Life Safety Crosswalk
|
|
- Austen Bruce
- 5 years ago
- Views:
Transcription
1 The Life Safety Crosswalk is an easy-to-use reference tool that crosswalks The Joint Commission s 2009 Life Safety with the 2008 and National Fire Protection Association s This crosswalk excerpt comes from HCPro s book, Life Safety Compliance Manual. The book explains The Joint Commission s 2009 life safety element-by-element, with expert analysis that will help you better comply with the requirements. The book s author is Brad Keyes, CHSP, safety consultant for The Greeley Company, a division of HCPro, Inc., in Marblehead, MA, and a former life safety specialist for The Joint Commission. For more information about the Life Safety Compliance Manual or to order a copy, go to Life Safety Compliance Manual 2008 HCPro, Inc. 1
2 Life Safety Crosswalk Administrative activities Statement of Conditions The design and management of an organization s physical environment must meet the requirements of the LSC. LS Your hospital designates responsibility A EC.5.20, 6 for LSC compliance assessment, electronic Statement of Conditions (e-soc) completion, and deficiency resolution management to an individual or group of individuals. LS Your organization s e-soc is maintained and up to date. Yes A EC.5.20, 2 LS Your organization resolves deficiencies identified in PFIs in accordance with the Joint Commission accepted schedule set forth in the PFI. Also see LS , s A EC.5.20, 5 Sufficient Progress CON-04 Interim Life Safety Measures (ILSM) During construction or other scenarios in which there are LSC deficiencies, your facility has mechanisms in place to protect staff members, patients, and visitors. LS During times when a fire alarm or sprinkler system is disabled in excess of four hours (during a 24-hour cycle), your facility contacts the appropriate response agency (e.g., the fire department), sets up a fire watch, and s these actions. Also see LS , 3. LS When obstructed or unusable exits exist, your organization posts signs to clearly identify alternative exits. Also see LS , 3. LS Periods of construction or other scenarios in which your facility cannot immediately meet the requirements in the LSC are addressed by your ILSM policy, in writing. Your policy also outlines when and how you will address any increased risks for life safety issues, including any special measures that must be followed. Also see LS , 3. Yes 3 A EC.5.50, 2 Footnote 3 A EC.5.50, 2 Bullet ; and Yes 2 A EC.5.50, HCPro, Inc. Life Safety Compliance Manual
3 LS During construction or in other scenarios in which your facility cannot immediately meet the requirements in the LSC, the hospital conducts daily inspections of the exits in affected areas as dictated by its ILSM policy. Also see LS , 3. LS When the hospital identifies LSC deficiencies that cannot immediately be corrected or during periods of construction, the hospital does the following: Provides temporary but equivalent fire alarm and detection systems for use when a fire system is impaired. The need for equivalent systems is based upon criteria in the hospital s ILSM policy. LS During construction or in other scenarios in which your facility cannot immediately meet the requirements in the LSC, the hospital maintains an appropriate level of firefighting equipment, as dictated by its ILSM policy. Also see LS , 3. LS During construction or in other scenarios in which your facility cannot immediately meet the requirements in the LSC, the hospital uses appropriate temporary partitions (smoke-tight, noncombustible, or limited-combustible materials), as dictated by its ILSM policy. Also see LS , 3. LS During construction or in other scenarios in which your facility cannot immediately meet the requirements in the LSC, the hospital heightens surveillance of its property and equipment, as dictated by its ILSM policy. Construction areas and related uses should be included in the surveillance. Also see LS , 3. 3 C EC.5.50, 2 Bullet 2 3 A EC.5.50, 2 Bullet 3 3 A EC.5.50, 2 Bullet 5 A EC.5.50, 2 Bullet 4 C EC.5.50, 2 Bullet 9 Life Safety Compliance Manual 2008 HCPro, Inc. 3
4 LS During construction or in other scenarios in which your facility cannot immediately meet the requirements in the LSC, the hospital ensures practices that maintain the lowest achievable flammable and combustible fire load, as dictated by its ILSM policy. Address proper storage, cleaning, and trash removal in such efforts. Also see LS , 3. LS During construction or in other scenarios in which your facility cannot immediately meet the requirements in the LSC, the hospital ensures that it gives additional training to staff members to use all types of firefighting equipment, as dictated by its ILSM policy. Also see LS , 3. LS During construction or in other scenarios in which your facility cannot immediately meet the requirements in the LSC, the hospital runs an additional quarterly fire drill for each shift, as dictated by its ILSM policy. Also see LS , 3, and EC , 1. LS During construction or in other scenarios in which your facility cannot immediately meet the requirements in the LSC, the hospital conducts monthly inspections and tests of temporary measures, as dictated by its ILSM policy. Also see LS , 3. LS The organization educates staff members on temporary fire safety measures, as well as building and construction issues, as dictated by its ILSM policy. Also see LS , 3. C EC.5.50, 2 Bullet 7 A EC.5.50, 2 Bullet 5 A EC.5.50, 2 Bullet 8 Yes C EC.5.50, 2 Bullet 3 3 A EC.5.50, 2 Bullet HCPro, Inc. Life Safety Compliance Manual
5 LS The hospital trains its workers to deal with impairments to building features designed to prevent the spread of fire, as dictated by its ILSM policy. Also see LS , 3. Note: The term compartmentalization refers to how the spread of fire is prevented through the use of building features (e.g., smoke barriers) to provide a safe exit route, dependent on a building s occupancy class. Healthcare occupancy 3 C EC.5.50, 2 Bullet 10 General building requirements Hospitals minimize the impact of fire and related effects through building design and other protective measures. LS National Fire Protection Association () 18/ requirements for height and construction type are met by the hospital s buildings. LS New healthcare occupancies are protected by appropriate automatic sprinkler systems. Existing healthcare occupancies contain the appropriate automatic sprinkler systems dependent on their construction type. LS Two-hour fire-rated walls adhere to the following guidelines: Such walls run from the floor to the underside of the deck above, and outside wall to outside wall. LS If two-hour fire-rated walls contain an opening, such openings must have a 1 1/2-hour fire rating. See LS , 3, and LS , 2. LS Hardware on fire-rated doors is fully operational (e.g., positive latching devices, automatic closing devices). Where two doors meet, the gap is no wider than 1/8 inch, and undercuts are 3/4 inch or less in size. Also see LS , 2. 3 A EC.5.20, 1 EC.A.1A (1,2) 3 A EC.5.20, 1 EC.A.1A (3) A EC.5.20, 1 EC.A.1B (1,2) A EC.5.20, 1 EC.A.1B (3) C EC.5.20, 1 EC.A.1C (1 5) 18/ , : ; ; ; ; Life Safety Compliance Manual 2008 HCPro, Inc. 5
6 LS A fire-rated door cannot feature unapproved protective plates more than 16 inches above its bottom. Note: Nonrated protective plates no higher than 48 inches from the bottom of the door are allowed on doors to hazardous rooms. LS Faces of 3/4-hour (or longer) fire-rated doors are clear of all objects except for informational signs. LS One-and-a-half-hour fire-rated dampers are in place on any ductwork penetrating two-hour FRR (or greater) walls. LS When utility devices penetrate fire-rated walls, regardless of the fire rating, the space surrounding the devices must be properly sealed with materials approved for the rating of that particular fire wall. Note: Expanding polyurethane foam is not acceptable in this scenario. LS The hospital fully complies with all appli cable provisions of the LSC in 18/19.1. EC.A.1D (1) EC.A.1D (2) A EC.5.20, 1 EC.A.1E EC.A.1H (1 6) : 2-4.5; : A-1999: 3-3.1; C EC.1.10, 5 Means of egress requirements Corridors, doors, stairways, and other means of egress are properly designed and maintained by the hospital. LS All doors in the path a person travels to exit the building (i.e., means of egress) are unlocked. LS In hospitals with an occupancy of 50 persons or greater, all doors in the path a person travels to exit the building swing toward the exit. LS Horizontal exit walls are required to be two-hour fire-resistance rated, and such walls run from the floor to the underside of the deck above, and outside wall to outside wall. Also see LS , 4. 3 A EC.5.20, 1 EC.A.5J (1) EC.A.5J (2) EC.A.5N (1 3) 18/ ; HCPro, Inc. Life Safety Compliance Manual
7 LS Buildings with exterior exit stairs are required to maintain walls that offer the same level of fire resistance between the exterior stairs and the interior of the build ing. Such walls must meet minimum requirements of at least a 10-ft. vertical extension from ground level to the uppermost landing or roof line, and at least 10 ft. horizontally. LS In new buildings, horizontal exit door windows (i.e., vision panels) are approved and do not have a center mullion. LS In new buildings, exterior walls have a one-hour fire rating for a minimum of 10 ft. in instances in which horizontal exit walls end at the exterior wall at less than a 180º angle. Openings in such an exterior wall must have a 3/4 hour fire rating. LS Hospitals are required to install handrails and railings on stairs and ramps on one side for existing healthcare occupancies, and on both sides for new healthcare occupancies. LS The hospital s exits shall discharge at grade level, or via a continuous, approved exit passageway that ends at a public way or an exterior exit discharge LS If your fire alarm or sprinkler system triggers the closing of a stairway door, it also closes the other doors in that stairway. LS Automatic-releasing devices are not permitted to hold open doors to boiler rooms, heater rooms, and mechanical equipment rooms situated in a means of egress in a new healthcare occupancy. LS Exit corridors adhere to the following requirements: 8 ft. wide in new buildings, 4 ft. wide in existing buildings. Modifications to existing corridors that exceed the 8-ft. width cannot reduce corridor width to less than 8 ft. EC.A.5L (1 3) C C C , EC.A.5H (1,2) 7.7 C : 18/ C C 18/ Life Safety Compliance Manual 2008 HCPro, Inc. 7
8 LS Objects protruding from corridor walls do not obstruct their width. Note: There are specific exceptions The Joint Commission will make for corridors that meet or exceed 6 ft. in width. Such exceptions (e.g., hand-rub dispensers, retractable desks) must: Be 36 inches or less in width Project 6 inches or less into the corridor Be 48 inches away from other such features Be above handrail height C 18/ LS All exit paths are free of unattended items that are not considered in use. C EC.5.20, 1, EC.A.6F LS Exit access doors and exit doors do not have objects on them that could in any way conceal, obscure, or confuse access to the exit route. Such items include mirrors, hangings, and draperies. C EC.5.20, 1, EC.A.6G LS A building s floors or compartments must have, at a minimum, two approved exits that are located remotely from each other. C EC.5.20, 1, EC.A.5A LS A minimum of two exits, located remotely from one another, exist for patient sleeping rooms or suites of such rooms that exceed 1,000 sq. ft. C EC.5.20, 1, EC.A.2C 18/ LS A minimum of two exits, located remotely from one another, exist for rooms or suites of rooms that are not used as patient sleeping rooms that exceed 2,500 sq. ft. C EC.5.20, 1, EC.A.2D 18/ LS Suites containing patient sleeping rooms cannot exceed 5,000 sq. ft. Suites that do not contain patient sleeping rooms cannot exceed 10,000 sq. ft. No intervening rooms in the suites can contain hazardous areas. C EC.5.20, 1, EC.A.2E 18/ to 18/ HCPro, Inc. Life Safety Compliance Manual
9 LS From any point in suites containing patient sleeping rooms, the hospital maintains a travel distance of 100 ft. or less to an exit access door. LS From any point in suites that do not contain patient sleeping rooms and that have up to one intervening room, the hospital maintains a travel distance of 100 ft. or less to an access door. In such suites with two intervening rooms, the hospital maintains a travel distance of 50 ft. or less to an access door. LS The facility s patient sleeping rooms directly open into an exit access corridor. LS The doors to patient sleeping rooms are unlocked. LS From any point in a patient sleeping room, the hospital maintains a travel distance of 50 ft. or less to a room door. LS The hospital maintains a travel distance of 100 ft. or less from any room door and an exit in existing buildings, or 150 ft. or less when an approved automatic sprinkler system exists. The hospital maintains a travel distance of 150 ft. or less from any room door and an exit in new buildings. LS The hospital maintains a travel distance of 150 ft. or less from any point in a room and an exit in existing buildings, or a minimum of 200 ft. when an approved automatic sprinkler system exists. The hospital maintains a travel distance of 200 ft. or less from any point in a patient room and an exit in new buildings. LS Dead-end corridors in new buildings do not exceed 30 ft. C C EC.5.20, 1, EC.A.2F (1) EC.5.20, 1, EC.A.2F (2,3) C EC5.20, 1 EC.A.2G 18/ / / A 18/ EC.A.5B (1) EC.A.5B (2) / EC.B.5B (2) EC.A.5B (3) / EC.B.5B (3) EC.B.5B (4) 18/ / / Life Safety Compliance Manual 2008 HCPro, Inc. 9
10 18/ LS All points of any means of egress have adequate illumination. This includes angles and intersections of corridors and passageways, stairways, stairway landings, exit doors, and exit discharges. LS The hospital arranges the illumination of all means of egress (including any exit discharges) such that the area will not be left in darkness if a single light bulb or fixture fails. LS For all stairs that serve five or more stories of the building, the hospital posts signs on each floor landing of the stairwell that indicate the following information: the story, the stairwell, the top and bottom, and the direction and story of the exit discharge. The signage must be placed 5 ft. from the floor of the landing so that it can be seen whether the door is open or closed. LS The hospital posts signage on any door, passage, or stairway that someone could mistake for an exit route but is not an exit or access to an exit that says No Exit. LS The facility has exit signs that are visible in circumstances in which the exit is not easily determinable. Such signs must be lit adequately and contain lettering that is a minimum of 4 inches high, or 6 inches high if the sign is lit externally. LS All other LSC requirements pertaining to the means of egress as set forth in 18/19.2 are met by the hospital. EC.A.5C C C EC.A.5I EC.A.5K (1 3) ; ; ; C 18/ HCPro, Inc. Life Safety Compliance Manual
11 Protection The organization protects individuals from fire and smoke by providing and maintaining building features. LS The facility encloses existing vertical openings, not including exit stairs, in construction with a one-hour fire rating. For new construction, the facility en closes vertical openings connecting three or fewer floors, not including exit stairs, with one-hour fire-resistance rated (FRR) walls, and those connecting four or more floors with two-hour FRR walls. See LS , 4. Note: The Joint Commission deems vertical openings to include, but does not limit them to com - municating stairs, ramps, elevator shafts, ventilation shafts, light shafts, trash chutes, linen chutes, and utility chases. LS The hospital protects all hazardous areas (including but not limited to the areas listed below) with walls and doors in a manner consistent with 18/ Also see LS , 5 and LS , 18. Note: The following subsections of this provide guidance on assessing the protection of hazardous areas and identifying deficiencies. A. Boiler/fuel-fired heater rooms Existing boiler/fuel-fired heater rooms are sprinklered, resist the passage of smoke, and contain self-closing doors or doors with automatic closing devices; or the walls are one-hour FRR and the doors are 3/4-hour FRR New boiler/fuel fired heater rooms are sprinklered and the walls are one-hour FRR and the doors are 3/4-hour FRR EC.A.4A (1 8); EC.B.4A (1 8) EC.A.2K Table 3.A.3 and 3.A.4 18/ / / Life Safety Compliance Manual 2008 HCPro, Inc. 11
12 18/ B. Central/bulk laundries exceeding 100 sq. ft. Existing central/bulk laundries exceeding 100 sq. ft. are sprinklered, resist the passage of smoke, and contain self-closing doors or doors with automatic closing devices; or the laundries walls are one-hour FRR and the doors are 3/4-hour FRR New central/bulk laundries exceeding 100 sq. ft. are sprinklered and the walls are one-hour FRR and the doors are 3/4-hour FRR C. Flammable liquid storage rooms (reference : , ) Existing flammable liquid storage room walls are two-hour FRR and doors are 1 1/2-hour FRR 18/ New flammable liquid storage rooms are sprinklered, walls are two-hour FRR, and doors are 1 1/2-hour FRR D. Laboratories ( contains information to help you determine whether a laboratory should be classified as a severe hazard area) 18/ Existing laboratories that are not severe hazard areas are sprinklered, resist the passage of smoke, and contain self-closing doors or doors with automatic closing devices; or the walls are one-hour FRR and the doors are 3/4-hour FRR. New laboratories that are not severe hazard areas are sprinklered, resist the passage of smoke, and contain self-closing doors or doors with automatic closing devices HCPro, Inc. Life Safety Compliance Manual
13 Existing laboratories that are severe hazard areas (reference : ) have walls that are two-hour FRR and doors that are 1 1/2-hour FRR. When the laboratory is sprinklered, the walls are one-hour FRR, and the doors are 3/4-hour FRR. New laboratories that are severe hazard areas (reference : ) are sprinklered, the walls are one-hour FRR, and the doors are 3/4-hour FRR. Existing flammable gas storage rooms have walls that are two-hour FRR and doors that are 1 1/2-hour FRR (reference : ). New flammable gas storage rooms are sprinklered, have walls that are two-hour FRR and doors that are 1 1/2-hour FRR (reference : ). E. Maintenance repair shops Existing maintenance repair shops are sprinklered, resist the passage of smoke, and contain self-closing doors or doors with automatic closing devices; or the walls are one-hour FRR and the doors are 3/4-hour FRR 18/ New maintenance repair shops are sprinklered, walls are one-hour FRR, and the doors are 3/4-hour FRR Life Safety Compliance Manual 2008 HCPro, Inc. 13
14 F. Piped oxygen tank supply rooms (reference : ) Existing piped oxygen tank supply rooms walls are one-hour FRR and the doors are 3/4-hour FRR : New piped oxygen tank supply rooms are sprinklered, walls are one-hour FRR, and the doors are 3/4-hour FRR G. Paint shops that are not severe hazard areas Existing paint shops that are not severe hazard areas are sprinklered, resist the passage of smoke, and contain self-closing doors or doors with automatic closing devices; or the walls are one-hour FRR and the doors are 3/4-hour FRR 18/ New paint shops that are not severe hazard areas are sprinklered, the walls are one-hour FRR, and the doors are 3/4-hour FRR H. Soiled linen rooms Existing soiled linen rooms are sprinklered, resist the passage of smoke, and contain self-closing doors or doors with automatic closing devices; or the walls are one-hour FRR and the doors are 3/4-hour FRR 18/ New soiled linen rooms are sprinklered, the walls are one-hour FRR, and the doors are 3/4-hour FRR HCPro, Inc. Life Safety Compliance Manual
15 18/ I. Storage rooms Existing storage rooms for combustible materials that exceed 50 sq. ft. are sprinklered, resist the passage of smoke, and contain self-closing doors or doors with automatic closing devices; or the walls are one-hour FRR and the doors are 3/4-hour FRR New storage rooms for combustible materials ranging in size from sq. ft. are sprinklered, resist the passage of smoke, and contain selfclosing doors or doors with automatic closing devices New storage rooms for combustible materials that exceed 100 sq. ft. are sprinklered, the walls are one-hour FRR, and the doors are 3/4-hour FRR J. Trash collection rooms Existing trash collection rooms are sprinklered, resist the passage of smoke, and contain self-closing doors or doors with automatic closing devices; or the walls are one-hour FRR and the doors are 3/4-hour FRR 18/ New trash collection rooms are sprinklered, the walls are one-hour FRR, and the doors are 3/4-hour FRR LS In gift shops that store or display combustibles in hazardous quantities, the walls are one-hour fire-resistance rated (FRR) and doors are 3/4-hour FRR. In existing buildings, such shops are sprinklered and use walls and doors to limit the passage of smoke. EC.A.2M (1,2) EC.B.2M (1,2) 18/ Life Safety Compliance Manual 2008 HCPro, Inc. 15
16 18/ LS Existing wall and ceiling interior finishes limit smoke development and the spread of flames and have a Class A or B rating. New walls and ceiling interior finishes must have a Class A rating. LS Interior floor finishes in smoke compartment corridors that are not sprinklered have a Class I radiant flux rating when they are newly installed. LS Existing corridor partitions meet the following requirements: 1/2-hour FRR; continue from floor slab to the above floor or roof slab; continue through concealed areas; are sealed properly; and limit the transfer of smoke by design. Note: The Joint Commission permits unsealed spaces not to exceed 1/8-inch around pipes, conduits, ducts, and wires above the ceiling. In sprinklered smoke compartments, it is permissible for corridor partitions to end at the ceiling as long as the ceiling is designed to limit the passage of smoke. Such limitation can be achieved by exposed, suspended-grid acoustical tile ceilings; sprinkler piping and sprinklers that penetrate the ceiling; ducted heating, ventilating, and HVAC supply and return-air diffusers; and lighting fixtures that are recessed. LS Corridor walls in new buildings are built to limit the transfer of smoke. EC.A.1F; EC.B.1F EC.A.1G; EC.B.1G EC.A.2A (1 3) ; EC.B2A ; (2) LS Fixed fire windows installed in corridor walls do not exceed 25% of the size of the wall in smoke compartments that are not sprinklered. Note: The Joint Commission permits existing window installations that are in compliance with previously accepted LSC criteria. EC.A.2H (1,2) HCPro, Inc. Life Safety Compliance Manual
17 ; LS Corridor doors in existing buildings contain at least a 1 3/4-inch solid-bonded wood core or equivalent. Such doors do not contain ventilating louvers or transfer grills. Exceptions include bathrooms, toilets, and sink closets that do not have any flammable or combustible material. LS There are no nonrated protective plates positioned higher than 48 inches from the bottom of corridor doors. LS Corridor doors adhere to the following requirements: fitted with positive latching hardware; arranged to restrict the passage of smoke; have hinges that allow them to swing; in paired doors, the meeting edges are 1/8 inch or less apart; undercuts are 1 inch or less; and do not contain roller latches. Note: The Joint Commission permits existing doors to have a device that keeps the door closed when 5-ft.-lb force is applied to the edge of the door. LS The hospital ensures the installment of openings in vision panels or doors in corridor walls (not including compartments containing patient sleeping rooms) are one half the distance from the floor to the ceiling or less. In new buildings, such openings must be 80 square inches or less, and in existing buildings, 20 square inches or less. Note: Examples of such openings include mail slots and pass-through windows in laboratories, pharmacies, and cashier stations. C EC.5.0, 1 EC.A.2I (2,5) EC.A.2I (6) 18/ / ; 18/ ; EC.A.2I (1,3,4) EC.A.2J (1,2) EC.B.2J (1,2) 18/ Life Safety Compliance Manual 2008 HCPro, Inc. 17
18 90A-1999: LS The hospital does not use corridors that serve adjoining areas for a portion of an air supply, air return, or exhaust air plenum. Note: The Joint Commission s interpretation of the applicable code permits incidental air movement between rooms and corridors (e.g., isolation rooms). This is in recognition of hospitals need for pressure differentials. See the Joint Commission for specific examples. LS For every story of existing buildings that exceed 30 patients in sleeping rooms, the hospital provides a minimum of two smoke compartments. LS For every story of new buildings with patient sleeping or treatment rooms, stories designated as non-sleeping with an occupant capacity that meets or exceeds 50 people, or on stories that are usable or unoccupied, the hospital provides a minimum of two smoke compartments. LS Smoke barriers are in place so that smoke compartments do not exceed 22,500 sq. ft., and the travel distance does not exceed 200 ft. from any point in the compartment to a smoke barrier door. LS Smoke compartment size is in compliance with 18/ EC.A.5D; EC.B.5E A EC.5.20, 1 EC.A.3A A EC.5.20, 1 EC.B.3A (1 3) ; EC.A.3B (1,2) EC.B.3B (1,2) 18/ C 18/ LS All smoke compartment barriers must extend from the floor slab below to the floor slab (or roof slab) above and extend continuously from outside wall to outside wall, through all interstitial spaces, and all penetrations are properly sealed. LS Smoke barriers have a 1/2-hour FRR in existing buildings, and one-hour FRR for new buildings. EC.A.3C (1,2) EC.B.3C (1,2) 18/ EC.A.3C (3) EC.B.3C (3) 18/ HCPro, Inc. Life Safety Compliance Manual
19 18/ ; LS Ducts penetrating any smoke barriers in existing buildings have smoke dampers protecting them that close upon activation of a smoke detector. Such detectors must be located in the duct system or the area that serves the smoke compartment. Note: The Joint Commission does not require dampers in common smoke barriers for existing buildings with two adjacent compartments that are sprinklered. LS Air transfer openings that extend through smoke barriers in ceiling areas and are in use as unducted common plenum for supply or return air are protected by smoke dampers. LS Where smoke barrier walls or doors have fixed fire window assemblies, such assemblies have a 20-minute FRR and do not exceed 25% of the size of the barrier in which they are installed. Note: The Joint Commission will accept existing window installations that have fixed wire glass or fire-rated glazing, are 1,296 square inches in size or smaller, and are set in approved metal frames. LS Smoke barrier doors meet the following requirements: They are self- or automatic closing; they are built with 1 3/4-inch or greater solid-bonded wood core or its equal; they are fit to resist the passage of smoke; where doors are paired, the gap where the doors meet does not exceed 1/8 inch; the undercut does not exceed 3/4 inch; and such doors do not contain nonrated protective plates that are positioned in excess of 48 inches from the door s bottom. EC.A.3F EC.A.3G EC.A.3H EC.B.3H EC.A.3E (1,2) EC.B.3E (1.2) ; ; EC.A.3D (1 4) EC.B.3D (1 4) 18/ ; 18/ ; Life Safety Compliance Manual 2008 HCPro, Inc. 19
20 LS All other LSC requirements for protection from fire and smoke related to 18/19.3 are met by the organization. Note: See The Joint Commission s Web site, for requirements related to the accepted amount of alcohol-based hand rub permitted within one smoke compartment. Fire Alarm The organization provides and maintains fire alarm systems. LS The hospital achieves automatic transmission of the hospital s fire alarm signal via at least one of the following: An auxiliary fire alarm system that has a direct connection to the fire department servicing the facility, in compliance with : 6-16 A central station service, in compliance with : 5-2 A proprietary supervising station system, in compliance with : 5-3 According to The Joint Commission policy for a manual transmission system. For details, see www. jointcommission.org/lsc. A remote supervising station fire alarm system as described in : 5-4. LS The hospital locates its master fire alarm control panel in a continuously occupied environment that is protected (i.e., enclosed with one-hour FRR walls and 3/4-hour FRR doors), or where there is a smoke detector. Also see LS , 5. 3 A C 18/ : : : : A : and HCPro, Inc. Life Safety Compliance Manual
21 LS The local fire department or equivalent agency approves the location of the remote ancillary annunciator panel. LS All fire alarm requirements pertaining to the LSC related to / are met by the hospital. Extinguishment Hospitals have a system for extinguishing fires and maintain those systems. LS The hospital monitors automatic sprinkler system components with its fire alarm system. LS The hospital connects its fire alarm system to water flow alarms. LS Approved automatic sprinkler system piping supports are free of damage and not loose. LS Approved automatic sprinkler system piping does not support any other item. LS There is no damage, corrosion, foreign materials, or paint present on sprinkler heads. LS The hospital maintains at least 18 inches of space below sprinkler deflectors and the top of any storage. Note: The Joint Commission permits hospitals to extend perimeter wall and stack shelving up to the ceiling in those instances in which such items are not directly below a sprinkler head. LS Isolated, hazardous areas protected by limited area sprinkler systems connected to the domestic water system feature a shutoff valve and have no more than six sprinkler heads. In new installations that have two or more sprinkler heads serving one area, the hospital provides water flow detection. C C 18/ A 18/ A C : C : C : EC.A.6B : A Life Safety Compliance Manual 2008 HCPro, Inc. 21
22 LS The hospital limits the travel distance from any point to the closest fire extinguisher to no more than 75 ft. LS Grease-producing cooking devices (e.g., fat fryers, ranges, griddles, or broilers) have Class K fire extinguishers within 30 ft. LS Exhaust hoods, an exhaust duct system, and grease-removal device that do not have mesh filters are present on greaseproducing cooking devices. LS Grease-producing cooking devices have an automatic fire-extinguishing system that will deactivate the fuel source. LS The automatic fire extinguishing systems for grease-producing cooking devices does the following: Deactivates the fuel source. LS Grease-producing cooking devices have an automatic fire-extinguishing system that will control the exhaust fans according to design. LS All automatic extinguishing requirements in the LSC related to : 18/ are met by the hospital. C 18/ : C 18/ ; : C 18/ ; : A 18/ ; : and A 18/ ; : and C 18/ ; : and C 18/ HCPro, Inc. Life Safety Compliance Manual
23 Special provision Special features that protect occupants from fire and smoke hazards exist and are maintained by the hospital. LS Hospitals that have buildings without windows, or portions of buildings without windows, adhere to the requirements set forth in 18/ LS Hospitals have an approved automatic sprinkler system, meeting the requirements of , in new high-rise buildings. C A 11.8 Building services The hospital protects occupants from the hazards of fire and smoke by the provision and maintenance of building services. LS Patient sleeping areas must not have fireplaces, and in those areas where fireplaces are permitted, the hospital maintains one-hour fire-resistance rated (FRR) construction separating the fireplace and patient sleeping spaces. LS The hospital provides fireplace enclosures for all fireplaces. Such enclosures are guaranteed to resist breakage up to 650 F and are built with heat-tempered glass or other material. LS Newly installed fireplace hearths are raised, at a minimum, 4 inches above the floor. LS The hospital equips new elevators with: Firefighters service key recall. Smoke detector automatic recall. Firefighters service emergency in-car key operation. Machine room smoke detectors. Elevator lobby smoke detectors. The hospital must also meet these requirements for existing elevators with a travel distance of 25 ft. or more above or below the level that best serve firefighters needs. C 18/ C 18/ C C 18/ Life Safety Compliance Manual 2008 HCPro, Inc. 23
24 LS Trash chutes discharge into designated rooms. Such rooms serve no other purpose. C 18/ C ; : C 18/ : LS In new buildings, vent openings in linen and waste chutes extend through the roof and into the outside atmosphere. LS Buildings that exceed two stories place approved automatic sprinkler systems in the following locations: above the top of openings to the linen and waste chute on the lowest service levels, and above the service door opening on alternating floors. LS Linen and waste chute service inlet door assemblies in existing buildings have a 3/4-hour FRR, or a one-hour FRR if such an assembly opens into a corridor. In new buildings, such assemblies are onehour FRR, or 1 1/2-hour FRR for chutes of four or more stories. LS The hospital places self-closing and positive latching devices on all linen and waste chute inlet and discharge service doors. C 18/ C 18/ ; : C 18/ C 18/ / ; : LS Discharge door assemblies for linen and trash chutes have a one-hour FRR. LS Collection rooms for linen and waste chute discharge are separated from the corridor by one-hour FRR walls HCPro, Inc. Life Safety Compliance Manual
25 LS All other LSC building service requirements related to 18/19.5 are met by the hospital. C 18/19.5 Operating features Operating features that conform to fire and smoke prevention requirements are provided and maintained by the hospital. LS Combustible decorations that are not flame-retardant are prohibited by the hospital. LS The hospital locates soiled linen and trash receptacles greater than 32 gal. in a room that has the protections of a hazardous area. Recycling containers are included in this requirement. LS In smoke compartments with patient sleeping and treatment areas, the organization prohibits portable space heaters. LS All other LSC operating feature requirements related to 18.7/19.7 are met by the hospital. Also see EC , 1. C 18/ C 18/ C 18/ C 18.7 and 19.7 Life Safety Compliance Manual 2008 HCPro, Inc. 25
26
Accreditation Program: Hospital
ccreditation Program: Hospital Life Safety 2008 The Joint ommission on ccreditation of Healthcare Organizations ccreditation Program: Hospital hapter: Life Safety Standard LS.0001 The [organization] designs
More informationFirst Aspen Federal Regulation Set: K LSC 2000 Health Existing
First Aspen Federal Regulation Set: K 01.01 LSC 2000 Health Existing K 0000 Title CFR Type INITIAL COMMENTS Memo K 0011 If the building has a common wall with a nonconforming building, the common wall
More informationChanges to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH)
Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH) The following represents a review of the Life Safety chapter of the new 2018 Joint Commission CAMH manual for
More informationAgency for Health Care Administration
Page 1 of 92 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS Type Memo Tag FED - KA100 - General Requirements - Other Title
More informationNFPA 101 Code Update from 2012 Edition to the 2015 Edition
NFPA 101 Code Update from 2012 Edition to the 2015 Edition Presented by: Gary Furdell AHCA Fire Protection Specialist 1 2 2012 Update to 2015 Chapter 18 New Health Care Occupancies 4 18.1.3.2 Atrium walls
More informationAgency for Health Care Administration
Page 1 of 100 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS CFR Type Memo Tag FED - KA100 - General Requirements - Other
More informationAgency for Health Care Administration
Page 1 of 92 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0100 - General Requirements
More informationAgency for Health Care Administration
Page 1 of 41 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K0011 - LIFE SAFETY CODE STANDARD If the building has a common wall with a nonconforming building, the common
More informationAgency for Health Care Administration
Page 1 of 51 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K0130 - MISCELLANEOUS Title MISCELLANEOUS OTHER LSC DEFICIENCY NOT ON 2786 FED - K9999 - FINAL OBSERVATIONS Title
More informationAgency for Health Care Administration
Page 1 of 75 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K0100 - General Requirements - Other Title General Requirements - Other General Requirements - Other List in the REMARKS
More informationAgency for Health Care Administration
Page 1 of 94 ST - K0000 - Initial Comments Title Initial Comments Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0100 - General
More informationAgency for Health Care Administration
Page 1 of 75 ST - K0000 - Initial Comments Title Initial Comments Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0001 - OTHER
More informationTHE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4
THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1 QUESTIONS How To Ask a Question: POLLING There will be occasional
More informationBalloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition
Copyright National Fire Protection Association 2013. All rights reserved. This copy is solely for your personal, noncommercial use in connection with participation in the NFPA Standards Development Process.
More informationNFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES
NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES Sharon S. Gilyeat, P.E., Principal Koffel Associates, Inc. www.koffel.com sgilyeat@koffel.com Expertly Engineering Safety From Fire
More informationTHE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5
THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5 AGENDA: Ambulatory Health Care & Business Occupancies Definitions / Examples Mixed & Contiguous Occupancies Ambulatory Health Care &
More informationCHAPTER 7 ALTERATIONS LEVEL
CHAPTER 7 ALTERATIONS LEVEL 2 SECTION 701 GENERAL 701.1 Scope. Level 2 alterations as described in Section 404 shall comply with the requirements of this chapter. Exception: Buildings in which the reconfiguration
More informationTaming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes JENSEN & HALSTEAD LTD.
Taming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes Comparing the Codes: NFPA 101 Life Safety Code (2000) (NFPA) International Building Code (2012) (IBC) Chicago
More informationChanges to Environment of Care and Life Safety Chapters Related to Life Safety Code Updates
Issued June 28, 207 Changes to Environment of Care and Life Safety Chapters Related to Life Safety Code Updates Environment of Care (EC) Chapter Nursing Care Center (NCC) Accreditation Program Standard
More informationUNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY
Revision No.: 11 Page 1 of 12 I. PURPOSE This procedure establishes a tool to help maintain a safe environment for all patients, visitors and staff by evaluating the loss of a life safety feature during
More informationK SURVEY FOR DATE OF PLAN APPROVAL SURVEY UNDER
DEPARTMENT OF HEALTH AND HUMAN SERVICES CENTERS FOR MEDICARE & MEDICA SERVICES FIRE SAFETY SURVEY REPORT - HEALTH CARE Form Approved OMB No. 0938-0242 1. (A) PROVER NUMBER 1. (B) MEDICA I.D. NO. 1. HOSPITAL
More informationLife Safety Code Common Discepancies Course# LSC102. EZpdh.com All Rights Reserved
Life Safety Code Common Discepancies Course# LSC102 EZpdh.com All Rights Reserved 1. K147 Electrical - Electrical wiring and equipment shall be in accordance with NFPA 70, National Electrical Code. 9.1.2
More informationNew DATE OF BLDG. PERMIT OR PLAN APPROVAL: SURVEYOR (SIGNATURE) TITLE OFFICE DATE REVIEW AUTHORITY OFFICIAL (SIGNATURE) TITLE OFFICE DATE
DEPARTMENT OF HEALTH & HUMAN SERVICES CENTERS FOR MEDICARE & MEDICAID SERVICES FIRE SAFETY SURVEY REPORT - AMBULATORY SURGICAL CENTERS Medicare 1. (A) PROVIDER NUMBER Identifying information as shown in
More informationFIRE SAFETY SURVEY REPORT 2000 CODE - HEALTH CARE Medicare Medicaid
DEPARTMENT OF HEALTH AND HUMAN SERVICES CENTERS FOR MEDICARE & MEDICA SERVICES FIRE SAFETY SURVEY REPORT - HEALTH CARE Medicare Medicaid 1. (A) PROVER NUMBER PART I Life & Safety Code, New and Existing
More informationReport on First Revisions with Statement June 2014 NFPA 101
101 FR3002 SAF-HEA (18.1.3.2) Recommendation: 18.1.3.2 Atrium walls in accordance with 6.1.14.4.6 shall be permitted to serve as part of the separation required by 6.1.14.4.1 for creating separated occupancies
More informationFIRE SAFETY SURVEY REPORT 2000 CODE - HEALTH CARE Medicare Medicaid
DEPARTMENT OF HEALTH AND HUMAN SERVICES CENTERS FOR MEDICARE & MEDICA SERVICES FIRE SAFETY SURVEY REPORT - HEALTH CARE Medicare Medicaid 2. NAME OF FACILITY 2. (A) MULTIPLE CONSTRUCTION (BLDGS) 3. SURVEY
More informationFire & Life Safety Code Compliance. Common Safety Deficiencies and Tips for Compliance for Long Term Care and Skilled Nursing Facilities
Fire & Life Safety Code Compliance Common Safety Deficiencies and Tips for Compliance for Long Term Care and Skilled Nursing Facilities LTC, Skilled Nursing Facilities COMMON LIFE SAFETY DEFICIENCIES
More informationPresented by: Brad Keyes, CHSP Senior Consultant Keyes Life Safety Compliance, LLC
Presented by: Brad Keyes, CHSP Senior Consultant Keyes Life Safety Compliance, LLC Changes to Life Safety Compliance Healthcare leaders will have to deal with many changes in Life Safety compliance when
More informationFIRE SAFETY SURVEY REPORT AMBULATORY SURGICAL CENTERS (ASC) & END STAGE RENAL DISEASE (ESRD) MEDICARE
DEPARTMENT OF HEALTH AND HUMAN SERVICES CENTERS FOR MEDICARE & MEDICA SERVICE Form Approved OMB Exempt FIRE SAFETY SURVEY REPORT AMBULATORY SURGICAL CENTERS (ASC) & END STAGE RENAL DISEASE (ESRD) MEDICARE
More informationLIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE
California Society for Healthcare Engineering SOUTHERN CALIFORNIA SEMINAR LIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE 1 PROGRAM AGENDA Adoption of 2012 LSC CMS Final Rule / Amendments
More informationNFPA 101 Life Safety Code Culture change 2012
NFPA 101 Life Safety Code Culture change 2012 Produced by Kansas Fire Marshal April, 2012 On March 9, 2012 Centers for Medicare & Medicaid Services implements a policy where they have formally adopted
More informationAgency for Health Care Administration
Page 1 of 98 ST - Y0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. Based on the LSC surveyor's determination
More informationAgency for Health Care Administration
Page 1 of 130 ST - K0000 - Initial Comments Title Initial Comments Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. Based on the LSC
More informationFire and Life Safety Review Form
Exits/Egress Fire and Life Safety Review Form 1. Doors shall swing in the direction of egress travel where serving and occupancy load of 50 or more. IFC 1010.1.2.1 2. Egress shall be readily openable from
More informationMeasures (ILSM) Process
Managing the Interim Life Safety Measures (ILSM) Process 1 A Program for The Texas Association of Healthcare Facility Management Monday, April 30, 2012 Robert H. Bartels, CHFM CHSP CHEP SASHE President,
More informationChanges to Environment of Care, Equipment Management, and Life Safety Chapters Related to Life Safety Code Updates
Issued September 20, 2017 Changes to Environment of Care, Equipment Management, and Life Safety Chapters Related to Life Safety Code Updates Environment of Care (EC) Chapter Home Care (OME) Accreditation
More informationNFPA 101 and NFPA 99, 2012 Editions Code Update. where art meets engineering
NFPA 101 and NFPA 99, 2012 Editions Code Update where art meets engineering Austin Dallas Denver Houston Kansas City Miami Nashville Phoenix Richmond Washington DC NFPA 101 and NFPA 99 where art meets
More informationC. None (No sprinkler system) K3 E. NUMBER OF BEDS CERTIFIED FOR MEDICAID
DEPARTMENT OF HEALTH AND HUMAN SERVICES CENTERS FOR MEDICARE & MEDICAID SERVICES FIRE SAFETY SURVEY REPORT - 2000 LIFE SAFETY CODE Intermediate Care Facilities for the Mentally Retarded LARGE PART I Figure
More informationInterim Life Safety Measures. Healthcare Construction Certificate - Level 1
Interim Life Safety Measures Purpose of Interim Life Safety Management BASIC SAFETY: During renovations projects in healthcare occupancies, the basic level of protection for the occupants must be maintained
More informationBalloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition
Copyright National Fire Protection Association 2013. All rights reserved. This copy is solely for your personal, noncommercial use in connection with participation in the NFPA Standards Development Process.
More informationTop (15) Life Safety Code Deficiencies and Tips for Compliance (10/01/2011 thru 02/22/2012)
1. K62 Automatic Sprinkler Systems - Automatic sprinkler systems are continuously maintained in reliable operating condition and are inspected and tested periodically. 18.7.6, 19.7.6, 4.6.12, NFPA 13,
More informationEC EP 14 All other electrical K-920 equipment in patient care vicinity NFPA , Chapter 10
MSL Healthcare Partners, Inc. Wild Card EPs Paraphrase K-tag # EC.02.04.03 EP 14 All other electrical K-920 equipment in patient care vicinity NFPA 992012, Chapter 10 K-924 K-928 K-931 K-tag Description
More informationAgency for Health Care Administration
Page 1 of 21 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0300 - Other
More informationASCs & LSC. Alice Epstein, DFASHRM, FNAHQ
, DFASHRM, FNAHQ Disclaimer The purpose of this presentation is to provide information, rather than advice or opinion. It is accurate to the best of the speaker's knowledge as of the date of the presentation.
More informationProcedure DESCRIPTION/OVERVIEW
Applies To: UNMH Responsible Department: Life Safety Revised: 07.08.16 Procedure Patient Age Group: (X ) N/A ( ) All Ages ( ) Newborns ( ) Pediatric ( ) Adult DESCRIPTION/OVERVIEW To assure the safety
More informationAgency for Health Care Administration
Page 1 of 34 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0001 - OTHER
More informationAgency for Health Care Administration
Page 1 of 133 ST - Y0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - Y1001 - Awareness of the
More informationBuilding Codes & Standards for Healthcare. Healthcare Construction Certificate - Level 1
Building Codes & Standards for Healthcare Building Codes and Standards AHJs Codes Defend in Place Walls Sprinklers Fire Alarm Important Dates for Healthcare Facilities 7/5/16 NFPA Life Safety Code 101
More informationPRINTED: 06/09/2017 FORM APPROVED CENTERS FOR MEDICARE & MEDICAID SERVICES OMB NO (X2) MULTIPLE CONSTRUCTION A. BUILDING 03 - A BUILDING
SUMMARY PROVER'S PLAN OF CORRECTION K 000 INITIAL COMMENTS K 000 A Life Safety Code Survey was conducted by the State Fire Marshal beginning on May 9th, 2017 and ending on May 10th, 2017. Adair Acute Care
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST FIRE AND LIFE SAFETY SYSTEMS FOR STRUCTURES FIVE OR MORE STORIES IN HEIGHT AND LESS THAN 75 FEET IN HEIGHT FROM THE POINT
More informationLIFE SAFETY & FIRE PREVENTION MANAGEMENT PLAN
Title/Description: Life Safety & Fire Prevention Management Department: Facilities Management Personnel: All Effective Date: 5/97 Revised: 7/00, 7/01, 7/02, 7/03, 7/04, 7/05, 7/08 LIFE SAFETY & FIRE PREVENTION
More informationReport on First Revisions with Statement June 2014 NFPA 101
101 FR6005 SAF-BCF (32.2.1.1.2) Recommendation: 32.2.1.1.2 Where there are sleeping accommodations for more than 16 residents are provided, the occupancy shall be classified as a large facility in accordance
More informationChapter Nursing Homes
Chapter 16.01 Nursing Homes Section 1. Licensing. No nursing, convalescent or old age home, as defined in Section 2 of this ordinance, shall be operated except under a license from the City Council of
More informationDEPARTMENT OF HEALTH AND HUMAN SERVICES K 011 K 011 NFPA 101 LIFE SAFETY CODE STANDARD
CENTERS FOR MEDICARE & MEDICA SERVICES OMB NO. 0938-0391 (X1) PROVER/SUPPLIER/CLIA ENTIFICATION NUMBER: (X3) SURVEY NAME OF PROVER OR SUPPLIER PROVER'S PLAN OF CORRECTION K 011 NFPA 101 LIFE SAFETY CODE
More information2012 B.C. Building Code Compliance Review (Division B Part 3)
Planning and Building Department 2012 B.C. Building Code Compliance Review PROJECT NAME:.. CIVIC ADDRESS:...... PERMIT APPLICATION NO.:. DATE:... I,, have: 1. reviewed the design, plans and supporting
More informationBusiness License Pre-inspection Checklist
Business License Pre-inspection Checklist August, 2016 Alberta Fire Code business license pre-inspection and annual checklist This checklist provides business owners with Alberta Fire Code requirements
More informationPENNSYLVANIA. Downloaded
Housekeeping/Laundry/Maintenance 205.26. Laundry. PENNSYLVANIA Downloaded 01.15.11 (a) A laundry room shall be provided in a facility where commercial laundry service is not used for the washing of soiled
More informationDefend In Place 2012 IFC Overview of Institutional Occupancies
Defend In Place 2012 IFC Overview of Institutional Occupancies ICC Course No. ICC CEU s = 0.50 SCFA Course 8506-15-0 Nathan Ellis Cell: 864-812-5183 Nathan.Ellis@llr.sc.gov Institutional Occupancies Course
More information2009 International Fire Code Errata. SECOND PRINTING (Posted April 6, 2010)
CHAPTER 1 SCOPE AND ADMINISTRATION 102.7 Referenced codes and standards. The codes and standards referenced in this code shall be those that are listed in Chapter 45 47 and such codes and standards shall
More informationCity of South Salt Lake Fire Code Training Exiting, Egress Systems and Egress Control
City of South Salt Lake Fire Code Training Exiting, Egress Systems and Egress Control 11-27-12 This document is designed as a summary guide using IFC requirements for the provisions associated with exiting,
More informationBUILDER S PRE-INSPECTION CHECKLIST
Warrenton Fire Protection District 606 Fairgrounds Rd. Warrenton, MO 63383 Ph: 636-456-8935 Fax: 636-456-7764 www.warrenton-fire.org BUILDER S PRE-INSPECTION CHECKLIST This checklist is designed as a general
More informationOther EC and LS documents may be requested by surveyors, as needed, throughout the survey.
Documentation required by the Hospital Accreditation program Life Safety (LS) and selected Environment of Care (EC) standards is presented in the following pages. These documents will be reviewed by the
More informationMINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry
MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Fire Alarm Systems Plan Review Checklist Date: Permit Number: Business Name: Address: Fire Alarm System Submittal
More informationPrepublication New Text Jan 2018 Changes to Environment of Care and Life Safety Chapters
Prepublication New Text Jan 2018 Changes to Environment of Care and Life Safety Chapters EC.01.01.01 EP3 Related to Life Safety Code Updates Hospital (HAP) Accreditation Program The hospital has a library
More informationCHAPTER 56 EXPLOSIVES AND FIREWORKS SECTION FIREWORKS 1.4G RETAIL STORAGE, DISPLAY, AND SALE
CHAPTER 56 EXPLOSIVES AND FIREWORKS SECTION 5609 is amended, to read as follows, with the entire section being an addition to the Fire Code: SECTION 5609. FIREWORKS 1.4G RETAIL STORAGE, DISPLAY, AND SALE
More informationBUILDER S PRE-INSPECTION CHECKLIST
Warrenton Fire Protection District 606 Fairgrounds Rd. Warrenton, MO 63383 Ph: 636-456-8935 Fax: 636-456-7764 www.warrenton-fire.org BUILDER S PRE-INSPECTION CHECKLIST This checklist is designed as a general
More informationTIPS FOR BETTER JOINT COMMISSION SURVEYS
TIPS FOR BETTER JOINT COMMISSION SURVEYS Washington Society for Healthcare Engineering September 21, 2011 Yakima, Washington The BASICS Most Failed Standards. Scoring. Electronic S. O. C. I.L.S.M. Building
More informationFor the Florida Building Commission And the Fire Code Advisory Council
Life-Safety Modifications Mechanical and Existing Building Compared to the 2012 Changes of the International Building Code and National Fire Protection Association- 101 For the Florida Building Commission
More informationCommon Building Code Misinterpretations
Common Building Code Misinterpretations Presented by: Ron Melucci, P.E. Technical Manager, FP Division Engineering Planning and Management, Inc. rbm@epm inc.com www.epm inc.com 508 875 2121 Engineering
More informationTHE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #6
THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #6 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1 QUESTIONS How To Ask a Question: POLLING There will be occasional
More informationMINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY
MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division 444 Cedar Street, Suite 145, St. Paul, Minnesota 55101-5145 Phone: 651/201-7200 FAX: 651/215-0525 TTY: 651/282/6555 Internet: http://www.fire.state.mn.us
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD LICENSED CARE FACILITIES SCOPE: This standard provides requirements for licensed care facilities known as for the Elderly with seven
More informationAHC Meeting #7 July 12-13, Occupancy WG Report
AHC Meeting #7 July 12-13, 2012 Part 1: CTC public comments on I-1/I-2 Condition designations..page 1 Part 2; AHC public comments on I-2 Condition designations Page 6 Part 3: Approved code change G244
More informationTHE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY)
FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY) BUILDING SUMMARY The building was constructed in Victorian times and is constructed of brick with knapped flint in fill on some outer walls. The building
More informationRenovation Program. Renovation Program GENERAL
Renovation Program GENERAL This program provides guidance and protocols for renovation projects in occupied, operational acute hospitals. Team building is essential to quality control and HFD Services
More informationSCHEDULE. Essential Safety Measures taken from Schedule 9 of the Building Regulations PART 1 BUILDING FIRE INTEGRITY
SCHEDULE Essential s taken from Schedule 9 of the Building Regulations 2006 43 PART 1 BUILDING FIRE INTEGRITY 1 Building elements required to satisfy prescribed fire-resistance levels 2 Materials and assemblies
More information2007 CBC & CFC Residential Care Facility Requirements (24 hour care only)
2007 & CFC Residential Care Facility Requirements (24 hour care only) Occupancy Construction Smoke Barrier I-1 Bedridden 7+non- Ambs Or bed- Ridden R-4 7+ambs (May have 6 nonambs or 6 bedridden) R-3.1
More informationUNIVERSITY OF TOLEDO
UNIVERSITY OF TOLEDO SUBJECT: INTERIM LIFE SAFETY MEASURES AND INFECTION Procedure No: LS-08-008 CONTROL PROCEDURE STATEMENT Interim life safety and infection control measures will be implemented to protect
More informationTHE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT SPORTS CENTRE
FIRE RISK ASSESSMENT SPORTS CENTRE BUILDING SUMMARY The building is used as a Sports Centre and contains a large sports hall with changing rooms, an office for staff and a fitness area. 1. Identification
More information2015 MECHANICAL CODE REQUIREMENTS
2015 MECHANICAL CODE REQUIREMENTS ANTRIM COUNTY BUILDING DEPARTMENT PO BOX 188 205 CAYUGA STREET BELLAIRE, MI 49615 (231) 533-8373 FAX (231) 533-6041 Mechanical requirements for residential buildings per
More informationNew Facilities. Minimum Requirements
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 Item Reference Violation General Requirements NFPA 1124-7.1.1 Retail sales of consumer fireworks in both new and existing buildings, structures, and
More informationThe Physical Environment Portal: Module 5, LS Leadership
The Physical Environment Portal: Module 5, LS.02.01.10 - Leadership Fire Safety: Background Fire safety impacts both the lives of the occupants and the physical structures. In the early 1900 s many buildings
More informationDeveloping a Healthcare Facility Fire Door Inspection Program
Developing a Healthcare Facility Fire Door Inspection Program WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio QUESTIONS How To Ask a Question: 1 POLLING There will be occasional interactive
More informationJanuary 1, 2014 Mandatory Effective Date
2013 Kentucky Building Code Highlights Winnie Blythe, Technical Advisor Dept. of Housing, Buildings, and Construction winnie.blythe@ky.gov www.dhbc.ky.gov 502-573-0373 January 1, 2014 Mandatory Effective
More informationPLAN REVIEW SUBMITTAL GUIDE
PLAN REVIEW SUBMITTAL GUIDE Plans, specifications and other construction documentation for the initial plan review should be as complete as possible at the time of submittal. Use this convenient guide
More informationLife Safety - Means of Egress/Exits NFPA 101
Life Safety - Means of Egress/Exits NFPA 101 Properly designed exits provide a safe path of escape from a fire or other emergency environment. The means of egress (exits) should be arranged to permit all
More informationMULTI-LEVEL & COVERED BOOTH CONDITIONS
MULTI-LEVEL & COVERED BOOTH CONDITIONS Covered Booth Definition To place something over or upon an exhibit or portion of an exhibit (e.g., roof, ceiling, tenting, lattice, fabric, plastic) to cover the
More informationFACILITY MANAGEMENT DEFICIENCIES IN CRITICAL ACCESS HOSPITALS (CAH)
FACILITY MANAGEMENT DEFICIENCIES IN CRITICAL ACCESS HOSPITALS (CAH) Presented by: Alise Howlett, Assoc. AIA, CFPE, CHFM Standards Advisor, EM/PE/LS HFAP A better healthcare survey experience 1 FREQUENT
More informationInspection Checklist Mechanical Rough in
Property Owner Name: Property Address: Permit Number: Inspectors Name: Review Date: Permits and Plans 1. Job address is posted in a visible location. (R319.1) 2. Permit and approved plans are on site and
More informationTHE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT HORSEFAIR HOUSE
FIRE RISK ASSESSMENT HORSEFAIR HOUSE BUILDING SUMMARY The building is utilised for the teaching of Science and contains Laboratories and Chemical storage. 1. Identification of the hazards 1.1 Identification
More informationSchool Fire Safety Checklist
Community Risk Reduction The (SFSC) includes many of the most common fire prevention and life safety issues found in schools. The SFSC is not intended to be an all inclusive list, but rather highlights
More informationPROJECT: CIVIC ADDRESS:... PERMIT APPLICATION NO.: DATE:... CRP:. Certified Professional:.
2012 B.C. Building Code Checklist (Division B Part 3) This checklist is provided as a reference only. The submission of this checklist with a Building Permit application should not be considered as a substitute
More informationPresented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC Web: Lauzon-LSC.com
Presented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC 262-945-4567 Lauzon.lsc@gmail.com Web: Lauzon-LSC.com 1 Wis Professional Engineer Experienced Facility Director Experienced AHJ WHEA Code
More informationLife Safety Checklist
Life Safety Checklist For Assisted Living and Specialty Care Assisted Living Facilities in Alabama prepared by: TIM BARRON, ARCHITECT, INC. 212 EDEN VIEW DRIVE HOOVER, AL 35244 205.444.1443 Tim@TimBarron.com
More informationShort Term Accommodations Fire Code Requirements
Short Term Accommodations Fire Code Requirements 1 Foreward The following is a comprehensive reference to Retrofit 9.3 of Division B of the Ontario Fire Code (OFC). Retrofit provisions were developed to
More informationBCBC 2012 CHANGES TO PART 3
BCBC 2012 CHANGES TO PART 3 Focus on changes that will have an practical effect. Basic concepts reviewed details to be confirmed. Material from Part 3 and related material from Part 9 Generally a harmonization
More informationFraternity, Sorority and Dormitory Buildings R-2 Fire and Life Safety Standards Inspection Form Fire Code of New York State (19 NYCRR Part 1225.
Fraternity, Sorority and Dormitory Buildings R-2 Fire and Life Safety Standards Inspection Form Fire Code of New York State (19 NYCRR Part 1225.1) House Name Date Address Inspector(s) No. of Residents
More informationFIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES
FIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES 1. The major objective is to provide an acceptable degree of life safety from fire in existing senior citizen lodges. This document
More information- CONSTRUCTION FIRE SAFETY STANDARDS
SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Construction Planning All construction sites shall plan and sequence their construction activities to ensure the early installation and operation of permanent
More informationCOUNTY OF SACRAMENTO DEPARTMENT OF COMMUNITY DEVELOPMENT BUILDING PERMITS & INSPECTION DIVISION
COUNTY OF SACRAMENTO DEPARTMENT OF COMMUNITY DEVELOPMENT BUILDING PERMITS & INSPECTION DIVISION Document # GI-16 Page 1 of 7 Large Family Day Care Homes Large family day care homes are licensed for day
More information