Q&A Session from Alarm Management Workflow Webinar (Apr.24/2013)

Size: px
Start display at page:

Download "Q&A Session from Alarm Management Workflow Webinar (Apr.24/2013)"

Transcription

1 Q&A Session from Alarm Management Workflow Webinar (Apr.24/2013) Question Answer from Kevin Brown Can you define HAZOP and LOPA? HAZOP stands for Hazard and Operability Study. LOPA stands for Layers of Protection. The HAZOP is used to identify major process hazard or operational issues due to the process design. The LOPA is to review the safety protection layers or safeguards to mitigate against hazards in the process. What does APD stand for? APD stands for Alarm Philosophy Document. Do you do the alarm cleanup before introducing a workflow process? This is really dependant on the support for alarm management in your facility. If support is low then I suggest you start with alarm cleanup documenting all changes, costs associated with these changes and the improvement. I would also document feedback from operators and if possible demonstrating how this improvement potentially would have mitigated an alarm flood from the last 1 or 2 incidents. If there is support at your facility then introducing workflow process right away will have an immediate impact. The maintenance and operational meeting is to discuss 3 5 bad actors per week and assign responsibility to fix. The next week you can report on the improvement as listed above which reinforces that the process is working and having a significant improvement. Do you recommend tracking if employees are following their assigned workflow process? The purpose of a workflow is to minimize the effort of maintaining the alarm management system and maximize the benefit. Initially, employees may not see the value and require tracking to enforce the importance of the workflow process. The best approach is to educate the employees on the benefit of the workflow process. Is there a different process to shelve an alarm or suppress it? This really depends on your computer control system. The system will use a form of suppression to shelve the alarm. The difference between a shelved and suppressed alarm is that the shelved alarm is time

2 based for when it is reactivated while a suppressed alarm will need operator intervention to un-suppress the alarm. There could be a different process for shelving versus suppressing but you could also use the same process just indicate that the alarm is being shelved or suppressed. When do we use suppressed alarms? There are numerous reasons to suppress an alarm: State or mode base change Nuisance alarm Equipment outage Equipment out of service Production change Production trials Process changes The reason you suppress an alarm is to remove a nonactionable alarm from the alarm graphic. These alarms can create complacency or hide important alarms due to the noise they create. If we expect an operator to take an action for every alarm as defined in the APD then we need to remove alarms that due to the operating conditions do not require an action. The easiest way to do this is by suppressing it. Make sure that the alarm is un-suppressed when conditions are back to normal. I have a shutdown unit. How do I shelve bad value alarms at shutdown and normalize them when my unit starts? This is called state based or modal alarm suppression. My preference for these applications is to automate the suppression based on the operation such as: When pump 101 stops and flow 112 is less than 50 suppress the following bad quality alarms. Unsuppress alarm when pump 101 starts and flow 112 is greater than 60 or valve 100 is opened greater than 10% Normally it is easier to identify when to suppress alarms then it is when to un-suppress alarms because the unit is down. Be careful how you choose your state to un-suppress the alarm because if it is done too early the operator will get all the nuisance alarms while he is starting up, creating a flood condition, or if it is done too late then the operator may not get an important alarm in time to react to it. How do you define a safety-related alarm? A safety-related alarm is an alarm that could lead to an employee being injured if the issue is not resolved quickly. Examples of these are: gas leaks (H2S), liquid overflow (toxic), equipment damage, etc.

3 How do you identify nuisance alarms by automatic reports? Nuisance alarms are defined as alarms that continuously activate when there is no actionable response. The reports that I use to identify nuisance alarms are: Most Frequent Alarms Chattering Alarms Symptomatic Alarms You said that a stale alarm is not required because it has been standing for 24 hours, yet our rationalization determined we needed it. How do I handle that situation? The reason I said that a stale alarm (one standing greater than 24 hours) is not required because the issue the alarm identified for the operator to resolve did not occur after the time identified in the rationalization. The way I approach these alarms is to review the rationalization documentation verifying that it is still correct then review with operations why this issue was not resolved yet there was no incident. After this review I will have determined the solution which may include removing the alarm, changing the alarm setpoint, creating a new alarm or incorporating a state based alarm. You indicated there is a difference between Stale and Standing alarms how do we incorporate that difference in my plant? Was the electronic shift log book part of 's Alarm software or stand alone? The first step is to define stale and standing alarms in your APD. Then use your workflow process to deal with these alarms. Example: Stale alarms are reviewed daily by the shift supervisor and recommendations are defined to resolve them. Standing alarms are reviewed by the operator and shift supervisor at shift change, and reviewed by the operator every hour. The electronic shift log book is standalone but can also be offered as a suite (OM Pro) with the alarm management software. We have stale alarms mainly due to process conditions, for example, low level alarms in knock out drums which are always in alarm state. Operations need the alarm, so how do we handle these types of alarms? If these alarms are only required during an operational state i.e. shutdown, startup, they can be suppressed when not required. If these alarms are required to indicate to the operator the level is low in the knock out drum then I would modify the graphic instead to show this and remove the alarm. The key to solving these types of alarms (required but always in alarm state) is to understand the purpose and consider the options to resolve other than an alarm i.e. graphic changes, user alerts. If the alarm is always in an activate state then it is of no value because the operator is not responding to it so there is no layer of protection.

4 Can you elaborate on how to differentiate between standing and stale alarms with live examples? Which alarm out of this has the highest priority to be taken care of? As I indicated in the webinar any alarm that rings in is considered standing whereas a stale alarm is an alarm that is active for a period of time (i.e. greater than 24 hours). The point I was trying to make during the webinar is that a standing alarm becomes reportable when it exceeds a reasonable amount of time and in my opinion 24 hours it too long. The reason we want to report and review standing alarms is because they have not returned to normal and there is still the potential that there could be an incident. If an alarm can be active for greater than 24 hours without an incident then an alarm was not required, it is labeled stale and should be reviewed and possibly removed. Example: A tank has an overflow onto the flow at the 97% of the height of the tank. The alarm is set to annunciate when the level reaches 85%. The priority on this alarm is low which means there is an expectation for the alarm to return to normal within 30 minutes based on the risk metrics. When the alarm annunciates the operator chooses to reduce the rate of the flow into the tank, however this action only results in slowing the rate of increase in the tank. Eventually the tank overflows onto the floor and there is an incident. The standing alarm report would have indicated that this alarm had exceeded the 30 minutes and needed further investigation. Same example except the tank has a second overflow that drains into the sewer below the other overflow that drains onto the flow. When the alarm annunciates the operator chooses to reduce the rate of the flow into the tank, however this action only results in slowing the rate of increase in the tank. Eventually the tank overflows into the sewer and there is no reportable incident. The standing alarm report would have indicated that this alarm had exceeded the 30 minutes and needed further investigation. Based on normal operation leaving the tank to over flow to the sewer is an acceptable response. If the overflow to sewer can handle the maximum feed rate into the tank and overflowing to the sewer is acceptable then this alarm would be on the stale alarm report and require the alarm to be removed. The standing alarm has the highest priority because there is a potential for an incident. There is no opportunity for an incident on the stale alarm and that is why it has a lower priority.

5 How do you calculate alarm KPI and how long will it be optimum after the commissioning phase of project? The alarm KPIs need to be defined in your APD and based on ISA 18.2, EEMUA 191, API 1167 or a corporate standard. The calculation is defined within these documentations. The purpose of KPIs is to indicate where the problem areas are and if we are having a positive impact on improving them. I would be monitoring them throughout commissioning and into operation. During the commissioning phase the alarms will be tested and these need to be identified and removed from your KPI calculations. What determines the frequency of alarm rationalization, assuming no new equipment is added to the process? Besides new equipment, you need to consider having a rationalization when the control strategy or process is changed. I would use the alarm KPIs to evaluate the operations to determine if a rationalization is required. For example, if alarm count per operator per hour has been increasing over the last 30 to 60 days and this is not due to nuisance alarms then consider rationalizing that process. Another option is to pick one process unit per year and rationalize it to confirm the alarms and to keep the rationalization team trained. How can we rationalize alarms for new equipment? Is there any guideline? The challenge with rationalizing new equipment is that the operators have no operating experience on this process. That being said it is important to rationalize this equipment before it goes into service because the operators will not be familiar with it and will need these alarms to indicate issues. The process for rationalizing new equipment is the same except you will require other personnel to participate: Vendor of supplied equipment 2 operators instead of one, with experience on similar equipment and process Process design engineer We have experience rationalizing new equipment and Greenfield and are happy to discuss our process with you. Can alarm rationalization be carried out if the facility does not have an alarm philosophy document? Yes a rationalization can be held without an APD, however I would not recommend it. If you do not have an APD then you will need to define the following: Alarm definition Risk matrices Alarm types Alarm design Graphic design, as it relates to alarm

6 If you do not have these parameters defined prior to the rationalization then the rationalization will take longer and require re-doing parts of it as you define these parameters. These parameters will need to be incorporated into your APD once it is written. We are starting the rationalization process in our refinery. Is there any standard guideline for Deadband, Filtering and Time Delay for typical loops? The ISA 18.2 or EEMUA 191 list starting values for deadband for measurements (i.e. flow, pressure, etc). My preference is not to apply a global deadband, filtering or time delay unless it has been identified that the measurements for the process are typically noisy. I identify the alarms that require these techniques through the chattering alarm report, or if the alarm setpoint is close to the operating setpoint. The measurement and results desired will determine whether to use a deadband, filter or time delay. The University of Alberta completed a study on applying a deadband to a nuisance alarm and determined that deadband will only resolve about 20% of the problems. Due to the process and measurement you may require more than one of these techniques to resolve the issue. If there are currently no deadbands or time-off delays implemented, would you do that as a standard with all alarms in parallel with the bad actor program? No I would not apply deadbands, filtering or time delays as a standard. I would only use them for the bad actors. Trying to resolve Bad PV alarms we are thinking to increase the extended range of analogue inputs. Is there any standard concerning this parameter as a percentage of the instrument range? I am not sure what you mean by extended range. If you are suggesting increasing the engineering range on the DCS beyond the design on the instrument calibration then this will not solve your problem and will instead create inaccuracies in your measurement. BAD PV alarms in my opinion are maintenance alarms and need to be dealt with by the instrument department. When a BAD PV alarm is created due to shutting down, consider suppressing these alarms during this state. If the operation operates outside of the calibration of the instrument then consider recalibrating it based on the range (instrument-based) or purchasing an instrument for the range of the operation. If BAD PV alarms are being created due to the 4 20 ma signal dropping (noisy signal, flaw in instrument), consider adding a time delay on for the alarm.

7 How do you incorporate the Time delays/dead bands for a Bad PV Alarm in s Experion and TPS? Without using logics? In Experion PKS R410, we introduced the ability to configure on-delay timers and off-delay timers (along with a deadband value for chattering alarms) for controller-based alarms. See the example screenshot of a DACA block (bottom of page 9). Can you explain the relationship between Master Boundary Data (MBD) and Alarm Configuration Management (ACM)? The Alarm Configuration Management (ACM) is the master alarm database. The software application connects to the computer control system and stores the alarm settings along with the rationalization data. If you are storing the Master Boundary Data (MBD) in the limit repository the two products are integrated. You showed a Operations Logbook screenshot, how do we get the alarm data in OL? Operations logbook can gather data from different sources including alarm database for shift summary. How can we target alarms on oplimit crossing? I am not sure what you are asking. Is this output limit or operation limit? Are you looking to report on this issue or what you need to do to resolve this issue? UOP CCR alarm appears for every cycle of lock hopper filling and emptying. As per ISA18.2 this cannot be categorized as an alarm but it is difficult to convince operations as it is UOP. Firstly define alarm in the APD. Alarm: is a notification to the operator indicating a condition change requiring operator intervention. If there is no operator action then based on the definition there is no alarm. When we have an alarm system that contains alarms that do not require an operator action then we are dependent on the operator deciding if this alarm requires an action. These alarms also build complacency and distract the operator from focusing on the process. If this is a normal condition and requires a notification to the operator, consider changing this to a user alert. If this condition is a normal condition but does not require an operator action unless there is no fill or empty alarm, consider changing the alarm to indicate that the lock fill or empty did not occur as expected. Do plants with dedicated control room personnel have more success with alarm management? Success with alarm management is not based on dedicated control room personnel but a dedicated operating staff that are continuously reviewing and improving the alarm system. I have seen success with and without dedicated control room personnel.

8 I have a facility with thousands of alarms appearing every day. I did the AOA (Alarm Objective Analysis). On the other hand, I have PHA (Process Hazard Analysis) and SOA (System Outage Analysis) telling which alarm should be set. Are the PHA and SOA enough to consider as the alarm reference, or should I continue the alarm rationalization using AOA? If you are getting thousands of alarms per operator then yes you need to continue with the AOA. PHA and SOA are excellent for identifying risks but they do not take into account the alarms as part of a process. The AOA will identify duplicate and redundant alarms which can be removed, reducing your alarm count. The process will result in proper alarm setpoints and priorities. During the AOA you identify an alarm is not required due to no operator action, redundant or duplicate, but if it was identified in the PHA or SOA then before the alarm is removed this result will need to be reviewed again by the PHA and SOA team. This can create extra work and that s why I suggest including AOA functionality in other processes i.e. HAZOP, LOPA, PHA etc. In our last PHA (Process Hazard Analysis) revalidation study, we found a bunch of controls had been compromised. In a plant where new resources are a problem, the team decided on putting some alarm-based controls that were prioritized. How often should we redo the alarm prioritization study? The purpose of having procedures is to confirm everyone is following the requirements. The new resources need to be educated on the APD and the rationalization process prior to making any changes to the alarms. The prioritization is determined during rationalization and consider re-doing a rationalization based on: Alarm rate is increasing New equipment New control strategy Incidents are due to alarm issues If your process is not changing, the bad actors are being dealt with properly and the alarm rates are within standards then you may never require a rationalization. Operations think the alarm problem at our facility is a maintenance issue which the control team must fix. You had several slides that involve their participation. Could you suggest how I get operations more involved? This is a common issue that I have seen at numerous facilities. My experience is that when operations own the alarm issue then the facility is successful with their alarm management program. To solve this problem we first must understand the reason why they believe the alarm problem is a maintenance issue. Typically the computer control system repair is done by maintenance and so this is seen as a maintenance issue and not an operations issue. The best way to approach this is through education with training sessions and workshops. An analogy I like to use is that your car has developed a noise so you take it to your mechanic. After a quick review, he figures it will only cost about $100 to fix and will be ready when you are done work. At the end of

9 the day you show up at the garage to find your motor sitting on the work bench in pieces and the mechanic tells you that your car won t be ready until next week and the bill will be $4500. Would you accept this? Then why would you give maintenance the responsibility to fix the alarm problem when the purpose of an alarm is to indicate to the operator that the process or equipment operation has changed and requires an action to correct. We have held workshops and training for the sole purpose of educating different groups within a facility and would be happy to explore a solution with you. Screenshot of DACA block:

excellence in Dependable Automation ALARM MANAGEMENT

excellence in Dependable Automation ALARM MANAGEMENT excellence in Dependable Automation ALARM MANAGEMENT www.exida.com Improve the performance of your operators through effective Alarm Management. Typical alarm management issues that hamper operator performance

More information

2012 Honeywell Pacific Users Group. Sus tain.ability.

2012 Honeywell Pacific Users Group. Sus tain.ability. 2012 Honeywell Pacific Users Group Sus tain.ability. 1 2012 Honeywell Pacific Users Group Sus tain.ability. Nico Oosthuizen Effective Alarm and Operations Management 2 Topics Overview What is the problem?

More information

2012 Honeywell Users Group EMEA Tyron Vardy A Guide to Effective Alarm Management

2012 Honeywell Users Group EMEA Tyron Vardy A Guide to Effective Alarm Management Sustain.Ability. 2012 Honeywell Users Group EMEA Tyron Vardy A Guide to Effective Alarm Management Introductions Tyron Vardy Alarm Management Specialist for over 15 years Matrikon Engineering Manager Developed

More information

Enhance Alarm Management

Enhance Alarm Management White Paper Enhance Alarm Management Executive Summary A properly design alarm management system will minimize production losses, safety incidents and environmental excursions. To do this effectively,

More information

Kevin Brown and Chris Stearns

Kevin Brown and Chris Stearns 2013 Honeywell Users Group Americas Kevin Brown and Chris Stearns Operations and Alarm Management Reap the benefits of a healthy alarm system 1 Agenda Alarm Management Effective best practices How can

More information

Sustain.Ability. Alarm Management: Be Pro-active, not Re-active Honeywell Users Group Europe, Middle East and Africa. Tyron Vardy, Honeywell

Sustain.Ability. Alarm Management: Be Pro-active, not Re-active Honeywell Users Group Europe, Middle East and Africa. Tyron Vardy, Honeywell Sustain.Ability. 2012 Honeywell Users Group EMEA 2014 Honeywell Users Group Europe, Middle East and Africa Alarm Management: Be Pro-active, not Re-active Tyron Vardy, Honeywell Agenda Introduction Defining

More information

DON T JUST REPORT ON ALARMS, TAKE

DON T JUST REPORT ON ALARMS, TAKE Tyron Vardy DON T JUST REPORT ON ALARMS, TAKE Product Director Beyond Alarm Reporting with DynAMo Alarm Suite R200 26 September 2017 ACTION! Alarm Management Best Practices 1 Alarm Management: A well documented

More information

Product introduction Layers of Protection Layer 3: Safety System Instrumented & Mechanical. Layer 2: Alarms Manual action needed

Product introduction Layers of Protection Layer 3: Safety System Instrumented & Mechanical. Layer 2: Alarms Manual action needed Thomas Skovholt, Global Product Manager HFC 2016 Slide 1 Product introduction Layers of Protection Incident or Production upset Barriers Higher Cost & Risk Steady state production Lower Cost & Risk Layer

More information

Economic and Effective Alarm Management

Economic and Effective Alarm Management Economic and Effective Alarm Management 2 Economic and Effective Alarm Management Introduction Like many industrial process plants, your manufacturing facility s distributed control system (DCS) may have

More information

Exaquantum/ARA Alarm Reporting and Analysis

Exaquantum/ARA Alarm Reporting and Analysis Exaquantum/ARA Alarm Reporting and Analysis - 1 - The Exaquantum Family Exaquantum/ARA is Yokogawa s Alarm Reporting and Analysis solution. Standards based, Exaquantum/ARA assists supervisors and managers

More information

Where Technology Shapes Solutions. Alarm management : Wasn t that problem already solved years ago?

Where Technology Shapes Solutions. Alarm management : Wasn t that problem already solved years ago? Honeywell Users Group 2011 Where Technology Shapes Solutions. Luc De Wilde, Total Petrochemicals Dal Vernon Reising, Human Centered Solutions Alarm management : Wasn t that problem already solved years

More information

Alarm Management Standards Are You Taking Them Seriously?

Alarm Management Standards Are You Taking Them Seriously? Alarm Management Standards Are You Taking Them Seriously? Executive Summary EEMUA Publication 191 ALARM SYSTEMS - A Guide to Design, Management, and Procurement was first released in 1999 and is well acknowledged

More information

DynAMo Alarm & Operations Management

DynAMo Alarm & Operations Management Connected Plant DynAMo Alarm & Operations Management Solution Note Delivering operations integrity through better plant safety, availability and compliance across your entire enterprise Honeywell s DynAMo

More information

The Top 10 Worst Performing Alarm Systems in Industry

The Top 10 Worst Performing Alarm Systems in Industry The Top 1 Worst Performing Alarm Systems in Industry Bill Hollifield Principal Alarm Management Consultant Mary Kay O Connor O Process Safety Symposium October 26 The Source of The Data PAS: Benchmarking

More information

Next Generation Alarm Management With DynAMo Alarm and Operations Management

Next Generation Alarm Management With DynAMo Alarm and Operations Management 2012 Honeywell Users Group EMEA Sustain.Ability. Next Generation Alarm Management With DynAMo Alarm and Operations Management Tyron Vardy Introductions Tyron Vardy Product Director for Advanced Solutions

More information

Effective Alarm Management for Dynamic and Vessel Control Systems

Effective Alarm Management for Dynamic and Vessel Control Systems DYNAMIC POSITIONING CONFERENCE October 12-13, 2010 OPERATIONS SESSION Effective Alarm Management for Dynamic and Vessel Control Systems By Steve Savoy Ensco Offshore Company 1. Introduction Marine control

More information

DeltaV Analyze. Introduction. Benefits. Continuous automated DeltaV System alarm system performance monitoring

DeltaV Analyze. Introduction. Benefits. Continuous automated DeltaV System alarm system performance monitoring DeltaV Distributed Control System Product Data Sheet December 2016 DeltaV Analyze Continuous automated DeltaV System alarm system performance monitoring Trends of alarms, events, and user actions Identification

More information

Alarm Management. Version Prepared by: Michael Davis- Hannibal. Softcon Software Control Services (Pty) Ltd.

Alarm Management. Version Prepared by: Michael Davis- Hannibal. Softcon Software Control Services (Pty) Ltd. Alarm Management. Version 0. 1 Prepared by: Michael Davis- Hannibal Softcon Software Control Services (Pty) Ltd. 7 March 2017 Revision History Name Date Reason For Changes Version MDH 22-Oct-10 Initial

More information

Martin Huber 26September 2017 F&G SOLUTIONS FOR THE PROCESS INDUSTRY

Martin Huber 26September 2017 F&G SOLUTIONS FOR THE PROCESS INDUSTRY Martin Huber 26September 2017 F&G SOLUTIONS FOR THE PROCESS INDUSTRY Agenda 1 Challenges in the Process Industry International codes and standards F&G in an industrial Facility Honeywell s industrial F&G

More information

SCADA ALARM MANAGEMENT. Tim Okely. GWMWater

SCADA ALARM MANAGEMENT. Tim Okely. GWMWater SCADA ALARM MANAGEMENT Paper Presented by: Tim Okely Author: Tim Okely, Instrument Technician, GWMWater 78 th Annual WIOA Victorian Water Industry Operations Conference and Exhibition Bendigo Exhibition

More information

Alarm Management Services

Alarm Management Services Alarm Management Services Know and improve alarm performance Integrate compeletely with almost any control system Increase operator efficiency Comply with regulatory and industry standards The Value of

More information

Too Many Alarms: Where Do I Begin?

Too Many Alarms: Where Do I Begin? Too Many Alarms: Where Do I Begin? Standards Certification Education & Training Publishing Conferences & Exhibits Speakers: Kevin Patel, PE, MBA Signature Automation, LLC 2013 ISA Water / Wastewater and

More information

Alarm Management Optimization (AMO) at Saudi Aramco

Alarm Management Optimization (AMO) at Saudi Aramco Alarm Management Optimization (AMO) at Saudi Aramco Presented at GPA GCC Chapter 5 th Specialized Technical Seminar Process Safety Management (PSM) in the Gas Processing Industry Wednesday 3 rd November

More information

Alarm System Performance Metrics

Alarm System Performance Metrics Alarm System Performance Metrics FPID Symposium, Cork March 2016 Standards Certification Education & Training Publishing Conferences & Exhibits Presenter Kim Van Camp is the Emerson Process Management

More information

ABB Ability System 800xA Alarm Management

ABB Ability System 800xA Alarm Management ABB Ability System 800xA Alarm Management Effective detection, notification, analysis and corrective action of abnormal situations. When an alarm sounds in a process controlled by ABB s System 800xA, operators

More information

Alarm Management Plan

Alarm Management Plan John E. Bogdan, Susan F. Booth, & David P. Garcia Abstract Why prepare an Alarm Management Plan just to meet PHMSA requirements (49 CFR Parts 192.631 and 195.446) when, for essentially the same effort,

More information

Improvements in Transmission Control Center Alarm Management Practices

Improvements in Transmission Control Center Alarm Management Practices Improvements in Transmission Control Center Alarm Management Practices Navin Bhatt, Mahendra Patel, Bill Hollifield, Andrew Hunter 2017 CIGRE Grid of the Future Symposium Cleveland, Ohio, U.S.A. 22-25

More information

Alarm Services. Introduction. Benefits. Service Data Sheet October Know and improve your alarm performance

Alarm Services. Introduction. Benefits. Service Data Sheet October Know and improve your alarm performance Service Data Sheet Alarm Services Know and improve your alarm performance Integrate completely with your DCS Increase your operator efficiency Comply to regulatory and industry standards The Alarm Services

More information

Alarm Rationalization

Alarm Rationalization DeltaV Distributed Control System White Paper October 2016 Alarm Rationalization This document examines the ISA-18.2 alarm rationalization process for DeltaV Process Automation Systems, utilizing alarm

More information

Unifying Alarms and Operating Envelopes for the Achievement of KPI s and Business Objectives

Unifying Alarms and Operating Envelopes for the Achievement of KPI s and Business Objectives Geometric Process Control Unifying Alarms and Operating Envelopes for the Achievement of KPI s and Business Objectives Robin Brooks, Alan Mahoney, John Wilson, Na Zhao, Process Plant Computing Ltd (PPCL),

More information

excellence in Dependable Automation The Alarm Shelving ebook

excellence in Dependable Automation The Alarm Shelving ebook excellence in Dependable Automation The Alarm Shelving ebook 1 Alarm Shelving. 2 Table of Contents 01: Introduction 4 02: Defining Nuisance Alarms 5 03: Why Nuisance Alarms Undermine Operator Situation

More information

Diagnostics with fieldbus

Diagnostics with fieldbus 2002 Emerson Process Management. All rights reserved. View this and other courses online at www.plantwebuniversity.com. Fieldbus 105 Diagnostics with fieldbus Overview More than device maintenance Equipment

More information

Presented at the ISPE ISA Automation Forum VP, Engineering Services

Presented at the ISPE ISA Automation Forum VP, Engineering Services Presented at the ISPE ISA Automation Forum - 2010 Alarm Response Procedures A Marriage of PCS and MES Author Name Bruce Greenwald Title VP, Engineering Services Company RE Mason Company Address 1726 Graham

More information

Meeting PHMSA Alarm Management Requirements: How TiPS Can Help

Meeting PHMSA Alarm Management Requirements: How TiPS Can Help Meeting PHMSA Alarm Management Requirements: How TiPS Can Help TiPS Incorporated provides a comprehensive program including services and software tools to help you design and implement a successful alarm

More information

Benchmarking Industry Practices for the Use of Alarms as Safeguards and Layers of Protection

Benchmarking Industry Practices for the Use of Alarms as Safeguards and Layers of Protection Benchmarking Industry Practices for the Use of Alarms as Safeguards and Layers of Protection Todd Stauffer, PE exida Consulting 64 N. Main Street, Sellersville, PA tstauffer@exida.com Dr. Peter Clarke,

More information

Stavros Chrysanthou Madrid DynAMo Alarm Management Secrets to unlocking complete Operational Integrity

Stavros Chrysanthou Madrid DynAMo Alarm Management Secrets to unlocking complete Operational Integrity Stavros Chrysanthou Madrid 2018 DynAMo Alarm Management Secrets to unlocking complete Operational Integrity Defining Operational Integrity 1 To secure a process plants integrity is to reduce the risk to

More information

DYNAMO ALARM MANAGEMENT

DYNAMO ALARM MANAGEMENT Tyron Vardy Product Director The Secret to Unlocking Operational Integrity 28 September 2017 DYNAMO ALARM MANAGEMENT Defining Operational Integrity 1 To secure a process plants integrity is to reduce the

More information

Alarm Management for Pipelines

Alarm Management for Pipelines Alarm Management for Pipelines Executive Summary In 2005 the National Transportation Safety Board concluded that an effective alarm review/audit system will increase the likelihood of controllers appropriately

More information

General Specifications

General Specifications General Specifications Model NTPC003 Exaquantum Alarm Master Database PROBLEM Poor alarm management is one of the leading causes of downtime and has contributed to some of the worst recorded industrial

More information

Alarm Management. Alarm Management. DeltaV Whitepaper. February 2011 Page 1

Alarm Management. Alarm Management. DeltaV Whitepaper. February 2011 Page 1 February 2011 Page 1 This document describes how the DeltaV process control system, DeltaV Analyze and services from Emerson and its alliance partners combine to provide a complete and effective foundation

More information

Alarm Management Reflections

Alarm Management Reflections 1 Alarm Management Reflections Standards Certification Education & Training Nicholas P Sands, CAP, PE Manufacturing Technology Fellow, DuPont Publishing Conferences & Exhibits About the Presenter Nicholas

More information

Understanding and Applying the ANSI/ISA 18.2 Alarm Management Standard

Understanding and Applying the ANSI/ISA 18.2 Alarm Management Standard Understanding and Applying the ANSI/ISA 18.2 Alarm Management Standard Written by Bill Hollifield, Principal Alarm Management and HMI Consultant, PAS High Performance HMI Cover Abstract Alarm Management

More information

New requirements for IEC best practice compliance

New requirements for IEC best practice compliance New requirements for IEC 61511 best practice compliance Proof testing and a SIL study may no longer be enough by Sven Grone Schneider Electric Safety Services Practice Leader Executive summary Since its

More information

DeltaV Analyze. DeltaV Analyze. Introduction. DeltaV Product Data Sheet. Continuous automated DeltaV System alarm system performance monitoring

DeltaV Analyze. DeltaV Analyze. Introduction. DeltaV Product Data Sheet. Continuous automated DeltaV System alarm system performance monitoring January 2013 Page 1 DeltaV Analyze The DeltaV Analyze Overview page summarizes your plant alarm and event performance. Continuous automated DeltaV System alarm system performance monitoring Trends of alarms,

More information

PERFORMANCE HUMAN NEXT-GENERATION SCADA HIGH. MACHINE INTERFACES Configuring HMIs to Display Operator-centric Information

PERFORMANCE HUMAN NEXT-GENERATION SCADA HIGH. MACHINE INTERFACES Configuring HMIs to Display Operator-centric Information NEXT-GENERATION SCADA HIGH PERFORMANCE HUMAN MACHINE INTERFACES Configuring HMIs to Display Operator-centric Information Ryan Kowalski, PE; Ed Kowalski, PE 11 September 2017 1 Disclaimers and Notices The

More information

FAST/TOOLS. Alarm System Performance Analysis (ASPA) Bulletin 50A01A00-02EN

FAST/TOOLS. Alarm System Performance Analysis (ASPA) Bulletin 50A01A00-02EN FAST/TOOLS Alarm System Performance Analysis (ASPA) Bulletin 50A01A00-02EN FAST/TOOLS Alarm System Performance Analysis (ASPA) is essential for improved safety and continuity of production across many

More information

Session Number: 3 Making the Most of Alarms as a Layer of Protection

Session Number: 3 Making the Most of Alarms as a Layer of Protection Session Number: 3 Making the Most of Alarms as a Layer of Protection Abstract Todd Stauffer Director Alarm Management Services, exida LLC Alarms and operator response are one of the first layers of protection

More information

Table of Contents PART I: The History and Current Status of the Industrial HMI PART II: Fundamentals of HMI Design and Best Practices

Table of Contents PART I: The History and Current Status of the Industrial HMI PART II: Fundamentals of HMI Design and Best Practices Table of Contents PART I: The History and Current Status of the Industrial HMI We begin with the origin and evolution of the industrial HMI. The positive and negative issues posed by the introduction of

More information

Building Automation Systems from Grantek: Going Beyond Compliance to Improve Operations

Building Automation Systems from Grantek: Going Beyond Compliance to Improve Operations Building Automation Systems from Grantek: Going Beyond Compliance to Improve Operations WWW.GRANTEK.COM 1 Overview Building automation systems (BAS) are necessary and ubiquitous in today s smart manufacturing

More information

Reciprocating Chiller

Reciprocating Chiller HVAC PRO for Windows User s Manual 637.5 OEM Section Technical Bulletin Issue Date 1094 Reciprocating Chiller Reciprocating Chiller Page 3 Description 3 Theory of Operation 5 Overview 5 Control Sequence

More information

2015 Honeywell Users Group Europe, Middle East and Africa

2015 Honeywell Users Group Europe, Middle East and Africa 2015 Honeywell Users Group Europe, Middle East and Africa Safety System Lifecycle Support and Honeywell s capabilities in Industrial Fire & Gas Johan School, Honeywell (Product Manager Safety Systems)

More information

BRIDGING THE SAFE AUTOMATION GAP PART 1

BRIDGING THE SAFE AUTOMATION GAP PART 1 BRIDGING THE SAFE AUTOMATION GAP PART 1 Angela E. Summers, Ph.D., P.E, President, SIS-TECH Solutions, LP Bridging the Safe Automation Gap Part 1, Mary Kay O Conner Process Safety Center, Texas A&M University,

More information

LOPA. DR. AA Process Control and Safety Group

LOPA. DR. AA Process Control and Safety Group LOPA DR. AA Process Control and Safety Group LOPA LOPA is a semi-quantitative risk analysis technique that is applied following a qualitative hazard identification tool such as HAZOP. Similar to HAZOP

More information

Alarm Management Implementation on a Plant. Standards Certification Education & Training Publishing Conferences & Exhibits

Alarm Management Implementation on a Plant. Standards Certification Education & Training Publishing Conferences & Exhibits Alarm Management Implementation on a Plant Standards Certification Education & Training Publishing Conferences & Exhibits Presenter Agenda Introduction Problems faced with Alarm Management Alarm Management

More information

InstrumentationTools.com

InstrumentationTools.com Author: Instrumentation Tools Categories: Safety Systems S84 / IEC 61511 Standard for Safety Instrumented Systems IEC 61511 is a technical standard which sets out practices in the engineering of systems

More information

Critical Condition Management on a Corporate Scale. Lyondell Is a Major Global Chemical Company

Critical Condition Management on a Corporate Scale. Lyondell Is a Major Global Chemical Company Critical Condition Management on a Corporate Scale Lothar Lang Consulting Engineer - CSEE Lyondell Chemical Company Lyondell Is a Major Global Chemical Company A global leader in the manufacture of chemicals

More information

Understanding and Applying the ANSI/ ISA 18.2 Alarm Management Standard in Australia

Understanding and Applying the ANSI/ ISA 18.2 Alarm Management Standard in Australia Understanding and Applying the ANSI/ ISA 18.2 Alarm Management Standard in Australia Abstract Alarm Management has become an ever-increasing topic of discussion in the power and processing industries.

More information

Alarm Enforcement or not?

Alarm Enforcement or not? Alarm Enforcement or not? By Lieven Dubois and Ian Brown, MAC Solutions Introduction Alarm Enforcement is the process of comparing Process Control System (PCS) alarm attributes with the authorised list

More information

Leak Detection Program Management (RP 1175) April 24-26, 2018 St. Louis, Missouri

Leak Detection Program Management (RP 1175) April 24-26, 2018 St. Louis, Missouri Leak Detection Program Management (RP 1175) April 24-26, 2018 St. Louis, Missouri Agenda Introduction Part 1 - Part 2 - Part 3 - Presentation from Chris Hoidal (PHMSA) Audience Q/A (~5 minutes) Presentation

More information

Using HAZOP/LOPA to Create an Effective Mechanical Integrity Program

Using HAZOP/LOPA to Create an Effective Mechanical Integrity Program Using HAZOP/LOPA to Create an Effective Mechanical Integrity Program Steven T. Maher, PE CSP & David J. Childs 949/282-0123 www.rmpcorp.com Download Presentation & Handout www.sems1.com/gcps/2017.htm Steven

More information

Keeping the peace (and quiet)

Keeping the peace (and quiet) Page 1 of 7 ISA Technical Information and Communities 1 September 2005 Keeping the peace (and quiet) The solution is better plant-wide communication and understanding of the alarm philosophy. By Roy Tanner,

More information

Key Topics. Steven T. Maher, PE CSP. Using HAZOP/LOPA to Create an Effective Mechanical Integrity Program. David J. Childs

Key Topics. Steven T. Maher, PE CSP. Using HAZOP/LOPA to Create an Effective Mechanical Integrity Program. David J. Childs Steven T. Maher, PE CSP Using HAZOP/LOPA to Create an Effective Mechanical Integrity Program Steven T. Maher, PE CSP & 949/282-0123 www.rmpcorp.com 37-Year Engineer 33 in Process Safety Consulting Specializing

More information

Alarm Management for SCADA control rooms

Alarm Management for SCADA control rooms Whitepaper Alarm Management for SCADA control rooms Definition of the term alarm The concept of alarms (French for a l arme which means spring to arms ) is very old and originates from the military concept

More information

Control System Studio - CSS - Alarm Handling

Control System Studio - CSS - Alarm Handling Control System Studio - CSS - Alarm Handling Kay Kasemir, Ph.D. ORNL/SNS kasemirk@ornl.gov June 2011 at KEK Managed by UT-Battelle Previous Attempts at SNS ALH; manual summary displays; generated soft-iocs

More information

SIL DETERMINATION AND PROBLEMS WITH THE APPLICATION OF LOPA

SIL DETERMINATION AND PROBLEMS WITH THE APPLICATION OF LOPA SIL DETERMINATION AND PROBLEMS WITH THE APPLICATION OF LOPA Alan G King Hazard & Reliability Specialist, ABB Engineering Services, Billingham, Cleveland UK. TS23 4YS For a number of years, industry has

More information

DeltaV Distributed Control System December 2017

DeltaV Distributed Control System December 2017 DeltaV Distributed Control System White Paper December 2017 Alarm Help This document provides instruction for using the Alarm Help feature in the DeltaV process control system. Increase Operator alarm

More information

LEARNING FROM TEXAS CITY REFINERY ( BP )

LEARNING FROM TEXAS CITY REFINERY ( BP ) LEARNING FROM TEXAS CITY REFINERY ( BP ) Raffinate Splitter Blow down Drum and Stack Blowdown Drum and ISOM Unit, After the Incident Aerial Photograph of Isomerization Unit Isomerization Unit Satellite

More information

Tom Miesner Principal Pipeline Knowledge & Development

Tom Miesner Principal Pipeline Knowledge & Development Introduction to Control Room Management What it Means and Requires May 20, 2011 By Tom Miesner Pipeline Knowledge and Development Tom Miesner Principal Pipeline Knowledge & Development Pipeline Education

More information

Universal Tag Locator. Operations management software for process facilities

Universal Tag Locator. Operations management software for process facilities Universal Tag Locator Operations management software for process facilities Universal Tag Locator An easy-to-use operations monitoring solution featuring extensive search and reporting capabilities to

More information

Smarter Field Instrumentation Life Cycle Management. Ray Rogowski Global Marketing PMC Instruments

Smarter Field Instrumentation Life Cycle Management. Ray Rogowski Global Marketing PMC Instruments Smarter Field Instrumentation Life Cycle Management Ray Rogowski Global Marketing PMC Instruments Smart LifeCycle Management Pressure Temperature Radar Remote Seal Flange Mount User Interface Buttons Single

More information

LifeCycle Engineering & Field Services

LifeCycle Engineering & Field Services Process & Analytical Solutions LifeCycle Engineering & Field Services SafeGuarding Products & Systems Lead with Integrity and Success Follows Proudly serving and supporting western Canadian Industry for

More information

Current Trends in SCADA Systems. Situational Awareness Alarm Management Data Availability System Robustness/Redundancy

Current Trends in SCADA Systems. Situational Awareness Alarm Management Data Availability System Robustness/Redundancy Current Trends in SCADA Systems Situational Awareness Alarm Management Data Availability System Robustness/Redundancy Graham Nasby, P.Eng, PMP, CAP Water SCADA & Security Specialist City of Guelph Water

More information

User manual and installation guide

User manual and installation guide User manual and installation guide 31046005 Copyright Phason Inc. All rights reserved. Printed in Canada About the manual The manual describes the features of your control and how to use them; it does

More information

Pushing Process Limits Without Compromising Safety

Pushing Process Limits Without Compromising Safety 913 A publication of CHEMICAL ENGINEERING TRANSACTIONS VOL. 48, 2016 Guest Editors: Eddy de Rademaeker, Peter Schmelzer Copyright 2016, AIDIC Servizi S.r.l., ISBN 978-88-95608-39-6; ISSN 2283-9216 The

More information

False Alarm Management

False Alarm Management False Alarm Management This document is intended only for fire system professionals who are already experienced in the selection and positioning of fire detectors. Whenever you apply any False Alarm Management

More information

Embracing Change: High Performance Graphics to Improve Operations Water/Wastewater Case Study

Embracing Change: High Performance Graphics to Improve Operations Water/Wastewater Case Study Embracing Change: High Performance Graphics to Improve Operations Water/Wastewater Case Study Standards Certification Education & Training Publishing Conferences & Exhibits Speaker: Jonathan Mitchell,

More information

AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY

AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY World-class services help reduce incidents, protect the environment, and keep people and plants safe White Paper PAGE 1 Introduction

More information

Updated May 15, OASyS DNA and Control Room Management Compliance Statement

Updated May 15, OASyS DNA and Control Room Management Compliance Statement Updated May 15, 2014 OASyS DNA and Control Room Management Compliance Statement 1 OASyS DNA and Control Room Management Executive Summary This document describes how OASyS, specifically the current release

More information

innova-ve entrepreneurial global 1

innova-ve entrepreneurial global 1 1 www.utm.my innova-ve entrepreneurial global 1 Using redundant sensors and final redundant control elements Using multiple sensors with voting systems and redundant final control elements Testing the

More information

HAZARDS EQUAL TRIPS OR ALARMS OR BOTH

HAZARDS EQUAL TRIPS OR ALARMS OR BOTH HAZARDS EQUAL TRIPS OR ALARMS OR BOTH Clive Timms Strathayr, Rhu-Na-Haven Road, Aboyne, Aberdeenshire, AB34 5JB; e-mail: clive.timms@assetintegrity.co.uk Anyone who has been involved in the application

More information

ANALYSIS OF HUMAN FACTORS FOR PROCESS SAFETY: APPLICATION OF LOPA-HF TO A FIRED FURNACE. Paul Baybutt Primatech Inc. and

ANALYSIS OF HUMAN FACTORS FOR PROCESS SAFETY: APPLICATION OF LOPA-HF TO A FIRED FURNACE. Paul Baybutt Primatech Inc. and ANALYSIS OF HUMAN FACTORS FOR PROCESS SAFETY: APPLICATION OF LOPA-HF TO A FIRED FURNACE by Paul Baybutt Primatech Inc. and Joel Haight The Pennsylvania State University Abstract Layers of Protection Analysis

More information

AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY

AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY World-class services help reduce incidents, protect the environment, and keep people and plants safe White Paper PAGE 1 Introduction

More information

I/A Series Software. Differential Gap (DGAP) Controller Block PSS 21S-3C5 B4 OVERVIEW PRODUCT SPECIFICATIONS

I/A Series Software. Differential Gap (DGAP) Controller Block PSS 21S-3C5 B4 OVERVIEW PRODUCT SPECIFICATIONS PRODUCT SPECIFICATIONS I/A Series Software Differential Gap (DGAP) Controller Block The DGAP Controller block is a differential gap on-off controller for controlling bi-state or tri-state control applications.

More information

IEC61511 Standard Overview

IEC61511 Standard Overview IEC61511 Standard Overview Andre Kneisel Instrumentation Engineer Chevron C.T. Refinery SAFA Symposium 2011 August 5 th, 2011 Presentation Overview Provide some understanding of the key aspects of Functional

More information

DCS-3000 AutoCure Operating Manual

DCS-3000 AutoCure Operating Manual DCS-3000 AutoCure Operating Manual DCS-3000 AutoCure Control System 2011 110707 page 1 ABLE OF CONENS 1. Overview 2. AutoCure operation 3. Casing control 4. Set Up (Changing the way the instrument works)

More information

CELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL

CELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL Operation Manual Celltrol II Bioreactor Control System Page 1 of 33 Table of Contents 1) Introduction... 3 1.1) Scope of Document... 3 1.2) Control System Overview... 3 1.3) Introduction to Celltrol II...

More information

No part of this publication may be reproduced, stored in an automated data file or made public in any form or by any means, whether electronic,

No part of this publication may be reproduced, stored in an automated data file or made public in any form or by any means, whether electronic, No part of this publication may be reproduced, stored in an automated data file or made public in any form or by any means, whether electronic, mechanical, by photocopying, recording or in any other manner

More information

Safety Instrumented Fire & Gas Systems

Safety Instrumented Fire & Gas Systems Safety Instrumented Fire & Gas Systems aesolutions Provides Full-Service Fire & Gas Engineering and Products The aesolutions FM-approved family of Fire & Gas safety systems ensures compliance with the

More information

Managing Alarms to Support Operational Discipline

Managing Alarms to Support Operational Discipline Managing Alarms to Support Operational Discipline Denise Chastain-Knight. PE, CFSE exida Consulting LLC 64 North Main Street Sellersville, PA, USA dchastainknight@exida.com Todd Stauffer, PE exida Consulting

More information

Ovation Alarm Management System

Ovation Alarm Management System Ovation Alarm Management System Features Multiple types of fully configurable, easy-tounderstand alarm displays Convenient access to past alarms, returns and state changes Simplified ability to acknowledge,

More information

False Alarm Management

False Alarm Management False Alarm Management This document is intended only for fire system professionals who are already experienced in the selection and positioning of fire detectors. Whenever you apply any False Alarm Management

More information

Facility Commander Wnx

Facility Commander Wnx Facility Commander Wnx Integrated security management platform for Windows Seamless. Effective. Efficient. Integrate security applications on one versatile platform It s easy and efficient to seamlessly

More information

GE Security. Wnx. Facility Commander. Integrated security management platform for Windows. Seamless. Effective. Efficient.

GE Security. Wnx. Facility Commander. Integrated security management platform for Windows. Seamless. Effective. Efficient. GE Security Facility Commander Wnx Integrated security management platform for Windows Seamless. Effective. Efficient. We have 70% security personnel turnover in a year. How can we effectively train them

More information

Automation and Energy Efficiency of Industrial Refrigeration Systems

Automation and Energy Efficiency of Industrial Refrigeration Systems Automation and Energy Efficiency of Industrial Refrigeration Systems E360 Forum Chicago, IL October 5, 2017 Mike Micak Director of Sales Logix Controls Introduction Management thinker Peter Drucker was

More information

PRIMATECH WHITE PAPER CHANGES IN THE SECOND EDITION OF IEC 61511: A PROCESS SAFETY PERSPECTIVE

PRIMATECH WHITE PAPER CHANGES IN THE SECOND EDITION OF IEC 61511: A PROCESS SAFETY PERSPECTIVE PRIMATECH WHITE PAPER CHANGES IN THE SECOND EDITION OF IEC 61511: A PROCESS SAFETY PERSPECTIVE Summary From the perspective of process safety, the most notable change is the addition of requirements for

More information

Safety Instrumented Systems

Safety Instrumented Systems Safety Instrumented Systems What is a Safety Instrumented System? A Safety Instrumented System SIS is a new term used in standards like IEC 61511 or IEC 61508 for what used to be called Emergency Shutdown

More information

Closing the Holes in the Swiss Cheese Model Maximizing the Reliability of Operator Response to Alarms

Closing the Holes in the Swiss Cheese Model Maximizing the Reliability of Operator Response to Alarms Closing the Holes in the Swiss Cheese Model Maximizing the Reliability of Operator Response to Alarms Todd Stauffer, PE Director Alarm Management, exida consulting 80 N. Main Street, Sellersville, PA 18960

More information

1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process.

1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process. SECTION 239950 MECHANICAL COMMISSIONING SYSTEMS PART 1 - GENERAL 1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process. B. Commissioning

More information

DATA SHEET BENEFITS CURRENT CHALLENGES SSM INFOTECH S X-FORCE AMS - THE IDEAL SOLUTION

DATA SHEET BENEFITS CURRENT CHALLENGES SSM INFOTECH S X-FORCE AMS - THE IDEAL SOLUTION DATA SHEET BENEFITS Alarm Printers, Report Printer Replacement Better Operator Attention Alarm Rationalization Remote Viewing of Alarms Unlimited Archiving of Alarms\Event Messages Alarm Consolidation

More information

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE Release January 2001 CONTENTS 1.0 GENERAL CHARACTERISTICS... 4 1.1 MAIN CHARACTERIS TICS... 4 2.0 USER INTERFACE (CODE C5121230)... 5 2.1 DISPLAY... 5 2.2 MEANING OF THE LEDS...

More information