POL-200-TS User Manual

Size: px
Start display at page:

Download "POL-200-TS User Manual"

Transcription

1 User Manual POL-200-TS ANALOGUE LOOP VERIFICATION TOOL 1/16

2 Security Information Several damage! Please, before to connect any external cable, ensure that loop cable has been disconnected from panel loop terminals and the panel is complete powered down. Check for the right terminal connections and that there is no external voltage between cables to be connected. Battery life maximum 3 years, check the manufacture year! Danger of explosion in case of inappropriate replacement of the battery! Battery waste disposal by manufacturer instruction! Caution! The warranty in case of damages is limited if the operation and installation instructions are not observed. The company is not liable for any consequential or incidental damages. This installation instruction must be read thoroughly before start mounting. Dissasembling: In accordance with the regulations 2002/96/EG (WEEE), after being disassembled, electrical and electronic equipment is taken back by the manufacturer for a proper disposal. Set Language POL-200-TS language menu. To change, select the option and the corresponding language. Restart the device. 2/16

3 Contents Page 1. Introduction Connection Multi-meter Loop Map Events recording Configuration Troubleshooting Technical Characteristics CE conformity /16

4 1. Introduction The POL-200-TS is a compact, graphic and intuitive hand-held tool (dimensions are 177mm x 97mm x 44mm) assists: Installer in commissioning and testing Notifier or Morley field loops before the configuring of the panel can start. Maintainer in the diagnosis and verification of the state of the installation and the connected field equipment, verifying the wiring map to detect the possible changes made over time. The six internal, 2500mA NiMH, rechargeable batteries provides the installer with sufficient capacity, up to 6 hours depending on the loop load. POL-200-TS is designed to be used only by trained personnel in order to properly interpretation the information read. Please note that POL-200-TS is a device designed to help you check the quality of the line and signal in your installation. POL-200-TS is not a fire protection equipment, it only provides the necessary information of support for the identification and solution of faults to a qualified technician. 4/16

5 2. Connecting Confirm that the loop wiring is correct: The POL-200-TS unit reports any short-circuit fault conditions in the loop (showing a lightning icon ), reverse polarity wiring (a diode icon ) and is also able to identify within seconds the total number of devices connected to the loop. The characteristics considered are for wiring in closed loop mode (panel output and back to it) The maximum resistance allowed from the OUTPUT end of the fire detection panel (or from POL-200-TS) to the INPUT in the fire detection panel is 40 ohms. Refer to the installation recommendations associated with the fire detection control center where you will connect the monitored loop with POL-200-TS. La siguiente tabla muestra los valores resistivos aproximados para los dos recommended loop cable types: Shielded/screen cable should only be connected to ground, GND, at one point inside the fire panel. The POL-200-TS allows the user to confirm that the shield is continuous, so it should be approximately twice (2x) and three (3x) times the resistance of the negative conductor. So, in case that the negative conductor has a: Capacitance between loop conductors so + and is below 0.5mF or 500nF Impedance between positive and cable shield (Infinite). 5/16

6 3. Multi-meter After the connection check that POL-200-TS has the correct load level, please note that batteries with an insufficient charge level can falsify the measurements. You will access the Multimeter function from the main screen. Verify that the line impedance conditions are adequate as described in the previous section. Then check for each voltage range, 0V, 5V and 24V, the voltages and consumption shown. Check for possible drifts, short circuits, faulty elements, connections or inadequate system devices or external to the system depending on the values obtained. The reading at 24v will provide a reference voltage drop in the loop Under the 5V reading should not have consumption, check the possible existence of derivations or inductions. 6/16

7 4. Loop The tool recognizes the sensors and modules on the loop before powering the fire alarm control panel (FACP). The POL-200-TS unit is compatible with the CLIP (Classic Loop Interface Protocol) with 99 sensors and 99 modules and the new Advanced or Opal protocol with up to 159 sensors and 159 modules. In the auto-programming menu, we will identify the number of detectors or modules that are connected in the loop identifying them according to their type: 7/16

8 CLIP PROTOCOL O Optical Sensor H or T Heat/Thermal sensor I ionization sensor M Multi-Sensor. Optical/ thermal P Pinnacle Laser L VIEW Laser S Smart Multi-criteria ADVANCED PROTOCOL For advanced protocol loops, POL-200-TS also identifies the following elements: S SMART 4 B Beam detectors P Indoor Manual Call Point M FAAST Aspiration unit Section of Modules - Symbols of identification by type: I or E Input Modules including Manual Call Points O or S Output modules R Output modules without End-of- Line (EOL) by default Relays Z Zone modules for conventional detectors 8/16

9 To select between CLIP and ADVANCED Protocol please access the configuration screen and in the button line select one of the two protocols available. Lower Case or Capital Letter: in case that in the auto learn a Lower case letter appears please confirm in the configuration that the correct protocol is selected between these difference options Notifier, Morley, System Sensor or Honeywell HBS. In case that in one address a device change the type ID or from lower case to capital letter, please check the wiring in this device as its answer is not correct. Possible reason is a defective device or noise due to interferences. Please also check that the device is not faulty or there is noise due to interference. A? Character in the ID type field can be indicative of a problem in the device or due to problems in the wiring line. A - character in ID type may be indicative of duplicate address. For each sampling POL-200-TS identifies the changes that have occurred since the previous sampling, for that, the type of ID that identifies each address will appear in red or black. The red color indicates that a change has occurred. To get more details about each of the elements, select them by clicking directly on them or with the help of the cursors and mark them by pressing the button. Holding down this button you will get the details of the selected item within the sampling table. The PWs value is for Honeywell technical team references, PW1 should be around 150 +/- 10% in Honeywell and Morley while around 300 +/- 10% for Notifier / System Sensor. Other values outside these range should be reported to Honeywell technical support for advice. 9/16

10 Select one of the items within the sampling table with the help of the arrows (arrows in the right margin of the screen) or by clicking on the screen. Press the button to access the advanced user information screen. From the self-programming menu and pressing the List button, the user can display a summary of installed elements. Clicking once more on the icon you will have access to a more detailed list of the devices of the loop, use the scroll keys located in the right side of the screen to move of 1 in 1 or in blocks of /16

11 5. Map To visually verify the wiring map of the loop you must follow the following instructions: In case the installer has correctly wired the isolators using the +IN, +OUT terminals in the B501AP or in the module terminals the POL-200-TS will activate the isolator to show in a graphic. POL -200-TS provides a device map for any of the protocols, CLIP or Advanced. Given the characteristics of each protocol, the information obtained may differ the location of each devices Remember that in CLIP protocol and multi-module devices, each input or output occupies one direction in the loop. For Advanced protocol only the main address will be visible. Note 1: For having the right mapping is required that the ISO terminals are properly wired and the devices support Advanced Protocol. Note 2: The device like the View FSL-751 or Pinnacle are only answering in CLIP so do not include an isolator to be activated from the POL-200-TS. 6. Events Recording You can register in a text file the values selected from the self-programming screen. Accessing the registration screen will display 3 registration options: Only selected items Full loop Maintenance 11/16

12 The first option requires previously performing a self-programming of the loop and marking the elements to register. To do this proceed as previously described, select the elements with the help of the cursors (arrows in the right margin of the screen) and press the button. Once the computers are selected and the only selected items register option is selected, the POL-200-TS will display the following screen: Register through the configuration option only the necessary information, consult with Honeywell s technical department or, if in doubt, select all the options. While logging is done, click the backspace icon to finish capturing data in the log file. It is recommended to use a short sampling time for a short period, even a single default read for stable loops, extending the sample time will result in a larger file size that will reduce the available space of the machine for future reports. The maintenance option will create a text file with the extension.mnt that can be edited with notepad or Word for later editing. NOTE. It is recommended that old maintenance and log files be removed from the folder in order to be able to generate new records. 12/16

13 7. Configuration In the configuration section, the user can change the date and time of the device in addition to changing the language. The lower CLIP icon allows you to select the two types of protocols available CLIP used by the Notifier ID50 / 60 and ID3000, HBS XLS80 or Morley DXc or Advanced by the Notifier Pearl. The Change Theme button allows us to change the background of the screen from white to black and vice versa. The About icon will indicate the software version of the computer, the Flash Format option should only be used if indicated by the Honeywell technical department. The QR icon will allow you to access with a Smartphone the latest online version of the computer. 13/16

14 8. Troubleshooting In case that this symbol appears in the right low corner a short-circuit between loop positive and negative is monitored. Please break the loop in sections to identify where the location of the short-circuit is. This symbol is reporting an inverse wiring fault. Please break the loop into sections to identify in which base the loop negative is incorrectly connected to the loop positive, or vice versa. h lower case: In case that in the auto-learn ALL the devices in the loop are shown with a lower case letter please check the protocol selected in the Configuration. It may be that the selected loop protocol, i.e. Morley, System Sensor or Honeywell HBS does not match the loop devices. Flashing the screen or the screen goes off: Check if the batteries loading level are adequate. Batteries may be damaged, replace. Device tags disappear or the question character appears: Verify that loop conditions meet Honeywell s requirements. Try replacing the device and check again. Check for possible noise on the line. Record the information and check the possibility of cycles of inappropriate behaviour, excessive current, etc. No devices appear Verify that you have not selected Ad protocol instead of CLIP Check that the loop is connected to the input, IN of the POL-200-TS device. There is no data recorded in my *.MNA, *.MNC and / or *.DAT files: Remove or delete old files, they are taking up the available memory space. 14/16

15 9. Technical Characteristics: Power supply: Autonomy: 230 Vac with 12 V charger (included). >6 h with baterías at 100% charge. Batteries: 6x AA 1.2V NiMH 2500mAh. Quick charge in 1h. Screen: Keypad: Dimensions: Color: Weight: 4.2 TFT 480 x 263 pixels (98x56mm) with colors. Dynamic capacitive touchpad. 97mm high x 177mm wide x 44mm deep (rubber protectors included). Black box with rubber protection in grey color. 550g (with batteries). POL-200-TS has an even power-off that can discharge the batteries if you do not use it for an extended period of time. Power ON/OFF button The package includes a USB cable type B to connect the unit to a PC to install a new version by copying it to the root folder in the POL-200-TS unit. Note. Autonomy. The batteries lifetime will depend on the output (sounder, flash, and strobes) activations, if the batteries are full charged and the installer is using the auto learn function the unit will provide up to 6 hours of autonomy. When the unit is switch of the current is very low below 250µA so the batteries will remain charge for days, anyway it will be recommended to full charge the unit before visit the site. Charge: 0 C to 40 C Discharge: 0ºC to 50ºC Storage: -20ºC to 30ºC Humidity: 65 ± 20% 15/16

16 10. CE conformity This document is a declaration that the products listed below conform to the essential protection requirements of the following European Directives: RoHS - Restrictions on the Use of Certain Hazardous Substances in Electrical and Electronic Equipment Directive 2011/65/EU Compliance with RoHS 2 - Product does not contain any hazardous substances above the limits designated in the RoHS Directive. Product falls within Category 9 - Monitoring and Control lnstruments The EMC Directive 2014/30/EU, by the application of the following EMC Standards: EN :2007 +A1: 2011 (Emissions) Electromagnetic compatibility (EMC) Generic emission standard for residential, commercial and light industrial environments. EN : A1: 2014 (lmmunity) EMC Product family standard: lmmunity requirements for components of fire, intruder and social alarm systems 16/16

17 Honeywell Life Safety Iberia C/Pau Vila Badalona Barcelona, Spain Tel.: Fax: POL-200-TS Diagnostic tool Ref. doc.: MN-DT-963_EN 20/06/ Honeywell International Inc.

Laptop / PC Programming Manual

Laptop / PC Programming Manual Laptop / PC Programming Manual Doc. # Fire PC Program rev B 01.07 This Document is property of Evax Systems, Inc. The Evax Fire Solutions Programmer Components 2 1.0 System Setup 4 1.1 Interface Setup

More information

INDEX 1- Introduction The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops The Control Panel 4 and 8 Loops...

INDEX 1- Introduction The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops The Control Panel 4 and 8 Loops... GUIDE MANUAL INDEX 1- Introduction...5...5...6 4- The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops...7 4.2- The Control Panel 4 and 8 Loops...9 5- Installation Guide...10 5.1- Pre-Installation

More information

Building Technologies. FDUL221 en Line tester operating instructions for electricians

Building Technologies. FDUL221 en Line tester operating instructions for electricians FDUL221 en Line tester operating instructions for electricians 1. Intended use The FDUL221 line tester is used to diagnose an addressed detector line in FDnet/C-NET. During diagnosis, the detector line

More information

E N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE ADDRESSABLE FAAST LT MODELS MI-FL2011EI, MI-FL2012EI AND MI-FL2022EI

E N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE ADDRESSABLE FAAST LT MODELS MI-FL2011EI, MI-FL2012EI AND MI-FL2022EI E N G L I S H FIRE ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE ADDRESSABLE FAAST LT MODELS MI-FL0EI, MI-FL0EI AND MI-FL0EI mm mm 0 mm DESCRIPTION The LT MI-FL0 Series is part of the Fire Alarm

More information

Intelligent addressable fire alarm control panel

Intelligent addressable fire alarm control panel Intelligent addressable fire alarm control panel Input current consumption: Panel rating: Batteries: Networking and Interfaces Panel to panel communication: Number of panels: Interface port: System capacity

More information

ZSC100 Gas Detection and Alarm System Controller

ZSC100 Gas Detection and Alarm System Controller ZSC100 Gas Detection and Alarm System Controller User Guide 1- Introduction... 3 1.1- General description... 3 1.2- Cautions and warnings... 3 2- Control panel... 4 2.1 Control panel overview... 4 2.2

More information

DDS-SSENSOR - INSTALLATION MANUAL. Installation Manual DDS-S SENSOR

DDS-SSENSOR - INSTALLATION MANUAL. Installation Manual DDS-S SENSOR Installation Manual DDS-S SENSOR 1 TRANSLATED DOCUMENT This manual has been compiled according to standard UNE-EN-ISO 12100. INSTALLATION MANUAL DDS-S SENSOR Read thoroughly all of these instructions before

More information

User Manual. Dryer Controller M720

User Manual. Dryer Controller M720 User Manual Dryer Controller M720 Hardware version 1.00 Software version 1.00 Preliminary version Manual M720 Dryer controller Page 1 of 42 Document history Preliminary version: - Created in April, 2009

More information

E N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE STAND-ALONE FAAST LT MODELS FL0111E FL0112E FL0122E. 367 mm.

E N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE STAND-ALONE FAAST LT MODELS FL0111E FL0112E FL0122E. 367 mm. E N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE STAND-ALONE FAAST LT MODELS FL0E FL0E FL0E mm mm 0 mm DESCRIPTION The LT FL0 Series is part of the Fire Alarm Aspiration

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd Product Data Sheet Mx-4000 Series User Manual MX-4100, MX-4200, MX-4400, Mx-4400/LE & Mx-4800 Fire Alarm Control Panels The operation and functions described in the manual are available from Software Versions

More information

THX-DL Data Logger USER & INSTALLATION MANUAL V

THX-DL Data Logger USER & INSTALLATION MANUAL V THX-DL Data Logger USER & INSTALLATION MANUAL V1.2012 www.thermomax-refrigeration.com Contents PRESENTATION Summary of Features 2 INSTALLATION Safety Precautions 4 THX Unit 4 Sensors 4 Alarm Relay 4 Power

More information

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL USER MANUAL 1 Table of Contents 1 SAFETY INFORMATION...3 1.1 SAFETY PRECAUTIONS DURING NORMAL OPERATION OF PANEL...3 1.3 BATTERY INFORMATION...3

More information

Dryer Controller M720

Dryer Controller M720 User Manual Dryer Controller M720 Hardware version 2.00 Software version 2.00 Manual M720 Dryer controller Page 1 of 60 Document history Preliminary version: - Created in April, 2009 Hardware Version 2.00,

More information

Operation Manual Fighter ProVision Software. Version: 0.0 Revision: 1

Operation Manual Fighter ProVision Software. Version: 0.0 Revision: 1 Operation Manual Fighter ProVision Software Version: 0.0 Revision: 1 TABLE OF CONTENTS 1. Introduction 5 2. Software Installation 5 3. PC Users 6 3.1 Introduction 6 3.2 Default Code 6 3.3 Edit PC User

More information

KM300 Carbon Monoxide Detection System Installation Manual

KM300 Carbon Monoxide Detection System Installation Manual GE Security KM300 Carbon Monoxide Detection System Installation Manual P/N 1068922 REV 2.0 16SEP09 Copyright Copyright 2009 GE Security, Inc. All rights reserved. This document may not be copied in whole

More information

Ref. 1067/024 Ref. 1067/032A Ref. 1067/052A

Ref. 1067/024 Ref. 1067/032A Ref. 1067/052A DS1067-062C Mod. 1067 LBT20063 REMOTE CONTROLLABLE ALARM CONTROL PANELS Ref. 1067/024 Ref. 1067/032A Ref. 1067/052A USER MANUAL TABLE OF CONTENTS INTRODUCTION... 6 1 CONTROL DEVICES... 7 1.1 1067/022 keypad

More information

ID50series. intelligent fire alarm panels

ID50series. intelligent fire alarm panels ID50series intelligent fire alarm panels features LPCB approved to EN54 parts 2 and 4 One loop capacity (99 sensors and 99 modules) 16 fire zones, 16 non fire zones Supports NOTIFIER advanced range of

More information

Siemens aspirating smoke detector (ASD) for the addressed FDnet/C-NET detector line or for standalone operation

Siemens aspirating smoke detector (ASD) for the addressed FDnet/C-NET detector line or for standalone operation Sinteso Cerberus PRO FDA241, FDA221 ASD Aspirating smoke detector Siemens aspirating smoke detector (ASD) for the addressed FDnet/C-NET detector line or for standalone operation Patented technology Early

More information

BSR Addressable Fire Detection control panel. Installation operation manual

BSR Addressable Fire Detection control panel. Installation operation manual BSR-1116 Addressable Fire Detection control panel Installation operation manual ATTENTION!!! READ THE MANUAL BEFORE THE INSTALLATION AND PAY ATTENTION TO PARAGRAPH 2.6.3 AND 2.6.4. Page 2 from 36 Contents

More information

intelligent fire alarm ID60series panels

intelligent fire alarm ID60series panels intelligent fire alarm ID60series panels features LPCB approved to EN54 Parts 2 and 4 One loop capacity (99 sensors and 99 modules) 16 fire zones, 16 non fire zones Supports advanced detection such as

More information

CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3

CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3 CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3 2.1 Electrical Specifications... 3 2.2 Communication Loop Parameters... 3 2.3 Dimensions...

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

REPEATER FS5200R INSTRUCTION MANUAL

REPEATER FS5200R INSTRUCTION MANUAL REPEATER FS5200R INSTRUCTION MANUAL Instruction Manual Page1 CONTENTS 1. Introduction... 3 2. Function... 3 3. Technical data... 3 4. Contents of delivery... 4 5. General information... 5 6. Duty Mode...

More information

ibox Modbus Server Gateway for the integration of Notifier ID3000 / ID3002 / ID60 / ID50 fire panels in Modbus enabled monitoring and control systems

ibox Modbus Server Gateway for the integration of Notifier ID3000 / ID3002 / ID60 / ID50 fire panels in Modbus enabled monitoring and control systems Honeywell Life Safety Iberia C/Pau Vila 15-19; 08911 Badalona Barcelona T. 902 03 05 45; Internacional:+34932424236 www.honeywelllifesafety.es infohlsiberia@honeywell.com ibox Modbus Server Gateway for

More information

rvm4c Installation Guide Remote Video Module

rvm4c Installation Guide Remote Video Module rvm4c EN Installation Guide Remote Video Module rvm4c Installation Guide Installation Diagrams EN 2 Installation Diagrams for the Transmitting Unit rvm4c Installation Guide Basic Hardware Installation

More information

The ID51 & ID52 can be upgraded to 2 loops without the need to change back box. FEATURES. Intelligent Features

The ID51 & ID52 can be upgraded to 2 loops without the need to change back box. FEATURES. Intelligent Features 990-052, Issue 6 20 March 2006 ID50 Series Single Loop Intelligent Fire Alarm Panels Section: Intelligent Fire Alarm Panels GENERAL The NOTIFIER ID50 series single loop intelligent fire alarm panels, has

More information

GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual

GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL Installation and Operation Manual 2 GG-2 Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified

More information

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide System Reset Trou ble Silence Ala rm Silence Manual Ala rm ENTER NO YES Letters Numb ers Keyword Radionics System Reset Trouble Silence Alarm Silence Manual Alarm ENTER NO YES Le ters Numbers Keyw ord

More information

QUICKFIT INSTALL HOOK-UP SHEET FOR ESL KIT REV 1.17 OP

QUICKFIT INSTALL HOOK-UP SHEET FOR ESL KIT REV 1.17 OP QUICKFIT INSTALL HOOK-UP SHEET FOR ESL KIT REV 1.17 OP PROGRAMMING STARTS Entering Installer mode If you want to get into program mode press followed by your installer code, default set to 000000

More information

U ser's Guide PC6010

U ser's Guide PC6010 User's Guide PC6010 Quick Reference Guide This manual is for Basic and Advanced users. Each of these types of user can access a different set of functions. The and symbols next to the title of each procedure

More information

DigiAir QUICK GUIDE & INSTRUCTION MANUAL

DigiAir QUICK GUIDE & INSTRUCTION MANUAL DigiAir QUICK GUIDE & INSTRUCTION MANUAL The most trusted brand in Alarm Signalling www.csldual.com @CSLDualCom CSL DualCom Limited Figure 1 - DigiAir Yellow Comms LED Red Fault LED Yellow Service LED

More information

FX FIRE DETECTION SYSTEM

FX FIRE DETECTION SYSTEM FX FIRE DETECTION SYSTEM Installation and commissioning manual Read this manual carefully before installation and commissioning! Installation and commissioning must be performed according to this manual.

More information

ZXSe Range Data Sheet

ZXSe Range Data Sheet ZXSe Range Data Sheet Analogue addressable fire alarm control panel Product Overview The ZXSe range of analogue addressable fire alarm control panels have been designed and constructed around proven and

More information

Installation and operation manual DPC200 - DIFFERENTIAL PRESSURE CONTROLLER. Low pressure with PI-control-mode

Installation and operation manual DPC200 - DIFFERENTIAL PRESSURE CONTROLLER. Low pressure with PI-control-mode Installation and operation manual DPC200 - DIFFERENTIAL PRESSURE CONTROLLER Low pressure with PI-control-mode Manufacturer: Phone: Fax: E-Mail: Website: Issue: Doc.-no.: Arthur Grillo GmbH Am Sandbach

More information

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel INSTALLATION, OPERATION AND MAINTENANCE MANUAL Version: CN-PM-1000.VER1.1-12/2012 EN54 INFORMATION In accordance with EN 54-2 clause 13.7, the maximum

More information

KFP-CF Series Operation Manual

KFP-CF Series Operation Manual KFP-CF Series Operation Manual P/N 501-415103-2-31 REV 03.10 ISS 13NOV13 Copyright Trademarks and patents Manufacturer Version Certification European Union directives Contact information 2013 UTC Fire

More information

FEC403EN Installation Manual

FEC403EN Installation Manual FEC403EN Installation Manual P/N 10-4101-501-2FC1-01 ISS 22JAN15 Copyright Trademarks and patents Manufacturer 2015 UTC Fire & Security. All rights reserved. The FEC403EN name and logo are trademarks of

More information

Analogue Addressable Fire Panels FP1500. Manual for Installation, Configuration and Commissioning

Analogue Addressable Fire Panels FP1500. Manual for Installation, Configuration and Commissioning Analogue Addressable Fire Panels FP1500 Manual for Installation, Configuration and Commissioning Version 2.1 / November 2003 Aritech is a GE Interlogix brand. http://www.geindustrial.com/ge-interlogix/emea

More information

Infrared Thermometer

Infrared Thermometer 572-2 Infrared Thermometer PN 4307046 March 2013, Rev. 1, 08/13 2013 Fluke Corporation. All rights reserved. Specifications are subject to change without notice. All product names are trademarks of their

More information

Security Alarm Systems

Security Alarm Systems eclipse Security Alarm Systems Contents Introduction 2 System Configuration 3 Control Panels 4 Remote Keypads & Expanders 5 Communication Modules 6 Upload/Download 6 Specifications 7 Introduction Zeta

More information

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

Syncro AS. Analogue Addressable Fire Control Panel. User Manual Syncro AS Analogue Addressable Fire Control Panel User Manual Man-1100 Issue 02 Nov. 2008 Index Section Page 1. Introduction...3 2. Safety...3 3. Panel Controls...4 3.1 Access Level 1...4 3.2 Access Level

More information

ZP2 Series Operation Manual

ZP2 Series Operation Manual ZP2 Series Operation Manual P/N 501-405203-2-31 REV 03.10 ISS 07NOV13 Copyright Trademarks and patents Manufacturer Version Certification European Union directives Contact information 2013 UTC Fire & Security.

More information

user manual Document No , Revision 03 November 2015

user manual Document No , Revision 03 November 2015 user manual Document No. 996-202-600-3, Revision 03 November 2015 Contents 1 Introduction...1 1.1 Notice...1 1.2 Models...1 2 User Control Levels...2 2.1 Level Definition...2 2.2 User Passwords...2 3 Controls

More information

Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual

Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual Revision 4/01.17 Contents 1. Introduction... 6 2. Terminology... 6 3. Function... 8 4. Technical data... 8 4.1. Physical configuration...

More information

ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL

ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL PRODUCT Specification FEATURES Designed To Meet The Requirements Of EN54 Expandable From 1 To 5 Loops As Standard A Variety Of Networking Options

More information

Accenta/Optima. User Guide. UK Security Panels. Servicing Organisation (Installer) name: Telephone Number: Date of Installation: Account Number:

Accenta/Optima. User Guide. UK Security Panels. Servicing Organisation (Installer) name: Telephone Number: Date of Installation: Account Number: Accenta/Optima User Guide ZONE 1 2 3 4 5 6 7 8 9 Chime Omit Prog PA 0 1 2 3 4 5 6 7 8 9 CHIME OMIT RESET PROG SET Accenta + TA PA DAY POWER PA! " # $ % & 0 1 2 3 5 6 7 8 Chime Omit Reset Prog 4 9 Set PA

More information

SCAN200E USER S MANUAL

SCAN200E USER S MANUAL SCAN200E USER S MANUAL Code No. 2071 1052 rev. 1.4 Code No. 2071 1052 Rev. 1.4 Page 2/16 SCAN200E User s Manual Foreword This manual is for SCAN200E Controller running software version 2.03 or later. We

More information

1 INTRODUCTION NOTICE WARNINGS AND CAUTIONS NATIONAL APPROVALS EN54 INFORMATION UNPACKING...

1 INTRODUCTION NOTICE WARNINGS AND CAUTIONS NATIONAL APPROVALS EN54 INFORMATION UNPACKING... ZX Fire Alarm Control Panels MORLEY-IAS Table of Contents 1 INTRODUCTION...1 1.1 NOTICE...1 1.2 WARNINGS AND CAUTIONS...1 1.3 NATIONAL APPROVALS...2 1.4 EN54 INFORMATION...2 2 UNPACKING...4 3 INSTALLATION...5

More information

Halton SAFE / 7.14 user guide and installation instructions

Halton SAFE / 7.14 user guide and installation instructions Halton SAFE / 7.14 user guide and installation instructions VERIFIED SOLUTIONS BY H A LTO N Enabling Wellbeing Table of contents 1 System description 3 2 User Accounts 4 3 Main menu 7 3.1 Main menu - Change

More information

SC-F3G User Manual 1.0

SC-F3G User Manual 1.0 SC-F3G User Manual 1.0 Table of Contents 1. Introduction... 3 2. Functions... 3 3. Features... 3 4. Package Contents... 3 5. Device Configuration... 4 6. Status LED signals... 5 7. Before You Start...

More information

LZR -I30. max. detection range of 30 ft x 30 ft LASER SCANNERS FOR INDUSTRIAL DOORS LZR-I Page 1 of 12

LZR -I30. max. detection range of 30 ft x 30 ft LASER SCANNERS FOR INDUSTRIAL DOORS LZR-I Page 1 of 12 EN LZR -I30 LASER SCANNERS FOR INDUSTRIAL DOORS max. detection range of 30 ft x 30 ft 75.5667.07 LZR-I30 0509 Page of SAFETY The device contains IR and visible laser diodes. IR laser: wavelength 905nm;

More information

Operations Manual TS400. Test Station for G450/G460 Gas Detector

Operations Manual TS400. Test Station for G450/G460 Gas Detector TS400 Test Station for G450/G460 Gas Detector Operations Manual 1194 Oak Valley Dr, Ste 20, Ann Arbor MI 48108 USA (800) 959-0329 (734) 769-0573 www.goodforgas.com GfG Products for Increased Safety Congratulations

More information

PodView Level Indicator LI40 Series Manual

PodView Level Indicator LI40 Series Manual PodView Level Indicator LI40 Series Manual Flowline Inc. 10500 Humbolt Street Los Alamitos, CA 90720 Tel: (562) 598 3015 Fax: (562) 431 8507 www.flowline.com Rev A MN204260 1 of 16 INTRODUCTION / TABLE

More information

64 Max IR Thermometer

64 Max IR Thermometer 64 Max IR Thermometer Users Manual January 2017 2017 Fluke Corporation. All rights reserved. Specifications are subject to change without notice. All product names are trademarks of their respective companies.

More information

Interface Modules for SENTRI

Interface Modules for SENTRI EQUIPMENT INTERFACED Data and Installation Interface s for SENTRI Low voltage (LV) / SEN-INT-INPUT 1- Interface (low voltage) SEN-INT-OUTPUT 1- & 1- Interface (low voltage) SEN-INT-4IO # 4- / Interface

More information

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117 Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel Revision E 61117 CAUTION: (Read This First) This panel has been designed to make it nearly bullet proof to mistakes made when wiring

More information

LZR -H110. LASER SCANNER FOR BARRIERS & GATES with max. detection range of 5.0 m x 6.5 m (16.5 ft x21 ft) User s Guide

LZR -H110. LASER SCANNER FOR BARRIERS & GATES with max. detection range of 5.0 m x 6.5 m (16.5 ft x21 ft) User s Guide EN LZR -H110 LASER SCANNER FOR BARRIERS & GATES with max. detection range of 5.0 m x 6.5 m (16.5 ft x21 ft) User s Guide 75.5897.02 LZR-H110 20170821 Page 1 of 12 SAFETY The device contains IR and visible

More information

Static Pressure Control

Static Pressure Control The (model SPC-2) is a fully programmable controller that provides extensive flexibility for your curtain or awning control needs. The SPC-2 automatically controls the pressure in a room by operating a

More information

Infrared Thermometer. Getting Started

Infrared Thermometer. Getting Started 572-2 Infrared Thermometer Getting Started PN 4307046 March 2013 2013 Fluke Corporation. All rights reserved. Specifications are subject to change without notice. All product names are trademarks of their

More information

GASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL

GASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL GASGUARDIAN 2 3 2-Channel Controller OPERATING & INSTALLATION MANUAL GasGuardian 2 3 Operating and Installation Manual Table of Contents General description.... 3 Installation. 3 Locating the GasGuardian-2..

More information

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2 Architectural & Engineering Specifications Control Panel 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality assurance...

More information

EWR2 WIRELESS SIGNAL REPEATER

EWR2 WIRELESS SIGNAL REPEATER SIGNAL REPEATER User manual v1.0 Compatible with: ESIM364 Ver.02.07.11 and up EPIR3 Ver.01.01.00 and up EWP1 Ver.16 and up EKB3W Ver.8 and up EW1 Ver.33 and up EWS1 Ver.16 and up EWD1 Ver.19 and up EWK1

More information

MX43. Analog and digital controller. 4 or 8 lines / 16 to 32 detectors max. Highly versatile controller. Cost savings on wiring installation

MX43. Analog and digital controller. 4 or 8 lines / 16 to 32 detectors max. Highly versatile controller. Cost savings on wiring installation Gas Detection Control Panel MX Analog and digital controller or 8 lines / 6 to s max Highly versatile controller Cost savings on wiring installation The Fixed Gas Detection People www.oldhamgas.com an

More information

NFS Supra / VSN-2Plus / ESS-2Plus Conventional Fire Alarm Control Panel. Installation and Operating Manual

NFS Supra / VSN-2Plus / ESS-2Plus Conventional Fire Alarm Control Panel. Installation and Operating Manual / VSN-2Plus / ESS-2Plus Conventional Fire Alarm Control Panel Installation and Operating Manual HLSI-MN-025-I v.05 April 2015 Note: This manual is valid for the following control panel models: NFS-Supra

More information

ViewMatrix. Software for Online Monitoring & Control of Matrix2000 Conventional Fire Alarm Panels. Version: 2.0 Revision: 0.1

ViewMatrix. Software for Online Monitoring & Control of Matrix2000 Conventional Fire Alarm Panels. Version: 2.0 Revision: 0.1 ViewMatrix Software for Online Monitoring & Control of Matrix2000 Conventional Fire Alarm Panels Version: 2.0 Revision: 0.1 CONTENTS 1. Introduction...3 2. Keyboard...5 2.1 POWER indication - Normal Operation...5

More information

End To End Optical Beam Smoke Detector. Additional Information

End To End Optical Beam Smoke Detector. Additional Information End To End Optical Beam Smoke Detector Additional Information EN 1. Multiple Zone Wiring When using more than one System Controller on a single zone of a conventional Fire Control Panel (FCP), it is important

More information

Advanced FireAlarm Panel 1-4Loop

Advanced FireAlarm Panel 1-4Loop Advanced FireAlarm Panel 1-4Loop Advanced Technologies Advanced Electronics Ltd IP Gateway Monitoring and interrogation via the internet Password protected multiple user permissions Event notification

More information

Watchguard WGAP864 User Manual

Watchguard WGAP864 User Manual Watchguard WGAP864 User Manual v1.0 Issued September 2016 1 2 Table of Contents Glossary... 5 1. Introduction to your Watchguard WGAP864... 6 2. Before Operating your Alarm System... 6 3. Understanding

More information

Digital Electronic Thermostat With RF

Digital Electronic Thermostat With RF RT300RF Manual:89 6/7/10 12:52 Page 1 Digital Electronic Thermostat With RF Instruction Manual Model No RT300RF 2 RT300RF Manual:89 6/7/10 12:52 Page 2 2 RT300RF INSTRUCTION MANUAL RT300RF Manual:89 6/7/10

More information

IMPORTANT. PLEASE NOTE: The infrared beam path MUST be kept clear of obstructions at all times!

IMPORTANT. PLEASE NOTE: The infrared beam path MUST be kept clear of obstructions at all times! USER GUIDE English IMPORTANT PLEASE NOTE: The infrared beam path MUST be kept clear of obstructions at all times! Failure to comply may result in the Detector initiating a Fire or Fault signal. Contents

More information

1. LCD 2. radar antenna (narrow field) 3. radar antenna (wide field) 4. AIR-curtain width adjustment 5. AIR-lenses

1. LCD 2. radar antenna (narrow field) 3. radar antenna (wide field) 4. AIR-curtain width adjustment 5. AIR-lenses IXIO-DT INDUSTRIAL Activation & safety sensor for industrial doors (US Version) ENGLISH DESCRIPTION 3 4 5 6 7 8 9 ACCESSORIES. LCD. radar antenna (narrow field) 3. radar antenna (wide field) 4. AIR-curtain

More information

6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL

6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL 6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL USER MANUAL Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0)

More information

Added password for IP setup page : Password must be in IP format!

Added password for IP setup page : Password must be in IP format! NETWORK POWER MONITOR Release : 21 August 2014 Hardware Version : Version 7 Firmware version 1.00 PC Application Software : Version (latest)...2 Added password for IP setup page : Password must be in IP

More information

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL Document No...G108WO1.DOC Serial No... Issue Date...17 th SEPTEMBER 1999 Software Version...1.4 APPROVED TO: NZS 4512:1997 AS/NZS 3548:1992 Fire Alarm

More information

Document No Issue 4 user manual

Document No Issue 4 user manual DX Document No. 996-148-000-4 Issue 4 user manual Dimension Series Table of Contents 1 INTRODUCTION... 5 1.1 NOTICE... 5 1.2 MODELS... 5 1.3 WARNINGS AND CAUTIONS... 7 1.4 NATIONAL APPROVALS... 7 1.5 EN54

More information

Segment design & and Bus Diagnostics

Segment design & and Bus Diagnostics Segment design & and Bus Diagnostics Arasu Thanigai Business Development Manager Pepperl+Fuchs Pte Ltd, Singapore On behalf of FF End user Council Taiwan 1 Taiwan FF Seminar Part1 - Segment design & Verification

More information

LZR -I100/ -I110. LASER SCANNERS for industrial doors. User s Guide for product version 0600 and more

LZR -I100/ -I110. LASER SCANNERS for industrial doors. User s Guide for product version 0600 and more EN LZR -I00/ -I0 LASER SCANNERS for industrial doors I00: max. detection range of 9.9 m x 9.9 m I0: max. detection range of 5.0 m x 5.0 m User s Guide for product version 0600 and more SAFETY The device

More information

Electronic Thermostat With RF

Electronic Thermostat With RF Electronic Thermostat With RF Model No: ERT20RF INSTRUCTION MANUAL 2 ERT20RF PRODUCT COMPLIANCE SALUS Controls Plc hereby declares that this product is in compliance with Directives 2004/108/EC, 2006/95/EEC

More information

FIRERAY 5000 range USER GUIDE

FIRERAY 5000 range USER GUIDE FIRERAY 5000 range USER GUIDE 0044-003-04 IMPORTANT PLEASE NOTE: The beam path MUST be kept clear of obstructions at all times! Failure to comply may result in the Detector initiating a Fire or Fault signal.

More information

SmartDial. Wireless. User Manual. -en_gb language A004. Document in original

SmartDial. Wireless. User Manual. -en_gb language A004. Document in original Wireless Document in original -en_gb language 2017-03-20 A004 Contents 1 Declaration of Conformity... 1 2 Product description... 3 3 Guidelines for installation... 4 4 Operation... 5 5 Interface Description...

More information

For Complete Fire and Gas Solutions

For Complete Fire and Gas Solutions Industrial Fire For Complete Fire and Gas Solutions 2 The Total Package What do you need from an integrated fire and gas system? In industrial fire and gas environments it s important to have a reliable

More information

WIDE SEARCH AREA HAND-HELD METAL DETECTION SET

WIDE SEARCH AREA HAND-HELD METAL DETECTION SET NSN: 6665150114797 WIDE SEARCH AREA HAND-HELD METAL DETECTION SET Wide Search Area for Faster and Accurate Screening Operations Search operations allowed even in close proximity of metal reinforced floors

More information

MX43. Analog and digital controller. 4 or 8 lines / 16 to 32 detectors max. Highly versatile controller. SIL1 reliability. Gas Detection Control Panel

MX43. Analog and digital controller. 4 or 8 lines / 16 to 32 detectors max. Highly versatile controller. SIL1 reliability. Gas Detection Control Panel Gas Detection Control Panel MX Analog and digital controller or 8 lines / 6 to s max Highly versatile controller SIL reliability Fixed The Fixed Gas Gas Detection Detection Experts People www.oldhamgas.com

More information

Alarm Controller Fire and CO

Alarm Controller Fire and CO Alarm Controller Fire and CO Model: Ei450 Instruction Manual Read and retain carefully for as long as the product is being used. It contains vital information on the operation and installation of your

More information

CSP-204 CSP-208 CSP-104 CSP-108

CSP-204 CSP-208 CSP-104 CSP-108 Fire Alarm Control Panel CSP-204 CSP-208 CSP-104 CSP-108 Operation manual Firmware version 1.1 csp-x_o_en 06/15 SATEL sp. z o.o. ul. Budowlanych 66 80-298 Gdańsk POLAND tel. 58 320 94 00 www.satel.eu CONTENTS

More information

System Manual W A R N I N G. PC6O1O Software Version 2.1

System Manual W A R N I N G. PC6O1O Software Version 2.1 System Manual W A R N I N G This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual

More information

OOH740, OOHC740. Cerberus PRO. Automatic fire detectors

OOH740, OOHC740. Cerberus PRO. Automatic fire detectors Cerberus PRO OOH740, OOHC740 Automatic fire detectors ASAtechnology For the automatically addressable detector bus C-NET collective / conventional (OOH740 only) Signal processing with ASAtechnology Event-controlled

More information

Laser Distance Sensor Type M Analog-Output

Laser Distance Sensor Type M Analog-Output Laser Distance Sensor Type M Analog-Output Operating Manual Version 2.3, May 2009 ELAG Elektronik AG l Stegackerstrasse 14 l CH-8409 Winterthur Contents 1. Safety 1.1 Laser safety 1.2 Electrical safety

More information

LZR -WIDESCAN OPENING, PRESENCE & SAFETY SENSOR FOR INDUSTRIAL DOORS

LZR -WIDESCAN OPENING, PRESENCE & SAFETY SENSOR FOR INDUSTRIAL DOORS LZR -WIDESCAN EN OPENING, PRESENCE & SAFETY SENSOR FOR INDUSTRIAL DOORS User s Guide for product version 0300 and higher See product label for serial number INSTALLATION & MAINTENANCE & TIPS Avoid extreme

More information

LINEAR HEAT DETECTION CABLE DURÁN-SAFE

LINEAR HEAT DETECTION CABLE DURÁN-SAFE LINEAR HEAT DETECTION CABLE DURÁN-SAFE Installation & User Manual 2018 DURAN ELECTRONICA S.L. - All rights reserved www.duranelectronica.com I-manSAFECABLE-v05 TABLE OF CONTENTS Pages 1. INTRODUCTION...

More information

Danfoss gas detection units

Danfoss gas detection units Data sheet Danfoss gas detection units Types GD Premium, Premium+, Premium Duplex, Premium Remote, Premium Flex and Premium Uptime The Premium line gas detection units are used for monitoring and warning

More information

icontrol OpenHome Converge Panel Interface Module Installation Guide Congratulations on purchasing your Panel Interface module.

icontrol OpenHome Converge Panel Interface Module Installation Guide Congratulations on purchasing your Panel Interface module. icontrol OpenHome Converge Panel Interface Module Installation Guide Congratulations on purchasing your Panel Interface module. The icontrol Networks, Inc. OpenHome Converge Panel Interface Module (PIM)

More information

Manual & Technical Documentation V1.1

Manual & Technical Documentation V1.1 Manual & Technical Documentation V1.1 tado Smart Thermostat tado Extension Kit ENGLISH Content Product Packages Compatibility Intelligence & Security Functions Smart Thermostat Usage Menu Structure Special

More information

Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual

Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual Revision 6/01.17 Contents 1. Introduction... 6 2. Terminology... 6 3. Function... 8 4. Technical data... 8 4.1. Physical configuration...

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd full installation, commissioning and operating manuals can be downloaded from www.haes-systems.co.uk combined addressable / conventional fire alarm control panel User Guide Approved Document No. MFBU-04

More information

FC330A-ECO Auto-addressing analogue 1-Loop fire detection panel

FC330A-ECO Auto-addressing analogue 1-Loop fire detection panel FC330A-ECO Auto-addressing analogue 1-Loop fire detection panel Synova TM Commissioning in no time thanks to automatic address allocation Auto-addressing makes setting dip switches unnecessary Automatic

More information

ZXSe Range. Fire Safety. Analogue addressable fire alarm control panel KEY FEATURES. Panel Features

ZXSe Range. Fire Safety. Analogue addressable fire alarm control panel KEY FEATURES. Panel Features Fire Safety ZXSe Range Analogue addressable fire alarm control panel The ZXSe range of analogue addressable fire alarm control panels have been designed and constructed around proven and reliable microprocessor

More information

FX NET FIRE DETECTION SYSTEM Installation and commissioning manual

FX NET FIRE DETECTION SYSTEM Installation and commissioning manual FX NET FIRE DETECTION SYSTEM Installation and commissioning manual Read this manual carefully before installation and commissioning! Installation and commissioning must be performed according to this manual.

More information

THANK YOU FOR VOTING TEXECOM INSTALLATION MANUAL. External Sounder & Strobe Unit

THANK YOU FOR VOTING TEXECOM INSTALLATION MANUAL. External Sounder & Strobe Unit 400 THANK YOU FOR VOTING TEXECOM INSTALLATION MANUAL External Sounder & Strobe Unit Contents Section Page 1. Installation 3 1.1 Mounting the Unit 3 1.2 Patented Engineer Hold-Off Mode 3 1.3 Installing

More information

ZITON RADIO LOOP MODULE

ZITON RADIO LOOP MODULE ZITON RADIO LOOP MODULE PROGRAMMING MANUAL Table of Contents Section Page No 1.0 INTRODUCTION...3 1.1 System Design...3 1.2 Handling Precautions...3 1.3 Packaging:...3 2.0 MENU STRUCTURE...4 2.1 Menu Structure

More information