1 General Alarm System User Manual Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT, ENGLAND +44 (0)

2 Document Revision Details Issue Modification Details Author Date 1 Document Creation RB 18/04/2016 N Issue 0 Page 2 of 19 Protec Fire Detection plc 2016

3 Table of Contents DOCUMENT REVISI DETAILS SCOPE OF DOCUMENT APPLICABLE STANDARD AND DIRECTIVE INFORMATI INTRODUCTI OVERVIEW GENERAL ALARM TERMINOLOGY SYSTEM OPERATI System normal Call Point Activation Cell Point Tamper General Alarm Activation Reset Local Panel/s Tamper Central Panel Tamper Local or Central Panel Lamp test Local / Central Power Supply Fail TESTING MAINTENANCE TYPICAL INSTALLATI The policy of Protec Fire Detection plc is one of continuous improvement. As such we reserve the right to make changes to product specifications at any time and without prior notice. Errors and omissions excepted. This equipment has been manufactured in conformance with the requirements of all applicable EU council directives and regulations Electrical or electronic devices that are no longer serviceable must be collected separately and sent for environmentally compatible recycling (in accordance with the European Waste Electrical and Electronic Equipment Directive). To dispose of old electrical or electronic devices, you should use the return and collection systems put in place in the country concerned. N Issue 0 Page 3 of 19 Protec Fire Detection plc 2016

4 1.0 Scope of Document The document enclosed details the information on the operation of the Protec General Alarm System including the interaction with the ELS program. 2.0 Applicable Standard and Directive Information The Protec General Alarm System is designed to meet the requirements of the Prison Service General Alarm System Specification including the relevant directives. Standard Name ( full details ) National Offender Management Service (NOMS) Custodial Property Technical Specification: General Alarm System for prisons Standard: STD/E/SPEC/011 Issue: 0007 Date: 15 th May 2013 Description This specification is intended to be used in the process of appointing manufacturers/installers to a framework contract for general alarm systems in prisons. Standard Name ( full details ) Low Voltage Directive ( Directive 2006/95/EC ) RoHs Directive ( Directive 2011/65/EU ) WEEE Directive ( Directive 2012/19/EU ) BSEN ( relevant parts ) Description Low Voltage Directive Restriction of the use of certain Hazardous Substances The Waste of Electrical and Electronic Equipment Electro Magnetic Compatibility EN60950 ( relevant parts ) Electrical Safety 3.0 Introduction The Protec General Alarm system is designed to provide effective and reliable response when raising an alarm for assistance in the event of an emergency. The alarm is raised by activating strategically located individual vandal resistant call points. The General Alarm System is monitored and controlled by a Programmable Logic Controller (PLC) to ensure operational reliability. All events are auditable on a central control PC software [Protec Event Logging System (ELS)] which records the operation of the General Alarm equipment. Control Panels are normally installed in secure locations (i.e. Plant Rooms, Roof Voids) and are used to monitor and control all the functions of the local general alarm system. Protec s range of General Alarm PLC units have been designed to comply with the latest MOJ technical specification to provide reliable, cost effective yet robust solution to suit most prison and custody cell applications. N Issue 0 Page 4 of 19 Protec Fire Detection plc 2016

5 4.0 Overview The Protec range of Control Panels use the Programmable Logic Controller (PLC) type of systems. The PLC units are enclosed within a rugged steel enclosure, finished in a RAL6018 (yellow/green) colour. All the essential components of the control panel are protected from unauthorised access by a hinged lockable steel door, which comes complete with tamper contacts as standard. The size of Control Panel and the associated Indicator Panel is generally determined by the number of general alarm zones required per building (typically 1No call point equals 1No zone). Key Features MOJ Compliant Monitors all General Alarm Call Points Indicator Panels; Available in 20, 40 and 60 Way Options Alarm Reset & Lamp Test Buttons Alarm, Power, Fault Twin Chip LED Indication Internal Audible Alarm Repeat Indictor Panel; LED indication Only (No controls) Units Available Local Audible and Visual Alarms Stand-Alone or Network Options Rugged Lockable Steel Enclosure Tamper and Fault Monitored Technical Features The PLC units require a 24V dc supply, provided by a separate battery charger, mounted adjacent to the control panel. The general alarm zone are typically a normally closed push button with inbuilt tamper switch. Each general alarm zone and each alarm circuit (s) are all hard-wired back to the Control Panel, generally using LSF cable. Each input terminal, which are used for the general alarm zones are pre-wired to provide a corresponding output contact, which are used to drive the Indicator Panel LED. The separate alarm output circuit contacts are to drive beacons or/and sounders. The Indicator and Repeat Indicator Panels are also hard-wired back to the Control Panel via LSF multicore cable. All Indicator and Repeat Indicator panels are low voltage devices (24V dc), with their supply voltage being provided via a multicore serial link cable wired direct from the PLC Control Panel. Panel Model 20 Way control & Indication 40 Way control & Indication 60 Way control & Indication 20 Way Repeat Indication 40 Way Repeat Indication 60 Way Repeat Indication Zonal Output Indicators 20 LED Zonal Display 40 LED Zonal Display 60 LED Zonal Display 20 LED Zonal Display 40 LED Zonal Display 60 LED Zonal Display Additional Indications Power Healthy, Tamper Fault and Supply failed LED Power Healthy, Tamper Fault and Supply failed LED Power Healthy, Tamper Fault and Supply failed LED Power Healthy, Tamper Fault and Supply failed LED Power Healthy, Tamper Fault and Supply failed LED Power Healthy, Tamper Fault and Supply failed LED Control Inputs Alarm Reset and Lamp Test button Alarm Reset and Lamp Test button Alarm Reset and Lamp Test button None None None s 4 Internal Alarm Circuits 24V) 4 Internal Alarm Circuits 24V) 6 Internal Alarm Circuits 24V) None None None N Issue 0 Page 5 of 19 Protec Fire Detection plc 2016

6 5.0 General Alarm terminology General Alarm Call Points Vandal resistant Call Point when pressed activates a general alarm. The call points are individual strategically located in the building for the most effective response to incidents. Each call point is fitted with a tamper switch and a circular shroud around the push button to prevent inadvertent operation. Local Control Unit Programmable Logic Controller (PLC) controlling the local operations of all external call points and local indication panel. Serial data and hardwire cross-site signal to the central control panel. Local Indication Panel Wing-based indicators provide local audible and visual annunciation of alarms. Including the means of resetting the local alarm. Local indications panels either 20way, 40way or 60way alarm indication. Central Control Unit Programmable Logic Controller (PLC) controlling the operations of all terminated hardwire signals from local control units and central indication panel. Monitors serial data from local controls units, connecting direct to the control room PC software: ELS. Maximum of 60 hardware contacts from the local control units and/or capable of monitoring additional local call points. Central Indication Panel Control room based indication provide audible and visual annunciation of the alarm/s at the local panel and additional local call points. Including the means of resetting the active alarms provide initially reset on the local indication panel unless resetting additional call points. Central indication panels are 60way alarm indication. Event Logging System All system events are recorded by a PC based auditable data system the Event Logging System (ELS). Provides an external reset function additional to the reset on the central indication panel. Reference ELS User Manual document. Tamper alarm Reset Lamp Test Alarm output devices An alarm raised to notify that the general alarm equipment has been opened or tampered by an unauthorised person; either a call point, local/central control unit, local/central indication panels, local/central power supply units. Call points are individually tamper monitored generating a fault within 20secs. The general alarm when authorised can be locally reset via the push button on the local indication panels and secondary reset via the push button on the central indication panel or Event Logging System PC software. The lamp test push button switch located on each indication panel (local and central) when pressed illuminates all LEDs and audible buzzer for 3 secs to ensure the LEDs and buzzer are operating correctly. The alarm output devices can either be visual (beacons) or audible (sounders) installed alongside general alarm call points. To assist an officer in quickly locating the origin of an alarm. The outputs can be programmed to operate until reset or only while the general alarm call point button is pressed. N Issue 0 Page 6 of 19 Protec Fire Detection plc 2016

7 6.0 System Operation When an officer/inmate requires emergency assistance, an alarm is raised by pressing the general alarm call point push button. Once pressed and released, the button returns to its normal position. If the call point front plate is removed (the inbuilt tamper activates) or there is short circuit on the cable the relevant zone on the local display panel will be activated. Upon activation of a general alarm call point the call is logged by the PLC Control Panel, the unit is then programmed to drive the associated zonal LED on the Indicator and Repeat Indicator panels and activate any local audible and visual alarms. Where the system forms part of a site wide network, upon the activation of an alarm a hard-wired and a data signal are transmitted across the site to both the Central Control PLC and the Event Logging PC unit via the cross-site cabling infrastructure. Once the event has been dealt with and the system has been reset via the local reset button, the Control Panel will return to its normal operating mode. A signal will then be sent via both the hard-wired and data cross-site cabling infrastructure to reset the Central Control PLC and log the time & date on the event log. 6.1 System normal No general alarms activations or tampers, power supply healthy. Call Point Local Indicator Panel Central Indicator Panel Event Logging System Buzzer Buzzer Local / Repeat Indicator Panel Output Alarm Central Indicator Panel EFFECT Internal Buzzer s (Non-latching) s (Latching) CAUSE General Alarm System Normal Internal Buzzer Event Logging System ELS has Logged the Event N/A N Issue 0 Page 7 of 19 Protec Fire Detection plc 2016

8 6.2 Call Point Activation A general alarm activation instigated by pressing the push button on a call point causes a corresponding zone indicator to illuminate constant and the audible buzzer to pulse (1 second On 1 second Off) for 10 seconds on the local indicator panel. Any local alarm output device will activate. The corresponding panel indicator will illuminate on the central indicator panel. All data is transmitted to the Event Logging System (ELS), location text will be displayed to correspond with the activated general alarm/s or tampers. All data is recorded for auditability on the ELS. General Alarm Call Point Activation: Zone indicator illuminate constant Call Point Local Indicator Panel Central Indicator Panel Event Logging System Buzzer Buzzer Example Call Point on Panel 1, Zone 3. Local / Repeat Indicator Panel Output Alarm Central Indicator Panel EFFECT CAUSE General Alarm System Zone Activation (upon to a period of 20seconds) Internal Buzzer - PULSED (10 SECDS ) s (Non-latching) s (Latching) - FOR DURATI OF PRESS Internal Buzzer - PULSED (10 SECDS ) Event Logging System ELS has Logged the Event YES N Issue 0 Page 8 of 19 Protec Fire Detection plc 2016

9 6.3 Cell Point Tamper A general alarm tamper activation is instigated by either removing the call point front cover or pressing and holding the push button on a call point. Either will initially report a general alarm then after 20secs generate into a tamper fault. A general alarm tamper activation causes the corresponding zone indicator to illuminate and pulse (1 second On and 1 second Off) and the audible buzzer to pulse (1 second On 1 second Off) on the local indicator panel. The corresponding panel indicator will illuminate and pulse (1 second On and 1 second Off) on the central indicator panel. All data is transmitted to the Event Logging System (ELS), location text will be displayed to correspond with the activated general alarm/s or tampers. All data is recorded for auditability on the ELS. General Alarm Call Point Tamper Activation: Zone indicator illuminate pulse (after 20secs) Call Point Local Indicator Panel Central Indicator Panel Event Logging System Buzzer Example Call Point on Panel 1, Zone 3. Local / Repeat Indicator Panel Output Alarm Central Indicator Panel EFFECT Internal Buzzer s (Non-latching) s (Latching) CAUSE General Alarm System Zone Tamper Activation (for a period of over 20 seconds) - PULSED - PULSED Internal Buzzer Event Logging System ELS has Logged the Event YES N Issue 0 Page 9 of 19 Protec Fire Detection plc 2016

10 6.4 General Alarm Activation Reset To reset a single or multiple general alarm activations you must ensure confirmation has been received the general alarm/s have been dealt by an authorised personal. The general alarm(s) has to be initially reset on the local control panel by pressing the reset button on the local indicator panel. To clear the general alarm on central control panel, either press the reset button on the central control indicator panel or using the PC Event logging system program select the reset icon. When additional Call Points are installed on the central control panel these will only be reset by the central indicator panel. N Issue 0 Page 10 of 19 Protec Fire Detection plc 2016

11 6.5 Local Panel(s) Tamper The local tamper alarm is activated when the following equipment has been opened or tampered with; causing the tamper switch to trigger: local control unit, local indication panel, repeat indicator panel and local PLC battery charger The tamper is notified by the tamper indicator illuminating on the local indication panel and transmitted to the Event Logging System (ELS), location text will be displayed corresponding to the tamper. All data is recorded for auditability on the ELS. Local Indicator Panel Central Indicator Panel Event Logging System Buzzer Local / Repeat Indicator Panel Output Alarm Central Indicator Panel EFFECT CAUSE General Alarm System on Local Tamper Activation (a) Local PLC Control Panel, (b) Local PLC Battery Charger or (c) Local/Repeat Indicator Panel Internal Buzzer - PULSED (10 SECDS ) s (Non-latching) s (Latching) Internal Buzzer Event Logging System ELS has Logged the Event YES N Issue 0 Page 11 of 19 Protec Fire Detection plc 2016

12 6.6 Central Panel Tamper The central tamper alarm is activated when the following equipment has been opened or tampered with; so that it has caused the tamper switch to trigger: central control unit, central indication panel, central PLC battery charger The tamper is notified by the tamper indicator illuminating on the central indication panel and transmitted to the Event Logging System (ELS), location text will be displayed corresponding to the tamper. All data is recorded for auditability on the ELS. Local Indicator Panel Central Indicator Panel Event Logging System Buzzer Local / Repeat Indicator Panel Output Alarm Central Indicator Panel EFFECT Internal Buzzer s (Non-latching) s (Latching) CAUSE General Alarm System on Central Tamper Activation (a) Central PLC Control Panel, (b) Central PLC Battery Charger or (c) Central Indicator Panel Internal Buzzer - PULSED (10 SECDS ) Event Logging System ELS has Logged the Event YES N Issue 0 Page 12 of 19 Protec Fire Detection plc 2016

13 6.7 Local or Central Panel Lamp test The Lamp test button should be daily tested to ensure all LEDs illuminate and the buzzer sounds. The Lamp test switch button only operates the LEDs local to that switch and any repeat indicator panels connected. The LED will illuminate and the buzzer will pulse for a for 3 secs duration. Local / Central Indicator Panel Buzzer Local & Repeat / Central Indicator Panel EFFECT All Internal Buzzer CAUSE General Alarm System on Lamp Test Activation for 3 SECDS for 3 SECDS for 3 SECDS for 3 SECDS PULSED for 3 SECDS s (Non-latching) Output Alarm s (Latching) Event Logging System ELS has Logged the Event NO N Issue 0 Page 13 of 19 Protec Fire Detection plc 2016

14 6.8 Local / Central Power Supply Fail The local and central control panels monitor the state of their local charger. When the local power supply has switched to batteries due to a mains failure or an on board fault the power supply fail LED will illuminate and the buzzer will pulse. All data is recorded for auditability on the ELS. Local / Central Indicator Panel Buzzer Local & Repeat / Central Indicator Panel EFFECT CAUSE General Alarm System on Power failure (> 30seconds) Internal Buzzer - PULSED (10 SECDS ) s (Non-latching) Output Alarm s (Latching) Event Logging System ELS has Logged the Event YES Note. The local / central indicator panel are delayed by 30 seconds before the fault is generated. N Issue 0 Page 14 of 19 Protec Fire Detection plc 2016

15 7.0 Testing To insure that your system continues to function as intended, you must test your system frequently. If your system does not function properly, call your installer company for a service. Contact the control room before and after you begin and end any testing on the general alarm system. Periodical system checks - Protec recommends tests to be performed daily: 1. Check the system is fault free. The event logging system will report any current faults on the system. 2. Each call point to be operated and the correct functioning of the system to be verified. a) Corresponding zone LED illuminate and an audible alarm sounds on the local indication panel. b) Any alarm output devices activate. c) Corresponding local panel LED illuminate and audible sounds on the central indication panel. d) Event logging system displays and records zone activation. 3. Lamp test each local and the central indication panel. a) Ensure all LEDs illuminate and the audible sound pulses. 8.0 Maintenance Providing the system is use in normal operation it requires minimum maintenance. Maintenance requirement are reference the technical standard number STD/E/SPEC/011 Section 27. Any vandalised equipment should be removed and replaced immediately. If replacement is delayed the equipment should be safely terminated and isolated from further vandalism. N Issue 0 Page 15 of 19 Protec Fire Detection plc 2016

16 9.0 Typical Installation Typical Site Wide General Alarm Installation N Issue 0 Page 16 of 19 Protec Fire Detection plc 2016

17 Typical Wing General Alarm Installation N Issue 0 Page 17 of 19 Protec Fire Detection plc 2016

18 Designed and manufactured in the United Kingdom N Issue 0 Page 18 of 19 Protec Fire Detection plc 2016

19 N Issue 0 Page 19 of 19 Protec Fire Detection plc 2016

PROPOINT PLUS ASPIRATING SMOKE DETECTION SYSTEM

PROPOINT PLUS ASPIRATING SMOKE DETECTION SYSTEM PROPOINT PLUS ASPIRATING SMOKE DETECTION SYSTEM USER MANUAL Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT, ENGLAND +44 (0) 1282 717171 www.protec.co.uk sales@protec.co.uk

More information

6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL

6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL 6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL USER MANUAL Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0)

More information

3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL

3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL 3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL USER MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273 Web:

More information

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL 3500 CONVENTIONAL FIRE ALARM CONTROL PANEL USER MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273 Web:

More information

Algo-Tec 6500/6600 INTERACTIVE ADDRESSABLE FIRE CONTROL SYSTEM

Algo-Tec 6500/6600 INTERACTIVE ADDRESSABLE FIRE CONTROL SYSTEM Algo-Tec 6500/6600 INTERACTIVE ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS) USER MANUAL Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT, ENGLAND +44 (0) 1282 717171 www.protec.co.uk

More information

HERCULES 6 GRAPHICS SYSTEM

HERCULES 6 GRAPHICS SYSTEM HERCULES 6 GRAPHICS SYSTEM USER MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273 Web: www.protec.co.uk

More information

Algo-Tec 6500/6600 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS)

Algo-Tec 6500/6600 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS) Algo-Tec 6500/6600 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS) COMMISSIONING MANUAL Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT, ENGLAND +44

More information

PROPOINTPLUS ASPIRATING SMOKE DETECTION SYSTEM

PROPOINTPLUS ASPIRATING SMOKE DETECTION SYSTEM PROPOINTPLUS ASPIRATING SMOKE DETECTION SYSTEM INSTALLATION AND COMMISSIONING MANUAL Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT, ENGLAND +44 (0) 1282 717171 www.protec.co.uk

More information

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL 3500 CONVENTIONAL FIRE ALARM CONTROL PANEL INSTALLATION AND COMMISSIONING MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax:

More information

Protec. Protec Algo-Tec TM 6100 Interactive Digital Addressable Fire Control System. Fire Detection - Addressable

Protec. Protec Algo-Tec TM 6100 Interactive Digital Addressable Fire Control System. Fire Detection - Addressable Protec Protec Algo-Tec TM 6100 Interactive Digital Addressable Fire Control System ADDRESSING SAFETY SYSTEMS WITH INTELLIGENCE Protec Protec Algo-TecTM 6100 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL

More information

Fire Detection - Addressable

Fire Detection - Addressable Technical Specification 6400 Series Common Specifications Temperature Range 0-40 C. Maximum Humidity 85% Non-Condensing. Working Voltage 21.5-30V dc. Secure Network Dual channel RS485 fault tolerant communications

More information

SYSTEM 5000 USER MANUAL

SYSTEM 5000 USER MANUAL SYSTEM 5000 USER MANUAL Table of Contents Section Page No 1 Introduction: -... 3 1.1 Procedure:... 3 1.2 Warnings and Cautions:... 3 2 User Control Levels:... 4 3 User Passwords:... 4 4 Controls and Displays:

More information

Algo-Tec 6300 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS)

Algo-Tec 6300 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS) Algo-Tec 6300 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS) INSTALLATION MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0)

More information

Type 8001 PRIME MOVER CONTROLS INC. ALARM ANNUNCIATOR TYPE8001 FEATURES SB 8001B

Type 8001 PRIME MOVER CONTROLS INC. ALARM ANNUNCIATOR TYPE8001 FEATURES SB 8001B PRODUCT BULLETIN SB 8001B Type 8001 ALARM ANNUNCIATOR TYPE8001 FEATURES 16 or 32 alarm points per flush mount enclosure Displays are backlit with long life LEDs and engraved to suit Dimmer controls built

More information

Protec. Protec Algo-Tec TM 6500 Open Protocol Interactive Digital Addressable Fire Control System with Algo-Tec 6600 Bridging Network

Protec. Protec Algo-Tec TM 6500 Open Protocol Interactive Digital Addressable Fire Control System with Algo-Tec 6600 Bridging Network Protec Protec Fire Detection plc Protec Algo-Tec TM 6500 Open Protocol Interactive Digital Addressable Fire Control System with Algo-Tec 6600 Bridging Network ADDRESSING SAFETY SYSTEMS WITH INTELLIGENCE

More information

Excel-EN Conventional Fire Control Panel

Excel-EN Conventional Fire Control Panel Available as 2, 4, 6, 8,10 or 12 zones Approved to EN54-2 & 4 Modular expansion zone cards Programmable relays and outputs Optional additional sounder circuits Optional additional programmable outputs

More information

USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4

USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4 PREMIER EX8 EXTINGUISHING PANEL USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN 12094 PART 1 & EN54 PARTS 2 & 4 USER MANUAL Approved Document No: GLT.MAN-132 INDEX Extinguishing

More information

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER Application The unit is primarily intended for use where there is a requirement to integrate a limited fire protection function into a larger control equipment scheme, or in specialist applications where

More information

Matrix2000. User Guide - CPD Advanced Analog Fire Alarm Control Panel 4 24 Zones. Version: 2.0 Revision: 1

Matrix2000. User Guide - CPD Advanced Analog Fire Alarm Control Panel 4 24 Zones. Version: 2.0 Revision: 1 Matrix2000 User Guide - CPD Advanced Analog Fire Alarm Control Panel 4 24 s Version: 2.0 Revision: 1 IMPORTANT INFORMATION Limitation of liability It is mandatory, Matrix2000 panel to be installed in accordance

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd OPERATIONAL NOTES FOR CONCEPT FIRE PANEL. NOTE ON NEW FIRE PANELS, POSITION 1 ON THE SIX WAY INTERNAL OPTION SWITCH IS TURNED ON, DISABLING THE ZONAL SOUNDERS. TO ENABLE ZONAL SOUNDERS TURN OFF. Operation

More information

CIRRUS PRO. User Manual and Responsibilities ASPIRATING FIRE DETECTOR

CIRRUS PRO. User Manual and Responsibilities ASPIRATING FIRE DETECTOR CIRRUS PRO ASPIRATING FIRE DETECTOR User Manual and Responsibilities Protec Fire Detection (Export) Ltd, Protec House, Churchill Way, Nelson, Lancashire. BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44

More information

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS QUICK USER GUIDE FOR, 2 & 4 ZONE PANELS INDICATORS COLOUR INDICATION MON FAULT Yellow On when a fault condition has occurred, or if no other fault Led is on, this indicates 24v auxiliary fuse failure.

More information

Protec. Protec Algo-Tec TM 6400 Interactive Digital Addressable Fire Control System. Fire Detection - Addressable

Protec. Protec Algo-Tec TM 6400 Interactive Digital Addressable Fire Control System. Fire Detection - Addressable Protec Protec Algo-Tec TM 6400 Interactive Digital Addressable Fire Control System ADDRESSING SAFETY SYSTEMS WITH INTELLIGENCE CAUTION Protec Protec Algo-Tec 6400 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL

More information

ZXSe Range Data Sheet

ZXSe Range Data Sheet ZXSe Range Data Sheet Analogue addressable fire alarm control panel Product Overview The ZXSe range of analogue addressable fire alarm control panels have been designed and constructed around proven and

More information

Logbook. Precept EN Fire Detection/Alarm Panel. & Precept EN Repeater

Logbook. Precept EN Fire Detection/Alarm Panel. & Precept EN Repeater APPROVED BY: JBJ Precept EN Fire Detection/Alarm Panel & Precept EN Repeater Logbook PAGE 1 of 19 List of Contents 1. FIRE ALARM SYSTEM MAINTENANCE... 3 2. USER RESPONSIBILITIES... 3 2.1. RESPONSIBLE PERSON...

More information

EL-OEM-3 OEM Packaged Voltage Data Logger

EL-OEM-3 OEM Packaged Voltage Data Logger FEATURES PCB Mounted (2.54mm pitch, header sockets) 0 to 2.4V d.c. Measurement Range Logging Rates between 1s and 12hr Stores 64,000 readings USB interface for set-up and data download (USB connector not

More information

ZXSe Range. Fire Safety. Analogue addressable fire alarm control panel KEY FEATURES. Panel Features

ZXSe Range. Fire Safety. Analogue addressable fire alarm control panel KEY FEATURES. Panel Features Fire Safety ZXSe Range Analogue addressable fire alarm control panel The ZXSe range of analogue addressable fire alarm control panels have been designed and constructed around proven and reliable microprocessor

More information

Control Panel User Guide

Control Panel User Guide Fire Detection & Alarm System Control Panel V4.14 Control Panel User Guide (TO BE RETAINED BY USER) 26-0397 Issue 6 Fike s policy is one of continual improvement and the right to change a specification

More information

Sita200plus. 200detectors. Single loop analogue addressable System

Sita200plus. 200detectors. Single loop analogue addressable System Single loop analogue addressable System Fast short circuit isolator in every device 15 combinations of smoke & heat detection modes Loop length up to 2km long with spurs INTELLIGENT FIRE TECHNOLOGY A D

More information

Protec. Protec Algo-Tec TM 6100 Interactive Digital Addressable Fire Control System. Fire Detection - Addressable

Protec. Protec Algo-Tec TM 6100 Interactive Digital Addressable Fire Control System. Fire Detection - Addressable Protec Fire Detection - Addressable Protec Algo-Tec TM 6100 Interactive Digital Addressable Fire Control System ADDRESSING SAFETY SYSTEMS WITH INTELLIGENCE Fire Detection - Addressable Protec Protec Algo-TecTM

More information

Features. Omni2 Door Warning Sign Alarm Annunciator DATASHEET. Model C1190B Door Warning Sign

Features. Omni2 Door Warning Sign Alarm Annunciator DATASHEET. Model C1190B Door Warning Sign Features DATASHEET Connects to multiple sensing instruments One/Two Channel Device Bright solid state LED Alarm Display Audible Alert (internal and external) High reliability, fully dual redundant alarm

More information

La Marche Manufacturing Company Option 16 Series. Digital Combined Accessory Package. Installation and Operation Manual

La Marche Manufacturing Company   Option 16 Series. Digital Combined Accessory Package. Installation and Operation Manual La Marche Manufacturing Company www.lamarchemfg.com Option 16 Series Digital Combined Accessory Package Installation and Operation Manual This manual is subject to change without notice. You may obtain

More information

Control Panel User Guide (TO BE RETAINED BY THE USER)

Control Panel User Guide (TO BE RETAINED BY THE USER) Fire Detection & Alarm System Control Panel V3 (Suitable for Quadnet control panels from V2.00) Control Panel User Guide (TO BE RETAINED BY THE USER) 26-0585 Issue 7 Fike s policy is one of continual improvement

More information

Application, Installation, Operation & Maintenance Manual

Application, Installation, Operation & Maintenance Manual APPROVED BY:JBJ PRESCIENT III FIRE ALARM & GAS EXTINGUISHING CONTROL PANEL Application, Installation, Operation & Maintenance Manual PAGE 1 of 43 CONTENTS 1. INTRODUCTION... 3 2. GENERAL DESCRIPTION...

More information

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels CF5000, MF5000 and FXP5000 Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels 16 zone panels Contents PANEL INSTALLATION...3 Installation...3 PANEL WIRING... 3 Mains power

More information

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels Installation and user manual for the FX range of fire panels 1, 2, 4 and 8 zone panels Contents Panel installation 3 Panel connections 3 Wiring connection drawings 4 Panel facilities 6 Installation check

More information

La Marche Manufacturing Company Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual

La Marche Manufacturing Company   Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual La Marche Manufacturing Company www.lamarchemfg.com Option 46 Series Digital Combined Accessory Package Installation and Operation Manual This manual is subject to change without notice. You may obtain

More information

Installation Manual. Premier IXP-W INS538

Installation Manual. Premier IXP-W INS538 Installation Manual Premier IXP-W INS538 1. Contents 1. Contents... 2 2. Premier IXP-W Interface... 3 Premier 8XP-W & 32XP-W Firmware... 3 3. Quick Start Guide... 4 4. System Overview... 5 Mounting the

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

Tinytag Plus LAN Data Logger with Temperature & Relative Humidity Probe (-25 to +85 C/0 to 100% RH) Standalone. Tinytag Connect

Tinytag Plus LAN Data Logger with Temperature & Relative Humidity Probe (-25 to +85 C/0 to 100% RH) Standalone. Tinytag Connect connect The TE-4500 is a temperature and relative humidity data logger that plugs directly into a network point and communicates across a LAN. The logger can be managed as a standalone logger, in conjunction

More information

The EN54 Part 2 & 4 Fire System

The EN54 Part 2 & 4 Fire System Scope of work: To design, supply, install and commission an Analogue Addressable Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54

More information

R Series Remote Annunciators and Expander Installation and Operation Guide

R Series Remote Annunciators and Expander Installation and Operation Guide GE Security R Series Remote Annunciators and Expander Installation and Operation Guide P/N 3100969 REV 1.0 ISS 15JUL08 Copyright Copyright 2008 GE Security, Inc. All rights reserved. This document may

More information

The ID51 & ID52 can be upgraded to 2 loops without the need to change back box. FEATURES. Intelligent Features

The ID51 & ID52 can be upgraded to 2 loops without the need to change back box. FEATURES. Intelligent Features 990-052, Issue 6 20 March 2006 ID50 Series Single Loop Intelligent Fire Alarm Panels Section: Intelligent Fire Alarm Panels GENERAL The NOTIFIER ID50 series single loop intelligent fire alarm panels, has

More information

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

ZX1e ZX2e ZX5e. Document No Issue 01 user manual ZX1e ZX2e ZX5e Document No. 996-130 Issue 01 user manual MORLEY-IAS ZX2E/ZX5E Fire Alarm Control Panels Table of Contents 1 INTRODUCTION... 4 1.1 NOTICE... 4 1.2 WARNINGS AND CAUTIONS... 4 1.3 NATIONAL

More information

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

Syncro AS. Analogue Addressable Fire Control Panel. User Manual Syncro AS Analogue Addressable Fire Control Panel User Manual Man-1100 Issue 02 Nov. 2008 Index Section Page 1. Introduction...3 2. Safety...3 3. Panel Controls...4 3.1 Access Level 1...4 3.2 Access Level

More information

Panel Functions & Indicators - Key to Icons General & Zone Fire LEDs ACCEPT SOUNDERS START/ STOP RESET BUZZER MUTE KEYSWITCH DELAY ON/OFF ITEM SELECT

Panel Functions & Indicators - Key to Icons General & Zone Fire LEDs ACCEPT SOUNDERS START/ STOP RESET BUZZER MUTE KEYSWITCH DELAY ON/OFF ITEM SELECT Islenska Français Deutsch Nederlands Svenska EN54-8 Zone Conventional Fire Control Panel User Manual 997-493-00, Issue 0 November 003 Panel Functions & Indicators - Key to Icons General & Zone Fire LEDs

More information

ZSC100 Gas Detection and Alarm System Controller

ZSC100 Gas Detection and Alarm System Controller ZSC100 Gas Detection and Alarm System Controller User Guide 1- Introduction... 3 1.1- General description... 3 1.2- Cautions and warnings... 3 2- Control panel... 4 2.1 Control panel overview... 4 2.2

More information

21-light Remote Annunciator. Owner s Manual

21-light Remote Annunciator. Owner s Manual 21-light Remote Annunciator Owner s Manual Annunciator Description... Inside Font Cover Detailed Specifications... 1 Environmental Specifications... 1 Power Supply Requirements... 1 Communication With

More information

KFP-CF Series Operation Manual

KFP-CF Series Operation Manual KFP-CF Series Operation Manual P/N 501-415103-2-31 REV 03.10 ISS 13NOV13 Copyright Trademarks and patents Manufacturer Version Certification European Union directives Contact information 2013 UTC Fire

More information

The supplier and installer of the system should be approved by the local civil defence authority.

The supplier and installer of the system should be approved by the local civil defence authority. ANALOGUE ADDRESSABLE FIRE ALARM SYSTEM 1. Scope of Work The contractor shall supply, install, test and commission a modern Analogue Addressable Fire Detection and Alarm System of an approved manufacturer

More information

Functional Performance Test

Functional Performance Test Fire Alarm Control Panel & Fire Alarm Annunciator Panel Notify all building occupants that testing will be conducted. Fire alarm contractor shall have personnel with 2-way radios at the fire alarm control

More information

FIREBETA EXTINGUISHING CONTROL PANEL (ECP)

FIREBETA EXTINGUISHING CONTROL PANEL (ECP) F I R E D E T E C T I O N A N D C O N T R O L FIREBETA EXTINGUISHING CONTROL PANEL (ECP) Three versions: 2 areas of detection and 1 area extinguishing 4 areas of detection and 1 area extinguishing 4 areas

More information

The EN54 Part 2, 4 and 13 Fire System

The EN54 Part 2, 4 and 13 Fire System Scope of work: To design, supply, install and commission an Analogue Addressable Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54

More information

Fire Alarm Control Panel. System Maintenance and Log Book

Fire Alarm Control Panel. System Maintenance and Log Book Fire Alarm Control Panel System Maintenance and Log Book Fire Alarm System Maintenance A fire alarm system must provide early and reliable warning of the outbreak of fire. To achieve this, the system remains

More information

20 Light Remote Annunciator

20 Light Remote Annunciator Light Remote Annunciator Owner s Manual Surface Mount Flush Mount 94-95- Standard Annunciator 94-, 94-95-, 95-4- 4- Annunciator w/remote Relay Panel 4-, 4-4-, 4-49-, 49-49-, 49- Time Multiplexed Annunciator

More information

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3 INTELLIGENT FIRE TECHNOLOGY Twinflex and Multipoint V3 User Guide (TO BE RETAINED BY USER) 26-0340 Issue 3 Rafiki Protection Limited Rafiki policy is one of continual improvement and the right to change

More information

DATAssure. Laboratory wireless alarm & monitoring system

DATAssure. Laboratory wireless alarm & monitoring system DATAssure Laboratory wireless alarm & monitoring system Wireless alarm & monitoring system A new monitoring generation The DATAssure wireless monitoring system is used across a broad range of market sectors

More information

DISABLED TOILET / EMERGENCY ASSISTANCE ALARMS

DISABLED TOILET / EMERGENCY ASSISTANCE ALARMS Folknoll Group Ltd. DISABLED TOILET / EMERGENCY ASSISTANCE ALARMS BS 8300:2009 AND DOCUMENT M COMPLIANT TOUGH, VANDAL RESISTANT IDEAL FOR PUBLIC USE File:DT 7800-018 DS1 V104 Disabled Toilet Alarm Product

More information

USER MANUAL & MAINTENANCE GUIDE OG OO

USER MANUAL & MAINTENANCE GUIDE OG OO M+48. USER MANUAL & MAINTENANCE GUIDE OG OO What to do if the Fire Alarm Panel shows an Alarm (Red LED) Write down which LEDs are lit (either in the log book, or on a piece of paper for transferring to

More information

The system is expanded via the RCC network with each RCC capable of passing information to and from up to 31 detection or output devices.

The system is expanded via the RCC network with each RCC capable of passing information to and from up to 31 detection or output devices. FireCell Radio Hub Fully addressable Wireless activation Third party approved (EN54) 2-way radio communication Loop powered Diagnostics port Range in excess of 150 metres Overview The model FCX-500-001

More information

Loadstar AC/DC Systems

Loadstar AC/DC Systems WARRANTY W A R R A N T Y YEAR The Loadstar range of AC/DC central battery units comply with the latest relevant European and British standards. High quality, cost effective units provide secure sources

More information

Conventional Fire System. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI User Manual

Conventional Fire System. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI User Manual Conventional Fire System BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI User Manual Contents Contents 1. INTRODUCTION... 3 1.1 Purpose...3 1.2 Definitions....3 Premises Management...

More information

ZP2 Series Operation Manual

ZP2 Series Operation Manual ZP2 Series Operation Manual P/N 501-405203-2-31 REV 03.10 ISS 07NOV13 Copyright Trademarks and patents Manufacturer Version Certification European Union directives Contact information 2013 UTC Fire & Security.

More information

System 800 Addressable Fire Detection & Alarm System

System 800 Addressable Fire Detection & Alarm System SECTION 5: page 1 Section 5: System 800 Addressable Fire Detection & Alarm System SECTION 5: page 3 10 reasons to specify 800 1 Plug and Play A user friendly panel not requiring special software tools

More information

AXS Strikemaster Engineering Manual

AXS Strikemaster Engineering Manual AXS Strikemaster AXS Strikemaster Programming and Operation Manual Jan 2014 Page 1 of 23 Table of Contents Important Note... 3 Features and Benefits... 3 Ordering Details... 4 Dimensions... 5 Installation...

More information

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009 Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual Man-1048 Issue 05 October 2009 CONTENTS Contents... Page Safety & Installation...2 Installation - continued...3

More information

Operating manual and Log book for the range of 1,2,4 and 8 zone fire Control and Repeat panels

Operating manual and Log book for the range of 1,2,4 and 8 zone fire Control and Repeat panels Operating manual and Log book for the range of 1,2,4 and 8 zone fire Control and Repeat panels The panels are designed in accordance with the requirements of EN54 Part 2:1997 (and include optional clauses

More information

SECURITY SYSTEM NOTES SPECIAL CODES ENTRY / EXIT DELAY TIMES ARM / DISARM CODES ZONE DESCRIPTIONS

SECURITY SYSTEM NOTES SPECIAL CODES ENTRY / EXIT DELAY TIMES ARM / DISARM CODES ZONE DESCRIPTIONS SECURITY SYSTEM NOTES Installing/Service Company For Service Call SPECIAL CODES "Chime" Digit 1 "Partial Arm" Digit 2 "Quick Arm" Digit 3 ENTRY / EXIT DELAY TIMES Exit Delay Time Entry Delay Time Secondary

More information

USER MANUAL CEF AP28 CONTROL PANEL

USER MANUAL CEF AP28 CONTROL PANEL USER MANUAL CEF AP28 CONTROL PANEL AP28 WARNINGS This product has mains voltage present within the housing. Please take the necessary precautions in not allowing any liquid to spill on or into the housing.

More information

Fire control panels FC360

Fire control panels FC360 Cerberus TM FIT Fire control panels FC360 FC361-ZZ, FC361-ZA, FC361-YZ, FC361-YA Fire control panels (1-loop) for addressable peripheral devices with integrated operating unit One loop with 126 addresses

More information

HRX Technical Manual. Version 1.2

HRX Technical Manual. Version 1.2 HRX 5000 Technical Manual Version 1.2 Contents: Specification...2 Connectors...5 RS-485 Network Connectors (J6 and J7)...5 RS-232 to Printer (J19)...6 RS-232 to PC (J8)...7 TCP/IP...8 Power (J21)...9 Fire

More information

Zerio Plus EDA-D6000 Radio Combined Heat Detector and Sounder Installation Instructions

Zerio Plus EDA-D6000 Radio Combined Heat Detector and Sounder Installation Instructions Zerio Plus EDA-D6000 Radio Combined Heat Detector and Sounder Installation Instructions EN54-3:2001+A1:2002+A2:2006 EN54-5:2000+A1:2002 EN54-25:2008 0359 Electro Detectors Ltd. Electro House Edinburgh

More information

2) This manual covers Fire and General Alarm systems. The differences are described in the appropriate sections.

2) This manual covers Fire and General Alarm systems. The differences are described in the appropriate sections. ISSUES ISSUE DATE RELEASED DETAILS OF CHANGE AUTHOR 4 Rev 2 September 2004 Changes for 4000 series. DB 4 Rev 3 April 2005 Screen shots updated and other minor changes K.Z. 4 Rev 4 September 2006 4 Rev

More information

LEAKSTOPPER RANGE Multizone water leak detection systems

LEAKSTOPPER RANGE Multizone water leak detection systems LEAKSTOPPER RANGE Multizone water leak detection systems WHAT DOES THE PRODUCT DO? The LeakStopper detects water leaks and instantly triggers an alarm to warn you. It is capable of monitoring between 2

More information

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel INSTALLATION, OPERATION AND MAINTENANCE MANUAL Version: CN-PM-1000.VER1.1-12/2012 EN54 INFORMATION In accordance with EN 54-2 clause 13.7, the maximum

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd full installation, commissioning and operating manuals can be downloaded from www.haes-systems.co.uk combined addressable / conventional fire alarm control panel User Guide Approved Document No. MFBU-04

More information

EMERGENCY ASSISTANCE ALARMS

EMERGENCY ASSISTANCE ALARMS Folknoll Group Ltd. EMERGENCY ASSISTANCE ALARMS BS 8300:2009 AND DOCUMENT M COMPLIANT TOUGH, VANDAL RESISTANT IDEAL FOR PUBLIC USE File:DT 7800-018 DS1 V105 Emergency Assistance Product Information.Docx

More information

ViewMatrix. Software for Online Monitoring & Control of Matrix2000 Conventional Fire Alarm Panels. Version: 2.0 Revision: 0.1

ViewMatrix. Software for Online Monitoring & Control of Matrix2000 Conventional Fire Alarm Panels. Version: 2.0 Revision: 0.1 ViewMatrix Software for Online Monitoring & Control of Matrix2000 Conventional Fire Alarm Panels Version: 2.0 Revision: 0.1 CONTENTS 1. Introduction...3 2. Keyboard...5 2.1 POWER indication - Normal Operation...5

More information

Installation Manual Premier Elite IXP-W

Installation Manual Premier Elite IXP-W Installation Manual Premier Elite IXP-W INS538-2 1. Contents 1. Contents... 2 2. Premier IXP-W Interface... 3 Premier Elite 8XP-W & 32XP-W Firmware... 3 3. Quick Start Guide... 4 4. System Overview...

More information

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions. 11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

More information

REPEATER FS5200R OPERATION MANUAL

REPEATER FS5200R OPERATION MANUAL REPEATER FS5200R OPERATION MANUAL 1. Function Repeater FS5200R receives and transmits data for Fire condition and Fault condition from remote fire control panels (repeaters) and provides information about

More information

Adam Equipment. NCSA 20plus. (P.N Revision B - September 2012)

Adam Equipment. NCSA 20plus. (P.N Revision B - September 2012) Adam Equipment NCSA 20plus (P.N. 7.00.6.6.0240 - Revision B - September 2012) Adam Equipment Company 2012 1.0 CONTENTS 1.0 CONTENTS...1 2.0 INTRODUCTION...2 2.1 FEATURES...2 2.2 TECHNICAL SPECIFICATIONS...2

More information

Protec. Protec Algo-Tec TM 6500 Interactive Digital Addressable Fire Control System with Algo-Tec 6600 Bridging Network. Fire Detection - Addressable

Protec. Protec Algo-Tec TM 6500 Interactive Digital Addressable Fire Control System with Algo-Tec 6600 Bridging Network. Fire Detection - Addressable Protec Protec Fire Detection Pty Ltd Protec Algo-Tec TM 6500 Interactive Digital Addressable Fire Control System with Algo-Tec 6600 Bridging Network ADDRESSING SAFETY SYSTEMS WITH INTELLIGENCE CAUTION

More information

General Purpose IO Technical Manual

General Purpose IO Technical Manual General Purpose IO Technical Manual Revision 1.06 8 November 2013 Pakton Technologies PAE222 GPIO Manual.docx Page 1 of 21 Revision 1.06 Last updated 8/11/2013 Table of Contents INTRODUCTION...3 Scope

More information

NEVER ACTIVATE THE STROBE WITH THE PCB OUT OF ITS PROTECTIVE CASE. EXTREME CARE IS ADVISED TO REMOVE THE RISK OF ELECTRIC SHOCK.

NEVER ACTIVATE THE STROBE WITH THE PCB OUT OF ITS PROTECTIVE CASE. EXTREME CARE IS ADVISED TO REMOVE THE RISK OF ELECTRIC SHOCK. VI64 Version:1.1 Issued 06/12/2007 INTRODUCTION Ventcroft s external sounder/strobes offer an unsurpassed range of models which provide for virtually any installation need. Most models feature a robust

More information

The EN54 Part 2 and 4 Fire System

The EN54 Part 2 and 4 Fire System Scope of work: To design, supply, install and commission a Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54 Part 2 and 4 Fire

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd Product Data Sheet Mx-4000 Series User Manual MX-4100, MX-4200, MX-4400, Mx-4400/LE & Mx-4800 Fire Alarm Control Panels The operation and functions described in the manual are available from Software Versions

More information

Prem1er EVACS16. Installation Manual VOICE ALARM CONTROL PANEL 4 16 ZONES

Prem1er EVACS16. Installation Manual VOICE ALARM CONTROL PANEL 4 16 ZONES Prem1er EVACS16 VOICE ALARM CONTROL PANEL 4 16 ZONES Installation Manual Approved Document No: GLT.MAN-141 PAGE 1 INDEX INDEX... 2 Summary... 3 Safety information & use of this manual... 5 Installation

More information

ADVISOR CD User Manual. Software from version: V

ADVISOR CD User Manual. Software from version: V ADVISOR CD 3403 User Manual Software from version: V6.0 142715999-1 COPYRIGHT SLC BV 1996. All rights reserved. No part of this publication may be reproduced, transmitted, stored in a retrieval system,

More information

Zerio Plus EDA-R6000 Radio Combined Optical Smoke Detector and Sounder Installation Instructions

Zerio Plus EDA-R6000 Radio Combined Optical Smoke Detector and Sounder Installation Instructions Zerio Plus EDA-R6000 Radio Combined Optical Smoke Detector and Sounder Installation Instructions EN54-3:2001+A1:2002+A2:2006 EN54-7:2000+A1:2002+A2:2006 EN54-25:2008 0359 Electro Detectors Ltd. Electro

More information

Conventional & Twin-wire Fire System

Conventional & Twin-wire Fire System Conventional & Twin-wire Fire System Advanced Customer Service At Advanced we re not just famous for our fire systems. Our Advanced360 customer support, service and technical training are widely acknowledged

More information

Fire Signalling. Signalling Solutions

Fire Signalling. Signalling Solutions Fire Signalling Signalling Solutions Introduction Introduction Klaxon Signals manufactures the world s largest range of sound signalling equipment and solutions for the European and worldwide market place.

More information

EL-OEM-3 OEM Packaged Voltage Data Logger

EL-OEM-3 OEM Packaged Voltage Data Logger OEM Packaged Voltage Data Logger ORDERING INFORMATION Standard Data Logger (Data Logger only. EasyLog software available from ) EL-OEM-3 FEATURES PCB Mounted (2.54mm pitch, header sockets) 0-2.4 Volt d.c.

More information

ZP3 Operator & Maintenance Manual Version 1

ZP3 Operator & Maintenance Manual Version 1 ZP3 Operator & Maintenance Manual Version 1 Introduction Thank you for selecting Clymac Ltd. Clymac can provide maintenance for the system, emergency call out, telephone support and any modifications required

More information

TOTAL SOLUTIONS. Liquid Level Control Product Guide. MATELEC AUSTRALIA innovative by design

TOTAL SOLUTIONS. Liquid Level Control Product Guide. MATELEC AUSTRALIA innovative by design TOTAL SOLUTIONS Liquid Level Control Product Guide MATELEC innovative by design Liquid Level Control Contents Dual Pump Controllers Section 1 The Range Common Features Operating Data Control Logic Setup

More information

one Operating instructions SenTRI ONE panel-based Fire detection and alarm system

one Operating instructions SenTRI ONE panel-based Fire detection and alarm system SenTRI ONE panel-based Fire detection and alarm system one 042bc/14 4188-978 issue 2_04-10_SenTRI ONE system oper Part of Document pack 2535-235 issue 2 1 Contents User responsibility - - - - - - - - -

More information

Telemetry Communications Device. Installation Guide. Interface for the Emizon managed network. Issue 1: February 2008

Telemetry Communications Device. Installation Guide. Interface for the Emizon managed network. Issue 1: February 2008 TCD Telemetry Communications Device Installation Guide Interface for the Emizon managed network Issue 1: February 2008 This guide sets out a simple check list together with a step-by-step guide to the

More information

Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual

Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual Revision 4/01.17 Contents 1. Introduction... 6 2. Terminology... 6 3. Function... 8 4. Technical data... 8 4.1. Physical configuration...

More information

User Operation Manual

User Operation Manual APPROVED BY: JBJ PRESCIENT III FIRE ALARM & GAS EXTINGUISHING CONTROL PANEL User Operation Manual PAGE 1 of 6 1 CONTENTS 1. FIRE - GENERAL... 3 2. FIRE - ZONES 1 OR 2 - AUTOMATIC MODE... 3 3. FIRE - ZONES

More information

Scimitar user manual & log book. Petersfield Business Park, Bedford Rd, Petersfield, Hampshire GU32 3QA Tel: Fax:

Scimitar user manual & log book. Petersfield Business Park, Bedford Rd, Petersfield, Hampshire GU32 3QA Tel: Fax: Petersfield Business Park, Bedford Rd, Petersfield, Hampshire GU32 3QA Tel: 01730 268 231. Fax: 01730 265 552 Scimitar user manual & log book SCIMITAR USER MANUAL Approved Document No. DFU7001001 Rev 2

More information