FW106 Fire Alarm Control Panel

Size: px
Start display at page:

Download "FW106 Fire Alarm Control Panel"

Transcription

1 Maple Armor FW106 Fire Alarm Control Panel Installation and Operation Manual DOC-FW106-UM R1.0

2 TABLE OF CONTENTS Control Panel Limitations... 1 Agency Listings, Approvals... 2 Underwriters Laboratories (UL/ULC)... 2 Requirements for All Installations... 2 Requirements for Local Protected Fire Alarm Systems... 2 Overview... 3 FW106 Fire Alarm Control Panel... 3 Board Assembly Diagram... 4 FW106 Configuration... 5 Specifications and Features... 6 The specifications and features of the FW106 Control Panel are described in Table System Components... 7 Components Overview... 7 AMI... 8 PTU... 9 PCU ALU NOU ROU XNU Battery INSTALLATION Cautions Control Panel Location Control Panel Installation Notice FW106 Mounting Space FW106 Installation Size Cabinet Mounting Remove Knock-Outs Battery Installation Unit Address Setting Operation Status handling Standby Condition Alarm Conditions Trouble Conditions Supervisory Conditions Device, Appliance Handling NAC Activation and Silence Device Supervision Detector Monitor I

3 Manual Station Response Drift Compensation Alarm Verification Event History LED, Buzzer, Buttons LEDs Operation Buzzer Operation Button Operation LCD Display Lamp Test Configuration and Maintenance PC Configuration Control Panel Access Control Control Panel Configuration SYSTEM WIRING Wiring Notes Power Limiting Wiring Entering the Enclosure Wiring Separation Power Supply Wiring AC Connection Battery Connection Addressable Loop Circuit Wiring Addressable Loop Circuit Wiring Class B Notification Appliance Circuit Wiring Notification Appliance Circuit Wiring Class A Notification Appliance Circuit Wiring Class B Relay Output Circuit Wiring External Network Circuit Wiring External Network Circuit Wiring - Class B Auxiliary Power Output Wiring Communication Port Connection System Checkout Before Turning the Power ON Power-up Procedure Troubleshooting Circuit Trouble Grounding Fault Battery Trouble Common Trouble Appendix-A: Compatible Devices Devices for Addressable Loop Circuits Appliances for Notification Appliance Circuits Appendix-B: Wire Selection Guide NAC Wire Selection Guide II

4 Appendix-C: Quantities of Notification Appliances Appendix-D: Battery Calculations Total System Currents Calculations Battery Capacity Appendix-D: FW106 Operating Instructions Appendix-E: Glossary and Acronyms III

5 List of Figures Figure 1 FW106 Control Panel... 3 Figure 2 Assembly Diagram... 4 Figure 3 Assembly Diagram (Inside)... 4 Figure 4 AMI (Front)... 8 Figure 5 AMI (Back)... 8 Figure 6 PTU... 9 Figure 7 PCU Figure 8 ALU Figure 9 NOU Figure 10 ROU Figure 11 XNU Figure 12 FW106 Enclosure Mounting Size Figure 13 FW106 Installation Size Figure 14 Wiring Separation Figure 15 Battery Installation Figure 16 Unit Address Switch Figure 17 LCD (Standby) Figure 18 LCD (Trouble) Figure 19 Alarm Verification Figure 20 Wiring Terminals Location Figure 21 AC Power Supply Wiring Figure 22 Ground Wiring Figure 23 AC Power Supply Wiring (Terminal) Figure 24 Battery Connection Figure 25 Addressable Loop Circuit Wiring Class A Figure 26 Addressable Loop Circuit Wiring Class B Figure 27 Notification Appliance Circuit Wiring Class A Figure 28 Notification Appliance Circuit Wiring Class B Figure 29 Relay Output Circuit Wiring Figure 30 External Network Circuit Wiring - Class B Figure 31 Auxiliary Power Output Wiring Figure 32 AMI Figure 33 Current Variation of NAC IV

6 List of Tables Table 1 FW106 Module Units... 5 Table 2 FW106 Control Panel Specifications... 6 Table 3 System Components... 7 Table 4 Battery Space Table 5 Unit Address Range Table 6 Trouble Event Type Table 7 LEDs Operation Table 8 Buttons Function Table 9 Access Level 0 Operation Table 10 Access Level 1 Operation Table 11 Access Level 2 Operation Table 12 Access Level 3 Operation Table 13 Device for Addressable Device Circuits Table 14 Appliance for Notification Appliance Circuits Table 15 Addressable Loop Wiring Table 16 NAC Wiring Table Table 17 Maximum Numbers of NA Table 18 System Currents Calculation Table 19 Battery Calculation V

7 Control Panel Limitations The FW106 control panel may not show an alarm condition without compatible initiating devices (smoke detectors, etc.) and notification devices (horn, lights, etc.) connected to it. Electrical ratings of the initiation and notification appliances must be compatible with the electrical ratings of the control panel and must be properly interconnected. The wiring used for interconnection must be large enough to carry the total current for all appliances without excessive voltage drop. Please refer to Appendix-B: Wire Selection Guide for detail. The control panel must be connected to a dedicated primary electrical source that has a high degree of reliability and adequate capacity for this control panel. The means of disconnecting this power source shall be available only to authorized personnel and clearly marked "Fire Alarm Circuit Control". A battery set (24V) that has enough capacity to properly operate the system for 24 hours standby and 5 minutes alarm per UL th Edition (section and ) or as otherwise required by local codes and the AHJ must also be connected to the control panel. These batteries do lose capacity with age. Batteries must be replaced when they fail to provide the control panel with the required standby and alarm power or after 4 years, whichever happens first. These batteries must be checked for performance at least twice a year or more often, if local requirements dictate. Even though this control panel was made to last for the expected life of the fire alarm system, parts can fail at any time. Therefore, a regular test program should be followed and documented to make sure each part of the system is tested, as indicated in Chapter 7 of NFPA 72, or more often if dictated by local code requirements. Malfunctioning units must be replaced or repaired immediately by factory authorized service personnel. This control panel is designed to show an alarm condition when the initiating devices connected to it detects specific conditions. These conditions may or may not represent a life-threatening condition. Unneeded evacuation of a building or an area may subject individuals to an unnecessary hazard. Therefore, it is important that the building owner, manager, or representative promulgate, distribute, and/or post instructions describing steps to be taken when the fire alarm control panel signals an alarm condition. These instructions should be developed in co-operation with representatives of the local authority having jurisdiction and in accordance with the applicable standards. 1

8 Agency Listings, Approvals Underwriters Laboratories (UL/ULC) Requirements for All Installations The general requirements are described in this section. When installing an individual device, refer to the specific section of the manual for additional requirements. 1. All field wiring must be installed in accordance with NFPA 70 National Electric Code, NBC, NBC, NFC, AHJ, and local code requirements. 2. Use the addressable smoke detectors listed in the compatibility chart (Appendix-A: Compatible Devices). 3. Use UL/ULC listed notification appliances compatible with the FW106 from those specified in Appendix-A: Compatible Devices of this manual. 4. A full system verification must be performed every time the panel is programmed or reprogrammed. Requirements for Local Protected Fire Alarm Systems At least one UL listed supervised notification appliances must be used. 2

9 Overview FW106 Fire Alarm Control Panel The FireWatcher FW106 is an intelligent Fire Alarm Control Panel designed for small to medium-scale facilities. The FireWatcher FW106 is ideally suited for both new and retrofit commercial, institutional, and industrial fire detection and notification applications. The FireWatcher FW106 is an addressable fire control system that meets the requirements of UL th Edition. It can support: 4 Addressable Loop Circuits and 1,008 addressable devices/points 4 Notification Appliance Circuits 5 form C dry relay contacts. The FW106 has A 7 colour LCD and a resolution of auxiliary function keys 9 LED indicators making it the most intuitive fire-alarm user interface. The FW106 can also connect with 4 remote annunciators via a CAN bus to form a fire emergency detection and notification network system. Figure 1 FW106 Control Panel 3

10 Board Assembly Diagram The FW106 provides modular assemble style. Figure 2 and Figure 3 show the assembly diagram: External Door Internal Door AMI Figure 2 Assembly Diagram External Door Internal Door Grounded Wire AMI ALU NOU XNU ROU Enclusure Mounting Hole 4 PCU Battery Grounded Wire PTU Figure 3 Assembly Diagram (Inside) 4

11 FW106 Configuration The FW106 function is governed by several modules. All the functional module units are shown in Table 1: Table 1 FW106 Module Units Module Units Type Qty. Fixed/ Configurable Notes AMI 1 Fixed Includes: CPU board, LCD, Keypad, LED, buzzer, etc. PTU 1 Fixed PCU 1 Fixed ALU 1-4 Configurable One ALU supports one addressable loop circuit and 252 devices. NOU 1-2 Configurable One NOU supports two NACs. ROU 1 Configurable XNU 1 Configurable For network connecting to annunciators Notes: ALU, NOU, ROU, and XNU are all of same dimension and same mechanical interface. 5

12 Specifications and Features The specifications and features of the FW106 Control Panel are described in Table 2. Table 2 FW106 Control Panel Specifications General Digital signal processor based design, fully configurable from front panel with password protection Environmental Operating temperature F (0-49 C) Relative humidity - Up to 90 F (32 C) To be installed in normal dry indoor environment only Primary Supply VAC 60Hz (3A), or VAC 50Hz (1.5A) Secondary Power Two 12V in series lead-acid batteries set Supply Charging capacity: 42AH Power Outputs Internal power supply for AMI ALUs and Addressable Loop Circuits NOUs and Notification Appliance Circuits XNUs, External Network Circuits ROUs One auxiliary power supply Non-Resettable/Resettable Power Output (configurable) Power limited 24VDC Output current: 500mA in normal standby, 1500mA in alarm One programmable relay 4 non-programmable status relays Status: Alarm, Supervisory, Trouble, Monitor Form C Contact Contact Rating: o 2A 125VAC o 2A 30VDC Relays Output Total of 4 circuits supported, total power available 8A 2 Class A or 2 Class B circuits on each NOU Maximum Current: 2A per NAC circuit Alarm Voltage: 24V nominal Bell code: Temporal 6

13 Notification Appliance Circuits Class B circuit For 4 remote annunciators connection Communications protocol: CAN Network Circuit Maximum Current (short ): 0.4A Class A/Class B circuit 252 addresses: detectors and modules max Output voltage range: 20.4V ~ 28V Maximum normal standby current: 100mA Maximum alarm current: 220mA Addressable Loop Circuits Maximum Current (short ): 0.4A Class A/Class B circuit 252 addresses: detectors and modules max Output voltage range: 20.4V ~ 28V Maximum normal standby current: 100mA Maximum alarm current: 220mA System Components Components Overview Table 3 describes the FW106 components. Model Table 3 System Components Description FW106 Components FW201 AMI FW391 PTU FW397 PCU FW327 ALU FW337 NOU FW347 ROU FW357 XNU 7

14 AMI The AMI is the main control unit of FW106 panel, which integrates the CPU board, 4 Signal status LEDs, 5 system status LEDs, 4 navigation buttons and 1 enter button, 6 functionality buttons and a buzzer. Signal Status LED LCD System Status LED Navigation and Enter Buttons Functionality Buttons Figure 4 AMI (Front) Ethernet Port 24VDC and CAN Bus Figure 5 AMI (Back) 8

15 PTU The PTU contains an internal transformer, which converts VAC, or VAC input to 24VAC output to PCU VAC, 60Hz, 3A Or VAC 50Hz, 1.5A Input Output to PCU 24VAC 12A maximum Figure 6 PTU VAC or VAC input is optional. A slide switch is used to fulfill this function. Please refer to AC Connection for switch usage information. 9

16 PCU Provide power supply output to the system (AMI, ALU, NOU, ROU, XNU, Addressable Loop Circuits, Notification Appliance Circuits, Relay output, Network circuits) with regulated 24VDC. Maximum output current is 12A. Terminals BAT+ and BAT- connect two lead-acid batteries (12VDC) in series. Maximum Charge Voltage: 27.8 VDC Maximum Charge Current: 3A. Sufficient battery charging capability is available to charge 42AH sealed leadacid batteries within code requirements for up to 24 hours standby plus 30 minutes alarm. Use a microprocessor-controlled transfer circuit to switch power supply for the system to standby batteries when AC power is off or low. Communicate to the AMI to report fault conditions. PCU address is set by the rotary switch on the board. The default is "1". The PCU must be set to a correct address before use. Please refer to Unit Address Setting section for detail. AUX. Output:24VDC Output: 24VDC CAN Bus Output: 24VDC CAN Bus Input from PTU:24VAC Battery Input Figure 7 PCU 10

17 ALU One ALU can support one addressable loop circuit, which supports up to 252 points of addressable devices. Initializes and operates all devices residing on the loop and communicates all relevant devices and event information, such as alarms and troubles, to the System CPU. Circuit topology support: Class A or Class B. ALU address is set by the rotary switch on the board. The valid address range is 1~4. CAN Bus Input:24VDC Figure 8 ALU The ALU must be set to a correct address before use. Please refer to Unit Address Setting section for detail. 11

18 NOU One NOU can support two independent notification appliance circuits. Circuit topology support: Class A or Class B. Maximum Current: 2A per NAC circuit, 4A total per NOU NOU address is set by the rotary switch on the board. The valid address range is 1~2. Notification Appliance Circuits CAN Bus Input:24VDC Figure 9 NOU The NOU must be set to a correct address before use. Please refer to Unit Address Setting section for detail. 12

19 ROU One ROU card supports five dry contact relays. o Alarm Relay o Supervisory Relay o Trouble Relay o Monitor Relay o Programmable Relay The relay contacts are Form C style. ROU address is set by the rotary switch on the board. The valid address range is 1. Relay Output Circuits CAN Bus Input:24VDC Figure 10 ROU The ROU must be set to a correct address before use. Please refer to Unit Address Setting section for detail. 13

20 XNU The FW106 control panel communicates to FW121 annunciators, up to 4. Circuit topology support: Class B. XNU address is set by the rotary switch on the board. The valid address range of the FW106 is 1. Figure 11 XNU The XNU must be set to a correct address before use. Please refer to Unit Address Setting section for detail. Battery FW106 can support 42 AH sealed lead-acid batteries within code requirements for up to 24 hours normal standby plus 30 minutes alarm. Batteries must be replaced when they fail to provide the control panel with the required standby and alarm power or after 4 years, whichever happens first. Please refer to Battery Calculations to select an appropriate Battery Capacity. 14

21 INSTALLATION Cautions 1. Remove the PCB for any procedure that may cause dust, metal shavings, grease, or such matter to affect the operation of the boards or get in contact with the units. 2. Disconnect all sources of power prior to installing or removing modules, connecting or disconnecting wiring and programming jumpers. 3. Group the incoming wires through the top of the enclosure. For easy identification and neatness use a wire tie. 4. DO NOT insert cables through bottom of the box. This space is reserved for Batteries. Control Panel Location The control panel should be located near an exit at ground level where the normal ambient temperature is maintained within the control panel specification (see the General Specifications). The unit should be in an area free of dust, vibration, moisture, and condensation. Any auxiliary battery box or other accessory not connected through a protective device or a circuit designed for remote connection must be within 20 ft. and in the same room, connected through the electrical conduit. Control Panel Installation Notice The cabinet must be fastened securely to a clean, dry, shock-free, and vibration-free surface in a protected environment. Consider the following when mounting the cabinet: Mounting height for visual and manual access to the Display Board Weight and size of cabinet Local mounting codes When mounting the cabinet, position the cabinet clear of obstructions so that the door can open freely and indicators and controls are easily accessible. The fire alarm control panel must be mounted in a properly accessible location, as required by the applicable codes and the AHJ. Installation must be done by qualified personnel who have thoroughly read and who understands these instructions. 15

22 FW106 Mounting Space The FW106 cabinet can be surface-mounted or flush-mounted. The mounting space is shown in Figure 12. Do NOT flush mount in a wall designated as a fire separation. Figure 12 FW106 Enclosure Mounting Size 16

23 FW106 Installation Size Figure 13 FW106 Installation Size 17

24 Cabinet Mounting To install the cabinet: Select a clean, dry, shock, and vibration-free surface in a protected environment. Position the cabinet clear of obstructions so that the front door opens freely and the controls and indicators are easily accessible. Mark the locations of the two upper mounting bolts of the cabinet on the wall. There are two key-shaped cutouts on the top of the back box. Make sure the end with the two key-shaped cutouts is on top when installing the back box. Drill the two holes marked in the previous step and screw in the top bolts, leaving a small gap between the wall and each top bolt. Choose a screw type and length able to support the control panel, options, and battery set. You may need a different screw type depending on the wall material. Place the cabinet over the two top bolts and allow it to slide down over the bolts. Mark, drill, and install the two bottom bolts in the cabinet. Tighten all four bolts securely against the back wall of the cabinet. Remove Knock-Outs Prepare the enclosure for electrical wiring by breaking out the appropriate conduit entry points. The optional knockout locations and quantities are shown in Figure 14. The power limited and non-power limited conductors must be separated. In order to maintain the minimum separation, follow the wire routing shown in Figure 14. At least 1/4 in. is required between the non-power limited and power limited conductors. Power limited and nonpower limited wiring must be run in a separate conduit. Attach conduit (if required) and run wires as required. Label each field cable for future reference. Basic system wiring and detector positioning must be done in accordance with NFPA 72 or other applicable codes and instructions from the appropriate local authority having jurisdiction. Unit connections and limitations are as indicated on the wiring diagrams included in the SYSTEM WIRING section of this manual. 18

25 For enclosure mounting Power Limited 12 optional knock-outs for field wiring For enclosure mounting Power Limited 4 optional knock-outs for field wiring Non Power Limited 4 optional knock-outs for relay wiring Non Power Limited 2 optional knock-outs for AC input For enclosure mounting Figure 14 Wiring Separation 19

26 Battery Installation Use the battery calculation chart to determine the battery capacity and size. Place the batteries in the space provided in the bottom of the enclosure. Refer to Table 4 to determine the maximum available battery space. Table 4 Battery Space mm inch Length (for 2 batteries) Width Height Battery position Figure 15 Battery Installation 20

27 Unit Address Setting Every unit (ALU, NOU, ROU, XNU, PCU) has an internal rotary switch to set an address. The rotary switch is located at the bottom of each unit s cover. Figure 16 Unit Address Switch The unit must be set to an appropriate address before use. The valid address range is listed in Table 5. Table 5 Unit Address Range Unit Type Address Range ALU 1~4 NOU 1~2 ROU 1 PCU 1 XNU 1 21

28 Operation Status handling This section describes the control panel responses and operation in standby condition, alarm condition, trouble condition, and supervisory condition. Standby Condition In normal standby operation, the green AC ON LED should be the only illuminated LED. The LCD will show the system label and the current time :47:23 Time & Date Normal FireWatcher Project:xxx Product Name & Project Name Functionality Buttons Acknowledge Buzzer Silence reset Manual Alarm Menu Figure 17 LCD (Standby) Alarm Conditions When the system detects an alarm condition, the system alarm LED activates (ON flashing) and the buzzer activates (ON alarm pattern). Local audible and visual signals along with remote alarm signals operate, and the LCD panel indicates the zone or point initiating the alarm. The LCD is similar to the Trouble conditions shown in Figure 1. When an alarm is received, proceed in accordance with the established emergency plan. Make sure all personnel is accounted for and notify the Fire Department. 22

29 To silence the visible and audible devices after the evacuation (where permitted by the codes and control panel programming), press the ALARM SILENCE button. The alarm visible and audible indicators will be silenced and the alarm silence LED will change from off to on. Pressing the ACKNOWLEDGE button will silence the local buzzer and change the LED alarm indicator from flashing to steady. Do not attempt to reset the system until the alarm condition has been cleared. The LCD will indicate the zone in which the alarm was detected. The detector or module associated with the device initiating the alarm will display a light indicating activation (if applicable). When the alarm condition has been corrected, return the system to normal standby operation by pressing the RESET button. Trouble Conditions In case of a trouble condition, the system trouble LED and any programmed trouble LEDs activate (ON flashing), the LCD identifies the problem, and the buzzer sounds in trouble pattern. Total: 8 Alarm Supervisory Trouble Other signal Output 1 Device_Missing A :30:25 Event Type Event List 2 Device_Missing A :30:25 3 Device_Missing A :30:25 4 Device_Missing A :30:25 5 Device_Missing A :30:25 6 Device_Missing A :30:25 7 Device_Missing A :30:25 8 Device_Missing A :30:25 Acknowledge Signal Silence Buzzer Silence reset Manual Alarm Menu Functionality Buttons Figure 18 LCD (Trouble) 23

30 Refer to Error! Reference source not found. for trouble event types and explanation of the events. Table 6 Trouble Event Type Category Trouble Event Type Explanation System PrimaryPower_Loss Primary power is lost Battery_Loss ControlPanel_Grounding PrimaryPower_OverVoltage Charger_OverVoltage ArchiveFile_Missing ConfigFile_Missing ConfigFile_ Damaged Battery is lost Control panel detects ground condition Primary power voltage is too high Charger voltage is too high History record file is missing Configuration file is missing Configuration file is damaged Unit ALU_Conf.Mismatch ALU s configuration file is mismatched with AMI s AMI_ Jumper Unit_Missing Ext._Missing Unit_Addr.Conflict AMI has a jumper shorted PCU/ALU/NOU/ROU/XNU is missing The network annunciator is missing 1. Two or more ALUs have the same addresses, or 2. Two NOUs have the same addresses Unit_ Illegal Unit_ SwitchError The unit is working, but it is not configured The unit address changed during running Circuit Ext._Illegal The network annunciator is working, but it is not configured Ext._Grounding Ext. Addr.Conflict Bus_Short The network circuit is grounded Two or more annunciators on the network circuit have the same address The addressable loop circuit is shorted 24

31 Bus_Open Bus_ CrossPower NOU_ CircuitTrbl The addressable loop circuit is open The addressable loop circuit wire is cross power The notification appliance circuit is malfunctioning (open, short, grounding, etc.) Field Device Heat_SensingError The heat detector sensing has an error Smoke_Contamination Smoke_SensingError Init.Device_Duplicate Init.Device_Illegal Init.Device_Missing Init.Device_WrongType Init.Device_Vol.Abnormal Init.Device_GeneralTrbl The chamber of the smoke detector is contaminated The chamber of the smoke detector is severely dirty and can t be used Two or more devices have the same address The device is working online, but it is not configured The device is configured, but it is missing The device type is incorrectly configured The device detects abnormal line voltage The device has internal hardware trouble When the trouble condition has been noted, pressing ACKNOWLEDGE button will silence the buzzer and change the trouble LED to steady ON. The panel has a 24-hour Supv /Trouble Resound function. If the trouble condition is not corrected and the Supv/Trouble Resound Reminder timer has elapsed, the panel will re-annunciate the trouble condition. When the indicated trouble condition has been cleared, the system reverts to normal standby condition automatically. Supervisory Conditions In case of a supervisory condition, the system supervisory LED activates (ON flashing) and the buzzer activates in supervisory pattern. The LCD notes the supervisory event and the buzzer sounds in supervisory pattern. When the supervisory condition has occurred, pressing ACKNOWLEDGE button will silence the buzzer and change the supervisory LED to steady ON. 25

32 If the panel is configured for Supv/Trouble Resound Reminder, when the supervisory condition is not corrected and the Supv/Trouble Resound Reminder timer has elapsed, the panel will re-annunciate the supervisory condition. Device, Appliance Handling NAC Activation and Silence The notification appliance circuits are controlled by a microprocessor to provide more versatility than in a total hardware system. Output Sounding Patterns - Notification appliance circuits are operable in Temporal pattern. Audible Silence Inhibit - Control panel may be programmed to inhibit audible silence from 0 to 20 minutes from the last alarm. All of the NACs are power limited and support synchronization of the listed devices. The open, short, and grounding troubles of notification appliance circuit are monitored. Device Supervision Device type supervision: If the type reported by an addressable detector or module does not agree with the configuration, the system reports a trouble condition. Device address supervision: The system checks that the configured devices on the Addressable Device Circuit and the Serial Interface Circuit respond to an address poll. The system reports a trouble condition if one of the following conditions is detected: Configured device is missing. Unconfigured device is installed. Two or more devices are programmed with the same address location (this trouble is only detected by manually checking). Detector Monitor The control panel processor polls the detectors for their status. The detector determines normal, trouble, and alarm conditions and communicates the status to the control panel. The control panel can automatically trigger an alarm or a trouble for various conditions, including: Active Illegal Wrong Type Missing Address Conflict General Trouble Sensing Error Contamination Please refer to the Trouble Conditions section for more detail on each event type. 26

33 Manual Station Response Addressable manual stations may be intermixed on the circuit with proper response programmed into the control panel. The alarm response time when pressing the manual station is less than 1.2 sec. Drift Compensation The Drift Compensation is built into a compatible detector and is not performed by the panel. Drift compensation automatically adjusts for gradually increasing effects of dust and other accumulations of dirt in the detectors. It will adjust the thresholds to compensate for a detector going dirty according to the gradual change in the normal clean air value received. When it can no longer compensate for an increasingly dirty detector, a dirty detector trouble (Contamination trouble) is indicated for that device. Alarm Verification The Alarm Verification function is supported by this panel. One typical alarm verification phase can be divided into 2 periods. The first period is a retard period in which no alarm reports on the Fire Alarm Control Panel (FACP). The second period is a confirmation period in which alarm reports on the Fire Alarm Control Panel if a device is in alarm status. The detail alarm verification phase is illustrated in Figure 19. Figure 19 Alarm Verification A - Smoke detector goes into alarm. (LED on device turns to steady on) AB - Retard Period: Fire Alarm Control Panel senses detector in alarm and delays alarm signal for 50s. During this period, no alarm event reports on the Fire Alarm Control Panel. BC - Confirmation Period: Detector is operational for alarm at point B. If the detector is still in alarm at point B, the Fire Alarm Control Panel will report an alarm. If the detector is not in alarm, the system returns to standby. If the detector re-alarms at any time during the confirmation period the Fire Alarm Control Panel will alarm. The period length is 60s. CD Restart next alarm verification period if new alarm occurs. 27

34 Event History The control panel includes a non-volatile memory recording 5000 events, plus a separate 1000 alarm-only events. Identified alarm, trouble, supervisory, status, and other significant events will be recorded along with the date and time of occurrence. These can be viewed by operating the front panel push buttons. To recall past events, proceed as follows: Press the MENU button. On the MENU display, select Archive. Press the Enter button. Use the up button next to the LCD to see the previous event display. Use the down button next to the LCD to see the next event display. The history record rule is: New events overwrite old events when filled. The events are sorted by time occurrence sequence. Events recorded in the history are: Alarm, Trouble, Supervisory, and Monitor conditions Alarm silence/resound System reset System startup Enable/disable function Start and stop of Walk Test Trouble/supervisory reminder Trouble/supervisory restored to normal 28

35 LED, Buzzer, Buttons The FW106 has a buzzer, 9 LEDs, 5 navigational buttons and enter button, 6 functionality buttons. LEDs Operation Refer to Table 7 for the LEDs operation. Table 7 LEDs Operation Steady ON Indicates that there are alarm events and all alarm events have been acknowledged. ALARM Red OFF Indicates that there is no alarm event in the system. Flashing Indicates that there are alarm events in the system, but some of them have not been acknowledged. Steady ON Indicates that there are supervisory events and all of them have been acknowledged. SUPERVISORY Yellow OFF Indicates that there is no supervisory event in the system. Flashing Indicates that there are supervisory events in the system, but some of them have not been acknowledged. Steady ON Indicates that there are trouble events and all of them have been acknowledged. TROUBLE Yellow OFF Indicates that there is no trouble event in the system. Flashing Indicates that there are trouble events in the system, but some of them have not been acknowledged. Steady ON Indicates that there are other signal events and all of them have been acknowledged. OTHER SIGNALS Yellow OFF Flashing Indicates that there is no other signal event in the system. Indicates that there are other signal events in the system, but some of them have not been acknowledged. AC ON Green Steady ON OFF Indicates that the system's main power works normally. Indicates that the system is not powered on yet or the system is powered by a battery 29

36 SIGNAL SILENCE Yellow Steady ON OFF Indicates that there are activated NAC devices and at least one of them has been silenced. Indicates that there is no NAC activated or a NAC is activated and not silenced. GROUND FAULT Yellow Steady ON OFF Indicates that there are Ground Fault events in the system. Indicates that there is no Ground Fault event in the system. BY PASS Yellow Steady ON OFF Indicates that there are disabled events. Indicates that there are no disabled events. CPU FAULT Yellow Steady ON OFF Indicates that the CPU is in fault. Indicates that there is no CPU fault. Buzzer Operation The buzzer operates as follows: Normally OFF indicates that the system is in normal condition or all events in the system have been acknowledged. ON (continuous) indicates that at least ONE unacknowledged alarm is present in the system. ON (1 pulse per 0.5 second) indicates that at least ONE unacknowledged supervisory event is present in the system. ON (1 pulse per 1 second) indicates that at least ONE unacknowledged trouble event is present in the system. ON (1 pulse per 2 second) indicates that at least ONE unacknowledged other signal event is present in the system. 30

37 Button Operation The control panel has 5 navigational and enter buttons, 6 functionality buttons. The button functions are listed in Table 8. Table 8 Buttons Function Navigation Buttons To select the items in the menu, or to select letters or digits for input. Cursor movement will be speedy if the button keeps being pressed. Enter Button To select or confirm information Notes: The functionality buttons below have different roles depending on the view. The roles in main view are listed below. F1 Acknowledge Acknowledges once a single unacknowledged event in the system. F2 Signal Silence/ Resound Signal Silence - Silences specific NAC devices in the system. This will cause specific activated NAC devices to become silenced. Signal Resound - Resound specific NAC devices in the system. This will cause specific activated, but silenced NAC devices, to resound. F3 Buzzer Silence/Resound Buzzer Silence Silence the buzzer Buzzer Resound Resound the buzzer F4 Reset Clears all obsolete events and resets all devices, except those disabled in the system. F5 Manual Alarm Activates NAC devices F6 Menu Button for user operations. 31

38 LCD Display The LCD can display 8 events at a time. Users can browse more events by pressing the up/down button until the first event or last event message is reached. Events are displayed according to the following rules: 1: Events priority: Alarm > Supervisory > Trouble > Other Signal>Output 2: Within events of the same priority, all events are displayed in order of occurrence, the latest being displayed first. However, the sequence of alarm event is configurable. Lamp Test When selected, the lamp test activates the LCD, the buzzer, and turns on all the LEDs on the user interface. It then reverts to its previous state. To initiate a lamp test, proceed as follows: 1: Press the "MENU" button. 2: Select Lamp Test to run. The lamp test operates the indicators only on the units being operated. No record is reported to the system history. 32

39 Configuration and Maintenance PC Configuration Programming the panel may be done by temporarily connecting the programming port to a computer. This is the recommended method to configure the panel. The Maple Armor FW401 Configurator software is available to configure of the control panel using a Personal Computer (PC) with an Ethernet port. This allows ease of operation by preparing the program in advance and downloading it to the control panel by a simple and fast operation. Control Panel Access Control The FW106 provides configuration and maintenance functions to set and control various features in the system. The configuration and maintenance functions are protected by access control. The following levels of security protect the system from unauthorized use: Level 1 Locked Door Level 2 Locked Door and 4-digit Password, Level 2 provides control functions. Level 3 Locked Door and 4-digit Password, Level 3 provides control functions and parameter change functions. To access the maintenance features, press the MENU button and select Access To System, enter the four digit code when prompted, then press OK. The User Level is also accessible from the Remote LCD Annunciators. 33

40 Control Panel Configuration The configuration and the maintenance of the control panel may be accomplished through the keypad included in the control panel. Different access levels have different operation rights. Refer to Table 9 to Table 12 for more details. Table 9 Access Level 0 Operation Access Control No Accessible Functions Access Control Browse real-time event(s) displayed on LCD Locked door Table 10 Access Level 1 Operation Browse all real-time events(s) Browse all system nodes properties Acknowledge all real-time events(s) Accessible Functions Silence/Resound buzzer Silence/Resound notification appliances Reset System Activate Manual Alarm Query History Record Access Control Table 11 Access Level 2 Operation Locked Door and 4-digit Password Browse system nodes properties Set System Time Set System Date Accessible Functions Silence/Resound Buzzer Bypass Field Devices Bypass NACs Bypass Status Relays 34

41 Access Control Accessible Functions Table 12 Access Level 3 Operation Locked Door and 4-digit Password Browse all system nodes properties Silence/Resound Buzzer System Change Customer Text Set System Time Set System Date Set Alarm Sequence Set Supervisory Latched Set Monitor Latched Set Daylight Saving Time Set Login Time Set Silence Inhibit Time Control Panel Annunciator ALU Change Customer Text Change Customer Text Change Topology Device Duplicate Check Device Register Device Auto Register NOU FW511 Smoke Detector Change Topology Change Device Address Change Device Type Bypass Device Change Customer Text Change Post 35

42 FW521 Heat Detector Change Device Address Change Device Type Bypass Device Change Customer Text Change Post FW721 Manual Station Change Device Address Change Device Type Bypass Device Change Customer Text Change Post FW811 Input Module Change Device Address Set Input Function Bypass Device Change Customer Text Change Post Change PostA FW831 Relay Module Change Device Address Bypass Device Change Customer Text Change Post Change PostA FW821 Input-Output Module Change Device Address Bypass Device Change Customer Text Change Post 36

43 Change PostA Notification Appliance Circuit Change Customer Text Change Post Programmable Relay Manual Zone Auto Zone Bypass Device Change Customer Text Change Customer Text When disabling an input or an output device, the application will indicate a trouble condition. 37

44 SYSTEM WIRING Before connecting the field wiring, check the wiring for opens, shorts, grounds, and stray voltages. WARNING Damage may result if a high-voltage insulation tester is used on wiring while connected to the control panel and field devices. Terminate the field wiring to the main board in accordance with the diagrams in the SYSTEM WIRING section and in the system design documents. All wiring must be in accordance with local codes and the National Electrical Code. Wiring Notes Basic system wiring and detector locations must be in accordance with NFPA 72 or other applicable codes and instructions from the appropriate local authority having jurisdiction. Devices that may be satisfactorily used with the control panel are shown in the Appendix-A: Compatible Devices. Wire reference data are listed in Appendix-B: Wire Selection Guide. Power Limiting In accordance with NEC Article 760 and UL 864, all power limited fire protective signalling conductors must be located at least 1/4 inch away from all of the following wiring located within a control panel: Electric light Power Class 1 or non-power limited fire protective signalling conductors To meet these requirements, the following guidelines must be observed when installing modules and wiring to this control panel. When installing power limited field wiring, the installer must comply with NEC article 760, which states: The fire alarm power-limited circuits are installed using Types FPL, FPLR, FPLP or permitted substitute cable, provided these power-limited cable conductors extending beyond the jacket are separated by a minimum of 0.25 in. (6.35 mm) or by a nonconductive sleeve or nonconductive barrier from all other conductors. If energy limited cable or equivalent is not used within the FW106 enclosure, then the following guidelines do not apply. In that case, be sure to follow standard wiring practices. Wiring Entering the Enclosure Non-Power Limited Wiring - Wiring entering the enclosure from the bottom left side and right side of the enclosure is considered non-power limited wiring. Wiring must be in the shortest route and must not overlap any other wiring. Power Limited Wiring - Wiring entering the enclosure from the top left side of the enclosure is considered power limited. Wiring must be in the shortest route and must not overlap any other wiring. 38

45 Wiring Separation All high voltage and non-power limited wiring must be separated from power limited wiring. A separation of at least 1/4 inch must be maintained with high voltage and non-power limited wiring running in separate conduit openings from power limited wiring. The AC power, the battery wiring, and the 5 relay circuits are not power limited. All other circuits leaving the control panel are power limited. Refer to Figure 20 for the proper installation rules. LA- LA+ LB- LB+ LA- LA+ LB- LB+ LA- LA+ LB- LB+ LA- LA+ LB- LB+ 2A- 2A+ 2B- 2B+ 1A- 1A+ 1B- 1B+ 2A- 2A+ 2B- 2B+ 1A- 1A+ 1B- 1B+ 2NO 2COM 2NC 4NO 4COM 4NC 5NC (NA) 1NO 1COM 1NC 3NO 3COM 3NC 5NO 5COM Power Limited circuit Non-Power Limited circuit Addressable Loop Circuit Addressable Loop Circuit Addressable Loop Circuit Addressable Loop Circuit Notification Appliance Circuit 1#/2# Notification Appliance Circuit 1#/2# External Network Relay Output Circuit Circuit 1#~5# AL AH BL BH ALU ALU ALU ALU NOU NOU XNU ROU Address = 1 Address = 2 Address = 3 Address = 4 Address = 1 Address = 2 Address = 1 Address = 1 4 Slots for ALU 2 Slots for NOU 1 Slot for XNU 1 Slot for ROU Non-Power Limited circuit AC Input Circuit Power Limited circuit Auxiliary Power Circuit VAUX GND PCU PTU Figure 20 Wiring Terminals Location 39

46 Power Supply Wiring AC Connection Wire the AC supply to the power supply on the back of the enclosure. The supply should originate from a dedicated 15A branch circuit. It should be provided with a breaker or other means of isolation that must be coloured red. Dangerous voltages will be present on the terminal block and on other components surrounding it when the AC supply is turned on. Do not touch. AC Input terminals must be located on the left side of the enclosure and in the knockouts position shown in Figure 21. Route all high voltage and non-power limited wiring together and away from power limited wiring. Refer to the Power Limiting section for more details. AC Power Connection Option 1 AC Power Connection Option 2 Figure 21 AC Power Supply Wiring Connect the ground cable to the earth stud on the enclosure back box. 40

47 Connect the ground cable to the earth stud Figure 22 Ground Wiring AC Switch Matches Rated Voltage! Make Sure this Slide Switch Matching Rated Voltage! Figure 23 AC Power Supply Wiring (Terminal) Make sure the slide switch matches the rated voltage. Otherwise the PTU will be permanently damaged! 41

48 Battery Connection WARNING Improper battery connections or shorting battery terminals may damage the system and/or the batteries and may cause personal injuries. The control panel battery charge capacity is up to 42AH. Use 12V batteries of the same AH rating. Determine the correct AH rating as per your current load calculation (see Appendix-D: Battery Calculations). Wire batteries in series to produce a 24-volt equivalent. Do not parallel batteries to increase the AH rating. PCU BAT+ BAT- Figure 24 Battery Connection 42

49 Addressable Loop Circuit Wiring One ALU card supports one addressable loop circuit. Addressable Loop Circuit supports Class A and Class B style. A maximum of 252 devices can be connected to the circuit. All the compatible detectors and manual stations are polarity insensitive, while the compatible modules are polarity sensitive. Refer to the instruction sheets packed with each device. The detectors and modules may be wired together according to several NFPA defined wiring styles. The wiring style that is appropriate for your installation should be determined from the relevant building codes and the local Authority Having Jurisdiction. Addressable Loop Circuit Wiring Class A Class A provides redundant communication paths. S H M I O I/O Up to 252 devices S Smoke Detector Isolator Module LA- LA+ LB- LB+ ALU H M Heat Detector Manual Station I O Input Module Relay Module I/O Input-Ouput Module Figure 25 Addressable Loop Circuit Wiring Class A 43

50 Addressable Loop Circuit Wiring Class B Class B wiring allows branching of circuit connections. S H M I O I/O S H M I O I/O Up to 252 devices S Smoke Detector Isolator Module LA- LA+ LB- LB+ ALU H M Heat Detector Manual Station I O Input Module Relay Module I/O Input-Ouput Module Figure 26 Addressable Loop Circuit Wiring Class B 44

51 Notification Appliance Circuit Wiring One NOU card supports two notification appliance circuits. Refer to the instruction sheets packed with each NAC device. Notification Appliance Circuit Wiring Class A S H H/S 2A- 2A+ 2B- 2B+ 1A- 1A+ 1B- 1B+ NAC circuit #2 is not shown, wire as shown above NOU S Strobe H Horn Horn/Strobe H/S Figure 27 Notification Appliance Circuit Wiring Class A 45

52 Notification Appliance Circuit Wiring Class B One EOL (R=10kOhms) is needed at the end of the line to monitor the circuit integrity. EOL (R=10KΩ) S H H/S 2A- 2A+ 2B- 2B+ 1A- 1A+ 1B- 1B+ NOU NAC circuit #2 is not shown, wire as shown above S Strobe H Horn Horn/Strobe H/S Figure 28 Notification Appliance Circuit Wiring Class B 46

53 2NO 2COM 2NC 4NO 4COM 4NC 5NC (NA) 1NO 1COM 1NC 3NO 3COM 3NC 5NO 5COM Installation and Operation Manual Relay Output Circuit Wiring One ROU card supports five dry contact relays. Alarm Relay Trouble Relay Program mable Relay Programmable on same line or with a - Relay contact (Shown in normal standby condition, see left drawing) NO Normal Open COM Common NC Normal Close Superviso ry Relay Monitor Relay Supervisory on same line or with a - ROU Figure 29 Relay Output Circuit Wiring 47

54 External Network Circuit Wiring The external network circuit can address up to 4 remote annunciators. Devices on the circuit may be connected up to 4000 feet from the control panel. The FW106 control panel can be connected to FW121 annunciators using a XNU. Remote Device Power The control panel auxiliary power can provide power for 4 annunciators. If more current supply is required for the connected devices (e.g. field modules), external power must be provided. Each address on the circuit must be fully powered from either auxiliary power of the control panel or of the external power. When connecting annunciators on the external network circuit, the data wires must be daisy chained and with no T-taps to preserve the integrity of the data. Figure 30 shows the proper wiring. External Network Circuit Wiring - Class B Address = 1 Address = 2~5 Address = 2~5 XNU XNU AL AH BL BH AL AH BL BH AL AH BL BH XNU Control Panel with caps FW106 control panel FW121 Annunciator FW121 Annunciator Figure 30 External Network Circuit Wiring - Class B About the XNU Jumper Each XNU has an internal jumper on its upper right side which must first be correctly configured. Jumper If this XNU is located at the end of the external network circuit (e.g. in the left figure, the XNUs of addresses 1 and 5), the jumper must be switched to ON. AL AH BL BH XNU ON external network circuit (e.g. in the XNUs of addresses 2, 3, and must be switched to OFF. AL AH BL BH Jumper OFF If this XNU is located in the middle of the the left figure, 4), the jumper XNU Please refer to the Unit Address Setting section to set the XNU s address. 48

55 Auxiliary Power Output Wiring The Power-supply and Charging Unit provide auxiliary power output connection. This power output can be configured as resettable or non-resettable. The resettable terminal interrupts the power for 6 seconds after a reset condition. Auxiliary Power Output (24VDC/1.5A Max) VAUX GND To provide external power supply for: - FW121 Annunciators - FW821 Input-Output modules PCU Figure 31 Auxiliary Power Output Wiring Communication Port Connection An Ethernet standard plug is provided for temporary connection to a computer for panel programming. The Ethernet standard plug is connected to the Ethernet port of the computer that has the FW401 configurator tool. This is used to upload and/or download panel configuration for programming. The computer must be disconnected from the panel if not in use. Ethernet Port Figure 32 AMI 49

56 System Checkout The following are the recommended steps that should be followed before and during the powering up of the FW106. Before Turning the Power ON 1. To prevent sparking, DO NOT connect the battery first. Connecting the batteries should only be done once the system has been powered from the main AC Supply. 2. Check all field (external) wiring for opens, shorts, and ground. 3. Check that all interconnection cables are secure and that all connectors are plugged in properly. 4. Check all switches for proper setting. 5. Check the AC power wiring for proper connection. Observe/check slide switch position. 6. Close the front cover plate before powering the system from main AC supply. Power-up Procedure 1. Once the Before Turning the Power ON procedure is done, power-up the panel. The green AC ON LED should illuminate. Since the batteries are not connected, the Battery Trouble LED should illuminate, the Trouble LED should flash, and the Trouble Relay (on the main board) will be active. 2. Connect the batteries while observing correct polarity; the red wire is positive (+) and the black wire is negative (-). All indicators should extinguish except for normal power AC ON green LED. 50

FireSeeker Fire Alarm Control Panel Model FS-250 Installation, Operation and Maintenance Manual

FireSeeker Fire Alarm Control Panel Model FS-250 Installation, Operation and Maintenance Manual FireSeeker Fire Alarm Control Panel Model FS-250 Installation, Operation and Maintenance Manual P/N 315-049353-1 Siemens Building Technologies Fire Safety TABLE OF CONTENTS INTRODUCTION... 1 CONTROL PANEL

More information

MR-2602 Two Zone Fire Alarm Control Panel

MR-2602 Two Zone Fire Alarm Control Panel MR-2602 Two Zone Fire Alarm Control Panel Installation Manual Secutron LT-2015 Rev.3 July 2010 Table of Contents 1 Introduction 1.1 The MR-2602 Fire Alarm Control Unit... 11 1.1.1 General features...

More information

MPC-6000 / MPC-7000 / RND-2

MPC-6000 / MPC-7000 / RND-2 MPC-6000 / MPC-7000 / RND-2 Fire Alarm System Control Unit Installation, Operation and Maintenance Manual Siemens Building Technologies, Inc. 8 Fernwood Road Florham Park, NJ 07932 Tel: (973) 593-2600

More information

FireSeeker Fire Alarm Control Panel Model FS-100 Installation, Operation, and Maintenance Manual

FireSeeker Fire Alarm Control Panel Model FS-100 Installation, Operation, and Maintenance Manual Fire Safety FireSeeker Fire Alarm Control Panel Model FS-100 Installation, Operation, and Maintenance Manual Siemens Building Technologies, Inc. Siemens Building Technologies, Ltd. 8 Fernwood Road 2 Kenview

More information

Fire Alarm Control Panel Model FC901-U3/FC901-R3

Fire Alarm Control Panel Model FC901-U3/FC901-R3 Fire Alarm Control Panel Model FC901-U3/FC901-R3 Installation, Operation and Maintenance Manual Siemens Industry Inc. TABLE OF CONTENTS INTRODUCTION... 1 CONTROL PANEL LIMITATIONS... 1 PREFACE... 2 FCC

More information

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 031703 Overview: The Altronix AL802ULADA is an extremely cost effective 8 amp voltage regulated

More information

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide System Reset Trou ble Silence Ala rm Silence Manual Ala rm ENTER NO YES Letters Numb ers Keyword Radionics System Reset Trouble Silence Alarm Silence Manual Alarm ENTER NO YES Le ters Numbers Keyw ord

More information

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0 CFP-105 Fire Alarm Control Panel Installation Manual Version 1.0 WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability

More information

Installation Guide for models:

Installation Guide for models: 140 58th St. Brooklyn, NY Access Power Controllers with Power Supplies Installation Guide for models: Maximal3FD - 12VDC @ 4.6 amp or 24VDC @ 5.2 amp. - Sixteen (16) PTC protected power-limited outputs.

More information

Installation Guide for models:

Installation Guide for models: 140 58th St. Brooklyn, NY Access Power Controllers with Power Supplies Installation Guide for models: Maximal11F - Power Supply 1: 12VDC @ 3.3 amp or 24VDC @ 3.6 amp. - Power Supply 2: 12VDC @ 3.3 amp

More information

Series. Access Power Controllers. Installation Guide

Series. Access Power Controllers. Installation Guide Series Access Power Controllers Installation Guide Models Include: Maxim11 - Power Supply 1: 12VDC @ 3.5 amp or 24VDC @ 2.7 amp. - Power Supply 2: 12VDC @ 3.5 amp or 24VDC @ 2.7 amp. - Sixteen (16) fuse

More information

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906 s Data Sheet Fire Safety & Security Products SXL-EX Fire Alarm Control Panel Conventional Zone Fire Alarm Control Panel ARCHITECT AND ENGINEER SPECIFICATIONS Four (4) zones expandable to eight (8) zones

More information

AL800ULADA. NAC Power Extender. Installation Guide

AL800ULADA. NAC Power Extender. Installation Guide AL800ULADA NAC Power Extender Installation Guide Rev. 122000 AL800ULADA - NAC Power Extender Overview: The Altronix AL800ULADA is an extremely cost effective 8 amp voltage regulated remote power supply/battery

More information

Specification/ Data Sheet

Specification/ Data Sheet Specification/ Data Sheet TRITON RP Agent Release Control Panel FEATURES Agent Release Control Panel designed specifically for suppression release operation with: Four initiating device circuits (IDCs)

More information

PEGAsys. Multi-Loop Intelligent Suppression Control System FEATURES DESCRIPTION. Effective: March 2007 K

PEGAsys. Multi-Loop Intelligent Suppression Control System FEATURES DESCRIPTION. Effective: March 2007 K PEGAsys Multi-Loop Intelligent Suppression Control System A UTC Fire & Security Company Effective: March 2007 K-76-028 FEATURES UL Listed CSFM Approved MEA Approved Peer-to-Peer Networking (to 32 nodes)

More information

AL600ULADA. NAC Power Extender. Installation Guide

AL600ULADA. NAC Power Extender. Installation Guide AL600ULADA NAC Power Extender Installation Guide Rev. 122000 AL600ULADA - NAC Power Extender Overview: The Altronix AL600ULADA is an extremely cost effective 6.5 amp voltage regulated remote power supply/battery

More information

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev Installation Guide for AL800UL-ADA NAC Power Extender Rev. 090500 Overview: The Altronix AL800UL-ADA is an extremely cost effective 8 amps voltage regulated remote power supply /battery charger. The AL800UL-ADA

More information

LifeAlarm Fire Alarm Control Panels

LifeAlarm Fire Alarm Control Panels LifeAlarm Fire Alarm Control Panels UL, ULC Approved* Features Control panel operator convenience features: Wide viewing angle 2 x 20 (40 character) alphanumeric LCD and dedicated LEDs provide convenient

More information

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

Syncro AS. Analogue Addressable Fire Control Panel. User Manual Syncro AS Analogue Addressable Fire Control Panel User Manual Man-1100 Issue 02 Nov. 2008 Index Section Page 1. Introduction...3 2. Safety...3 3. Panel Controls...4 3.1 Access Level 1...4 3.2 Access Level

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep. Power Supply/Chargers Installation Guide Models Include: eflow4na8d - 4A @ 12VDC or 24VDC - Eight (8) PTC Outputs eflow6na8d - 4A @ 12VDC or 24VDC - Eight (8) PTC Outputs eflow102na8d - 10A @ 12VDC - Eight

More information

FMR Installation Instructions. Addressable Fire System Controller

FMR Installation Instructions. Addressable Fire System Controller FMR-7033 EN Installation Instructions Addressable Fire System Controller EN 2 FMR-7033 Installation Instructions Contents Contents Contents...2 1.0 Introduction...3 2.0 Description...3 3.0 Device Mounting...3

More information

DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION Fike s Cheetah Xi 50 (P/N 10-071) is a state-of-the-art true intelligent digital peer-to-peer modular suppression control system.

More information

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R Region Project Page 1 PART 1 - GENERAL 1.1 REFERENCES.1 CAN/ULC-S524-2006, Standard for the Installation of Fire Alarm Systems..2 CAN/ULC-S525-2007, Audible Signal Device for Fire Alarm Systems..3 CAN/ULC-S526-2007,

More information

MODEL B2 INSTALLATION MANUAL

MODEL B2 INSTALLATION MANUAL RELEASE DEVICES GENERAL DESCRIPTION MODEL B2 INSTALLATION MANUAL S/N: The B2 Series Time Delay Release Devices are UL Listed, Canadian Listed, and CSFM Listed for use on rolling doors, single-slide and

More information

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep. Power Supply/Chargers Installation Guide Models Include: eflow4na8-4a @ 12VDC or 24VDC - Eight (8) Fused Outputs eflow6na8-4a @ 12VDC or 24VDC - Eight (8) Fused Outputs eflow102na8-10a @ 12VDC - Eight

More information

DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION Fike s CyberCat 254 (P/N 10-066) is a state-of-the-art true intelligent digital peer-to-peer modular fire alarm control system.

More information

Booster Power Supply Manual

Booster Power Supply Manual Supply Manual DEVELOPED BY COPYRIGHT NOTICE General Signal Building Systems Corporation 6411 Parkland Drive Sarasota, FL 34243 (941) 739-4300 Copyright 1999 General Signal Building Systems Corporation

More information

Laptop / PC Programming Manual

Laptop / PC Programming Manual Laptop / PC Programming Manual Doc. # Fire PC Program rev B 01.07 This Document is property of Evax Systems, Inc. The Evax Fire Solutions Programmer Components 2 1.0 System Setup 4 1.1 Interface Setup

More information

30.45 Electric Release PDRP-2001

30.45 Electric Release PDRP-2001 The PDRP-2001 Fire Alarm Control Panel (FACP) is a six-zone control panel for single and dual hazard deluge and preaction applications. The FACP is compatible with conventional input devices (2-wire or

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd full installation, commissioning and operating manuals can be downloaded from www.haes-systems.co.uk combined addressable / conventional fire alarm control panel User Guide Approved Document No. MFBU-04

More information

Notification Appliance Circuit Module

Notification Appliance Circuit Module Notification Appliance Circuit Module D192G en Installation guide Notification Appliance Circuit Module Notices en 3 1 Notices These instructions cover the installation of the D192G Notification Appliance

More information

PS1240x Series Dual Voltage Access Control Power Supply Systems Operating and Installation Instructions Rev D.01

PS1240x Series Dual Voltage Access Control Power Supply Systems Operating and Installation Instructions Rev D.01 PS1240x Series Dual Voltage Access Control Power Supply Systems Operating and Installation Instructions Warnings and Notices WARNING - To reduce the risk of fire or electric shock, do not expose this product

More information

CONVENTIONAL FIRE ALARM CONTROL UNITS. MR-2300 SERIES Fire Alarm Control Units MEA

CONVENTIONAL FIRE ALARM CONTROL UNITS. MR-2300 SERIES Fire Alarm Control Units MEA CONVENTIONAL FIRE ALARM CONTROL UNITS MR-2300 SERIES Fire Alarm Control Units Description Secutron s MR-2300 Series fire alarm control panels consist of six and twelve zone models which are equipped with

More information

SP-1000X. Panic Device Power Controller Installation Guide. Rev

SP-1000X. Panic Device Power Controller Installation Guide. Rev TM SP-1000X Panic Device Power Controller Installation Guide Rev. 120213 Overview: SP-1000X will operate up to two (2) 24VDC panic hardware devices simultaneously. It is designed to handle the high current

More information

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm Operating & Maintenance Manual Alert-4 Ethernet LCD Master Alarm w w w. a m i c o. c o m Contents User Responsibility 4 Introduction 4 Features 5 Description of the Alarm 5 Shipment Details 5 The Alarm

More information

CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM

CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION Fike s Cheetah Xi (P/N 10-068) is a state-of-the-art true intelligent digital peer-topeer modular suppression control system. It is ideal for

More information

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL RELEASE DEVICES MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL The LiftMaster Fire Control (LM21-AFC) Release Device/Control Panel is UL/CUL listed normally energized fail-safe device incorporating

More information

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual Fire Safety Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual Siemens Building Technologies, Inc. Siemens Building Technologies, Ltd. 8 Fernwood Road 2 Kenview

More information

Conventional Releasing Control Panel

Conventional Releasing Control Panel s Data Sheet Fire Safety Products Conventional Releasing Control Panel Pre-Action Deluge Agent-Releasing Fire System Model TXR-320 Remote configurable Up to two (2) hazard areas Operable with the following:

More information

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL MADE IN THE U.S.A. U.L. LISTED CANADIAN LISTED CSFM: 7300-1418:100 GENERAL DESCRIPTION SERIAL NUMBER The Cookson Company FIREFLY II PLUS Time Delay Release

More information

Halton SAFE / 7.14 user guide and installation instructions

Halton SAFE / 7.14 user guide and installation instructions Halton SAFE / 7.14 user guide and installation instructions VERIFIED SOLUTIONS BY H A LTO N Enabling Wellbeing Table of contents 1 System description 3 2 User Accounts 4 3 Main menu 7 3.1 Main menu - Change

More information

Addressable Fire Alarm Control Panel

Addressable Fire Alarm Control Panel PRODUCT SPECIFICATION XR2400F Addressable FACP Addressable Fire Alarm Control Panel Description The DMP XR2400F Addressable Fire Alarm Control Panel is an expandable Fire Alarm Control with built-in DACT

More information

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel INSTALLATION, OPERATION AND MAINTENANCE MANUAL Version: CN-PM-1000.VER1.1-12/2012 EN54 INFORMATION In accordance with EN 54-2 clause 13.7, the maximum

More information

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs ACM Series Access Power Controllers with Power Supplies Installation Guide Models Include: AL400ULACM AL600ULACM - 12VDC @ 4 amp - 12VDC or 24VDC @ 6 amp. or 24VDC @ 3 amp - Fused Outputs - Fused Outputs

More information

Doc. No Part No Rev. U * T*

Doc. No Part No Rev. U * T* Doc. No. 430545 Part No. 579-357 Rev. U *0579357T* Blank Page- Back of Front Cover Copyrights and Trademarks 2005-2018 Johnson Controls. All rights reserved. Specifications and other information shown

More information

IDENTIFLEX 610 ANALOG / ADDRESSABLE FIRE ALARM CONTROL PANEL

IDENTIFLEX 610 ANALOG / ADDRESSABLE FIRE ALARM CONTROL PANEL IDENTIFLEX 610 ANALOG / ADDRESSABLE FIRE ALARM CONTROL PANEL INSTALLATION & OPERATION MANUAL GAMEWELL P/N 71810 60 PLEASANT STREET ISSUE 3, 10/04/2000 ASHLAND, MA 01721 FIRMWARE VER. 7 THIS PAGE INTENTIONALLY

More information

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum. September 29, 1997 Firecycle III 433 a 1. PRODUCT NAME VIKING Model E-1 Manufactured 1997 Present 2. MANUFACTURED FOR THE VIKING CORPORATION 210 N Industrial Park Road Hastings, Michigan 49058, U.S.A.

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with automatic detection and control. The work described in

More information

The supplier and installer of the system should be approved by the local civil defence authority.

The supplier and installer of the system should be approved by the local civil defence authority. ANALOGUE ADDRESSABLE FIRE ALARM SYSTEM 1. Scope of Work The contractor shall supply, install, test and commission a modern Analogue Addressable Fire Detection and Alarm System of an approved manufacturer

More information

Addressable NAC Output Module D327A

Addressable NAC Output Module D327A Installation Instructions Notice Addressable NAC Output Module D327A These instructions cover the installation of the D327A Addressable NAC Output Module in an analog system controlled by a Bosch D8024,

More information

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information)

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 042010 Agency Listings: UL Listed Control Units for Fire Protective Signaling Systems (UL 864).

More information

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

ZX1e ZX2e ZX5e. Document No Issue 01 user manual ZX1e ZX2e ZX5e Document No. 996-130 Issue 01 user manual MORLEY-IAS ZX2E/ZX5E Fire Alarm Control Panels Table of Contents 1 INTRODUCTION... 4 1.1 NOTICE... 4 1.2 WARNINGS AND CAUTIONS... 4 1.3 NATIONAL

More information

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS GENERAL DESCRIPTION... 2 STANDARD AND OPTIONAL PARTS LIST... 2 PARTS DIAGRAM... 3 TERMINAL DRAWING AND SPECIAL NOTES...

More information

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual CONTENTS Installation Precautions... 1 EN 54 Information... 2 Chapter 1 Product Overview... 3 1.1 Features... 3 1.2 Technical Specifications... 3 1.2.1 Operating Voltage... 3 1.2.2 Batteries... 3 1.2.3

More information

THE "SS90" SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL

THE SS90 SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL S S S S S S S S 90 OLID TATE ECURITIES, INC SOLID STATE FAIL-SAFE UNIT * PATENT PENDING LISTED U 99Y9 RESET L RELEASING DEVICE SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE

More information

DS9400 Series. Release Notes for Firmware V2.07. Fire Alarm Control Panel

DS9400 Series. Release Notes for Firmware V2.07. Fire Alarm Control Panel DS9400 Series EN Release Notes for Firmware V2.07 Fire Alarm Control Panel DS9400 Series Release Notes for Firmware V2.07 Trademarks Trademarks Gentex is a trademark of Gentex Corporation, Fire Protection

More information

AND ARCHITECT SPECIFICATIONS

AND ARCHITECT SPECIFICATIONS PXL Conventional Zone Fire Alarm Control Panel ENGINEER AND ARCHITECT SPECIFICATIONS 12 Zone System Expandable to 32 10 Amp Base Power Supply Multiple Power Supplies Available - Local or Remote 4 Notification

More information

CONVENTIONAL FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels MEA. Features. Description

CONVENTIONAL FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels MEA. Features. Description CONVENTIONAL FIRE ALARM CONTROL PANELS SFC-200 Series Fire Alarm Control Panels Description Summit s SFC-200 Series fire alarm control panels consist of six and twelve zone models which are equipped with

More information

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL USER MANUAL 1 Table of Contents 1 SAFETY INFORMATION...3 1.1 SAFETY PRECAUTIONS DURING NORMAL OPERATION OF PANEL...3 1.3 BATTERY INFORMATION...3

More information

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2 Architectural & Engineering Specifications Control Panel 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality assurance...

More information

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014 January 16, 2014 Release Control Panel 290a 1. Description The Viking VFR400 is a microprocessor based releasing control panel for use on preaction, deluge, Surefire, Firecycle multicycle sprinkler systems,

More information

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC. M Series Multi-Output Access Control Power Supply Chargers Installation Guide Models Include: AL300ULM AL400ULM - 2.5 amp @ 12VDC or 24VDC. - 3 amp @ 12VDC or 4 amp @ 24VDC. AL600ULM AL1012ULM - 6 amp

More information

"SS90" SERIES CONTROLS MODEL C INSTALLATION MANUAL

SS90 SERIES CONTROLS MODEL C INSTALLATION MANUAL S S S SS O L I D S S90 TATE ECURITIES, INC SOLID STATE FAIL-SAFE UNIT * PATENT PENDING LISTED U L 99Y9 RESET RELEASING DEVICE SOLID STATE SECURITIES, INC. "SS90" SERIES CONTROLS MADE IN THE U.S.A. MODEL

More information

EVO192 v3.0 Fire and Burglary What s New

EVO192 v3.0 Fire and Burglary What s New EVO192 v3.0 Fire and Burglary What s New Compatibility: EVO192 v3.0 TM50 v1.31 K641 v2.41 Overview: CP-01 Compliancy Wiring Diagram The following sections/options have been added to the EVO192 panel. They

More information

RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev

RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev RPSMLR2 RPSMLR2BB Panic Device Power Controller Installation Guide LISTED Rev. 102715 Overview: RPSMLR2BB, RPSMLR2 will operate up to two (2) 24VDC panic hardware devices simultaneously. It is designed

More information

MANUAL RESET ALARM RELEASE

MANUAL RESET ALARM RELEASE Fire Door Release MODEL AR-D2 MANUAL RESET ALARM RELEASE INSTRUCTION MANUAL AR-D2 GENERAL INFORMATION 1. Review all installation instructions, procedures, cautions and warnings contained within this manual

More information

Section 4: Operating Instructions

Section 4: Operating Instructions Section 4: Operating Instructions 4.1 Panel Control Buttons 4.1.1 Acknowledge/Step The first press of the Acknowledge/Step key silences the piezo sounder, changes flashing LEDs to steady and also changes

More information

QA16 Addressable System

QA16 Addressable System QA16 Addressable System Operating Manual HORING LIH INDUSTRIAL CO., LTD. www.horinglih.com QA16 System Characteristics Each loop can connect with 250 devices. Easy system programming through PC to panel.

More information

FEC400 Series. Installation Manual

FEC400 Series. Installation Manual FEC400 Series Conventional microprocessor controlled fire detection and alarm panels with extinguishing control Installation Manual Version 2.3 / August 2004 Aritech is a GE Interlogix brand. http://www.geindustrial.com/ge-interlogix/emea

More information

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC. M Series Multi-Output Access Control Power Supply Charger Installation Guide Models Include: AL300ULM AL400ULM - 2.5 amp @ 12VDC or 24VDC. - 4 amp @ 12VDC or 3 amp @ 24VDC. AL600ULM AL1012ULM - 6 amp @

More information

To operate the 5207 you can use either the built-in touchpad or the Model 5230 Remote Annunciator.

To operate the 5207 you can use either the built-in touchpad or the Model 5230 Remote Annunciator. Section 5 Operation To operate the 5207 you can use either the built-in touchpad or the Model 5230 Remote Annunciator. Figure 5-1 Built-in Touchpad (Seven-Segment Display) Figure 5-2 Model 5230 Remote

More information

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3 INTELLIGENT FIRE TECHNOLOGY Twinflex and Multipoint V3 User Guide (TO BE RETAINED BY USER) 26-0340 Issue 3 Rafiki Protection Limited Rafiki policy is one of continual improvement and the right to change

More information

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev Installation Guide for AL600ULM Multi-Output Access Control Power Supply Charger Rev. 091800 1 AL600ULM - Multi-Output Access Control Power Supply/Charger Overview: The AL600ULM multi-output access control

More information

Concerns: Affects: Dated: June 12, SECTION 1: GENERAL Scope Work Included... 3

Concerns: Affects: Dated: June 12, SECTION 1: GENERAL Scope Work Included... 3 Technical Service Note Detection Systems, Inc. Fairport, New York 14450-9199 Technical Service (800) 374-7454 Sales: (800) 289-0096 and (585) 223-4060 Fax: (585) 223-9180 Concerns: Affects: Dated: June

More information

Operator s Manual Part: InfoAlarm Product: 4100U, 4100ES Rev. B

Operator s Manual Part: InfoAlarm Product: 4100U, 4100ES Rev. B Operator s Manual Part: InfoAlarm Product: 4100U, 4100ES 579-685 Rev. B ii iii Cautions and Warnings Cautions and Warnings READ AND SAVE THESE INSTRUCTIONS- Follow the instructions in this installation

More information

Model 17A00 Expansion Enclosure

Model 17A00 Expansion Enclosure HOME AUTOMATION, INC. Model 17A00 Expansion Enclosure Installation Manual Document Number 17I00-1 Rev A March, 2002 Home Automation, Inc. Model 17A00 Expansion Enclosure Installation Manual Document Number

More information

MANUAL RESET ALARM RELEASE BOX

MANUAL RESET ALARM RELEASE BOX MANUAL RESET ALARM RELEASE BOX (For 100~240VAC or 24VAC or 24VDC) INSTRUCTION MANUAL WARNING 1. CAUTION: Review all installation instructions, procedures, cautions and warnings contained within this manual

More information

Fire Alarm System Fundamentals

Fire Alarm System Fundamentals Fire Alarm System Fundamentals Mircom is the largest and oldest privately owned fire alarm and life safety manufacturer in North America and 5th largest overall with 50 years of industry experience. Mircom

More information

21-light Remote Annunciator. Owner s Manual

21-light Remote Annunciator. Owner s Manual 21-light Remote Annunciator Owner s Manual Annunciator Description... Inside Font Cover Detailed Specifications... 1 Environmental Specifications... 1 Power Supply Requirements... 1 Communication With

More information

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels Installation and user manual for the FX range of fire panels 1, 2, 4 and 8 zone panels Contents Panel installation 3 Panel connections 3 Wiring connection drawings 4 Panel facilities 6 Installation check

More information

INSTALLATION & OPERATION GUIDE

INSTALLATION & OPERATION GUIDE M R - 2 3 0 6 - L D LED Fire Alarm Control Panel INSTALLATION & OPERATION GUIDE Document #: LT-950SEC Rev. 2 February 2007 WARNING: This manual contains information on limitations regarding product use

More information

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE D (OPERATION) INITIATE A DYNAMIC BATTERY TEST The system tests the back-up battery once every 24 hours. The owner can initiate a dynamic battery test at any time with the following codes while the system

More information

Fire Control/Communicator

Fire Control/Communicator Operation and Installation Manual Fire Control/Communicator 1 2 3 4 5 12V AC,20V A, 60Hz or +24V DC 12V AC, 20V A, 60Hz or -24V DC EARTH GND BATTERY - BATTERY + 6 INITIATING A1-7 INITIATING A2-8 INITIATING

More information

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION 1. GENERAL SPECIFICATION 1.1 The contractor shall provide an Intelligent AlarmLine Linear Heat Detection System to perform the following functionality: A. Fire Alarm, Supervisory and Trouble-Event Initiation

More information

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description MODUL-R FIRE ALARM CONTROL PANELS MR-2900/MR-2920 Addressable Fire Alarm Control Panels Description MR-2900 Fire Alarm Control Panel The MR-2900 fire alarm system control unit is the heart of a sophisticated

More information

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV LC1 & 2 Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV ZIRCONLC1 One Zone Conventional Fire Panel ZIRCONLC2 Two Zone Conventional Fire Panel Compliant with EN54-2:1998 & EN54-4:1998

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE Deluge Devices 270a 1. PRODUCT NAME VIKING PAR-3 Available since 1991 2. MANUFACTURED FOR: THE VIKING CORPORATION 210 N. Industrial Park Road Hastings, Michigan 49058 U.S.A. Telephone: (269) 945-9501 (877)

More information

user manual Document No , Revision 03 November 2015

user manual Document No , Revision 03 November 2015 user manual Document No. 996-202-600-3, Revision 03 November 2015 Contents 1 Introduction...1 1.1 Notice...1 1.2 Models...1 2 User Control Levels...2 2.1 Level Definition...2 2.2 User Passwords...2 3 Controls

More information

Commercial and Light Industrial Fire Alarm Control Panel

Commercial and Light Industrial Fire Alarm Control Panel FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel Features Easily expandable. All new plug-in board design Two supervised audible circuits Lamp and system trouble circuit test Ground

More information

Print Specification. Publication. Instructions. Specific requirements. General requirements

Print Specification. Publication. Instructions. Specific requirements. General requirements Print Specification Publication GSA-CC1 Single Input Signal Module Installation Sheet P/N P-047550-1802-EN REV 04 ISS 23JUN15 Instructions This page is the print specification for the publication. It is

More information

Product Data Sheet. Remote Terminals. Features:

Product Data Sheet. Remote Terminals. Features: Remote Terminals Product Data Sheet Features: Based around two core products, the Mx- 4010 Remote Display Terminal (RDT) and the fully functional Mx-4020 Remote Control Terminal (RCT). Both remote terminals

More information

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep. 140 58th St. Brooklyn, NY Power Supply/Chargers Installation Guide Models Include: eflow4n/eflow4nx - 4 amp @ 12VDC or 24VDC eflow4n8/eflow4nx8 eflow4n8d/eflow4nx8d - 4 amp @ 12VDC or 24VDC - 4 amp @ 12VDC

More information

POWERPATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262)

POWERPATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262) PATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262) NAC ETENDER SUPPLIES Installation Instructions 273 Branchport Avenue, Long Branch, NJ 07740-6899 Ph: (800) 631-2148 Fax: (732) 222-8707 Web

More information

AFP-300/400 OPERATORS MANUAL INTELLIGENT FIRE DETECTION AND ALARM SYSTEM SOFTWARE VERSION 2.2 REVISION AUS 3

AFP-300/400 OPERATORS MANUAL INTELLIGENT FIRE DETECTION AND ALARM SYSTEM SOFTWARE VERSION 2.2 REVISION AUS 3 OPERATORS MANUAL AFP-300/400 INTELLIGENT FIRE DETECTION AND ALARM SYSTEM SOFTWARE VERSION 2.2 REVISION AUS 3 NSW (Head Office) 7 Columbia Court Norwest Business Park Baulkham Hills NSW 2153 Ph: (02) 9899-4155

More information

Control/Communicator 5110XM. Installation Instructions Installation Instructions Installation Instructions N8026 4/96

Control/Communicator 5110XM. Installation Instructions Installation Instructions Installation Instructions N8026 4/96 Control/Communicator 5110XM Installation Instructions Installation Instructions Installation Instructions N8026 4/96 TABLE OF CONTENTS Section 1: GENERAL DESCRIPTION... 6 Basic Hardwired...6 Remote Keypads...6

More information

Across-the-Line SERIES MP300 Combined Manual and Automatic

Across-the-Line SERIES MP300 Combined Manual and Automatic Across-the-Line SERIES MP300 Combined Manual and Automatic Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s Standard for Centrifugal Fire Pumps

More information

Dryer Controller M720

Dryer Controller M720 User Manual Dryer Controller M720 Hardware version 2.00 Software version 2.00 Manual M720 Dryer controller Page 1 of 60 Document history Preliminary version: - Created in April, 2009 Hardware Version 2.00,

More information

TrueAlarm Fire Alarm Systems

TrueAlarm Fire Alarm Systems OPERATOR OPERATOR OR TROUBLE CONDITION: TO : FIRE PRIORITY 2SYSTEM SYSTEM SIGNALS POWER INDICATOR. SUPERVISORYTROUBLE SILENCED ON D. TO SILENCE SIGNALS: - PRESS " SILENCE". SUPV TBL SYSTEM ACK ACK ACK

More information

Soft Start Series MP700 Solid State, Reduced Voltage

Soft Start Series MP700 Solid State, Reduced Voltage Metron Fire Pump Controls and Accessories Soft Start Series MP700 Solid State, Reduced Voltage Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s

More information