Model TL104 MANTL104. Test Lamp for Flame Detection

Size: px
Start display at page:

Download "Model TL104 MANTL104. Test Lamp for Flame Detection"

Transcription

1 Model TL104 Test Lamp for Flame Detection The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically authorized in writing by General Monitors. Instruction Manual General Monitors reserves the right to change published specifications and designs without prior notice. MANTL104 Part No. Revision MANTL104 C/02-06

2 This page is intentionally left blank. ii

3 Table of Contents ABOUT THIS MANUAL...IV Format Conventions... iv Notes, Cautions, and Warnings... iv Contacting Customer Support... iv 1.0 INTRODUCTION Notice Special Warning Description Test Lamp Operating Principle TEST LAMP COMPONENTS Lamp Housing Assembly Microcontroller Solid State Relay Dip Switch and Setting Mode Jumper and Settings Lead Acid Rechargeable Battery Recharge Jack and Cap Test Lamp Momentary Contact Button Red Aluminum Case and Gray Cap USE AND OPERATION TEST LAMP MAINTENANCE AND WARRANTY Maintenance Warranty TROUBLESHOOTING GUIDE CUSTOMER SUPPORT General Monitors Offices Other Sources of Help APPENDIX Specifications...9 iii

4 About This Manual This manual provides instructions for operating, and maintaining the General Monitors (GM) TL104 Test Lamp. The intended audience includes installation personnel, field service technicians, and other technical staff involved in using a TL104. Format Conventions Several format conventions are used throughout this manual for Notes, Cautions, and Warnings. These conventions are described below. Notes, Cautions, and Warnings NOTE: Notes provide supplementary details such as exception conditions, alternate methods for a task, time saving tips, and references to related information. CAUTION: These notices describe precautions to prevent hazardous conditions that may damage the equipment. WARNING: These notices describe precautions to prevent hazardous conditions that may cause injury to people working with the equipment. Contacting Customer Support For additional product information not contained in this manual, please contact General Monitors Customer Support. Refer to Section 6.0 for contact information. iv

5 1.0 Introduction 1.1 Notice All information contained in this instruction manual may be used only to set up and operate the TL104 Test Lamp with flame detectors provided by General Monitors. The sale of the test lamp does not license the user to reproduce GM drawings, or to utilize any information contained in this manual without prior written permission. The TL104 Test Lamp is easy to set up and operate. However, this manual should be read in full, and the information contained herein understood, before attempting to operate the test lamp in service. 1.2 Special Warning WARNING: CAUTION: UV light is injurious to one s vision. Do not stare into functioning lamp. Wear eye protection of UV blocking glasses to prevent eye injury. Do not attempt to recharge the TL104 in areas where combustible gases or potential explosive gases are located. 1.3 Description The TL104 is a battery operated rechargeable test lamp specifically designed to test General Monitors UV, UV/IR and Digital Frequency IR flame detection systems. The test lamp provides a high-energy, broadband radiation source that emits sufficient energy in both the ultraviolet and infrared spectra to activate UV and/or IR detectors. To simulate the flickering of a fire, the test lamp automatically flashes at various selectable rates. The TL104 is designed for use in Class I, Division 1, 2, Groups C and D areas. The test lamp functions on internal lead-acid batteries which, when fully charged, allows continuous operation for 20 to 30 minutes. An internal circuit prevents operation when the battery is low. 1.4 Test Lamp Operating Principle The test lamp can function in two modes, TL104 and TL103 mode. The mode is set by a function jumper and can be changed at any time. When set in TL103 mode, the jumper makes the TL104 Test Lamp backwards compatible with older TL103 Test Lamps. It also allows the triggering of alarm or test mode in many General Monitors detectors including, the FL3XXX Series and also the UV/IR Type VI detectors. In TL103 mode, configuring the dipswitch can consign the test lamp to a particular detector. In TL103 mode, the dipswitch sets the flash timing for FL3XXX Series and also the UV/IR Type VI detectors. In TL104 mode, the test lamp can function to trigger test mode in newer flame detectors, such as, the FL4000. The TL104 mode has a higher flash rate than the TL103 mode. TL104 mode flash rate is controlled by a microcontroller, which also monitors battery voltage and shuts off the test lamp when the battery voltage is low. 1

6 2.0 Test Lamp Components 2.1 Lamp Housing Assembly NOTE: Do not put fingerprints on the reflector or the lamp case, as this will reduce the available radiation required by the individual detector. The lamp housing assembly consists of a gold-plated parabolic reflector with the lamp affixed to its center. The test lamp s functional board can be accessed under the lamp housing. 2.2 Microcontroller The TL104 s mode-flashing timing is controlled by a microcontroller. This device also monitors battery voltage and shuts down the flash lamp output when the battery charge is low. The microcontroller resides on the functional board. 2.3 Solid State Relay The VN920 solid-state relay replaces the functions of the traditional electromechanical relay and is silent. The TL104 Test Lamp is therefore silent during its operation, unlike the older TL103 Test Lamp. The solid-state relay resides on the functional board. 2.4 Dip Switch and Setting The four-position dipswitch is used to configure the test lamp in TL103 mode to function with FL3XXX and UV/IR Type VI detectors. Positions of the dipswitch for each of these detectors are noted in Table 1 and are available for reference in the TL104 nameplate. The dipswitch resides on the functional board. 2.5 Mode Jumper and Settings The mode jumper has two positions, one for TL104 mode and another for the TL103 mode. TL104 mode features a higher flash rate and is the mode required for new flame detectors such as the FL4000. Detectors FL3XXX and UV/IR Type VI detectors require the TL103 mode. When the TL103 mode is selected, it is important to configure the dipswitch for the specific detector to ensure proper operation (Section 2.4). For further reference see Table 1. The mode jumper and settings reside on the functional board. NOTE: The FL4000 detector will not respond to TL103 mode. 2

7 2.6 Lead Acid Rechargeable Battery The TL104 Test Lamp is powered by a 120V, 2.5Ah lead acid rechargeable battery. It is important to keep the test lamp docked with its battery charger when the test lamp is not being used. This will increase the expected life of the lead acid battery and will always keep the test lamp available for immediate use. NOTE: The normal recharge time for the lead acid rechargeable battery is 14 hours. 2.7 Recharge Jack and Cap The recharge jack is located directly under the aluminum single slotted cap and can be accessed when the aluminum cap is removed. The battery charger is connected to the recharge jack. When this is done and the battery charger is connected to 120 AC power line, the battery will be recharged. 2.8 Test Lamp Momentary Contact Button The test lamp momentary contact button is the red button which, when depressed, will activate the Test Lamp. 2.9 Red Aluminum Case and Gray Cap The red aluminum case and gray cap are designed for explosion proof requirements and are designed for use in Class I, Division 1, 2, Groups C and D areas. 3

8 3.0 Use and Operation Before beginning a flame detector check, adjust the dipswitch setting in the TL104 test lamp according to the type of GM flame detector used. Table 1 shows the dipswitch configurations for GM flame detectors FL3XXX and UV/IR Type VI. Using a fully charged TL104, stand up to the distance specified in Table 1 from the flame detector to be tested and aim the TL104 directly into the detector window. Press the ON button and ensure the high intensity intermittent beam strikes the detector face. If the system is operating normally, the control module will go into a warning condition after a few flashes of the test lamp. If the lamp remains ON for the period set by the time delay adjustment, the controller will go into alarm 1. Before testing any GM flame detector, see Table 1 and Figure 1 to assure that dipswitch settings and mode jumper position are correct for the particular detector. CAUTION: When operating in conditions involving fog, rain or frost, UV and IR radiation are (diminished) with increasing levels of moisture. The moisture level will affect the potential range of the detector. When using the test lamp in conditions of frost, make sure that the lens is free of frost and ice. A plastic card can be used without scratching the lens cap to remove frost build-up. NOTE: Recharging the battery and normal docking of the test lamp when not in use is highly recommended. This will extend the useful life of the battery and also make the test lamp available for immediate use. Normal recharge time is 14 hours. Dipswitch Configuration Jumper Figure 1: Functional board located under lamp assembly NOTE: The dipswitch settings, as shown in Figure 1, are all open. 1 For test initiation with the FL4000 flame detector, please refer to the FL4000 Instruction Manual. 4

9 Detector Test Mode Initiation or/detector Alarm Trigger with TL104 Flame Detector UV/IR Type V & VI Test Lamp Mode Dipswitch Setting Maximum Distance to Detector (ft) TL Results UV/IR Type V & VI triggers into alarm mode FL3000 TL FL3000 triggers into FL3001 TL FL3001 triggers into FL3002 TL FL3002 triggers into FL3100 TL FL3100 triggers into FL3101 TL FL3101 triggers into FL3102 TL FL3102 triggers into FL3110 TL FL3110 triggers into FL3111 TL FL3111 triggers into FL3112 TL103 8 FL3112 triggers into FL4000 TL104 Any dipswitch setting FL4000 TL104 Any dipswitch setting FL4000 TL104 Any dipswitch setting 35 (High Sensitivity) 18 (Medium Sensitivity) 8 (Low Sensitivity) FL4000 TL103 NA NA FL4000 enters test mode FL4000 enters test mode FL4000 enters test mode FL4000 ignores TL103 mode Table 1: Detector Test Mode Initiation or/detector Alarm Trigger with TL104 5

10 4.0 Test Lamp Maintenance and Warranty 4.1 Maintenance Routine maintenance for the test lamp is minimal. When the battery can no longer hold the requisite charge after a 14-hour recharge, the battery must be recycled. General Monitors has a recycle program in place to recycle the used lead-acid battery. When the test lamp is not being used, it is important to ensure that the test lamp is docked on the charger and the charger is connected to a live 120 VAC power cord. Make sure that the test lamp lens is free of frost or large accumulations of moisture during frosty conditions or inclement weather. 4.2 Warranty General Monitors warrants the TL104 Test Lamp and the accessory battery charger to be free from defects in workmanship or material under normal use and service within two (2) years from the date of shipment. General Monitors will repair or replace without charge any equipment found to be defective during the warranty period. Full determination of the nature of, and responsibility for, defective or damaged equipment will be made by General Monitors personnel. Defective or damaged equipment must be shipped prepaid to General Monitors or the representative from which shipment was made. In all cases, this warranty is limited to the cost of the equipment supplied by General Monitors. The customer will assume all liability for the misuse of this equipment by its employees or other personnel. All warranties are contingent upon proper use in the application for which the product was intended and do not cover products which have been modified or repaired without General Monitors approval or which have been subjected to neglect, accident, improper installation or application, or on which the original identification marks have been removed or altered. Except for the express warranty stated above, General Monitors disclaims all warranties with regard to the products sold, including all implied warranties of merchantability and fitness and the express warranties stated herein are in lieu of all obligations or liabilities on the part of General Monitors for damages including, but not limited to, consequential damages arising out of / or in connection with the use or performance of the product. 6

11 5.0 Troubleshooting Guide The following table lists potential problems that can affect the test lamp circuit. Follow the individual steps to pinpoint and define circuit ailments. This section is intended to be a guide in correcting problems, which may arise in the field. General Monitors should be contacted for assistance if the corrective action listed does not eliminate the problem. Condition Test Lamp does not flash Possible Solution Battery may require a recharge Check Table 1 Test Lamp flashes but is unable to trigger detector Verify that dipswitch settings are set as specified in Table 1 Verify Mode Jumper is set according to Figure 1 Test Lamp does not flash, and battery has been recharged for 14 hours Test Lamp does not flash, and battery has been recharged for 14 hours, and lamp filament is not broken Lamp filament may be broken. Check power and lamp connectors Internal battery pack may have blown a fuse Table 2: Troubleshooting Table 7

12 6.0 Customer Support 6.1 General Monitors Offices Area UNITED STATES Corporate Office: Simpatica Circle Lake Forest, CA Phone/Fax/ Toll Free: Phone: Fax: Whithorn Drive Houston, TX UNITED KINGDOM Heather Close Lyme Green Business Park Macclesfield, Cheshire, United Kingdom, SK11 0LR IRELAND Ballybrit Business Park Galway, Republic of Ireland SINGAPORE No. 2 Kallang Pudding Rd. #09-16 Mactech Building Singapore Phone: Fax: gmhou@generalmonitors.com Phone: Fax: info@generalmonitors.co.uk Phone: Fax: info@gmil.ie Phone: Fax: genmon@gmpacifica.com.sg MIDDLE EAST LOB12, #G20 P.O. Box Jebel Ali, Dubai United Arab Emirates 6.2 Other Sources of Help Phone: Fax: gmme@emirates.net.ae General Monitors provides extensive documentation, white papers, and product literature for the company s complete line of safety products, many of which can be used in combination with the TL104. Many of these documents are available online at the General Monitors website at 8

13 7.0 Appendix 7.1 Specifications Operating temperature: Storage temperature: Humidity range: Weight: 5 F to 122 F (-15 C to +50 C) 5 F to 122 F (-15 C to +50 C) 0 to 90 ± 3% RH, non-condensing 7.9 lb (about 3.5 kg) Dimensions: 13 L x 5 D (330 mm L x 127 mm D) Approvals: Charging time: Output spectra: Charger input: Output: Detection Range: CSA, CE Marking 14 hours minimum Broadband emissions in UV, visible and IR 115 V ± 10%, 50/60 Hz ma See Table 1 for maximum distance per flame detector model 9

14 ADDENDUM Product Disposal Considerations This product may contain hazardous and/or toxic substances. EU Member states shall dispose according to WEEE regulations. For further General Monitors product WEEE disposal information please visit: All other countries or states: please dispose of in accordance with existing federal, state and local environmental control regulations. 10

High Temperature Remote Gas Calibrator

High Temperature Remote Gas Calibrator High Temperature Remote Gas Calibrator The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically authorized in writing

More information

Design Manual Installation Operation Maintenance

Design Manual Installation Operation Maintenance Design Manual Installation Operation Maintenance Model FT194 UV/IR Portable Flame Detector Test Lamp 23282 Mill Creek Drive, Suite 215 Laguna Hills, CA 92653 USA +1.949.583.1857 Phone +1.949.340.3343 Fax

More information

Model FMD. Field Mounted Display Module

Model FMD. Field Mounted Display Module Field Mounted Display Module The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically authorized in writing by General

More information

Flame Simulator User Manual. Publication Rev. A

Flame Simulator User Manual. Publication Rev. A Flame Simulator User Manual Publication Introduction This manual contains information for the Flame Simulator from Forney Corporation, 16479 Dallas Parkway, Suite 600, Addison, Texas. www.forneycorp.com

More information

FL500 Modbus Communication Operating Manual. Order No.: /00. MSAsafety.com

FL500 Modbus Communication Operating Manual. Order No.: /00. MSAsafety.com FL500 Modbus Communication Operating Manual Order No.: 10193214/00 MSAsafety.com 1000 Cranberry Woods Drive Cranberry Township, PA 16066 A Phone 1-800-MSA-2222 Fax 1-800-967-0398 For your local MSA contacts

More information

Model Gas Alarm Panel APPLICABILITY & EFFECTIVITY. This manual provides instructions for the following Sierra Monitor products:

Model Gas Alarm Panel APPLICABILITY & EFFECTIVITY. This manual provides instructions for the following Sierra Monitor products: Model 2102 Gas Alarm Panel APPLICABILITY & EFFECTIVITY This manual provides instructions for the following Sierra Monitor products: Model Description 2102-00 Alarm Panel 2 Channel 2102-01 Alarm Panel 2

More information

FM Approved Fire & Gas Detection System

FM Approved Fire & Gas Detection System H a z a r d W a t c h FM Approved Fire & Gas Detection System State of the Art Fire and Intelligent, Modular and Flexible The HazardWatch Integrated Fire and Gas Detection System from General Monitors

More information

Model 4001 Series Single Channel Controller

Model 4001 Series Single Channel Controller Model 4001 Series Single Channel Controller Sierra Monitor Corporation 1991 Tarob Court, Milpitas, CA 95035 (408) 262-6611 (800) 727-4377 (408) 262-9042 - Fax E-Mail: sales@sierramonitor.com Web site:

More information

Model SM100. Aspirated Sampling Module

Model SM100. Aspirated Sampling Module Aspirated Sampling Module The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically authorized in writing by General

More information

Model 2280A. Four Channel Control Module Hydrogen Sulfide Gas Applications

Model 2280A. Four Channel Control Module Hydrogen Sulfide Gas Applications Four Channel Control Module Hydrogen Sulfide Gas Applications The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically

More information

Model 2602A. Zero Two Series Control for Hydrogen Sulfide Gas Applications

Model 2602A. Zero Two Series Control for Hydrogen Sulfide Gas Applications Model 2602A Zero Two Series Control for Hydrogen Sulfide Gas Applications The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent

More information

1022 R/T Remote Monitor

1022 R/T Remote Monitor 1022 R/T Remote Monitor INSTRUCTIONS AMC-1022R/T WITH REMOTE SENSOR OR TRANSMITTER INSTALLATION AND OPERATING INSTRUCTIONS FOR THE AMC-1022R/T UNIT IMPORTANT: Please read these installation and operating

More information

GAS MONITOR Model Model

GAS MONITOR Model Model Sierra Monitor Corporation 1991 Tarob Court, Milpitas, CA 95035 (408) 262-6611 (800) 727-4377 (408) 262-9042 - Fax E-mail: sierra@sierramonitor.com Web Site: www.sierramonitor.com GAS MONITOR Model 2350-00

More information

Model 580A. Two Channel Control Module Combustible Gas Applications

Model 580A. Two Channel Control Module Combustible Gas Applications Two Channel Control Module Combustible Gas Applications The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically authorized

More information

MODEL RLY-DIM-D INSTALLATION INSTRUCTIONS

MODEL RLY-DIM-D INSTALLATION INSTRUCTIONS MODEL RLY-DIM-D INSTALLATION INSTRUCTIONS IMPORTANT SAFEFGUARDS WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD ALWAYS BE FOLLOWED. THESE INCLUDE: READ AND FOLLOW ALL SAFETY INSTRUCTIONS

More information

NIR O P E R A T I N G I N S T R U C T I O N S RETROREFLECTIVE PHOTOEYE U L M O N I T O R E D DEVICE

NIR O P E R A T I N G I N S T R U C T I O N S RETROREFLECTIVE PHOTOEYE U L M O N I T O R E D DEVICE O P E R A T I N G I N S T R U C T I O N S NIR-50-325 RETROREFLECTIVE PHOTOEYE U L 3 2 5-2 0 1 8 M O N I T O R E D DEVICE 4564 Johnston Parkway, Cleveland, Ohio 44128 P. 800 426 9912 F. 216 518 9884 Sales

More information

Flame Simulator: FS-UVIR-975. User Manual

Flame Simulator: FS-UVIR-975. User Manual Flame Simulator: FS-UVIR-975 User Manual 00809-0800-4975 Legal Notice The Flame Simulator described in this document is the property of Rosemount. No part of the hardware, software, or documentation may

More information

Certificate of Compliance

Certificate of Compliance FF0 001 Certificate of Compliance Certificate: 70116279 (LR 025993_0_000) Issued to: General Monitors, Incorporated 26776 Simpatica Circle Lake Forest, California 92630 USA Attention: Larry Vlagea The

More information

Applying Neural Network Technology to the Next Generation Flame Detector

Applying Neural Network Technology to the Next Generation Flame Detector Applying Neural Network Technology to the Next Generation Flame Detector Breakthrough Neural Network Intelligence for Improved False Alarm Immunity www.generalmonitors.com Innovative Technology for Superior

More information

Multipurpose test lamp kit

Multipurpose test lamp kit Multipurpose test lamp kit Reference Manual Part Number: MAN-0131, rev. 4 Release: June 2016 Important Instructions Net Safety Monitoring, Inc (Net Safety) designs, manufactures and tests products to

More information

Reacti-Therm I and III Heating Modules

Reacti-Therm I and III Heating Modules INSTRUCTIONS Reacti-Therm I and III Heating Modules TS-18822 TS-18824 Number TS-18822 TS-18824 Description Reacti-Therm I Heating Module (single block) Reacti-Therm III Heating Module (triple block) 2101.1

More information

FUNCTIONAL SAFETY MANUAL. Gassonic Observer-H and Observer-i Ultrasonic Gas Leak Detector

FUNCTIONAL SAFETY MANUAL. Gassonic Observer-H and Observer-i Ultrasonic Gas Leak Detector FUNCTIONAL SAFETY MANUAL Gassonic Observer-H and Observer-i Ultrasonic Gas Leak Detector The information and technical data disclosed in this document may be used and disseminated only for the purposes

More information

Global Water Instrumentation, Inc.

Global Water Instrumentation, Inc. Instrumentation, Inc. 11390 Amalgam Way Gold River, CA 95670 T: 800-876-1172 Int l: (916) 638-3429, F: (916) 638-3270 High Water Alarm WA400-DC WA400-AC WA400-BU WA400-FS WA400-AL 10/23/06 P/N: 01-527

More information

! "! # Please read these installation and operating instructions completely and carefully before starting.

! ! # Please read these installation and operating instructions completely and carefully before starting. ! "! # $% Please read these installation and operating instructions completely and carefully before starting. File name:3009405d Revised,20/10/2008 Copyright, July 2004 The Armstrong Monitoring Corporation

More information

MODEL FL3102. Digital Frequency Infra-Red (DFIR) Flame Detector MANFL3102. Instruction Manual 07-08

MODEL FL3102. Digital Frequency Infra-Red (DFIR) Flame Detector MANFL3102. Instruction Manual 07-08 MODEL FL3102 Digital Frequency Infra-Red (DFIR) Flame Detector The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically

More information

Model 20201/20201-A/20201-B Wind Sensor Heater. User's Manual. All Weather Inc National Drive Sacramento, CA USA

Model 20201/20201-A/20201-B Wind Sensor Heater. User's Manual. All Weather Inc National Drive Sacramento, CA USA Model 20201/20201-A/20201-B Wind Sensor Heater User's Manual All Weather Inc. 1165 National Drive Sacramento, CA 95834 USA www.allweatherinc.com 20201 Wind Sensor Heater User's Manual CONTENTS INTRODUCTION...1

More information

Testing Emission Source ITES Operating Manual OM

Testing Emission Source ITES Operating Manual OM San Jose CA 95112 Page 1 of 5 Testing Emission Source ITES Operating Manual 50017-001 OM San Jose CA 95112 Page 2 of 5 1. Purpose The Testing Emission Source ITES GSKF.676216.001 (hereinafter after referred

More information

UV/IR Flame Simulator Model FS-1200

UV/IR Flame Simulator Model FS-1200 UV/IR Flame Simulator Model FS-1200 Installation Instructions Document ref: TM380102, Rev. (D), March 2016 218 Little Falls Rd., Cedar Grove, NJ 07009, USA Phone: +1 (973) 239 8398 Fax: +1 (973) 239 7614

More information

Model IR4000S CO 2. Single-Point Carbon Dioxide Monitor. Instruction Manual 12-11

Model IR4000S CO 2. Single-Point Carbon Dioxide Monitor. Instruction Manual 12-11 Single-Point Carbon Dioxide Monitor The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically authorized in writing

More information

Duct Mount. Installation Instructions

Duct Mount. Installation Instructions Duct Mount Installation Instructions 00809-0600-4975 Legal Notice The Flame Detector described in this document is the property of Rosemount. No part of the hardware, software, or documentation may be

More information

Sentry LIQUID LEVEL ALARM MODEL 100 OPERATING MANUAL.

Sentry LIQUID LEVEL ALARM MODEL 100 OPERATING MANUAL. Sentry LIQUID LEVEL ALARM MODEL 100 OPERATING MANUAL www.aquaticsentry.com TABLE OF CONTENTS 1. SAFETY PRECAUTIONS... 3 2. APPLICATION... 3 2.1 HIGH Liquid Level Alarm 2.2 LOW Liquid Level Alarm 3. INSTALLATION...

More information

MaxLite LED Vapor Tight Linear Fixture

MaxLite LED Vapor Tight Linear Fixture General Safety Information To reduce the risk of death, personal injury or property damage from fire, electric shock, falling parts, cuts/abrasions, and other hazards read all warnings and instructions

More information

Owner s Manual. Filterless UV Air Purifier. This Manual Includes:

Owner s Manual. Filterless UV Air Purifier. This Manual Includes: Filterless UV Air Purifier Item No. 203758 Owner s Manual This Manual Includes: Warranty Safety Warnings Operating Instructions Replacement Directions Troubleshooting Tips Cleaning and Maintenance Tips

More information

Interrupted Ignition Series Oil Primary Control

Interrupted Ignition Series Oil Primary Control Interrupted Ignition Series Oil Primary Control Application Guide & Installation Instruction for ICM1511*, ICM1512*, ICM151*, ICM1514* For more information on our complete range of American-made products

More information

CA5000 Liquid CO 2 Freezer Backup System

CA5000 Liquid CO 2 Freezer Backup System CA5000 Liquid CO 2 Freezer Backup System OPERATING INSTRUCTIONS MANUAL HAMPSHIRE CONTROLS CORPORATION ONE GROVE STREET / P.O. BOX 516, DOVER, NEW HAMPSHIRE USA 03821 TEL. (603) 749-9424 FAX (603) 749-9433

More information

UVS & UVE REMOTE LAMP AIR DISINFECTION SYSTEMS OWNERS GUIDE

UVS & UVE REMOTE LAMP AIR DISINFECTION SYSTEMS OWNERS GUIDE UVS & UVE REMOTE LAMP AIR DISINFECTION SYSTEMS OWNERS GUIDE Models: UVS- 1200T, 1900T, 1202T, 1902T Models: UVE- 1200T, 1900T, 1202T, 1902T Table of Contents: Page 2- Shipping and Packing List, Safety

More information

RK / RK Methane Detector Operator s Manual

RK / RK Methane Detector Operator s Manual 61-1006RK / 61-0192RK Methane Detector Operator s Manual Part Number: 71-0228RK Revision: 0 Released: 10/29/18 www.rkiinstruments.com WARNING Read and understand this instruction manual before operating

More information

Flame Simulator: FS-IR-975. User Manual

Flame Simulator: FS-IR-975. User Manual Flame Simulator: FS-IR-975 User Manual 00809-0500-4975 Legal Notice The Flame Simulator described in this document is the property of Rosemount. No part of the hardware, software, or documentation may

More information

Test Lamp for 210 series flame detectors Non EX

Test Lamp for 210 series flame detectors Non EX Manual TC-169/1 Test Lamp for 210 series flame detectors Non EX http://sense-ware.com Check the website www.sense-ware.com for the latest information and latest version of this manual as well as the applicable

More information

ELECTRIC FIREPLACE HEATER WITH SINGLE GLASS DOOR

ELECTRIC FIREPLACE HEATER WITH SINGLE GLASS DOOR ELECTRIC FIREPLACE HEATER WITH SINGLE GLASS DOOR Model 91797 ASSEMBLY and Operating Instructions Visit our website at: http://www.harborfreight.com Read this material before using this product. Failure

More information

MODEL EPC-D-F-ATS INSTALLATION INSTRUCTIONS ! IMPORTANT SAFEGUARDS!

MODEL EPC-D-F-ATS INSTALLATION INSTRUCTIONS ! IMPORTANT SAFEGUARDS! MODEL EPC-D-F-ATS INSTALLATI INSTRUCTIS! IMPORTANT SAFEGUARDS! WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIS SHOULD ALWAYS BE FOLLOWED, INCLUDING THE FOLLOWING: READ AND FOLLOW ALL SAFETY INSTRUCTIS

More information

Owner s Manual & Safety Instructions

Owner s Manual & Safety Instructions Owner s Manual & Safety Instructions Save This Manual Keep this manual for the safety warnings and precautions, assembly, operating, inspection, maintenance and cleaning procedures. Write the product s

More information

ULTRAMAX GOLD UMX REMOTE LAMP AIR DISINFECTION SYSTEMS w/ ODOR REDUCING TECHNOLOGY (PCO) OWNERS GUIDE

ULTRAMAX GOLD UMX REMOTE LAMP AIR DISINFECTION SYSTEMS w/ ODOR REDUCING TECHNOLOGY (PCO) OWNERS GUIDE ULTRAMAX GOLD UMX REMOTE LAMP AIR DISINFECTION SYSTEMS w/ ODOR REDUCING TECHNOLOGY (PCO) OWNERS GUIDE Models: UMX-1200T/ UMX-1900T / UMX-1202T/ UMX-1902T 120-240VAC Power Input with Remote Mount Lamps

More information

Watt-Muncher Load Bank Manual WATT-MUNCHER. Portable Load Bank. 6 June 2018 Simplex Service Page 1 of 13

Watt-Muncher Load Bank Manual WATT-MUNCHER. Portable Load Bank. 6 June 2018 Simplex Service Page 1 of 13 WATT-MUNCHER Portable Load Bank 6 June 2018 Simplex Service 800-637-8603 Page 1 of 13 This manual was last revised: 6 June 2018 For up-to-date information on this product or others, please contact Simplex

More information

GasScanner 8C. Eight Channel Monitor. Operator s Manual. MINT-0281-XX Rev. A 01/29/08

GasScanner 8C. Eight Channel Monitor. Operator s Manual. MINT-0281-XX Rev. A 01/29/08 GasScanner 8C Eight Channel Monitor Operator s Manual MINT-0281-XX Rev. A 01/29/08 Product Warranty Matheson Tri-Gas, Inc., warrants gas alarm equipment sold by us to be free from defects in materials,

More information

Remote Relay Module (RRM)

Remote Relay Module (RRM) Remote Relay Module (RRM) Instruction Manual WARNING THIS MANUAL MUST BE CAREFULLY READ BY ALL INDIVIDUALS WHO HAVE OR WILL HAVE THE RESPONSIBILITY FOR INSTALLING, USING OR SERVICING THIS PRODUCT. Like

More information

Installation Manual September Opticom Infrared System. Model 798 Emitter Bezel Mount Kit

Installation Manual September Opticom Infrared System. Model 798 Emitter Bezel Mount Kit Installation Manual September 2009 Opticom Infrared System Model 798 Emitter Bezel Mount Kit Installation i Table of Contents 1 About This Manual... 1 1.1 Purpose of Manual... 1 1.2 Manual Conventions...

More information

OPERATION MANUAL. CLASSIC PLUS 14 and CLASSIC PLUS 26 ~ SECTION EN FRANÇAIS

OPERATION MANUAL. CLASSIC PLUS 14 and CLASSIC PLUS 26 ~ SECTION EN FRANÇAIS OPERATION MANUAL CLASSIC PLUS 14 and CLASSIC PLUS 26 READ THIS MANUAL CAREFULLY FOR INSTRUCTIONS ON CORRECT INSTALLATION AND USAGE, AND READ ALL SAFEGUARDS. SECCION ~ EN ESPANOL SECTION EN FRANÇAIS 2003

More information

RK/ RK Oxygen Detector Operator s Manual

RK/ RK Oxygen Detector Operator s Manual 65-2502RK/65-2510RK Oxygen Detector Operator s Manual Part Number: 71-0074RK Revision: A Released: 3/1/11 www.rkiinstruments.com WARNING Read and understand this instruction manual before operating detector.

More information

RAM3 Remote Alarm Module

RAM3 Remote Alarm Module RAM3 Remote Alarm Module INSTRUCTIONS Installation and Operation of the AMC-RAM3 with AMC Monitors IMPORTANT: Please read this installation and operating instructions completely and carefully before starting.

More information

MaxLite LED Round Pendant Highbay Series

MaxLite LED Round Pendant Highbay Series General Safety Information To reduce the risk of death, personal injury or property damage from fire, electric shock, falling parts, cuts/abrasions, and other hazards read all warnings and instructions

More information

MaxLite LED High Bay Fixtures

MaxLite LED High Bay Fixtures General Safety Information To reduce the risk of death, personal injury or property damage from fire, electric shock, falling parts, cuts/abrasions, and other hazards read all warnings and instructions

More information

Ozone + UV Sanitation

Ozone + UV Sanitation Ozone + UV Sanitation Installation Manual 4-2177-01 Rev.C IMPORTANT SAFETY INSTRUCTIONS When installing and operating the DEL Spa Solar Eclipse, basic precautions should always be followed: READ AND FOLLOW

More information

RK/ RK Combustible Gas Detector Operator s Manual

RK/ RK Combustible Gas Detector Operator s Manual 61-1003RK/61-0190RK Combustible Gas Detector Operator s Manual Part Number: 71-0120RK Revision: 0 Released: 2/11/11 www.rkiinstruments.com WARNING Read and understand this instruction manual before operating

More information

GENERAL MONITORS. Protection for life. Product Guide. Total Solution Provider for Gas and Flame Detection

GENERAL MONITORS. Protection for life. Product Guide. Total Solution Provider for Gas and Flame Detection GENERAL MONITORS Protection for life. Product Guide Total Solution Provider for Gas and Flame Detection Protection for Life People around the globe who work in hazardous environments know they can depend

More information

RK-05 Carbon Monoxide Detector Operator s Manual

RK-05 Carbon Monoxide Detector Operator s Manual 65-2433RK-05 Carbon Monoxide Detector Operator s Manual Part Number: 71-0189RK Revision: 0 Released: 5/17/11 RKI Instruments, Inc. www.rkiinstruments.com WARNING Read and understand this instruction manual

More information

Reacti-Therm I and III Heating/Stirring Modules

Reacti-Therm I and III Heating/Stirring Modules INSTRUCTIONS Reacti-Therm I and III Heating/Stirring Modules TS-18821 TS-18823 Number TS-18821 TS-18823 Description Reacti-Therm I Heating/Stirring Module (single block) Reacti-Therm III Heating/Stirring

More information

Filter Oven with Controller 101FRDC00-50 / 101FRDC00-CTRL

Filter Oven with Controller 101FRDC00-50 / 101FRDC00-CTRL Filter Oven with Controller 101FRDC00-50 / 101FRDC00-CTRL Andover Corporation 4 Commercial Drive Salem, New Hampshire 03079-2800 Tel: (603) 893-6888 US Toll Free: (888) 893-9992 Fax: (603) 893-6508 Email:

More information

Beacon 800 Gas Monitor Operator s Manual

Beacon 800 Gas Monitor Operator s Manual Beacon 800 Gas Monitor Operator s Manual Part Number: 71-0037RK Revision: F Released: 4/18/17 www.rkiinstruments.com Product Warranty RKI Instruments, Inc. warrants gas alarm equipment sold by us to be

More information

SEC Signature Process Gas Analyzer

SEC Signature Process Gas Analyzer SEC Signature Process Gas Analyzer Instruction and Operation Manual Sensor Electronics Corporation 5500 Lincoln Drive Minneapolis, Minnesota 55436 USA (952) 938-9486 Fax (952) 938-9617 email sensor@minn.net

More information

Installation, Operation & Service Manual

Installation, Operation & Service Manual Installation, Operation & Service Manual WARNING Improper installation, adjustment, alteration, service or maintenance can result in death, injury or property damage. Read the Installation, Operation and

More information

20 High velocity Air

20 High velocity Air 20 High velocity Air Circulator 66878 Set up and Operating Instructions Distributed exclusively by Harbor Freight Tools. 3491 Mission Oaks Blvd., Camarillo, CA 93011 Visit our website at: http://www.harborfreight.com

More information

Buzzer Unit. TAN-5000 Series. Operating Manual

Buzzer Unit. TAN-5000 Series. Operating Manual PT1E-1040 Buzzer Unit TAN-5000 Series Operating Manual Request for the Customers Read and understand this operating manual before using the buzzer unit. Use the buzzer unit in accordance with the operating

More information

STATUS ALARM ALARM HISTORY POWER HISTORY RESET

STATUS ALARM ALARM HISTORY POWER HISTORY RESET Instruction Manual Model 1582-70L2 RF Switch June 2011, Rev. D CH1 AUTO CH2 SWITCH 1 2 1 2 STATUS 1 2 MODEL 1582 SWITCH CROSS TECHNOLOGIES INC. CH1 ONLINE MANUAL SELECT CH2 SWITCH MANUAL REMOTE ONLINE

More information

CC Series VACUUM PUMPS

CC Series VACUUM PUMPS CC Series VACUUM PUMPS OPERATING MANUAL Thank you for selecting a Javac select product! Please read this operation manual carefully before use. Only suitably qualified personnel should operate this equipment.

More information

1040 Gas Monitor INSTALLATION AND OPERATING INSTRUCTIONS AMC-1040 WITH INTEGRAL ELECTROCHEMICAL SENSOR

1040 Gas Monitor INSTALLATION AND OPERATING INSTRUCTIONS AMC-1040 WITH INTEGRAL ELECTROCHEMICAL SENSOR 1040 Gas Monitor INSTALLATION AND OPERATING INSTRUCTIONS AMC-1040 WITH INTEGRAL ELECTROCHEMICAL SENSOR IMPORTANT: Please read these installation and operating instructions completely and carefully before

More information

RK Combustible Gas Transmitter Operator s Manual

RK Combustible Gas Transmitter Operator s Manual 65-2400RK Combustible Gas Transmitter Operator s Manual Part Number: 71-0060RK Revision: C Released: 1/31/13 www.rkiinstruments.com WARNING Read and understand this instruction manual before operating

More information

G-TECTA Cellaguard Carbon Dioxide and Oxygen Fixed Monitors

G-TECTA Cellaguard Carbon Dioxide and Oxygen Fixed Monitors G-TECTA Cellaguard Carbon Dioxide and Oxygen Fixed Monitors EN Operating Manual 2 3 Contents Safety and Warning information 2 Introduction 3 Operation & Set Up 3 Cellaguard Features 3 Initial Set Up 4

More information

D-TEK Select. Refrigerant Leak Detector

D-TEK Select. Refrigerant Leak Detector O P E R A T I N G M A N U A L D-TEK Select Refrigerant Leak Detector DECLARATION OF CONFORMITY This is to certify that this equipment, designed and manufactured by INFICON Inc., Two Technology Place, East

More information

Environmental Monitoring SmartSlot Card

Environmental Monitoring SmartSlot Card Environmental Monitoring SmartSlot Card AP9612TH Installation and Quick Start Manual Contents Introduction............................. 1 Overview 1 Product inventory 1 Safety notice 2 Your inspection

More information

RK Hydrogen Sulfide Transmitter Operator s Manual

RK Hydrogen Sulfide Transmitter Operator s Manual 65-2331RK Hydrogen Sulfide Transmitter Operator s Manual Part Number: 71-0176RK Revision: B Released: 11/26/14 RKI Instruments, Inc. www.rkiinstruments.com WARNING Read and understand this instruction

More information

RK-05 Combustible Gas Transmitter Operator s Manual

RK-05 Combustible Gas Transmitter Operator s Manual 65-2405RK-05 Combustible Gas Transmitter Operator s Manual Part Number: 71-0180RK Revision: 0 Released: 2/16/11 RKI Instruments, Inc. www.rkiinstruments.com WARNING Read and understand this instruction

More information

GASGUARD NH 3. Ammonia Sensor OPERATING & INSTALLATION MANUAL

GASGUARD NH 3. Ammonia Sensor OPERATING & INSTALLATION MANUAL GASGUARD NH 3 Ammonia Sensor OPERATING & INSTALLATION MANUAL Operating and Installation Manual 2 Table of Contents GasGuard NH 3 Operating and Instruction Manual General description. 4 Installation.. 4

More information

MGC Dock User s Manual

MGC Dock User s Manual Operator s Manual Contents Warnings Statements/Avertisseement... 3 READ FIRST BEFORE OPERATION... 3 Basic Operation... 4 Clip Dock Components... 4 LEDs... 4 Operation... 5 Turning the Clip Dock On and

More information

RK Carbon Monoxide Transmitter Operator s Manual

RK Carbon Monoxide Transmitter Operator s Manual 65-2432RK Carbon Monoxide Transmitter Operator s Manual Part Number: 71-0070RK Revision: P1 Released: July 8, 2001 RKI Instruments, Inc. 1855 Whipple Road Hayward CA 94544 Phone: 800-754-5165 Fax: 510-441-5650

More information

NEUTRONICS MINI ID R-1234yf REFRIGERANT IDENTIFIER OPERATION MANUAL

NEUTRONICS MINI ID R-1234yf REFRIGERANT IDENTIFIER OPERATION MANUAL NEUTRONICS MINI ID R-1234yf REFRIGERANT IDENTIFIER OPERATION MANUAL 456 Creamery Way, Exton, PA 19341, USA Phone: 610.524.8800 Fax: 610.524.8807 Email: info@refrigerantid.com www.refrigerantid.com Page

More information

Wide Range InfraRed (IR) Thermometer with Type K input and Laser Pointer

Wide Range InfraRed (IR) Thermometer with Type K input and Laser Pointer User Manual Wide Range InfraRed (IR) Thermometer with Type K input and Laser Pointer MODEL 42515 Introduction Congratulations on your purchase of the Model 42515 IR Thermometer. The Model 42515 IR thermometer

More information

AMC-RAM-4. Refrigerant Alarm Module USER MANUAL. Please read the installation and operating instructions completely and carefully before starting.

AMC-RAM-4. Refrigerant Alarm Module USER MANUAL. Please read the installation and operating instructions completely and carefully before starting. AMC-RAM-4 Refrigerant Alarm Module USER MANUAL IMPORTANT: Please read the installation and operating instructions completely and carefully before starting. Filename: 3310405B, DOC, AMC_RAM4_Manual.doc

More information

FRESHAIR USER S MANUAL. CAUTION: Read manual carefully for proper procedures and operation.

FRESHAIR USER S MANUAL. CAUTION: Read manual carefully for proper procedures and operation. FRESHAIR Cube Purifies up to 1500 square FEET USER S MANUAL CAUTION: Read manual carefully for proper procedures and operation. welcome Congratulations on your new FreshAir Cube Your FreshAir Cube comes

More information

SAFETY MANUAL. X2200 UV, X9800 IR, X5200 UVIR SIL 2 Certified Flame Detectors

SAFETY MANUAL. X2200 UV, X9800 IR, X5200 UVIR SIL 2 Certified Flame Detectors SAFETY MANUAL X2200 UV, X9800 IR, X5200 UVIR SIL 2 Certified Flame Detectors SAFETY-CERTIFIED Flame DETECTORs This manual addresses the specific requirements and recommendations applicable to the proper

More information

Distributed By: M&M Control Service, INC

Distributed By: M&M Control Service, INC APPROVED The UV1A3/6, UV2/UV2A6/UV2C, 45UV2, 45UV3, UV90-3/6/9 Scanners are used with the M-Series, M-Series II, MicroM, FlameWorx, MB-2 and D-Series controls as well as the Fireye FLAME-MONITOR TM, BurnerLogix

More information

DETCON MODEL AV1/AV2-C1D2M Hazardous Duty Class I. Div 2, Multitone Alarm Station

DETCON MODEL AV1/AV2-C1D2M Hazardous Duty Class I. Div 2, Multitone Alarm Station DETCON MODEL AV1/AV2-C1D2M Hazardous Duty Class I. Div 2, Multitone Alarm Station Operator s Installation and Instruction Manual DETCON, Inc. 3200 Research Forest Dr, The Woodlands, Texas 77387 Ph.281.367.4100

More information

THANK YOU FOR PURCHASING THE LV-H133 TOWER HEPA AIR PURIFIER BY LEVOIT! GET STYLE #LevoitLove #LevoitLifestyle

THANK YOU FOR PURCHASING THE LV-H133 TOWER HEPA AIR PURIFIER BY LEVOIT! GET STYLE #LevoitLove #LevoitLifestyle Model No.: LV-H133 Tower HEPA Air Purifier Questions or Concerns? Please contact us Monday - Friday 9:00 am - 5:00 pm PT at support@levoit.com or (888) 726-8520. THANK YOU FOR PURCHASING THE LV-H133 TOWER

More information

Instruction Manual. 36 in. and 42 in. Popcorn Staging Cabinets

Instruction Manual. 36 in. and 42 in. Popcorn Staging Cabinets Instruction Manual 36 in. and 42 in. Popcorn Staging Cabinets Model Series 2856 and 2855 42 in. Model 2855-00-000 36 in. Model 2856-00-000 10700 Medallion Drive, Cincinnati, Ohio 45241-4807 USA 2016 Gold

More information

Users Manual. LAURUS Systems, Inc. - Ph: Fax:

Users Manual. LAURUS Systems, Inc. - Ph: Fax: Users Manual LAURUS Systems, Inc. - Ph: 410-465-5558 - Fax: 410-465-5257 - www.laurussystems.com Introduction The rad-d is a security and inspection system that detects emissions from radioactive material.

More information

Sentry LIQUID LEVEL CONTROLLER MODEL 120 OPERATING MANUAL.

Sentry LIQUID LEVEL CONTROLLER MODEL 120 OPERATING MANUAL. Sentry LIQUID LEVEL CONTROLLER MODEL 120 OPERATING MANUAL www.aquaticsentry.com TABLE OF CONTENTS 1. SAFETY PRECAUTIONS... 3 2. APPLICATION... 3 2.1 HIGH AND LOW LEVEL ALARM 2.2 PUMP DOWN CONTROLLER 2.3

More information

Module de relais Relay Module. Manuel de l utilisateur 301RW. User Manual ERP /07

Module de relais Relay Module. Manuel de l utilisateur 301RW. User Manual ERP /07 Module de relais Relay Module Manuel de l utilisateur 301RW User Manual ERP 511397 02/07 Relay Module 301R User Manual ERP 511397 2/07 Notices and Trademarks Copyright by Honeywell International Inc.

More information

Solar Powered Wireless Photobeam Sensors

Solar Powered Wireless Photobeam Sensors Installation & Operating Manual Solar Powered Wireless Photobeam Sensors SWPB-50 SWPB-100 SWPB-250 SWPB-400 50ft 100ft 250ft 400ft Create a Virtual Wall with the photobeam sensors! FEATURES Detection Range:

More information

OI-2400-DOCK Multi Gas Docking Station. Operation Manual trevision 2.2w

OI-2400-DOCK Multi Gas Docking Station. Operation Manual trevision 2.2w OI-2400-DOCK Multi Gas Docking Station Operation Manual trevision 2.2w Table of Contents Introduction... 3 Warnings Statements/Avertisseement... 4 Basic Operation... 5 OI-2400-DOCK Components... 5 LEDs...

More information

CO Guardian LLC Document No E. AIRPORT DRIVE Date: TUCSON, AZ CO Guardian LLC 1951 E. Airport Dr.

CO Guardian LLC Document No E. AIRPORT DRIVE Date: TUCSON, AZ CO Guardian LLC 1951 E. Airport Dr. 1951 E. AIRPORT DRIVE Date: 8-20-2004 CO Guardian LLC 1951 E. Airport Dr. Tucson, AZ 85706 OWNERS MANUAL CARBON MONOXIDE DETECTOR MODEL 452-201 REMOTE UNIT MODEL 452-201 OWNERS MANUAL Page 1 of 22 INTENTIONALLY

More information

A10. Installation & Operation Manual. Flow Switch. For the latest version of this manual, visit kteksolidslevel.com.

A10. Installation & Operation Manual. Flow Switch. For the latest version of this manual, visit kteksolidslevel.com. Installation & Operation Manual A10 For the latest version of this manual, visit kteksolidslevel.com. K-TEK Solids Level l 6100 West by Northwest #140 l Tel: +(1) 713.462.7665 l Toll Free 800.245.7056

More information

OWNERS MANUAL OPERATION GUIDE

OWNERS MANUAL OPERATION GUIDE OWNERS MANUAL OPERATION GUIDE Built in Redmond Oregon USA www.laserlinemfg.com P/N 1700-0041 REV. 7.24.17 PRODUCT OVERVIEW The GL1700 Laser Guide was designed from the ground up to provide precise start-stop

More information

OPERATION MANUAL. CLASSIC 10 and CLASSIC 18 SERIAL NUMBER FROM JANUARY 2009 (0109) TO PRESENT

OPERATION MANUAL. CLASSIC 10 and CLASSIC 18 SERIAL NUMBER FROM JANUARY 2009 (0109) TO PRESENT OPERATION MANUAL CLASSIC 10 and CLASSIC 18 SERIAL NUMBER FROM JANUARY 2009 (0109) TO PRESENT READ THIS MANUAL CAREFULLY FOR INSTRUCTIONS ON CORRECT INSTALLATION AND USAGE, AND READ ALL SAFEGUARDS SECCIÓN

More information

Instruction Manual Hydraulic Crimping Tool

Instruction Manual Hydraulic Crimping Tool Instruction Manual Hydraulic Crimping Tool 902-480 Due to continuing improvements, actual product may differ slightly from the product described herein. Read this material before using this product. Failure

More information

MODEL 8143 SIGNAL SELECTOR INSTALLATION AND OPERATION MANUAL

MODEL 8143 SIGNAL SELECTOR INSTALLATION AND OPERATION MANUAL MODEL 8143 SIGNAL SELECTOR INSTALLATION AND OPERATION MANUAL 95 Methodist Hill Drive Rochester, NY 14623 Phone: US +1.585.321.5800 Fax: US +1.585.321.5219 www.spectracomcorp.com Part Number 8143-5000-0050

More information

Instruction Manual. For All Corning Hot Plates, Stirrers, Stirrer/Hot Plates with Digital Displays, and External Temperature Controller (6795PR)

Instruction Manual. For All Corning Hot Plates, Stirrers, Stirrer/Hot Plates with Digital Displays, and External Temperature Controller (6795PR) Instruction Manual For All Corning Hot Plates, Stirrers, Stirrer/Hot Plates with Digital Displays, and External Temperature Controller (6795PR) Corning Cat. No. 230V 230V Model No. Product Top Plate Size

More information

64&3 (6*%& Distributed by! ALDI, INC.! Batavia, IL 60510!

64&3 (6*%& Distributed by! ALDI, INC.! Batavia, IL 60510! 64&3 (6*%& Distributed by! ALDI, INC.! Batavia, IL 60510! www.aldi.us! NOW YOU HAVE PURCHASED AN EASY HOME PRODUCT. YOU CAN BE ASSURED IN THE KNOWLEDGE THAT AS WELL AS YOUR MANUFACTURER S WARRANTY, YOU

More information

STATUS ALARM HISTORY ALARM RESET

STATUS ALARM HISTORY ALARM RESET Instruction Manual Model 1582-42L Data Switch February 1999, Rev 0 CH1 AUTO CH2 SWITCH 1 2 1 2 STATUS 1 2 MODEL 1582 SWITCH CROSS TECHNOLOGIES INC. CH1 ONLINE MANUAL SELECT CH2 ONLINE SWITCH RESET MAN

More information

BioZone Scientific International contact information

BioZone Scientific International contact information BEFORE USE Americas BioZone Scientific International contact information Europe 7751 Kingspointe Parkway, Suite 124 Linnoitustie 4 B Orlando, FL 32819 02600 Espoo United States of America Finland Phone:

More information

FUME HOOD MONITOR ALNOR AIRGARD 200

FUME HOOD MONITOR ALNOR AIRGARD 200 FUME HOOD MONITOR ALNOR AIRGARD 200 OWNER S MANUAL P/N 116670080, REV 09 SEPTEMBER 2014 LIMITATION OF WARRANTY AND LIABILITY (effective April 2014) (For country-specific terms and conditions outside of

More information