Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016

Size: px
Start display at page:

Download "Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016"

Transcription

1 Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting Prepared Especially for : OSFM TEC 2016 Acceptance Testing

2 Agenda Before you begin Completing the Acceptance Test Documentation Set the stage for on-going, trouble free service

3 Before you Begin Ensure that an approved/reviewed set of drawings are available Compare the approved set to the Installer s asbuilt set Contemplate any deviations Field modifications should be justified by the installer and/or designer Ask for a completed test & inspect document The AHJ should not be the first one to test the system Verify UL Central Station Services are provided

4 Pre-Test Documentation Before requesting final approval of the installation, if required by the authority having jurisdiction, the installing contractor shall furnish a written statement stating that the system has been installed in accordance with approved plans and tested in accordance with the manufacturer s published instructions and the appropriate NFPA requirements * The record of completion form, Figure , shall be permitted to be a part of the written statement required in When more than one contractor has been responsible for the installation, each contractor shall complete the portions of the form for which that contractor had responsibility.

5 Qualified Personnel Equipment Listed for the purpose System Designer Experienced in the proper design, application, installation and testing of fire alarm systems Factory Trained & Certified Certified by Nationally Recognized Organization (NICET) Registered, licensed or certified by the State or AHJ System Installer Qualified or supervised by persons who are Same as Designer

6 Qualified Personnel A Service Personnel should be able to do the following: 1. Understand the requirements contained in the National Fire Alarm Code and the fire alarm requirements contained in the National Electrical Code. 2. Understand basic job site safety laws and requirements. 3. Apply troubleshooting techniques, and determine the cause of fire alarm system trouble conditions. 4. Understand equipment specific requirements, such as programming, application, and compatibility. 5. Read and interpret fire alarm system design documentation and manufacturer s inspection, testing, and maintenance guidelines. 6. Properly use tools and test equipment required for testing and maintenance of fire alarm systems and their components. 7. Properly apply the test methods required by the National Fire Alarm Code.

7 Qualified Personnel Service personnel shall be qualified and experienced in the inspection, testing, and maintenance of the fire alarm systems. Qualified personnel shall include, but not be limited to, one or more of the following. 1. *Personnel who are factory trained and certified for fire alarm system service of the specific type and brand of system. 2. *Personnel who are certified by a nationally recognized fire alarm certification organization acceptable to the authority of having jurisdiction. 3. *Personnel who are registered, licensed, or certified by a state or local authority. 4. Personnel who are employed and qualified by an organization listed by a nationally recognized testing laboratory for the servicing of fire alarm systems.

8 Qualified Personnel

9 Qualified Monitoring Company

10 GENERAL INSTRUCTIONS The system installer and a qualified representatives of all trades involved will perform this acceptance test and log the test results on NFPA Inspection and Testing Form or other document required by the authority having jurisdiction (AHJ) The system installer is responsible for ensuring that the testing does not damage equipment In larger systems, cycling mechanical systems over-and-over may significantly reduce the lifespan of the equipment All failures or discrepancies revealed during testing, as well as any deviation from NFPA 72, must be entered as a note on NFPA Test Form Confirm that an input/output matrix for the system is available Ensure that Central Station Services and Test & Inspect Contracts are in Place

11 A As an example, testing of the elevator fire service and shutdown functions will usually require a coordinated multi-discipline effort with presence of qualified service personnel for the fire alarm system, the elevator system, and other building systems. The presence of inspection authorities might also be needed in some jurisdictions. The development of a test plan should be considered to ensure that the testing of these features is accomplished in a coordinated and timely manner. This plan should also ensure that all appropriate parties alarm system and the elevator system are fulfilled. See and for specific elevator fire safety functions.

12 OFF-SITE MONITORING If the system is connected to an off-site monitoring service (Central Station, remote supervising station or municipal alarm system) the monitoring service must be alerted and then disabled prior to testing Disabling the off-site monitoring will create a trouble condition in the system The off-site monitoring service needs to be made aware of who is testing the system, approximately how long the test will take and the names of people authorized to report a real fire during the test (this should be a customer representative)

13 OCCUPANT NOTIFICATION Verify that all personnel in the building have been notified that the fire alarm system is going to be tested

14 Before proceeding with any testing, all persons and facilities receiving alarm, supervisory, or trouble signals and all building occupants shall be notified of the testing to prevent unnecessary response.

15 INSTALLATION CHECKS Complete the following, and record the results on the testing documentation form. Confirm that the main system power supply (i.e. electricaldistribution panel breaker) is clearly marked FIRE ALARM CIRCUIT Confirm that the power supply is locked on or accessible only to authorized personnel. Confirm that the location of the circuit disconnecting means is permanently identified at the fire alarm control panel (FACP)

16 INSTALLATION CHECKS Dedicated Branch Circuit. A dedicated branch circuit of one of the following shall supply primary power (usually commercial light and power) Mechanical Protection The dedicated branch circuit(s) and connections shall be mechanically protected Circuit disconnecting means shall have a red marking, shall be accessible only to authorized personnel, and shall be identified as FIRE ALARM CIRCUIT The location of the circuit disconnecting means shall be permanently identified at the fire alarm control unit The location of any remotely located power supply shall be identified at the master control unit as well as on the record drawings. Identification on the control unit display shall be acceptable

17 INSTALLATION CHECKS Complete the following, and record the results on the testing documentation form (continued) Confirm that the system control panel is properly grounded with a minimum 12 AWG conductor Verify that all fuses are installed in all fire alarm modules and are proper rating Confirm that conduit entry and wiring, including non-power limited, conforms with panel requirements and also that wiring is properly spaced

18 SYSTEM POWER SUPPLY TESTING GENERAL REQUIREMENTS If there is no battery standby confirm that the main power supply is provided by a dedicated branch of an emergency system in accordance with the National Electric Code, Articles 700, 701, or 702 Confirm with the electrical contractor that the jurisdiction s electrical inspector has approved the emergency system installation With the AC power applied confirm that the power-on indicator is illuminated

19 AC POWER FAIL VERIFICATION With batteries connected, disconnect the main power supply to the FACP and verify FACP trouble tone sounds FACP system trouble indicator illuminates If available, the FACP alphanumeric display indicates the type of trouble FACP power-on indicator is off Acknowledge the system trouble to silence the audible trouble signal Verify the visible system trouble indicator is illuminated Restore the main power supply to the FACP and verify System trouble indicator is off Power-on indicator illuminates

20 VERIFICATION OF RE-SOUND AND SIGNAL SILENCE This test should be performed once at the control panel or each area on selective signaling systems. Consult the input/output matrix to determine specific notification appliance circuit operation Initiate an alarm and verify FACP tone device sounds Notification appliance operate in designated areas Associated alarm indicator flashes on Operate the alarm silence switch and, if applicable, acknowledge switch and verify FACP tone device silences Notification appliances cease operation Associated alarm indicator illuminates steadily

21 VERIFICATION OF RE-SOUND AND SIGNAL SILENCE (Continued) Activate a second initiating device and verify FACP tone device sounds Audible notification appliances re-sound is designated areas. Associated alarm indicator flashes on Operate the alarm silence switch and, if applicable, acknowledge switch and verify FACP: tone device silences Notification appliances cease operation Associated alarm indicator illuminates steadily Restore the initiating devices to normal, reset the FACP and verify that the system has returned to normal

22 BATTERY FAIL VERIFICATION Remove harness from all system battery terminals and verify FACP tone sounds within 200 seconds FACP system trouble indicator illuminates If applicable, FACP alphanumeric display indicates a battery failure Acknowledge the system trouble indicator to silence audible trouble signal, and verify that the system trouble indicator is illuminated Reconnect the battery harness and verify FACP system trouble indicator if off. FACP power trouble indicator is off. If applicable, FACP alphanumeric display reads System Normal

23 TESTING THAT CIRCUITS ARE PROPERLY MONITORED FOR INTEGRITY (ELECTRICALLY SUPERVISED) Jumper each side of every initiation-device circuit, signaling line circuit and initiating-device circuit to ground individually Confirm that a trouble condition is reported to the FACP each time a circuit is connected to ground Ten percent of the smoke detectors on every initiatingdevice circuit and signaling line circuit should be removed from their bases, one at a time Confirm that a trouble condition is reported to the FACP with each devise removed Reinstall a device before removing the next one Document which detectors have been removed from their base.

24 TESTING THAT CIRCUITS ARE PROPERLY MONITORED FOR INTEGRITY (ELECTRICALLY SUPERVISED) Break one connection on 10% of the initiating devices (manual pull boxes, heat detectors, sprinklers flow switches, valve supervisory switches, spot smoke detectors, duct smoke detectors) and one connection on 10% of the devices on signaling line circuits (It should be noted that spot smoke detectors, in most cases, can be removed from their base for trouble testing) Confirm that a trouble condition is reported to the FACP Remake each connection before opening the next connection Remove one connection on 10% of the appliances on each notification-appliance circuit Confirm that a trouble condition is reported to the FACP Remake each connection before opening the next connection. Document which appliance have had their circuit opened

25 FUNCTIONAL TESTING OF INITIATING DEVICES GENERAL INSTRUCTIONS The following tests require the use of building floor plans showing all initiating devices, notification appliances, fire zones and control relays Proper annunciation (labeling) must be verified for every initiating device Using the input/output matrix, confirm that each activated initiating devise operates the correct notification appliances and any other controlled equipment Record the results of the following tests on acceptable device documentation Every initiating device on the system must be actuated

26 FUNCTIONAL TESTING OF INITIATING DEVICES MANUAL FIRE ALARM BOXES (PULL STATIONS) Confirm that each fire alarm box is unobstructed, readily accessible, located in the normal path of egress and that the installed height of each fire alarm box meets applicable requirement (NFPA or ADA) Activate each manual box by physically operating the device. Opening the fire alarm box with a key is not an acceptable test method

27 FUNCTIONAL TESTING OF INITIATING DEVICES SPOT SMOKE DETECTORS Visually confirm proper application and location of every detector Document any misapplication Should not be installed in dead air spaces, or in close proximity to air diffusers Should not be installed on ceilings closer than 4 inches to a wall Sidewall-mounted detectors should be installed between 4 inches and 12 inches from the ceiling Should not be installed closer than 3 feet to an air diffuser or returnair opening Should not be installed near ceiling fans Should not be installed in kitchens, furnace rooms, incinerator rooms, above ashtrays in elevator lobbies or in location where nonhostile: smoke can normally be expected

28 FUNCTIONAL TESTING OF INITIATING DEVICES (Spot smoke detectors - Continued) Confirm that there is a smoke detector installed within 21 feet of the FACP, if the FACP area is not continuously occupied Not required if fully sprinkled under 2007 NFPA Activate every spot-type smoke detector with the SOLO test tool or other approved test device Using the magnetic switch on a detector is not an acceptable test method If detector sensitivity testing is a project requirement, use the smoke detector sensitivity test tool See NFPA 72 and/or detector white papers for other detector application guidelines

29 Table (J) Multi sensor detectors 1. Each of the detection principles present within the detector shall be tested independently for specific detection principle regardless of the configuration status at the time of testing. Each detector shall also be tested to manufacturer s instructions. 2. Detectors shall be tested together if technology allows individual detector responses to be verified.

30 FUNCTIONAL TESTING OF INITIATING DEVICES DUCT SMOKE DETECTORS Confirm proper application and location of every duct detector. (For additional information concerning detector placement, refer to NFPA 72) Initiate an alarm condition at each duct detector by introducing smoke into the detector (The use of the remote-test switch for an acceptance test is not acceptable. See installation instruction that come with the device for further details on methods for testing duct detectors) Documentation from the Mechanical Contractor that proves differential pressure between the exhaust and sampling tubes should be provided Note: Duct detectors supplied by others, such as the mechanical contractor, are to be tested by the supplier

31 FUNCTIONAL TESTING OF INITIATING DEVICES RATE-OF-RISE HEAT DETECTORS Activate every rate-of-rise heat detector using the SOLO rate-of-rise test tool or other approved method (Care should be taken to avoid damaging or destroying detectors during testing)

32 FUNCTIONAL TESTING OF INITIATING DEVICES MECHANICAL FIXED-TEMPERATURE HEAT DETECTORS Remove the keyed restorable heat element to initiate an alarm from each detector For non-keyed detectors, initiate an alarm by shorting across the terminals of each detector After each alarm is confirmed, reinstall the heat element where applicable, and reset the system

33 FUNCTIONAL TESTING OF INITIATING DEVICES ELECTRONIC HEAT DETECTORS Activate every electronic heat detector using the SOLO test tool or other approved method. Caution must be used in choosing the heat source so as not to damage the unit LINEAR HEAT DETECTION Verify that linear heat detection is tested according to the manufacturer s instructions

34 FUNCTIONAL TESTING OF INITIATING DEVICES RADIANT-ENERGY (FLAME) DETECTORS Verify that each radiant detector is tested according to the manufacturer s instructions Air Sampling Detection Air flow through all ports shall be verified for operation Alarm response (120 seconds max) shall be verified through the last port on each pipe run

35 FUNCTIONAL TESTING OF INITIATING DEVICES PROJECTED-BEAM SMOKE DETECTORS Confirm that the line of sight between the transmitter and receiver of each beam detector is not above any ceiling fans and is clear of any obstructions Verify that all detectors are placed in accordance with building plans Activate every projected-beam detector by obscuring the beam using the filter kit

36 FUNCTIONAL TESTING OF INITIATING DEVICES This testing must be conducted in cooperation with the sprinkler contractor. SPRINKLER SYSTEM SWITCHES The Sprinkler contractor shall initiate an alarm from every flow switch by flowing water at the appropriate sprinkler system inspector s test valve (Manually operating a flow switch is not an acceptable method) Confirm that the retard mechanism is correctly set by verifying that an alarm occurs within 90 seconds after starting water flow Move every sprinkler valve off-normal and confirm a supervisory signal at the FACP Confirm supervisory signals at the FACP for any other supervisory devices, such as fire pump running

37 FUNCTIONAL TESTING OF INDICATING APPLIANCES This testing is performed concurrently with the testing of initiating devices and requires a copy of the floor plans that show notification appliance locations. Horns/Speakers and Strobes While visible appliances are quiescent (not activated), verify that the candela rating of each one is consistent with that shown on the floor plans Confirm that each appliance, audible and visible, operates during an alarm Adequate Sound Pressure Levels (SPL) should be observed throughout the protected area in accordance with NFPA 72 and the applicable code. As a minimum, representative sound pressure levels should be measured throughout the occupied space

38 SOUND MEASUREMENT RECOMMENDATIONS Measurements shall be taken with an ANSI S1.4a compliant Type 2 Sound Level Meter The sound meter shall be set using the time-weighted characteristic F(FAST), and shall record the maximum sound output (Peak Hold) when the audible emergency evacuation signal is on Representative measurements should be taken in the center of a subject room or occupied space, with the meter held at a height of approximately 4.5 feet (1.5m) and at least 1.5 feet (.5m) from any hard surface If required, multiple measurements should be taken and the average SPL shall be recorded In sleeping areas where a barrier such as a door is located between the notification appliance and the listener, the should pressure level shall be measured with the door closed or other barrier in place between the appliance and the listener If inadequate or excessive SPL s are observed, the technician should consult the installer and/or System Designer and recommend any corrective action or system adjustments

39 VOICE EVACUATION SYSTEMS Verify that the speaker-tap settings are consistent with that shown on floor plans and design documents Measure and record representative SPL s throughout the occupied space as described above, and as otherwise required Ensure the pre-recoded message is distinguishable and understandable

40 VOICE EVACUATION SYSTEMS Ensure that the prerecorded message is playing on the alarm floor the floor above and the floor below after tripping an initiating device, all levels must be verified for correct operations of evac message routing Verify the operation by area for emergency paging, stairwells must be zoned separately than other areas. All areas must meet required SPL levels Plug into and operate all fire-fighter phone jack locations verify that the call is received from the correct location

41 Synchronization of Visuals Visible notification appliances shall be installed in accordance with Table (a), using one of the following: 1. A single visible notification appliance. 2. Two visible notification appliances located on opposite walls. 3. * Two groups of visible notification appliances, where visual appliances of each group are synchronized, in the same room or adjacent space within the field of view. This shall include synchronization of strobes operated by separate systems. 4. More than two visible notification appliances or groups of synchronized appliances in the same room or adjacent space within the field of view that flash in synchronization.

42 ELEVATOR-RECALL This test should be performed with the assistance of the elevator contractor. Initiate an alarm on an elevator-recall detector on a floor other than the primary recall floor Confirm that the elevator returns to the primary recall floor Initiate an alarm on an elevator-recall detector on the primary recall floor Confirm that the elevator returns to an alternate floor Confirm that the operation of any other functions, such as shunt trip and/or elevator warning lights

43 AUXILIARY RELAYS This section can be used to check auxiliary operation or controls not included in any other section. Before performing this test, review the input/output matrix. Initiate an alarm and verify that each auxiliary relay performs the required function Fan Shutdown Verify that each unit shuts down in accordance with the input/output matrix Stairwell and/or atrium pressurization Verify that fans run in accordance with the input/output matrix Damper Controls Verify operation in accordance with the input/output matrix Access and/or egress controlled doors Verify that all doors unlock in accordance with the input/output matrix

44 SMOKE DOOR RELEASE This testing is done concurrently with the testing of initiating devices and is best accomplished with a copy of the floor plans that show magnetic door holder locations. Confirm that each magnetic door holder de-energizes during an alarm, documenting proper operation of each Confirm that no obstruction, such as a carpet, prevents the door from closing and latching Confirm that magnetic door holders are not powered when the primary AC system power fails (Unless part of the 24 volt system and included in battery calculations)

45 FAN CONTROL AND FAN OVERRIDE CONTROL SYSTEM These tests must be conducted with the HVAC contractor. Record the results of the following tests on acceptable documentation. Before starting this physical testing, review the input/output matrix and the programmer s report. With the FACP normal: Place each FACP fan-control switch in the on position Verify that the proper fan has begun to operate and that the associated fan funning indicator is illuminated Verify that the local HOA (Hand-off-Auto) switch as the fan is overridden

46 FAN CONTROL AND FAN OVERRIDE CONTROL SYSTEM (Continued) Place each FACP fan-control switch in the AUTO position Verify that the appropriate fan is under control of temperature-control equipment and, if applicable, that the associated AUTO indicator next to the switches is illuminated Verify that the local HOA switch at the fan is not overridden Place each FACP fan-control switch in the OFF position Verify that the proper fan stops and that the associated FAN STOPPED indicator next to the switch is illuminated Verify that the local HOA switch at the fan is overridden With all fan-control switches in the AUTO position, reset the FACP Verify that all fans restart in the appropriate sequence

47 BYPASS SWITCHES Operate all bypass switches and verify that a trouble condition is activated at the FACP

48 Additional Oregon Requirements

49 DOCUMENTATION Upon completion of the testing, and when required, complete and sign NFPA 72 Record of Completion The installer s representative shall prepare and sign its respective parts of the Record of Completion Copies of the NFPA INSPECTION AND TESTING form shall be distributed, as required, to the system owner, the AHJ, the provider of supervising station service, and the installer A copy of all completed forms shall be left at the FACP and in the permanent project file

50 Building Reports Joint Commission Template

51 Testing Log

52 Notes and Recommendations in EC Format

53 Inspection Summary in EC Format

54

55

56

57

58

59

60

61

62 Post Acceptance Documentation Documentation Required. Every system shall include the following documentation, which shall be delivered to the owner or the owner s representative upon final acceptance of the system: 1. An owner s manual and manufacturer s published instructions covering all system equipment 2. Record drawings (As-Built) 3. For software-based systems, a record copy of the sitespecific software A complete record of the tests and operations of each system shall be kept until the next test and for 1 year thereafter.

63 Continued Service IFC Maintenance, inspection and testing. The building owner shall be responsible for to maintain the fire and life safety systems in an operable condition at all times. Service personnel shall meet the qualification requirements of NFPA 72 for maintaining, inspecting and testing such systems. A written record shall be maintained and shall be made available to the fire code official.

64 Continued Service * For software-based systems, a copy of the site-specific software shall be provided to the owner or owner s designated representative. A copy of the software shall be stored in nonvolatile non-erasable, non-rewritable memory and shall be stored on-site.

65 Reference Materials IFC NFPA ADA Oregon State Fire Marshal s Web Site - Fire & Life Safety Practices Detector Test Tools: SOLO 461 (available from SDI

66 Need Help??? Contact Performance Systems Portland, Oregon (HQ) Bothell, Washington It helps us to help you!!!!

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems

Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems Your Presenter: Merton Bunker, PE Inspections and tests are intended to reduce or limit: Loss of life

More information

2. HVAC and smoke control systems; fire, smoke, and combination fire/smoke dampers. 5. Central control and monitoring system.

2. HVAC and smoke control systems; fire, smoke, and combination fire/smoke dampers. 5. Central control and monitoring system. PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible.. This

More information

Functional Performance Test

Functional Performance Test Fire Alarm Control Panel & Fire Alarm Annunciator Panel Notify all building occupants that testing will be conducted. Fire alarm contractor shall have personnel with 2-way radios at the fire alarm control

More information

DIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM

DIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM DIVISION 26 ELECTRICAL SECTION 26 81 11 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install all equipment and accessories for a complete local, analog addressable, manually and automatically actuated,

More information

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2

More information

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used. PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire alarm and signaling systems at Sam Houston State University provide the highest level of life safety possible. This

More information

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard

More information

Hinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Hinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 28 3111 DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Manual fire-alarm boxes. 3. System smoke detectors. 4. Heat detectors.

More information

FIRE & LIFE SAFTEY STANDARD

FIRE & LIFE SAFTEY STANDARD Title: Effective Date: 01/01/14 Revised Date: 1/1/14 Code References: Title 16, Chapter 16.16 of the Roseville Municipal Code, NFPA 72 Note: This standard is a summary of Fire Department clarifications

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved

More information

Smoke Detector Activation of any smoke detector shall start the alarm verification mode.

Smoke Detector Activation of any smoke detector shall start the alarm verification mode. Description: The purpose of the section is to provide the UMCP Design Standards for the design and implementation of Fire Alarm Systems at the UMCP campus. Related Sections: TBD Effective Date: July 10,

More information

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline Moreno Valley Fire Department Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 8, 2017 Alarm & Signaling Systems PURPOSE Fire alarm and signaling systems are designed to

More information

Unified Fire Authority - Fire Prevention Bureau

Unified Fire Authority - Fire Prevention Bureau Unified Fire Authority - Fire Prevention Bureau FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance

More information

1.3 REFERENCE STANDARDS

1.3 REFERENCE STANDARDS SECTION 28 4600 FIRE DETECTION AND ALARM PART 1 -GENERAL 1.1 SECTION INCLUDES A. Fire alarm system design and installation, including all components, wiring, and conduit. B. Circuits from protected premises

More information

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE Effective Date: 11/01/02 Purpose: MECKLENBURG COUNTY To establish a set of guidelines for performance testing of all newly installed or upgraded fire alarm systems in order to ensure that all devices and

More information

Michigan State University Construction Standards FIRE DETECTION AND ALARM PAGE

Michigan State University Construction Standards FIRE DETECTION AND ALARM PAGE PAGE 283100-1 SECTION 283100 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

SECTION FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM

SECTION FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM SECTION 2 8 31 00 FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Request For Proposal apply to this Section.

More information

NFPA Changes

NFPA Changes Chapter 21, Emergency Control Functions and Interfaces Summary. Chapter 21 is new. These requirements were formerly found in Chapter 6, Protected Premises Fire Alarm Systems. The term fire safety function

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Alarm System Plan Review 2009 International Fire Code and 2010 NFPA 72 Date of Review // BLD201 - Project Address: Project Name: _ Professional

More information

Fire Alarm System Fundamentals

Fire Alarm System Fundamentals Fire Alarm System Fundamentals Mircom is the largest and oldest privately owned fire alarm and life safety manufacturer in North America and 5th largest overall with 50 years of industry experience. Mircom

More information

University Design Standard Fire Alarm Systems

University Design Standard Fire Alarm Systems 1.0 Overview University Design Standard Fire Alarm Systems This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit

More information

El Reno Fire Department Fire Alarm Plan Review Worksheet

El Reno Fire Department Fire Alarm Plan Review Worksheet El Reno Fire Department Fire Alarm Plan Review Worksheet This Fire Alarm Plan Review Checklist is provided as a guide to assist with your Fire Alarm Plan Review Submittal requirements. Please contact us

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 8/2004 Fire Chief Lee Koontz Fire Marshal Paul Smith EFD-FMO 3-1 2003 International Fire & Building Code as Amended NFPA Standards

More information

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions. 11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

More information

SECTION : FIRE ALARM & DETECTION SYSTEMS

SECTION : FIRE ALARM & DETECTION SYSTEMS SECTION 28 31 10: FIRE ALARM & DETECTION SYSTEMS 1. GENERAL A. This section applies to fire detection/alarm system and carbon monoxide system components and equipment installed during new construction

More information

Architect s Project Number of 12 Fire Alarm/Smoke Detection Systems District Master Specs 2013 Edition

Architect s Project Number of 12 Fire Alarm/Smoke Detection Systems District Master Specs 2013 Edition PART 1 GENERAL 1.1 SECTION INCLUDES SECTION 28 31 00 FIRE ALARM AND SMOKE DETECTION SYSTEMS A. Fire alarm and smoke detection systems 1.2 REFERENCES A. NFPA 72 B. NFPA 101 1.3 REGULATORY REQUIREMENTS A.

More information

COUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III

COUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III SECTION 28 3111 - DIGITAL ADDRESSABLE FIRE ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Changes in NFPA

Changes in NFPA Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration

More information

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. 2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is

More information

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION FIRE ALARM SYSTEM

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION FIRE ALARM SYSTEM OSU PROJECT NO. 30-04-15 PAGE 1 PART 1 GENERAL 1.1 WORK INCLUDED A. Provide all labor, materials, and equipment required to provide a complete and operating system of manual and automatic detection devices,

More information

SECTION FIRE ALARM SYSTEMS

SECTION FIRE ALARM SYSTEMS SECTION 16721 FIRE ALARM SYSTEMS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work

More information

SECTION COMMON WORK RESULTS FOR SAFETY AND SECURITY 1.1 RELATED SECTIONS

SECTION COMMON WORK RESULTS FOR SAFETY AND SECURITY 1.1 RELATED SECTIONS SECTION 280500 COMMON WORK RESULTS FOR SAFETY AND SECURITY PART 1 - GENERAL 1.1 RELATED SECTIONS A. All division 28 work shall, in addition to all division 1 specification sections, comply with all of

More information

Lake County / Multi-Department Storage Facility / Project / December 12, 2016 SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Lake County / Multi-Department Storage Facility / Project / December 12, 2016 SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS SECTION 283111 A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

OKLAHOMA STATE UNIVERSITY

OKLAHOMA STATE UNIVERSITY ENVIRONMENTAL HEALTH & SAFETY ADDRESSABLE FIRE ALARM SYSTEM STANDARD Revised 6/15 Revised: 6/15 Contact(s) Implementation Date Comments Gerald Petre, EHS June 2016 Review and Update Page 1 1.1 GENERAL

More information

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Rancho Cucamonga Fire Protection District Prevention Bureau Standard Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Updated: December 2016 for consistency

More information

Type of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number:

Type of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number: DATE OF SUBMISSION TO: Department of Licenses and Inspections Commercial and Industrial Fire Inspection Unit 990 Spring Garden Street, 3 rd Floor, Philadelphia, PA 19123 AP# CITY OF PHILADELPHIA FIRE ALARM

More information

Fire Alarm System Inspection and Testing Report

Fire Alarm System Inspection and Testing Report Fire Alarm System and ing Report Date of : Time of : 1. PROPERTY INFORMATION: Name of Property: Address: of property: Occupancy Type: Name of property representative: Address: Phone: Fax: E-mail: Local

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 13852- PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this

More information

Fire Alarm, Water Flow Alarm & Signaling Systems

Fire Alarm, Water Flow Alarm & Signaling Systems Orange County Fire Authority Community Risk Reduction 1 Fire Authority Road, Building A, Irvine, CA 92602 www.ocfa.org 714-573-6100 Fire Alarm, Water Flow Alarm & Signaling Systems Guideline D-03 Serving

More information

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R Region Project Page 1 PART 1 - GENERAL 1.1 REFERENCES.1 CAN/ULC-S524-2006, Standard for the Installation of Fire Alarm Systems..2 CAN/ULC-S525-2007, Audible Signal Device for Fire Alarm Systems..3 CAN/ULC-S526-2007,

More information

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS SECTION 907 FIRE ALARM AND DETECTION SYSTEMS 907.1 General. This section covers the application, installation, performance and maintenance of fire alarm systems and their components in new and existing

More information

STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018

STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018 STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018 STANDARD INFORMATION Standard Number: NFPA 72 Standard Name: National Fire Alarm and Signaling Code Standard Edition and Issue Date: 2016 Edition

More information

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax) FIRE DEPARTMENT SANTA CLARA COUNTY 14700 Winchester Blvd., Los Gatos, CA. 95032-1818 (408) 378-4010 (408) 378-9342 (fax) www.sccfd.org STANDARD DETAILS & SPECIFICATIONS Spec No C-4 Rev. Date 03/10/10 SUBJECT:

More information

NFPA 72 Code Changes vs 2013

NFPA 72 Code Changes vs 2013 NFPA 72 Code Changes - 2010 vs 2013 AFAA-NE Westborough, MA February 7, 2018 Richard Roux NFPA 72 National Fire Alarm and Signaling Code Overview and 2013 Changes NFPA 72 1993 Edition Aug 20, 1993 1996

More information

Fire alarm system specification for multiple tenant retail buildings

Fire alarm system specification for multiple tenant retail buildings Date: June 20, 2011 Project name: Baederwood Shopping Center Multiple Tenant Buildings B & C City/ State: Abington, PA Landlord s Vendor Contact: Dan Morrin Jr., NECCO Security Phone: (215)638-7999 Email:

More information

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS PART 1 GENERAL 1.1 SECTION INCLUDES A. Fire alarm and smoke detection systems 1.2 REFERENCES A. NFPA 72 B. NFPA 101 1.3 REGULATORY REQUIREMENTS A. System: UL listed B. Conform to requirements of NFPA 101

More information

SECTION DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM SECTION 283111 DIGITAL, ADDRESSABLE FIRE ALARM PART 1 - GENERAL 1.1 GENERAL A. This Section includes the following: 1. Fire-alarm control panel. 2. Manual fire-alarm boxes. 3. Smoke detectors. 4. Heat

More information

rpsa FIRE PROTECTION ENGINEERS

rpsa FIRE PROTECTION ENGINEERS FIRE PROTECTION ENGINEERS R.P. SCHIFILITI ASSOCIATES, INC. P.O. Box 297 Reading, Massachusetts 01867-0497 USA 781.944.9300 Fax / Data 781.942.7500 Telephone Elevator Fire Safety: Elevator Recall and Elevator

More information

Environmental Health & Safety

Environmental Health & Safety Environmental Health & Safety Oklahoma State University ADDRESSABLE FIRE ALARM SYSTEM STANDARD Environmental Health and Safety University Health Services Suite 002 Stillwater, OK 74078 (405) 744-7241 www.ehs.okstate.edu

More information

SECTION FIRE ALARM SYSTEMS

SECTION FIRE ALARM SYSTEMS SECTION 28 3100 PART 1 -GENERAL 1.01 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this

More information

DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM

DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics. A28.1 Standard of Practice - Fire Alarm Systems NOTE: Significant revisions or additions to the previous standards are highlighted in italics. OBJECTIVE OF STANDARD To provide compliant smart addressable

More information

Full Service Central Station Fire Alarm Listing Evaluation

Full Service Central Station Fire Alarm Listing Evaluation Full Service Central Station Fire Alarm Listing Evaluation Listing Evaluation A UL Listing project includes: 1. Evaluating the central station facility for compliance with UL 827, Central-Station Alarm

More information

THE BASICS OF FIRE ALARM PLAN REVIEW

THE BASICS OF FIRE ALARM PLAN REVIEW THE BASICS OF FIRE ALARM PLAN REVIEW Art Shaw A Shaw & Associates, LLC. ashaw@arthurshaw.com 231.838.3269 Fire Protection System Plan Reviewer FP000006 NFPA Certified Plans Examiner 02-0005 NFPA Certified

More information

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course Florida Building Code 2010 Chapter 9 Fire Protection Systems Advanced Course 1 Introduction This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors

More information

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE CHEETAH Xi 50 CONTROL PANEL SYSTEM

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE CHEETAH Xi 50 CONTROL PANEL SYSTEM SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Total Flood ECARO-25 TM clean agent fire suppression system utilizing HFC-125 as the fire extinguishing agent

More information

Florida Building Code 2010

Florida Building Code 2010 Introduction Florida Building Code 2010 Chapter 9 Fire Protection Systems This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors are familiar with

More information

You are required to READ ALL PAGES. of this application

You are required to READ ALL PAGES. of this application Fire/Smoke/Heat/CO Application Checklist You are required to READ ALL PAGES of this application NEW ROCHELLE FIRE DEPARTMENT 90 Beaufort Pl, New Rochelle, NY 10801 - (914) 654-2213 APPLICATION FOR FIRE/SMOKE/HEAT/CO

More information

Fire Prevention Coffee Break Training. February 2017

Fire Prevention Coffee Break Training. February 2017 Fire Prevention Coffee Break Training February 2017 Agenda FDC s - Lund Standpipes - Phelan Fire Alarm Testing Phelan/Dooley Questions and Answers Open Forum Standpipe requirement Standpipes are required

More information

1. The fire detection and alarm system (including the conduit) shall be a separate bid item and not part of the general electrical contract.

1. The fire detection and alarm system (including the conduit) shall be a separate bid item and not part of the general electrical contract. PART 1 - GENERAL SECTION 28 31 11 STANDARD 1.1 FIRE ALARM SYSTEM REQUIREMENTS A. Contractor Requirements 1. The fire detection and alarm system (including the conduit) shall be a separate bid item and

More information

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement of 1 9/22/2014 1:38 PM Second Revision No. 104-NFPA 72-2014 [ Section No. 3.3.3 ] 3.3.3 Accessible, Readily (Readily Accessible). Capable of being reached quickly for operation, renewal, or inspections

More information

SECTION FIRE ALARM SYSTEM PART 1 GENERAL

SECTION FIRE ALARM SYSTEM PART 1 GENERAL SECTION 16720 - FIRE ALARM SYSTEM PART 1 GENERAL 1.1 SCOPE & RELATED DOCUMENTS A. The work covered by this section of the specifications includes the furnishing of all labor, equipment, materials, and

More information

COMMERCIAL (IBC) FIRE ALARM SUBMITTAL GUIDE

COMMERCIAL (IBC) FIRE ALARM SUBMITTAL GUIDE COMMERCIAL (IBC) FIRE ALARM SUBMITTAL GUIDE SUPERVISION OF AUTOMATIC FIRE SPRINKLER SYSTEMS SUPERVISION OF ALTERNATIVE AUTOMATIC FIRE-EXTINGUISHING SYSTEMS FIRE ALARM AND DETECTION SYSTEMS The Fire Alarm

More information

Concerns: Affects: Dated: June 12, SECTION 1: GENERAL Scope Work Included... 3

Concerns: Affects: Dated: June 12, SECTION 1: GENERAL Scope Work Included... 3 Technical Service Note Detection Systems, Inc. Fairport, New York 14450-9199 Technical Service (800) 374-7454 Sales: (800) 289-0096 and (585) 223-4060 Fax: (585) 223-9180 Concerns: Affects: Dated: June

More information

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev Installation Guide for AL600ULM Multi-Output Access Control Power Supply Charger Rev. 091800 1 AL600ULM - Multi-Output Access Control Power Supply/Charger Overview: The AL600ULM multi-output access control

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST FIRE AND LIFE SAFETY SYSTEMS FOR STRUCTURES FIVE OR MORE STORIES IN HEIGHT AND LESS THAN 75 FEET IN HEIGHT FROM THE POINT

More information

Duct smoke housings, 4-wire D341/D341P and D342/D342P

Duct smoke housings, 4-wire D341/D341P and D342/D342P Duct smoke housings, 4-wire D341/D341P and D342/D342P en Installation manual Duct smoke housings, 4-wire Notices en 3 1 Notices These instructions cover the installation of the D341/D342 Duct smoke housings

More information

SECTION FIRE ALARM

SECTION FIRE ALARM SECTION 16740 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this

More information

LifeAlarm Fire Alarm Control Panels

LifeAlarm Fire Alarm Control Panels LifeAlarm Fire Alarm Control Panels UL, ULC Approved* Features Control panel operator convenience features: Wide viewing angle 2 x 20 (40 character) alphanumeric LCD and dedicated LEDs provide convenient

More information

Brown University Revised April 12, 2013 Facilities Design & Construction Standards

Brown University Revised April 12, 2013 Facilities Design & Construction Standards SECTION 28 31 10 - FIRE ALARM SYSTEMS, SMOKE ALARMS, CARBON MONOXIDE PART 1 - GENERAL 1.1 SUMMARY: A. Section Includes: 1. Fire Alarm and Detection Systems 2. Single Station Smoke Alarms 3. Single Station

More information

Division 28 - Electronic Safety and Security

Division 28 - Electronic Safety and Security Division 28 - Electronic Safety and Security 28 31 11 Fire Alarm Systems Fire alarm systems shall be installed in buildings when required by this section. 1. Purpose: The primary purpose of a fire alarm

More information

SECTION FIRE DETECTION AND ALARM

SECTION FIRE DETECTION AND ALARM PART 1 - GENERAL 1.1 DESCRIPTION SECTION 28 46 00 SPEC WRITER NOTES: 1. The A/E must obtain a copy of the VA ENGINEERING GUIDE FOR FIRE PROTECTION DESIGN which provides fire alarm system criteria that

More information

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications:

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications: PART 1 GENERAL 1.01 Quality Assurance A. Fire Alarm Contractor Qualifications: 1 The Fire Alarm contractor shall be an Edwards Systems Technology (EST) designated representative and authorized to sell,

More information

A. Provide addressable fire alarm system throughout the facility and supervise wet and preaction fire sprinkler system.

A. Provide addressable fire alarm system throughout the facility and supervise wet and preaction fire sprinkler system. SECTION 283111 - PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

109-B Concord Drive Casselberry, FL DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72. Owner s Address: Owner's Phone Number:

109-B Concord Drive Casselberry, FL DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72. Owner s Address: Owner's Phone Number: 109-B Concord Drive Casselberry, FL 32707 407.830.6500 DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72 Pg 1 of 4 Equity One 11180600 Owner/Representative: WO#: _Customer#: 1550 NE Miami Garden Dr

More information

COMMISSION ORDER. IT IS FURTHER ORDERED that the Request for Bid and Notice to Bidders be displayed on the Franklin County website.

COMMISSION ORDER. IT IS FURTHER ORDERED that the Request for Bid and Notice to Bidders be displayed on the Franklin County website. 4.e STATE OF MISSOURI County of Franklin ss. COMMISSION ORDER Commission Order No. 2016-316 Third Quarter Term 2016 Tuesday,August,09,2016 Bid Notice IN THE MATTER OF ADVERTISING FOR SEALED BIDS FOR SMOKE

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE Deluge Devices 270a 1. PRODUCT NAME VIKING PAR-3 Available since 1991 2. MANUFACTURED FOR: THE VIKING CORPORATION 210 N. Industrial Park Road Hastings, Michigan 49058 U.S.A. Telephone: (269) 945-9501 (877)

More information

1. Buildings on the Pullman campus are monitored by a Simplex 4120 FDA Network or a Siemens XLS Network.

1. Buildings on the Pullman campus are monitored by a Simplex 4120 FDA Network or a Siemens XLS Network. 28 31 00 PART 1 - GENERAL 1.01 SCOPE A. Background: Washington State University has agreements with Simplex- Grinnell and Siemens Industry, Inc. to provide Fire Detection and Alarm (FDA) systems for the

More information

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM SECTION 1 - GENERAL CONDITIONS SPECIFICATION FOR A TOTAL FLOOD I. SCOPE: This specification outlines the requirements for a Total Flood ECARO-25 TM clean agent fire suppression system utilizing HFC-125

More information

Specification/ Data Sheet

Specification/ Data Sheet Specification/ Data Sheet TRITON RP Agent Release Control Panel FEATURES Agent Release Control Panel designed specifically for suppression release operation with: Four initiating device circuits (IDCs)

More information

2018 NICET Code Transition Changes

2018 NICET Code Transition Changes 2018 NICET Code Transition Changes NICET will be transitioning to newer codes accepted in their exams in mid-october 2018, specifically: NFPA 72 2016 NFPA 70 2014 IBC 2015 NFPA 101 2015 Here are some changes

More information

Voice Annunicated Fire Alarm System Page 1 of 26

Voice Annunicated Fire Alarm System Page 1 of 26 Last Update: May 12, 2017 Consultant s Handbook Page 1 of 26 A. General: 1. Voice annunciated, intelligent, addressable fire alarm systems at BSU are used in all residence halls, high rise buildings and

More information

DERRY FIRE DEPARTMENT LISTED AGENT CERTIFICATION PROGRAM

DERRY FIRE DEPARTMENT LISTED AGENT CERTIFICATION PROGRAM DERRY FIRE DEPARTMENT LISTED AGENT CERTIFICATION PROGRAM THIS COURSE IS FOR AGENTS WISHING TO DISABLE TRANSMITTING SIGNALS IN ORDER TO PERFORM MAINTENANCE TESTING AND DRILLS. OBJECTIVE The objective of

More information

ICC CODE CORNER 2012 IFC Code & Commentary

ICC CODE CORNER 2012 IFC Code & Commentary 907.7 Acceptance tests and completion. Upon completion of the installation, the fire alarm system and all fire alarm components shall be tested in accordance with NFPA 72. A complete performance test of

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Notification Appliances

More information

The following information shall become and form part of the contract documents.

The following information shall become and form part of the contract documents. October 4, 206 To: Attention: Re: All Bidders All Bidders JCBE Gymnasium HVAC Upgrades BC#: 206433 Edmonds Project No.: BHM6090 All bidders, The following information shall become and form part of the

More information

ONYX FirstVision Specification Interactive Firefighters Display

ONYX FirstVision Specification Interactive Firefighters Display ONYX FirstVision Specification Interactive Firefighters Display NOTIFIER is a registered trademark, and ONYX FirstVision, NOTI FIRE NET, and VeriFire are trademarks of Honeywell International Inc. Microsoft

More information

MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO

MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO Prepared For: Public Schools Facilities Authority State of New Mexico 2019 Galisteo, Suite

More information

System Test Report CLEAN AGENT

System Test Report CLEAN AGENT City of Black Hawk Fire Department 196 Clear Creek Street PO Box 68 Black Hawk, CO 80422-068 Office 303-582-0426 Fax 303-582-2229 www.cityofblackhawk.org System Test Report CLEAN AGENT Occupancy Information

More information

IN2 Digital, Addressable Fire-alarm System

IN2 Digital, Addressable Fire-alarm System Illinois Math and Science Academy DigitalCommons@IMSA Project Manuals IN2 2015 IN2 Digital, Addressable Fire-alarm System Illinois Mathematics and Science Academy Follow this and additional works at: http://digitalcommons.imsa.edu/facility_in2_manuals

More information

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications:

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications: PART 1 GENERAL 1.01 Quality Assurance A. Fire Alarm Contractor Qualifications: 1 The Fire Alarm contractor shall be an Edwards Systems Technology (EST) designated representative and authorized to sell,

More information

26 of 128 9/23/2014 9:25 AM

26 of 128 9/23/2014 9:25 AM 26 of 128 9/23/2014 9:25 AM Second Revision No. 105-NFPA 72-2014 [ Global Comment ] Revise the Annex F figures that include a smoke detector symbol (hexagon with a whisp of smoke) so that the new smoke

More information

SECTION TOTAL FLOODING ECARO-25 CLEAN AGENT FIRE EXTINGUISHING SYSTEM

SECTION TOTAL FLOODING ECARO-25 CLEAN AGENT FIRE EXTINGUISHING SYSTEM SECTION 13966 TOTAL FLOODING ECARO-25 CLEAN AGENT FIRE EXTINGUISHING SYSTEM Display hidden notes to specifier by using Tools / Options / View / Hidden Text. PART 1 GENERAL 1.1 SECTION INCLUDES A. Total

More information

DESIGN & CONSTRUCTION GUIDELINES

DESIGN & CONSTRUCTION GUIDELINES Facilities Management 4202 E. Fowler Avenue, OPM 100 Phone: (813) 974-2625 Design & Construction Tampa, Florida 33620-7550 Website: usf.edu/fm-dc DESIGN & CONSTRUCTION GUIDELINES DIVISION 28 ELECTRONIC

More information

Brighton Area Fire Authority

Brighton Area Fire Authority 615 W. Grand River Ave. Brighton, MI 48116 o: 810-229-6640 f: 810-229-1619 January 14, 2019 Fire Alarm Contractors RE: Fire Alarm Credential & Submittal Requirements To Whom It May Concern: The following

More information

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPUSLE VALVE, Fike FK AGENT & SHP PRO CONTROL PANEL

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPUSLE VALVE, Fike FK AGENT & SHP PRO CONTROL PANEL SECTION 1 GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Total Flood Clean Agent Fire Suppression System utilizing FK-5-1-12 as the fire extinguishing agent and with a

More information

C. All control equipment must have transient protection devices to comply with UL864 requirements.

C. All control equipment must have transient protection devices to comply with UL864 requirements. SECTION 28 31 11 - PART 1 - GENERAL 1.1 SCOPE & RELATED DOCUMENTS A. The work covered by this section of the specifications includes the furnishing of all labor, equipment, materials, and performance of

More information

Fire Alarm and Life Safety System Inspection Certificate

Fire Alarm and Life Safety System Inspection Certificate Fire Alarm and Life Safety System Inspection Certificate For Sample FireScan Healthcare 123 Main Street Anytown, State 55555 Tested to NFPA 72 Standards, 2007 Edition This Inspection was performed in accordance

More information

Fort Rouge Leisure Centre Section HVAC Upgrades Phase 2 Page 1 of 5 Bid Opportunity No March 2013 FIRE ALARM SYSTEMS

Fort Rouge Leisure Centre Section HVAC Upgrades Phase 2 Page 1 of 5 Bid Opportunity No March 2013 FIRE ALARM SYSTEMS HVAC Upgrades Phase 2 Page 1 of 5 Part 1 General 1.1 SUMMARY.1 Section Includes:.1 Materials and installation for fire alarm systems upgrades..2 Audible signal devices..3 End-of-line devices..4 Sustainable

More information