ASME A In jurisdictions not enforcing the NBCC, fire alarm initiating devices used to initiate Phase I Emergency Recall Operation shall be installed in conformance with the requirements of NFPA 72, and shall be located a) at each floor served by the elevator b) in the associated elevator machine room, machinery space containing a motor controller or electric driving machine, control space, or control room c) in the elevator hoistway, when sprinklers are located in those hoistways. 41

42 NFPA Elevator Recall for Firefighters Service Smoke detectors shall not be installed in unsprinklered elevator hoistways unless they are installed to activate the elevator hoistway smoke relief equipment If ambient conditions installation of prohibit automatic smoke detection, other automatic fire detection shall be permitted. 42

43 NFPA Smoke-Sensing Fire Detectors * Unless specifically designed and listed for the expected conditions, smoke detectors shall not be installed if any of the following ambient conditions exist: (1) Temperature below 32 F (2) Temperature above 100 F (3) Relative humidity above 93 percent (4) Air velocity greater than 300 ft/min 43

44 44

45 NFPA Elevator Recall for Firefighters Service All initiating devices used to initiate firefighters service recall, shall be connected to the building fire alarm system. 45

46 NFPA Elevator Recall for Firefighters Service * In facilities without a building fire alarm system, initiating devices used to initiate firefighters service recall shall be connected to a dedicated function fire alarm system control unit that shall be designated as elevator recall control and supervisory control unit, permanently identified on the dedicated function fire alarm control unit and on the record drawings. 46

47 NFPA Elevator Recall for Firefighters Service Unless otherwise required by the authority having the elevator machine room jurisdiction, only the elevator lobby, elevator hoistway, and elevator machine room smoke detectors shall be used to recall elevators for firefighters service. 47

48 NFPA Elevator Recall for Firefighters Service * A lobby smoke detector shall be located on the ceiling within 21 ft. of the centerline of each elevator door within the elevator bank under control of the detector. Exception: For lobby ceiling configurations exceeding 15 ft in height or that are other than flat and smooth, detector locations shall be determined in accordance with Chapter 17 (Chapter 5 in 2007 NFPA 72). 48

49 Smoke Detector Location 49

50 50

51 51

52 52

53 53

54 NFPA Location and Spacing * If the intent is to initiate action when smoke/fire threatens a specific object or space, the detector shall be permitted to be installed in close proximity to that object or space. NFPA If the intent is to protect against a specific hazard, the detector(s) shall be permitted to be installed closer to the hazard in a position where the detector can intercept the smoke. 54

55 NFPA A There are some applications that do not require full area protection, but do require detection to initiate action when specific objects or spaces are threatened by smoke or fire such as at elevator landings that have ceilings in excess of 15 ft. and for protection of fire alarm control units. In high ceiling areas, to achieve the desired initiation such as for elevator recall and protection of FACUs, detection should be placed on the wall above and within 60 in. from the top of the elevator door(s) or FACU. 55

56 56

57 57

58 58

59 NFPA Elevator Recall for Firefighters Service Actuation from the elevator hoistway, elevator machine room, elevator machinery space, elevator control space, or elevator control room smoke detectors shall cause separate and distinct visible annunciation at the building fire alarm control unit and at required annunciators to alert fire fighters and other emergency personnel that the elevators are no longer safe to use. Paragraph in NFPA is very similar. 59

60 ASME A Phase Emergency Recall Operation by Fire Alarm Initiating Devices When a fire alarm initiating device in the machine room, control space, control room or hoistway initiates Phase 1 Emergency Recall Operation, the visual signal shall illuminate intermittently only in a car(s) with equipment in that machine room, control space, control room or hoistway. 60

61 FIG (h) Visual Signal 61

62 NFPA Elevator Recall for Firefighters Service * Visual Warning. For each elevator or group of elevators, an output(s) shall be provided for the elevator visual warning signal in response to the following: (1) Activation of the elevator machine room, elevator machinery space, elevator control space, or elevator control room initiating devices identified in (2) Activation of the elevator hoistway initiating devices identified in Paragraph in NFPA is identical. 62

63 63

64 NFPA Chapter 21 - Emergency Control Functions and Interfaces * A listed relay or other listed appliance connected to the fire alarm system used to initiate control of protected premises emergency control functions shall be located within 3 ft of the controlled circuit or appliance The relay or other appliance shall function within the voltage and current limitations of the fire alarm control unit. Paragraph * in NFPA is identical. 64

65 65

66 NFPA Elevator Hoistways and Machine Rooms * Upright, pendent, or sidewall spray sprinklers shall be installed at the top of elevator hoistways The sprinkler required at the top of the elevator hoistway by shall not be required where the hoistway for passenger elevators is noncombustible or limited combustible and the car enclosure materials meet the requirements of ASME A

67 NFPA Elevator Hoistways and Machine Rooms Sprinklers shall be installed at the top and bottom of elevators that utilize polyurethane-coated steel belts or other similar combustible belt material. 67

68 NFPA Elevator Hoistways and Machine Rooms * Sidewall spray sprinklers shall be installed at the bottom of each elevator hoistway not more than 2 ft above the floor of the pit The sprinkler required at the bottom of the elevator hoistway by shall not be required for enclosed, noncombustible elevator shafts that do not contain combustible hydraulic fluids. 68

69 ASME A A /2005 allowed no power disconnect as long as sprinklers were located 24 in. or less above the pit floor. (slide 22) In jurisdictions not enforcing the NBCC, where elevator equipment is located or its enclosure is configured such that application of water from sprinklers could cause unsafe elevator operation, means shall be provided to automatically disconnect the main line power supply to the affected elevator and any other power supplies used to move the elevator upon or prior to the application of water. 69

70 NFPA Elevator Shutdown * Where heat detectors are used to shut down elevator power prior to sprinkler operation, the detector shall have both a lower temperature rating and a higher sensitivity as compared to the sprinkler. Paragraph * in NFPA is identical. 70

71 Example Use 165: F, ordinary temperature rated sprinkler. Use 135: F, thermistor-based heat detector. Or maintain a similar relationship based on ambient temperatures Note: Sprinklers in elevator machine rooms and hoistways must be of ordinary or intermediate temperature rating. (NFPA 13 [2010], ) 71

72 NFPA Elevator Shutdown * If heat detectors are used to shut down elevator power prior to sprinkler operation, they shall be placed within 24 in. of each sprinkler head and be installed in accordance with the requirements of Chapter 17(5). Alternatively, engineering methods, such as specified in Annex B, shall be permitted to be used to select and place heat detectors to ensure response prior to any sprinkler head operation under a variety of fire growth rate scenarios. Paragraph in NFPA is identical. 72

73 NFPA Elevator Shutdown * If pressure or waterflow switches are used to shut down elevator power immediately upon or prior to the discharge of water from sprinklers, the use of devices with time-delay switches or time-delay capability shall not be permitted. Paragraph in NFPA is identical. 73

74 NFPA Elevator Shutdown * Control circuits to shut down elevator power shall be monitored for presence of operating voltage. Loss of voltage to the control circuit for the disconnecting means shall cause a supervisory signal to be indicated at the control unit and required remote annunciators. Paragraph in NFPA is identical. 74

75 NFPA Elevator Shutdown * The initiating devices described in (HD) and (WFS) shall be monitored for integrity by the control unit required in Section and Paragraph in NFPA is identical. 75

76 Shunt Trip Operation (theoretical) Smoke detector actuates, causing elevator recall Elevators arrive at the recall floor and doors open Heat buildup causes heat detector to actuate Shunt trip operates, removing power from the elevator Sprinkler operates extinguishing heat source 76

77 Concern: Potential of passengers becoming entrapped in the elevator if a heat detector or waterflow switch actuates (to cause shunt trip ) prior to the completion of the recall function! An A17.1 task force was convened to discuss this concern. Recommendations included exempting sprinklers from being installed in elevator machine rooms and the top of the hoistway, delaying the release of water so recall can be completed first the delay strategy and use of the Earthquake Mode (stop at the next floor). 77

78 NFPA Elevator Shutdown A Upon activation of the heat detector used for elevator power shut down, there should be a delay in the activation of the power shunt trip. This delay should be the time that it takes the elevator cab to travel from the top of the hoistway to the lowest recall level. Identical verbiage in paragraph A of the 2007 NFPA 72 78

79 79

80 What are we doing locally? Loudoun County Fire Marshal is enforcing IBC requirement for all sprinkled elevator shafts to be provided with detection for shunt trip (smokes for recall, heats for shunt trip) Heat detectors in elevator machine rooms and elevator shafts must cause a supervisory condition and shunt trip the elevator power. Theory is that the smoke detector will already have alarmed the panel 80

81 What are we doing locally? Arlington County Fire Marshal has always enforced IBC requirement for all sprinkled elevator shafts to be provided with detection for shunt trip (smokes for recall, heats for shunt trip) Heat detectors in elevator machine rooms and elevator shafts cause an alarm condition and shunt trip the elevator power. The speakers in recalled elevator cabs must be silenced after a time delay so they don t sit on a floor that isn t on fire scaring people. 81

82 What are we doing locally? Most other jurisdictions Require all elevator shafts with sprinklers over 2 AFF to be provided with detection for shunt trip (smokes for recall, heats for shunt trip). This may of course change now. Heat detectors in elevator machine rooms and elevator shafts cause an alarm condition and shunt trip the elevator power. No AHJ is enforcing the delay mentioned in the Annex material. 82

83 Problems? The most common problem reported is a lack of understanding of what is actually required. We have heard of contractors installing heats and smokes in shafts per direction of the Fire Marshal and then having to remove them at the direction of the Elevator Inspector or vice versa. Where conflicts exist between the Building Code and the Elevator Code it is the Building Code that has the last say. Questions? 83

84 Ongoing Industry Effort 84

85 Background: Emergency egress re-examined as a result of September 11, 2001 attack on the WTC Workshop on the Use of Elevators in Fires and other Emergencies (Atlanta March 2-4, 2004) 85

86 Tall Buildings: made us re-examine the way we look at high-rise buildings and evacuation strategies 86

87 2004 Workshop: Co-sponsored by ASME, NIST, ICC, NFPA, IAFF, and the US Access Board 20 attendees representing a cross section of industry 20 Fire service representatives funded by NIST and FEMA 87

88 Workshop Program: Focus: Use of Elevators by Firefighters Use of Elevators by Occupants During Emergencies Goal: to develop proposals that can be submitted to various code writing organizations 88

89 Workshop: Steering Committee: made up of representatives from each of the sponsoring organizations Review breakout groups recommendations Develop a prioritized list of issues Conduct a hazard analysis of the issues Draft code revision proposals addressing those issues 89

90 Process: ASME took lead on the hazard analysis 2 Task Groups were formed Occupant Use to evaluate the use of elevators for egress in emergencies what can be done to decrease egress time Firefighter Use to evaluate use of elevators by firefighters during fire operations what can be done to mitigate existing hazards 90

91 Consistent Themes - Concerns: Culture change since 9-11 total evacuation Elevators are not a substitute for stairs Evacuation of mobility impaired people Lack of firefighter confidence in using elevators Elevator reliability issues Water entering hoistways 91

92 Consistent Themes - Concerns: Rescue of passengers Shunt trip entrapment Loss of elevator power from elsewhere in the building Retraining occupants to use elevators (in some buildings) Cost concerns Not enough information for occupants to make an informed decision 92

93 Consistent Themes - Recommendations: Mandatory adoption of ASME A17.3 everywhere Ensure reliability of Phase I, Phase II operation Better training on elevator operation for firefighters Regular testing by qualified (certified?) personnel Building Emergency Action Plan enforcement 93

94 Consistent Themes - Recommendations: Sprinkler all buildings Compartmented/pressurized lobbies/vestibules Area of Refuge / Rescue Assistance Better real time communications to occupants Better real time communications to firefighters Elevator technician respond to building emergencies 94

95 Consistent Themes - Process: Utilize Hazard Analysis Involve firefighters in decisions Involve appropriate committees and organizations (A17-B44, IBC, NFPA, Access Board, etc.) 95

96 Process: Hazard Analysis (not a risk analysis) Develop scenarios Identify hazards Mitigate the hazard Identify residual hazards Mitigate the residual hazards 96

97 97

98 Recommendations: Robust Fire Service Elevator Provides greater protection allowing the elevator to continue to operate for the firefighters during their operations. Protection from water Protection from smoke and heat Direct access to protected lobby and stairwell containing standpipe Protection of primary and backup power supplies 98

99 Recommendations: Occupant Evacuation Operation [OEO] Scalable: OEO can be applied to one or more elevators in the building but is not necessarily required on all elevators. Allows elevators to be used for evacuation until they are recalled. Routing of elevators Cancel all pre-existing calls Respond only to hall calls at affected floors As the fire grows to include more floors, the zone of affected floors would also increase 99

100 Recommendations: Provide protected elevator lobbies Dynamic signage at elevator lobbies Early warning detection 2-hour fire rating for elevator power feeders Remote control operation of elevators for firefighter use (shuttle equipment, etc.) 100

101 Current Status: Proceeding at GLACIAL SPEED 101

102 A Edition (has been released) NFPA Edition (has been released) Elevator Use in Fires and Other Emergencies For Occupants For Firefighters Hazard Analysis almost finished NFPA and ICC jumping the gun NFPA 101 and IBC 102

103 NFPA First Responders Use Elevators The conditions monitored and displayed shall include, but are not limited to the following: (various temperatures, availability of emergency power, elevator location and status, etc.) The conditions shall be displayed on a standard emergency services interface complying with Section

104 NFPA Elevators for Occupant-Controlled Evacuation 21.6 talks about required status indicators (red and green) and signage for the use of these elevators, however this is really pre-mature For instance, the current thinking of the task group is that these status indicators and signage will be provided by the elevator provider. 104

105 Response to current construction demand Different terms used occupant-controlled evacuation elevator evacuation operation occupant evacuation elevators NFPA 101 Annex B in mandatory language so can be adopted as needed Conference in Orlando, FL - 12/

106 Stay tuned! Questions?? 106

107 Thank You for Attending!! 107

Interfacing Fire Alarm, Sprinkler and Elevator Systems

Interfacing Fire Alarm, Sprinkler and Elevator Systems 1 Interfacing Fire Alarm, Sprinkler and Elevator Systems Rodger Reiswig, SET Director, Industry Relations SimplexGrinnell November 17, 2010 Interfacing to Elevators 2 ASME A17.1 Safety Code for Elevators

More information

rpsa FIRE PROTECTION ENGINEERS

rpsa FIRE PROTECTION ENGINEERS FIRE PROTECTION ENGINEERS R.P. SCHIFILITI ASSOCIATES, INC. P.O. Box 297 Reading, Massachusetts 01867-0497 USA 781.944.9300 Fax / Data 781.942.7500 Telephone Elevator Fire Safety: Elevator Recall and Elevator

More information

ELEVATORS. Integration of Codes between Fire Alarm, Sprinklers, and Elevators 12/5/2017

ELEVATORS. Integration of Codes between Fire Alarm, Sprinklers, and Elevators 12/5/2017 12/5/2017 1 ELEVATORS Integration of Codes between Fire Alarm, Sprinklers, and Elevators Encore Electric Inc. Prepared By John McGovern and Jeffrey Engelstad 12/5/2017 Encore Electric Inc. 2 Agenda Basics

More information

NFPA Changes

NFPA Changes Chapter 21, Emergency Control Functions and Interfaces Summary. Chapter 21 is new. These requirements were formerly found in Chapter 6, Protected Premises Fire Alarm Systems. The term fire safety function

More information

Presentation Material: The material will be presented in a PowerPoint format and available digitally/ paper.

Presentation Material: The material will be presented in a PowerPoint format and available digitally/ paper. This fire alarm seminar is an overview of elevator fire alarm system interfacing fundamentals and the current requirements. It covers the terminology, life safety functions, and correct application of

More information

HCD DSA OSHPD 1 2 1/AC AC SS SS/CC

HCD DSA OSHPD 1 2 1/AC AC SS SS/CC CALIFORNIA BUILDING CODE MATRIX ADOPTION TABLE CHAPTER 30 ELEVATORS AND CONVEYING SYSTEMS (Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter 1 for state agency

More information

The Owner will provide the QEI inspection and certification services.

The Owner will provide the QEI inspection and certification services. General The Owner will provide the QEI inspection and certification services. Elevators Electric operated traction elevators are preferred; holeless hydraulic oil operation may be considered where use

More information

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE Effective Date: 11/01/02 Purpose: MECKLENBURG COUNTY To establish a set of guidelines for performance testing of all newly installed or upgraded fire alarm systems in order to ensure that all devices and

More information

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition Copyright National Fire Protection Association 2013. All rights reserved. This copy is solely for your personal, noncommercial use in connection with participation in the NFPA Standards Development Process.

More information

9/23/ :47 AM. Second Revision No NFPA [ New Section after ] Submitter Information Verification. Committee Statement

9/23/ :47 AM. Second Revision No NFPA [ New Section after ] Submitter Information Verification. Committee Statement Second Revision No. 5501-NFPA 5000-2016 [ New Section after 29.2.1.2 ] 29.2.1.3 Bathtubs, bathtub-shower combinations, and nonemergency showers shall be provided with grab bars in accordance with the provisions

More information

Changes in NFPA

Changes in NFPA Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration

More information

A17 Standards Committee Interpretations Volume 3

A17 Standards Committee Interpretations Volume 3 A17 Standards Committee Interpretations Volume 3 Page Interpretations Approved at the September 2009 A17 Standards Committee Meeting 2 Interpretations Approved at the January 2010 A17 Standards Committee

More information

Fire Alarm System Fundamentals

Fire Alarm System Fundamentals Fire Alarm System Fundamentals Mircom is the largest and oldest privately owned fire alarm and life safety manufacturer in North America and 5th largest overall with 50 years of industry experience. Mircom

More information

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. 2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is

More information

ELEVATORS AND FIRE ALARM SYSTEM INTERFACES CANADIANFIRE ALARM ASSOCIATION 2011 ONTARIO ANNUAL TECHNICAL SEMINAR

ELEVATORS AND FIRE ALARM SYSTEM INTERFACES CANADIANFIRE ALARM ASSOCIATION 2011 ONTARIO ANNUAL TECHNICAL SEMINAR ELEVATORS AND FIRE ALARM SYSTEM INTERFACES CANADIANFIRE ALARM ASSOCIATION 2011 ONTARIO ANNUAL TECHNICAL SEMINAR 1 PRESENTED BY SIMON CROSBY, CET, CFPS RANDAL BROWN & ASSOCIATESLTD. 416-492-5886 X234 SCROSBY@RBACODES.COM

More information

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline Moreno Valley Fire Department Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 8, 2017 Alarm & Signaling Systems PURPOSE Fire alarm and signaling systems are designed to

More information

El Reno Fire Department Fire Alarm Plan Review Worksheet

El Reno Fire Department Fire Alarm Plan Review Worksheet El Reno Fire Department Fire Alarm Plan Review Worksheet This Fire Alarm Plan Review Checklist is provided as a guide to assist with your Fire Alarm Plan Review Submittal requirements. Please contact us

More information

APPENDIX K MODIFIED INDUSTRY STANDARDS FOR ELEVATORS AND CONVEYING SYSTEMS

APPENDIX K MODIFIED INDUSTRY STANDARDS FOR ELEVATORS AND CONVEYING SYSTEMS APPENDIX K MODIFIED INDUSTRY STANDARDS FOR ELEVATORS AND CONVEYING SYSTEMS CHAPTER K1 MODIFICATIONS TO ASME A17.1-2000, SAFETY CODE FOR ELEVATORS AND ESCALATORS K101.1 General. As referenced by Chapter

More information

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course Florida Building Code 2010 Chapter 9 Fire Protection Systems Advanced Course 1 Introduction This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors

More information

HIGH-RISE RETROFIT ORDINANCES - NO and NO

HIGH-RISE RETROFIT ORDINANCES - NO and NO INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: LAMC 91.8604 Effective: 9-06-90 DOCUMENT NO. P/BC 2002-054 Revised: 4-15-03 Previously Issued As: MGD 88 HIGH-RISE RETROFIT ORDINANCES - NO.

More information

Division 28 - Electronic Safety and Security

Division 28 - Electronic Safety and Security Division 28 - Electronic Safety and Security 28 31 11 Fire Alarm Systems Fire alarm systems shall be installed in buildings when required by this section. 1. Purpose: The primary purpose of a fire alarm

More information

Elevator Emergency Equipment Instructor s Guide

Elevator Emergency Equipment Instructor s Guide Table of Contents Overview.......4 Sensory Inspection 11 Emergency Equipment in Elevator Systems..14 Fire Service Phase I & II 24 Summary..35 1 Icons Used In This Guide Agenda Topic # Topic Title Duration

More information

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Services and Fire Protection Equipment Linda MacKay DATE: November 10, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter Ballot Final Results The

More information

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS SECTION 907 FIRE ALARM AND DETECTION SYSTEMS 907.1 General. This section covers the application, installation, performance and maintenance of fire alarm systems and their components in new and existing

More information

Report on First Revision June 2014 NFPA 5000

Report on First Revision June 2014 NFPA 5000 5000- Log #12 BLD-BSF Final Action: (55.2 (New) ) NOTE: This proposal appeared as Comment 5000-168 (Log #86) which was held from the A11 ROC on Proposal 5000-239. Submitter: Technical Correlating Committee

More information

Table EXIT ACCESS TRAVEL DISTANCE a OCCUPANCY SYSTEM SYSTEM. A, E, F-1, I-1, M, b,d R, S-1. B c. F-2, S-2, U c

Table EXIT ACCESS TRAVEL DISTANCE a OCCUPANCY SYSTEM SYSTEM. A, E, F-1, I-1, M, b,d R, S-1. B c. F-2, S-2, U c Table 1015.1 EXIT ACCESS TRAVEL DISTANCE a WITHOUT SPRINKLER WITH SPRINKLER OCCUPANCY SYSTEM SYSTEM A, E, F-1, I-1, M, 200 250 b,d R, S-1 B 200 300 c F-2, S-2, U 300 400 c No Change to Other Entries in

More information

Florida Building Code 2010

Florida Building Code 2010 Introduction Florida Building Code 2010 Chapter 9 Fire Protection Systems This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors are familiar with

More information

FEO Initiation Devices Dean McLellan

FEO Initiation Devices Dean McLellan FEO Initiation Devices Dean McLellan Enforcement Protocol 1. TSSAct 2. Ontario Regulation 209/01 3. Code Adoption Document (CAD) 4. Director s Orders 5. Applicable Code 1. Sub Codes (NBCC, CEC) A17/B44

More information

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Service and Fire Protection Equipment Gregory Harrington, P.E., Staff Liaison DATE: October 1, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Alarm System Plan Review 2009 International Fire Code and 2010 NFPA 72 Date of Review // BLD201 - Project Address: Project Name: _ Professional

More information

STATE OF MARYLAND DEPARTMENT OF STATE POLICE OFFICE OF THE STATE FIRE MARSHAL

STATE OF MARYLAND DEPARTMENT OF STATE POLICE OFFICE OF THE STATE FIRE MARSHAL STATE OF MARYLAND DEPARTMENT OF STATE POLICE OFFICE OF THE STATE FIRE MARSHAL Larry Hogan Governor Boyd K. Rutherford Lt. Governor 1201 Reisterstown Road Pikesville, MD 21208 410-653-8980 Fax 410-653-8988

More information

First Revision No. 158-NFPA [ Global Input ] Submitter Information Verification. Committee Statement

First Revision No. 158-NFPA [ Global Input ] Submitter Information Verification. Committee Statement of 326 11/21/2013 1:03 PM First Revision No. 158-NFPA 72-2013 [ Global Input ] Revise 2.3.1 to update UL 864 to "2003, revised 2012" and upate ANSI/ASME A17 to 2013. Submittal Date: Wed Sep 11 11:08:52

More information

M E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014)

M E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169 7471 Phone: 617 770 3000 Fax: 617 770 0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Means of Egress

More information

ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS

ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS Prepared for Smoke Safety Council 6775 SW 111 th Avenue, Suite 10 Beaverton, OR 97008 Prepared by Jesse J. Beitel Alison J. Wakelin Craig L.

More information

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Rancho Cucamonga Fire Protection District Prevention Bureau Standard Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Updated: December 2016 for consistency

More information

CAFAA S 22 nd ANNUAL STATE AGENCY FORUM 09/28/17

CAFAA S 22 nd ANNUAL STATE AGENCY FORUM 09/28/17 STEVE SCHWARTZ (Consolidated Fire Protection) Q-01 NFPA 72 Chapter 18 Section 18.4.2.4, The standard evacuation signal shall be synchronized within a notification zone. We have been taught that a floor

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR6005 SAF-BCF (32.2.1.1.2) Recommendation: 32.2.1.1.2 Where there are sleeping accommodations for more than 16 residents are provided, the occupancy shall be classified as a large facility in accordance

More information

Emergency Power & Fire Service Checklist

Emergency Power & Fire Service Checklist Emergency Power & Fire Service Checklist www.technicalsafetybc.ca contact@technicalsafetybc.ca Toll Free: 1 866 566 7233 The intended purpose of this form is to provide a mechanism for inspectors to be

More information

SPECIAL AMUSEMENT OCCUPANCIES HAUNTED HOUSE, SCARE HOUSE OR MAZE

SPECIAL AMUSEMENT OCCUPANCIES HAUNTED HOUSE, SCARE HOUSE OR MAZE SPECIAL AMUSEMENT OCCUPANCIES HAUNTED HOUSE, SCARE HOUSE OR MAZE Summary Guadalupe County requirements for the Permit Issuance and safe operation of a Temporary Special Amusement Occupancy. PURPOSE To

More information

DEALING WITH FIRE SAFETY

DEALING WITH FIRE SAFETY DEALING WITH FIRE SAFETY Personal Care Homes And Assisted Living Facilities Presented by: Harold D. Hicks, P.E., FSFPE Fire Protection Engineer 1 Atlantic Code Consultants 2 Our Objectives Recognize the

More information

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing. 9/20/2016 2:27 PM Second Revision No. 5006-NFPA 101-2016 [ Section No. 3.3.56 ] 3.3.56 Delayed Action Closer. Self-closing device that incorporates a delay prior to the initiation of closing. Mechanical

More information

NFPA 96, 2017 REVIEW SUMMARY

NFPA 96, 2017 REVIEW SUMMARY NFPA 96, 2017 REVIEW SUMMARY 1) NFPA 96 REVISION SUMMARY NFPA 96 Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations The 2017 edition adds a new normative annex on mobile

More information

Review of Revisions to NFPA 1, 2015 Edition

Review of Revisions to NFPA 1, 2015 Edition James S Peterkin, PE, LEED AP Senior Fire Protection Engineer TLC Engineering for Architecture Anthony Apfelbeck, CFPS, CBO, CFO, FM, FIFireE, MPA Building and Fire Official City of Altamonte Springs,

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 21 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0300 - Other

More information

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2

More information

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016 1. Introduction The intent of this document is to establish minimum standards for the practice of fire protection engineering within the State of Oklahoma as conducted by licensed professional engineers.

More information

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics. A28.1 Standard of Practice - Fire Alarm Systems NOTE: Significant revisions or additions to the previous standards are highlighted in italics. OBJECTIVE OF STANDARD To provide compliant smart addressable

More information

FIRE SAFETY REQUIREMENTS FOR PRE RESIDENTIAL BUILDINGS OF THREE OR MORE STORIES (DOROTHY MAE ORDINANCE - NO. 158,963)

FIRE SAFETY REQUIREMENTS FOR PRE RESIDENTIAL BUILDINGS OF THREE OR MORE STORIES (DOROTHY MAE ORDINANCE - NO. 158,963) INFORMATION BULLETIN / PUBLIC - MECHANICAL CODE REFERENCE NO.: LAMC 91.8604 Effective: 6-20-84 DOCUMENT NO. P/MC 2002-005 Revised: 6-15-00 Previously Issued As: MGD #74 FIRE SAFETY REQUIREMENTS FOR PRE-

More information

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE Developed by the Midwestern Regional Work Group CONTENTS Item 15 Limited area sprinkler systems Item 20 Scope of IFC Ch 7 Item 21 Fire-resistance-rated

More information

2012 International Fire Code Significant Changes. IFC Background. Purpose IBC and 2012 NFPA 101 Significant Means of Egress Changes

2012 International Fire Code Significant Changes. IFC Background. Purpose IBC and 2012 NFPA 101 Significant Means of Egress Changes 2012 International Fire Code Significant Changes Andrew M. Schneider, P.E. Senior Fire Protection Engineer aschneider@koffel.com Koffel Associates, Inc. www.koffel.com Expertly Engineering Safety From

More information

2018 NICET Code Transition Changes

2018 NICET Code Transition Changes 2018 NICET Code Transition Changes NICET will be transitioning to newer codes accepted in their exams in mid-october 2018, specifically: NFPA 72 2016 NFPA 70 2014 IBC 2015 NFPA 101 2015 Here are some changes

More information

The Technical Committee on Commissioning and Integrated Testing

The Technical Committee on Commissioning and Integrated Testing National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org TO: FROM: The Technical Committee on Commissioning and Integrated Testing

More information

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions. 11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

More information

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard

More information

October 2018 Draft for Public Review. A XX/B44-XX, Safety Code for Elevators and Escalators (Proposed Revisions of ASME A17.

October 2018 Draft for Public Review. A XX/B44-XX, Safety Code for Elevators and Escalators (Proposed Revisions of ASME A17. A17.1-20XX/B44-XX Page 1 of 102 October 2018 Draft for Public Review A17.1-20XX/B44-XX, Safety Code for Elevators and Escalators (Proposed Revisions of ASME A17.1-2016/CSA B44-16) TENTATIVE SUBJECT TO

More information

2012 OBC Changes. Summary of key changes to Life Safety and Fire Protection Systems for CFAA January 22, 2014

2012 OBC Changes. Summary of key changes to Life Safety and Fire Protection Systems for CFAA January 22, 2014 2012 OBC Changes Summary of key changes to Life Safety and Fire Protection Systems for CFAA January 22, 2014 2012 OBC New Sentence 3.2.4.2(6) Buildings interconnected by walkways permitted in Articles

More information

TRI-LAKES MONUMENT FIRE PROTECTION DISTRICT

TRI-LAKES MONUMENT FIRE PROTECTION DISTRICT TRI-LAKES MONUMENT FIRE PROTECTION DISTRICT LOCAL AMENDMENTS INTERNATIONAL FIRE CODE 2009 December 5, 2012 1 Chapter 1 Administration Chapter 5 Fire Service Features Chapter 9 Fire Protection Systems Chapter

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved

More information

Second Revision No. 20-NFPA [ Section No. 1.4 ] Supplemental Information. Submitter Information Verification. Committee Statement

Second Revision No. 20-NFPA [ Section No. 1.4 ] Supplemental Information. Submitter Information Verification. Committee Statement Second Revision No. 20-NFPA 14-2015 [ Section No. 1.4 ] 1.4* Equivalency. Nothing in this standard is intended to prevent the use of systems, methods, or devices of equivalent or superior quality, strength,

More information

Fire Protection Coffee Break Training May 2016

Fire Protection Coffee Break Training May 2016 Fire Protection Coffee Break Training May 2016 Introduction High-Rise Requirements Questions and Answers Agenda Overview Site Fire Access Aerial Access Power/Back-up Power Elevators and Access Sprinklers

More information

Recommended Amendments to the 2003 International Fire Code North Central Texas Council of Governments region

Recommended Amendments to the 2003 International Fire Code North Central Texas Council of Governments region Recommended Amendments to the 2003 International Fire Code North Central Texas Council of Governments region The following sections, paragraphs, and sentences of the 2003 International Fire Code are hereby

More information

Circulation Report for SIG-TMS Comments Document # 72

Circulation Report for SIG-TMS Comments Document # 72 1 72-12 Eligible To Vote:28 Affirmative: 24 : 0 Abstain: 0 : 4 3.3.x Deficiency (New) (Log # 209 ) 72-13 Eligible To Vote:28 Affirmative: 24 : 0 Abstain: 0 : 4 3.3.x Deficiency (New) (Log # 234 ) 72-15

More information

Table OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS

Table OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.

More information

National Fire Protection Association M E M O R A N D U M. Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems

National Fire Protection Association M E M O R A N D U M. Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Testing and Maintenance

More information

Maintaining Building and Fire Safety During Active Assailant Events and Other Terrorist Events

Maintaining Building and Fire Safety During Active Assailant Events and Other Terrorist Events Position Statement Maintaining Building and Fire Safety During Active Assailant Events and Other Terrorist Events Maintaining school safety in light of recent terrorist events is challenging for everyone,

More information

Chapter 4: Fire Protection Systems

Chapter 4: Fire Protection Systems Chapter 4: Fire Protection Systems Automatic Extinguishing Systems (Fire Sprinklers) One of the most important aspects of a storage warehouse inspection is ensuring that the automatic extinguishing system

More information

TG FIRE DRILLS. Office of the Fire Marshal and Emergency Management

TG FIRE DRILLS. Office of the Fire Marshal and Emergency Management FIRE DRILLS Office of the Fire Marshal and Emergency Management Preface This guideline updates TG-01-2004 published in October 2004. Portions of the guideline have been changed to reflect the current requirements

More information

Talking about NFPA History of NFPA NFPA Standard 1710: Organization and Deployment of Fire Suppression Operations, EMS

Talking about NFPA History of NFPA NFPA Standard 1710: Organization and Deployment of Fire Suppression Operations, EMS NFPA Standard 1710: Organization and Deployment of Fire Suppression Operations, EMS and Special Ops The History The Right Description and The 2015 Revision Recognized early aggressive and offensive primary

More information

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY Revision No.: 11 Page 1 of 12 I. PURPOSE This procedure establishes a tool to help maintain a safe environment for all patients, visitors and staff by evaluating the loss of a life safety feature during

More information

FIRE SERVICE FEATURES

FIRE SERVICE FEATURES CHAPTER 5 FIRE SERVICE FEATURES SECTION 501 GENERAL 501.1 Scope. Fire service features for buildings, structures and premises shall comply with this chapter. 501.2 Permits. A permit shall be required as

More information

Chapter 17, Initiating Devices

Chapter 17, Initiating Devices Chapter 17, Initiating Devices Summary. Chapter 17 was Chapter 5 in NFPA 72-2007. The term authority having jurisdiction is replaced in some sections by the term other governing laws, codes, or standards.

More information

SEMINOLE FIRE DEPARTMENT TENT PERMIT CONDITIONS

SEMINOLE FIRE DEPARTMENT TENT PERMIT CONDITIONS CITY OF SEMINOLE BUILDING DEPARTEMENT/FIRE DEPARTMENT 9199 113 th Street N. SEMINOLE, FL 33772 Phone: (727) 392-1966 - FAX (727) 319-6583 NO SMOKING UNDER THE TENT(S) Tents may be erected in any zoning

More information

STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018

STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018 STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018 STANDARD INFORMATION Standard Number: NFPA 72 Standard Name: National Fire Alarm and Signaling Code Standard Edition and Issue Date: 2016 Edition

More information

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements Module 3 Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements 1 WATER-BASED SUPPRESSION SYSTEMS-PART TWO This module covers: 1. Ohio Building Code requirements and when and why

More information

CHINO VALLEY INDEPENDENT FIRE DISTRICT FIRE PROTECTION STANDARD

CHINO VALLEY INDEPENDENT FIRE DISTRICT FIRE PROTECTION STANDARD CHINO VALLEY INDEPENDENT FIRE DISTRICT FIRE PROTECTION STANDARD HIGH-RISE REQUIREMENTS STANDARD # 113 REVISED 02/03/1992 PAGES 16 Index Section 1: Section 2: Section 3: Section 4: Section 5: Section 6:

More information

CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS RANDAL BROWN & ASSOCIATES ENGINEERING LTD. CONSULTING ENGINEERS LIFE SAFETY & FIRE PROTECTION 105 6 LANSING SQUARE TORONTO, ONTARIO CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY

More information

ICC CODE CORNER 2012 IFC Code & Commentary

ICC CODE CORNER 2012 IFC Code & Commentary SECTION 910 SMOKE AND HEAT VENTS 910.1 General. Where required by this code or otherwise installed, smoke and heat vents or mechanical smoke exhaust systems and draft curtains shall conform to the requirements

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 8/2004 Fire Chief Lee Koontz Fire Marshal Paul Smith EFD-FMO 3-1 2003 International Fire & Building Code as Amended NFPA Standards

More information

FIRE & LIFE SAFTEY STANDARD

FIRE & LIFE SAFTEY STANDARD Title: Effective Date: 01/01/14 Revised Date: 1/1/14 Code References: Title 16, Chapter 16.16 of the Roseville Municipal Code, NFPA 72 Note: This standard is a summary of Fire Department clarifications

More information

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES Sharon S. Gilyeat, P.E., Principal Koffel Associates, Inc. www.koffel.com sgilyeat@koffel.com Expertly Engineering Safety From Fire

More information

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016 Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting Prepared Especially for : OSFM TEC 2016 Acceptance Testing 11-2008 Agenda Before you begin Completing the

More information

Port of Portland Conveying Equipment Guidelines

Port of Portland Conveying Equipment Guidelines Role: Consultant for the Port Design Guidelines Port of Portland Conveying Equipment Guidelines ELEVATOR, ESCALATOR, AND MOVING WALK DESIGN OVERVIEW The Division 14 specification sections include appropriate

More information

Fire Alarm, Water Flow Alarm & Signaling Systems

Fire Alarm, Water Flow Alarm & Signaling Systems Orange County Fire Authority Community Risk Reduction 1 Fire Authority Road, Building A, Irvine, CA 92602 www.ocfa.org 714-573-6100 Fire Alarm, Water Flow Alarm & Signaling Systems Guideline D-03 Serving

More information

TEN STEP PROCESS PREPARING FIRE SAFETY PLANS

TEN STEP PROCESS PREPARING FIRE SAFETY PLANS TEN STEP PROCESS PREPARING FIRE SAFETY PLANS STEP 1 CONDUCT FIRE SAFETY AUDIT IDENTIFY BUILDING FEATURES AND HUMAN RESOURCES. STEP 2 APPOINTMENT OF SUPERVISORY STAFF IDENTIFY TRAINED SUPERVISORY STAFF

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 92 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS Type Memo Tag FED - KA100 - General Requirements - Other Title

More information

Fire Prevention Coffee Break Training. February 2017

Fire Prevention Coffee Break Training. February 2017 Fire Prevention Coffee Break Training February 2017 Agenda FDC s - Lund Standpipes - Phelan Fire Alarm Testing Phelan/Dooley Questions and Answers Open Forum Standpipe requirement Standpipes are required

More information

PERFORMANCE COMPLIANCE METHODS

PERFORMANCE COMPLIANCE METHODS CHAPTER 13 PERFORMANCE COMPLIANCE METHODS SECTION 1301 GENERAL 1301.1 Scope. The provisions of this chapter shall apply to the alteration, repair, addition and change of occupancy of existing structures,

More information

GENERAL AREAS OF INSPECTION

GENERAL AREAS OF INSPECTION This information is intended to assist you in preparation for the annual high-rise inspection. This is not a complete list and the Inspector may identify other conditions or issues in the building that

More information

PERFORMANCE COMPLIANCE METHODS

PERFORMANCE COMPLIANCE METHODS CHAPTER 13 PERFORMANCE COMPLIANCE METHODS SECTION 1301 GENERAL 1301.1 Scope. The provisions of this chapter shall apply to the alteration, repair, addition and change of occupancy of existing structures,

More information

Residential-based Care Facility R-4 Guideline

Residential-based Care Facility R-4 Guideline Moreno Valley Fire Department Fire Prevention Bureau Residential-based Care Facility R-4 Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: April 7, 2017 Residential-based Care

More information

APPENDIX A International Building Code Amendments

APPENDIX A International Building Code Amendments APPENDIX A 2012 International Building Code Amendments The following sections, paragraphs, and sentences of the 2012 International Building Code are hereby amended as follows: Standard type is text from

More information

D. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following:

D. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following: PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of Sam Houston State University for the design and construction of standpipe systems to include combination standpipe

More information

Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region

Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region The following sections, paragraphs, and sentences of the 2015 International Existing

More information

LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION

LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION CHAPTER 23.45 Sections LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION 23.45.100 Local amendments to the International Fire Code, 2006 Edition... 2 23.45.102.1 Construction and design provisions...

More information

Recommended Amendments to the 2015 International Building Code North Central Texas Council of Governments Region

Recommended Amendments to the 2015 International Building Code North Central Texas Council of Governments Region Recommended Amendments to the 2015 International Building Code North Central Texas Council of Governments Region The following sections, paragraphs, and sentences of the 2015 International Building Code

More information

Smoke Detector Activation of any smoke detector shall start the alarm verification mode.

Smoke Detector Activation of any smoke detector shall start the alarm verification mode. Description: The purpose of the section is to provide the UMCP Design Standards for the design and implementation of Fire Alarm Systems at the UMCP campus. Related Sections: TBD Effective Date: July 10,

More information

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax) FIRE DEPARTMENT SANTA CLARA COUNTY 14700 Winchester Blvd., Los Gatos, CA. 95032-1818 (408) 378-4010 (408) 378-9342 (fax) www.sccfd.org STANDARD DETAILS & SPECIFICATIONS Spec No C-4 Rev. Date 03/10/10 SUBJECT:

More information

INITIAL FIRE ASSESSMENT REPORT (FAR)

INITIAL FIRE ASSESSMENT REPORT (FAR) INITIAL FIRE ASSESSMENT REPORT (FAR) Factory SQ Station, Plot # 221-223, Jamirdia, Valuka, Mymensingh Mymensingh 17 Jun 2014 The Alliance for Bangladesh Worker Safety Page 1/17 Factory 17 Jun 2014 Introduction

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 100 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS CFR Type Memo Tag FED - KA100 - General Requirements - Other

More information

The Social Accountability International (SAI) Fire Safety Checklist

The Social Accountability International (SAI) Fire Safety Checklist The Social Accountability International (SAI) Fire Safety Checklist Introduction The Social Accountability International (SAI) Fire Safety Checklist is a guidance tool prepared for SA8000 & BSCI Auditors

More information