Selection of Explosion Protected Equipment for Hazardous Locations. Compiled by: Pieter Coetzee ZONE 2 ZONE 1 ZONE 0.

Size: px
Start display at page:

Download "Selection of Explosion Protected Equipment for Hazardous Locations. Compiled by: Pieter Coetzee ZONE 2 ZONE 1 ZONE 0."

Transcription

1 Selection of Explosion Protected Equipment for Hazardous Locations Compiled by: Pieter Coetzee ZONE 2 ZONE 0 ZONE 1 Be safe be Ex

2 Contents Introduction Occupational Health and Safety Act. (Act 85 of 1993) & ARP 0108 Area Classification Equipment Protection Levels (EPL) Temperature Classification Different Ex Techniques Marking of Ex Equipment Selection of EPE Conclusion

3 Introduction Hazardous Location Definition An area in which an explosive gas atmosphere or combustible dust, in the form of a cloud is present, or may be expected to be present, in quantities such as to require special precautions for the construction, installation and use of equipment Explosion protected descriptive of electrical apparatus designed and approved for use in hazardous locations in accordance with a suitable protection method, including Ex d, Ex i, Ex e, Ex p, Ex na, Ex s, Ex m and Ex q

4 Three components are required for an explosion or fire to occur Oxygen Flammable Substance Ignition Source

5 Possible results from explosions, incidents and fires Includes Loss of life Loss of production (Financial Impact) Damage to plants Environmental impact

6 Occupational Health and Safety Act. (Act 85 of 1993) Act The Act shall refer to the latest issue of the Occupational Health and Safety Act 85/1993 (OHSA). To meet safety requirements as per section 44 of the OHS Act. (EMR 9(1)) Every employer or user shall identify all hazardous locations and classify them in accordance with the relevant health and safety standard incorporated into these Regulations under section 44 of the act.

7 Occupational Health and Safety Act. (Act 85 of 1993) To ensure legal compliances at all time EMR 9(3) requires that: every employer or user referred to in sub regulation (1) shall be in possession of a certificate in a form acceptable to the chief inspector which has been issued by an approved inspection authority and in which it is certified that the electrical machinery referred to in sub regulation (2) has been manufactured and tested for the groups of dangerous articles in accordance with the relevant health and safety standard incorporated into these Regulations under section 44 of the Act: Provided that in lieu of such certificate an inspector may approve permanent labelling on such machinery, which label shall contain all the relevant information.

8 ARP 0108 Annex c Upgrading and maintenance of EPE certificates for mines and factories C.1 In South Africa, all EPE used in underground mines (Group I) and on surface (Group II) shall be covered by an IA certificate. The requirements in C.2 to C.15 cover the validity of IA certificates. C.2 All IA certificates issued shall have a validity period of 10 years. Where a product is in service and its certificate has expired it will not be affected. IA certificates based on overseas certification will be valid for a period of one year

9 Responsibilities and Authorities Description Regulation Standard Responsibility Area Classification EMR 9(1) EIR 4(1) Selection of Ex equipment EMR 9(1) EIR 4(1) Installation of Ex equipment EMR 9(1) EMR 9(2) SANS SANS SANS SANS EIR 4(1) Certification of Ex equipment EMR 9(1) SANS Maintenance and inspection of Ex equipment EMR 9(8) EIR 2(1) ARP 0108 SANS SANS Plant owner (Competent personnel; committees or consultant) Production Manager Plant owner and projects ( Engineering) Electrical Engineering Manager Plant owner done by own personnel or contractors SGI-MOR Approved test Laboratory(ATL) Plant owner( All Ex equipment must be inspected every two years) OSH ACT Repair of Ex equipment EIR 2(1) SANS SANS Approved test Laboratory(ATL) SABS; EXPLOLABS; MASC Certificate of compliance(coc) - SANS MIE test installation and make sure it complies and then issue a COC Mechanical Equipment EN & 3 Mechanical

10 Area Classification /Map

11 Important information on Area Classification drawing/map

12 Important information on Area Classification drawing /Map

13 Three zones for gases and vapours Substance Zones Frequency of formation of explosive atmosphere Gases and Vapours 0 Location in which an explosive gas/vapours or mist atmosphere is present continuously or for long periods. 1000hrs + per year 1 Location in which an explosive gas/vapours or mist atmosphere is likely to occur in normal operation hrs per year 2 Location in which Gas/Vapours or mist atmospheres present during abnormal circumstances hrs per year Examples Zone 0 is not found in the open air but inside vessels or badly ventilated rooms. Zone 1 are normally small volumes found around sample points or pump seals at certain frequency a day.(eg. Twice a day) Large part of the plant is normally a Zone 2 area for eg. abnormalities at flanges or sample points. Zone 0 is the most severe zone (the highest probability of flammable atmosphere presence). Equipment for this zone requires the most stringent protection against providing a source of ignition.

14 Example of a typical zone activity would be filling a barrel of petrol in an enclosed area Zone 2 Zone 0 Zone 1 Zone 1 Zone 0 Zone 0 Zone 1 Zone 2 Present continuously or for long periods Likely to occur in normal operation Present during abnormal circumstances. 1000hrs + per year hrs per year hrs per year

15 Area divided into Zones Zone 0 Zone 1 Zone 2 Present continuously or for long periods. 1000hrs + per year Likely to occur in normal operation hrs per year Present during abnormal circumstances hrs per year Vent Bund Wall Liquid

16 Flammable substance Hazardous areas are defined by three main criteria: The type of hazard The likelihood of the hazard being present in flammable concentrations The (auto) ignition temperature of the hazardous material The type of hazard (Groups) The hazard will be in the form of a gas, vapour, dust or fibre. Gases and Vapours (Group I/II) Gases and vapours are categorized in terms of their ignition energy or the maximum experimental safe gap (in respect of flameproof protection). This categorization leads to the Gas Groups:

17 Gas Groups Industry Mining Industry Group I Surface Industry Group II Gas Group I IIA Substance MIE Selection of equipment Methane 200µJ Equipment only suitable for mines unless it is additional approved for surface: Marked I/IIC Propane 180 µj and higher IIA; IIB and IIC certified equipment may be use in an IIA area. IIB Ethylene 60 µj -180 µj IIB and IIC certified equipment may be used in an IIB area. IIC Hydrogen 20 µj 60 µj Only IIC certified equipment is allowed to be used in an IIC area. (The gases noted in the table are typical gases for each group.) MIE Minimum ignition energy Gas Group IIC is the most severe gas group

18 Temperature Classes Explosion proof equipment, installed within the Ex area, is divided into 6 temperature classes (T1 to T6). Temperature class is not as it is often wrongly believed the operating temperature range of the equipment, but the maximum permissible surface temperature of the equipment, in relation to + 40 C ambient temperature on any surface area, and should not be exceeded at any time. The maximum surface temperature must remain below the ignition temperature of the surrounding medium at all times. The equipment requirements increases from T1 to T6. T-Class Maximum surface temperature of the equipment Ignition temperatures of combustible substances T1 450 C > 450 C T2 300 C > 300 C T3 200 C > 200 C T4 135 C > 135 C T5 100 C > 100 C T6 85 C > 85 C

19 Auto-ignition temperatures (vapours/gases and dust) Vapours/gases Gas Temperature Methane 580 C Hydrogen 560 C Propane 493 C Ethylene 425 C Acetylene 305 C Naphtha 290 C Carbon disulfide 102 C Dust Substance Temperature Sugar 460 C Wood 340 C Flour 340 C Grain dust 300 C Tea 300 C

20 Equipment Protection Level (EPL) Group Ex risk Zone EPL I (mines) energized Ma I (mines) de-energized in presence of Ex atmosphere Mb Minimum type of protection II (gas) II (gas) II (gas) explosive atmosphere > 1000 hrs/yr explosive atmosphere between 10 and 1000 hrs/yr explosive atmosphere between 1 and 10 hrs/yr 0 Ga ia, ma 1 Gb ib, mb, px, py, e, o, q, s 2 Gc n, ic, pz III (dust) III (dust) III (dust) explosive surface > 1000 hrs/yr explosive surface between 10 and 1000 hrs/yr 20 Da 21 Db explosive surface between 10 and Dc

21 Different Ex Techniques Technique Protection Type Symbol Application Typical application Energy Limiting Intrinsic Safety Ex ia Zone o Instrumentation; Ex ib Zone 1 control gear Ex ic Zone 2 Ex iad Zone 20 Containment Flameproof Ex d Zone 1 & 2 Switchgear; motors; pumps Principle Refined Mechanical design Refined Mechanical design Segregation (Isolation) Increase Safety Ex e Zone 1 & 2 Motors; Light fittings Non-sparking Ex na Zone 2 Motors; Light fittings Pressurization Exp; Ex pd Zone 1& 2 Zone 21 Motors; analysers; control rooms Segregation (Isolation) Encapsulation Ex m; Ex md Zone 1& 2 Zone 20 Solenoids; fuses; relays Segregation (Isolation) Sand filling Ex q Zone 1 & 2 Strip heaters, capacitors

22 Marking of Ex equipment E Ex ia IIC T6 Ga Equipment protection level (EPL) Temperature Classification (T-Class) identifies the maximum ignitioncapable surface temperature which the equipment will exhibit.(t6 =85 C) Unless otherwise stated, the maximum ambient temperature to which the equipment may be subjected (and thus the maximum ambient temperature for which the T-Class will be true) is 40 C Gas Group/Apparatus Group The roman II indicates surface industry (not mining). IIC is the most onerous subgroup in Group II. Equipment which is suitable for IIC will also be suitable for IIA and IIB Code letters indicate the type of protection (or types) of protection utilized by this equipment. ia indicates Intrinsic Safety Ex: is the symbol for explosion protection The initial E indicating conformity with European EN standards. This E is no longer used so it will not be shown on equipment which has been designed and certified since around 2007

23 Selection of EPE for hazardous location Equipment marking Ex d IIC T5 Gb - 20 to 40 C Verification sheet Area Equipment Compliance Zone 1 d (Gb) Suitable Gas Group IIB IIC Suitable Temperature class T4 T5 Suitable Ambient temperature - 20 to 40 C - 20 to 40 C Suitable

24 Conclusion

Legislation associated with Hazardous Locations. Pieter Coetzee ZONE 2 ZONE 1 ZONE 0. Be safe be Ex

Legislation associated with Hazardous Locations. Pieter Coetzee ZONE 2 ZONE 1 ZONE 0. Be safe be Ex Legislation associated with Hazardous Locations Pieter Coetzee ZONE 2 ZONE 0 ZONE 1 Be safe be Ex Contents History Introduction Occupational Health and Safety Act. (Act 85 of 1993) General Machinery Regulation

More information

Hazardous Areas - EXPLOSIONPROOF SOLENOIDS

Hazardous Areas - EXPLOSIONPROOF SOLENOIDS Hazardous Areas - EXPLOSIONPROOF SOLENOIDS SOME HISTORY The classification of hazardous areas into zones established the level of protection required for electrical equipment installed in explosive gas

More information

Airo Wireless Intrinsically Safe White Paper. Written By: David Schmitt

Airo Wireless Intrinsically Safe White Paper. Written By: David Schmitt Airo Wireless Intrinsically Safe White Paper Written By: David Schmitt Intrinsically Safe Cell Phone/Smartphone/PDA Intrinsically Safe (IS) is a protection certification for safe operation with electronic

More information

UL HAZARDOUS LOCATIONS SERVICES

UL HAZARDOUS LOCATIONS SERVICES UL HAZARDOUS LOCATIONS SERVICES The international preference in hazardous locations certification for over 100 years ul.com/hazloc Explosive Gas Atmospheres Class I Division S Includes flammable gases,

More information

Guide for hazardous areas

Guide for hazardous areas Guide for hazardous areas 1 Hazardous areas definitions 2 Gas and dust s 3 Temperature classifications 4 Common flammable gases, vapours and dust types 5 Protection concepts ATEX and IECEx 6 Protection

More information

Beamex. Calibration White Paper. Calibration in hazardous areas

Beamex. Calibration White Paper.   Calibration in hazardous areas Beamex Calibration White Paper info@beamex.com Calibration in hazardous areas This article discusses calibration in hazardous areas and what everyone needs to be aware of before entering into a hazardous

More information

The R. STAHL Technology Group Worldwide Success with Competence and Customer Support

The R. STAHL Technology Group Worldwide Success with Competence and Customer Support The R. STAHL Technology Group Worldwide Success with Competence and Customer Support The entrepreneurial basis of the R. STAHL Technology Group follows a long tradition. The product range is aimed at specialised

More information

Beamex Calibration White Paper. Calibration in hazardous areas

Beamex Calibration White Paper.  Calibration in hazardous areas Beamex Calibration White Paper info@beamex.com Calibration in hazardous areas This article discusses calibration in hazardous areas and what everyone needs to be aware of before entering into a hazardous

More information

REGULATIONS EUROPEAN ATEX DIRECTIVE. INTERNATIONAL SCHEME: IECEx AREAS CLASSIFICATION DEFINED BY DIRECTIVE 1999/92/EC

REGULATIONS EUROPEAN ATEX DIRECTIVE. INTERNATIONAL SCHEME: IECEx AREAS CLASSIFICATION DEFINED BY DIRECTIVE 1999/92/EC EUROPEAN ATEX DIRECTIVE > European Directive 2014/34/EU ATEX Directive 2014/34/EU is a "new approach" directive that applies to protective systems against explosions as well as all equipment used in or

More information

NZQA registered unit standard version 1 Page 1 of 5. Install fixed gas detection apparatus in hazardous areas

NZQA registered unit standard version 1 Page 1 of 5. Install fixed gas detection apparatus in hazardous areas Page 1 of 5 Title Install fixed gas detection apparatus in hazardous areas Level 4 Credits 2 Purpose This unit standard covers the installation, calibration, and response checking of fixed gas detection

More information

Overview of Hazardous Locations as They Relate to Solenoid Valves

Overview of Hazardous Locations as They Relate to Solenoid Valves Overview of Hazardous Locations as They Relate to Solenoid Valves Defined: Hazardous Location - "where fire or explosion hazards may exist due to flammable gases or vapors, flammable liquids, combustible

More information

Weighing Solutions for Hazardous Areas FULL COMPLIANCE WITH ATEX DIRECTIVE

Weighing Solutions for Hazardous Areas FULL COMPLIANCE WITH ATEX DIRECTIVE Weighing Solutions for Hazardous Areas FULL COMPLIANCE WITH ATEX DIRECTIVE PUE HX5.EX explosion-proof hazardous area indicator ATEX APPROVAL PUE HX5.EX is a cutting-edge weighing indicator, designed to

More information

HAZARDOUS AREA CLASSIFICATION AND SELECTION OF EQUIPMENT FOR SAFE USE THEREIN FROM AN ELECTRICAL VIEWPOINT

HAZARDOUS AREA CLASSIFICATION AND SELECTION OF EQUIPMENT FOR SAFE USE THEREIN FROM AN ELECTRICAL VIEWPOINT HAZARDOUS AREA CLASSIFICATION AND SELECTION OF EQUIPMENT FOR SAFE USE THEREIN FROM AN ELECTRICAL VIEWPOINT Olof Bekker Pr. Eng. BSc. Eng. BML S.MSAIEE, M.NACE Engineering Manager, Electrical COMMITMENT

More information

Hazardous Area Classification in Oil & Gas Industry. A Fire Prevention Tool

Hazardous Area Classification in Oil & Gas Industry. A Fire Prevention Tool Hazardous Area Classification in Oil & Gas Industry A Fire Prevention Tool SFPE ENGINEERING TECHNOLOGY CONFERENCE Oct 4, 2010 New Orleans, LA 1 Overview Oil and gas plants handle flammable materials 2

More information

ATEX, NOMENCLATURE AND CODING

ATEX, NOMENCLATURE AND CODING Technical Notes ATEX, NOMENCLATURE AND CODING The intent of this technical note is approach to the user to the ATEX normative. For this we will begin defining, what is an explosive atmosphere, what are

More information

HOW TO FIND THE RIGHT DEVICE FOR YOUR FACILITY

HOW TO FIND THE RIGHT DEVICE FOR YOUR FACILITY HOW TO FIND THE RIGHT DEVICE FOR YOUR FACILITY Cell Phones Smartphones PDA integrating people, products and processes Intrinsically Safe Cell Phone/Smartphone/PDA Intrinsically Safe (IS) is a protection

More information

Electrical Installations Design, Selection, Erection and Inspection

Electrical Installations Design, Selection, Erection and Inspection IECEx International Conference 2018 Jakarta, Indonesia Electrical Installations Design, Selection, Erection and Inspection IECEx International Conference 2018 Jakarta, Indonesia Peter Thurnherr thuba Ltd.,

More information

Guide to Hazardous Location Approvals:

Guide to Hazardous Location Approvals: Selection Guide Guide to Hazardous Location Approvals: MICRO SWITCH Hazardous Area Limit Switches Introduction There are many considerations when selecting a switch to be used in hazardous areas. In addition

More information

Guide to Hazardous Location Approvals: MICRO SWITCH Hazardous Area Limit Switches

Guide to Hazardous Location Approvals: MICRO SWITCH Hazardous Area Limit Switches Guide to Hazardous Location Approvals: MICRO SWITCH Hazardous Area Limit Switches A Selection Guide Introduction There are many considerations when selecting a switch to be used in hazardous areas. In

More information

WHAT WHITE PAPER IS POTENTIALLY EXPLOSIVE ATMOSPHERE CERTIFICATION AND WHY YOU. June 2010

WHAT WHITE PAPER IS POTENTIALLY EXPLOSIVE ATMOSPHERE CERTIFICATION AND WHY YOU. June 2010 WHITE PAPER WHAT IS POTENTIALLY EXPLOSIVE ATMOSPHERE CERTIFICATION AND WHY YOU MAY NEED IT! June 2010 Copyright Extronics Ltd 2010 The information contained in this document is subject to change without

More information

ATEX, NOMENCLATURE AND CODING

ATEX, NOMENCLATURE AND CODING ATEX, NOMENCLATURE AND CODING The intent of this technical note is approach to the user to the ATEX normative. For this we will begin defining, what is an explosive atmosphere, what are ATEX, as well as

More information

TECHNICAL SOLUTIONS APPLICABLE TO ELECTRICAL EQUIPMENTS DESIGNED FOR USE IN EXPLOSIVE GAS ATMOSPHERES

TECHNICAL SOLUTIONS APPLICABLE TO ELECTRICAL EQUIPMENTS DESIGNED FOR USE IN EXPLOSIVE GAS ATMOSPHERES TECHNICAL SOLUTIONS APPLICABLE TO ELECTRICAL EQUIPMENTS DESIGNED FOR USE IN EXPLOSIVE GAS ATMOSPHERES TECHNICAL SOLUTIONS APPLICABLE TO ELECTRICAL EQUIPMENTS DESIGNED FOR USE IN EXPLOSIVE GAS ATMOSPHERES

More information

Intrinsically Safe Solutions

Intrinsically Safe Solutions Intrinsically Safe Solutions INSTALLATION MANUAL 04/12/14 Rev D DOC-01-029 Documentation Feedback Your feedback helps us keep our documentation up to date and accurate. If you have any comments or suggestions

More information

IECEx International Conference 2017 Shanghai, China. Electrical Installations Design, Selection, Erection and Inspection

IECEx International Conference 2017 Shanghai, China. Electrical Installations Design, Selection, Erection and Inspection IECEx International Conference 2017 Shanghai, China Electrical Installations Design, Selection, Erection and Inspection IECEx International Conference 2017 Peter Thurnherr Shanghai thuba Electric Co. Ltd.,

More information

Erik Leider Project Engineer Hazardous Locations, Gas & Oil Underwriters Laboratories

Erik Leider Project Engineer Hazardous Locations, Gas & Oil Underwriters Laboratories Hazardous Locations: Understanding the Basics of Global Compliance Requirements Erik Leider Project Engineer Hazardous Locations, Gas & Oil Underwriters Laboratories DISCLAIMER/ TERMS OF USE: THE INFORMATION

More information

A guide to the use of electrical equipment in potentially explosive atmospheres To view this document in PDF format click here.

A guide to the use of electrical equipment in potentially explosive atmospheres To view this document in PDF format click here. A guide to the use of electrical equipment in potentially explosive atmospheres To view this document in PDF format click here Introduction Potentially Explosive Atmospheres exist where there is a risk

More information

MICROpeL 75 Combustible Gas Sensor Part Number: PM

MICROpeL 75 Combustible Gas Sensor Part Number: PM MICROpeL 75 Combustible Gas Sensor Part Number: PM759-000 Key Features & Benefits: ATEX, UL and CSA Approvals Withstands EN/IEC 60079-0 impact test Enhanced H 2 S and silicone poison resistance Reduced

More information

CLASS I LOCATIONS ZONE CLASSIFICATION

CLASS I LOCATIONS ZONE CLASSIFICATION HAZARDOUS (CLASSIFIED) LOCATIONS Hazardous locations are those locations where the risk of a fire or explosion may exist due to the presence of flammable gases or vapors, flammable liquids, combustible

More information

CONSULTING Training Courses

CONSULTING Training Courses CONSULTING Training Courses 2 EXPLOLABS TRAINING MAKES THE DIFFERENCE 1. GENERAL Why training by Explolabs Consulting? For training in the specialized, high-risk field of explosion protection, one needs

More information

Guidelines for Market Surveillance of Equipment for Explosive Environments (Hazardous Locations)

Guidelines for Market Surveillance of Equipment for Explosive Environments (Hazardous Locations) Annex II Guidelines for Market Surveillance of Equipment for Explosive Environments (Hazardous Locations) 1. According to Recommendation L, market surveillance should be included as a flanking area of

More information

Explosion-protected actuator Page 259 of 292

Explosion-protected actuator Page 259 of 292 Explosion-protected actuator Page 259 of 292 9.5 Explosion-protected actuator 9.5.1. What is an explosion? A flammable substance and oxygen, in a certain mixture, must be available to set off an explosion.

More information

Guide to Intrinsically Safe Portable Radios

Guide to Intrinsically Safe Portable Radios Guide to Intrinsically Safe Portable Radios An overview of common IS standards www.taitradio.com GUIDE TO INTRINSICALLY SAFE PORTABLE RADIOS SUMMARY The development of equipment for explosive atmospheres

More information

ATEX - GUIDE. A short introduction to ATEX Terminology. Equipment for use in flammable atmospheres C E R T I F I E D DANISH TECHNOLOGICAL INSTITUTE

ATEX - GUIDE. A short introduction to ATEX Terminology. Equipment for use in flammable atmospheres C E R T I F I E D DANISH TECHNOLOGICAL INSTITUTE DANISH TECHNOLOGICAL INSTITUTE The Danish Technological Institute is a self-owned and not-f-profit institution. We develop, apply and disseminate research- and technologically-based knowledge f the Danish

More information

Equipment and Solutions

Equipment and Solutions Equipment and Solutions Solution [formally technor atex] Subject to errors or changes Editing completed January 2016 Ex-tech Group is located at Forus in Stavanger, Norway, one of the world s top Centers

More information

1. GENERAL TECHNICAL INFORMATION

1. GENERAL TECHNICAL INFORMATION 1. GENERAL TECHNICAL INFORMATION 1.1 EXPLOSIVE ATMOSPHERES: Every time that dangerous quantities and concentration of flammable gas, vapors mixture or dust clouds exists, risk of explosions may arise.

More information

ATEX - GUIDE. A short introduction to ATEX Terminology. Equipment for use in flammable atmospheres

ATEX - GUIDE. A short introduction to ATEX Terminology. Equipment for use in flammable atmospheres Quick Introduction to: DANISH TECHNOLOGICAL INSTITUTE The Danish Technological Institute is a self-owned and not-fprofit institution. We develop, apply and disseminate research- and technologically-based

More information

Dual certification! Air handling units for potentially explosive atmospheres

Dual certification! Air handling units for potentially explosive atmospheres Dual certification! Air handling units for potentially explosive atmospheres X-CUBE Ex A certified safety product The air handling unit with dual ATEX certification ATEX directive 2014/34/EU applies to

More information

SOUTH AFRICAN NATIONAL STANDARD

SOUTH AFRICAN NATIONAL STANDARD ISBN 978-0-626-30262-7 SOUTH AFRICAN NATIONAL STANDARD The installation, inspection and maintenance of equipment used in explosive atmospheres Part 1: Installations including surface installations on mines

More information

AS/NZS :2009 Explosive atmospheres - Part 14: Electrical installations design, selection and erection

AS/NZS :2009 Explosive atmospheres - Part 14: Electrical installations design, selection and erection Skip to main content Skip to primary navigation Home Home About this portal Latest updates Menu Print Save Email Resource detail Citations AS/NZS 60079.14:2009 Explosive atmospheres - Part 14: Electrical

More information

EUROPEAN DIRECTIVES Explosive atmospheres ATEX 2014/34/EU

EUROPEAN DIRECTIVES Explosive atmospheres ATEX 2014/34/EU EUROPEAN DIRECTIVES Explosive atmospheres ATEX 2014/34/EU GENERAL The accidental ignition of an atmosphere containing a large quantity of gas, vapour, mists and/or dust may cause an explosion. Specific

More information

Explosion protection Marijan Gorše, dipl. ing.

Explosion protection Marijan Gorše, dipl. ing. Explosion protection Marijan Gorše, dipl. ing. 1/18 Flammable Gas Atmosphere We Can Control Them Explosion hazards mostly arise from flammable gases and vapours. Instead of avoiding their ignition by explosion

More information

Understanding Hazardous Locations Concepts

Understanding Hazardous Locations Concepts Gas Well Deliquification Workshop Sheraton Hotel, February 23 26, 2014 Understanding Hazardous Locations Concepts Mark Scantlebury, P. Eng., BASc President and CEO Extreme Telematics Corp. Disclaimer The

More information

ATEX GUIDE. A short introduction to ATEX Terminology. Equipment for use in flammable atmospheres. Directive 94/9/EC

ATEX GUIDE. A short introduction to ATEX Terminology. Equipment for use in flammable atmospheres. Directive 94/9/EC Quick Introduction to TÛV Denmark TÜV Denmark - is a part of the TÜV NORD Group a global Organisation f Certification and Inspection of: Quality Management Systems, Products, Processes and Qualification

More information

S T R I T T & P R I E B E I N C.

S T R I T T & P R I E B E I N C. Equipment Enclosure Comparisons Type of Enclosure European - Area of use Designation Standard IEC - Area of use Designation Standard USA - Area of use Designation Standard Flameproof Enclosure An enclosure

More information

Technical Data. General specifications Switching element function Rated operating distance s n 4 mm

Technical Data. General specifications Switching element function Rated operating distance s n 4 mm 0102 Model Number Features 4 mm non-flush Accessories BF 12 Mounting flange, 12 mm Technical Data specifications Switching element function NAMUR, NO Rated operating distance s n 4 mm Installation non-flush

More information

PYROS. Código: FT-PY01-I Revisión: TECHNICAL DATA. Polycarbonate tube of 4 mm. thickness LIGHT FITTING. Laquered steel painted white

PYROS. Código: FT-PY01-I Revisión: TECHNICAL DATA. Polycarbonate tube of 4 mm. thickness LIGHT FITTING. Laquered steel painted white . TECHNICAL DATA LIGHT FITTING REFLECTOR Polycarbonate tube of 4 mm. thickness Laquered steel painted white END CAPS Aluminium 2030 (polyester paint RAL 7047) POWER SOURCE LAMP TYPE 220-240V, 50/60Hz T8

More information

Explosive. Atmospheres. Safety and Reliability

Explosive. Atmospheres. Safety and Reliability Explosive Atmospheres Safety and Reliability Explosive Atmospheres When it comes to hazardous areas, the utilisation of suitable products and their proper maintenance are mandatory requirements in order

More information

ESSENTIAL EXPLOSION PROTECTION

ESSENTIAL EXPLOSION PROTECTION ESSENTIAL EXPLOSION PROTECTION 2 3 FOREWORD In many industries, gases, vapours, mist and dust develop and escape in the course of manufacturing, processing, transporting and storing combustible substances.

More information

NCS/SAS IAS/PES Chapter Seminar January 25-27, Hazardous Locations. OBIEC Consulting George Morlidge Fluor Canada

NCS/SAS IAS/PES Chapter Seminar January 25-27, Hazardous Locations. OBIEC Consulting George Morlidge Fluor Canada January 25-27, 2016 Hazardous Locations Marty Cole Tim Driscoll Hubbell Canada OBIEC Consulting George Morlidge Fluor Canada 1 Hazardous Locations - Agenda Canadian Electrical Code 2015 Changes What s

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD IEC 61892-7 INTERNATIONAL STANDARD Edition 2.0 2007-11 Mobile and fixed offshore units Electrical installations Part 7: Hazardous areas INTERNATIONAL ELECTROTECHNICAL COMMISSION PRICE CODE XA ICS 47.020.60

More information

Hazardous Location Surge Protection Solutions

Hazardous Location Surge Protection Solutions Hazardous Location Surge Protection Solutions Agenda PolyPhaser Transtector Market Leaders Hazardous Locations Class I Division 2 Qualifications and Definitions Impacts to Your Business Hazardous Applications

More information

OPTIWAVE X500 Supplementary Instructions

OPTIWAVE X500 Supplementary Instructions OPTIWAVE X500 Supplementary Instructions OPTIWAVE 3500 C OPTIWAVE 6500 C OPTIWAVE 7500 C Supplementary Instructions for ATEX applications KROHNE CONTENTS OPTIWAVE X500 1 General safety information 4 1.1

More information

Hazardous area descriptions

Hazardous area descriptions Hazardous area descriptions National Electrical Code (NEC) 500 Traditional standards used in North America. Example: Class I, Div 1, Group B, C, D, T4 Permitted Class Permitted Division Permitted Group

More information

INSTRUCTION MANUAL IS-mB1 Minialite Intrinsically Safe Round LED Beacon

INSTRUCTION MANUAL IS-mB1 Minialite Intrinsically Safe Round LED Beacon INSTRUCTION MANUAL Minialite Intrinsically Safe Round LED This instruction sheet describes installations which conform to EN60079:Part14:2008 Electrical Installation in Hazardous Areas. When designing

More information

[ TECHNOLOGY ] and does this definition affect a burner.

[ TECHNOLOGY ] and does this definition affect a burner. [ TECHNOLOGY ] JBD-11,500-G type burner for natural gas ATEX, EExd Zone 2. For combined cycle power plant in Riga Latvia. Aitor Fernández Project Engineer Automation Department Head afernandez@emcombustion.es

More information

Drive Technology \ Drive Automation \ System Integration \ Services * _0817* Inquiry Forms for Explosion-Proof Gearmotors

Drive Technology \ Drive Automation \ System Integration \ Services * _0817* Inquiry Forms for Explosion-Proof Gearmotors Drive Technology \ Drive Automation \ System Integration \ Services *23511257_0817* Inquiry Forms for Explosion-Proof Gearmotors Edition 08/2017 23511257/EN SEW-EURODRIVE Driving the world Inquiry forms

More information

Seat Ventilation offers an extensive range of ATEX certified products and is undertaking great efforts to extend this range even further.

Seat Ventilation offers an extensive range of ATEX certified products and is undertaking great efforts to extend this range even further. ATEX SOLUTIONS In order to apply a single level for health and safety requirements and to overcome barriers of trade within Europe, national regulations for explosion prevention were harmonized in 1975

More information

OPTIBAR DP 7060 Supplementary Instructions

OPTIBAR DP 7060 Supplementary Instructions OPTIBAR DP 7060 Supplementary Instructions Differential pressure transmitter Category ATEX II 1/2G, 2G Ex db ia IIC T6...T1 Ga/Gb, Gb IECEx Ex db ia IIC T6...T1 Ga/Gb, Gb Housing Aluminium: Single chamber,

More information

A GUIDE TO EUROPEAN (EEC) CERTIFICATION FOR ELECTRICAL EQUIPMENT IN HAZARDOUS AREAS

A GUIDE TO EUROPEAN (EEC) CERTIFICATION FOR ELECTRICAL EQUIPMENT IN HAZARDOUS AREAS A GUIDE TO EUROPEAN (EEC) CERTIFICATION FOR ELECTRICAL EQUIPMENT IN HAZARDOUS AREAS For a print friendly page click here INTRODUCTION Hazardous areas are those in which there exists a risk of explosion

More information

EtherCAT Box Modules (EPxxxx-xxxx)

EtherCAT Box Modules (EPxxxx-xxxx) Notes about operation of EtherCAT Box Modules (EPxxxx-xxxx) in potentially explosive areas (ATEX) Version: 1.1.0 Date: 2011-06-10 Table of Contents Table of Contents 1 Foreword 1 1.1 Notes on the documentation

More information

IS (Intrinsic safety) - Ex (Epsilon x) ATEX CENELEC

IS (Intrinsic safety) - Ex (Epsilon x) ATEX CENELEC IS (Intrinsic safety) - Ex (Epsilon x) ATEX CENELEC By: Helge Knudsen, Test&Approval, Niros Telecommunication A/S You may have heard those expressions concerning Transceivers and other electric equipment

More information

ATEX Safety Switches. More than safety.

ATEX Safety Switches. More than safety. ATEX Safety Switches More than safety. AUDIN - 8, avenue de la malle - 5370 Saint Brice Courcelles Tel : 03.6.0.0. - Fax : 03.6.0.8.0 - Web : http: www.audin.fr - Email : info@audin.fr ATEX products from

More information

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 07/16/08 TSEWG TP-8: ELECTRICAL EQUIPMENT ENCLOSURES AND HAZARDOUS LOCATIONS

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 07/16/08 TSEWG TP-8: ELECTRICAL EQUIPMENT ENCLOSURES AND HAZARDOUS LOCATIONS TSEWG TP-8: ELECTRICAL EQUIPMENT ENCLOSURES AND HAZARDOUS LOCATIONS ENCLOSURES. Select equipment enclosures to provide the following: To protect facility personnel from coming in contact with live parts.

More information

Intrinsically safe acoustic emission equipment opens the door to permanent monitoring applications in the oil and gas industry

Intrinsically safe acoustic emission equipment opens the door to permanent monitoring applications in the oil and gas industry 18th World Conference on Nondestructive Testing, 16-20 April 2012, Durban, South Africa Intrinsically safe acoustic emission equipment opens the door to permanent monitoring applications in the oil and

More information

Many different instruments Many different operating principles including: May sample many different gases & vapour From relatively simple to complex

Many different instruments Many different operating principles including: May sample many different gases & vapour From relatively simple to complex Part 2 Direct Reading Instrumentation Direct Reading Instruments Many different instruments Many different operating principles including: Electrochemical Photoionisation Flame ionisation Chemiluminescence

More information

Fact Sheet No.2. CompEx Modules EX01 to EX04 for Gas and Vapour Environments

Fact Sheet No.2. CompEx Modules EX01 to EX04 for Gas and Vapour Environments Fact Sheet No.2 CompEx Modules EX01 to EX04 for Gas and Vapour Environments Module Breakdown EX01: The preparation & installation of Ex d, n, e and p equipment in potentially explosive atmospheres. EX02:

More information

NON ELECTRICAL EQUIPMENT IN HAZARDOUS AREAS

NON ELECTRICAL EQUIPMENT IN HAZARDOUS AREAS NON ELECTRICAL EQUIPMENT IN HAZARDOUS AREAS The ATEX Directive consists of two EU Directives, ATEX Directive 2014/34/EU and ATEX Directive 99/92/EC. ATEX Directive 2014/34/EU embodies the European minimum

More information

Hazardous Area Classifications and Protections

Hazardous Area Classifications and Protections Hazardous Area Classifications Product Bulletin Hazardous Area Classifications and Protections The intent of this document is to provide a broad overview of hazardous area classifications and the types

More information

IECEx Certificate of Conformity

IECEx Certificate of Conformity IECEx Certificate of Conformity INTERNATIONAL ELECTROTECHNICAL COMMISSION IEC Certification Scheme for Explosive Atmospheres for rules and details of the IECEx Scheme visit www.iecex.com Certificate No.:

More information

Implementation of ATEX Guidelines

Implementation of ATEX Guidelines Implementation of ATEX Guidelines Temperature and Climatic Test Chambers for Usage under Conditions Carrying a Risk of Fire and Explosion What are ATEX guidelines? Introduction Duties of the system user...

More information

Certificate of Compliance

Certificate of Compliance FF0 001 Certificate of Compliance Certificate: 70116284 (LR 064969_0_00) Issued to: Mine Safety Appliances Company North American Division 1000 Cranberry Woods Dr Cranberry Township, Pennsylvania 16066-5296

More information

Smart encoders & actuators

Smart encoders & actuators Declaration of Conformity The manufacturer: LIKA ELECTRONIC SRL 36010 Carrè (VI) - Italy hereby declares that the following products (only when correctly assembled): XAC8018/1PB-14 XAC8018/1CB-14 XAC8018/1FD-14

More information

Switches compliant with ATEX directive

Switches compliant with ATEX directive Switches compliant with ATEX directive General Catalogue - Technical concepts page Position switches FD / FL series page 9 / Category Zone EPL Approvals 2G Gb Mb II 2G Ex ia IIC T6 Gb I Ex ia I Mb Product

More information

Approval of Ex (Electrical) Equipment for use/installation in Hazardous Areas.

Approval of Ex (Electrical) Equipment for use/installation in Hazardous Areas. Approval of Ex (Electrical) Equipment for use/installation in Hazardous Areas. Requirement under Rule 102 of the Petroleum Rules, 2002 lays down that no electrical wiring shall be installed and no electrical

More information

VSD AND SS DRIVING ATEX MOTORS February 2014

VSD AND SS DRIVING ATEX MOTORS February 2014 VSD AND SS DRIVING ATEX MOTORS February 2014 1 Introduction to ATEX 2 ATEX motor designation 3 VSD Sample Solutions 4 SS descriptions Introduction to ATEX EU territory define the use of electrical equipment

More information

TRASCO ATEX Couplings

TRASCO ATEX Couplings TRASCO ATEX Couplings ATEX ANNEX GRM-CERT-EX-EN SIT S.p.A. Viale A. Volta, 2-20090 Cusago (MI) - Italy Tel. +39.02891441 Fax +39.0289144291 - info@sitspa.it www.sitspa.it ATEX Annex This Annex is an integral

More information

Technical Data. General specifications Switching element function Rated operating distance s n 5 mm

Technical Data. General specifications Switching element function Rated operating distance s n 5 mm 0102 Model Number Features 5 mm flush Usable up to SIL 3 acc. to IEC 61508 Application Danger! In safety-related applications the sensor must be operated with a qualified fail safe interface from Pepperl+Fuchs,

More information

ANNEX GD-CERT-EX-EN SIT

ANNEX GD-CERT-EX-EN SIT SITEX ATEX Couplings ATEX ANNEX GD-CERT-EX-EN SIT S.p.A. Viale A. Volta, 2-20090 Cusago (MI) - Italy Tel. +39.02891441 Fax +39.0289144291 - info@sitspa.it www.sitspa.com ATEX Annex This Annex is an integral

More information

Page 1 Copyright by the Fieldbus Foundation All rights reserved.

Page 1 Copyright by the Fieldbus Foundation All rights reserved. Page 1 Copyright by the Fieldbus Foundation 1996-2004.. FOUNDATION Fieldbus Application Guide 31,25 kbit/s Intrinsically Safe Systems AG-163 Revision 2.0 This application guide has been prepared to aid

More information

4P75 CiTipeL Combustible Gas Sensor Part Number: PM

4P75 CiTipeL Combustible Gas Sensor Part Number: PM Product Datasheet 4P75 Document Purpose The purpose of this document is to present the performance specification of the 4P75 CiTipeL. This document should be used in conjunction with Operating Principles

More information

RE: USE OF FIREPRO IN POTENTIALLY EXPLOSIVE ATMOSPHERES

RE: USE OF FIREPRO IN POTENTIALLY EXPLOSIVE ATMOSPHERES Limassol 20 th August, 2015 RE: USE OF FIREPRO IN POTENTIALLY EXPLOSIVE ATMOSPHERES This document is intended to provide clarification on the use of FirePro Condensed Aerosol Generators in Potential Explosive

More information

Area Classification and Types of Protection for Explosive Atmospheres: A Review

Area Classification and Types of Protection for Explosive Atmospheres: A Review TELKOMNIKA Indonesian Journal of Electrical Engineering Vol. 16, No. 2, November 2015, pp. 238 ~ 243 DOI: 10.11591/telkomnika.v16i2.8506 238 Area Classification and Types of Protection for Explosive Atmospheres:

More information

Gas Detection GAS BOOK.

Gas Detection GAS BOOK. Gas Detection GAS BOOK 3 Typical applications for portable gas detectors Confined spaces Confined spaces can be found in a myriad of industries and applications and are one of the most prevalent applications

More information

for CE 134 CCSAUS certificate Meggitt SA Route de Moncor 4 PO Box 1616 CH Fribourg Switzerland Title page EN

for CE 134 CCSAUS certificate Meggitt SA Route de Moncor 4 PO Box 1616 CH Fribourg Switzerland Title page EN Title page CCSAUS certificate: EN 70034691 for EX Meggitt SA Route de Moncor 4 PO Box 1616 CH - 1701 Fribourg Switzerland CCSAUS certificate 70034691 www.meggittsensingsystems.com www.vibro-meter.com THIS

More information

ATEX Explained A brief Introduction

ATEX Explained A brief Introduction The Trusted Source for Secure Identity Solutions ATEX Explained A brief Introduction January 19, 2016 ATEX Zones Zones 1 (gas) or 21 (dust) (area in which under normal operation a potentially explosive

More information

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-d.

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-d. Additional Operating Instructions SITRANS F Vortex flowmeters Ex-d Edition 09/208 CONTENTS Safety instructions 3. General notes... 3.2 EU conformity... 3.3 Approval according to the IECEx scheme... 3.4

More information

NATIONAL RULES FOR ELECTRICAL INSTALLATIONS IN POTENTIALLY EXPLOSIVE ATMOSPHERES. ET 105:2001 (Second Edition)

NATIONAL RULES FOR ELECTRICAL INSTALLATIONS IN POTENTIALLY EXPLOSIVE ATMOSPHERES. ET 105:2001 (Second Edition) NATIONAL RULES FOR ELECTRICAL INSTALLATIONS IN POTENTIALLY EXPLOSIVE ATMOSPHERES ET 105:2001 (Second Edition) Consolidated Amendments, Corrigenda and Errata 01/2010 Introduction When ET 105:2001 was originally

More information

IECEx Certificate of Conformity

IECEx Certificate of Conformity IECEx Certificate of Conformity INTERNATIONAL ELECTROTECHNICAL COMMISSION IEC Certification Scheme for Explosive Atmospheres for rules and details of the IECEx Scheme visit www.iecex.com Certificate IECEx

More information

Certificate of Compliance

Certificate of Compliance FF0 001 Certificate of Compliance Certificate: 70116279 (LR 025993_0_000) Issued to: General Monitors, Incorporated 26776 Simpatica Circle Lake Forest, California 92630 USA Attention: Larry Vlagea The

More information

Selecting a Safe Tank Gauging Product. Understanding Hazardous Area Definitions for Equipment Approvals

Selecting a Safe Tank Gauging Product. Understanding Hazardous Area Definitions for Equipment Approvals Selecting a Safe Tank Gauging Product Understanding Hazardous Area Definitions for Equipment Approvals Hazardous Area Approvals A Worldwide Requirement There are many environmental considerations within

More information

Apparatus Groups are sometimes referred to, erroneously, as Gas Groups.

Apparatus Groups are sometimes referred to, erroneously, as Gas Groups. ATEX Jargon Buster ABB s ATEX jargon buster explains the terminology users are likely to encounter when purchasing equipment for hazardous areas. If you have a specific ATEX question, please send an email

More information

INSTRUCTION & SERVICE MANUAL

INSTRUCTION & SERVICE MANUAL INSTRUCTION & SERVICE MANUAL D2xC1 ALARM HORN AND STROBE For Use In Hazardous Locations 3) Ratings and Markings 3.1 ATEX / IECEx certification The D2xC1 Alarm Horn and Strobe complies with the following

More information

Phoenix Explosion-proof. Pan & Tilt heads and Camera Housings for potentially exposed environments. Answers for infrastructure.

Phoenix Explosion-proof. Pan & Tilt heads and Camera Housings for potentially exposed environments. Answers for infrastructure. Phoenix Explosion-proof Pan & Tilt heads and Camera Housings for potentially exposed environments Answers for infrastructure. Video monitoring under extreme conditions Security Products from Siemens is

More information

Technical Data. Dimensions

Technical Data. Dimensions 0102 Model Number Features 8 mm non-flush Stainless steel housing Usable up to SIL2 acc. to IEC 61508 Technical Data specifications Switching element function NAMUR, NC Rated operating distance s n 8 mm

More information

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK 17065:2012 to provide product conformity certification Newport Business Park New Port Road Ellesmere Port CH65 4LZ United Kingdom Contact:

More information

ATM Lighting sp. z o.o

ATM Lighting sp. z o.o INSTALLATION AND MAINTENANCE MANUAL FOR EXPLOSIONPROOF LIGHT FITTING EXL390LED Carefully read the instructions before mounting the light fitting. ATM Lighting sp. z o.o., ul. Budowlanych 31, 80-298 Gdańsk,

More information

Manual Power relay SR853

Manual Power relay SR853 Manual Power relay SR853 Product types SR853.8.x.x, Rev. 1 SR853 manual page2 The symbols WARNING, CAUTION, NOTE This symbol warns of a serious hazard. Failure to observe this warning may result in death

More information

Manual. WAGO-I/O-SYSTEM 750 Use in Hazardous Environments 750-xxx Definition of Terms, Marking and Installation Regulations. Version 1.0.

Manual. WAGO-I/O-SYSTEM 750 Use in Hazardous Environments 750-xxx Definition of Terms, Marking and Installation Regulations. Version 1.0. WAGO-I/O-SYSTEM 750 Use in Hazardous Environments 750-xxx Definition of Terms, Marking and Installation Regulations 2 General WAGO-I/O-SYSTEM 750 General 2010 by WAGO Kontakttechnik GmbH & Co. KG All rights

More information

Training, Assessment, Consultants for Hazardous & Industrial Areas

Training, Assessment, Consultants for Hazardous & Industrial Areas Training, Assessment, Consultants for Hazardous & Industrial Areas EPIT provides specialist training, assessment and consultancy services for engineers working in hazardous and industrial environments.

More information

manual addendum DELPHI Ex

manual addendum DELPHI Ex manual addendum DELPHI Ex II 2G Ex eb IIC T4 Gb II 2D Ex tb IIIC T135 C IP65 Db Tamb=-20 +40 C Reference list: Norm (last issue) Title Dir. 2014/34/UE EN 60079-31 EN60079-0 EN60079-7 Equipment and Protective

More information