Design Guidelines Fire Safety in New and Refurbished Buildings

Size: px
Start display at page:

Download "Design Guidelines Fire Safety in New and Refurbished Buildings"

Transcription

1 Design Guidelines Fire Safety in New and Refurbished Buildings Introduction All major new or refurbishment projects must comply with the Technical Standards (Scotland) Regulations as a matter of course. There are however, a number of areas where the University wishes to make provisions above and beyond the minimum requirements in the Technical Standards or make additional improvements to existing buildings where upgrades to meet the Standards are not strictly required as part of a Building Warrant application (e.g. situations where the status quo is deemed to comply). These improved provisions are normally required to comply with Risk Assessments carried out by the University Fire Safety Adviser as required under the Fire (Scotland) Regulations 2006 It will be necessary on every new build or major replacement project to meet with the University Fire Safety Adviser and a representative from Estates and Buildings to review existing fire risk assessments and/or agree any provisions that go beyond the requirements of the Technical Standards. The guidelines listed in this document provide guidance on existing fire strategies and lists typical areas for consideration. Plan Drawings Plan drawings covering the layout of the building, compartmentation and intended fire warning system schematics should be submitted for comment at the earliest opportunity. Considerations for Means of Escape Dead end conditions existing on plan or in buildings should be considered as this may reflect on the fire safety measures required to protect the occupiers of these areas. It may include upgrading, to a suitable resistance, walls, door, glazing etc or may have an influence on the category of fire warning system required. Provision of smoke stopping doors in corridors to reduce the spread of combustion products is generally met by the Technical Standards; however, in some circumstances do not always provide the practical solution. In some cases, large rooms, i.e. seminar or lecture rooms where occupant capacity exceeds 60 persons, should be considered for alternative means of escape where technical standard applied is angle Created on 14/04/2010 Page 1 of 5

2 of divergence and thus does not provide a practical solution because of distance to final exit or discharge into one inappropriate route on corridor. Where final exit from a building is via an external route the route should be constructed of non-slippery hard standing and illuminated throughout its length. Where final exit from a building is via and external staircase the staircase should be afforded appropriate fire protection to allow the occupier to use the staircase in event of fire. The staircase should also be illuminated throughout its length. Protected lobbies onto staircases are required in certain circumstances by the Technical Standards; however, there may be other occasions when it may be appropriate to consider such lobbies, in single staircase conditions when no provision is required, or to assist with disabled evacuation procedures, or afford protection to lifts, or reference to number of storeys. This may also have an influence on the category of fire warning system required. Where rooms do not open directly onto a corridor or escape route (e.g. room accessed from another room). Ironmongery fitted to doors should not be of a type whereby occupiers can be inadvertently locked in the rooms. Doors should be easily and immediately openable from the inside without the use of keys e.g. turnbuckle. There will be circumstances where security is an issue and this should also be considered independently but not be a hindrance to escape in event of fire. Self-closing devices fitted to doors should not be of a type that will permit occupiers of buildings to tamper with the devices thus rendering them ineffective. Self closers should also be delayed action type in all circulation areas to improve disabled access. Places of public assembly should have push bar to open mechanisms on emergency exit doors. Push pads are only permitted on staff area doors. Passive Fire Protection (P.F.P.) Fire separation within a compartment should be considered and the following direction recommended if considered necessary. This may also have an influence on the category of fire warning system required Corridor walls should be continuous from floor to structural soffit. If construction involves flexible partitioning then cavity barriers or fire curtains should follow the line of the corridor walls. Subdivision of the ceiling and floor voids by fire curtain should be considered. Created on 14/04/2010 Page 2 of 5

3 All Services penetrations including power cable or data cable penetration through corridor and compartment walls or floors should be suitably fire stopped with appropriate materials on both sides of the wall or floor. The booklet Ensuring Best Practice for Passive Fire Protection in Buildings should be referred to for guidance on all items concerning P.F.P. Provision for the Disabled Consideration should be given to including the designation of specific temporary waiting areas in buildings which will allow disabled people to use and be evacuated from University Buildings whether or not this is a requirement as part of the Building Warrant. Deaf Alerter should be installed. Consideration should be given to the provision of a fixed communication system and its location with regard to temporary waiting areas for disabled people and appropriate communication panels next to the fire alarm panel. In multi-storey buildings provision of appropriate lifts that will permit disabled person evacuation in event of fire should be considered. All the above items will have an influence on the category of fire warning system required. Automatic Fire Detection and Fire Warning System Categories of Fire Alarm installation are defined in British Standard 5839 Part1: In determining which category should be employed three main factors must be considered. The protection of Life The protection of property The protection of business against interruption to its operation. These three factors form the essential part of the Risk Assessment process and to ensure compliance the following items must be considered in determining the category of alarm system required. Use of the building Means of Escape Created on 14/04/2010 Page 3 of 5

4 Procedures for disabled persons Construction of the building Fire compartmentation Fire separation within the compartment Passive fire resistance Residual Hazards or Fire Risks within the building Special provisions required for protection of equipment Special provisions for the protection of heritage, listed buildings etc Management of the building and working practices. Site specific evacuation procedures After consideration of the factors and items indicated above the category of fire Alarm for installation in the building will be confirmed. As an example residencies would always have a category minimum of L2 whereas other University buildings could fall into any of the other categories specified in BS 5839:Part1; 2002 Other points for consideration 1. Whether full or phased evacuation required. 2. Additional requirements of Fire Alarm panel. 3. Requirements for plant, ventilation, lift etc. 4. Limitation of false alarms. 5. Additional requirements for disabled persons. e.g. communication device, no sounders in temporary waiting areas or near fire and communication panels. 6. Provision of a telephone adjacent to Fire alarm panel 7. Location and use of magnetic devices Strobe or beacons should be considered as an addition or replacement for sounders in the following locations: -- i. Large Seminar Rooms ii. iii. iv. Lecture Rooms All Toilets Plant and Machinery Rooms v. Places of Public Assembly vi. vii. Libraries Theatre Auditoriums Created on 14/04/2010 Page 4 of 5

5 viii. Staircases used as temporary waiting areas for disabled persons Before acceptance of the installed alarm system the appropriate certification for design, installation, commissioning and acceptance must be provided together with the documentation as required by the British Standard. Commissioning During the commissioning process all system must be demonstrated and accepted by Estates and the FSU. The occupiers should also be instructed in the daily and weekly testing regimes and appropriate certificates produced. General The provision of all fire exit signage luminous units or pictorial signs should be considered. Storey or final exits should always be illuminated. Emergency lighting must always be provided. The standard being: Maintained in Places of general assembly and residencies: Non Maintained in other areas The provision of all firefighting equipment should be considered and probable costs estimated. Created on 14/04/2010 Page 5 of 5

UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES

UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES Mandatory Fire Safety Instruction UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES Principal Contractor fire safety considerations in shared occupancy project or refurbishments

More information

GENERAL FIRE SAFETY TERMS & DEFINITIONS

GENERAL FIRE SAFETY TERMS & DEFINITIONS UCL Fire Technical Note - TN006 Fire Safety Technical Guide GENERAL FIRE SAFETY TERMS & DEFINITIONS Reference: BS4422-2005 Fire Safety Vocabulary - for further information and definitions BS EN ISO 13943-2000:

More information

FIRE RISK ASSESSMENT NOT KNOWN 15/10/ SOMERTON COURT BROADMOSS DRIVE SIMON ROFFEY

FIRE RISK ASSESSMENT NOT KNOWN 15/10/ SOMERTON COURT BROADMOSS DRIVE SIMON ROFFEY UPRN Date of inspection Address 1 (flat numbers) Address 2 (street) Address 3 (area) Fire Risk Assessor Checked by Approved by Postcode Does the building have common areas? Was access available to the

More information

Fire Enforcement Report

Fire Enforcement Report AGENDA ITEM 4.4 Fire Enforcement Report Executive Lead: Director of Planning Author: Senior Fire Safety Adviser, Capital Planning & Estate Management Contact Details for further information: Frank Barrett,

More information

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY Revision No.: 11 Page 1 of 12 I. PURPOSE This procedure establishes a tool to help maintain a safe environment for all patients, visitors and staff by evaluating the loss of a life safety feature during

More information

- CONSTRUCTION FIRE SAFETY STANDARDS

- CONSTRUCTION FIRE SAFETY STANDARDS SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Construction Planning All construction sites shall plan and sequence their construction activities to ensure the early installation and operation of permanent

More information

EMERGENCY EVACUATION PLAN

EMERGENCY EVACUATION PLAN UCL ESTATES & FACILITIES DIVISION Construction Maintenance & Fire Safety UNIVERSITY COLLEGE LONDON EMERGENCY EVACUATION PLAN Regulatory Reform (Fire Safety) Order 2005 Name & Address of Building: Occupying

More information

UK Direction BS7671 BS 8492 BS /01/2018

UK Direction BS7671 BS 8492 BS /01/2018 UK Direction BS7671 BS 8492 BS6701 23/01/2018 BS7671:2015 The 17 th Edition Revision 3 details the requirements for an improved fire rating on all cables within a fire route. 422.2.1 In conditions BD2

More information

Fire Alarm Control Panel. System Maintenance and Log Book

Fire Alarm Control Panel. System Maintenance and Log Book Fire Alarm Control Panel System Maintenance and Log Book Fire Alarm System Maintenance A fire alarm system must provide early and reliable warning of the outbreak of fire. To achieve this, the system remains

More information

BUILDING FIRE STRATEGY (Operational & Fire Engineering Information)

BUILDING FIRE STRATEGY (Operational & Fire Engineering Information) Safety Services Fire Safety Fire Strategy for: 132 Hampstead Road (317) UNIVERSITY COLLEGE LONDON BUILDING FIRE STRATEGY (Operational & Fire Engineering Information) Regulatory Reform (Fire Safety) Order

More information

Unit 2 Fire Safety (Zone 1)

Unit 2 Fire Safety (Zone 1) IFE Level 3 Diploma in Fire Safety and Fire Science Unit 2 Fire Safety (Zone 1) Examiner Report March 2018 Introduction 42% of candidates attained a Pass. Half of the candidates that attained a Pass secured

More information

Element C3.5 Means of Escape

Element C3.5 Means of Escape .5 Means of Escape RRFSO Article 14 Legal Factors Responsible person must ensure routes to emergency exits and exits themselves are kept clear at all times Exits must directly lead to place of safety Safe

More information

Dear Customer. Section Old F8 January 2017 Amendment 4. Replace with new title page and document history pages 1 2B

Dear Customer. Section Old F8 January 2017 Amendment 4. Replace with new title page and document history pages 1 2B Dear Customer Please find enclosed Amendment 4, effective 14 February 2014, to the Acceptable Solution and Verification Method for Clause F8 Signs of the New Zealand Building Code. THe previous amendment

More information

Areas of the building to which access was not available. Details of any onsite management (if known)

Areas of the building to which access was not available. Details of any onsite management (if known) SECTION ONE UPRN Address 1 (block name and/or street number) Address 2 (flat numbers) Address 3 (street) Address 4 (area) Postcode Date of inspection Suggested review date Fire Risk Assessor Property Designation

More information

FIRE RISK ASSESSMENT

FIRE RISK ASSESSMENT FIRE RISK ASSESSMENT Full Property Name: St Augustine s Catholic Voluntary Academy Full Property Address: Opposite 93 PE9 1SR Date of Fire Risk Assessment: 6 th June 2017 Name of Fire Risk Assessor: Peter

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY)

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY) FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY) BUILDING SUMMARY The building was constructed in Victorian times and is constructed of brick with knapped flint in fill on some outer walls. The building

More information

UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK. Regulatory Reform (Fire Safety) Order 2005 DARWIN BUILDING

UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK. Regulatory Reform (Fire Safety) Order 2005 DARWIN BUILDING UCL ESTATES Fire Safety UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK Regulatory Reform (Fire Safety) Order 2005 DARWIN BUILDING University College London Gower Street, London WC1E 6BT Contents

More information

WORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES

WORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES 1 WORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES TABLE 2.1 CONSTRUCTION OF STRUCTURAL MEMBERS AND FLOOR AND ROOF (1) ASSEMBLIES (Applies to each fire zone)

More information

FIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES

FIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES FIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES 1. The major objective is to provide an acceptable degree of life safety from fire in existing senior citizen lodges. This document

More information

Northern Ireland HMO Fire Safety Guide

Northern Ireland HMO Fire Safety Guide Northern Ireland HMO Fire Safety Guide 2 February 2018 Contents Equality Statement 5 Houses in Multiple Occupation (HMO) Fire Safety Standards 6 1.0 Introduction 6 2.0 Definition of Houses in Multiple

More information

Fire safety procedure

Fire safety procedure Fire safety procedure Review date: October 2020 Responsible (s): Health and Safety Applicable to Staff: Accessible to Students: Accessible to general public: (including clients) Yes Yes Yes 1 Contents

More information

Building Construction i. approx. age ii. building structure iii. cladding iv. floors v. walls vi. roof

Building Construction i. approx. age ii. building structure iii. cladding iv. floors v. walls vi. roof SECTION ONE UPRN Address 1 (block name and/or street number) Address 2 (flat numbers) Address 3 (street) Address 4 (area) Postcode Date of inspection Suggested review date Fire Risk Assessor Property Designation

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 92 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS Type Memo Tag FED - KA100 - General Requirements - Other Title

More information

BUILDING FIRE STRATEGY

BUILDING FIRE STRATEGY UCL ESTATES Fire Safety UNIVERSITY COLLEGE LONDON BUILDING FIRE STRATEGY Regulatory Reform (Fire Safety) Order 2005, BS 9999: 2008 (Annex H) & BS PAS 911 Name & Address of Building: DEVELOPMENT PLANNING

More information

- CONSTRUCTION FIRE SAFETY STANDARDS

- CONSTRUCTION FIRE SAFETY STANDARDS SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Hot Work Permits All construction sites shall implement a system of Hot Work Permits for all work activities that generate heat, sparks or flames. All of the

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 100 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS CFR Type Memo Tag FED - KA100 - General Requirements - Other

More information

FIRE SAFETY LOG BOOK. (Record of Fire Safety Equipment Testing)

FIRE SAFETY LOG BOOK. (Record of Fire Safety Equipment Testing) FIRE SAFETY LOG BOOK (Record of Fire Safety Equipment Testing) Fire safety log book MARCH 2013 CONTENTS 1.0 PREMISES SPECIFIC INFORMATION 2.0 FIRE SAFETY EQUIPMENT TESTING 2.1 Escape Routes 2.2 Fire Warning

More information

A Guide To BS Understanding the selection, spacing and siting of detectors

A Guide To BS Understanding the selection, spacing and siting of detectors World Class Leaders in Fire Detection Since 1918 A Guide To BS5839-12017 Understanding the selection, spacing and siting of detectors Welcome to A Guide to BS5839 Part 1 : 2017 from HOCHIKI EUROPE (UK)

More information

GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT

GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT FIRE FOR 75 Fox Street Building OCTOBER 2014 Report for Department of Infrastructure Development Fire Services Preliminary Report:

More information

PREMISES FIRE SAFETY HANDBOOK

PREMISES FIRE SAFETY HANDBOOK UCL ESTATES Fire Safety UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK Regulatory Reform (Fire Safety) Order 2005 BIDBOROUGH HOUSE University College London 38-50 Bidborough Street, London, WC1H

More information

LIFE SAFETY CODE ESSENTIALS PRESENTED BY: LARRY VIGIL, RISK CONSULTANT

LIFE SAFETY CODE ESSENTIALS PRESENTED BY: LARRY VIGIL, RISK CONSULTANT LIFE SAFETY CODE ESSENTIALS PRESENTED BY: LARRY VIGIL, RISK CONSULTANT INTRODUCTION 2007-11 5,690 Structure fires 75 Civilian Deaths $83 Million Direct Property Damage 71% in Nursery, Elementary, Middle

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 51 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K0130 - MISCELLANEOUS Title MISCELLANEOUS OTHER LSC DEFICIENCY NOT ON 2786 FED - K9999 - FINAL OBSERVATIONS Title

More information

fire risk assessment For use by landlords of small premises Premises Address

fire risk assessment For use by landlords of small premises Premises Address fire risk assessment For use by landlords of small premises Premises Address FIRE RISK ASSESSMENT for use by landlords of small premises Person having control of the premises: Name of landlord (if different):

More information

Fire resistance. Appendix E. E.1 Fire resistance. Appendix. (A copy of this Appendix is available on /)

Fire resistance. Appendix E. E.1 Fire resistance. Appendix. (A copy of this Appendix is available on /) Fire resistance (A copy of this is available on www.routledge.com/books/details/ 9780415809696/).1 Fire resistance The overall aim of fire safety precautions is to ensure that: all corridor doors shall

More information

PREMISES FIRE SAFETY HANDBOOK

PREMISES FIRE SAFETY HANDBOOK UCL ESTATES Fire Safety UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK Regulatory Reform (Fire Safety) Order 2005 188 TOTTENHAM COURT ROAD University College London 188 TOTTENHAM COURT ROAD, LONDON,

More information

Fire Risk Assessment Guidance

Fire Risk Assessment Guidance Fire Risk Assessment Guidance This document is a guidance note to accompany the example fire risk assessment template. The example fire risk assessment template has been designed with small to medium domestic

More information

Interim Life Safety Measures. Healthcare Construction Certificate - Level 1

Interim Life Safety Measures. Healthcare Construction Certificate - Level 1 Interim Life Safety Measures Purpose of Interim Life Safety Management BASIC SAFETY: During renovations projects in healthcare occupancies, the basic level of protection for the occupants must be maintained

More information

Fire Safety Management

Fire Safety Management Fire Safety Management Wednesday 20 th June 2018 Russ Timpson www.bcptesting.com 24-storey Grenfell Tower in Kensington, West London June 14, 2017 We shape our buildings, thereafter they shape us Winston

More information

Fire detection and alarm

Fire detection and alarm Fire detection and alarm Aesthetic Install all cabling and cable containment neatly and unobtrusively, meeting the highest electrical industry installation standards. Neatly lay and securely fix cables.

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NEW BUILDINGS

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NEW BUILDINGS FIRE RISK ASSESSMENT NEW BUILDINGS BUILDING SUMMARY The building is utilised for classroom teaching for Modern Languages. 1. Identification of the hazards 1.1 Identification of sources of fuel. Timber

More information

Fire Risk Assessment

Fire Risk Assessment Fire Risk Assessment George Wright House HS.F.119 (rev03) delivering promises, improving lives Contents 1 Premises particulars... 1 2 General statement of policy... 1 3 Management system... 1 4 General

More information

3.1 Introduction. 3.1 Introduction

3.1 Introduction. 3.1 Introduction DEPARTMENT OF ARCHITECTURE ABUBAKAR TAFAWA BALEWA UNIVERSITY, BAUCHI ARC 624: ADVANCED BUILDING SERVICES LESSON 3: FIRE DETECTION AND ALARM SYSTEMS IN BUILDINGS 3.1 Introduction 3.1 Introduction 3.2 Conventional

More information

University of London

University of London University of London Senate House and Stewart House Fire safety arrangements Contents 1. Introduction p.2 2. Fire Risk Assessment documentation p.2 3. Action to be taken by a person discovering a fire

More information

Design of Fire safety in Multi Occupancy Residential Accommodation

Design of Fire safety in Multi Occupancy Residential Accommodation Design of Fire safety in Multi Occupancy Residential Accommodation Myth vs Reality Myth. Fire is bright Reality. It isn t. Flames are bright Outside fires have bright flames because of the availability

More information

FIA Guidance on Manual Call Point - Protection - False Alarm Mitigation

FIA Guidance on Manual Call Point - Protection - False Alarm Mitigation Guidance Note FIA Guidance on Manual Call Point - Protection - False Alarm Mitigation FIA Guidance on Manual Call Point - Protection False Alarm Mitigation 1. INTRODUCTION... 3 2. BS 5839-1 RECOMMENDATIONS...

More information

Understanding Passive Fire Protection

Understanding Passive Fire Protection ASFP Response to Hackitt Report/Scottish Regulatory Review What is Passive Fire Protection and why is it important? Niall Rowan Chief Executive Officer Association for Specialist Fire Protection Contents

More information

Fire Procedures. April 2016

Fire Procedures. April 2016 Estates Department Fire Procedures April 2016 Author Robert Hardman Estates Manager Last Policy Review Date 1/04/16 Next policy Review Date 1/04/17 Reviewed by The Laurus Trust School Fire Procedures Contents

More information

MAINTENANCE OF ESSENTIAL SAFETY MEASURES EXPLAINED (Building Regulations 2006)

MAINTENANCE OF ESSENTIAL SAFETY MEASURES EXPLAINED (Building Regulations 2006) MAINTENANCE OF ESSENTIAL SAFETY MEASURES EXPLAINED (Building Regulations 2006) 1. INTRODUCTION 1.1 Essential Safety Measures Defined Essential Safety Measures (previously called essential services) are

More information

CURTIN UNIVERSITY PROJECT DELIVERY GUIDELINES

CURTIN UNIVERSITY PROJECT DELIVERY GUIDELINES CURTIN UNIVERSITY PROJECT DELIVERY GUIDELINES EMERGENCY MANAGEMENT DESIGN GUIDELINES 000331 Details of revisions Level Details Date Initial 1 Document created from 20150513NewBuildsAndRedevelopments.docx

More information

UNIVERSITY COLLEGE LONDON EMERGENCY PLAN. Regulatory Reform (Fire Safety) Order 2005 PART ONE - SPECIFIC INSTRUCTIONS & OTHER RELEVANT INFORMATION:

UNIVERSITY COLLEGE LONDON EMERGENCY PLAN. Regulatory Reform (Fire Safety) Order 2005 PART ONE - SPECIFIC INSTRUCTIONS & OTHER RELEVANT INFORMATION: UCL ESTATES & FACILITIES DIVISION Construction Maintenance & Fire Safety UNIVERSITY COLLEGE LONDON EMERGENCY PLAN Regulatory Reform (Fire Safety) Order 2005 Name & Address of Building: Occupying Department(s)

More information

Passive Fire Protection Guidance for the Fire Risk Assessor. Niall Rowan Technical Officer Association for Specialist Fire Protection

Passive Fire Protection Guidance for the Fire Risk Assessor. Niall Rowan Technical Officer Association for Specialist Fire Protection Passive Fire Protection Guidance for the Fire Risk Assessor Niall Rowan Technical Officer Association for Specialist Fire Protection ASFP has just completed a guide on what to look for when undertaking

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT OVERALL COLOUR ACTION CODE RISK AMBER STATUTORY INSTRUMENT 2005:1541 REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT Address of Premises: Thuurock CCG, Civic Offices New Road Grays Responsible

More information

UNIVERSITY COLLEGE LONDON EMERGENCY PLAN. Regulatory Reform (Fire Safety) Order 2005 PART ONE - SPECIFIC INSTRUCTIONS & OTHER RELEVANT INFORMATION:

UNIVERSITY COLLEGE LONDON EMERGENCY PLAN. Regulatory Reform (Fire Safety) Order 2005 PART ONE - SPECIFIC INSTRUCTIONS & OTHER RELEVANT INFORMATION: UCL ESTATES Fire Safety UNIVERSITY COLLEGE LONDON EMERGENCY PLAN Regulatory Reform (Fire Safety) Order 2005 Name & Address of Building: Occupying Department(s) / School(s) / Institute(s): Christopher Ingold

More information

Fire Safety Management Plan. Qube 90, Whitfield Street, W1T 4EZ. Fire Safety Management Plan & Evacuation Procedures

Fire Safety Management Plan. Qube 90, Whitfield Street, W1T 4EZ. Fire Safety Management Plan & Evacuation Procedures Fire Safety Management Plan & Evacuation Procedures Contents 1.0 Introduction 2.0 Means of Escape in Case of Fire 3.0 Means for Giving Warning in Case of Fire 4.0 Means for Fighting Fire 5. 0 Discovering

More information

Case Study 1 Underground Car Park

Case Study 1 Underground Car Park Case Study 1 Underground Car Park Dorota Brzezińska 1, Janusz Paliszek 2, Piotr Smardz 2, Renata Ollesz 1, Karol Kaczor 2 1 Lodz University of Technology, GRID - Lodz, 2 INBEPO Wroclaw, Poland Building

More information

Fire precautions in dwellings

Fire precautions in dwellings NORWICH City Council Fire precautions in dwellings Private sector housing Providing homes building communities Version 2 Published by Norwich City Council June 2010 Contents Page Introduction 1 2 Types

More information

IDD 033C - Fire door sets

IDD 033C - Fire door sets IDD 033C - Fire door sets Why are fire door sets important? Fire doors are one of the most important features of a building s fire precautions and have two key functions: To protect escape routes from

More information

FIRE SAFETY FOR PRE-SCHOOLS AND CHILDCARE FACILITIES GENERAL GUIDANCE COUNTY COMMITTEE LIMERICK CHILDCARE

FIRE SAFETY FOR PRE-SCHOOLS AND CHILDCARE FACILITIES GENERAL GUIDANCE COUNTY COMMITTEE LIMERICK CHILDCARE COUNTY COMMITTEE CHILDCARE LIMERICK COISTE CHONTAE LUIMNIGH UM CHÚRAM LEANAÍ Limerick County Fire & Rescue Service GENERAL GUIDANCE FIRE SAFETY FOR PRE-SCHOOLS AND CHILDCARE FACILITIES Foreword We are

More information

Schedule of works required for Fire Protection in a 2 Storey semi-detached/terraced house

Schedule of works required for Fire Protection in a 2 Storey semi-detached/terraced house Schedule of works required for Fire Protection in a 2 Storey semi-detached/terraced house THIS DOES NOT COVER 3 STOREY PROPERTIES you must consult with the Private Sector Housing Team on any 3 storey property.

More information

FIRE RISK ASSESSMENT MATHEMATICS BUILDING (INCLUDING OLD OCEANOGRAPHY BUILDING)

FIRE RISK ASSESSMENT MATHEMATICS BUILDING (INCLUDING OLD OCEANOGRAPHY BUILDING) FIRE RISK ASSESSMENT MATHEMATICS BUILDING (INCLUDING OLD OCEANOGRAPHY BUILDING) Responsible person: University of Liverpool Address of premises: Maths building Assessor: Steve Dunkley Person consulted:

More information

EMERGENCY EVACUATION PLAN

EMERGENCY EVACUATION PLAN UCL ESTATES & FACILITIES DIVISION Construction Maintenance & Fire Safety UNIVERSITY COLLEGE LONDON EMERGENCY PLAN Regulatory Reform (Fire Safety) Order 2005 Name & Address of Building: Occupying Department(s)

More information

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Pocket guide to. Fire Alarm Systems Design BS Standard

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Pocket guide to. Fire Alarm Systems Design BS Standard Pocket guide to Fire Alarm Systems Design BS 5839-1 Standard AVAILABLE TO DOWNLOAD ON THE APOLLO APP The Regulatory Reform (Fire Safety) Order (FSO) became law on 1 October 2006 Legally you must comply!

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT SPORTS CENTRE

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT SPORTS CENTRE FIRE RISK ASSESSMENT SPORTS CENTRE BUILDING SUMMARY The building is used as a Sports Centre and contains a large sports hall with changing rooms, an office for staff and a fitness area. 1. Identification

More information

Fire Safety Protocol

Fire Safety Protocol CORPORATE HEALTH AND SAFETY POLICY: Part 3 Arrangements Fire Safety Protocol Document Status: [ ] Guidance for Managers [] Protocol [ ] Procedures Version 0.1/ August 2013 DRAFT EALING NCIL Table of Contents

More information

Policy for Safe Evacuation of Persons with Disabilities

Policy for Safe Evacuation of Persons with Disabilities Policy for Safe Evacuation of Persons with Disabilities 1. Policy Statement The London School of Economics is committed to promoting access for people who have a disability or long-term medical condition.

More information

C. None (No sprinkler system) K3 E. NUMBER OF BEDS CERTIFIED FOR MEDICAID

C. None (No sprinkler system) K3 E. NUMBER OF BEDS CERTIFIED FOR MEDICAID DEPARTMENT OF HEALTH AND HUMAN SERVICES CENTERS FOR MEDICARE & MEDICAID SERVICES FIRE SAFETY SURVEY REPORT - 2000 LIFE SAFETY CODE Intermediate Care Facilities for the Mentally Retarded LARGE PART I Figure

More information

Maintenance Guide EMS Security Group Ltd. All rights reserved. MK154 Iss5 18/11/15 AJM

Maintenance Guide EMS Security Group Ltd. All rights reserved. MK154 Iss5 18/11/15 AJM Maintenance Guide 2015 EMS Security Group Ltd. All rights reserved. MK154 Iss5 18/11/15 AJM Contents Overview 3 Pre-testing Guidelines 4 Daily Maintenance 4 Weekly Maintenance 5 Six Monthly Maintenance

More information

Fire Safety Risk Assessment Large Premises

Fire Safety Risk Assessment Large Premises Fire Safety Risk Assessment Large Premises Premises Name: Person Completing this Assessment: Date of Assessment: Date of Next Review: (Recommended Annually) Fire Safety Risk Assessment (Large Premises)

More information

1.4 Provide and fix the following ironmongery.

1.4 Provide and fix the following ironmongery. Schedule of works required for Fire Protection in a first & second floor purpose built masionette above shops where the exit door is at first floor level. THIS DOES NOT COVER NORMAL 3 STOREY PROPERTIES

More information

Fire Design Guide. Introduction Scope Aims Consultation Design Strategy Compartmentation Provision...

Fire Design Guide. Introduction Scope Aims Consultation Design Strategy Compartmentation Provision... Fire Design Guide Contents Introduction... 3 Scope... 3 Aims... 3 Consultation... 3 Design Strategy... 4 Compartmentation... 4 Provision... 4 Sub-compartmentation... 5 Doorways... 6 Penetrations... 6 Cause

More information

Fire Risk Assessment

Fire Risk Assessment Fire Risk Assessment Maritime Studios Pendennis Rise Falmouth TR11 4FB Carried out by: Date: October 2015 Review Date: October 2016 Les Carter CMIOSH Health & Safety Consultant Mobile 07831 636751, Email

More information

BUILDING FIRE STRATEGY

BUILDING FIRE STRATEGY UCL ESTATES Fire Safety UNIVERSITY COLLEGE LONDON BUILDING FIRE STRATEGY Regulatory Reform (Fire Safety) Order 2005, BS 9999: 2008 (Annex H) & BS PAS 911 Name & Address of Building: Occupying Department(s)

More information

Passive Fire Protection Guidance. Niall Rowan Technical Officer Association for Specialist Fire Protection

Passive Fire Protection Guidance. Niall Rowan Technical Officer Association for Specialist Fire Protection Passive Fire Protection Guidance for the Fire Risk Assessor Niall Rowan Technical Officer Association for Specialist Fire Protection ASFP has just completed a guide on what to look for when undertaking

More information

TYPE 1 FIRE RISK ASSESSMENT REVIEW (NO DESTRUCTIVE AUDIT)

TYPE 1 FIRE RISK ASSESSMENT REVIEW (NO DESTRUCTIVE AUDIT) TYPE 1 FIRE RISK ASSESSMENT REVIEW (NO DESTRUCTIVE AUDIT) BRECON TOWERS BLACKBERRY LANE STOCKPORT SK5 8JW Date of this risk assessment review: 4th July 2017 Date of last risk assessment review: 8th May

More information

Guidance for writing a Personal Emergency Evacuation Plan (PEEP)

Guidance for writing a Personal Emergency Evacuation Plan (PEEP) Guidance for writing a Personal Emergency Evacuation Plan (PEEP) If assistance with escape is required, the extent of such assistance should be identified in the PEEP i.e. the number of assistants and

More information

Duties and Responsibilities of Fire Marshals

Duties and Responsibilities of Fire Marshals Occupational Health & Safety Directorate Duties and Responsibilities of Fire Marshals (QM_OHSD_FS022) Contents 1. As a Fire Marshal you must:... 3 2. As a Fire Marshal you should carry out the following

More information

The Mungo Foundation. Fire Safety Policy and Procedure

The Mungo Foundation. Fire Safety Policy and Procedure The Mungo Foundation Fire Safety Policy and Procedure IMPLEMENTATION The Departments of Human Resources, Services and Development and Finance are responsible for the implementation of this policy and these

More information

Fire Risk Assessment

Fire Risk Assessment Fire Risk Assessment Carr House HS.F.119 (rev03) delivering promises, improving lives Contents 1 Premises particulars... 1 2 General statement of policy... 1 3 Management system... 1 4 General description

More information

CHAPTER 5 - STRUCTURAL FIRE PRECAUTIONS

CHAPTER 5 - STRUCTURAL FIRE PRECAUTIONS CHAPTER 5 - STRUCTURAL FIRE PRECAUTIONS 5.1 General In the previous chapter, the importance of protecting escape routes from penetration by smoke and fire was discussed, so as to ensure they can be safely

More information

AFEC FIRE ENGINEERING TEMPLATE FOR CLIENTS INTERNALLY COMPLETED RISK ASSESMENT

AFEC FIRE ENGINEERING TEMPLATE FOR CLIENTS INTERNALLY COMPLETED RISK ASSESMENT AFEC FIRE & RISK ENGINEERING SPECIALISTS would like to share an in house Risk Assessment Template we have developed for in house use to assist Facilities Managers and Environmental Health and Safety Staff

More information

161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures

161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures 161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures Contents 1.0 Introduction 2.0 Means of Escape in Case of Fire 3.0 Means for Giving Warning in Case of Fire 4.0 Means

More information

Reviewed: DD Month Emergency Evacuation of People with a Disability Options Matrix for Developing a PEEP

Reviewed: DD Month Emergency Evacuation of People with a Disability Options Matrix for Developing a PEEP Safety Office Reviewed: 17 July 2012 Reviewed: DD Month Emergency Evacuation of People with a Disability Options Matrix for Developing a PEEP The following matrix includes most disability types and recommends

More information

UNIVERSITY COLLEGE LONDON EMERGENCY PLAN. Regulatory Reform (Fire Safety) Order 2005 PART ONE - SPECIFIC INSTRUCTIONS & OTHER RELEVANT INFORMATION:

UNIVERSITY COLLEGE LONDON EMERGENCY PLAN. Regulatory Reform (Fire Safety) Order 2005 PART ONE - SPECIFIC INSTRUCTIONS & OTHER RELEVANT INFORMATION: Bldg Name: Rockefeller & Medical School (201 & 374) UCL ESTATES Fire Safety UNIVERSITY COLLEGE LONDON EMERGENCY PLAN Regulatory Reform (Fire Safety) Order 2005 Name & Address of Building: Occupying Department(s)

More information

Fire Safety Design Guide

Fire Safety Design Guide Health and Safety Services Safety Guide 34 Part B Contents Summary... iii 1. Introduction... 1 2. National legislation and standards... 1 3. Fire engineering... 2 4. Means of escape doors... 3 5. Means

More information

Fire Risk Assessment Borough High Street

Fire Risk Assessment Borough High Street Fire Risk Assessment Borough High Street Page 1 of 8 / BHS Fire Risk Assessment / 07/2017 / V4.0 / ES Premises Details Occupier Premises Address Premises Description FIRE RISK ASSESSMENT Report of Audit

More information

Charlotte Building, 17 Gresse Street, London W1T 1QL

Charlotte Building, 17 Gresse Street, London W1T 1QL Charlotte Building, 17 Gresse Street, London W1T 1QL Fire Safety Management & Evacuation Procedures Contents 1.0 Introduction 2.0 Means of Escape in Case of Fire 3.0 Means for Giving Warning in Case of

More information

NOTTINGHAM CITY HOMES

NOTTINGHAM CITY HOMES APPENDIX 1 NOTTINGHAM CITY HOMES FIRE SAFETY POLICY 2013/14 Draft for Board Uncontrolled when printed Page 1 of 14 DOCUMENT CONTROL Identification and Approval Status Document Title: Nottingham City Homes

More information

GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT

GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT FIRE FOR 69 PRESIDENT SEPTEMBER 2014 Report for Department of Infrastructure Development Fire Services Preliminary Report: 69

More information

Fire Risk Assessment Guide

Fire Risk Assessment Guide Fire Risk Assessment Guide Thank you for your interest in the Fire Risk Assessment for your block. All of our blocks have had a recent Fire Risk Assessment in line with regulatory requirements and we are

More information

Fire Safety Policy 2018/19

Fire Safety Policy 2018/19 Fire Safety Policy 2018/19 Reviewed: March 2016 Next Review: March 2019 1. Policy Statement The School is committed to ensuring, so far as is reasonably practicable, the health, safety and welfare of all

More information

Fire Risk Assessment. A safety guide for users of the hall

Fire Risk Assessment. A safety guide for users of the hall Fire Risk Assessment A safety guide for users of the hall Assessment by the Trustees, August 2012 Description of Premises Wanstrow Village Hall is a modern, stone-built, community building situated at

More information

Fire Alarm Systems Design. incorporating Amendment No.2. a guide to BS5839. Part1:2002

Fire Alarm Systems Design. incorporating Amendment No.2. a guide to BS5839. Part1:2002 a guide to Fire Alarm Systems Design BS5839 Part1:2002 incorporating Amendment No.2 The Regulatory Reform (Fire Safety) Order (RRO) became law on 1 October 2006 Legally you must comply! What is the RRO?

More information

London Borough of Hammersmith & Fulham

London Borough of Hammersmith & Fulham Assessment Details: Property Assessed Flora Gardens 186-197, FLORA GARDENS, LONDON Assessment Date 19/12/2017 Assessment Valid Until 04/12/2020 Assessor Details Mark Richards LBHF Fire Risk Assessor QA

More information

GDST Fire Safety Strategy March 2016

GDST Fire Safety Strategy March 2016 GDST Fire Safety Strategy March 2016 GDST Fire Safety Strategy v1.0 March 2016 Page 1 of 17 Contents 1. Introduction 3 2. Compliance Statement 3 3. Fire Safety Strategy Aims and Objectives 3 Strategic

More information

PREMISES FIRE SAFETY HANDBOOK

PREMISES FIRE SAFETY HANDBOOK UCL ESTATES Fire Safety UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK Regulatory Reform (Fire Safety) Order 2005 1-19 TORRINGTON PLACE University College London 1-19 Torrington Place, London,

More information

RISK ASSESSMENT & EMERGENCY PREPAREDNESS PLAN

RISK ASSESSMENT & EMERGENCY PREPAREDNESS PLAN RISK ASSESSMENT & EMERGENCY PREPAREDNESS PLAN RISK ASSESSMENT The phases of an emergency includes: 1. Risk assessment 2. Mitigation 3. Preparedness 4. Response 5. Recovery Areas of Risk includes: Naturally

More information

Sandwell Valley School and Sandwell Community Care Trust Training. 150 Birmingham Road, West Bromwich, B70 6QT

Sandwell Valley School and Sandwell Community Care Trust Training. 150 Birmingham Road, West Bromwich, B70 6QT Fire Risk Assessment Company ame Address of premises (premises being assessed) Sandwell Valley School and Sandwell Community Care Trust Training 150 Birmingham Road, West Bromwich, B70 6QT ame of Responsible

More information

I. Scope: II. Environmental Health and Safety Fire Alarm System Impairment Program - Guideline Revision Date: April, 2018

I. Scope: II. Environmental Health and Safety Fire Alarm System Impairment Program - Guideline Revision Date: April, 2018 Environmental Health and Safety Fire Alarm System Impairment Program - Guideline Revision Date: April, 2018 Prepared by: EH&S The probability of casualties and major structural damage increases when fire

More information

Certification Assessment Instrument and Guidelines

Certification Assessment Instrument and Guidelines Certification Instrument Full compliance with BCA 96 will ensure passing 19 for Section 1 Do not need 100 to pass 1 SECTION 1 SAFETY (25 POINTS) Residential Fire Sprinkler System Not required to pass Section

More information

ACCESS SECURITY SYSTEMS (ELECTRONIC LOCKING) & ACCESSIBLE DOOR OPENING DEVICES ON MEANS OF ESCAPE

ACCESS SECURITY SYSTEMS (ELECTRONIC LOCKING) & ACCESSIBLE DOOR OPENING DEVICES ON MEANS OF ESCAPE Fire Safety Technical Guide ACCESS SECURITY SYSTEMS (ELECTRONIC LOCKING) & ACCESSIBLE DOOR OPENING DEVICES ON MEANS OF ESCAPE Access Security & Accessible Door Opening Systems - what you need to know:

More information