4100 Programming Instructions-Ver. 8.01

Size: px
Start display at page:

Download "4100 Programming Instructions-Ver. 8.01"

Transcription

1 4100 Programming Instructions-Ver Rev. A

2 Table of Contents INTRODUCTION TO 4100 PROGRAMMER VERSION Introduction... 1 Related Documentation... 1 INSTALLATION Programmer... 2 SERIAL DIGITAL ALARM COMMUNICATOR TRANSMITTER (SDACT)... 3 SDACT... 3 SDACT Programmer... 3 Adding the SDACT... 3 SDACT Event Reporting... 5 VERY EARLY SMOKE DETECTION APPARATUS (VESDA) INTERFACE... 6 VESDA... 6 VESDA Interface... 6 Adding a VESDA Peripheral... 7 VESDA Configuration MA ZAM (AMZ) mA ZAM (AMZ) Configuring 4-20mA ZAM Point Types Adding a 4-20mA ZAM NEW POINT TYPES Style-C Monitor Supervisory Duct Detector Priority 2 with Open Circuit Trouble Generic Normally Open Fire/Supervisory COMPUTER PORT PROTOCOL SHOW Command LIST Command PRINT Command TYPE Command SELECT Command CLEAR Command WALKTEST Command Command Error Codes CUSTOM CONTROL EXAMPLES mA ZAM Custom Control VESDA Custom Control INDEX i

3 Copyrights & Trademarks Copyright Simplex Time Recorder Co All rights reserved. Printed in the United States of America. Information in this document is subject to change without notice. No part of this document may be reproduced or transmitted in any form or by any means, electronic or mechanical, for any purpose, without the express written consent of Simplex Time Recorder Company. MAPNET II Communication Net is protected by US Patent No. 4,796,025. TrueAlarm Analog Detection is protected by US Patent No. 5,155,468. TrueAlarm Detector Base is protected by US Patent No. 5,173, 683. Windows is a trademark of the Microsoft Corporation. VESDA Scanner and MiniVESDA-50 are trademarks and the name VESDA and VESDA E70-D are registered trademarks of Vision Systems. All other logos are trademarks of their respective companies. Cautions & Warnings SYSTEM REACCEPTANCE TEST AFTER SOFTWARE CHANGES: To ensure proper system operation, this product must be tested in accordance with NFPA , Chapter 7 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair, or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified. ii

4 Introduction to 4100 Programmer Version 8 Introduction This document describes all enhancements in the 4100 Programmer Version 8 software. Some functional enhancements are included briefly, as they are detailed in separate installation instruction manuals. Version 8 supports an interface to the Serial DACT (SDACT), VESDA sensors, the 20mA Monitor ZAM, and new point types. It also enhances the 4100 Computer Port to provide full front panel functionality from a remote location with the exception of enabling a download. Important: When making any change to a 4100 job, you must use the Job Builder to build the job before uploading that job to the 4100 panel. Related Documentation The following is a list of related documentation that you should refer to for additional information. Serial DACT - Installation & Configuration Instructions ma Monitor ZAM - Installation Instructions Custom Control Editor - Programming Instructions.. FA Programming Unit - Pocket Reference... FA /4020/UT - Summary Guide for CRT Operating Commands... FA VESDA Hardware Interface Configuration Instructions VESDA Systems Manual... Accompanies VESDA Equipment 1

5 Installation 4100 Programmer The 4100 Programmer Unit software Version 8 is a DOS-based program. The Programmer Unit software comes on four 720 KB 3.5 diskettes. Follow Steps 1 through 4 to install the 4100 Programmer Unit onto a PC. Note: Please refer to FSB-1008 when installing the 4100 Programmer Unit on an HP Omnibook 5000C laptop computer. 1. Turn your PC on and boot-up to a DOS command line. 2. Insert Disk 1 of the 4100 Programmer Unit software Version 8 into the floppy drive. 3. From the C:\> prompt, type A: and then press Enter. 4. From the A:\> prompt, type install and then press Enter (Figure 1 appears). Figure Programmer Installation Screen Follow the prompts to install all four diskettes. When the installation of the programmer is complete, you can then install any Executive Software (e.g.,, UT, 4020, etc.). When necessary, your Autoexec.bat and Config.sys files may need specific changes in order for the 4100 Programmer to work properly. The installation program can make these changes for you when you answer Yes at the appropriate prompt. 2

6 Serial Digital Alarm Communicator Transmitter (SDACT) SDACT The SDACT allows per-point reporting of alarm and trouble conditions to a central station via the public telephone network. This device is a new 4100-family slave card and uses internal Serial communication to communicate with the host panel. To use the SDACT, you must have Version 8 of the 4100 Programmer Unit and Master software. SDACT Programmer The SDACT comes with its own programmer software. Refer to the SDACT - Installation Instructions ( ) for more information. The SDACT software is Windows-based and is used independently of the 4100 Programmer. Although most of the programming of the SDACT is done from its own programmer, you must use the 4100 Programmer Version 8 to add an SDACT to a This section describes how to add an SDACT to a Adding the SDACT The SDACT is configured in the 4100 Programmer as an Interface card type (similar to an RS232, Mapnet, etc.). Data entry for the card is also similar to the RS232 with certain limitations. The SDACT consumes one of the five available RS232 ports in the 4100 system and one of the CRT/Computer ports. Use Steps 1 through 6 below to add an SDACT to the 4100 Programmer. 1. Boot up the 4100 Programmer on your PC. 2. Create a new job or load a specific job from the Utilities menu. 3. After the job is successfully loaded, use the arrow keys to select the Configuration menu and press Enter (see Figure 2). Figure 2. System Configuration Menu Continued on next page 3

7 Serial Digital Alarm Communicator Transmitter (SDACT), Continued Adding the SDACT, continued 4. Using the arrow keys, select the System Cards menu and press Enter (see Figure 3). Figure 3. Card Configuration Editor 5. Press the letter A to add a card to the Using the arrow keys, select the Interface menu from the choices at the top of the screen and press Enter (see Figure 4). Figure 4. Add an Interface Card 6. Using the arrow keys, select the Serial DACT Interface option and press Enter. The programmer now requests how many SDACTs you wish to add and whether or not the SDACT is being added locally. Enter the correct response for both of these choices. After adding the SDACT, return to the Utilities menu. Use the arrow keys to select Save Current Job from the Utilities menu and press Enter. Type the appropriate information for saving the file and save the configuration. 4

8 Serial Digital Alarm Communicator Transmitter (SDACT), Continued SDACT Event Reporting You can change the default Event reporting categories to control what information is reported from the 4100 to the SDACT (fire, pri2, supervisory, trouble, etc.). No other programming is required. The default settings are shown in Figure 5. Follow Steps 1 through 5 below to choose those events you wish reported by the 4100 to the SDACT. 1. Using the 4100 Programmer, select the Utilities menu and load the specific job that contains your SDACT. 2. After the job is successfully loaded, use the arrow keys to select the Configuration menu (Figure 2) and press Enter. 3. Using the arrow keys, select the System Cards menu (Figure 3) and press Enter. 4. Using the arrow keys, select Serial DACT Interface from the list of available cards and press Enter (see Figure 5). Figure 5. SDACT Interface Card Data Entry 5. Using the arrow keys, select the Port Annunciation category and use the space bar to toggle the Enabled status of each event you wish reported to the SDACT. After completing the Event Reporting configuration, return to the Utilities menu. Use the arrow keys to select Save Current Job from the Utilities menu and press Enter. Type the appropriate information for saving the file and save the configuration. You can now build your job from the Job builder menu. 5

9 Very Early Smoke Detection Apparatus (VESDA) Interface VESDA The 4100 Programmer (Version 8) provides the ability to program VESDA smoke detectors into the 4100-family systems. This programming provides full alarm reporting capability, logging, annunciation, and display of selected analog information. To use the VESDA interface, you must have the VESDA Gateway at Revision 400 as well as Version 8 of the 4100 Programmer Unit and Master software and Revision 1.01 of the VESDA interface slave. When installing the VESDA interface, please refer to the VESDA Interface - Installation/Operating Procedures ( ). VESDA Interface You must configure the VESDA sensor using the VESDA System Manual before programming the Although part of the configuration is done from the VESDA product, you must use the 4100 Programmer Version 8 to add VESDA devices to a This section describes how to add the VESDA devices (shown in Table 1) to a Two new point types exist in order to support the VESDA devices (shown in Table 2). Table 1. VESDA Devices VSCAN VE70D VMIN50 Device Type Description VESDA Scanner VESDA E70-D MiniVESDA-50 Table 2. VESDA Point Types S3SMOKE S3UTIL Point Type Description Three stage smoke detector Three stage utility monitor 6

10 Very Early Smoke Detection Apparatus (VESDA) Interface, Continued Adding a VESDA Peripheral Each VESDA card type that is added to the 4100 consumes one of the available Mapnet channels. This means that the total number of Mapnet and VESDA cards cannot exceed ten. Use Steps 1 through 6 below to add a VESDA peripheral to the 4100 Programmer. 1. Boot up the 4100 Programmer on your PC. 2. Create a new job or load a specific job from the Utilities menu. 3. After the job is successfully loaded, use the arrow keys to select the Configuration menu and press Enter (see Figure 6). Figure 6. System Configuration Menu 4. Using the arrow keys, select the System Cards menu and press Enter (see Figure 7). Figure 7. Card Configuration Editor Continued on next page 7

11 Very Early Smoke Detection Apparatus (VESDA) Interface, Continued Adding a VESDA Peripheral, (continued) 5. Press the letter A to add a card to the Using the arrow keys, select the Interface menu from the choices at the top of the screen and press Enter (see Figure 8). Figure 8. Card Configuration Editor 6. Using the arrow keys, select the VESDA Interface option and press Enter. The programmer now requests how many VESDAs you wish to add and whether or not the VESDA is being added locally. Enter the correct response for both of these choices. After adding the VESDA, return to the Utilities menu. Use the arrow keys to select Save Current Job from the Utilities menu and press Enter. Type the appropriate information for saving the file and save the configuration. You can now build your job from the Job builder menu. 8

12 Very Early Smoke Detection Apparatus (VESDA) Interface, Continued VESDA Configuration This section describes how to select a device type, point type, and custom label for your VESDA device. Use the following steps to configure a VESDA within a Note: Each VESDA device consumes four MAPNET device addresses. Even though the VESDA Scanner uses all four, the MiniVESDA-50 and VESDA E70-D use only one each. 1. After successfully loading a job, select the Configuration menu and select System Cards. 2. Scroll through the available cards and choose the VESDA Interface. Once the VESDA Interface is highlighted, press E to edit the configuration (see Figure 9). Figure 9. VESDA Interface Card Data Entry 3. Using the arrow keys, move the highlight field in the Dev-Type column to the appropriate Mapnet address (e.g., M1-1). Press F2 for a list of allowable device types (shown in Table 1). 4. Choose the device type that matches the VESDA unit that is installed from the list of allowable types. The 4100 Programmer automatically fills in the Point Type column for you. If this is not the desired point type for the device chosen, use the arrow keys to highlight the Point Type field for that address and press F2. Select your desired point type (shown in Table 2) and press Enter. 5. Press Tab to move the highlight field to the Custom Label column. In this field you can add or edit a label for the point. You can use up to 40 alphanumeric characters for your label. All letters appear in uppercase. 9

13 4-20mA ZAM (AMZ) 4-20mA ZAM (AMZ) The 4-20mA ZAM (AMZ) is supported as a new Mapnet device in 4100 Version 8. This device allows monitoring of various third party sensors including toxic, flammable, and explosive gas sensors. When adding the AMZ, the 4100 Master/Programmer must be at Version 8 and Revision 6.01 Mapnet firmware must be used. Adding an AMZ to one Mapnet channel does not require upgrading any other Mapnet channels in the same 4100 that do not have AMZs programmed. When installing the AMZ, please refer to MAPNET II 20mA Monitor ZAM - Installation Instructions ( ). Configuring 4-20mA ZAM Point Types Before adding an AMZ to a 4100, you must know the types of devices you wish the AMZ to monitor. In order for the AMZ to operate correctly, the point types for this device are user-definable. In other words, you will define the types of points (CO sensor, flammable gas, etc.) the AMZ monitors. This section describes how to configure several user-defined point types to be used by the 4-20mA ZAM. 1. Boot up the 4100 Programmer on your PC. 2. Create a new job or load a specific job from the Utilities menu. 3. After the job is successfully loaded, use the arrow keys to select the Configuration menu and press Enter (see Figure 10). Figure 10. System Configuration Menu 4. Using the arrow keys, select ANALOG MONITOR POINT TYPES and press Enter (see Figure 11). Continued on next page 10

14 4-20mA ZAM, Continued Configuring 4-20mA ZAM Point Types (continued) Figure 11. Analog Monitor Point Types 5. Press the letter A to add a user-defined point type for the AMZ. There are eight input fields available for your input. These fields are shown in Figure 12. The fields and the type of information each field must possess for the proper configuration of the AMZ point type are listed in Table 3. The 4100 Programmer allows for a maximum of 100 user-defined AMZ point types. Table 3. AMZ Input Fields Input Field Description AMZ Type: This field describes the type of device the AMZ monitors. In Figure 12 the AMZ Type is CO (Carbon Monoxide sensor). Alm Type: This field specifies the type of alarm sent to the 4100 when a specified threshold is crossed. The choices are FIRE, MPRI2 (Priority 2), TROUBLE, LATSUPV (Latching Supervisory), or UTILITY. Eng Unit Text: This field defines the Engineering Unit text that is displayed by the Examples are PPM (Parts Per Million), PPB (Parts Per Billion). Display: This field defines how many places to the left of the decimal you wish to display. For example: XXX. (whole numbers), XXX.X (tenths), or XXX.XX (hundredths). A total of five numbers is allowed with a range of 0 to ma: This is the value, in Engineering Units, you wish to display when the sensor reading is at 4mA. 20 ma: This is the value, in Engineering Units, you wish to display when the sensor reading is at 20mA. Alarm Threshold: Type a Y in this field to indicate you wish a threshold crossing to send an alarm condition (defined in Alm Type above) to the Units: This field indicates the threshold value, in Engineering Units. The 4100 Programmer automatically computes the Milli-amps and Sensor Counts. Continued on next page 11

15 4-20mA ZAM, Continued Configuring a 4-20mA (continued) Important: When choosing one alarm threshold, use Threshold 3 first. When choosing two alarm thresholds, use Threshold 2 as your first choice and Threshold 3 as your second choice. Figure 12. Configuring the Analog Monitor Point Type Adding a 4-20mA ZAM This section describes how to select a device type, point type, and custom label for the 4-20mA ZAM. Use the following steps to add a 4-20mA ZAM to a Important: You must use the steps in the Configuring a 4-20mA ZAM section of this publication before you can add a 4-20mA ZAM to the Refer to the 4100 Front Panel Operation Addendum ( ) to program the calibration date in the 4100 for all devices. 1. Boot up the 4100 Programmer on your PC. 2. Create a new job or load a specific job from the Utilities menu. 3. After the job is successfully loaded, use the arrow keys to select the Configuration menu and press Enter. 4. Using the arrow keys, select the System Cards menu and press Enter (see Figure 13). Continued on next page 12

16 4-20mA ZAM, Continued Adding a 4-20mA ZAM (continued) Figure 13. Card Configuration Editor 5. Press the letter A to add a card to the Using the arrow keys, select the Interface menu from the choices at the top of the screen and press Enter (see Figure 14). Figure 14. Add an Interface Card 6. Using the arrow keys, select the MAPNET Interface option and press Enter. The programmer now requests how many Mapnets you wish to add and whether or not the Mapnet is being added locally. Enter the correct response for both of these choices. You now have to edit the Mapnet Interface. 7. Select the Configuration menu and select System Cards. 8. Using the arrow keys, select the MAPNET Interface and press E to edit the selection. Continued on next page 13

17 4-20mA ZAM, Continued Adding a 4-20mA ZAM (continued) 9. With the highlight field in the Dev-Type column, press F2. From the list of allowable types choose ANAMON (see Figure 15). Figure 15. MAPNET Interface Card Data Entry (Dev-Type) 10. Press Enter after choosing the device type. Press Tab to move the highlight field to the Point Type column and press F2 for allowable choices (see Figure 16). Figure 16. MAPNET Interface Card Data Entry (Point Type) 11. Use the arrow keys to select a point type that you have already defined in the Configuring 4-20mA ZAM Point Types section of this publication. After adding the Mapnet Interface, return to the Utilities menu. Use the arrow keys to select Save Current Job from the Utilities menu and press Enter. Type the appropriate information for saving the file and save the configuration. You can now build your job from the Job builder menu. 14

18 Point Types Four new point types are introduced in the 4100 Programmer Version 8. These point types include a Style-C Monitor Point, Supervisory Duct Detector, Priority 2 with Open Circuit Trouble, and a Normally Open Generic Fire/Supervisory point type to connect remote panels. Style-C Monitor The 4100 Version 8 supports a new Style-C fire monitor point. The point type (STYLEC) has a FIRE MONITOR ZONE banner and maps physical states to the logical states shown in Table 4. Table 4. STYLEC Point Type Physical/Logical States Physical State Logical State Status Message Normal Normal NORMAL Abnormal Fire FIRE ALARM Open Circuit Trouble OPEN CKT TROUBLE Short Circuit Trouble SHORT CKT TROUBLE This point type may be programmed on any tri-state monitor point on any eight-zone monitor card. The STYLEC point type is not supported on the 24 I/O or Mapnet cards. The 4100 Programmer auto-generates this point into all lists appropriate for a general fire alarm point (e.g., L18, Walk Test lists, etc.). The Fire state latches until a system reset is performed, but both trouble conditions clear immediately once the zone is restored to normal. Where a physical state of Short Circuit an Alarm is the usual Logical State. With this point type, a Short Circuit has the Logical State of Trouble. Supervisory Duct Detector The supervisory duct detector point type (SDUCT) has a DUCT DETECTOR banner and maps physical states to the logical states shown in Table 5. Table 5. SDUCT Point Type Physical/Logical States Physical State Logical State Status Message Normal Normal NORMAL Abnormal Supervisory ABNORMAL Open Circuit Trouble OPEN CKT TROUBLE Short Circuit Supervisory ABNORMAL This point type may be programmed on any monitor point on eight-zone monitor cards or on Mapnet devices. The supervisory and trouble conditions are nonlatching and clear once the point is returned to normal. 15

19 Point Types, Continued Priority 2 with Open Circuit Trouble Unlike previous Priority 2 (PRI2) points, the Generic Priority 2 (GENPRI2) monitor point is not designed for security applications. Instead, it is designed with more generic applications in mind. This point type has a PRI2 MONITOR banner and maps an open circuit physical state to a logical trouble condition instead of a PRI2 alarm. The physical and logical states are shown in Table 6. Table 6. GENPRI2 Point Type Physical/Logical States Physical State Logical State Status Message Normal Normal NORMAL Abnormal Priority 2 PRI2 ALARM Open Circuit Trouble OPEN CKT TROUBLE Short Circuit Priority 2 PRI2 ALARM This point type may be programmed on any monitor point on eight-zone monitor cards or on Mapnet devices. The Priority 2 alarm state latches until a PRI2 reset is completed but the trouble condition only clears when the point is restored to normal. Generic Normally Open Fire/Supervisory The Generic Normally Open Fire/Supervisory (GENFS) point type performs exactly as Water Flow/Sprinkler Open (WSO) point type but provides a different point type banner and different, more generic status messages. This point type is used to connect a remote panel to a 4100 system with a contact closure output. A supervisory/trouble condition (abnormal state) indicates that the remote panel is in trouble, while an open circuit trouble indicates that the wiring used to connect the two panels has failed. This point type has a FIRE/SUPV MONITOR banner and maps physical and logical states as shown in Table 7. Table 7. GENFS Point Type Physical/Logical States Physical State Logical State Status Message Normal Normal NORMAL Abnormal Supervisory SUPERVISORY\TROUBLE Open Circuit Trouble OPEN CKT TROUBLE Short Circuit Fire FIRE ALARM This point type may be programmed on any tri-state monitor point on any eightzone monitor card. This point type is not supported on the 24 I/O or Mapnet cards. The 4100 Programmer auto-generates this point into the same lists as a WSO point. The fire state latches until the zone is restored to normal and a system reset is performed. The supervisory state clears immediately when the zone is restored to normal. 16

20 Computer Port Protocol The 4100 computer port protocol has several enhancements with the release of Version 8. These enhancements are supplied to permit nearly every operation allowed from the front panel of the These enhancements include viewing and clearing of the historical logs, network diagnostic capability, Walk Test, etc. These enhancements require Version 8 of the master/programmer software and Revision 2.01 or later of the RS232 Interface firmware. When referring to commands, the asterisk (*) is a marker of the minimum amount of characters needed to execute a command. For example, SH*OW. The letters SH are the only characters required for the command to be recognized. If any form of the command line ends with a "/P", and the output is greater than what can fit on one screen, the display stops with the screen full and prompts you to "Press Return For More Output. While paused, unsolicited output is frozen. A time delay allows the screen to be paused for no more than 30 seconds. Unsolicited output is allowed only after the command has completed all output applicable. Without the "/P", text will scroll off the screen when screen fills up. SHOW Command The SHOW command has two different input formats: SHOW <point> and SHOW <keyword>. SHOW Point This command followed by a point ID is the equivalent of using the FUNCTION button on the front panel. It is a way of outputting to the computer port information about a point other than just the point s status. The SHOW <point> form has only one input format, but the output format changes depending on the point category. A sample output is shown below. Input Format: SH*OW <point><cr> where <point> is a standard point ID in either zone or address format. Example: SHOW ZN1<CR> MONITOR ZONE CUSTOM LABEL ZN1 PULL STATION POINT ADDRESS: ZONE CLASS B MONITOR CARD Local Unit - Main Panel Continued on next page 17

21 Computer Port Protocol, Continued SHOW Command (continued) UNIT NUMBER: 0 RUI NUMBER: LOCAL PRIMARY STATUS ALARM PHYSICAL STATE SHORT RAW STATE SHORT ACTIVE STATE ON ARMED STATE ARMED ENABLED STATE ENABLED UNVERIFIED 0 SHOW Keyword The SHOW command followed by a valid keyword outputs information to the computer port appropriate to the keyword. The keywords are listed below. PORTS - Outputs a list of all ports configured and their device types. When no ports are present, a No Ports Configured message is returned. TOPOLOGY - Identical to the loop topology line of the DIAGNOSTIC command without an argument. If there are no nodes, a No network card configured message is returned. NODES - Outputs a listing of all nodes in the network showing the node number, node name, and the online status of the node. COUNTS - Outputs the totals of off-normal conditions for the system lists. CARDS - Outputs a list of all cards configured at the node. 18

22 Computer Port Protocol, Continued LIST Command This command returns the current logical point status for the point requested in an easy-to-read format. The output format is a single line per reported status formatted as follows: ZONE, CUSTOM LABEL, POINT BANNER, STATUS. If ACK is needed, the STATUS is followed by an asterisk. The four methods of input for the LIST command are shown below. L*IST <point> - This command followed by only a point ID outputs one line for each abnormal/on status for the point. L*IST <point> [qualifier] - This command followed by both a point ID and a qualifier outputs only one line for the status described by the qualifier. The following is a list of qualifiers. A - Primary F - Fire P - Pri2 S - Supervisory T - Trouble U - Utility C - Control D - Disable trouble L*IST [qualifier]- This command followed immediately by a qualifier outputs one line for each point in the abnormal/on state described by the qualifier. Note: LIST A<CR> is not allowed. L*IST <CR> - This command followed only by <CR> outputs one line for each abnormal/on status for each point in the system. PRINT Command This command causes reports to be output via the currently selected reports printer in the same manner as is now possible via the front panel or the CRT menus. The reports are as follows: ALOG - Sends the Alarm Historical Log to the currently selected printer. TLOG - Sends the Trouble Historical Log to the currently selected printer. TASTAT*US - Sends the TrueAlarm Status Report to the currently selected printer. TASERV*ICE - Sends the TrueAlarm Service Report to the currently selected printer. Note: See the SELECT command to change the currently selected report printer. Continued on next page 19

23 Computer Port Protocol, Continued TYPE Command This command causes reports to be output via the currently selected reports printer in the same manner as is now possible via the front panel or the CRT menus. The reports are as follows: ALOG - Sends the Alarm Historical Log to the currently selected printer. TLOG - Sends the Trouble Historical Log to the currently selected printer. TASTAT*US - Sends the TrueAlarm Status Report to the currently selected printer. TASERV*ICE - Sends the TrueAlarm Service Report to the currently selected printer. This command stops at the end of each page of text automatically and prompts you for further instructions from the CRT menus. SELECT Command This command allows you to select a report printer. Typing "SELECT" by itself returns a list of printers available each with its device type. If no printers are configured, the message "No printers configured" is returned. The currently selected report printer is denoted by an asterisk. Typing "SELECT" followed by a number from 1 to 5 changes the currently selected printer to the port number chosen. If an invalid port number is typed, an error message is returned. CLEAR Command This command clears the Alarm Historical Log or the Trouble Historical Log depending on the argument passed. In order to execute this command, it is necessary to be logged in. An access level of 3 is required by default, but can be changed by the programmer. If an error occurs on the input line, an appropriate error message is returned. CLEAR ALOG - CLEAR TLOG - Clears the Alarm Historical Log. Clears the Trouble Historical Log. CLEAR TALLY <point identification> - Clears the Alarm Verification Tally for the point specified. CLEAR PEAK <point identification> - Clears the Peak Analog Value for the point specified. Continued on next page 20

24 Computer Port Protocol, Continued WALKTEST Command This command initiates or stops Walk Test. The command must be followed by <arg1> (arg1 is the Walk Test group number) after which up to four qualifiers can be passed in the command line in any order. The qualifiers are listed in Table 7. Typing "WALKTEST" followed by a number returns the current Walk Test status for the group specified. If an invalid group number is entered, an appropriate error message is returned. If any qualifier is omitted in the command line, the current value remains in effect. Qualifiers are evaluated from left to right. If conflicting qualifiers are input, the right most qualifier is the one remaining in effect. Table 7. Walk Test Qualifiers Qualifier ON OFF LOG NOLOG ZONE ZERO SIG NOSIG Description Initiates Walk Test Terminates Walk Test Causes Walk Test events to be logged Terminates Walk Test event logging Enables zone / disables zero coding during Walk Test Enables zero / disables zone coding during Walk Test Enables audible signal during Walk Test Disables signal during Walk Test Example: WALK 1 ON<CR> initiates Walk Test on group 1. Command Error Codes When issuing commands to the computer port, error conditions may exist that cause an error message to be returned. The following is a list of these error messages: %ERROR 1: Invalid command syntax %ERROR 2: Invalid point %ERROR 3: Operation invalid for point %ERROR 4: Qualifier invalid for point %ERROR 5: Insufficient access level %ERROR 6: Insufficient port priority %ERROR 7: Report printer in trouble %ERROR 8: Report queue is full %ERROR 9: No printers configured in the system %ERROR 10: Reports generator is busy - try again later %ERROR 11: Node not configured %ERROR 12: Can not send messages to self %ERROR 13: Invalid Walk Test group %ERROR 14: Unable to Enter Walk Test - Alarms present %ERROR 15: No Walk Test points configured %ERROR 16: No Network Card Configured 21

25 Custom Control Examples This section shows Custom Control programming examples for the 4-20mA ZAM and the VESDA devices. These are common applications to be used as reference only. 4-20mA ZAM Custom Control The following Custom Control input qualifiers are applicable to the AMZ points: ON FIRE DISABLE TROUBLE TBLACK FIRE ALARM ACK DETECT SUPV SUPVACK PRIORITY 2 ALARM PRI2 ALARM ACK PRI2 ALARM DETECT Note: The DETECT status is true only for the initial alarm brought in for each AMZ point. It is not true for each time the AMZ reaches an alarm threshold. ANALOG VALUE The value in engineering units of the AMZ point may be used as input to custom control equations. The full range of qualifiers may be used; 'equal to', 'not equal to', 'greater than', 'greater than or equal to', 'less than', and 'less than or equal to'. Example: COMMENTS: [END-OF-COMMENTS] INPUTS: If AMZ: M1-1 is greater than value: 15 ppm [END-OF-INPUTS] OUTPUTS: TRACK points ON pri=9,9 P256 UTILITY [END-OF-OUTPUTS] END: Continued on next page 22

26 Custom Control Examples, Continued 4-20mA ZAM Custom Control (continued) AMZ THRESHOLD With Version 8 a new Custom Control input qualifier for AMZ points exists. It is called 'AMZ THRESHOLD'. It is used in the same manner as 'SMOKE LEVEL' is used today, except user defined levels are assigned to the AMZ points. Following is an example of a Custom Control equation using the AMZ threshold as an input: COMMENTS: [END-OF-COMMENTS] INPUTS: The AMZ THRESHOLD at or above THRESHOLD 1 of: M1-X USRDEF CUSTOM LABEL [END-OF-INPUTS] OUTPUTS: TRACK points ON pri=9,9 P256 UTILITY [END-OF-OUTPUTS] END: LED MODES There are no new LED modes for the AMZ points. Many of the existing LED modes are applicable for these points. If it is desired to track the level of the AMZ point through LEDs, Custom Control can be written to have a pseudo track the desired level, and have the LED track the pseudo. The following LED modes are applicable to AMZ points: ON, OFF, FIRE, PRI2ALM, P2ALERT, SUPERV, SALERT, PALERT, TROUBLE, TALERT, and DISABLE. SWITCH MODES The only switch modes that are valid for the AMZ points are 'DE', (Disable/Enable), 'TDE', (Toggle Disable/Enable), and switch modes that control the LED. Note: When an AMZ point is disabled, no 'SENSOR TROUBLE' will come in from the device, (for example, the sensor is being calibrated), and power is not removed from the device. Continued on next page 23

27 Custom Control Examples, Continued 4-20mA ZAM Custom Control (continued) A PROGRAMMING EXAMPLE Some sensors have an analog range denoting discrete occurrences. For instance, a flame detector may report a trouble by sending a value of 5 ma, a detection of infrared by a value of 10 ma, detection of UV by a value of 15 ma, and a detection of infrared and UV by a value of 20 ma. Custom programming would be required to use this sensor to its full capacity. 1. Several pseudo points are defined as shown in Figure 17. Figure 17. Digital Pseudo Card Data Entry Screen 2. The AMZ ZAM is programmed as shown in Figure 18 and 19. Figure 18. Analog Monitor Point Types Screen Continued on next page 24

28 Custom Control Examples, Continued 4-20mA ZAM Custom Control (continued) Figure 19. MAPNET Interface Card Data Entry Screen 3. Custom Control is written to bring the pseudos at the correct time under the correct events. TROUBLE DETECTION CUSTOM CONTROL COMMENTS: TROUBLE DETECTION [END-OF-COMMENTS] INPUTS: If AMZ: M1-1 is greater than value: 4 ma AND If AMZ: M1-1 is less than value: 7 ma [END-OF-INPUTS] OUTPUTS: TRACK points ON pri=9,9 P256 TROUBLE [END-OF-OUTPUTS] END: Continued on next page 25

29 Custom Control Examples, Continued 4-20mA ZAM Custom Control (continued) INFRARED DETECTION CUSTOM CONTROL COMMENTS: INFRARED DETECTION [END-OF-COMMENTS] INPUTS: If AMZ: M1-1 is greater than value: 7 ma AND If AMZ: M1-1 is less than value: 12 ma [END-OF-INPUTS] OUTPUTS: TRACK points ON pri=9,9 P257 FIRE [END-OF-OUTPUTS] END: UV DETECTION CUSTOM CONTROL COMMENTS: UV DETECTION [END-OF-COMMENTS] INPUTS: If AMZ: M1-1 is greater than value: 12 ma AND If AMZ: M1-1 is less than value: 17 ma [END-OF-INPUTS] OUTPUTS: TRACK points ON pri=9,9 P258 TROUBLE [END-OF-OUTPUTS] END: INFRARED AND UV DETECTION CUSTOM CONTROL COMMENTS: INFRARED AND UV DETECTION [END-OF-COMMENTS] INPUTS: If AMZ: M1-1 is greater than value: 17 ma [END-OF-INPUTS] OUTPUTS: TRACK points ON pri=9,9 P259 TROUBLE [END-OF-OUTPUTS] END: 26

30 Custom Control Examples, Continued VESDA Custom Control This section contains some sample Custom Control equations that could help provide some flexibility in configuring the VESDA devices within the Two issues are addressed. Customizing logical states associated with the alert, action and fire states of the VESDA detector Providing a redundant detection system without having to annunciate duplicate alarm conditions CUSTOMIZED LOGICAL STATES In order to provide customized logical states for a VESDA device, the following steps must be taken. 1. Configure device with a point type of S3UTIL 2. Reserve three digital pseudo points and configure them to provide the desired logical state 3. Write custom control equation(s) to turn on the pseudo points when the appropriate VESDA device thresholds are crossed Example An application requires the alert, action, and fire thresholds of a VESDA device to map to Supervisory, Priority 2 alarm, and Fire alarm respectively. Assume the VESDA device is addressed as M Configure M1-1 with point type S3UTIL. 2. Reserve three digital pseudo points (P256, P257, P258 for this example). P256 is configured as supervisory P257 is configured as priority 2 P258 is configured as fire 3. Provide descriptive custom labels that tie the pseudos back to the VESDA detector being customized. 4. Write three custom control equations (shown below) so the pseudos track the logical state of the VESDA device and cause Supervisory, Priority 2 and Fire conditions when appropriate. 5. Insert the three digital pseudos into L73 (CONTROL POINTS OFF - ON SYSTEM RESET) so that the points turn off on a successful system reset. Continued on next page 27

31 Custom Control Examples, Continued VESDA Custom Control (continued) COMMENTS: VESDA STAGE 1 ALARM [END-OF-COMMENTS] INPUTS: STAGE 1 ALARM M1-1 [END-OF-INPUTS] OUTPUTS: HOLD points ON PRI= 9,9 P256 SUPV [END-OF-OUTPUTS] END: COMMENTS: VESDA STAGE 2 ALARM [END-OF-COMMENTS] INPUTS: STAGE 2 ALARM M1-1 [END-OF-INPUTS] OUTPUTS: HOLD points ON PRI= 9,9 P257 PRI2 [END-OF-OUTPUTS] END: COMMENTS: VESDA STAGE 3 ALARM [END-OF-COMMENTS] INPUTS: STAGE 3 ALARM M1-1 [END-OF-INPUTS] OUTPUTS: HOLD points ON PRI= 9,9 P258 FIRE [END-OF-OUTPUTS] END: Continued on next page 28

32 Custom Control Examples, Continued VESDA Custom Control (continued) REDUNDANCY WITHOUT DUPLICATE ALARMS To provide a redundant detection system without creating duplicate alarms in the FACP, follow these steps: 1. Configure the redundant GENIAM device as a utility device. 2. Reserve a digital pseudo to annunciate the abnormal condition when the primary means of alarm detection fails. 3. Write custom control equations to turn on the pseudo points when the primary means of detection fails and a threshold level has been crossed. Example An application requires that a redundant means of alarm detection is present for a VESDA device. Duplicate alarm conditions are not permitted. Assume VESDA device is addressed as M1-1 and the GENIAM device is addressed as M Configure M1-1 with point type S3MOKE. 2. Configure M2-1 with point type UTILITY (device is monitoring the fire threshold only). 3. Reserve a digital pseudo point (P256 for this example). 4. P256 is configured as fire. 5. Provide a descriptive custom label that ties the pseudo back to the VESDA detector being backed up with redundant system. 6. Write a custom control equation so the pseudo tracks the logical state of the VESDA device only when the primary means of detection is lost. COMMENTS: REDUNDANT VESDA [END-OF-COMMENTS] INPUTS: ON state of M2-1 AND NOT ON of M1-1 DELAY 5 [END-OF-INPUTS] OUTPUTS: TRACK ON PRI= 9,9 P256 FIRE [END-OF-OUTPUTS] END: 29

33 Index A Add an Interface Card 4 Adding a 4-20mA ZAM 12 Adding the SDACT 3 AMZ 10, 11, 22, 23, 24, 25, 26 Analog Value 22 ANAMON Point type 14 C Card Configuration Editor 4 CLEAR Command 20 Command Error Codes 21 Computer Port 1, 17, 18, 19, 20, 21 Customized Logical States 27 R Redundancy without Duplicate Alarms 29 S SDACT Interface Card Data Entry 5 SDACT Programmer 3 SDUCT 15 SELECT Command 20 Serial DACT 1, 4, 5 SHOW Command 17, 18 STYLEC Point Type 15 Switch Modes 23 System Configuration Menu 3 G GENFS Point Type 16 GENPRI2 Point Type 16 I Infrared and UV Detection Custom Control 26 Infrared Detection Custom Control 26 L LED MODES 23 LIST Command 19 P T TYPE Command 20 U UV Detection Custom Control 26 V VESDA 1, 6, 7, 8, 9, 22, 27, 28, 29 VESDA Configuration 9 W WALKTEST Command 21 PRINT Command 19 30

FIRE FIRE. 4100U Fire Alarm. Operator's Manual. Technical Manuals Online! -

FIRE FIRE. 4100U Fire Alarm. Operator's Manual. Technical Manuals Online! - FIRE FIRE 4100U Fire Alarm Operator's Manual 579-197 574-xxx Rev. Rev. B 4 Blank Page- Back of Front Cover Copyrights and Trademarks Copyright Simplex Time Recorder Co., 2001. All rights reserved. Printed

More information

Operator s Manual Part: InfoAlarm Product: 4100U, 4100ES Rev. B

Operator s Manual Part: InfoAlarm Product: 4100U, 4100ES Rev. B Operator s Manual Part: InfoAlarm Product: 4100U, 4100ES 579-685 Rev. B ii iii Cautions and Warnings Cautions and Warnings READ AND SAVE THESE INSTRUCTIONS- Follow the instructions in this installation

More information

Section 9 System Operation

Section 9 System Operation Section 9 System Operation Operation of the control panel is simple. Menus guide you step-by-step through operations. This section of the manual is an overview of the operation menus. Please read this

More information

Section 8 System Operation

Section 8 System Operation Section 8 System Operation Operation of the control panel is simple. Menus guide you step-by-step through operations. This section of the manual is an overview of the operation menus. Please read this

More information

Laptop / PC Programming Manual

Laptop / PC Programming Manual Laptop / PC Programming Manual Doc. # Fire PC Program rev B 01.07 This Document is property of Evax Systems, Inc. The Evax Fire Solutions Programmer Components 2 1.0 System Setup 4 1.1 Interface Setup

More information

Simplex Panel Interface Guide

Simplex Panel Interface Guide Simplex Panel Interface Guide February 2016 SATEON Software Integrations Simplex Panel Interface Guide Issue 1.0, released February 2016 Disclaimer Copyright 2016, Grosvenor Technology. All rights reserved.

More information

TrueAlarm Fire Alarm Systems

TrueAlarm Fire Alarm Systems OPERATOR OPERATOR OR TROUBLE CONDITION: TO : FIRE PRIORITY 2SYSTEM SYSTEM SIGNALS POWER INDICATOR. SUPERVISORYTROUBLE SILENCED ON D. TO SILENCE SIGNALS: - PRESS " SILENCE". SUPV TBL SYSTEM ACK ACK ACK

More information

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide System Reset Trou ble Silence Ala rm Silence Manual Ala rm ENTER NO YES Letters Numb ers Keyword Radionics System Reset Trouble Silence Alarm Silence Manual Alarm ENTER NO YES Le ters Numbers Keyw ord

More information

4010 Fire Alarm PC Programmer Installation and Programming Instructions

4010 Fire Alarm PC Programmer Installation and Programming Instructions 4010 Fire Alarm PC Programmer Installation and Programming Instructions 574-187 Rev. C Copyright and Trademarks Copyright Simplex Time Recorder Co., 2000. All rights reserved. Printed in the United States

More information

Avigilon Control Center System Integration Guide

Avigilon Control Center System Integration Guide Avigilon Control Center System Integration Guide with Gallagher Command Centre INT-CARDAX-C-Rev3 Copyright 2013 Avigilon. All rights reserved. No copying, distribution, publication, modification, or incorporation

More information

DS9400 Series. Release Notes for Firmware V2.07. Fire Alarm Control Panel

DS9400 Series. Release Notes for Firmware V2.07. Fire Alarm Control Panel DS9400 Series EN Release Notes for Firmware V2.07 Fire Alarm Control Panel DS9400 Series Release Notes for Firmware V2.07 Trademarks Trademarks Gentex is a trademark of Gentex Corporation, Fire Protection

More information

Fire Command Keypad. XR5 User s Guide

Fire Command Keypad. XR5 User s Guide Fire Command Keypad XR5 User s Guide Silencing an Alarm While the fire alarm horns, strobes, or sirens are sounding use one of the following methods to silence the alarm depending on which type of keypad

More information

ION Meter Alerts TECHNICAL NOTE NOVEMBER In This Document

ION Meter Alerts TECHNICAL NOTE NOVEMBER In This Document 70072-0125-01 TECHNICAL NOTE NOVEMBER 2006 ION Meter Alerts A PowerLogic ION meter can send alerts to indicate a user specified power system condition such as a power quality problem (including surges,

More information

LifeAlarm Fire Alarm Control Panels

LifeAlarm Fire Alarm Control Panels LifeAlarm Fire Alarm Control Panels UL, ULC Approved* Features Control panel operator convenience features: Wide viewing angle 2 x 20 (40 character) alphanumeric LCD and dedicated LEDs provide convenient

More information

DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION Fike s Cheetah Xi 50 (P/N 10-071) is a state-of-the-art true intelligent digital peer-to-peer modular suppression control system.

More information

Fire Command Center. XR2400F User s Guide

Fire Command Center. XR2400F User s Guide Fire Command Center XR2400F User s Guide Silencing an Alarm While the fire alarm horns, strobes, or sirens are sounding use one of the following methods to silence the alarm. 1. Turn the keyswitch to enable

More information

Watchguard WGAP864 User Manual

Watchguard WGAP864 User Manual Watchguard WGAP864 User Manual v1.0 Issued September 2016 1 2 Table of Contents Glossary... 5 1. Introduction to your Watchguard WGAP864... 6 2. Before Operating your Alarm System... 6 3. Understanding

More information

IDNet and MAPNET II Addressable Devices

IDNet and MAPNET II Addressable Devices Devices Compatible with 4008, 4010, 4010ES, 4100U, & 4100ES IDNet Communications, & MAPNET II Communications Model Description Model Description Listings 4090-9101 Class B IDC ZAM 4098-9791 Sensor Base,

More information

Alarm Monitoring and Management

Alarm Monitoring and Management CHAPTER 10 This chapter describes Cisco Transport Controller (CTC) alarm management. To troubleshoot specific alarms, refer to the Cisco ONS 15310-MA SDH Troubleshooting Guide. Chapter topics include:

More information

R Series Remote Annunciators and Expander Installation and Operation Guide

R Series Remote Annunciators and Expander Installation and Operation Guide GE Security R Series Remote Annunciators and Expander Installation and Operation Guide P/N 3100969 REV 1.0 ISS 15JUL08 Copyright Copyright 2008 GE Security, Inc. All rights reserved. This document may

More information

2) This manual covers Fire and General Alarm systems. The differences are described in the appropriate sections.

2) This manual covers Fire and General Alarm systems. The differences are described in the appropriate sections. ISSUES ISSUE DATE RELEASED DETAILS OF CHANGE AUTHOR 4 Rev 2 September 2004 Changes for 4000 series. DB 4 Rev 3 April 2005 Screen shots updated and other minor changes K.Z. 4 Rev 4 September 2006 4 Rev

More information

4010 Fire Alarm Front Panel Installing, Operating, and Programming Instructions

4010 Fire Alarm Front Panel Installing, Operating, and Programming Instructions 4010 Fire Alarm Front Panel Installing, Operating, and Programming Instructions 574-052 Rev. F This page intentionally blank Copyright and Trademarks Copyright Simplex Time Recorder Co., 2000. All rights

More information

Addendum HART Communication with the X2200 UV Flame Detector 1.1 4/

Addendum HART Communication with the X2200 UV Flame Detector 1.1 4/ Addendum HART Communication with the X2200 UV Flame Detector 1.1 4/09 Table Of Contents Interconnecting the HART Communicator with the Detector.... 1 HART Device Description Language.... 3 Detector Wiring.......................................

More information

Network Display Unit Installation Instructions

Network Display Unit Installation Instructions Network Display Unit Installation Instructions Introduction This publication describes the installation procedures for the optional Network Display Units (NDUs). This product is compatible with both the

More information

Meridian wiredhart. HART Field Device Specification Goldmine Rd. Monroe, NC USA

Meridian wiredhart. HART Field Device Specification Goldmine Rd. Monroe, NC USA HART Field Device Specification Meridian wiredhart 4320 Goldmine Rd. Monroe, NC 28110 USA HART is a registered trademark of the HART Communication Foundation TABLE OF CONTENTS 1. Introduction...5 1.1 Scope...5

More information

Monitoring Operator Guide. Access Control Manager Software Version

Monitoring Operator Guide. Access Control Manager Software Version Monitoring Operator Guide Access Control Manager Software Version 5.10.10 2018, Avigilon Corporation. All rights reserved. AVIGILON, the AVIGILON logo, ACCESS CONTROL MANAGER, ACM, ACM VERIFY AND TRUSTED

More information

PEGAsys. Multi-Loop Intelligent Suppression Control System FEATURES DESCRIPTION. Effective: March 2007 K

PEGAsys. Multi-Loop Intelligent Suppression Control System FEATURES DESCRIPTION. Effective: March 2007 K PEGAsys Multi-Loop Intelligent Suppression Control System A UTC Fire & Security Company Effective: March 2007 K-76-028 FEATURES UL Listed CSFM Approved MEA Approved Peer-to-Peer Networking (to 32 nodes)

More information

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2 Architectural & Engineering Specifications Control Panel 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality assurance...

More information

BlackBerry AtHoc Networked Crisis Communication Siemens Indoor Fire Panel Installation and Configuration Guide Release Version 7.

BlackBerry AtHoc Networked Crisis Communication Siemens Indoor Fire Panel Installation and Configuration Guide Release Version 7. BlackBerry AtHoc Networked Crisis Communication Siemens Indoor Fire Panel Installation and Configuration Guide Release Version 7.3, October 2017 Copyright 2017 BlackBerry Limited. All Rights Reserved.

More information

FieldServer Driver - Serial FS Notifier NCA

FieldServer Driver - Serial FS Notifier NCA Driver Version: 1.00 Document Revision: 15 Description FieldServer Driver - Serial FS-8700-98 Notifier NCA The NCA (Network Control Annunciator) Serial driver allows the FieldServer to record data from

More information

Instruction manual MTL process alarm equipment. October 2016 CSM 725B rev 2 MTL RTK 725B. Configuration Software Manual

Instruction manual MTL process alarm equipment. October 2016 CSM 725B rev 2 MTL RTK 725B. Configuration Software Manual Instruction manual MTL process alarm equipment October 2016 CSM 725B rev 2 MTL RTK 725B Configuration Software Manual SECTION 1 - INTRODUCTION... 5 Basic Requirements... 5 SECTION 2 - SOFTWARE INSTALLATION...

More information

SCAN200E USER S MANUAL

SCAN200E USER S MANUAL SCAN200E USER S MANUAL Code No. 2071 1052 rev. 1.4 Code No. 2071 1052 Rev. 1.4 Page 2/16 SCAN200E User s Manual Foreword This manual is for SCAN200E Controller running software version 2.03 or later. We

More information

Panel Remote Annunciators Installation Instructions

Panel Remote Annunciators Installation Instructions Panel Remote Annunciators Installation Instructions Introduction This publication describes the installation procedures for the following PIDs: 4100-9607 Remote Annunciator w/ Flexible User Interface Domestic

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd Product Data Sheet Mx-4000 Series User Manual MX-4100, MX-4200, MX-4400, Mx-4400/LE & Mx-4800 Fire Alarm Control Panels The operation and functions described in the manual are available from Software Versions

More information

Oracle Communications Performance Intelligence Center

Oracle Communications Performance Intelligence Center Oracle Communications Performance Intelligence Center System Alarms Guide Release 10.2.1 E77506-01 June 2017 1 Oracle Communications Performance Intelligence Center System Alarms Guide, Release 10.2.1

More information

Moxa Proactive Monitoring User s Manual

Moxa Proactive Monitoring User s Manual User s Manual Edition 2, May 2016 www.moxa.com/product 2016 Moxa Inc. All rights reserved. User s Manual The software described in this manual is furnished under a license agreement and may be used only

More information

TrueAlarm Fire Alarm Controls

TrueAlarm Fire Alarm Controls FIRE ALARM ALARMS S DISABLEMENT DISABLED ZONES SITE SPECIFIC PROGRAMMABLE KEYS/LEDS S /DISABLED SILENCED DISABLE/ENABLE S SILENCE/RESOUND SYSTEM PULL DOOR TO OPEN RESET PANEL SILENCE POWER INDICATION OF

More information

OJD ITB No Attachment E Duress Alarm Equipment Specifications

OJD ITB No Attachment E Duress Alarm Equipment Specifications Duress Alarm Equipment Specifications PART 1 GENERAL 1.1 SECTION INCLUDES A. Duress devices. B. Alarm control panel. C. Signaling devices. 1.2 REFERENCE STANDARDS A. NFPA 70 - National Electrical Code;

More information

WeatherLink for Alarm Output Addendum

WeatherLink for Alarm Output Addendum WeatherLink for Alarm Output Addendum Introduction This Streaming Data Logger is designed to provide an electrical interface between a Vantage Pro or Vantage Pro2 weather station console or Weather Envoy

More information

Alarm Monitoring and Management

Alarm Monitoring and Management 14 CHAPTER This chapter explains how to manage alarms with Cisco Transport Controller (CTC). To troubleshoot specific alarms, refer to the Cisco ONS 15454 SDH Troubleshooting Guide. Chapter topics include:

More information

Software Release M2.7 Summary for the Notifier AM2020/AFP1010 Fire / Security Control Panels, Including NOTI FIRE NET and Peripherals

Software Release M2.7 Summary for the Notifier AM2020/AFP1010 Fire / Security Control Panels, Including NOTI FIRE NET and Peripherals 12 Clintonville Road Northford, CT 0642-1610 203-484-161 FAX: 203-484-118 Software Release M2. Summary for the Notifier AM2020/AFP1010 Fire / Security Control Panels, Including NOTI FIRE NET and Peripherals

More information

725B Configuration Software Manual

725B Configuration Software Manual 725B Configuration Software Manual REV DATED DESCRIPTION AUTHOR APPROVED 0 09-03-10 First Issue P.Cartmell Page 1 of 80 SECTION 1 - SOFTWARE INSTALLATION... 5 725B ConfigurationSoftware Installation...

More information

Avigilon Control Center 5 System Integration Guide

Avigilon Control Center 5 System Integration Guide Avigilon Control Center 5 System Integration Guide for Paxton Net2 Access Control Systems 2014 Avigilon Corporation. All rights reserved. Unless expressly granted in writing, no license is granted with

More information

Table of Contents. Appendix A Special Characters 31

Table of Contents. Appendix A Special Characters 31 Table of Contents Introduction 2 Section 1: General System Operation 3 1.1 Getting to Know Your System... 3 1.2 How to Arm... 4 1.3 Alternate Arming Methods... 5 1.4 Disarming... 6 1.5 Alarm Memory...

More information

Operation Manual Fighter ProVision Software. Version: 0.0 Revision: 1

Operation Manual Fighter ProVision Software. Version: 0.0 Revision: 1 Operation Manual Fighter ProVision Software Version: 0.0 Revision: 1 TABLE OF CONTENTS 1. Introduction 5 2. Software Installation 5 3. PC Users 6 3.1 Introduction 6 3.2 Default Code 6 3.3 Edit PC User

More information

Xtralis VESDA LCD Programmer Quick Reference Guide

Xtralis VESDA LCD Programmer Quick Reference Guide Xtralis VESDA LCD Programmer Quick Guide Xtralis VESDA VLP Xtralis VESDA VLS Xtralis VESDA VLC Scope of this Manual This manual is to be used as a quick reference guide to perform the initial detector

More information

LineGuard 2300 Program User Manual (FloBoss 107)

LineGuard 2300 Program User Manual (FloBoss 107) Form A6251 Part Number D301346X012 November 2012 LineGuard 2300 Program User Manual (FloBoss 107) Remote Automation Solutions Revision Tracking Sheet November 2012 This manual may be revised periodically

More information

Control/Communicator

Control/Communicator Architectural & Engineering Specifications Control/Communicator 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality

More information

UAS 7000 Local Management

UAS 7000 Local Management Issue 2, October 1998 Operation UAS 7000 Local Management Includes Support for: UAS 7001 NIU UAS 7002 NIU UAS 7616 DIU UAS 7616M DIU UAS 7626 DIU General DataComm, Inc. Preface iii Local Management Access...

More information

OPERATOR S MANUAL MR-2100/2200. Fire Alarm Control Unit. Revision 0 Document #: LT-2002

OPERATOR S MANUAL MR-2100/2200. Fire Alarm Control Unit. Revision 0 Document #: LT-2002 MR-2100/2200 Fire Alarm Control Unit OPERATOR S MANUAL Revision 0 Document #: LT-2002 WARNING: This manual contains information on limitations regarding product use and function and information on the

More information

User s Guide. SUB-MA7240O-0001.OG.Solution doc. Created: 6/05/03. Last Updated: 23/09/03. MA7240AO-0001 Version 1.0

User s Guide. SUB-MA7240O-0001.OG.Solution doc. Created: 6/05/03. Last Updated: 23/09/03. MA7240AO-0001 Version 1.0 User s Guide SUB-MA7240O-0001.OG.Solution40-111.doc Created: 6/05/03 Last Updated: 23/09/03 MA7240AO-0001 Version 1.0 2 Table Of Contents User List...6 Quick Reference..7 Features...7 Keypad User's Guide...8

More information

Fire System Objects. Introduction Page *3. Engineering *17. Data Base Generation *43

Fire System Objects. Introduction Page *3. Engineering *17. Data Base Generation *43 Metasys etwork Technical Manual 636 Objects Section Technical Bulletin Issue Date 696 Fire System Objects Introduction Page *3 Description *3 Purpose *5 Capabilities *7 Functional Diagram *1 Operator Interface

More information

DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION Fike s CyberCat 254 (P/N 10-066) is a state-of-the-art true intelligent digital peer-to-peer modular fire alarm control system.

More information

USER MANUAL FOR OPERATING SYSTEM

USER MANUAL FOR OPERATING SYSTEM P2262 ALARM PANEL USER MANUAL FOR OPERATING SYSTEM 21765-07 September 1999 Associated Controls (Aust) PTY. LTD. 29 Smith Street, Hillsdale, NSW, 2036. PH (02) 9311 3255, FAX (02) 9311 3779 Page 1 of 177

More information

Security System. User s Guide for the Text Command Center

Security System. User s Guide for the Text Command Center User s Guide for the Text Command Center MY ALARM COMPANY IS: CALL BEFORE TEST: THIS SECURITY SYSTEM IS CONNECTED TO TELEPHONE NUMBER: THE SECURITY CONTROL PANEL IS CONNECTED TO THE PHONE JACK LOCATED:

More information

Security System. User Guide for the LED Command Center

Security System. User Guide for the LED Command Center Security System User Guide for the LED Command Center National Security Systems Inc (800)457-1999 MY SECURITY COMPANY IS: CALL BEFORE TEST: THIS SECURITY SYSTEM IS CONNECTED TO TELEPHONE NUMBER: THE SECURITY

More information

2000 Series. Program Entry Guide. Control Panels

2000 Series. Program Entry Guide. Control Panels 2000 Series EN Program Entry Guide Control Panels 2000 Series Program Entry Guide About This Manual EN 2 About This Manual This guide describes the programming parameters available to the 2000 Series Control

More information

Milestone SMI Intrepid II Perimeter Module 1.1 User s Manual

Milestone SMI Intrepid II Perimeter Module 1.1 User s Manual Milestone SMI Intrepid II Perimeter Module 1.1 User s Manual Target Audience for this Document This document is aimed at system users and provides descriptions on how to install and maintain the Milestone

More information

Network Hardware and wiring (quiz)...

Network Hardware and wiring (quiz)... 4120 Network/TSW (FA049) Course Agenda Day 1 Course Introduction (Presentation)... 8:00 am to 8:30 am Break Module 1 Installing and Configuring Network Software Applications 4120 New Network Programmer

More information

Avigilon Control Center System Integration Guide

Avigilon Control Center System Integration Guide Avigilon Control Center System Integration Guide with Gallagher Command Centre INT-CARDAX-C-Rev2 Copyright 2011 Avigilon. All rights reserved. No copying, distribution, publication, modification, or incorporation

More information

FlameGard 5 UV/IR HART

FlameGard 5 UV/IR HART FlameGard 5 UV/IR HART HART Communication Manual The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically authorized

More information

CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM

CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION Fike s Cheetah Xi (P/N 10-068) is a state-of-the-art true intelligent digital peer-topeer modular suppression control system. It is ideal for

More information

2000 SERIES DIAGNOSTIC ALARM CONTROL SYSTEM

2000 SERIES DIAGNOSTIC ALARM CONTROL SYSTEM 2000 SERIES DIAGNOSTIC ALARM CONTROL SYSTEM OPERATING INSTRUCTIONS MODELS: 2300 2500 2700 This information is relevant to systems fitted with Issue 4.1 (or later) Master Keypad Software, also to Networked

More information

Fire Alarm Network Reference

Fire Alarm Network Reference Fire Alarm Network Reference Network Overview with Applications Reference Features Network communications among system fire alarm control panels provides: Support for up to 99 nodes per Network Loop to

More information

User s Manual. YTA110, YTA310, YTA320, and YTA710 Temperature Transmitters. Manual Change No

User s Manual. YTA110, YTA310, YTA320, and YTA710 Temperature Transmitters. Manual Change No User s Manual YTA110, YTA310, YTA320, and YTA710 Temperature Transmitters Manual Change No. 16-045 Please use this manual change for the manuals listed below. 1. Applicable manuals, revised item, revised

More information

Advisor Advanced Mobile Application User Manual

Advisor Advanced Mobile Application User Manual Advisor Advanced Mobile Application User Manual Content Warnings and Disclaimers 2 Advanced Mobile 2 Contact information 2 Description 2 Screen navigation 4 Gestures 4 Menu 4 Help navigation 4 Login 5

More information

4010 Fire Alarm Applications Manual

4010 Fire Alarm Applications Manual 4010 Fire Alarm Applications Manual 574-908 Rev. A Copyright and Trademarks Copyright Simplex Time Recorder Co., 1999. All rights reserved. Printed in the United States of America. Information in this

More information

MicroTech Series 200 Centrifugal Chiller

MicroTech Series 200 Centrifugal Chiller Protocol Data Information Packet Version 2.2 Group: Controls Date: March 1999 MicroTech Series 200 Centrifugal Chiller Data Communications Packet for Protocol 2002 McQuay International Revision History

More information

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

ZX1e ZX2e ZX5e. Document No Issue 01 user manual ZX1e ZX2e ZX5e Document No. 996-130 Issue 01 user manual MORLEY-IAS ZX2E/ZX5E Fire Alarm Control Panels Table of Contents 1 INTRODUCTION... 4 1.1 NOTICE... 4 1.2 WARNINGS AND CAUTIONS... 4 1.3 NATIONAL

More information

HERCULES 6 GRAPHICS SYSTEM

HERCULES 6 GRAPHICS SYSTEM HERCULES 6 GRAPHICS SYSTEM USER MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273 Web: www.protec.co.uk

More information

4100U City and Relay Cards Installation Instructions

4100U City and Relay Cards Installation Instructions 4100U City and Relay Cards Installation Instructions Introduction This publication describes the installation procedure for the following: 4100-6031/6032 City Circuit Cards 4100-6033 Alarm Relay Card Inspecting

More information

FlameGard 5 MSIR HART

FlameGard 5 MSIR HART FlameGard 5 MSIR HART Multi-Spectral Infrared Flame Detector HART Communication with the FlameGard 5 Multi-spectral Infrared Detector The information and technical data disclosed in this document may be

More information

System Galaxy Quick Guide

System Galaxy Quick Guide System Galaxy Quick Guide CONFIGURATION AND OPERATION Integrating CCTV with System Galaxy JAN 2019 SG 11.1.0.2 System Galaxy Quick Guide For CCTV Integration Configuration & Operation Information in this

More information

Multi-Point Peripherals

Multi-Point Peripherals UL, ULC Approved* Multi-Point Peripherals TrueAlarm CO Sensor Bases for Smoke, Heat, and Photo/Heat Sensors using IDNet Communications Features Fig 1: TrueAlarm CO Sensor Base with Sounder (shown with

More information

ZITON RADIO LOOP MODULE

ZITON RADIO LOOP MODULE ZITON RADIO LOOP MODULE PROGRAMMING MANUAL Table of Contents Section Page No 1.0 INTRODUCTION...3 1.1 System Design...3 1.2 Handling Precautions...3 1.3 Packaging:...3 2.0 MENU STRUCTURE...4 2.1 Menu Structure

More information

D1255RB/D1256RB/D1257RB

D1255RB/D1256RB/D1257RB D1255RB/D1256RB/D1257RB EN Installation Instructions Fire Keypads and Fire Alarm Annunciator D1255RB/D1256RB/D1257RB Installation Instructions Listings and Approvals Listings and Approvals UL 365 UL 609

More information

MMX TM. Intelligent Fire Alarm Network. User Guide

MMX TM. Intelligent Fire Alarm Network. User Guide MMX TM Intelligent Fire Alarm Network User Guide LT-893SEC Rev 1 May 2017 MMX TM User Guide Table of Contents Introduction... 1 About this Manual... 1 Front Panel Indicators, Controls, and Operation...

More information

P2267 NETWORK INTERFACE

P2267 NETWORK INTERFACE P2267 NETWORK INTERFACE USER MANUAL FOR OPERATING SYSTEMS: 22031-03 23636-01 October 2009 Associated Controls (Australia) Pty. Limited 2-4 Norfolk Road Greenacre, NSW, 2190. PH +61 2 9642 4922, FAX +61

More information

CBI-064. User Manual. Caddx to KNX-BUS Interface

CBI-064. User Manual. Caddx to KNX-BUS Interface CBI-064 Caddx to KNX-BUS Interface User Manual GDS Intelligence in Buildings El. Venizelou 116 Nea Erithrea 14671 Tel: +30 2108071288 Email: info@gds.com.gr Web: gds.com.gr Contents 1 Device Description...

More information

VISTA-32FBPT. Commercial Fire and Burglary Partitioned Security Systems with Scheduling. User Guide /12 Rev. B

VISTA-32FBPT. Commercial Fire and Burglary Partitioned Security Systems with Scheduling. User Guide /12 Rev. B VISTA-32FBPT Commercial Fire and Burglary Partitioned Security Systems with Scheduling User Guide 800-11045 2/12 Rev. B 2 TABLE OF CONTENTS SYSTEM OVERVIEW...5 General...5 A Partitioned System...5 Zones...6

More information

NetworX Series. NX-8 Commercial Fire Panel Installation and Startup

NetworX Series. NX-8 Commercial Fire Panel Installation and Startup NetworX Series NX-8 Commercial Fire Panel Installation and Startup 2004 GE Security All rights reserved. Printed in the United States of America. These instructions do not purport to cover all details

More information

R-Series Remote Annunciators and Expanders Installation and Operation Guide

R-Series Remote Annunciators and Expanders Installation and Operation Guide R-Series Remote Annunciators and Expanders Installation and Operation Guide P/N 3100969-EN REV 05 ISS 06MAY13 Copyright Trademarks and patents Manufacturer Version FCC compliance Contact information 2013

More information

Alarms and Events. Defining Alarm Conditions. Database-Generated Alarms

Alarms and Events. Defining Alarm Conditions. Database-Generated Alarms 9 Defining Alarm Conditions Database-Generated Alarms The LookoutDirect alarm service keeps track of error messages and any process elements you have defined alarm conditions for. You can define alarm

More information

Testing the System. Battery Test. Dialer Test. Fire Drill Test (Code + [#] + 69) One-Man Fire Walk-Test (Code + [#] + 68)

Testing the System. Battery Test. Dialer Test. Fire Drill Test (Code + [#] + 69) One-Man Fire Walk-Test (Code + [#] + 68) F A 1 7 0 0 c Testing the System Battery Test When AC power is present, the FA1700C runs a brief battery test every 60 seconds to determine if there is a battery connected, and runs an extended battery

More information

user manual Document No , Revision 03 November 2015

user manual Document No , Revision 03 November 2015 user manual Document No. 996-202-600-3, Revision 03 November 2015 Contents 1 Introduction...1 1.1 Notice...1 1.2 Models...1 2 User Control Levels...2 2.1 Level Definition...2 2.2 User Passwords...2 3 Controls

More information

Addendum. HART Communication with the FlexSonic Acoustic Detector. 1.1 Rev: 1/

Addendum. HART Communication with the FlexSonic Acoustic Detector. 1.1 Rev: 1/ Addendum HART Communication with the FlexSonic Acoustic Detector 1.1 Rev: 1/15 Table Of Contents Interconnecting the HART Communicator with the Acoustic Detector... 1 HART Device Description Language...

More information

ICS Regent. Fire Detector Input Modules PD-6032 (T3419)

ICS Regent. Fire Detector Input Modules PD-6032 (T3419) ICS Regent Fire Detector Input Modules (T3419) Issue 1, March, 06 Fire detector input modules provide interfaces for 16 fire detector inputs such as smoke detectors, flame detectors, temperature detectors,

More information

VISTA-128BP/VISTA-250BP/ VISTA-128SIA Enhanced Commercial Burglary Partitioned Security System With Scheduling User Guide K5895V5 4/09 Rev C

VISTA-128BP/VISTA-250BP/ VISTA-128SIA Enhanced Commercial Burglary Partitioned Security System With Scheduling User Guide K5895V5 4/09 Rev C VISTA-128BP/VISTA-250BP/ VISTA-128SIA Enhanced Commercial Burglary Partitioned Security System With Scheduling User Guide K5895V5 4/09 Rev C Your Honeywell security system is designed for use with devices

More information

Fire Operator Workstation (Fire OWS) User s Guide

Fire Operator Workstation (Fire OWS) User s Guide Fire Operator Workstation (Fire OWS) User s Guide 1-1 Fire Operator Workstation (Fire OWS) User s Guide Introduction This user s guide details the components, capabilities, and operation procedures of

More information

Contents. Glossary

Contents. Glossary Contents Glossary ------------------------------------------------------------------------------------------------------ 6 1. Introduction to the IDS 1632 -------------------------------------------------------------

More information

D1265. User's Guide. Touchscreen Keypad

D1265. User's Guide. Touchscreen Keypad D1265 EN User's Guide Touchscreen Keypad D1265 User's Guide Contents This system includes a telephone line seizure feature. The system can be programmed to communicate with a central monitoring station

More information

Installation Instructions. Fire Command Center/Fire Alarm Annunciators D1256/D1257

Installation Instructions. Fire Command Center/Fire Alarm Annunciators D1256/D1257 Instructions Fire Command Center/Fire Alarm Annunciators D1256/D1257 74-06925-000-H Page 2 2004 Bosch Security Systems Contents 1.0 Introduction...5 1.1 Before You Begin...5 1.2 Type Styles Used Here...5

More information

Integrated Security Solutions

Integrated Security Solutions Integrated Security Solutions Table of Contents Control Panels 4 Keypads 8 Communication Modules 16 I/O Expanders 20 Door Control 24 Home Automation 25 RF Receivers 26 3 Our integrated security solutions

More information

Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT

Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT-1201739 Release 1.2 Issued Date July 30, 2004 Supersedes Document Introduction.................................................

More information

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers. ModSync Sequencing System Installation & Operation Manual For use with Fulton Steam Boilers. Revision 3.0 8/21/2008 - 2 - Table of Contents Introduction Page 4 Features Page 4 Sequence of Operation Page

More information

User Manual. Dryer Controller M720

User Manual. Dryer Controller M720 User Manual Dryer Controller M720 Hardware version 1.00 Software version 1.00 Preliminary version Manual M720 Dryer controller Page 1 of 42 Document history Preliminary version: - Created in April, 2009

More information

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description MODUL-R FIRE ALARM CONTROL PANELS MR-2900/MR-2920 Addressable Fire Alarm Control Panels Description MR-2900 Fire Alarm Control Panel The MR-2900 fire alarm system control unit is the heart of a sophisticated

More information

VISTA-128BPT/ VISTA-250BPT/ VISTA-128BPTSIA

VISTA-128BPT/ VISTA-250BPT/ VISTA-128BPTSIA VISTA-128BPT/ VISTA-250BPT/ VISTA-128BPTSIA Commercial Burglary Partitioned Security System With Scheduling User Guide 800-06905 6/10 Rev. E IMPORTANT! RECOMMENDATIONS FOR PROPER INTRUSION PROTECTION For

More information

GV2 Series Control Panels

GV2 Series Control Panels GV2 Series Control Panels EN Owner's Manual Supplement System Requirements Minimum system requirements for Classification in accordance with ANSI/SIA CP-01-2000: UL Listed and Classified control unit Model

More information

Area Systems While the alarm bell or siren is sounding, enter your user code. The system silences the alarm bell or siren.

Area Systems While the alarm bell or siren is sounding, enter your user code. The system silences the alarm bell or siren. XR20 User s Guide Silencing an Alarm All/Perimeter and Home/Away Systems While the alarm bell or siren is sounding, enter your user code. The keypad displays DISARM SILENCE. Press the Select key under

More information