GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT
|
|
- Ralph Marsh
- 5 years ago
- Views:
Transcription
1 GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT FIRE FOR LIBRARY HOTEL OCTOBER 2014
2 Report for Department of Infrastructure Development Fire Services Preliminary Report: Library Hotel Oct 2014 Table of Contents 1. INTRODUCTION Design Criteria and Specifications Scope of the Services Scheme Report PROJECT SUMMARY FIRE SYSTEMS Fire Water System Details Smoke Ventilation Details Means of Escape Details Structure and Compartmentation Details Recommendation... 4 i P a g e
3 1. INTRODUCTION Library Hotel is located at cnr. Commissioner and Fraser Streets, Johannesburg, Gauteng (see Locality Map). Figure 1: Locality Map The project brief, as issued by Gauteng Funding Agency, was to conduct an initial assessment of the building fire infrastructure and systems of Library Hotel, and to provide recommendations regarding the repairs and renovations of the building. 1.1 Design Criteria and Specifications This project will be implemented in compliance with all the requirements of the National Building Regulations and the new SANS10400, with specific focus on Part T of the regulations. The entire assessment shall be carried out in accordance with relevant SANS codes applicable for the facility: SANS T, The application of the National Building Regulations Part T: Fire Protection SANS D, The application of the National Building Regulations Part D: Public safety. SANS M, The application of the National Building Regulations Part M: Stairways. SANS W, The application of the national building regulations Part W: Fire Installation SANS 543, Fire Hose Reels SANS , Symbolic safety signs Part 1: Standard signs and General requirements 1
4 SANS , The use and control of fire-fighting equipment Part 1: Portable and wheeled (mobile) fire extinguishers. SANS 1910, Portable refillable fire extinguishers 1.2 Scope of the Services Scheme Report This report deals with the fire services to be implemented based on the existing systems and proposed architectural changes to the building, this is photographic assessment only. 2. PROJECT SUMMARY 2.1 Project Description Library Hotel is an existing multi-level building and is comprised of ground floor, upper floors and a service level. The Library Hotel building is a total of 2349 m 2. The building is currently in a state of disrepair and appears to have been in the process of being refurbished. The majority of the services, Fire systems included, have been stripped or demolished. 3. FIRE SYSTEMS 3.1 Fire Water System Details The entire fire water system is non-operational. All hose reels have been completely removed, figure 2. All portable fire extinguishers have been removed, figure 1. All hydrants have been removed from the vertical riser pipes. There is no indication of a pump or tank supply for the fire water system. There is no statutory fire signage installed indicating fire equipment. There is currently no means of fighting a fire should one occur in the building. Figure 1 Extinguisher Mounting Board Figure 2 Hose Reel Location 2
5 3.2 Smoke Ventilation Details The main central stair has no ventilation and is open to each floor Smoke ventilation on the floors is by openable windows (figure 3, 4), these are not in working condition and many have been removed. Figure 3 Openable Windows Figure 4 Removed windows 3.3 Means of Escape The Library Hotel building is currently served by a central fire escape stair that is not enclosed and is open on all levels. There was an additional staircase to the west of the building that has been demolished Details Hand railings are on a single side of the stairs only, current regulations require handrails on both sides. The northern fire escape stair has been demolished, figure 6. The central staircase is open to all levels, figure 5. This stairwell needs to be enclosed into a fire compartment to ensure integrity of the emergency route and limit fire spread between levels. Hand railings in the staircases have been damaged and there are sections missing (figure 11). These require repairs or replacement. There is no statutory fire signage installed indicating escape routes. Figure 5 - Central Staircase Figure 6 - Northern Staircase The number of safe escape routes are not adequate for a population of a standard office building. The demolished staircase is required for adequate means of escape. The central stair has no smoke ventilation, ventilation will be required once enclosed. 3
6 3.4 Structure and Compartmentation The Library Hotel building is of concrete structure with brick internal structure. There are numerous vertical shafts and service penetrations between floors Details There are several areas of damaged slabs, structural engineer needs to comment on structural stability in terms of a fire situation. There are many old service penetrations through floor slab (figure 7), all openings through slabs require fire sealing rated to 120 minutes. Figure 7 Vertical Openings 4 Recommendation The critical remedial work required to meet the minimum national fire standard is recommended and a high level budgetary cost for the remedial work is presented. Install new fire hose reels, fire hydrants and fire extinguishers as per SANS T/W. Install new fire water booster pump and storage tank. Install new statutory fire signage throughout. Repair/ replace existing handrails in stairwells. Enclose central fire escape stair and add natural ventilation at top of stair at 25% of stairwell footprint area. Install second hand rail within all stairwells as per SANS S. Reinstate demolished stairwells. Install new fire doors to all escape stairs. All vertical penetrations through floor slab to be fire sealed All damaged sections of slab to be repaired to ensure a minimum of 60 minutes structural stability 4
GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT
GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT FIRE FOR 69 PRESIDENT SEPTEMBER 2014 Report for Department of Infrastructure Development Fire Services Preliminary Report: 69
More informationGAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT
GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT FIRE FOR 75 Fox Street Building OCTOBER 2014 Report for Department of Infrastructure Development Fire Services Preliminary Report:
More informationGAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT
GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT VERTICAL TRANSPORT FOR ABSA BUILDING OCTOBER 2014 Report for Gauteng Department of Infrastructure Development Vertical Transport
More informationSCHEDULE. Essential Safety Measures taken from Schedule 9 of the Building Regulations PART 1 BUILDING FIRE INTEGRITY
SCHEDULE Essential s taken from Schedule 9 of the Building Regulations 2006 43 PART 1 BUILDING FIRE INTEGRITY 1 Building elements required to satisfy prescribed fire-resistance levels 2 Materials and assemblies
More informationTHE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NEW BUILDINGS
FIRE RISK ASSESSMENT NEW BUILDINGS BUILDING SUMMARY The building is utilised for classroom teaching for Modern Languages. 1. Identification of the hazards 1.1 Identification of sources of fuel. Timber
More informationFIRE RISK ASSESSMENT NOT KNOWN 15/10/ SOMERTON COURT BROADMOSS DRIVE SIMON ROFFEY
UPRN Date of inspection Address 1 (flat numbers) Address 2 (street) Address 3 (area) Fire Risk Assessor Checked by Approved by Postcode Does the building have common areas? Was access available to the
More informationTHE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY)
FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY) BUILDING SUMMARY The building was constructed in Victorian times and is constructed of brick with knapped flint in fill on some outer walls. The building
More informationBUILDING ASSESSMENT REPORT ELECTRICAL SERVICES FOR 75 FOX STREET BUILDING
GAUTENG DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT ELECTRICAL SERVICES FOR 75 FOX STREET BUILDING September 2014 Contents 1. INTRODUCTION... 3 1.1. Design Criteria and Specification...
More informationTHE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT SPORTS CENTRE
FIRE RISK ASSESSMENT SPORTS CENTRE BUILDING SUMMARY The building is used as a Sports Centre and contains a large sports hall with changing rooms, an office for staff and a fitness area. 1. Identification
More informationTHE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT HORSEFAIR HOUSE
FIRE RISK ASSESSMENT HORSEFAIR HOUSE BUILDING SUMMARY The building is utilised for the teaching of Science and contains Laboratories and Chemical storage. 1. Identification of the hazards 1.1 Identification
More informationUCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES
Mandatory Fire Safety Instruction UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES Principal Contractor fire safety considerations in shared occupancy project or refurbishments
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT DANNY'S KNITWEAR LTD. ACCORD ID: 12228 SURABARI, GAZIPUR, SADAR, GAZIPUR Other Factories: ne October 17, 2015 Page 2 Fire Safety Inspection Report Introduction manufacturing
More informationEQUIVALENT INITIAL FIRE SAFETY ASSESSMENT
EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Plot # 33-36 Sector # 07, Chittagong Chittagong Chittagong 08 Jun 2014 The Alliance for Worker Safety Page 1/18 08 Jun 2014 Introduction to the Report
More information- CONSTRUCTION FIRE SAFETY STANDARDS
SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Hot Work Permits All construction sites shall implement a system of Hot Work Permits for all work activities that generate heat, sparks or flames. All of the
More informationMWL Consulting Company
MWL Consulting Company NFPA Member since1990 Fire Service Section Fire Marshal (retired) Newport Fire Department Michael W. Leber 17 Whitwell Avenue Newport, RI 02840 Mobile Phone 401-439-5322 mlebernpt@aol.com
More informationSome Important Aspects of Fire Safety Regulations about High Rise Buildings
Some Important Aspects of Fire Safety Regulations about High Rise Buildings Tokyo University of Science Prof. Kyoichi Kobayashi (Dr. of Engineering) Many high rise buildings are being built with awful
More informationEnclosure 4- RISK ASSESSMENT
Enclosure 4- RISK ASSESSMENT RISK ASSESSMENT Risk is a potential that a chosen action or activity will lead to a loss of human or property. Risk assessment is a step for Risk Management. Risk assessment
More informationINITIAL FIRE SAFETY ASSESSMENT - EXPANSION
INITIAL FIRE SAFETY ASSESSMENT - EXPANSION Factory Plot 47-52 & 68-73, KEPZ North Patenga Chittagong Chittagong 06 Mar 2017 The Alliance for Bangladesh Worker Safety Page 1/23 06 Mar 2017 Introduction
More informationINITIAL FIRE SAFETY ASSESSMENT
INITIAL FIRE SAFETY ASSESSMENT Factory Plot No -246-249, Adamjee EPZ, Siddhirganj, Narayanganj Narayanganj 17 Jul 2016 The Alliance for Bangladesh Worker Safety Page 1/17 Factory 17 Jul 2016 Introduction
More informationLYHA Fire Safety Policy
LYHA Fire Safety Policy Introduction This Fire Safety Policy shows our approach to Fire Safety in the work place and in our homes. It identifies our approach to Fire Safety in: The workplace Flats with
More informationHealth, Safety and Wellbeing Management Arrangements. Core I Consider I Complex. Fire Safety. Health, Safety and Wellbeing Service
Health, Safety and Wellbeing Management Arrangements Core I Consider I Complex Fire Safety Health, Safety and Wellbeing Service 1. Success Indicators The following indicators will demonstrate success in
More informationFire Risk Assessment
Fire Risk Assessment Maritime Studios Pendennis Rise Falmouth TR11 4FB Carried out by: Date: October 2015 Review Date: October 2016 Les Carter CMIOSH Health & Safety Consultant Mobile 07831 636751, Email
More information- CONSTRUCTION FIRE SAFETY STANDARDS
SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Construction Planning All construction sites shall plan and sequence their construction activities to ensure the early installation and operation of permanent
More informationWhere EXCESSIVE reduce the number of ignition sources such as: ACTIONS TAKEN/TO BE TAKEN:-*
Snowtraxx International General Hotel Risk Assessments 2015/16 Version Date: Hotel: Resort: Staff Name: Fire Prevention Where EXCESSIVE reduce the number of ignition sources such as: by the outbreak of
More informationINITIAL FIRE SAFETY ASSESSMENT
INITIAL FIRE SAFETY ASSESSMENT Factory Assessor: 180, Baizid Bostami Road Nasirabad I/A Area-1, Building -1, Chittagong Chittagong Chittagong Bangladesh Emkay Enterprises 31 Jan 2015 The Alliance for Bangladesh
More informationCertification Assessment Instrument and Guidelines
Certification Instrument Full compliance with BCA 96 will ensure passing 19 for Section 1 Do not need 100 to pass 1 SECTION 1 SAFETY (25 POINTS) Residential Fire Sprinkler System Not required to pass Section
More informationREGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT
OVERALL COLOUR ACTION CODE RISK AMBER STATUTORY INSTRUMENT 2005:1541 REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT Address of Premises: Thuurock CCG, Civic Offices New Road Grays Responsible
More informationSURREY FIRE SERVICE. Construction Fire Safety Plan Bulletin
SURREY FIRE SERVICE Construction Fire Safety Plan Bulletin The B.C. Fire Code requires building owners/contractors to comply with the requirements of the BC Fire Code 5.6 Construction and Demolition Sites
More informationFIRE RISK ASSESSMENT
FIRE RISK ASSESSMENT Full Property Name: St Augustine s Catholic Voluntary Academy Full Property Address: Opposite 93 PE9 1SR Date of Fire Risk Assessment: 6 th June 2017 Name of Fire Risk Assessor: Peter
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT MULTIFABS LTD KASHIMPUR, NAYAPARA Other Factories: ne April 9, 2014 Page 2 Fire Safety Inspection Report Introduction manufacturing complex was surveyed for fire safety on
More informationLondon Borough of Hammersmith & Fulham
Assessment Details: Property Assessed Flora Gardens 186-197, FLORA GARDENS, LONDON Assessment Date 19/12/2017 Assessment Valid Until 04/12/2020 Assessor Details Mark Richards LBHF Fire Risk Assessor QA
More informationBUILDING FIRE STRATEGY (Operational & Fire Engineering Information)
Safety Services Fire Safety Fire Strategy for: 132 Hampstead Road (317) UNIVERSITY COLLEGE LONDON BUILDING FIRE STRATEGY (Operational & Fire Engineering Information) Regulatory Reform (Fire Safety) Order
More informationOur Ref: CD/FSSD/12/02/03/01 DID: FAX:
Our Ref: CD/FSSD/12/02/03/01 DID: 68481407 FAX: 68481493 14 Jan 2010 Registrar, Board of Architects (BOA) Registrar, Professional Engineers Board (PEB) President, Singapore Institute of Architects (SIA)
More informationLevel 2 Award in Fire Safety (QCF) (SCQF Level 5 in Scotland) Unit 1 title: Fire safety principles
Level 2 Award in Fire Safety (QCF) (SCQF Level 5 in Scotland) Qualification code: 600/8190/9 Unit 1 title: Fire safety principles Unit number: D/601/9698 TBC in Scotland TBC in Scotland Learning Outcomes
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT TOYO COMPOSITE KNIT GARMENTS LTD 1, SOUTH KAMALAPUR SARDER COMPLEX, DHAKA Other Factories: Pure Cotton Ltd, Knit and Knitwear Ltd June 7, 2014 Page 2 Fire Safety Inspection
More informationReviewed: DD Month Emergency Evacuation of People with a Disability Options Matrix for Developing a PEEP
Safety Office Reviewed: 17 July 2012 Reviewed: DD Month Emergency Evacuation of People with a Disability Options Matrix for Developing a PEEP The following matrix includes most disability types and recommends
More informationINITIAL FIRE ASSESSMENT REPORT (FAR)
INITIAL FIRE ASSESSMENT REPORT (FAR) Factory SQ Station, Plot # 221-223, Jamirdia, Valuka, Mymensingh Mymensingh 17 Jun 2014 The Alliance for Bangladesh Worker Safety Page 1/17 Factory 17 Jun 2014 Introduction
More informationSAFETY. USE OF SAFETY CHECK LISTS A safety check for compliance with current regulations should be performed yearly.
SAFETY GENERAL Buildings must be designed according to building and fire safety codes and other regulatory standards at the time of construction. However, such codes and standards are continuously changing.
More informationKensington Aldridge Academy, London W10
Kensington Aldridge Academy, London W10 Fire Safety Review Job Number: 1103 June 2018 FIRE SAFETY REVIEW CONTENTS EXECUTIVE SUMMARY 1.0 INTRODUCTION 2.0 FIRE SAFETY REQUIREMENTS 3.0 EXTERNAL WALL SPECIFICATION
More informationSlight Harm Moderate Harm Extreme Harm Low Trivial Risk Tolerable Risk Moderate Risk Medium Tolerable Risk Moderate Risk Substantial Risk
Fire Risk Assessment: ABC Sample House Sample Road SA1 3M2 C J Sparks Ltd 13 Alexandra Gardens Carshalton SM5 4LJ T: 02077577457 W: www.cjsparks.com E: sales@cjsparks.com Ref: 3077 Action Plan Number Action
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT MAHID APPAREL LTD ACCORD ID: 11956 NOWPARA, MADHABDI, NARSINGDI, DHAKA-1604 OTHER FACTORIES: NONE February 20, 2015 Page 2 SUMMARY was surveyed for fire safety on 2/20/2015
More informationAFEC FIRE ENGINEERING TEMPLATE FOR CLIENTS INTERNALLY COMPLETED RISK ASSESMENT
AFEC FIRE & RISK ENGINEERING SPECIALISTS would like to share an in house Risk Assessment Template we have developed for in house use to assist Facilities Managers and Environmental Health and Safety Staff
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT VINTAGE GARMENTS LTD EAST NARSHINGPUR, BURI PARA, ASHULIA, SAVAR Other Factories: ne June 1, 2014 Page 2 Fire Safety Inspection Report Introduction manufacturing complex was
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT BEQ KNIT LTD. ZIRABO, ASHULIA, SAVAR, DHAKA Other Factories: Beq Sweaters Ltd., Tammam Design Ltd. April 22, 2014 Page 2 Fire Safety Inspection Report Introduction manufacturing
More informationFollowing are the systems proposed as per NBC & Local Fire Authority:
1. OBJECTIVES AND STRATEGIES OF THE FIRE PROTECTION DESIGN This report describes the design parameters, system requirements of fire protection system for mixed occupancy (Assembly + Business) building
More information8.1. Fire and Heritage. The maintenance series. Information sheet. Guidelines on Fire Safety in Heritage Buildings
The maintenance series Information sheet 8.1 Fire and Heritage Destruction of the Prince of Wales Theatre by fire on 3 October 1860. It was situated at the corner of King and Castlereagh Streets, Sydney.
More informationINITIAL FIRE SAFETY ASSESSMENT
INITIAL FIRE SAFETY ASSESSMENT Factory Name: Assessor: Anzir Apparels Limited, Unit-1 Karim supermarket, Baipal, Baipal, Savar Savar Dhaka Bangladesh Emkay Enterprises 30 Apr 2014 The Alliance for Bangladesh
More information150 Elgin - Office Tower and Grant House Renovations
APPLICATION OF THE ONTARIO BUILDING CODE 150 Elgin - Office Tower and Grant House Renovations 150 Elgin Street Ottawa, Ontario Presented to: Mr. Brandon Donnelly Morguard Investments Limited c/o Mr. Harry
More informationFIRE SAFETY IN PURPOSE BUILT BLOCKS OF FLATS
A GUIDE ON FIRE SAFETY IN PURPOSE BUILT BLOCKS OF FLATS INTRODUCTION Fire safety in blocks of flats is something that must be taken very seriously. The Local Government Group (LGG) was commissioned to
More informationOCCUPATIONAL PROFILE FIRE FIGHTING EQUIPMENT TECHNICIAN (Special Class Electrician, Fire Detection System Designer) CURRICULUM CODE:
OCCUPATIONAL PROFILE FIRE FIGHTING EQUIPMENT TECHNICIAN (Special Class Electrician, Fire Detection System Designer) CURRICULUM CODE: 1. OCCUPATIONAL PURPOSE A Fire Fighting Equipment Technician installs
More informationUnit 2: Fire Safety (F/505/6006)
L3D2 THE INSTITUTION OF FIRE ENGINEERS Founded 1918 Incorporated 1924 IFE Level 3 Diploma in Fire Science and Fire Safety (VRQ) Unit 2: Fire Safety (F/505/6006) Thursday 10 March 2016 10.30 13.30 Instructions
More informationCURTIN UNIVERSITY PROJECT DELIVERY GUIDELINES
CURTIN UNIVERSITY PROJECT DELIVERY GUIDELINES EMERGENCY MANAGEMENT DESIGN GUIDELINES 000331 Details of revisions Level Details Date Initial 1 Document created from 20150513NewBuildsAndRedevelopments.docx
More informationREGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT
REGULATORY REFORM (FIRE SAFETY) ORDER 005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT Responsible person (e.g. employer) or person having control of the premises: Address of premises: Graham Care Group Cornford
More informationFire Risk Assessment
Fire Risk Assessment Manor House HS.F.119 (rev03) delivering promises improving lives Contents 1 Premises particulars... 1 2 General statement of policy... 1 3 Management systems... 1 4 General description
More informationAreas of the building to which access was not available. Details of any onsite management (if known)
SECTION ONE UPRN Address 1 (block name and/or street number) Address 2 (flat numbers) Address 3 (street) Address 4 (area) Postcode Date of inspection Suggested review date Fire Risk Assessor Property Designation
More informationFIRE SAFETY INSPECTION REPORT
Page 1 FIRE SAFETY INSPECTION REPORT Impress Fashion Ltd. ACCORD ID: 12245 Dag No. 2224, Matuial, Konapara, Katherpool, Jatrabari, Dhaka-1362 Other Factories: None Date: August 27, 2015 Sl No. Category
More informationIndependent Living Scheme Fire Risk Assessment. General needs residential sleeping accommodation
Sutton House 1 Forster Street Radford ttingham NG67 3DQ At ttingham City Homes we want our residents to be assured that their homes are safe. We willingly accept our duty to comply with our statutory fire
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT GLOBAL OUTWEAR LTD. PLOT # M/1, ROAD # 7, SECTION # 7, MIRPUR, DHAKA March 3, 2014 Accord - Bangladesh RMG Fire Safety Inspection Global Outwear Ltd. Page 2 SUMMARY Global
More informationBuilding Construction i. approx. age ii. building structure iii. cladding iv. floors v. walls vi. roof
SECTION ONE UPRN Address 1 (block name and/or street number) Address 2 (flat numbers) Address 3 (street) Address 4 (area) Postcode Date of inspection Suggested review date Fire Risk Assessor Property Designation
More informationINITIAL FIRE SAFETY ASSESSMENT
INITIAL FIRE SAFETY ASSESSMENT Factory Bashtoli, Sinabah, Sofipur, Kaliakoir, Gazipur Gazipur Dhaka 08 Sep 2014 The Alliance for Worker Safety Page 1/10 Factory 08 Sep 2014 Introduction to the Report The
More informationFire Risk Assessment
Fire Risk Assessment Carr House HS.F.119 (rev03) delivering promises, improving lives Contents 1 Premises particulars... 1 2 General statement of policy... 1 3 Management system... 1 4 General description
More informationPROJECT: NITESH PALO Bangalore FIRE SAFETY MEASURES
PROJECT: NITESH PALO ALTO @ Bangalore FIRE SAFETY MEASURES System Description 1 Firewater pumping system 2 Wet riser system and hose reel system. 3 Automatic sprinkler system 4 Yard hydrant system 5 Pressurization
More informationEQUIVALENT INITIAL FIRE SAFETY ASSESSMENT
EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Assessor: Konabari, Neelnagar, Gazipur Gazipur Dhaka Bangladesh Uttaron The Alliance for Bangladesh Worker Safety Page 1/13 Introduction to the Report The following
More informationFire Safety Regulations
Student residence Haus Erasmus Vienna 1070 Kenyongasse 23-25 I. Introduction Fire Safety Regulations These fire safety procedures contain important information about the actions of residents to ensure
More informationSCOUT HALL INSPECTION CHECKLIST
Scouts Australia NSW Level 1, Quad 3 102 Bennelong Parkway Sydney Olympic Park 2127 P O Box 125 Lidcombe NSW 1825 Ph: 02 9735 9000 Fax: 02 9735 9001 SCOUT HALL INSPECTION CHECKLIST Please complete all
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT KAROONI KNIT COMPOSITE RATANPUR, SHAFIPUR KALIAKOIR OTHER FACTORIES: NONE April 5, 2014 Page 2 SUMMARY was surveyed for fire safety on 4/5/2014 by Hughes Associates, Inc.
More informationTechnical write-up on Fire safety services
1. General: Technical write-up on Fire safety services Nitesh Santa Clara, proposed development is a residential apartment with multiple blocks. Document briefs on fire safety systems envisaged for the
More informationINITIAL FIRE SAFETY ASSESSMENT
INITIAL FIRE SAFETY ASSESSMENT Factory Assessor: 107/112 Nazrul Market 1st & 2nd floor, Chawk Bazar, Chittagong Emkay Enterprises 09 Apr 2014 The Alliance for Bangladesh Worker Safety Page 1/28 Factory
More informationAMBASSADOR HOUSE. A guide on. Fire Safety in Purpose Built Blocks of Flats
AMBASSADOR HOUSE A guide on Fire Safety in Purpose Built Blocks of Flats INTRODUCTION Fire safety in blocks of flats is something that must be taken very seriously. The Local Government Group (LGG) was
More informationMAINTENANCE OF ESSENTIAL SAFETY MEASURES EXPLAINED (Building Regulations 2006)
MAINTENANCE OF ESSENTIAL SAFETY MEASURES EXPLAINED (Building Regulations 2006) 1. INTRODUCTION 1.1 Essential Safety Measures Defined Essential Safety Measures (previously called essential services) are
More informationCOMPLYING DEVELOPMENT CERTIFICATE APPLICATION FORM
COMPLYING DEVELOPMENT CERTIFICATE APPLICATION FORM Under the Environmental Planning and Assessment Act 1979/ Environmental Planning and Assessment Regulation 2000 SUBJECT LAND Lot: Section: DP/SP: APPLICANT/S
More informationINITIAL FIRE ASSESSMENT REPORT (FAR)
INITIAL FIRE ASSESSMENT REPORT (FAR) Factory 94/95 (OLD) 46 NEW (Ground To 5th), BLOCK C TONGI INDUSTRIAL AREA,, TONGI, GAZIPUR, GAZIPUR, 0, BD GAZIPUR Dhaka Bangladesh 11 Apr 2014 The Alliance for Bangladesh
More informationINITIAL FIRE SAFETY ASSESSMENT
INITIAL FIRE SAFETY ASSESSMENT Factory Anowara, Plot # G1 and G2, Korean EPZ, Chittagong Chittagong 21 May 2015 The Alliance for Bangladesh Worker Safety Page 1/22 21 May 2015 Introduction to the Report
More informationElement C3.5 Means of Escape
.5 Means of Escape RRFSO Article 14 Legal Factors Responsible person must ensure routes to emergency exits and exits themselves are kept clear at all times Exits must directly lead to place of safety Safe
More informationRHBL 7325 ENVIRONMENTAL ANALYSIS. By: Whitney Musick
RHBL 7325 ENVIRONMENTAL ANALYSIS By: Whitney Musick UALR s Ottenheimer Library Photo Credit: http://www.flickr.com/photos/30091470@n08/4565851613/ Background Description Ottenheimer Library is centrally
More informationShort-Term & Accessory Short-Term Rental Safety Certification
Short-Term & Accessory Short-Term Rental Safety Certification Permit Application Center (City Hall) 555 Liberty St. SE, Room 320 Salem, OR 97301 503-588-6213 (For office use only) License #: If you need
More informationBlue Whirl Building. General Fire Safety Checklist. conducted for. Location 1029 McLean Ave, Dallas, TX 75211, USA. Visit 20 Sep :08 PM
General Fire Safety Checklist conducted for Blue Whirl Building Location 1029 McLean Ave, Dallas, TX 75211, USA Visit 20 Sep 2018 03:08 PM Prepared by SafetyCulture Staff Completed on 20 Sep 2018 03:58
More informationFire Safety in Communal Areas Policy
Fire Safety in Communal Areas Policy Date approved by senior management team 27 th July 2017 Board of Management / Committee name Board of Management Approval date 2 nd October 2017 Implementation date
More informationEQUIVALENT INITIAL FIRE SAFETY ASSESSMENT
EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Name: 4 YOU CLOTHING LTD 367/1 Senpara Parbata, Mirpur-10, Dhaka Dhaka Dhaka Bangladesh 27 May 2014 The Alliance for Bangladesh Worker Safety Page 1/20
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT PORTLAND TEXTILE LTD. ACCORD ID: 11873 PLOT NO. 14-15, SECTOR 6, CHITTAGONG EXPORT PROCESSING ZONE, CHITTAGONG OTHER FACTORIES: NONE November 3, 2015 Page 2 SUMMARY was surveyed
More informationFIRE SAFETY MANAGEMENT PLANS DEVELOPMENT GUIDE A GUIDE TO DEVELOPING
FIRE FETY MANAGEMENT PLANS DEVOPMENT GUIDE A GUIDE TO DEVOPING FIRE FETY MANAGEMENT PLANS EXAMPLE FIRE FETY MANAGEMENT PLAN This example of a Fire Safety Management Plan does not relate to an actual building
More informationProcedure DESCRIPTION/OVERVIEW
Applies To: UNMH Responsible Department: Life Safety Revised: 07.08.16 Procedure Patient Age Group: (X ) N/A ( ) All Ages ( ) Newborns ( ) Pediatric ( ) Adult DESCRIPTION/OVERVIEW To assure the safety
More informationFIRE DEPARTMENT - RULES FOR FIRE PROTECTION IN AUSTRIA
93 FIRE DEPARTMENT - RULES FOR FIRE PROTECTION IN AUSTRIA INTRODUCTION 94 Legal requirements for the protection of firefighters Requirements of Building Act Fire Prevention Act Technical Guidelines OIB
More informationAPPENDIX C APPROVAL PROCESS SUBMISSION FORMS. HCJ/LJ/B100841/JR Issue I April 16. Appendix C
APPENDIX C APPROVAL PROCESS SUBMISSION FORMS STEP 2A CONCEPT DESIGN SUBMISSION To: Edward Utteridge From: Jonathan Everitt jeveritt@oriumdesign.co.uk Terry Lailey t.lailey@oriumdesign.co.uk Checklist (tick
More informationPRINCE GEORGE LIBRARY NEW ENTRANCE REPORT Patricia Boulevard Prince George, BC V2L 3V9
#230 177 Victoria Street P rince George, BC V2L 5R8 Tel. (250) 564-7285 F ax. (250) 564-7286 1100 Patricia Boulevard Prince George, BC V2L 3V9 PRINCE GEORGE LIBRARY NEW ENTRANCE REPORT CITY OF PRINCE GEORGE
More informationFive London Hospital Fires: Report by Philip Gibbs, LFB. For internal training use only.
Introduction This report is a summary of the findings from a study conducted into the Five London Hospital Fires by Philip Gibbs of London Fire Brigade. The purpose of this report is to: Highlight fire
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT MAGPIE COMPOSITE TEXTILE LTD. 832/833, DEWAN IDRIS ROAD, AMTOLI, ASHULIA, SAVAR, DHAKA OTHER FACTORIES: NONE May 17, 2014 Page 2 SUMMARY was surveyed for fire safety on 5/17/2014
More informationFIRE SAFETY INSPECTION REPORT REDPOINT JACKETS LTD, DHAKA, BANGLADESH
FIRE SAFETY INSPECTION REPORT REDPOINT JACKETS LTD, DHAKA, BANGLADESH January 3, 2014 Redpoint Jackets Ltd. PAGE 1 SUMMARY The four story factory housing Redpoint Jackets Ltd. located in Dhaka Export Processing
More informationFire Safety Regulations
Student residence Spengergasse Vienna 1050 Spengergasse 27 I. Introduction Fire Safety Regulations These fire safety procedures contain important information about the actions of residents to ensure a
More informationOsceola County Department of Fire Rescue and Emergency Medical Services
St. Number Dir Street Name Street Type Inspected Time of Day to be Re-inspected Zip Code Occupancy Type Emergency Contact Phone (Inc. Area Code) Building Owner Building Owner Mailing Address Bldg. Owner
More informationGeneral needs sleeping accommodation
Colwick Woods Court Colwick Road Colwick, ttingham NG2 4BA At ttingham City Homes we want our residents to be assured that their homes are safe. We willingly accept our duty to comply with our statutory
More informationIndependent Living Scheme Fire Risk Assessment. Independent living sheltered residential accommodation and public library
Independent Living Scheme Fire Risk Assessment Strelley Court Strelley Road Strelley ttingham NG8 3BJ At ttingham City Homes we want our residents to be assured that their homes are safe. We willingly
More informationNirmal Chandra Sinha. Supposed to complete(dd/ MM/YYYY) Comments after Physical Inspection
Factory Name Address Fire Safety Follow up INTIMATE APPARELS LTD Karnaphuli EPZ, Plot no. 91-93, rth Patenga Date 05/20/2014 Date Report Received 11-August/15 Date of 1 st Follow-up 08-vember/15 Date of
More information161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures
161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures Contents 1.0 Introduction 2.0 Means of Escape in Case of Fire 3.0 Means for Giving Warning in Case of Fire 4.0 Means
More informationEQUIVALENT INITIAL FIRE SAFETY ASSESSMENT
EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT 171-181, Baizid Bostami Road Nasirabad I/A, Chittagong Chittagong The Alliance for Bangladesh Worker Safety Page 1/14 Introduction to the Report The following
More informationLow Location Lighting
Low Location Lighting system The spreading of smoke is one of the most dangerous consequences of a fire rendering evacuation difficult and in some cases impossible. Under these conditions, visibility is
More informationFire Risk Assessment Guide
Fire Risk Assessment Guide Thank you for your interest in the Fire Risk Assessment for your block. All of our blocks have had a recent Fire Risk Assessment in line with regulatory requirements and we are
More informationWater Mist and Heritage Buildings Case - St. Mark s Dome, Venice
Water Mist and Heritage Buildings Case - St. Mark s Dome, Venice By Nino Frisina Sales Director Marioff Italy IWMA Conference I Rome I 25 October 2017 Shutterstock.com AGENDA Background Case - St. Mark
More informationFire Risk Assessment (FRA) Checklist
Fire Risk Assessment (FRA) Checklist Assessed by: Job Title: Department/Location: Date Document Downloaded: Date of Assessment: Duty Holder Name: FRA. Description / Comments FHRA. 1. MANAGEMENT, PLANNING
More informationThe Physical Environment Portal: Module 5, LS Leadership
The Physical Environment Portal: Module 5, LS.02.01.10 - Leadership Fire Safety: Background Fire safety impacts both the lives of the occupants and the physical structures. In the early 1900 s many buildings
More information