Universal fault annunciator for panel mounting

Size: px
Start display at page:

Download "Universal fault annunciator for panel mounting"

Transcription

1 Universal fault annunciator for panel mounting Communication over Ethernet USM - Universal-fault annunciator for panel mounting Low depth housing for panel mounting Versions with 8, 16, 32 or 48 inputs Sealed front panel, protection class IP 54 Integrated buttons, function inputs and relay outputs Networkable over Ethernet IP-Structures Self-monitoring Software parameterisation per PC or over USS Web-Interface All common reporting procedures can be realised Signal and operating voltage ranges 12 V 250 V AC/DC Very bright LED with large reading angle and a wide range of colours Plug-in screw terminals Pockets for individual LED and button labels Datasheet MSM-USM-DB-UK-002

2 msm-usm General system description The universal-fault annunciator USM was developed especially for facilities which are networked by Ethernet structures and it is based on the approved BSM fault annunicator family. USM are available in 4 different versions: 1. System devices a. Acquisition device for acquiring messages over galvanical inputs, as well as the indication and transmission over Ethernet to a Universal fault annunciating server (USS) by a probrietary communication protocol. b. Indication device for display of fault messages, which are provided over the Ethernet interface of the Universal fault annunciating server by a probrietary communication protocol. c. Universal fault annunciating server USS with processing logic and mapping of acqiured and formed messages to indication devices and also to the IEC interface. Transmission to a superior system Indication device Acquisition device 2. Fault annunciating devices with normed interface a. Acquisition device for acquiring messages over galvanical inputs, as well as the indication and forwarding over Ethernet interface with the IEC protocol. Transmission to a superior system Page 2 of 12

3 universal fault annunciator for panel mounting b. Indication device for display of fault messages, which are provided by arbitrary automatisation devices over the Ethernet-interface by the IEC protocol. Acquisition and indication devices The fault annunciator for panel mounting are produced with 8, 16, 32 or 48 channels. The sealed front face comprises 4 buttons and the LED-displays. The fault annunciator is structured into groups of 8 messages each. All fault annunciators have an Ethernet interface in common, which can be used as protocol interface by proprietary protocol or IEC A windows based PC-program is provided for the parameterisation. Herewith the common alarm sequences, input processings, formation of collective reports and horn control can be set, beside protocol parameters, IP address and the assignment to the information object addresses. Customer-specific fault reporting procedures can be preset in the factory. The parameterisation can be done via the RS232-interface or by Ethernet via Telnet-Port. When using the optional USS fault annunciating server, the attached acquisition and indication modules can be configured on alternative via standard internet browser by the integrated webserver of the USS. Message inputs Reporting groups LED colours Buttons Function inputs Relay outputs Collective report According to the design variant the fault annunciator has message inputs, which can be specified with different voltages. They can be preprocessed or receive its messages from the protocol interface. 8 reporting inputs are consolidated to form a reporting group featuring 8 LED displays and a common label pocket. red, green, yellow, white or blue (mixed configuration available on request) The function of the four buttons that are integrated in the front panel depends on the implemented reporting procedure (e.g. message acknowledgement, reset, lamp test etc.) The two function inputs of the fault annunciator are used according to the selected reporting procedure, e.g. external acknowledgement. 4 change-over contacts 1 x live contact / malfunction 3 x message-specific function (e.g. collective report 1, collective report 2, horn etc.) The function of the collective report depends on the parametrization procedure and is specified in the type data sheet. Page 3 of 12

4 Msm-usm Self-monitoring Softwareparameterising The fault annunciator has an integrated self-monitoring signalling fault-free function via LED and relay contact. Possibly connected expansion modules are also monitored. The fault annunciators can be parameterised with a PC program based on Windows. Transferring the parameters is done via connection between RS-232 COM-port and service- and parameterisation interface of the USM or by Ethernet via telnet port. Following parameters can be adjusted: IP-adress Protocol specific parameters Assignment of fault messages and alarming functions Reporting sequence with single- or double frequency flashing light First-up value or new value sequence Collective report static or dynamic Buttons and function inputs can be assigned on available relay outputs (e.g. acknowledgement or lamp test) If inputs available: Inputs configurable for NO- or NC contacts per each Response delay adjustable per input between 5 ms und 60 s Free assignment of inputs to reporting sequences and collective reports Automatic horn acknowledgement (adjustable horn duration time s) Message processing The function specification of a fault annunciator includes message processing, which is structured in three groups: Alarm sequence Formation of collective reports Horn control Alarm sequences Using the the PC program for parameterisation, reporting sequences can be build up from the following components: first-value or new-value sequence 1- or 2-frequency flashlight, steadylight-steadylight or operation fault indication If messages are used as indication displays, they must be parameterised as operation indicators. Default setting in the standard variant: new-value sequence with one frequency flash light and single acknowledgement Page 4 of 12

5 universal fault annunciator for panel mounting Collective reports The different fault reporting procedures use different options to form collective reports. In principle, the following variants may be used: Description static / parallel to input static / parallel to input / acknowledgeable static / parallel to output static / parallel to output / acknowledgeable static / dynamic / parallel to input static / dynamic / parallel to output dynamic Procedure The collective report is set with the first incoming message and resets with the last receding message. The collective report is set with the first incoming message and resets with the last receding message or when acknowledged. The collective report is set with the first incoming message. Once all messages have been gone and acknowledged the collective report is cancelled. The collective report is set with the first incoming message and reset independently from the state of the messages by the acknowledgement. The collective report is set with the first incoming message. For each further message, the collective report is cancelled for approx. 0.8 s and then set again. Once all messages have been receded, the collective report is cancelled permanently. The collective report is set with the first incoming message. For each further message, the collective report is cancelled for approx. 0.8 s and then set again. Once all messages have been receded and acknowledged, the collective report is deleted permanently. The collective report is activated for approx. 0.8 s with each incoming message. Default setting of the standard variant: Horn triggering static / parallel to input Function Selection Meaning Horn triggering (can be set via DIP switch) retriggerable The horn is retriggered by new incoming messages, even if messages are already present. not retriggerable The horn is retriggered for new incoming messages only if no messages are already present. Horn acknowledgement manual (continuous tone) The horn is acknowledged manually via a button or function input. automatic (pulse tone) The horn is acknowledged automatically according to the set time. manual with acknowledgement The horn is acknowledged together with the lamp acknowledgement via the acknowledgement button. There is no special horn acknowledgement. Horn locking none The horn can always be acknowledged. message acknowledgement The horn can only be acknowledged once the message has been acknowledged. Default setting of the standard variant: horn triggering selectable per DIP switch horn acknowledgement manual ( continous tone ) no horn lock Furthermore information about the integrated alarm sequences can be found in the separate documentation Alarm sequences of the EES-fault annunciators Document set SM-MA-ZI-DE. Page 5 of 12

6 Msm-usm Labelling The labelling of the USM is done by designation strips, which are inserted under the protective sheet after releasing the front frame. Designation templates are available in Word and pdf format. With the software parameterising variant the strips can be created directly from the parameterisation program. Universal fault annunciator (USS) The universal fault annunciator USS is able to be networked with acquisition fault annunciators and indication devices and is used for the following tasks: Fault annunciating server for up to 100 networkable fault annunciators Support of up to 3072 messages as plain text messages Selectable routing of acquired and formed messages to IEC-interface, indication modules and processing logic Forming of collective reports and relaying of selective parameterisable messages or collective reports per IEC /-104 Plain text message buffer for 1000 messages ( ring buffer ) Centralised parameterisation over Web-Browser per network or DSL Service access over gateway per network or DSL Connection of additional indication modules per network with message input Technical data USM Supply voltage Key Rated voltage Voltage range Power consumption* USM 08 USM 16 USM 32 USM V AC/DC V DC 8 13 V AC < 4 W < 4,5 W < 6 W < 7 W 1 24 V AC/DC V DC V AC < 4 W < 4,5 W < 6 W < 7 W 2 48 V AC/DC 60 V DC V DC V AC < 4,5 W < 5 W < 6,5 W < 8 W V AC/DC 220 V AC/DC V DC V AC < 5 W < 5,5 W < 7 W < 8 W Page 6 of 12

7 universal fault annunciator for panel mounting Signal voltage (if inputs are present) Key Rated voltage Voltage range Input resistance 0 12 V AC/DC 7 35 V AC/DC ~ 5 kω 1 24 V AC/DC V AC/DC ~ 10 kω 3 48 V AC/DC 60 V AC/DC V AC/DC ~ 22 kω V AC/DC V AC/DC ~ 70 kω H 125 V AC/DC V AC/DC ~ 100 kω V AC/DC V AC/DC ~ 200 kω If not otherwise noted, the given information for alternating voltage are refering to a sinusoidal alternating voltage with a frequency of 50/60 Hz. General data Buffer time in the event of failure / short circuit 100 ms Response delay Standard variant pre-set in factory 5 ms s; standard 100 ms Software parameterisable variant adjustable (5 ms s) Flashing frequency Single frequency 2 Hz Slow flashing 0.5 Hz Load capacity of relay contacts V AC 2 A; 110 V DC 0.5 A; 220 V DC 0.3 A Ethernet-Connection 100 Base-T / RJ 45 Mechanical data Type Front frame H x W x D [mm] Front panel cut-out [mm] Depth with front frame and terminals [mm] Weight USM x 96 x x 91 +0,5 100 approx. 0,40 kg USM x 96 x x 91 +0,5 100 approx. 0,45 kg USM x 192 x x ,5 100 approx. 0,70 kg USM x 287 x x ,5 100 approx. 1,00 kg Mounting panel mounting Required installation depth 120 mm Minimal horizontal gap between 2 devices 15 mm Connection terminals pluggable Wire cross section rigid or flexible Without wire sleeves 0,2... 2,5 mm 2 With wire sleeves 0, ,5 mm 2 Ambient environment Operating temperature -20 C C without condensation Storage temperature -20 C C without condensation Duty cycle 100 % Protection class at the front IP 54 Protection class at the rear IP 20 Humidity 75% r.h. max. on average over the year; up to 93% r.h. during 56 days; condensation during operation not permitted [Test: 40 C, 93% r.h. >4days] Page 7 of 12

8 Msm-usm Dielectric strength Voltage dielectric strength RS232 interface against Digital inputs 4 kv AC / 50 Hz 1 min Relay outputs 4 kv AC / 50 Hz 1 min Supply ( 110 / 230 V AC/DC ) 3 kv AC / 50 Hz 1 min Supply ( 12 / 24 / 48 V AC/DC ) 1 kv AC / 50 Hz 1 min relay contacts against each other 500 V / 50 Hz 1 min Impulse withstand strength RS232 interface against Digital inputs 2.5 kv; 1.2 / 50 μs; 0.5 J; acc. to IEC :2000 Relay outputs 2.5 kv; 1.2 / 50 μs; 0.5 J; acc. to IEC :2000 Supply 2.5 kv; 1.2 / 50 μs; 0.5 J; acc. to IEC :2000 relay contacts against each other 500 V; 1.2 / 50 μs; 0.5 J; acc. to IEC :2000 Electromagnetic compatibility Noise immunity acc. to DIN EN : DIN EN : DIN EN : DIN EN : DIN EN : DIN EN : Noise irradiation acc. to DIN EN : DIN EN 55011: Technical data USS Mechanical data Assembly on C-DIN rail TS 35 acc. to EN60715: Housing / Protection class ABS / IP 40 Terminals pluggable Wire cross section rigid or flexible Without wire sleeves 0,2 2,5 mm 2 With wire sleeves 0,25 2,5 mm 2 Operating and storage temperature -20 C C without condensation Humidity max. 95% non condensing Operation voltage Nominal operation voltage UB 24 V DC Operation voltage range V DC Power consumption approx. 2,5 W Ethernet Connection 100 Base-T / RJ 45 Range with Twisted-Pair network cable 100 m Load on relays contacts V AC 2 A; 110 V DC 0,5 A; 220 V DC 0,3 A EMC compatibility acc. to Noise immunity for industry areas EN : Static discharge (ESD) EN : Class 3 Electromagnetic fields EN : Class 3 Fast transients (BURST) EN : Class 3 Surge EN : Class 3 Conducted disturbance EN : Class 3 Voltage dips EN : Noise emmission for industry areas EN : Radio disturbances EN 55011: Class A Page 8 of 12

9 universal fault annunciator for panel mounting Terminal assignment Message inputs Acqusition device 8 channels Functional inputs 1 and 2 Message inputs Relays: Live Acqusition device 16 channels Functional inputs 1 and 2 Relays: Live Message inputs Message inputs Message inputs Message inputs Relays: Live Message inputs Functional inputs 1 and 2 Acqusition device 32 channels Page 9 of 12

10 Msm-usm Terminal assignment Message inputs Relays: Live Message inputs Message inputs Message inputs Message inputs Message inputs Functional inputs 1 and 2 Acqusition device 48 channels Terminal assignment operation indicator Relays: Live Functional inputs 1 and 2 Example: Operation indicator 48 channels Page 10 of 12

11 universal fault annunciator for panel mounting Terminal assignment USS2010 Protocol-interface RS-232 Fault alarming relay SDP-interface Ethernet jack Dimensional drawing USS2010 approx. 70 Protocol interface IEC Ethernet - interface for IEC Communication to USM and parameterisation Dimensions in mm. Subject to changes without prior notice. Page 11 of 12

12 Msm-usm Order identification System integrated devices Article-No. Designation Detail 58U08E0AS0.. USM08E-00ECP-S0-.. Acquisition device 8 inputs 58U16E0AS0.. USM16E-00ECP-S0-.. Acquisition device 16 inputs 58U32E0AS0.. USM32E-00ECP-S0-.. Acquisition device 32 inputs 58U48E0AS0.. USM48E-00ECP-S0-.. Acquisition device 48 inputs 58U08A0AS0.X USM08A-00ECP-S0-.X Indication device 8 messages 58U16A0AS0.X USM16A-00ECP-S0-.X Indication device 16 messages 58U32A0AS0.X USM32A-00ECP-S0-.X Indication device 32 messages 58U48A0AS0.X USM48A-00ECP-S0-.X Indication device 48 messages 58USS2010 USS2010 Fault annunciating server with IEC /104 Stand-alone devices with standard interface (IEC substation) Article-No. Designation Detail 58U16E0HS0.. USM16E S0-.. Acquisition device 16 inputs 58U32E0HS0.. USM32E S0.. Acquisition device 32 inputs 58U48E0HS0.. USM48E S0.. Acquisition device 48 inputs 58U48A0HM0.X USM48A M0-.X Indication device 48 messages The. are wildcards for the supply- and respective signalvoltage according to the voltage keys in the technical data section. Please specify them when placing your order. Kontakt Contact Elektra Elektronik GmbH & Co Störcontroller KG Hummelbühl Backnang Germany Tel.: +49 (0) 7191/182-0 Fax: +49 (0) 7191/ info@ees-online.de Internet:

Panel Mounted Fault Annunciator Series

Panel Mounted Fault Annunciator Series Panel Mounted Fault Annunciator Series BSM / USM Panel-mounted fault annunciator Annunciators for panel mounting with 8, 16, 24, 32, 40 and 48 signal inputs Status retention of inputs and sequence in case

More information

Panel Mounted Fault Annunciator Series

Panel Mounted Fault Annunciator Series Panel Mounted Fault Annunciator Series BSM / USM Panel-mounted fault annunciator Annunciators for panel mounting with,,,, 0 and signal inputs Storage of the last state of inputs and sequence in the case

More information

Window facia fault annunciators

Window facia fault annunciators Window facia fault annunciators WAP Window Annunciator Panel 15.08.2017 Annunciators for panel mounting with 24 signal inputs Storage of the last state of inputs and sequence in the case of power failure

More information

Parameterisable compact fault annunciator with permanent display

Parameterisable compact fault annunciator with permanent display Parameterisable compact fault annunciator with permanent display FSM 10 Drop-flap fault annunciator 31.08.2010 Permanent display even on power failure Compact module for 10 alarms Supply and alarm signal

More information

THE SOLUTION. MSM-Product family OPERATING MANUAL. A fault annunciator of the. BSM Basic fault annunciator for panel mounting. INFOwww.ees-online.

THE SOLUTION. MSM-Product family OPERATING MANUAL. A fault annunciator of the. BSM Basic fault annunciator for panel mounting. INFOwww.ees-online. A fault annunciator of the MSM-Product family 17.07.2006 BSM Basic fault annunciator for panel mounting INFOwww.ees-online.de Contents overview 1 Validity 3 2 General notes 3 2.1 Used symbols 4 2.2 Used

More information

Panel Mounted Fault Annunciator Series

Panel Mounted Fault Annunciator Series Panel Mounted Fault Annunciator Series BSM / USM Panel-mounted fault annunciator 3.8.27 Annunciators for panel mounting with 8, 6, 24, 32, 4 and 48 signal inputs Status retention of inputs and sequence

More information

MSM - Expansion modules

MSM - Expansion modules MSM - Expansion modules Transistor- and relay modules for devices of the MSM-product family Free assignment of the output arrays to the input arrays of the annunciator Triggering of relays or transistor

More information

Panel Mounted Fault Annunciator Series

Panel Mounted Fault Annunciator Series Panel Mounted Fault Annunciator Series BSM Panel-mounted fault annunciator (2nd Generation) Operating manual Table of Content Table of content 1 Validity... 3 2 General notes... 5 2.1 Additional instructions...

More information

Panel Mounted Fault Annunciator Series

Panel Mounted Fault Annunciator Series Panel Mounted Fault Annunciator Series BSM Panel-mounted fault annunciator (2nd Generation) Operating manual Table of Content Table of content 1 Validity... 4 2 General notes... 6 2.1 Additional instructions...

More information

Universal fault annunciator for panel mounting

Universal fault annunciator for panel mounting Universal fault annunciator for panel mounting USM Universal fault annunciator for panel mounting (2nd Generation) Operating manual MSM-USM2G-BA-UK-001 Table of content Table of content 1 Validity... 4

More information

Annunciator Unit SACO 16 D1. Product Guide

Annunciator Unit SACO 16 D1. Product Guide Issued: Aprill 1999 Status: Updated Version: C/20.03.2006 Data subject to change without notice Features Flexible, field-customizable 16-channel annunciator unit Alarm channels activated by normally open

More information

Annunciator unit. Application

Annunciator unit. Application Issued: April 1999 Status: April 1999 Version: B/09.11.2001 Data subject to change without notice Features Flexible, field-customizable 16-channel annunciator unit Alarm channels activated by normally

More information

ME 3011C / Alarm Indication / Quick Reference Guide

ME 3011C / Alarm Indication / Quick Reference Guide Tables of Contents Page Application 1 Features 1 Important Safety Information! 2 Note to this Guide 2 Further Information 2 Device Variants 2 General Functions 3 Annunciator Sequences - ISA 18.1 3 Plan

More information

1.7. Insulation fault evaluators EDS460/490 EDS461/491

1.7. Insulation fault evaluators EDS460/490 EDS461/491 Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 65 35305 Grünberg Tel.: 06401 807-0 Fax: 06401 807-59 Insulation fault evaluators EDS460/490 EDS461/491 Insulation fault evaluators with display and control

More information

ISOMETER IRDH275BM-7 with coupling device AGH675-7 and AGH675-7MV15

ISOMETER IRDH275BM-7 with coupling device AGH675-7 and AGH675-7MV15 with coupling device AGH675-7 and AGH675-7MV15 Device combination for insulation monitoring in unearthed AC, AC/DC and DC power systems (IT systems) IRDH275BM-7_D00123_03_D_XXEN/01.2017 with coupling device

More information

Remote alarm indicator and test combination MK2430

Remote alarm indicator and test combination MK2430 Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 5 35305 Grünberg Tel.: 040 807-0 Fax: 040 807-259 Remote alarm indicator and test combination MK2430 Remote alarm indicator and test combination with LC

More information

Analog Annunciator Unit SACO 16 A3. Product Guide

Analog Annunciator Unit SACO 16 A3. Product Guide Issued: Aprill 1999 Status: Updated Version: C/20.03.2006 Data subject to change without notice Features Powerful, flexible and field-customizable 16-channel analog input signal annunciator unit A full

More information

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Phone: Fax:

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Phone: Fax: Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 5 35305 Grünberg Phone: 040 807-0 Fax: 040 807-259 Alarm indicator and test combination MK2430 Remote alarm indicator and test combination with LC display

More information

ISOSCAN EDS460/490 EDS461/491. Insulation fault locators with control and display function for EDS systems (insulation fault location systems)

ISOSCAN EDS460/490 EDS461/491. Insulation fault locators with control and display function for EDS systems (insulation fault location systems) ISOSCAN EDS460/490 EDS461/491 Insulation fault locators with control and display function for EDS systems (insulation fault location systems) EDS460-490_D00085_01_D_XXEN/01.2017 ISOSCAN EDS460/490 EDS461/491

More information

1.7. Insulation fault evaluators EDS460/490 EDS461/491

1.7. Insulation fault evaluators EDS460/490 EDS461/491 Bender Incorporated 700 Fox Chase, Coatesville PA 1930 Tel.: (800) 356-466 Fax: (610) 383-7100 Insulation fault evaluators EDS460/490 EDS461/491 Insulation fault evaluators with display and control function

More information

www. ElectricalPartManuals. com Annunciator unit Features Self-contained microprocessor-based annunciator unit with 64 alarm channels Application

www. ElectricalPartManuals. com Annunciator unit Features Self-contained microprocessor-based annunciator unit with 64 alarm channels Application Features Self-contained microprocessor-based annunciator unit with 64 alarm channels pplication larm channels activated by normally open or normally closed contact Small and large stand-alone annunciator

More information

ISOSCAN EDS460-DG. Insulation fault locator for DC IT systems with high system leakage capacitances

ISOSCAN EDS460-DG. Insulation fault locator for DC IT systems with high system leakage capacitances ISOSCAN Insulation fault locator for DC IT systems with high system leakage capacitances _D00108_00_D_XXEN/05.2015 ISOSCAN Insulation fault locator for DC IT systems with high system leakage capacitances

More information

Insulation fault evaluator EDS460-DG

Insulation fault evaluator EDS460-DG Insulation fault evaluator for localising insulation faults in DC IT systems with a number of branch circuits where high system leakage capacitances are involved Preliminary data sheet TDB108021en/09.2008

More information

AO Annunciator Module

AO Annunciator Module General Specifications GS48C43Z01-00E-N AO-543-01 Annunciator Module GENERAL Figure 1 This module has two independent annunciator circuits. The circuits handle fault signals and operator actions (acknowledge,

More information

REA 105 Arc Protection Module. Operator s Manual

REA 105 Arc Protection Module. Operator s Manual REA 105 1MRS 751005-MUM Issued: 20.04.1998 Version: B2/26.5.2000 Checked: Approved: REA 105 We reserve the right to change data without prior notice. Contents: 1. General...4 1.1. Features...4 2. Safety...5

More information

Installation / Monitoring Technique

Installation / Monitoring Technique Installation / Monitoring Technique INFOMSTER Common larm System, us Connection New- / First- /Common Signal nnunciator RP 5994, RP 5995 Replacements for: N 5969, N 5970, N 597 055005 Circuit Diagrams

More information

ISOMETER IRDH375. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems)

ISOMETER IRDH375. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) IRDH375_D00124_01_D_XXEN/07.2018 Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) Product

More information

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems)

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems) ISOMETER IR425 Insulation monitoring device for unearthed AC/DC control circuits (IT systems) IR425-D4_D00039_04_D_XXEN/05.2017 ISOMETER IR425 Insulation monitoring device for unearthed AC/DC control circuits

More information

M1000 Alarm Annunciator

M1000 Alarm Annunciator Data Sheet Alarm Annunciator Reliable Supervision and Control 10 inputs with LED indications Supports both NO/NC input contacts 10 open collector outputs Built-in siren relay Text label for alarm descriptions

More information

LINETRAXX VME420. Multi-functional relay for overvoltage, undervoltage and frequency monitoring in AC/DC systems with external supply voltage

LINETRAXX VME420. Multi-functional relay for overvoltage, undervoltage and frequency monitoring in AC/DC systems with external supply voltage LINETRAXX VME420 Multi-functional monitoring relay for undervoltage, overvoltage and frequency monitoring in AC/DC systems with separate supply voltage VME420_D00026_01_D_XXEN/06.2016 LINETRAXX VME420

More information

Residual current monitor RCM470LY/RCM475LY. for TN and TT systems (AC and pulsating DC currents)

Residual current monitor RCM470LY/RCM475LY. for TN and TT systems (AC and pulsating DC currents) Residual current monitor RCM470LY/RCM475LY for TN and TT systems (AC and pulsating DC currents) TDB401003en/03.2010 Residual current monitor RCM470LY Residual current monitor for TN and TT systems (AC

More information

TCM-2 Thyristor Control Module DATA SHEET

TCM-2 Thyristor Control Module DATA SHEET TCM-2 Thyristor Control Module TCM-2 Thyristor DATA DATA SHEET Control Module DATA SHEET Alarm panels Type Compact Q96 design Extremely easy push-button programming (no jumpers or the like) Individual

More information

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge Replaceable LED modules 11 Alarm Sequences as per ISA-18.1 standard Each channel/window fully field programmable RS232 or RS485 MODBUS-RTU communication Repeat relay for each window and multifunction relays

More information

LINETRAXX VMD420. Multi-functional voltage relay for 3(N)AC systems, frequency/overvoltage/undervoltage, phase, phase failure, asymmetry

LINETRAXX VMD420. Multi-functional voltage relay for 3(N)AC systems, frequency/overvoltage/undervoltage, phase, phase failure, asymmetry LINETRAXX VMD420 Multi-functional voltage relay for 3(N)AC systems, frequency/overvoltage/undervoltage, phase, phase failure, asymmetry VMD420_D00137_02_D_XXEN/06.2016 LINETRAXX VMD420 Multi-functional

More information

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems)

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems) Insulation monitoring device for unearthed AC/DC control circuits (IT systems) TDB103005en/05.2013 Insulation monitoring device for unearthed AC/DC control circuits (IT systems) Product description The

More information

Operating Manual VMD420

Operating Manual VMD420 Operating Manual VMD420 Voltage and frequency monitor for monitoring of 3(N)AC systems up to 0...500 V for undervoltage and overvoltage and under and overfrequency Software version: D238 V2.2x Power in

More information

1.7 A-ISOMETER IRDH575. RoHS. Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax:

1.7 A-ISOMETER IRDH575. RoHS. Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax: Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 65 505 Grünberg Tel.: 060 807-0 Fax: 060 807-59 A-ISOMETER IRDH575 Insulation monitoring device for unearthed AC, DC and AC/DC systems (IT systems) with

More information

RCMA423-DM RCMA423-DM1C RCMA423-DM2C RCMA423-DM3C. Operating Manual

RCMA423-DM RCMA423-DM1C RCMA423-DM2C RCMA423-DM3C. Operating Manual Operating Manual RCMA423-DM RCMA423-DM1C RCMA423-DM2C RCMA423-DM3C Residual current monitor with one analogue output signal for monitoring AC-, DC- and pulsed DC currents in TN- and TT systems Software

More information

System 9000TS Sequence of Events Recorder

System 9000TS Sequence of Events Recorder System 000TS Sequence of Events Recorder ms Event Recorder and combined Annunciator Modular, rack mounting design expandable to over 000 inputs ms time stamping of events across the whole system Up to,000

More information

GM420. Digital Ground Continuity Relay For AC Systems. Technical Bulletin NAE /

GM420. Digital Ground Continuity Relay For AC Systems. Technical Bulletin NAE / 3 GM20 Digital Ground Continuity Relay For AC Systems Technical Bulletin NAE03230 / 0.20 GM20 Ground continuity monitor For AC systems Description The GM20 monitors the loop resistance of ground conductors

More information

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3 PRODUCT OVERVIEW

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3 PRODUCT OVERVIEW NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM Local configuration and monitoring with Raychem Touch 1500 touch screen display PRODUCT OVERVIEW The nvent RAYCHEM NGC-40 is a multipoint

More information

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax:

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax: Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 5 505 Grünberg Tel.: 00 807-0 Fax: 00 807-259 Insulation monitoring device for unearthed AC/DC systems (IT systems for the supply of operating theatre

More information

LINETRAXX RCMA420. Residual current monitor for monitoring AC, DC and pulsed DC currents in TN and TT systems

LINETRAXX RCMA420. Residual current monitor for monitoring AC, DC and pulsed DC currents in TN and TT systems LINETRAXX RCMA420 Residual current monitor for monitoring AC, DC and pulsed DC currents in TN and TT systems RCMA420_D00059_01_D_XXEN/06.2016 LINETRAXX RCMA420 Residual current monitor for monitoring AC,

More information

ME 3011 compact. Electronic Alarm Indication Systems. Power Station Control Systems. Automation Equipment. Power Distribution Control Systems

ME 3011 compact. Electronic Alarm Indication Systems. Power Station Control Systems. Automation Equipment. Power Distribution Control Systems Electronic Alarm Indication Systems ME 3011 compact Power Station Control Systems Power Distribution Control Systems Control Room Technology Automation Equipment 2 Table of Contents Contents Page System

More information

VAMP 120 & 121. Arc flash detection units. Product picture

VAMP 120 & 121. Arc flash detection units. Product picture Arc flash detection units VAMP 120 and 121(D) are extremely fast arc flash detection units for LV and MV switchgear and controlgear. The units are especially designed to increase the safety and to minimize

More information

ISOMETER IR1575. Insulation monitoring device for unearthed AC/3(N)AC systems up to 480 V and DC systems up to 480 V

ISOMETER IR1575. Insulation monitoring device for unearthed AC/3(N)AC systems up to 480 V and DC systems up to 480 V Insulation monitoring device for unearthed AC/3(N)AC systems up to 480 V and DC systems up to 480 V IR1575_D00116_00_D_XXEN/05.2015 Insulation monitoring device for unearthed AC/3(N)AC systems up to 480

More information

Connections, displays and operating elements C D E G H. Installing the control unit

Connections, displays and operating elements C D E G H. Installing the control unit 1 2 3 GB Control unit 0-10 V REG-K/3-gang with manual mode Operating instructions Art. no. MTN646991 ¼ DANGER Risk of fatal injury from electrical current. All work on the device should only be carried

More information

AIS750 Series Alarm Annunciator

AIS750 Series Alarm Annunciator Unparallel, modular, multipoint design with Integrated controllers Two Operation Modes (Stand-alone & Serial) All sizes confi gurable up to 440 Alarm Points RS485 / RS232 Serial Communication Manual &

More information

DRAFT 20 October 2014

DRAFT 20 October 2014 Technical data MTL process alarm equipment EPS rev 8 Programmable alarm annunciator Modular construction from 1 to 256 alarm channels Multi-redundant design so there is no single point of failure Choice

More information

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3 NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM Local configuration and monitoring with Raychem Touch 1500 touch screen display PRODUCT OVERVIEW The Raychem NGC-40 is a multipoint electronic

More information

Master devices. Type X-AIR-ZMAS. Zone master module for up to 25 zone modules, with integral webserver and interfaces to higher-level systems

Master devices. Type X-AIR-ZMAS. Zone master module for up to 25 zone modules, with integral webserver and interfaces to higher-level systems X X testregistrierung Type Web server, also for mobile devices Zone modules Zone master module for up to 25 zone modules, with integral webserver and interfaces to higher-level systems X-AIRCONTROL zone

More information

ISOMETER isomed427p. Application Medical IT system in accordance with IEC , IEC , IEC and DIN VDE

ISOMETER isomed427p. Application Medical IT system in accordance with IEC , IEC , IEC and DIN VDE Insulation monitoring device with integrated load and temperature monitoring and locating current injector for insulation fault location systems for medical IT systems _D00043_02_D_XXEN/09.2016 Insulation

More information

M2000 Engine Controller

M2000 Engine Controller M2000 Engine Controller Integrated control and protection of diesel and gas engines for all purposes Especially suited for auxiliary generator sets 1 IN OPERATION 1 2 STARTFAIL 2 3 OVERSPEED RPM FAIL 3

More information

VAMP 121. Arc protection unit. User manual

VAMP 121. Arc protection unit. User manual VAMP 121 Arc protection unit User manual VM121.EN014_B Table of contents VAMP 121 Table of contents 1. General... 4 1.1. Arc protection unit VAMP 121... 4 2. Unit configuration... 6 3. Sensors... 8 3.1.

More information

Interface and EOL Modules 8

Interface and EOL Modules 8 Interface and EOL Modules Interface Modules Series 420 25 Interface Modules Series 100 291 EOL Modules 293 254 Interface and EOL Modules Interface Modules Series 420 Interface Modules Serie 420 Interface

More information

ACTIVE INFRARED BARRIER

ACTIVE INFRARED BARRIER Although PROTECH provides high security indoor intrusion sensors for the military and government markets, our specialty is outdoor protection. Since we first introduced our PIRAMID outdoor dual technology

More information

C-Bus Four Channel Analogue Output Unit Installation Instructions

C-Bus Four Channel Analogue Output Unit Installation Instructions C-Bus Four Channel Analogue Output Unit Installation Instructions 5504AMP Series REGISTERED PATENT Table of Contents Section... Page 1.0 Product Range...3 2.0 Description...3 3.0 Capabilities...3 4.0 Wiring

More information

Product Information. PipeMonitor District Heating Monitoring with Leak Localisation

Product Information. PipeMonitor District Heating Monitoring with Leak Localisation The thresholds for insulation and loop resistance are programmable via built-in buttons which are shown in the display of the main module. In addition to the settings the display can also indicate the

More information

Multi-Gas-Controller MGC2

Multi-Gas-Controller MGC2 Page 1 Aug. 2018 Gas measuring, monitoring and warning controller based on state-of-the-art micro-technology for continuous monitoring of the ambient air to detect toxic and combustible gases, refrigerants

More information

C-Bus Four Channel General Input Unit Installation Instructions

C-Bus Four Channel General Input Unit Installation Instructions C-Bus Four Channel General Input Unit Installation Instructions 5504GI Series REGISTERED DESIGN REGISTERED PATENT Table of Contents Section...Page 1.0 Product Range... 3 2.0 Description... 3 3.0 Capabilities...

More information

Soft Starter Centrifugal Pump Soft Starter Series

Soft Starter Centrifugal Pump Soft Starter Series Soft Starter Centrifugal Pump Soft Starter Series Type RSWT Optimised algorithm for centrifugal pumps Simple User Interface 3-phase controlled Internally bypassed Multi voltage operation Integrated overload

More information

PolyGard 2-channel Gas Controller MGC-03

PolyGard 2-channel Gas Controller MGC-03 PolyGard 2-channel Gas Controller MGC-03 DESCRIPTION Gas measuring and monitoring controller based on state-ofthe-art micro-technology with integrated buzzer for continuous monitoring of the ambient air

More information

FT702LT Turbine control wind sensor gives durability a new meaning FT702LT. series

FT702LT Turbine control wind sensor gives durability a new meaning FT702LT. series FT702LT Turbine control wind sensor......gives durability a new meaning FT702LT series Proven High Availability The FT702LT ultrasonic anemometer is the result of FT Technologies 10 years of experience

More information

Process Alarm Solutions

Process Alarm Solutions Process Alarm Solutions Reliable Supervision and Control» Control. Monitor. Protect. SELCO Flexible alarm panels for supervision and control SELCO provides efficient and reliable solutions for alarm monitoring

More information

Operating Manual RCM420

Operating Manual RCM420 Operating Manual RCM420 Residual current monitor for AC current monitoring in TN and TT systems Software version: D240 V1.2x TGH1410en/03.2012 Bender GmbH & Co. KG Londorfer Str. 65 35305 Grünberg Germany

More information

Automation System TROVIS 5400 Boiler Controller TROVIS 5474

Automation System TROVIS 5400 Boiler Controller TROVIS 5474 Automation System TROVIS 5400 Boiler Controller TROVIS 5474 Application Weather-sensitive control of up to two boilers, designed for single-stage, two-stage or also modulating operating mode. Communication

More information

On the job around the clock 24/7: Fire detection systems

On the job around the clock 24/7: Fire detection systems On the job around the clock 24/7: Fire detection systems Version 02.2010 Version: 02.2010 Product catalogue Fire detection systems This product catalogue is intended for sales purposes only. For planning,

More information

Features. Omni2 Door Warning Sign Alarm Annunciator DATASHEET. Model C1190B Door Warning Sign

Features. Omni2 Door Warning Sign Alarm Annunciator DATASHEET. Model C1190B Door Warning Sign Features DATASHEET Connects to multiple sensing instruments One/Two Channel Device Bright solid state LED Alarm Display Audible Alert (internal and external) High reliability, fully dual redundant alarm

More information

RSWT. Three phase AC pumps and ventilators soft starter. Benefits. Description

RSWT. Three phase AC pumps and ventilators soft starter. Benefits. Description Three phase AC pumps and ventilators soft starter Description Benefits Easy to use. The is equipped with a self-learning algorithm that automatically adjusts the start parameters to optimise the motor

More information

SCR100 User Manual. Version:1.1 Date:Dec 2009

SCR100 User Manual. Version:1.1 Date:Dec 2009 SCR100 User Manual Version:1.1 Date:Dec 2009 Introduction: This document mainly introduces the installations and connections of SCR100 products, and the brief operations about attendance software. Important

More information

Laboratory Honeywell Technology Solutions, Bangalore-EMC Lab, 19/2, Devarabisanahalli Village, K.R. Puram, Varthur Hobli, Bangalore, Karnataka

Laboratory Honeywell Technology Solutions, Bangalore-EMC Lab, 19/2, Devarabisanahalli Village, K.R. Puram, Varthur Hobli, Bangalore, Karnataka Last Amended on 07.10.2015 Page 1 of 18 I. EMC Test Facility 1. Electrical and Electronic Products, Process Control Devices, Lighting Control Products, Sensing and Control Devices, Electromechanical Products,

More information

RTK 9000TS system. MTL sequence of events recorder. Technical data MTL process alarm equipment

RTK 9000TS system. MTL sequence of events recorder. Technical data MTL process alarm equipment Technical data MTL process alarm equipment EPS RTK 9000TS Rev RTK 9000TS system MTL sequence of events recorder Modular, rack mounting design expandable to over 900 inputs ms time stamping of events irrespective

More information

Advanced Diagnostic Gateway with Ethernet and FF-H1 Interface and I/O. Assembly

Advanced Diagnostic Gateway with Ethernet and FF-H1 Interface and I/O. Assembly Advanced Diagnostic Gateway with Ethernet and FF-H1 Interface and I/O Features Assembly System integration kit for Advanced Diagnostics PCS integration via Diagnostic Manager or device DTM Simple automatic

More information

M2500 Engine Controller Installation Manual

M2500 Engine Controller Installation Manual M2500 Engine Controller Installation Manual Revision: 23-04-2012 Page 1 Contents 1 Preface... 4 2 Installation... 5 3 Terminal Connections... 6 4 Inputs... 7 4.1 Power Supply... 7 4.2 Mode/ Control Inputs...

More information

SIL725 Safety Annunciator

SIL725 Safety Annunciator SIL725 Safety Annunciar Configurable SIL2 Annunciar certified IEC61508 SIRA certified at safety integrity level SIL2 IEC61508 Modular construction from 1 128 alarm channels Multi-redundant design Choice

More information

I/A Series 716C 1/16 DIN Temperature Controller

I/A Series 716C 1/16 DIN Temperature Controller Product Specifications I/A Series 716C 1/16 DIN Temperature Controller PSS 2C-1B5 A The Foxboro 716C is a powerful compact, 1/16 DIN, microprocessor-based temperature controller that offers a variety of

More information

System 9000TS Sequence of Events Recorder

System 9000TS Sequence of Events Recorder System 9000TS Sequence of Events Recorder ms Event Recorder and combined Annunciator The RTK System 9000TS Sequence of Events Recorder leads the way in the latest technically advanced event and alarm management

More information

DPB52. True RMS 3-Phase, Multifunction monitoring relay. Benefits. Description

DPB52. True RMS 3-Phase, Multifunction monitoring relay. Benefits. Description DPB52 True RMS 3-Phase, Multifunction monitoring relay Description Benefits Measuring Voltage Range. Very wide input voltage range: from 125 to 624V ( 208V 40% to 480 + 30% ). Adjustable Voltage Ranges

More information

SENTINEL A - Fault Passage Indicator

SENTINEL A - Fault Passage Indicator SENTINEL A - Fault Passage Indicator AMPEREMETRIC FAULT PASSAGE INDICATORS FOR OVERHEAD MV NETWORKS Installed on poles of overhead lines, the Overhead-Sentinel-A range allows locating the fault arisen

More information

IT system floor-standing distribution

IT system floor-standing distribution IT system floor-standing distribution cabinet series -IPS-F/EDS for supplying power to medical locations in accordance with IEC 60364-7-710 and featuring a built-in insulation fault location system IT

More information

Index Arc Guard Systems. Arc Guard Systems. Arc Guard Systems Industrial Automation Supply - Tel:

Index Arc Guard Systems. Arc Guard Systems. Arc Guard Systems Industrial Automation Supply   - Tel: Systems Index Systems - Systems Systems...1 -.16 General information Description...1 System description...2 Overview...3 Ordering details Arc monitor with detectors...4 Current sensing unit...5 Technical

More information

DEIF A/S. Technical Manual. Type EC-2 Engine Control Unit D. Technical Manual

DEIF A/S. Technical Manual. Type EC-2 Engine Control Unit D. Technical Manual Technical Manual Type EC-2 Engine Control Unit 4189340232D DEIF A/S Technical Manual DEIF A/S Tel.: (+45) 9614 9614 Frisenborgvej 33, DK-7800 Skive Fax: (+45) 9614 9615 Denmark E-mail: deif@deif.com Contents

More information

PolyGard Single Point Controller SPC-X3-20XX for refrigerant gases and vapours

PolyGard Single Point Controller SPC-X3-20XX for refrigerant gases and vapours PolyGard Single Point Controller SPC-X3-20XX for refrigerant gases and vapours DESCRIPTION Gas measuring, monitoring and warning controller based on state-of-the-art micro-technology with integrated sensor

More information

Operating Manual TR600

Operating Manual TR600 ZIEHL industrie elektronik GmbH + Co KG Daimlerstraße 13, D 74523 Schwäbisch Hall + 49 791 504-0, info@ziehl.de, www.ziehl.de Temperature Relays and MINIKA Mains Monitoring Digital Panelmeters MINIPAN

More information

Rules for Intruder Alarm Systems

Rules for Intruder Alarm Systems Rules for Intruder Alarm Systems Opening detectors (Magnetic contacts) Part 1: Requirements VdS 2120en 03/96 (03) Subject 44 1 General; 2 Terms and definitions; 3 Classification 1 General 1.1 Scope These

More information

Solution F2. Fire Alarm Control Panels one step ahead.

Solution F2. Fire Alarm Control Panels one step ahead. Solution F2 Fire Alarm Control Panels one step ahead. Sicherheitstechnik Sicherheitstechnik GmbH GmbH The Fire Alarm Control Panel Solution F2 Solution F2 in B2 enclosure (B01090-00) The Concept The Solution

More information

VME421H Voltage and frequency monitor

VME421H Voltage and frequency monitor EN Manual VME421H Voltage and frequency monitor for monitoring AC/DC systems for undervoltage, overvoltage, underfrequency and overfrequency Software version VME421H-D-1: D236 V2.2x Software version VME421H-D-2:

More information

enproteko.com Specifications Ratings Item voltage to 24 VAC 5/6 Hz 24 VAC 5/6 Hz or 24 VDC Allowable voltage Characteristics 85% to 11% of power suppl

enproteko.com Specifications Ratings Item voltage to 24 VAC 5/6 Hz 24 VAC 5/6 Hz or 24 VDC Allowable voltage Characteristics 85% to 11% of power suppl enproteko.com Temperature Monitoring Relay K8AB-TH Compact and Slim Relay Ideal for Temperature Alarms and Monitoring Excessive increases can be prevented and abnormal s can be monitored. Temperature monitoring

More information

HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR

HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR 2 MB 103 TRANSFORMER TEMPERATURE CONTROL UNIT WITH CONTROL SIGNAL Recent approval of new

More information

Monitoring Devices 11/1

Monitoring Devices 11/1 11/4 Introduction 11/6 5TE5 8 light indicators 11/7 4AC3 0, 4AC3 1 bells, buzzers 11/7 5TT3 46 fault signaling units 11/8 7LQ2 1, 5TT3 3 dusk switches 11/9 7LQ2 0 temperature controllers 11/9 5TT3 170

More information

Technical Manual. Level Alarm Unit CARLA & WIDS

Technical Manual. Level Alarm Unit CARLA & WIDS CARLA & WIDS Technical Manual SAS au Capital de 2 158 244-444 871 933 R.C.S. Bourges - APE : 2651B Headquarter : 9, rue Isaac Newton - 18000 Bourges - France Technical Manual CARLA for Tankers Cargo Tanks

More information

Ordering Key. Dielectric strength

Ordering Key. Dielectric strength Controllers AC Semiconductor Controller Type Soft starting and stopping of 3-phase squirrel cage motors Low inrush and reduced vibration during starting Integrated bypassing of semiconductors Rated operational

More information

GMA200-MT. Operation Manual. Gas detection controller for mounting rail assembly

GMA200-MT. Operation Manual. Gas detection controller for mounting rail assembly Operation Manual GMA200-MT Gas detection controller for mounting rail assembly GfG GESELLSCHAFT FÜR GERÄTEBAU MBH KLÖNNESTRASSE 99 44143 DORTMUND, Germany TEL. +49 / (0)231 / 564 00 0 FAX +49 / (0)231

More information

Dew point set DS 400

Dew point set DS 400 set DS 400 Dew point set DS 400 for stationary dew point monitoring of refrigeration or adsorption dryers. The touch screen graphic display enables an intuitive operation and shows the progress of the

More information

DATAssure. Laboratory wireless alarm & monitoring system

DATAssure. Laboratory wireless alarm & monitoring system DATAssure Laboratory wireless alarm & monitoring system Wireless alarm & monitoring system A new monitoring generation The DATAssure wireless monitoring system is used across a broad range of market sectors

More information

for relative humidity and temperature

for relative humidity and temperature 1 861 1861P01 Duct sensor for relative humidity and temperature QFM65 Operating voltage AC 24 V Signal output DC 0...10 V for relative humidity and temperature Measurement accuracy ±3 % r. h. within the

More information

Instructions manual. By-alarm. By-alarm Manager software

Instructions manual. By-alarm. By-alarm Manager software Instructions manual By-alarm By-alarm Manager software Index 1. Procedure for the complete programming of the By-alarm system 5 Operations to be carried out prior to the programming with By-Alarm Manager

More information

VAmP 120. Arc Flash Protection Units. Arc Protection. Customer benefits

VAmP 120. Arc Flash Protection Units. Arc Protection. Customer benefits Arc Protection 01 VAmP 120 Arc Flash Protection Units Customer benefits Personnel Safety A fast and reliable arc protection unit may save human lives in case of an arc fault arising in a switchgear during

More information

Lift Station Level Controller

Lift Station Level Controller Lift Station Level Controller Installation and Operation Manual 1 California Motor Controls, Inc. Benicia, CA Table of Contents 1. Features Product Overview... 4-6 Access Security... 7 Optional Features...

More information

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option SM3000 Videographic Recorder User Guide (RTU) Communications Option ABB The Company We are an established world force in the design and manufacture of instrumentation for industrial process control, flow

More information