1 Effective Date: 11/01/02 Purpose: MECKLENBURG COUNTY To establish a set of guidelines for performance testing of all newly installed or upgraded fire alarm systems in order to ensure that all devices and related equipment (i.e. additional fire suppression and extinguishing systems) meet the minimum requirements of NFPA 72. Policy: A. Plans and specifications, or shop drawings, for automatic and manual fire protective signaling systems shall be submitted and approved by the Mecklenburg County Fire Marshal s Office Plans Review Section prior to the installation of equipment and wiring. The shop drawings shall include at a minimum: 1. Floor plan(s). 2. Locations of all alarm initiation and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation equipment. 5. Power connection. 6. Battery calculations 7. Conductor types and sizes. 8. Voltage drops calculations. 9. Manufacturer, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. B. Upon installation of all fire alarm systems and any related equipment, the system(s) shall be subject to an acceptance test and witnessed by the Fire Marshal. C. Upon installation and testing of the system(s), test certificates meeting the minimum requirements of the applicable NFPA standards shall be provided to the inspector at his or her request. D. All systems and related fire suppression equipment shall be fully installed, tested and confirmed operable prior to a Certificate of Occupancy being issued. E. The following requirements are ones that meet the minimum requirements of NFPA 72 and the North Carolina Fire Code and are provided as a guide in conducting the required acceptance test(s):
2 1. Manual Fire Alarm Boxes a. Manual fire alarm boxes shall be located not more than 5 feet from the entrance to each exit. Additional manual fire alarm boxes shall be located so that travel distance to the nearest box does not exceed 200 feet measured horizontally on the same floor. Exception: Manual fire alarm boxes shall not be required in Group E occupancies where the building is equipped throughout with an approved automatic sprinkler system, the notification appliances will activate on sprinkler water flow and manual activation is provided from a normally occupied location. b. The height of the manual fire alarm boxes shall be a minimum of 42 inches and a maximum of 48 inches measured vertically, from the floor level to the activating handle or lever of the box. c. Manual fire alarm boxes shall be red in color. d. Where fire alarm systems are not monitored by a supervising station, an approved permanent sign on or beside the box shall be installed that reads: WHEN ALARM SOUNDS - CALL FIRE DEPARTMENT. e. The fire official can require the installation of listed manual fire alarm box protective covers to prevent malicious false alarms or to provide protection from physical damage. 2. Power Supply and Wiring a. Primary and secondary power supply and wiring shall comply with the requirements of the ICC Electrical Code and NFPA Zones a. Each floor shall be zoned separately and a zone shall not exceed 22, square feet. The length of any zone shall not exceed 300 feet in any direction. Exception: Automatic sprinkler system zones shall not exceed the area permitted by NFPA 13. b. A zoning indicator panel and the associated controls shall be provided in an approved location. The visual zone indication shall lock in until the system is reset and shall not be canceled by the operation of an audible-alarm silencing switch. c. The primary purpose of the fire alarm system annunciation is to enable responding personnel to identify the location of a fire quickly and accurately and to indicate the status of emergency equipment or fire safety functions that might affect the safety of occupants in a fire situation. All required annunciation means shall be readily accessible to responding personnel and shall be located as required by the fire official to facilitate an efficient response to the fire situation.
3 d. In buildings that have floors located more than 75 feet above the lowest level of fire department vehicle access that are occupied for human occupancy, a separate zone by floor shall be provided for all of the following types of alarm-initiating devices where provided: Smoke detectors. Sprinkler water flow devices. Manual fire alarm boxes. Other types of automatic fire detection devices or suppression systems. 4. Alarm Notification Appliances. a. Visible alarm notification appliances shall be provided in public and common areas. b. Group I-1 and R-1 sleeping accommodations shall be provided with a visible alarm notification appliance, activated by both the in-room smoke alarm and the building fire alarm system. c. Wall-mounted appliances shall have their tops above the finished floors at heights of not less than 90 inches and below the finished ceilings at heights of not less than 6 inches. Wall-mounted appliances shall be mounted such that the entire lens is not less than 80 inches and not greater than 96 inches above the finished floor. d. Visible notification appliances shall be located not more than 15 feet from the end of the corridor with a separation not greater than 100 feet between appliances. If there is an interruption of the concentrated viewing path, such as a fire door, an elevation change, or any other obstruction, the area shall be treated as a separate corridor. e. In corridors where there are more than two visible notification appliances in any field of view, they shall be spaced a minimum of 55 feet from each other or they shall flash in synchronization. 5. Audible Alarms a. Audible alarm notification appliances shall be provided and sound a distinctive sound that is not to be used for any purpose other than that of a fire alarm. The use of the distinctive three-pulse temporal pattern fire alarm evacuation signal required by NFPA 72 became effective July 1, 1996, for new systems installed after that date. The audible alarm notification appliances shall provide a sound pressure level of 15 decibels (dba) above the average ambient sound level or 5 dba above the maximum sound level having a duration of at least 60 seconds, whichever is greater, in every occupied space within the building. The minimum sound pressure levels
4 occupancies. MECKLENBURG COUNTY shall be: 70 dba in occupancies in Groups R and I-1; 90 dba in mechanical equipment rooms; and 60 dba in other occupancies. The maximum sound pressure level for audible alarm notification appliances shall be 120 dba at the minimum hearing distance from the audible appliance. Where the average ambient noise is greater than 105 dba, visible alarm notification appliances shall be provided in accordance with NFPA72 and audible alarm notification appliances shall not be required. Exception: Visible alarm notification appliances shall be allowed in lieu of audible alarm notification appliances in critical care areas of Group I-2 b. Where audible appliances are installed to provide signals for sleeping areas, they shall have a sound level of at least 15 dba above the average ambient sound level or 5 dba above the maximum sound level having a duration of at least 60 seconds or a sound level of at least 70 dba, whichever is greater, measured at the pillow level in the occupiable area. If any barrier, such as a door, curtain, or retractable partition, is located between the notification appliance and the pillow, the sound pressure level shall be measured with the barrier placed between the appliance and the pillow. c. Actuation of alarm notification appliances or emergency voice communications and annunciation at the protected premises shall occur within 10 seconds after the activation of an initiating device. d. Trouble signals required to indicate at the protected premises shall be indicated by distinctive audible signals. These trouble signals shall be distinctive from alarm signals and shall be located in an area where it is likely to be heard. 6. Smoke Detectors. a. Spot-type smoke detectors shall be located on the ceiling not less than 4 inches from a sidewall to the near edge or, if on a sidewall, between 4 and 12 inches down from the ceiling to the top of the detector. b. On smooth ceilings, spacing of 30 feet shall be permitted. c. Smoke detectors shall not be located directly in the air stream of supply registers. In spaces served by air-handling systems, detectors shall not be located where airflow prevents operation of the detectors. d. An approved, single-station smoke alarm shall be installed in every guest room and every living area and sleeping room within a guest suite in new hotels and dormitories, in every sleeping room in lodges or rooming houses, and inside and outside every sleeping area in the immediate vicinity of the bedrooms and on all levels of the dwelling unit including basements in new apartment buildings.
5 Exception: In apartment buildings protected throughout by an approved supervised automatic sprinkler system, the smoke alarms are not required inside the sleeping rooms. e. In new construction where two or more smoke alarms are required within a living unit, suite of rooms, or similar area, they shall be arranged so that operation of any smoke alarm shall cause the alarm in all smoke alarms within the living unit, suite of rooms or similar area to sound. f. The alarms shall sound only within an individual living unit, suite of rooms or similar area and shall not actuate the building fire alarm system. g. Duct smoke detectors shall be connected to the building s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Exceptions: The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building s alarm notification appliances. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble. h. System-type smoke detectors or other automatic fire detection located in elevator lobbies, elevator hoist ways and elevator machine rooms used to initiate fire fighter s service recall shall be connected to the building fire alarm system. A lobby smoke detector shall be located on the ceiling within 21 feet of the centerline of each elevator door within the elevator bank under control of the detector. i. Smoke detectors shall not be installed in elevator hoist ways. Exception: Where the top of the elevator hoist way is protected by automatic sprinklers or where a smoke detector is installed to activate the elevator hoist way smoke relief equipment 7. Door Release Service and Unlocking Devices. a. Magnetic door holders that allow doors to close upon loss of operating power shall not be required to have a secondary power source. b. Any device or system intended to actuate the locking or unlocking of exits shall be connected to the fire alarm system serving the protected premises. c. All exits connected shall unlock upon receipt of any fire alarm signal by means of the fire alarm system serving the protected premises and shall also unlock upon loss of the primary power. 8. Fire-Extinguishing Systems.
6 a. Automatic fire-extinguishing systems or suppression systems shall be connected to the building fire alarm system where a fire alarm system is required. 9. Alarm Signals and Monitoring. a. Fire alarm systems and automatic sprinkler systems shall be monitored by an approved supervising station in accordance with NFPA 72. Exceptions: Single and multiple-station smoke alarms required by IBC - Section Smoke detectors in Group I-3 occupancies. Supervising service is not required for automatic sprinkler systems in one- and two-family dwellings. Limited area sprinkler systems serving fewer than 20 sprinklers. b. Manual fire alarms, automatic fire extinguishing systems, and emergency alarm systems in Group H occupancies shall be monitored by an approved supervising station. Exception: When approved by the building official, on-site monitoring at a constantly attended location shall be permitted provided that notifications to the fire department will be equal to those provided by an approved supervising station. c. Water flow detecting devices shall initiate an alarm no more than 90 seconds after a sustained flow of at least 10 gpm. d. Upon activation of the initiating device(s), receipt of the correct initiating device signal at the supervising central station until the initiation of retransmission to the public fire service communications center should take a maximum of 90 seconds. e. A minimum of two separate means of interconnection shall be provided between the primary and remote communications center receiving equipment. This interconnection shall be dedicated and shall not be used for any other purpose. Revised Date: 11/01/09
2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.
2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is
More informationSECTION 907 FIRE ALARM AND DETECTION SYSTEMS
SECTION 907 FIRE ALARM AND DETECTION SYSTEMS 907.1 General. This section covers the application, installation, performance and maintenance of fire alarm systems and their components in new and existing
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved
More informationFlorida Building Code Chapter 9 Fire Protection Systems Advanced Course
Florida Building Code 2010 Chapter 9 Fire Protection Systems Advanced Course 1 Introduction This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors
More informationMOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Alarm System Plan Review 2009 International Fire Code and 2010 NFPA 72 Date of Review // BLD201 - Project Address: Project Name: _ Professional
More informationFlorida Building Code 2010
Introduction Florida Building Code 2010 Chapter 9 Fire Protection Systems This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors are familiar with
More informationEl Reno Fire Department Fire Alarm Plan Review Worksheet
El Reno Fire Department Fire Alarm Plan Review Worksheet This Fire Alarm Plan Review Checklist is provided as a guide to assist with your Fire Alarm Plan Review Submittal requirements. Please contact us
More informationSANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)
FIRE DEPARTMENT SANTA CLARA COUNTY 14700 Winchester Blvd., Los Gatos, CA. 95032-1818 (408) 378-4010 (408) 378-9342 (fax) www.sccfd.org STANDARD DETAILS & SPECIFICATIONS Spec No C-4 Rev. Date 03/10/10 SUBJECT:
More informationNFPA Changes
Chapter 21, Emergency Control Functions and Interfaces Summary. Chapter 21 is new. These requirements were formerly found in Chapter 6, Protected Premises Fire Alarm Systems. The term fire safety function
More informationMoreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline
Moreno Valley Fire Department Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 8, 2017 Alarm & Signaling Systems PURPOSE Fire alarm and signaling systems are designed to
More informationTHE BASICS OF FIRE ALARM PLAN REVIEW
THE BASICS OF FIRE ALARM PLAN REVIEW Art Shaw A Shaw & Associates, LLC. ashaw@arthurshaw.com 231.838.3269 Fire Protection System Plan Reviewer FP000006 NFPA Certified Plans Examiner 02-0005 NFPA Certified
More informationFire Protection Coffee Break Training May 2016
Fire Protection Coffee Break Training May 2016 Introduction High-Rise Requirements Questions and Answers Agenda Overview Site Fire Access Aerial Access Power/Back-up Power Elevators and Access Sprinklers
More informationFire Alarm, Water Flow Alarm & Signaling Systems
Orange County Fire Authority Community Risk Reduction 1 Fire Authority Road, Building A, Irvine, CA 92602 www.ocfa.org 714-573-6100 Fire Alarm, Water Flow Alarm & Signaling Systems Guideline D-03 Serving
More informationFire Alarm System Fundamentals
Fire Alarm System Fundamentals Mircom is the largest and oldest privately owned fire alarm and life safety manufacturer in North America and 5th largest overall with 50 years of industry experience. Mircom
More informationOverview of Fire Alarm Provisions Based on the 2012 IBC, IFC and NFPA 72, 2013 Edition
Accreditation Overview of Fire Alarm Provisions Based on the 2012 IBC, IFC and NFPA 72, 2013 Primarily based on Section 907 Portions of Section 903 and 909 are included. Portions of Chapter 10 are included.
More information12/14/2013. Fire alarm and emergency power SPRINKLER HEAD
Fire alarm and emergency power SPRINKLER HEAD 1 Alert signal Alarm signal Fire detector Heat detector Smoke detector Smoke alarm 1. Detector locations 1. Fire detector locations (3.2.4.11) 2. Smoke detector
More informationType of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number:
DATE OF SUBMISSION TO: Department of Licenses and Inspections Commercial and Industrial Fire Inspection Unit 990 Spring Garden Street, 3 rd Floor, Philadelphia, PA 19123 AP# CITY OF PHILADELPHIA FIRE ALARM
More informationrpsa FIRE PROTECTION ENGINEERS
FIRE PROTECTION ENGINEERS R.P. SCHIFILITI ASSOCIATES, INC. P.O. Box 297 Reading, Massachusetts 01867-0497 USA 781.944.9300 Fax / Data 781.942.7500 Telephone Elevator Fire Safety: Elevator Recall and Elevator
More informationTABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2
Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2
More information2018 NICET Code Transition Changes
2018 NICET Code Transition Changes NICET will be transitioning to newer codes accepted in their exams in mid-october 2018, specifically: NFPA 72 2016 NFPA 70 2014 IBC 2015 NFPA 101 2015 Here are some changes
More informationBold items are particular to the City of Euless
EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 8/2004 Fire Chief Lee Koontz Fire Marshal Paul Smith EFD-FMO 3-1 2003 International Fire & Building Code as Amended NFPA Standards
More informationResidential Care Facilities Requirements
Development Services Department Building Division 311 Vernon Street Roseville, California 95678-2649 Residential Care Facilities Requirements SUBMITTAL REQUIREMENTS: Note: These requirements are in addition
More informationPROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED
Ministry of Municipal Affairs PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED CHANGE NUMBER: SOURCE: B-03-02-07 Ontario-NBC CODE REFERENCE: Division B / 3.2.4.22. and 3.2.4.23. DESCRIPTION
More informationAgency for Health Care Administration
Page 1 of 92 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS Type Memo Tag FED - KA100 - General Requirements - Other Title
More informationSECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD
PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard
More informationFire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016
Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting Prepared Especially for : OSFM TEC 2016 Acceptance Testing 11-2008 Agenda Before you begin Completing the
More informationChanges in NFPA
Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration
More informationRiverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951)
Riverside County Fire Department Office of the Fire Marshal 2300 Market St., Ste. 150, Riverside, CA 92501 Ph. (951) 955-4777 Fax (951) 955-4886 Guideline Title: Residentially Based Care Facilities Group
More informationFire Alarm System Fundamentals Presented By: Shamim Rashid-Sumar, Vice President Middle East Operations Rolf Jensen and Associates, Inc.
Fire Alarm System Fundamentals Presented By: Shamim Rashid-Sumar, Vice President Middle East Operations Rolf Jensen and Associates, Inc. (RJA) Overview Understanding the Codes Fire Alarm Systems (Manual
More informationSECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM
SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationChapter 4: Fire Protection Systems
Chapter 4: Fire Protection Systems Automatic Extinguishing Systems (Fire Sprinklers) One of the most important aspects of a storage warehouse inspection is ensuring that the automatic extinguishing system
More informationRancho Cucamonga Fire Protection District Prevention Bureau Standard
Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Updated: December 2016 for consistency
More informationTHIS ORDINANCE ONLY AFFECTS EXISTING FIRE ALARM SYSTEMS.
THIS ORDINANCE ONLY AFFECTS EXISTING FIRE ALARM SYSTEMS. IF YOU RECEIVED A NOTICE BY MAIL AND YOU DO NOT CURRENTLY HAVE A FIRE ALARM INSTALLED IN YOUR BUILDING, YOU MAY DISREGARD THE NOTICE. Dear Building
More informationMINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry
MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Fire Alarm Systems Plan Review Checklist Date: Permit Number: Business Name: Address: Fire Alarm System Submittal
More information2012 OBC Changes. Summary of key changes to Life Safety and Fire Protection Systems for CFAA January 22, 2014
2012 OBC Changes Summary of key changes to Life Safety and Fire Protection Systems for CFAA January 22, 2014 2012 OBC New Sentence 3.2.4.2(6) Buildings interconnected by walkways permitted in Articles
More informationM E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot
M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Service and Fire Protection Equipment Gregory Harrington, P.E., Staff Liaison DATE: October 1, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter
More informationAgency for Health Care Administration
Page 1 of 100 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS CFR Type Memo Tag FED - KA100 - General Requirements - Other
More informationCFAA Technical Seminar Ontario Building Code Updates to 2015
CFAA Technical Seminar Ontario Building Code Updates to 2015 October 28, 2015 2015 Fire Alarm Updates Ontario Building Code Glenn Somerton P.Eng. Senior Code Specialist Morrison Hershfield Limited gsomerton@morrisonhershfield.com
More informationFIRE & LIFE SAFTEY STANDARD
Title: Effective Date: 01/01/14 Revised Date: 1/1/14 Code References: Title 16, Chapter 16.16 of the Roseville Municipal Code, NFPA 72 Note: This standard is a summary of Fire Department clarifications
More informationFunctional Performance Test
Fire Alarm Control Panel & Fire Alarm Annunciator Panel Notify all building occupants that testing will be conducted. Fire alarm contractor shall have personnel with 2-way radios at the fire alarm control
More informationCOMMERCIAL (IBC) FIRE ALARM SUBMITTAL GUIDE
COMMERCIAL (IBC) FIRE ALARM SUBMITTAL GUIDE SUPERVISION OF AUTOMATIC FIRE SPRINKLER SYSTEMS SUPERVISION OF ALTERNATIVE AUTOMATIC FIRE-EXTINGUISHING SYSTEMS FIRE ALARM AND DETECTION SYSTEMS The Fire Alarm
More information5123: information. The graphic plan shall include, but may not be limited to: (a) A primary and secondary means of exit from each floor;
ACTION: Original DATE: 09/30/2005 1:17 PM 5123:2-3-11 Fire safety and emergency response plans. (A) Purpose The purpose of this rule is to ensure the safety of individuals residing in residential facilities
More informationResidential Based Care Facility Guidelines
Moreno Valley Fire Department Fire Prevention Bureau Residential Based Care Facility Guidelines Approved and Authorized By: Randall Metz, Fire Marshal Issued: January 1, 2011 Residential Based Care Facilities
More informationFor additional information regarding R-3.1 residential care facilities please contact (951)
Riverside County Fire Department Fire/Life Safety Inspection Division Riverside Office: 2300 Market St., Ste. 150, Riverside, CA 92501 Ph. (951) 955-4823 Fax (951) 955-4886 Palm Desert Office: 77-933 Las
More informationDate Issued: December 14, 2017 Revision: 2.1
2.1 1. Introduction A is implemented to ensure the fire safety of building occupants or a building area when the Fire Alarm System or a Fire Protection System has been temporarily disabled due to malfunction,
More informationReport to Adhoc Health Code change proposal regarding locking arrangements From John Woestman, BMHA
Report to Adhoc Health Code change proposal regarding locking arrangements From John Woestman, BMHA This report is provided for information only. BMHA is not asking for Adhoc Health Care to sponser as
More informationBalloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition
Copyright National Fire Protection Association 2013. All rights reserved. This copy is solely for your personal, noncommercial use in connection with participation in the NFPA Standards Development Process.
More information2012 International Building Code Errata (Portions of text and tables not shown are unaffected by the errata)
[F]TABLE 903.2.11.6 ADDITIONAL REQUIRED SUPPRESSION SYSTEMS SECTION SUBJECT 402.10 402.5 Covered and open mall buildings (Portions of table not show remain unchanged) 2012 International Building Code SEVENTH
More information780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS 780 CMR: MASSACHUSETTS AMENDMENTS TO AND THE INTERNATIONAL BUILDING CODE 2009
780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS 780 CMR: MASSACHUSETTS AMENDMENTS TO AND THE INTERNATIONAL BUILDING CODE 2009 CHAPTER 9: FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope.
More informationM E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment
M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Services and Fire Protection Equipment Linda MacKay DATE: November 10, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter Ballot Final Results The
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST FIRE AND LIFE SAFETY SYSTEMS FOR STRUCTURES FIVE OR MORE STORIES IN HEIGHT AND LESS THAN 75 FEET IN HEIGHT FROM THE POINT
More informationStandard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.
A28.1 Standard of Practice - Fire Alarm Systems NOTE: Significant revisions or additions to the previous standards are highlighted in italics. OBJECTIVE OF STANDARD To provide compliant smart addressable
More information3.1 Introduction. 3.1 Introduction
DEPARTMENT OF ARCHITECTURE ABUBAKAR TAFAWA BALEWA UNIVERSITY, BAUCHI ARC 624: ADVANCED BUILDING SERVICES LESSON 3: FIRE DETECTION AND ALARM SYSTEMS IN BUILDINGS 3.1 Introduction 3.1 Introduction 3.2 Conventional
More informationDefend In Place 2012 IFC Overview of Institutional Occupancies
Defend In Place 2012 IFC Overview of Institutional Occupancies ICC Course No. ICC CEU s = 0.50 SCFA Course 8506-15-0 Nathan Ellis Cell: 864-812-5183 Nathan.Ellis@llr.sc.gov Institutional Occupancies Course
More informationAgency for Health Care Administration
Page 1 of 51 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K0130 - MISCELLANEOUS Title MISCELLANEOUS OTHER LSC DEFICIENCY NOT ON 2786 FED - K9999 - FINAL OBSERVATIONS Title
More informationSTANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018
STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018 STANDARD INFORMATION Standard Number: NFPA 72 Standard Name: National Fire Alarm and Signaling Code Standard Edition and Issue Date: 2016 Edition
More informationResidential-based Care Facility R-4 Guideline
Moreno Valley Fire Department Fire Prevention Bureau Residential-based Care Facility R-4 Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: April 7, 2017 Residential-based Care
More informationGROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES
[B] APPENDIX SR GROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES The provisions contained in this appendix are adopted by the Building Codes Division of the State of Oregon SECTION SR101
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD LICENSED CARE FACILITIES SCOPE: This standard provides requirements for licensed care facilities known as for the Elderly with seven
More informationMD-DC-VA Automatic Fire Alarm Association, Inc. Interfacing Fire Alarm, Sprinkler and Elevator Systems In Maryland, DC and Virginia
, Inc. Interfacing Fire Alarm, Sprinkler and Elevator Systems In Maryland, DC and Virginia Presented by: Andrew Roe, SET Alarm Tech Solutions, LLC Scope: The Purpose of Elevator Controls History of Elevator
More information2. HVAC and smoke control systems; fire, smoke, and combination fire/smoke dampers. 5. Central control and monitoring system.
PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible.. This
More informationEMERGENCY PLANNING AND PREPAREDNESS
CHAPTER 4 EMERGENCY PLANNING AND PREPAREDNESS SECTION 401 GENERAL 401.1 Scope. Reporting of emergencies, coordination with emergency response forces, emergency plans, and procedures for managing or responding
More informationUniversity Design Standard Fire Alarm Systems
1.0 Overview University Design Standard Fire Alarm Systems This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit
More informationMichigan State University Construction Standards FIRE DETECTION AND ALARM PAGE
PAGE 283100-1 SECTION 283100 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions
More informationLOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION
CHAPTER 23.45 Sections LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION 23.45.100 Local amendments to the International Fire Code, 2006 Edition... 2 23.45.102.1 Construction and design provisions...
More informationUpdate all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.
11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.
More informationBritish Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety
Div B 3.2.1.1.(4), (5) & (6) Exceptions in Determining Building Height BCBC1998-3.2.1.1.(4), (5) & (7) replace (harmonize with NBC) - NBC 2005 has significant revisions to provisions for mezzanines. These
More informationInterfacing Fire Alarm, Sprinkler and Elevator Systems
1 Interfacing Fire Alarm, Sprinkler and Elevator Systems Rodger Reiswig, SET Director, Industry Relations SimplexGrinnell November 17, 2010 Interfacing to Elevators 2 ASME A17.1 Safety Code for Elevators
More informationGENERAL AREAS OF INSPECTION
This information is intended to assist you in preparation for the annual high-rise inspection. This is not a complete list and the Inspector may identify other conditions or issues in the building that
More informationLarge Family Daycare Guideline
Moreno Valley Fire Department Fire Prevention Bureau Large Family Daycare Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: April 10, 2017 Large Family Daycare Guideline Purpose
More informationMemphis Housing Authority High Rise Fire Alarm Upgrades. Questions from Contractors (Through Addendum #2) Communications Systems, Inc.
Memphis Housing Authority High Rise Fire Alarm Upgrades Questions from Contractors (Through Addendum #2) Communications Systems, Inc.: Legend 1. DL - Dome light symbol should be on the tenant emergency
More informationSmoke Detector Activation of any smoke detector shall start the alarm verification mode.
Description: The purpose of the section is to provide the UMCP Design Standards for the design and implementation of Fire Alarm Systems at the UMCP campus. Related Sections: TBD Effective Date: July 10,
More informationJanuary 1, 2014 Mandatory Effective Date
2013 Kentucky Building Code Highlights Winnie Blythe, Technical Advisor Dept. of Housing, Buildings, and Construction winnie.blythe@ky.gov www.dhbc.ky.gov 502-573-0373 January 1, 2014 Mandatory Effective
More informationSAF-BCF SECOND REVISIONS WITH STATEMENTS
Page 196 of 331 32.2.1.3 ] Second Revision No. 153-NFPA 101-2013 [ New Section after 32.2.1.4 Multiple-Level Buildings. For purposes of applying requirements of this chapter that utilize the term level
More informationICC CODE CORNER 2015 International Fire Code
PART II GENERAL SAFETY PROVISIONS CHAPTER 4 EMERGENCY PLANNING AND PREPAREDNESS SECTION 401 GENERAL 401.1 Scope. Reporting of emergencies, coordination with emergency response forces, emergency plans and
More informationHCD DSA OSHPD 1 2 1/AC AC SS SS/CC
CALIFORNIA BUILDING CODE MATRIX ADOPTION TABLE CHAPTER 30 ELEVATORS AND CONVEYING SYSTEMS (Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter 1 for state agency
More informationPART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications:
PART 1 GENERAL 1.01 Quality Assurance A. Fire Alarm Contractor Qualifications: 1 The Fire Alarm contractor shall be an Edwards Systems Technology (EST) designated representative and authorized to sell,
More informationGROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES
[B] APPENDIX SR GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES The provisions contained in this appendix are adopted by the Building Codes Division of the State of Oregon. SECTION SR101 GENERAL
More informationSTATE OF MARYLAND DEPARTMENT OF STATE POLICE OFFICE OF THE STATE FIRE MARSHAL
STATE OF MARYLAND DEPARTMENT OF STATE POLICE OFFICE OF THE STATE FIRE MARSHAL Larry Hogan Governor Boyd K. Rutherford Lt. Governor 1201 Reisterstown Road Pikesville, MD 21208 410-653-8980 Fax 410-653-8988
More informationAutomatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems
Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems Your Presenter: Merton Bunker, PE Inspections and tests are intended to reduce or limit: Loss of life
More informationHinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM
SECTION 28 3111 DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Manual fire-alarm boxes. 3. System smoke detectors. 4. Heat detectors.
More informationFIRE SAFETY REQUIREMENTS FOR PRE RESIDENTIAL BUILDINGS OF THREE OR MORE STORIES (DOROTHY MAE ORDINANCE - NO. 158,963)
INFORMATION BULLETIN / PUBLIC - MECHANICAL CODE REFERENCE NO.: LAMC 91.8604 Effective: 6-20-84 DOCUMENT NO. P/MC 2002-005 Revised: 6-15-00 Previously Issued As: MGD #74 FIRE SAFETY REQUIREMENTS FOR PRE-
More informationSECTION 915 CARBON MONOXIDE DETECTION
SECTION 915 CARBON MONOXIDE DETECTION 915.1. General. Carbon monoxide alarms and carbon monoxide detectors shall be installed in buildings as required in accordance with Section 915.2 for residential buildings
More informationFIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES
FIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES 1. The major objective is to provide an acceptable degree of life safety from fire in existing senior citizen lodges. This document
More informationSECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM
SECTION 13852- PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this
More informationApplying Performance-based Fire Alarm System Design Part 4
Fire Alarm Notebook by Dean K. Wilson. P.E. Page 1 Applying Performance-based Fire Alarm System Design Part 4 by Dean K. Wilson, P.E. Over the course of the last four issues I have continued to discuss
More informationClarification. Summary of Changes. Summary of Changes. Alan Cavers Area Manager Fire & Security Systems Group
Summary of Changes CAN/ULC-S524-06 Installation of Fire Alarm Systems Alan Cavers Area Manager Fire & Security Systems Group Course Title Rev Date: Summary of Changes Correct Deficiencies noted CAN/ULC-S524-01
More informationStandard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment
NFPA 720 2015 Summary Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment TM, 7Oct14 CODE: Title, Standard, not Code Consistent with recent trend at NFPA, this document
More informationFIRE PROTECTION SYSTEMS
CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall specify where fire protection systems are required and shall apply to the design, installation and
More informationFIRE ALARM SYSTEMS & 780 CMR. Dave LeBlanc, PE, FSFPE March 17, 2015
FIRE ALARM SYSTEMS & 780 CMR Dave LeBlanc, PE, FSFPE March 17, 2015 BIOGRAPHY David J. LeBlanc, PE, FSFPE BS EE & MS FPE - WPI 23 Years PE Technical Committee Member NFPA72 - National Fire Alarm Code NFPA3
More informationHIGH-RISE RETROFIT ORDINANCES - NO and NO
INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: LAMC 91.8604 Effective: 9-06-90 DOCUMENT NO. P/BC 2002-054 Revised: 4-15-03 Previously Issued As: MGD 88 HIGH-RISE RETROFIT ORDINANCES - NO.
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION GUIDELINE RESIDENTIAL CARE FACILITIES 2007 CBC/CFC (R-3.1)
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION GUIDELINE RESIDENTIAL CARE FACILITIES Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: This Checklist outlines
More informationThe 2013 National Fire Alarm and Signaling Code
ARE YOU A MEMBER OF AFAA? WHY SHOULD YOU BE A MEMBER BECAUSE YOUR BUSINESS IS IMPORTANT James Mongeau The 2013 National Fire Alarm and Signaling Code 1 NFPA 72 Organization Be*er organiza2on Easier to
More information2007 CBC & CFC Residential Care Facility Requirements (24 hour care only)
2007 & CFC Residential Care Facility Requirements (24 hour care only) Occupancy Construction Smoke Barrier I-1 Bedridden 7+non- Ambs Or bed- Ridden R-4 7+ambs (May have 6 nonambs or 6 bedridden) R-3.1
More informationEMERGENCY PLANNING AND PREPAREDNESS
CHAPTER 4 EMERGENCY PLANNING AND PREPAREDNESS SECTION 401 GENERAL 401.1 Scope. Reporting of emergencies, coordination with emergency response forces, emergency plans and procedures for managing or responding
More information97 FCV 006 Page 2 of 16 EXPLANATORY MATERIAL
Page 2 of 16 EXPLANATORY MATERIAL In November 1996, the Fire Technical Council introduced a guideline entitled "Approved Fire Safety Guidelines for Apartment Buildings". The guideline was established under
More informationUnified Fire Authority - Fire Prevention Bureau
Unified Fire Authority - Fire Prevention Bureau FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance
More informationFIRE PROTECTION SYSTEMS
CHAPTER 9 FIRE PROTECTION SYSTEMS > SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall specify where fire protection systems are required and shall apply to the design, installation,
More informationGROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES
APPENDIX SR GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES The provisions contained in this appendix are adopted by the Building Codes Division of the State of Oregon. SECTION SR101 GENERAL
More informationFIRE PROTECTION SYSTEMS
CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall specify where fire protection systems are required and shall apply to the design, installation and
More information