INSTALLATION INSTRUCTIONS

Size: px
Start display at page:

Download "INSTALLATION INSTRUCTIONS"

Transcription

1 INSTALLATION INSTRUCTIONS The SensorNet I/O Module provides attachment for up to 32 alarms and up to 16 switched devices. An RS-232 or RS-422 communications port is also provided for receiving serial alarms. Install Kit Contents Part Number Qty Description Mounting DIN Rail Machine Screw, M4x Screw, Sem Thdrl, M3x Connector, 3.5mm, 1x Connector, 3.5mm, 1x Connector, 3.5mm, 1x Connector,.200, 1x Connector,.200, 1x Resistor, 1K Ohm, 1%,.25W m Cable, 3 Cond, 18AWG SensorNet Network Design Guide SensorNet I/O Module Installation Instructions WARNING To reduce risk of fire or electric shock, do not expose this product to rain or other moisture. Setup for RS-422 Alarms The SensorNet I/O Module can accept alarms from attached processors via RS-232 or RS-422 asynchronous communications protocol. A later section will discuss how to attach these devices. If you plan to use RS-422 protocol, a jumper on the SensorNet I/O Module printed circuit board must be set before mounting the unit. 1. Referring to Figure 2, remove the three screws that hold the cover in place. Set the cover and screws aside. 2. Set jumper JW1 on the printed circuit board to the RS-422 setting, as shown in Figure Replace the cover and screws that hold it in place. Figure 2. Cover Figure 3. Communications Jumper Cover Attaching the Optional DIN Rail A DIN rail and attachment screws are provided for mounting external control devices to the unit. 1. Position the DIN rail ( ) on top of the SensorNet I/O Module so the screw holes can be seen through the holes in the center of the rail. 2. Attach the rail to the unit's top cover using the three M4x6 machine screws ( ), as shown in Figure Position DIN interface devices so their connections face the back of the SensorNet I/O Module and slide them from either end or snap them onto the rail. Figure 1. DIN Rail Jumper RS422 JW1 RS232 INSTALLATION INSTRUCTIONS 1 OF 7

2 Mounting the Unit The SensorNet I/O Module can be mounted in several ways to accommodate differing customer requirements. Mounting brackets are provided in the install kit to secure the unit in many orientations. Figure 5. Under-Shelf Mount Alarm and Device Table Top Mount 1. Place the SensorNet I/O Module on top of the table in the desired position with the American Dynamics logo and display lights facing the front of the table. Rack Mount 1. Position a mounting bracket ( ) at each end of the unit as shown in Figure Attach each bracket using two M3x8 screws ( ) from the install kit. 3. Mount in an open rack position using two rack mount bolts (not provided) at each end. Figure 4. Rack Mount Alarm and Device Mounting Wall Mount End View Keyhole slots on the bottom of the SensorNet I/O Module allow the unit to hang on a wall with its front facing upward. When mounted this way, wires from alarms and switched devices connect to the back of the unit, which faces downward. Vertical or front-down orientations are also allowed, but require use of the mounting brackets. See step 11 and Figure 7, on the following page. Mounting End View Refer to Figure 6 to prepare the wall for mounting. Figure 6. Wall Mount Dimensions Line a Rack Mount Bolts Under-Shelf Mount 1. Install a mounting bracket ( ) at each end, so it is aligned with the top of the unit, as shown in Figure Attach each bracket using two M3x8 screws ( ) from the install kit. 3. Attach the unit to the underside of the shelf with two wood or metal screws (not provided) at each end. INSTALLATION INSTRUCTIONS 2 OF 7 Line c "A" 12.9cm (5.1in) 7.2cm (2.8in) 21.7cm (8.6in) 17.9cm (7.1in) "C" Line e 6.4cm (2.5in) 17.93cm (7.1in) Line b 43.4cm (17.1in) Line f Line d "B" 1. Position the location of the SensorNet I/O Module's front panel (facing upward) on the wall by drawing a 43.4cm (17.1in) horizontal line (a). Make sure the control lights on the front of the panel can be seen from this location. 2. Draw a horizontal line (b) 12.9cm (5.1in) below the first line to locate the I/O Module's back panel (facing down). Make sure the alarm and device attachment cables reach this location. 3. Draw vertical lines (c and d) through lines a and b, 43.4cm (17.1in) apart at the left and right end of line a. The rectangle defined by lines a, b, c, and d marks the SensorNet I/O Module's location. 4. Draw a vertical centerline (e) through lines a and b, 21.7cm (8.6in) from line c. 5. Draw a horizontal line (f), 7.2cm (2.8in) below line a. Mark points "A" and "B" on this line, 17.9cm (7.1in) to the left and right of line e. These are the positions of the two lower mounting screws.

3 6. Mark point "C" on the vertical centerline (e), 6.4cm (2.5in) above line f. This is the position of the upper mounting screw. 7. Drill pilot holes at points "A", "B", and "C". 8. If using wall anchors (not provided), drill holes, insert anchors, and tighten screws, leaving.5cm (.2in) of threads exposed. 9. If using wood or metal screws (not provided), insert and thread completely, then loosen, leaving.5cm (.2in) of threads exposed. 10. Hang the SensorNet I/O Module on the three screws, using the keyhole slots on the bottom of the unit. 11. If necessary, secure the unit using mounting brackets ( ) from the install kit. Align each bracket's flange with the base of the unit as shown in Figure 7 and secure to the wall with anchors. Figure 7. Securing the Wall Mount Alarm and Device Wall Anchors Mounting End View INSTALLATION INSTRUCTIONS 3 OF 7

4 Figure 8. SensorNet I/O Module Back Panel RS232 TXHI + TXLO - RXHI + RXLO - RS485 24V AC RT8 AL8 RT7 AL7 RT6 AL6 RT5 AL5 RT4 AL4 RT3 AL3 RT2 AL2 RT1 AL1 RT16 AL16 RT15 AL15 RT14 AL14 RT13 AL13 RT12 AL12 RT11 AL11 RT10 AL10 RT9 AL9 RS422 Switched Devices Alarms Communications Interface: Choose One SensorNet Connector Termination Switch Left - Terminated Right - Not Terminated Address Switches Power Connector SensorNet I/O Module Connections The SensorNet I/O Module uses removable connectors for all device and communications attachments. All attachments except RS-232 use compression-type connectors provided in the install kit. RS-232 requires a DB9(M), connector or cable. Due to the difficulty of working with crimp connections, the cabling and connector alternatives, and the ready availability of RS- 232 cables, this connector is not provided in the install kit. The back of the unit is labeled to identify each connection point, as shown in Figure 8. Attaching Switched Devices Two 24-position compression connectors ( ) are provided in the install kin to attach up to 16 switched devices. Three terminals to each switching relay provide normally-closed (NC), common (COM), and normallyopen (NO) connections. Refer to Figure 9 while making the connections. 1. Begin with devices 1 through 8, using one 1x24 connector. 2. Strip 6mm (.25in) of insulation from each device connection lead. 3. Insert one lead into the center (COM) opening and the second lead into the NC or NO connector opening (see Figure 9). 4. Tighten the screw over each inserted lead until it is held firmly in position (see Figure 9). Do not overtighten. 5. After all leads are secured, plug the connector into the lower slot on the SensorNet I/O Module (see Figure 9). 6. Using a second 1x24 connector from the install kit, repeat steps 2-4 to attach devices After all leads are secured, plug the 1x24 connector into the upper slot on the SensorNet I/O Module (see Figure 9). Figure 9. Switched Device Connections NC COM NO Switched Devices 9-16 Switched Devices 1-8 Insert Fully Tighten to hold leads in place INSTALLATION INSTRUCTIONS 4 OF 7

5 Attaching Alarms Four 16-position compression connectors ( ) are provided in the install kit to attach up to 32 alarms. Two terminals connect each alarm. Refer to Figure 10 while making the connections. 1. Begin with alarms 1 through 8, using a 1x16 connector. 2. Strip 6mm (.25in) of insulation from each device connection wire. 3. Insert each wire pair into the appropriate AL (alarm) or RT (alarm return) connector openings. 4. Tighten the screw over each inserted lead until it is held firmly in position (see Figure 10). Do not overtighten. 5. After all leads are attached, plug the 1x16 connector into the lower left-hand alarm slot on the SensorNet I/O Module. 6. Repeat steps 2-5 up to three more times for alarms 9-16, 17-24, and Use one 1x16 connector from the install kit for each group of 8 alarms. 7. After all leads are attached to each connector, plug it into the appropriate slot on the SensorNet I/O Module (see Figure 10). Figure 10. Attaching Alarms Alarms Alarms Wire each alarm circuit as follows (see Figure 11): 1. Run a two-wire cable from the location of each alarm sensor to the SensorNet I/O Module. Label each end with the alarm identification. 2. Connect one resistor ( ) from the SensorNet I/O Module Install kit across the alarm sensor's terminals. 3. Connect one lead from a second 1K ohm resistor to one of the alarm sensor's terminals. Connect this resistor's second lead to one wire from the cable to the SensorNet I/O Module. 4. Connect the cable's second wire to the alarm terminal that has one resistor attached. 5. Tighten or solder all connections and insulate with electrical tape, if necessary. Figure 11. Supervised Alarm Installation Alarm Sensor 1KΩ 1KΩ to SensorNet I/O Module With resistors installed, the unit detects the four states and voltages shown in the following table. In addition, the supporting video system can identify the state of each switch and line, and display their condition on its status screen. Alarms 1-8 RT8 AL8 RT7 AL7 RT6 AL6 RT5 AL5 RT4 AL4 RT3 AL3 RT2 AL2 RT1 AL1 RT8 AL8 RT7 AL7 RT6 AL6 RT5 AL5 RT4 AL4 RT3 AL3 RT2 AL2 RT1 AL1 Insert Fully RT16 AL16 RT15 AL15 RT14 AL14 RT13 AL13 RT12 AL12 RT11 AL11 RT10 AL10 RT9 AL9 RT16 AL16 RT15 AL15 RT14 AL14 RT13 AL13 RT12 AL12 RT11 AL11 RT10 AL10 RT9 AL9 Tighten to hold leads in place Alarms 9-16 Alarm or Line State Input Load Nominal Voltage Allowable Voltage Range Line Shorted 0Ω 0V <1.75V Line Supervised - Switch Closed Line Supervised - Switch Open Line Open 1kΩ 2.5V >1.75V, <3.17V 2kΩ 3.33V >3.17V, <4.24V no load ( Ω) 5V >4.24V Wiring Supervised Alarms Place two 1k-ohm resistors from the install kit ( ) into each alarm circuit, as described below. This allows the SensorNet I/O Module to detect open circuits or shorts in the two-wire cable connecting the alarm sensor to the unit. Place resistors at the alarm end of the line, as close as possible to the alarm switch. This allows shorts or opens at any point between the resistors and the SensorNet I/O Module to be detected. The twisted pair cable's maximum resistance should be less than 200 ohms. 22AWG copper wire (19 ohms per 305m (1000ft) at 50 C) allows a distance of up to 1.6km (1 mile) for a twisted pair. With no resistors installed, the unit detects only the two non-supervised states. It cannot determine whether the state is set by the alarm switch or line trouble. In this configuration, it is also not possible to trigger an alarm on a troubled (line open or short) condition. Attaching Communications Alarm Sources These alarms are initiated by a separate computer-based alarm tracking system that outputs an alarm message on its RS-232 or RS-422 port whenever an alarm occurs. The SensorNet I/O Module comes set up for attaching an RS- 232 input line. via RS-422 requires a jumper change on the controller board (see procedures on page 1) and use of a different connector and SensorNet I/O Module port. INSTALLATION INSTRUCTIONS 5 OF 7

6 RS-232 Alarms 1. The female DB9 connector on the back of the unit has the following pin assignments: Pin 2 Pin 3 Pin 5 Transmit Data Receive Data Ground 2. Use a commercially-available or locally-built RS-232 cable to attach the alarm system to the unit. If necessary, modify the cable wiring to achieve the above pin assignments. RS-422 Alarms 1. Wire the 1x5 connector ( ) from the install kit as follows: Pin 1 Receive Data + Pin 2 Receive Data - Pin 3 Transmit Data + Pin 4 Transmit Data Pin 5 Ground 2. Wire the other end of the cable to the 1x3 connector ( ) from the install kit according to the following table Transformer Universal Power Supply Cable SensorNet I/O Module AC Common Red Pin 1 Gnd Ground White Pin 2 AC 24V Black Pin 3 3. Strip 6mm (.25in) of insulation from each power lead and insert it into the appropriate connector opening. Tighten the screws above each lead until they held firmly in position. Do not over-tighten. 4. Plug the 1x3 connector into the 24V connector on the back of the SensorNet I/O Module. 5. Check your work against Figure Plug the power cord into the Universal Power Supply and connect it to a 110 or 220v AC power receptacle. Figure 12. Power Connection 24V AC Transformer 2. Strip 6mm (.25in) of insulation from each lead and insert it into the appropriate connector opening. Tighten the screws above each lead until it is held firmly in position. Do not over-tighten. 3. Plug the 1x5 connector into the RS-422 port on the back of the SensorNet I/O Module (see Figure 8). Attaching to SensorNet 1. Strip 6mm (.25in) of insulation from each of the SensorNet leads and insert them into the two openings in the 1x2 connector ( ) from the install kit. 2. Tighten the screws above each lead until they are held firmly in position. Do not over-tighten. 3. Plug the 1x2 connector into the RS-485 port on the back of the SensorNet I/O Module (see Figure 8). Setting the SensorNet Address 1. Dial in the SensorNet address using the two rotary switches on the back of the SensorNet I/O Module (see Figure 8). The right switch selects the units digit and the left switch selects the ten's digit. The allowable range is 01 to If this device requires termination, set the terminating switch to the left (resistor) position; otherwise, set it to the right ("Not") position (see Figure 8). Connecting Power 1. Connect the three-wire cable ( ) to the ground, COM, and 24V terminals of the transformer ( ) or Universal Power Supply ( ) that is shipped with the unit. COM 12V~ 17V~ 20V~ 24V~ or Universal Power Supply INSTALLATION INSTRUCTIONS 6 OF 7

7 Front Panel Lights and Controls The SensorNet I/O Module has five indicator lights on the front panel, as shown in Figure 13. Figure 13. Indicator Lights and Controls Reset AC Power Processor Active Reset An unlabeled hole in the panel that gives access to a button that resets the unit's microprocessor. Use a paper clip or small screwdriver to depress the button. A green LED that indicates 24 VAC ~ is applied. I/O A green LED that blinks to indicate the SensorNet I/O Module processor is operating. RS-485 A green LED showing SensorNet activity. Off indicates no activity. On continuously indicates the network is active and transmitting data. Blinking indicates the SensorNet I/O Module is answering polls. RS- 232/422 American Dynamics I/ O SensorNet Active RS48 5 RS232/42 2 Serial Comm False Carrier Detect A randomly blinking red LED that indicates the network is experiencing transmission errors. Usually indicates invalid frame lengths or noise on the line. A green LED indicating communications with serial alarms is occurring. This light blinks twice when the unit is reset or powered up (see Troubleshooting section). The first blink indicates a successful ROM check and the second shows a successful RAM check. If either test fails, the test halts with the LED lit continuously. Troubleshooting The SensorNet I/O Module's LED indicator lights indicate when activity is occurring during operation. They can also identify many errors that could occur: Normal Operation ROM Checksum Failure RAM Write/Read Failure Device Address Settings are not in Range 1. ~ LED comes on. 2. RS-232/422 LED comes on for 1.25 seconds during ROM test, goes off briefly and flashes once during RAM test. 3. RS-485 LED begins flashing rapidly after ~5 seconds, indicating SensorNet polls are being received. 4. I/O LED blinks continuously indicating that attached devices are being polled. 5. RS-232/422 LED flashes when messages are received. 6. RS-232/422 LED stays lit continuously during software loads to the unit. 1. RS-232/422 LED comes on and stays on. 2. Re-load SensorNet I/O Module software from the host system. 1. RS-232/422 LED comes on for 1.25 seconds during ROM test, goes off briefly and then remains on. 1. RS-232/422 and I/O LEDs continue to flash rapidly. 2. RS-485 light does not blink. Line Errors 1. LED flashes randomly to indicate SensorNet transmission errors. 2. Check for invalid frame lengths or noise on the line. Not Functional No Power 1. Module continuously resets (steps 1. and 2. under Normal Operation). 2. I/O LED does not blink. 3. Check for low power or hardware/software problem. 1. ~ LED does not come on. INSTALLATION INSTRUCTIONS 7 OF 7

MEGA. cal electronic gas alarm. Installation, Operation, and Maintenance Instructions. Part No Rev. D Pg.

MEGA. cal electronic gas alarm. Installation, Operation, and Maintenance Instructions. Part No Rev. D Pg. WARD OXYGEN Installation, Operation, and Maintenance Instructions MEGA medical electronic gas alarm MEGA WARD MEGA medical electronic gas alarm WARD POWER SUPPLY Medical Electronic Gas Alarm OXYGEN SYSTEM

More information

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required.

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required. TTSIM-1A TraceTek Sensor Interface Module with Relay Installation Items (not supplied) General Information Installation/Operation Instructions Please read these instructions and keep them in a safe place.

More information

ALARM OUTPUT MODULE. Product #7736

ALARM OUTPUT MODULE. Product #7736 ALARM OUTPUT MODULE The Alarm Output Module (AOM) enables you to use weather station alarms or commands from your computer to automatically start or stop external devices such as indicator lights, audio

More information

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16 TraceTek TTSIM-1A TraceTek Sensor Interface Module with Relay Installation/OPERATION Instructions Approvals and Certifications TYPE NM General Signaling Equipment 76LJ Only AC versions are UL listed and

More information

DCA4. Digitally controlled Audio Matrix. Current Thinking. Product Specification March Document Number DDC DCA ACS

DCA4. Digitally controlled Audio Matrix. Current Thinking. Product Specification March Document Number DDC DCA ACS DCA4 Digitally controlled Audio Matrix Product Specification March 2002 Current Thinking Document Number DDC DCA 7001 01 ACS Introduction Voice Alarm (VA) systems are the quickest way to evacuate the public

More information

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS GENERAL INFORMATION Please read these instructions and keep them in a safe place. These instructions must

More information

Duct and Rough Service Carbon Monoxide Sensor

Duct and Rough Service Carbon Monoxide Sensor Product Identification and Overview Duct and Rough Service Carbon Monoxide Sensor BAPI s Carbon Monoxide Sensor offers enhanced electrochemical sensing with outstanding accuracy at low concentrations.

More information

5 Inch Speed Dome Installation Manual V2.0.0

5 Inch Speed Dome Installation Manual V2.0.0 5 Inch Speed Dome Installation Manual V2.0.0 2010-01 1 Thank you for purchasing our product. If there is any question or request, please do not hesitate to contact dealer. This manual is applicable to

More information

DESCRIPTION INSTALLATION

DESCRIPTION INSTALLATION DESCRIPTION The Model 10A11 Two-Way Audio/Voice Alarm Module allows two-way communication with a central station after an alarm, paging and listening from an on-premises or remote phone, annunciation of

More information

Addressable NAC Output Module D327A

Addressable NAC Output Module D327A Installation Instructions Notice Addressable NAC Output Module D327A These instructions cover the installation of the D327A Addressable NAC Output Module in an analog system controlled by a Bosch D8024,

More information

21-light Remote Annunciator. Owner s Manual

21-light Remote Annunciator. Owner s Manual 21-light Remote Annunciator Owner s Manual Annunciator Description... Inside Font Cover Detailed Specifications... 1 Environmental Specifications... 1 Power Supply Requirements... 1 Communication With

More information

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option SM3000 Videographic Recorder User Guide (RTU) Communications Option ABB The Company We are an established world force in the design and manufacture of instrumentation for industrial process control, flow

More information

Pioneer-R16 Gas Monitor Operator s Manual

Pioneer-R16 Gas Monitor Operator s Manual Pioneer-R16 Gas Monitor Operator s Manual Edition 7/2/97 RKI INSTRUMENTS, INC RKI Instruments, Inc. 33248 Central Ave, Union City, CA 94587 (510) 441-5656 Chapter 1: Description About the Pioneer-R16 Gas

More information

D7053. Installation Instructions Multiplex Input/Output Module

D7053. Installation Instructions Multiplex Input/Output Module D EN Installation Instructions Multiplex Input/Output Module D Installation Instructions Notices Notices These instructions cover the installation of the D Multiplex Input/Output Module in a fire system

More information

ECO N DATE DESCRIPTION OF CHANGE CHG

ECO N DATE DESCRIPTION OF CHANGE CHG Model Number: M21E-24-DIN Description: The product is a loop powered device which controls an unsupervised dual pole output channel suitable to manage 24VAC loads. The M21E-24-DIN is micro-controller operated,

More information

4 Channel Contact Closure SFP DIN Fiber Link System

4 Channel Contact Closure SFP DIN Fiber Link System USER GUIDE The leader in rugged fiber optic technology. U- 07A-0707 Channel Contact Closure DIN Fiber Link System Installation and Configuration Information Description The system provides transmission

More information

Wiring Instructions for the 2900 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector

Wiring Instructions for the 2900 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector Wiring Instructions for the 900 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector CAUTION: FAILURE TO INSTALL OR ADJUST PROPERLY MAY RESULT IN INJURY OR

More information

Sensor Interface Module Installation/Operation Instructions

Sensor Interface Module Installation/Operation Instructions TraceTek TTSIM-1 Sensor Interface Module Installation/Operation Instructions Approvals and Certifications TYPE NM General Signaling Equipment 76LJ Only AC versions are UL listed and VDE Certified. For

More information

Independent Zone Control (I.Z.C.)

Independent Zone Control (I.Z.C.) Operation and Installation Guide Independent Zone Control (I.Z.C.) DELAYED INSTANT ARMED 1 2 3 4 7 5 6 8 9 * * fi Radionics R D279A Operation & Installation Guide 46456B Page 2 Copyright 2000 Radionics

More information

PERTRONIC INDUSTRIES LTD F4-RMAX Installation Note

PERTRONIC INDUSTRIES LTD F4-RMAX Installation Note Product Overview: The Pertronic F4 Remote LED Mimic / Aux Relay Module F4-RMAX is an optional extra for the Pertronic F4 conventional 4-zone fire alarm panel. This board enables the fire alarm panel to

More information

Quick Alert Remote (QA216R)

Quick Alert Remote (QA216R) Quick Alert Remote (QA216R) Description The QA 216 Remote is used by AT&T to monitor tower lights and turned down facilities. It is a 16-bit alarm unit used to transport discrete alarms from a remote location

More information

Table of Contents What to Expect with. Tools Needed. Mounting Options. Wiring. Switch Housing.

Table of Contents What to Expect with. Tools Needed. Mounting Options. Wiring. Switch Housing. Table of Contents Congratulations on purchasing your new Hunter ceiling fan! It will provide comfort and performance in your home or office for many years. This installation and operation manual contains

More information

RMS/RPX Reader. User Manual

RMS/RPX Reader. User Manual RMS/RPX Reader User Manual Copyright Disclaimer Trademarks and patents Intended use FCC compliance Copyright 2005, GE Security Inc. All rights reserved. This document may not be copied or otherwise reproduced,

More information

IR Intelligent Speed Dome Installation Manual

IR Intelligent Speed Dome Installation Manual IR Intelligent Speed Dome Installation Manual Version 1.0.0 Table of Contents 1 INSTALLATION PREPARATION... 1 1.1 Basic Requirement... 1 1.2 Installation Check... 1 1.3 Cable Preparation... 1 1.3.1 The

More information

PERMACONN PM1030 Includes DI300. Installation Manual

PERMACONN PM1030 Includes DI300. Installation Manual PERMACONN PM1030 Includes DI300 Installation Manual Radio Data Comms Unit 5/20-30 Stubbs Street Silverwater NSW 2128 Telephone: 02 9352 1777 Facsimile: 02 9352 1700 Introduction The PERMACONN system provides

More information

Low Water Cutoff (LWCO) IQ Option Card p/n , for Hot Water Boilers

Low Water Cutoff (LWCO) IQ Option Card p/n , for Hot Water Boilers Low Water Cutoff (LWCO) IQ Option Card p/n 102711-01, 102714-01 for Hot Water Boilers Instruction Sheet 102-360 APPLICATION The Low Water Cutoff (LWCO) IQ Option Cards are advanced, microprocessor based

More information

Smart Water Heater Controller

Smart Water Heater Controller Smart Water Heater Controller Installation Instructions Version 1.0 2016 1 Introduction Congratulations on the purchase of your Aquanta Smart Water Heater Controller! The Aquanta retrofittable water heater

More information

FIRECLASS Networking. Addressable Fire Alarm Control Panels From Software version 21. Product Application and Design Information FC-A-FCNET-A

FIRECLASS Networking. Addressable Fire Alarm Control Panels From Software version 21. Product Application and Design Information FC-A-FCNET-A FIRECLASS Networking Addressable Fire Alarm Control Panels From Software version 21 Product Application and Design Information FC-A-FCNET-A Doc. version 1 23. March 2012 FIRECLASS. Hillcrest Business Park,

More information

NGC-UIT-ORD User interface terminal for Raychem NGC systems Installation Instructions

NGC-UIT-ORD User interface terminal for Raychem NGC systems Installation Instructions NGC-UIT-ORD User interface terminal for Raychem NGC systems Installation Instructions Description The NGC-UIT-ORD is a panel mounted display used in conjunction with other approved Raychem control and

More information

WD-CS. Water leak detection cable. Technical Overview. Features. Page 1. Data Sheet Ref: Issue: 5.1.

WD-CS. Water leak detection cable. Technical Overview. Features. Page 1. Data Sheet Ref: Issue: 5.1. Data Sheet Ref: 90501085 WD-CS Water leak detection cable Technical Overview The WD-CS range of cable sensors are typically used to detect water leaks usually under floors, and are used in conjunction

More information

4100U City and Relay Cards Installation Instructions

4100U City and Relay Cards Installation Instructions 4100U City and Relay Cards Installation Instructions Introduction This publication describes the installation procedure for the following: 4100-6031/6032 City Circuit Cards 4100-6033 Alarm Relay Card Inspecting

More information

VPS3 Installation Manual

VPS3 Installation Manual 1-512-756-1678 VPS3 Installation Manual VPS3 Viewer (Local Unit) VPS3 Sender (Remote Unit) Content Introduction...2 Features...2 Packing Checklist...2 Patents...2 Limited Warranty...2 Overall Certificate...3

More information

RS485 MODBUS Module 8AI

RS485 MODBUS Module 8AI Version 1.4 15/04/2013 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have

More information

Input/Output Modules Data Sheet

Input/Output Modules Data Sheet Input/Output Modules Data Sheet The wide range of input and output modules available from NOTIFIER delivers exceptional flexibility to a NOTIFIER fire detection and alarm system. Using these modules enables

More information

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description MODUL-R FIRE ALARM CONTROL PANELS MR-2900/MR-2920 Addressable Fire Alarm Control Panels Description MR-2900 Fire Alarm Control Panel The MR-2900 fire alarm system control unit is the heart of a sophisticated

More information

LMS-188-4P-BMS 4 POINT DIGITAL MONITOR/ALARM WITH PROTOCOL CONVERTER OPERATING INSTRUCTIONS

LMS-188-4P-BMS 4 POINT DIGITAL MONITOR/ALARM WITH PROTOCOL CONVERTER OPERATING INSTRUCTIONS G LMS 188 4P BMS August, 2018 LMS-188-4P-BMS 4 POINT DIGITAL MONITOR/ALARM WITH PROTOCOL CONVERTER OPERATING INSTRUCTIONS! WARNING: This product can expose you to chemicals including lead, which is known

More information

ATS Annunciator - MODBUS

ATS Annunciator - MODBUS GE Zenith Controls ATS Annunciator - MODBUS Model 150047443 Quick Start Guide ATS Annunciator monitors and controls up to 8 Automatic Transfer Switches equipped with the MX150/250 Controller. Before getting

More information

Installing the Cisco ONS FAP-4 Fuse Alarm Panel

Installing the Cisco ONS FAP-4 Fuse Alarm Panel Installing the Cisco ONS 15454-FAP-4 Fuse Alarm Panel Product Number: 15454-FAP-4= This document explains how to install, test, operate, and maintain the Cisco ONS 15454-FAP-4 fuse alarm panel. This document

More information

D7052. Installation Instructions Multiplex Dual Input Module

D7052. Installation Instructions Multiplex Dual Input Module D EN Installation Instructions Multiplex Dual Input Module D Installation Instructions Notices Notices Figure : D Features These instructions cover the installation of the D Multiplex Dual Input Module

More information

Vess A2000 Series. IO Terminal Board. User Information. Version PROMISE Technology, Inc. All Rights Reserved.

Vess A2000 Series. IO Terminal Board. User Information. Version PROMISE Technology, Inc. All Rights Reserved. Vess A2000 Series IO Terminal Board User Information Version 1.0 2014 PROMISE Technology, Inc. All Rights Reserved. Contents Introduction 1 I/O Terminal Board Features 2 Pin Assignments 3 Sensor Input

More information

IR Intelligent Speed Dome Installation Manual

IR Intelligent Speed Dome Installation Manual IR Intelligent Speed Dome Installation Manual Version 1.0.0 Table of Contents 1 INSTALLATION PREPARATION... 1 1.1 Basic Requirement... 1 1.2 Installation Check... 1 1.3 Cable Preparation... 1 1.3.1 The

More information

15R HARDWARE INSTALLATION GUIDE

15R HARDWARE INSTALLATION GUIDE 15R HARDWARE INSTALLATION GUIDE Table of Contents Section 1 Ratings....................................................................... 3 Section 2 Site Preparation................................................................

More information

Installation Instructions Azatrax Dual Infrared Model Train Detector MRD2 'Turnout' Edition

Installation Instructions Azatrax Dual Infrared Model Train Detector MRD2 'Turnout' Edition Installation Instructions Azatrax Dual Infrared Model Train Detector MRD2 'Turnout' Edition What it is: The MRD2 'turnout' edition is a two-channel model train detector. It can detect model trains at two

More information

Microwave/PIR Intrusion Detector with POPIT Interface ZX970

Microwave/PIR Intrusion Detector with POPIT Interface ZX970 Microwave/PIR Intrusion Detector with POPIT Interface ZX970 Installation Instructions 1.0 Specifications Input Power: 9 to 15 VDC, 6 ma nominal (35 ma with LED on) Zonex Current Draw: 500 ma Standby Power:

More information

SAFETY INFORMATION AND WARNINGS

SAFETY INFORMATION AND WARNINGS This manual refers to the Model SST-3 control panel manufactured since October 31, 2013, which uses a universal (100 277 VAC; 50/60 Hz) power supply. Older units use a voltage-specific power supply and

More information

Model AD C AD RS-422 Distributor

Model AD C AD RS-422 Distributor Model C AD RS-422 Distributor Installation and Operation Instructions Speed LT, Speed, Speed Ultra, Speed Optima, and Speed Optima LT The C Distributor is used to interface American Dynamics Switching

More information

ADT Home Security Starter Kit. Setup Guide

ADT Home Security Starter Kit. Setup Guide PRINTER S INSTRUCTIONS: GUIDE,QUICK START,NOVA - NORTEK P/N: 10016840C- INK: BLACK PLUS PMS 286C - MATERIAL: 105G COATED PAPER - SIZE: 127MM X 142.24MM - SCALE: 1-1 - BINDING: TRIM, FOLD AND SADDLE STITCHED

More information

SMARTWALK DEMENTIA WANDERING SYSTEM

SMARTWALK DEMENTIA WANDERING SYSTEM A division of NESS CORPORATION PTY LTD SMARTWALK DEMENTIA WANDERING SYSTEM SWD Door Responder SWD Resonator SWD-PET (Sold Separately) SWD-PET-BAND (Sold Separately) INSTALLATION MANUAL 1. CONTENTS 1. CONTENTS...1

More information

REPEATER FS5200R INSTRUCTION MANUAL

REPEATER FS5200R INSTRUCTION MANUAL REPEATER FS5200R INSTRUCTION MANUAL Instruction Manual Page1 CONTENTS 1. Introduction... 3 2. Function... 3 3. Technical data... 3 4. Contents of delivery... 4 5. General information... 5 6. Duty Mode...

More information

Table of Contents SECTION PAGE SECTION 1 INTRODUCTION Description Features Models... SECTION 2 RS-232 COMMUNICATIONS...

Table of Contents SECTION PAGE SECTION 1 INTRODUCTION Description Features Models... SECTION 2 RS-232 COMMUNICATIONS... SECTION Table of Contents SECTION 1 INTRODUCTION...................... 1.1 Description............................... 1.2 Features................................. 1.3 Models..................................

More information

BK AND BKT BLOWER ACCESSORY INSTALLATION INSTRUCTIONS

BK AND BKT BLOWER ACCESSORY INSTALLATION INSTRUCTIONS BK AND BKT BLOWER ACCESSORY INSTALLATION INSTRUCTIONS MODEL BK MANUALLY CONTROLLED BLOWER MODEL BKT THERMOSTATICALLY CONTROLLED BLOWER WARNING: ELECTRICAL GROUNDING INSTRUCTIONS This appliance is equipped

More information

Table of Contents What to Expect with Your Installation. Top Housing. Ceiling Plate. Tools Needed.

Table of Contents What to Expect with Your Installation. Top Housing. Ceiling Plate. Tools Needed. Table of Contents Congratulations on purchasing your new Hunter ceiling fan! It will provide comfort and performance in your home or office for many years. This installation and operation manual contains

More information

Fratech Multipath-IP

Fratech Multipath-IP Rev 2.0 (May 2013) Installer Manual 1 Current Part Numbers: Fratech Multipath-IP E-Link STU PCB & Accessory Kit only In Metal Enclosure with Power Supply 998325-PK 998325-XS Installer Manual This document

More information

ACCURATE ELECTRONICS INC

ACCURATE ELECTRONICS INC ACCURATE ELECTRONICS INC Page 1 of 7 Model 108078 2 Sept 09 WWW.ACCURATE.ORG PO BOX 1654 97075-1654 8687 SW Hall Blvd 97008 BEAVERTON OR USA 503.641.0118 FAX 503.646.3903 Practice Section 108078 Rev A

More information

TOUCH 1500 User Interface Terminal for Raychem NGC Systems Installation Instructions

TOUCH 1500 User Interface Terminal for Raychem NGC Systems Installation Instructions TOUCH 1500 User Interface Terminal for Raychem NGC Systems Installation Instructions Approvals / Certifications Hazardous Locations Class I, Division 2 Groups A, B, C, D Touch 1500-HAZ-CPU and Touch 1500-HAZ-TS

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS TT-1343 5/06b INSTALLATION INSTRUCTIONS Original Issue Date: 8/03 Model: Automatic Transfer Switches Equipped with Series 1000 Programmable Controller Market: ATS Subject: Remote Annunciator Kits GM28938-KP1,

More information

Table of Contents SECTION PAGE

Table of Contents SECTION PAGE Table of Contents SECTION PAGE SECTION 1 INTRODUCTION................... 1.1 Description.............................. 1.2 Features................................ 1.3 Models.................................

More information

T874 Multistage Thermostat and Q674 Subbase

T874 Multistage Thermostat and Q674 Subbase SUPER TRADELINE T874 Multistage Thermostat and Q674 Subbase Application The T874D Thermostat and Q674E Subbase provide 4 to 30 Vac control of standard stage heating and stage cooling systems. The Y594D

More information

USER MANUAL FOR OPERATING SYSTEM

USER MANUAL FOR OPERATING SYSTEM P2262 ALARM PANEL USER MANUAL FOR OPERATING SYSTEM 21765-07 September 1999 Associated Controls (Aust) PTY. LTD. 29 Smith Street, Hillsdale, NSW, 2036. PH (02) 9311 3255, FAX (02) 9311 3779 Page 1 of 177

More information

Booster Power Supply Manual

Booster Power Supply Manual Supply Manual DEVELOPED BY COPYRIGHT NOTICE General Signal Building Systems Corporation 6411 Parkland Drive Sarasota, FL 34243 (941) 739-4300 Copyright 1999 General Signal Building Systems Corporation

More information

GSM RFID VOICE Alarm System

GSM RFID VOICE Alarm System GSM RFID VOICE Alarm System User s Manual For a better understanding of this product, please read this user manual thoroughly before using it. CONTENTS [Function Instruction] [Control Panel] Control Panel

More information

FMR Installation Instructions. Addressable Fire System Controller

FMR Installation Instructions. Addressable Fire System Controller FMR-7033 EN Installation Instructions Addressable Fire System Controller EN 2 FMR-7033 Installation Instructions Contents Contents Contents...2 1.0 Introduction...3 2.0 Description...3 3.0 Device Mounting...3

More information

Installation and Operation Manual Low Power (LP) DC Power System

Installation and Operation Manual Low Power (LP) DC Power System Installation and Operation Manual Low Power (LP) DC Power System LPS Power Enclosure LPB Battery Enclosure 2051259 R3 Information in this document is subject to change without notice and does not represent

More information

Alarm Panel [ PRELIMINARY HARDWARE MANUAL ] USER MANUAL. v1.0a. May 7, 2008 D-OC-UM

Alarm Panel [ PRELIMINARY HARDWARE MANUAL ] USER MANUAL. v1.0a. May 7, 2008 D-OC-UM Alarm Panel USER MANUAL [ PRELIMINARY HARDWARE MANUAL ] Visit our website at www.dpstelecom.com for the latest PDF manual and FAQs. May 7, 2008 D-OC-UM085.07010 v1.0a Revision History April 28, 2008 May

More information

TraceTek Sensing Module Installation, Operation and Maintenance Instructions DESCRIPTION SPECIFICATIONS APPROVALS TYPE NM

TraceTek Sensing Module Installation, Operation and Maintenance Instructions DESCRIPTION SPECIFICATIONS APPROVALS TYPE NM TTC-1 TraceTek Sensing Module Installation, Operation and Maintenance Instructions DESCRIPTION The nvent RAYCHEM TraceTek TTC-1 sensing module is used with TraceTek sensing cables to detect liquid leaks.

More information

TrueCom. Building Communications Systems 5115-Series , Area of Rescue Communications System. Description

TrueCom. Building Communications Systems 5115-Series , Area of Rescue Communications System. Description TrueCom Building Communications Systems 5115-Series 5115-9001, -9002 Area of Rescue Communications System Description The Simplex 5115-9001 and -9002 Area of Rescue Communications System provides buildings

More information

Four-Door Access Controller User s Manual

Four-Door Access Controller User s Manual Four-Door Access Controller User s Manual V1.0.0 1 Table of Contents 1 Overview... 1 2 Device Appearance... 2 3 Device Installation and Uninstallation... 3 3.1 Device Installation... 3 3.2 Device Uninstallation...

More information

Pre-Installation Requirements:

Pre-Installation Requirements: AlphaRefuge 2100 Series (V3) Area of Refuge and Rescue Assistance system Installation, Use and Wiring Instructions Pre-Installation Requirements: 120V Power Determine Communication: 1. Dedicated analog

More information

SCR/SCRF Series Battery Charger

SCR/SCRF Series Battery Charger JD0036-00 Installing and Calibrating the Combined Alarm-Status Monitor (CASM) Scope Reference Materials Required 1. Installing a new CASM option (EJ0837-##) 1 2. Replacing a CASM circuit board (EN0014-##)

More information

Installation Instructions Model DLC

Installation Instructions Model DLC Installation Instructions Model DLC Device Loop Card INTRODUCTION OPERATION The SIEMENS Model DLC Device Loop Card is the interface for connection of FireFinder-XLS smoke detectors, manual stations, monitor

More information

Dual Column Dehydrating Breather Manual

Dual Column Dehydrating Breather Manual Dual Column Dehydrating Breather Manual DCB-MANUAL 1.6 Read and understand this manual prior to operating or servicing the products. SPX Transformer Solutions, Inc., Service & Components Division U.S.

More information

Public Safety DAS Annunciator Panel

Public Safety DAS Annunciator Panel Public Safety DAS Annunciator Panel 120 VAC Models: 1221-A, 1221-B, 1221-C Revision D 91117 48 VDC Models: 1221-A-48, 1221-B-48, 1221-C-48 24 VDC Models: 1221A-24, 1221-B-24, 1221-C-24 CAUTION: (Read This

More information

C-IV 60 CEILING FAN READ AND SAVE THESE INSTRUCTIONS. FAN RATING AC 120V. 60Hz

C-IV 60 CEILING FAN READ AND SAVE THESE INSTRUCTIONS. FAN RATING AC 120V. 60Hz C-IV 60 CEILING FAN READ AND SAVE THESE INSTRUCTIONS FAN RATING AC 120V. 60Hz Please do not use any electric or battery powered tools in the assembly and installation of this or any Matthews Fan Company

More information

6 Inch Speed Dome Installation Manual V2.0.0

6 Inch Speed Dome Installation Manual V2.0.0 6 Inch Speed Dome Installation Manual V2.0.0 2010-01 1 Thank you for purchasing our product. If there is any question or request, please do not hesitate to contact dealer. This manual is applicable to

More information

Product Manual SZ1145

Product Manual SZ1145 Product Manual SZ114 General Purpose Monitor Communicating Controls Description The SZ114 is a microprocessor-based monitoring and alarm interface designed to monitor up to four 1000 Ω platinum temperature

More information

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3 PRODUCT OVERVIEW

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3 PRODUCT OVERVIEW NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM Local configuration and monitoring with Raychem Touch 1500 touch screen display PRODUCT OVERVIEW The nvent RAYCHEM NGC-40 is a multipoint

More information

GLOBAL. InstallatIon & operation manual

GLOBAL. InstallatIon & operation manual InstallatIon & operation manual INDEX 1. INTRODUCTION... 5 2. FEATURES AND FUNCTIONS 2.1 Reporting Options... 2.2 Interfaces... 2.3 Programming... 2.4 Indicators and Controls...... 6 6 6 6 6 3. INSTALLATION...

More information

Table of Contents 1. OVERVIEW SYSTEM LAYOUT SPECIFICATIONS FUNCTION... 11

Table of Contents 1. OVERVIEW SYSTEM LAYOUT SPECIFICATIONS FUNCTION... 11 Table of Contents 1. OVERVIEW... 3 2. SYSTEM LAYOUT... 4 3. SPECIFICATIONS... 8 3.1 SYSTEM COMPONENTS...9 3.2 PLC INPUTS AND OUTPUTS...9 3.3 FUNCTION KEYS...10 3.4 DEFAULT SET POINTS AND TIMERS...10 4.

More information

WARNING: ELECTRICAL GROUNDING INSTRUCTIONS

WARNING: ELECTRICAL GROUNDING INSTRUCTIONS BK AND BKT BLOWER ACCESSORY INSTALLATION INSTRUCTIONS Model BK Manually led Blower Model BKT Thermostatically led Blower WARNING: ELECTRICAL GROUNDING INSTRUCTIONS This appliance is equipped with a three-prong

More information

Safety, Installation, and Operation Manual

Safety, Installation, and Operation Manual Automatic Steam Humidifier Control Safety, Installation, and Operation Manual READ COMPLETE INSTALLATION INSTRUCTIONS BEFORE STARTING. WARNING This product must be installed by a qualified heating and

More information

Please read and save these instructions. Should you have any questions or difficulty installing your fan, call us first!

Please read and save these instructions. Should you have any questions or difficulty installing your fan, call us first! IC/Air2 and IC/Air3 Installation Instructions and Owners Manual Please read and save these instructions. Should you have any questions or difficulty installing your fan, call us first! Customer Service

More information

Owner s Guide and Installation Manual

Owner s Guide and Installation Manual Tribeca Owner s Guide and Installation Manual English Form# M6000-01 20120416 2012 Casablanca Fan Co. Welcome Your new Casablanca ceiling fan is an addition to your home or office that will provide comfort

More information

Instruction Manual Model Backup Switch, 1 for 8

Instruction Manual Model Backup Switch, 1 for 8 Instruction Manual Model 2582-282 Backup Switch, 1 for 8 December 2011, Rev. 0 MODEL 2582 SWITCH CROSS TECHNOLOGIES INC. SWITCH ALARM PSA PSB ALARM OFFLINE ONLINE UNIT STATUS 1 2 3 4 5 6 7 8 BU PROT MODE

More information

Duct smoke housings, 4-wire D341/D341P and D342/D342P

Duct smoke housings, 4-wire D341/D341P and D342/D342P Duct smoke housings, 4-wire D341/D341P and D342/D342P en Installation manual Duct smoke housings, 4-wire Notices en 3 1 Notices These instructions cover the installation of the D341/D342 Duct smoke housings

More information

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3 NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM Local configuration and monitoring with Raychem Touch 1500 touch screen display PRODUCT OVERVIEW The Raychem NGC-40 is a multipoint electronic

More information

Automatic Air Dehydrator with Ethernet Communications Model ADH NETCOM

Automatic Air Dehydrator with Ethernet Communications Model ADH NETCOM Automatic Air Dehydrator with Ethernet Communications Model ADH NETCOM Environmental Technology, Inc. 1850 North Sheridan Street South Bend, Indiana 46628 USA (574) 233-1202 or (800) 234-4239 FAX (574)

More information

Table of Contents. What to Expect with Your Installation. Tools Needed. Mounting Options. Ceiling Bracket. Wiring.

Table of Contents.   What to Expect with Your Installation. Tools Needed. Mounting Options. Ceiling Bracket. Wiring. www.hunterfan.com Table of Contents What to Expect with Your Installation Congratulations on purchasing your new Hunter ceiling fan! It will provide comfort and performance in your home or office for many

More information

Interface and EOL Modules 8

Interface and EOL Modules 8 Interface and EOL Modules Interface Modules Series 420 25 Interface Modules Series 100 291 EOL Modules 293 254 Interface and EOL Modules Interface Modules Series 420 Interface Modules Serie 420 Interface

More information

CAN bus-based I/O module, CIO relays Mounting Terminals and wiring Commissioning, using the utility software

CAN bus-based I/O module, CIO relays Mounting Terminals and wiring Commissioning, using the utility software INSTALLATION AND COMMISSIONING GUIDE CAN bus-based I/O module, CIO 208 8 relays Mounting Terminals and wiring Commissioning, using the utility software DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45

More information

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA 99336 www.jmcvr.com 1-509-586-9893 Table of Contents TABLE OF FIGURES...1 OVERVIEW OF THE HRC CAPABILITIES...2 INSTALLATION AND

More information

ACCURATE ELECTRONICS INC PO BOX SW HALL BLVD BEAVERTON OR USA FAX

ACCURATE ELECTRONICS INC PO BOX SW HALL BLVD BEAVERTON OR USA FAX Page 1 of 10 Model 10807800 January 2014 ACCURATE ELECTRONICS INC PO BOX 1654 97075-1654 8687 SW HALL BLVD 97008 BEAVERTON OR USA 503.641.0118 FAX 503.646.3903 WWW.ACCURATE.ORG Practice Section 10807800

More information

Installation Instructions

Installation Instructions www.aquanta.io Aquanta by Sunnovations Inc. www.sunnovations.com Installation Instructions For online instructions go to: https://portal.aquanta.io/setup 1 Tools Needed: Phillips screw driver Flathead

More information

IDP-Zone-6 Six Zone Interface Module

IDP-Zone-6 Six Zone Interface Module INSTALLATION AND MAINTENANCE INSTRUCTIONS IDP-Zone-6 Six Zone Interface Module BEFORE INSTALLING If the modules will be installed in an existing operational system, inform the operator and local authority

More information

OVEN INDUSTRIES, INC.

OVEN INDUSTRIES, INC. OVEN INDUSTRIES, INC. OPERATING MANUAL Model 5C7-252 TEMPERATURE CONTROLLER With PLC Inputs Introduction Thank you for purchasing our controller. The Model 5C7-252 is an exceptionally versatile unit and

More information

Maintenance Manual ALARM SHELF 19D902821P1 & P2. ericssonz LBI-38496C. TABLE OF CONTENTS (Vendor Documentation)

Maintenance Manual ALARM SHELF 19D902821P1 & P2. ericssonz LBI-38496C. TABLE OF CONTENTS (Vendor Documentation) LBI-38496C Maintenance Manual ALARM SHELF 19D902821P1 & P2 TABLE OF CONTENTS (Vendor Documentation) CENTRAL PROCESSING UNIT... LPM S/BC5-6 (WinSystems) ANALOG INPUT... LPM-A/D-12M (WinSystems) EXPANDER

More information

ESS-2200 Double Station Scrub Sink. with Two Sensor Operated Gooseneck Spout. ESS-3200 Deluxe Double Station Scrub Sink

ESS-2200 Double Station Scrub Sink. with Two Sensor Operated Gooseneck Spout. ESS-3200 Deluxe Double Station Scrub Sink ESS-2000/3000 Series I.I. Rev. 2 (02/03) Code No. 016162 INSTALLATION INSTRUCTIONS SINGLE, DOUBLE AND TRIPLE STATION SENSOR OPERATED SYSTEMS ESS-2000 SERIES ESS-2100 Single Station Scrub Sink with One

More information

HALOGUARD TM IR MONITOR (OPTIONAL) FOUR or EIGHT POINT SCANNER INSTRUCTION MANUAL

HALOGUARD TM IR MONITOR (OPTIONAL) FOUR or EIGHT POINT SCANNER INSTRUCTION MANUAL HALOGUARD TM IR MONITOR (OPTIONAL) FOUR or EIGHT POINT SCANNER INSTRUCTION MANUAL SE R IA L N O. M O D E L N O. Tem p. Range 1 - = > 60 o F 2 - = 40-60 o F 3 - = < 40 o F G as Type 1 - R-11 2 - R-12 3

More information

ABLOY DA460 SWING DOOR OPERATOR. Installation and commissioning manual

ABLOY DA460 SWING DOOR OPERATOR. Installation and commissioning manual ABLOY DA460 SWING DOOR OPERATOR Installation and commissioning manual APPROVALS / STANDARDS 73/23/EEC (Low Voltage directive) 93/68/EEC (Low Voltage directive) 89/336/EEC (EMC directive) Statement of fire

More information

Product Manual SZ1144

Product Manual SZ1144 Product Manual SZ1144 Refrigeration Temperature Monitor Communicating Controls Description The SZ1144 is a microprocessor-based monitoring and alarm interface designed to monitor up to four 1000 Ω platinum

More information

Safety Please be mindful of the following for the installation, maintenance, wiring, and related inspections:

Safety Please be mindful of the following for the installation, maintenance, wiring, and related inspections: Operation Instructions for T300 Thank you for choosing the ViewX human-machine interface. For more efficient use of the ViewX human- machine interface, please read the included quick startup guide before

More information