Instruction Manual. Electronic gas and smoke detector GRM

Size: px
Start display at page:

Download "Instruction Manual. Electronic gas and smoke detector GRM"

Transcription

1 Mess-, Regel- und Überwachungsgeräte für Haustechnik, Industrie und Umweltschutz Lindenstraße 20 DE Güglingen Telefon +49(0) Service +49(0) Telefax +49(0) Internet Instruction Manual Electronic gas and smoke detector GRM Control unit # Smoke sensor # Gas sensor for Methane (natural gas) # 61188A Gas sensor for Propane-Butane (liquid gas) # 61189A Read manual before use! Observe all safety information! Keep manual for future use!

2 Contents 1 About this instruction manual Structure of warning Explanation of symbols and typeface Safety Intended use Predictable incorrect application Safe handling Qualification of personnel Modifications to the product Use of spare parts and accessories Liability information Product description Scope of delivery Application examples Specifications Approvals, tests and conformities Transportation and storage Installation and commissioning Installing the gas sensor Installing the smoke sensor Installing the control unit Electrical connection Commissioning the device Function test Operation Maintenance Maintenance intervals Maintenance activities Troubleshooting Shutting down and disposal Spare parts and accessories Warranty Copyright Customer satisfaction Addresses GRM

3 1 About this instruction manual 1.1 Structure of warning About this instruction manual This instruction manual is part of the product. Read this manual before using the product. Keep this manual during the entire service life of the product and always have it readily available for reference. Always hand this manual over to future owners or users of the product. WARNING TERM The type and source of danger is shown here. Precautions to take in order to avoid the danger are shown here. There are three different levels of warning: Warning term DANGER WARNING CAUTION Meaning 1.2 Explanation of symbols and typeface Symbol Imminent danger! Failure to observe the information will result in death or serious injuries. Possible imminent danger! Failure to observe the information may result in death or serious injuries. Dangerous situation! Failure to observe the information may result in minor or serious injuries as well as damage to property. Meaning Prerequisite for an activity Activity consisting of a single step 1. Activity consisting of several steps Result of an activity Bulleted list Text Highlighting Indication on a display Highlighting GRM 3

4 Safety 2 Safety 2.1 Intended use The gas and smoke detector GRM consists of a control unit and one or two gas or smoke sensors. The gas and smoke Detector GRM is only suitable for: Monitoring of ambient air for presence of gases or smoke Providing an alarm signal when a defined concentration of gas and/or smoke in the ambient air has been exceeded Onward transmission of the alarm signal. Any use other than the use explicitly stated in this instruction manual is not permitted. 2.2 Predictable incorrect application The control unit, the gas sensor and the smoke sensor must under no circumstances whatsoever be used in the following: Hazardous areas (ex) If the device is operated in hazardous areas, sparks may cause deflagrations, fires or explosions Damp and wet room environments In addition, and in order to avoid false alarms, the smoke sensor must not be used in the following: Rooms in which smoking is permitted Rooms in which smoke, heavy dirt or dust occurs, e.g. kitchens, work shops or barns In areas in which air circulation or insects could trigger false alarms In close vicinity of ventilators and air conditioning units In the vicinity of very bright light sources In the vicinity of fluorescent tubes, current carrying power cables or areas with an increased level of electro-smog. 2.3 Safe handling This product represents state-of-the-art technology and is manufactured in accordance with the pertinent safety regulations. Each unit is subjected to a function and safety test prior to despatch. Operate the product only when it is in perfect condition. Always observe the instruction manual, all pertinent local and national directives and guidelines as well as health and safety regulations and directives regarding the prevention of accidents. 4 GRM

5 Safety WARNING Severe burns or death due to mains voltage in the control unit (AC 230 V, 50 Hz). Do not expose the control unit to water. Interrupt the mains voltage supply before opening the control unit or before performing maintenance and cleaning work and make sure it cannot be switched on by accident. Do not tamper with the control unit in any way whatsoever. 2.4 Qualification of personnel The product may only be installed, commissioned, operated, maintained, shut down and disposed of by qualified, specially trained personnel. Electrical work may only be carried out by qualified electricians in accordance with local and national regulations. 2.5 Modifications to the product Changes or modifications made to the product by unauthorised persons may lead to malfunctions and are prohibited for safety reasons. 2.6 Use of spare parts and accessories Use of unsuitable spare parts and accessories may cause damage to the product. Use only the manufacturer s genuine spare parts and accessories (refer to chapter 11, page 19). 2.7 Liability information The manufacturer shall not be liable for any direct or consequential damage resulting from failure to observe the technical instructions, guidelines and recommendations. The manufacturer and the sales company shall not be liable for costs or damages incurred by the user or by third parties in the use or application of this device, particularly in case of improper use of the device, misuse or malfunction of the connection, malfunction of the device or of connected devices. The manufacturer or the sales company shall not be liable for damages resulting from any use other than the use explicitly stated in this instruction manual. The manufacturer shall not be liable for misprints. Für Druckfehler übernimmt der Hersteller keine Haftung. GRM 5

6 Product description 3 Product description The gas and smoke detector GRM monitors the concentration of explosive gases, vapours and/or smoke developments in the ambient air. If the level of permissible gas or smoke concentration is exceeded at one of the connected sensors, a visual and audible alarm is initiated at the control unit. Application areas are, for instance, boiler rooms, offices, storage areas or in cellars and living rooms. Control unit a b c d e Green pilot lamp Without function Red alarm lamp Mute button Without function Fig. 1: Control unit The green pilot light indicates that the instrument is operational. When an alarm condition occurs, the red alarm lamp lights up and the buzzer sounds. The buzzer can be muted by pressing the mute button. For safety reasons the alarm lamp remains on during the entire alarm period. If the cause for alarm has been rectified, the alarm lamp can be extinguished by pressing the mute button for a second time. The alarm is initiated via one of the connected sensors. With fault conditions such as open circuit in the sensor connection cable, the red alarm light blinks and the buzzer sounds. The control unit incorporates voltage-free changeover relay contacts for the connection of additional remote alarm units with appropriate voltage supply, e.g. visual and audible alarm units. During normal operation the relay is energised, in an alarm condition the relay is deenergised (fail-safe principle). 6 GRM

7 Product description Gas sensor 1 Green pilot lamp 2 Yellow fault light 3 Red alarm lamp Fig. 2: Gas sensor The gas sensor is works pre-calibrated to methane or propane and butane. It detects on a semi-conductor basis the concentration of gases which are present in ambient air. The gas sensors are adjusted to a detection level which corresponds to 20 % of the lower explosion limit (LEL) of the relevant gas. The green pilot light is lit when the gas sensor is operational. The yellow fault lamp lights up when a fault occurs on the gas sensor side. The red alarm lamp lights up when a proper alarm occurs. Smoke sensor 1 Red alarm lamp Fig. 3: Smoke sensor The smoke sensor monitors the concentration of smoke in the ambient air. The red alarm light can be seen through the ventilation slots and blinks approx. every 45 seconds if the gas sensor is operational. If a proper alarm occurs, a pulsed audible alarm sounds. 3.1 Scope of delivery The control unit is always part of the delivery. As every application requires different sensors, no standard sensors are supplied. The following sensors are available: Smoke sensor Gas sensor for methane (natural gas) Gas sensor for propane-butane (liquified gas) The gas and smoke sensors can be connected to the control unit in the following combinations: 1 gas- and 1 smoke sensor 2 gas sensors 2 smoke sensors GRM 7

8 Product description 1 gas sensors 1 smoke sensor Sensors must be ordered separately. This instruction manual contains all information necessary for the safe operation of the GRM and its selectable sensors. 3.2 Application examples 1 GRM 2 AFRISO event reporting system 3 Internet 4 5 Mobile phone 6 Fax 7 Phone Fig. 4: AFRISO event reporting system for remote reporting of leaks Fig. 5: Control unit with mounting frame for control panel mounting; right: control panel cutout 8 GRM

9 4 Specifications Table 1: Specifications sensors Parameter General Value Gas sensor Dimensions W x H x D: 80 x 80 x 35 mm Specifications Smoke sensor Ø x L: 155 x 38 mm Weight 100 g 200 g Housing material Plastics Humidity Max. 75 % relative humidity Response delay After switching on: approx. 2 minutes In operation: approx. 2 seconds Emissions - Min. 85 db(a), A- valued noise level of the audible alarm at a distance of three metres. Operating temperature range Ambient 0 C to +40 C Storage 0 C to +40 C Supply Nominal voltage DC 12 V GRM 9

10 Specifications Table 2: Specifications control unit Parameter General Dimensions (W x H x D) Weight Housing material Emissions Value 100 x 188 x 65 mm 0.55 kg Plastics ABS Operating temperature range Ambient 0 C to +40 C Storage 0 C to +40 C Supply Nominal voltage Rated power Mains fuse Switching load of output relay Electrical safety Electrical safety EN Protection class II EN Min. 70 db(a), A-valued noise level of the audible alarm at a distance of one metre AC 230 V ± 10 %, 50/60 Hz 15 VA T 100 ma Protection IP 40 EN Electromagnetic compatibility (EMC) Noise suppression EN Noise immunity EN Max. AC 250 V, 2 A, resistive load 10 GRM

11 Screw connections at the control unit Transportation and storage The centre rubber cable gland can be replaced by a cable gland M20. Cable gland M16 M20 Cable diameter mm mm 4.1 Approvals, tests and conformities The gas and smoke detector GRM conforms to the EMC Directive (2004/108/EC) and to the Low Voltage Directive (2006/95/EC). 5 Transportation and storage CAUTION Damage to the device due to improper transportation. Do not throw or drop the device. CAUTION Damage to the device due to improper storage. Store device in a clean and dry environment. Store device only within its permissible temperature range, refer to chapter 4, page 9. GRM 11

12 Installation and commissioning 6 Installation and commissioning The control unit and the probe must never be installed in hazardous areas. 6.1 Installing the gas sensor Mounting position is at the height which corresponds to the spread of the escaping gas. a b cm Max. 5 m Fig. 6: Mounting position of a methane (natural gas) gas sensor a b cm Max. 5 m Fig. 7: Mounting position of propane-butane sensor (liquified gas) 1. Loosen screw at the front of the housing und remove upper housing part. 2. Fix gas sensor to the wall with two screws through the mounting holes. 12 GRM

13 Installation and commissioning 6.2 Installing the smoke sensor Smoke sensors in living accommodations should be mounted between living rooms and bedrooms because most house fires start in the living area. Mounting position is on the ceiling in the centre of the room. The minimum distance to the walls is 60 cm. Sensors should not be in rooms which under normal conditions have a great amount of smoke or vapours present, e.g. kitchens, humid and damp rooms, in close vicinity to ventilators or air conditioning units or in rooms in which people smoke. a b Centre of room Min. 60 cm Fig. 8: Mounting position of a smoke sensor 1 Opening Fig. 9: Opening at the smoke sensor 1. Flip open the smoke detector from the opening spot. 2. Fix smoke detector to the ceiling with two screws through the mounting holes. 6.3 Installing the control unit The control unit must be mounted to an even, rigid and dry wall at eye level. The control unit must be accessible and easy to oversee at all times. GRM 13

14 Installation and commissioning The control unit must not be reached by water or splash water. The control unit must not be installed in damp rooms. The maximum ambient temperature at the control unit must not be exceeded, refer to table 2, page 10. In the case of outdoor installation, the control unit must be protected from direct atmospheric influences. 1. Open control unit. 2. Fasten control unit to the wall (A or B). A 1 Mount the screw to the wall. 2 Hang the control unit to the screw. 3 Fixate the control unit by screwing the lug to the wall. B Drill the fastening holes in the bottom part with a Ø 5 mm drill. Mount the bottom part to the wall with the screws shipped with the unit. 14 GRM

15 Installation and commissioning 3. Connect the unit electrically, refer to chapter 6.4, page Close control unit. 6.4 Electrical connection Mains supply is disconnected and cannot be switched back on by accident. The maximum distance between sensor and control unit is 50 m Ensure that the mains connecting cable is sufficiently protected against damage, for instance, run in metal conduit. Mains supply cable should be fused separately (max. 16 A). Connection of sensors to control unit: use 3-core cable with a cross section of min. 0.5 mm², e.g. bell wire YR 3 x 0.8 mm. Mains connection should be provided via firmly installed and fixed cable, e.g. NYM-O 2 x 1.5 mm². 1. Run the cable of the 1st sensor through the middle rubber/ screwed cable gland and connect to the middle terminal (S1). 2. Run the cable of the 2nd sensor through the right hand gland and connect to the right hand terminal (S2). 3. Run the cable for an additional external alarm unit through the left hand gland and connect to the left hand terminal. Polarity is not critical. 4. Run mains supply cable through the left hand gland. 5. Connect Phase to terminal L and Neutral to terminal N. GRM 15

16 Installation and commissioning Coding plug: Connection of two sensors. Left and right terminals are connected. Remove black coding plug. Coding plug: Connection of one sensor Left terminal is connected. Right terminal is not connected. Coding plug must be plugged in. a b c d e Mains supply Relay contact for additonal alarm 1. Sensor 2. Sensor Coding plug Fig. 10: Electrical connection of control unit Relay contact position in Alarm: COM-NC; in normal operation: COM-NO. CAUTION The switching contact may be destroyed by voltage peaks when inductive consumers are switched off. Use commercially available standard RC combinations such as 0.1 µf/100 Ohm for inductive consumers. 6.5 Commissioning the device Control unit and probes have been installed as per chapter 6, page 12. Electrical connection has been completed as per chapter 6.4, page 15. Probes have been connected to control unit. Output relay has been connected (if required). Mains connection is ready. Flat cable is connected to printed circuit board. Control unit has been closed with screws. 16 GRM

17 6.6 Function test If all prerequisites are met, the device is ready for operation. 1. Switch on the power supply via the on-site mains fuse. 2. Perfom a function test, refer to chapter 6.6, page 17. Operation At the smoke sensor Depress the test button TEST/RESET for three seconds until the alarm sounds. 1 Test button TEST/RESET 7 Operation After the mains supply has been switched on, the connected sensors will be ready after approx. 2 minutes of warm-up time. 8 Maintenance 8.1 Maintenance intervals Table 3: Maintenance intervals When Activity 2 x per annum Vacuum clean the housings of the sensors carefully. 8.2 Maintenance activities Replacing the mains fuse F1 Mains voltage is interrupted and cannot be switched on by accident. 1. Open control unit, refer to chapter 6.3, page Open up the black, vertical safety bracket using a screwdriver: Press down and turn by ¼ turn in anti-clockwise direction. 3. Remove insert. 4. Replace mains fuse F1, refer to table 2, page Place insert back into the safety bracket and close with a screwdriver: Press down and turn by ¼ turn in clockwise direction. 6. Close control unit, refer to chapter 6.3, page Switch on the mains voltage. GRM 17

18 Troubleshooting 9 Troubleshooting Repair work may only be carried out by qualified, specially trained personnel. Table 4: Troubleshooting Problem Possible reason Remedy Green pilot LED of the control unit is not on. Red alarm LED on control unit is lit and buzzer sounds even though there is no alarm condition at the sensor. Red alarm LED on control unit blinks and buzzer sounds although there is no alarm condition at the sensor. After pressing the mute button twice following an alarm condition, the red alarm lamp stays on. Additional external alarm does not react during an alarm condition. Mains supply failure. Mains cable is not connected. Mains fuse is defect. False alarm resulting from dirty sensors. Coding plug in wrong position. False alarm as a result of an open circuit in the cable between control unit and sensor. False alarm resulting from a defect sensor. Alarm condition still exists. Additional alarm instrument is defect. 18 GRM Restore mains supply. Connect mains cable. Replace mains fuse. Carefully clean sensors. Place coding plug in right position, see chapter 6.4, page 15. Ensure that proper connection is restored. Replace sensor. The ambient air must be free from gases and smoke. Exchange additional alarm unit.

19 Shutting down and disposal Problem Possible reason Remedy Other malfunction. Return the device to the manufacturer. 10 Shutting down and disposal 1. Disconnect mains supply. 2. Remove the device (see chapter 6, page 11, steps in reverse sequence). 3. To protect the environment, this device must not be disposed of together with the normal household waste. Dispose of the device according to local directives or council guidelines. This device consists of materials that can be reused by recycling firms. The electronic inserts can be removed easily and are constructed from recyclable materials. If you do not have the opportunity to dispose of the old device in accordance with environmental regulations, please contact us for possibilities to dispose of it or to return it. 11 Spare parts and accessories Part Part No. Event reporting system Phone Alarm SD Event reporting system GSM Alarm Event reporting system EMS Event reporting system EMS Mounting frame for control unit IP54 kit with screw connection M Mains fuse F1 (M 100 ma) RC combination (0,1 µf/100 Ohm) Horn KH 1 (for dry rooms) Combination Light and Horn unit Revolving alarm light (for damp rooms and outdoor installation) Horn HPW 2 (for damp rooms and outdoor installation) GRM 19

20 Warranty 12 Warranty The manufacturer s warranty for this product is 24 months from date of purchase. This warranty applies to all countries in which this product is sold by the manufacturer or its authorised representatives. 13 Copyright The manufacturer holds the copyright to this manual. This manual may only be reprinted, translated, copied in part or in whole with the prior written consent of the manufacturer. We reserve the right to modify any specifications or alter any illustrations in this manual without prior notice. 14 Customer satisfaction Customer satisfaction is our prime objective. Please get in touch with us if you have any questions, suggestions or problems regarding your product. 15 Addresses The addresses of our worldwide representatives can be found on the Internet at 20 GRM

Instruction Manual. Alarm Unit For Low Gas Level # Read manual before use! Observe all safety information! Keep manual for future use!

Instruction Manual. Alarm Unit For Low Gas Level # Read manual before use! Observe all safety information! Keep manual for future use! Mess-, Regel- und Überwachungsgeräte für Haustechnik, Industrie und Umweltschutz Lindenstraße 20 74363 Güglingen Telefon +49 7135-102-0 Service +49 7135-102-211 Telefax +49 7135-102-147 info@afriso.de

More information

Operating instructions

Operating instructions Operating instructions Level switches Minimelder, Maximelder Minimelder-R (with relay) Maximelder-R (with relay) Read instructions before using product! Observe all safety information! Keep instructions

More information

Operating instructions

Operating instructions Mess-, Regel- und Überwachungsgeräte für Haustechnik, Industrie und Umweltschutz Lindenstraße 20 74363 Güglingen Telefon +49 7135 102-0 Service +49 7135-102-211 Telefax +49 7135-102-147 info@afriso.de

More information

Operating Instructions

Operating Instructions Mess-, Regel- und Überwachungsgeräte für Haustechnik, Industrie und Umweltschutz Lindenstraße 20 DE-74363 Güglingen Telefon: +49(0)7135-102-0 Service: +49(0)7135-102-211 Telefax: +49(0)7135-102-147 E-Mail:

More information

Instruction Manual. Automatic fuel oil de-aerator SMART-FLO 3/K B100 COMPATIBLE

Instruction Manual. Automatic fuel oil de-aerator SMART-FLO 3/K B100 COMPATIBLE Sid Harvey s 605 Locust Street Garden City, NY 11530 Instruction Manual Automatic fuel oil de-aerator SMART-FLO 3/K Read manual before use! Observe all safety information! Keep manual for future use! 05.2015

More information

Operating instructions for the radio heat detector GS412

Operating instructions for the radio heat detector GS412 Operating instructions for the radio heat detector GS412 Index 1. Safety instructions... 3 2. Suitable and unsuitable locations... 3 2.1 Radio heat detectors should be installed in the following rooms:...

More information

1. Safety instructions Mounting location in rooms of the heat detectors... 3

1. Safety instructions Mounting location in rooms of the heat detectors... 3 Operating instructions for the heat detector GS403 Index 1. Safety instructions... 3 2. Mounting location in rooms of the heat detectors... 3 2.1 Heat detectors should be installed in the following rooms:...

More information

FSW300 Series Flow Switch

FSW300 Series Flow Switch . FSW300 Series Flow Switch - 2 - Series FSW300 Series FSW300 Table of contents page 0 About this operating manual... 4 1 Device description... 5 1.1 Intended use... 5 1.1.1 Reed contact - Switching of

More information

Installation instructions and operating manual. Sauna control system FCU1000 / FCU1200

Installation instructions and operating manual. Sauna control system FCU1000 / FCU1200 Series FCU1x00 Installation instructions and operating manual Sauna control system FCU1000 / FCU1200 only sauna FCU1000 additional humidity FCU1200 Doc-ID: B_M_FCU1xxx-A5_EN Version: V 1.06 certificated

More information

Inspection Light LED 6149/2. Operating instructions EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN

Inspection Light LED 6149/2. Operating instructions EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN Inspection Light LED Operating instructions Additional languages www.stahl-ex.com Contents 1 General Information...3 1.1 Manufacturer...3 1.2 Information regarding the operating instructions...3 1.3 Conformity

More information

2CKA001473B System Manual Busch-Infoline. Handicapped toilet signal set 1510 UC

2CKA001473B System Manual Busch-Infoline. Handicapped toilet signal set 1510 UC 2CKA001473B9007 19.05.2017 System Manual Busch-Infoline Handicapped toilet signal set 1510 UC-... -101 Table of contents Table of contents 1 Notes on the instruction manual... 3 2 Safety... 4 2.1 Information

More information

3-way switching valve

3-way switching valve Operating Manual UK 3-way switching valve for domestic hot water charging USV 1" AG USV 5/4" AG USV 6/4" IG UK805189 / 201109 Translation of the original instruction manual Please read first This operating

More information

Operating instructions

Operating instructions Operating instructions Leak detector LAG-14 ER BRL A part 1 (DIBt) Annex 15.24 Read instructions before using product! Observe all safety information! Keep instructions for future use! 05.2016 0 854.001.0153

More information

USER GUIDE. DRENA 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS - WASTE WATER -

USER GUIDE. DRENA 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS - WASTE WATER - USER GUIDE DRENA 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS - WASTE WATER - II CONTENTS 1. SYMBOLS AND WARNINGS... 5 2. GENERAL INFORMATION... 6 3. WARNINGS... 7 4. GENERAL DESCRIPTION... 8 5. INSTALLATION...

More information

Installation and operating instructions. Temperature difference controller 6 inputs, 3 outputs, integrated data logger for SD card

Installation and operating instructions. Temperature difference controller 6 inputs, 3 outputs, integrated data logger for SD card SOLARTHERMIE - SOLAR THERMAL - SOLAR TÉRMICO - SOLAIRE THERMIQUE - SOLARE TERMICO Installation and operating instructions Temperature difference controller 6 inputs, 3 outputs, integrated data logger for

More information

LC3000 Level Controller Installation and Maintenance Instructions

LC3000 Level Controller Installation and Maintenance Instructions 4025550/12 IM-P402-36 AB Issue 12 LC3000 Level Controller Installation and Maintenance Instructions 1. General safety information LC3000 NORM ALARM TEST 2. General product information 3. Installation 4.

More information

MANUAL Oil Level Sensor

MANUAL Oil Level Sensor PROCESS AUTOMATION MANUAL Oil Level Sensor KVF-104-PF ISO9001 0102 With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery for Products

More information

BN30 OPERATING MANUAL SOCKET THERMOSTAT TRT-BA-BN30-TC-001-EN

BN30 OPERATING MANUAL SOCKET THERMOSTAT TRT-BA-BN30-TC-001-EN BN30 EN OPERATING MANUAL SOCKET THERMOSTAT TRT-BA-BN30-TC-001-EN table of contents Notes regarding the operating manual... 1 Safety... 2 Information about the device... 2 Technical data... 3 Transport

More information

LFE50. UV Flame Safeguard. Building Technologies Division DETACTOGYR

LFE50. UV Flame Safeguard. Building Technologies Division DETACTOGYR 7 783 DETACTOGYR Flame Safeguard The... together with the QRA50M / QRA51M form a self-checking flame supervision system (DETACTOGYR ) designed for use with continuously operating oil or gas burners or

More information

SMART EVO 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS

SMART EVO 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS SMART EVO 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS CONTENTS 1. INTRODUCTION... 5 2. WARNINGS... 6 3. GENERAL DESCRIPTION... 7 4. INSTALLATION... 8 5. LUMINOUS INDICATORS AND COMMANDS... 9 6. DIP-SWITCH

More information

Instructions For Use ENG. LED Magnifier Lamp

Instructions For Use ENG. LED Magnifier Lamp Instructions For Use ENG OPTICA 488 LED Magnifier Lamp ENG Table of Contents 1. For your safety...3 1.1 Designated use...3 1.2 Safety instructions...3 1.3 Warning levels...4 2. Mounting...4 2.1 Mounting

More information

MANUAL Overflow sensor NVF-104/34-PF

MANUAL Overflow sensor NVF-104/34-PF PROCESS AUTOMATION MANUAL Overflow sensor NVF-104/34-PF ISO9001 0102 Overflow sensor NVF-104/34-PF With regard to the supply of products, the current issue of the following document is applicable: The

More information

1 measurement signal input 4-20 ma for connection to an external gas sensor 5 freely programmable alarm switching points per measuring point

1 measurement signal input 4-20 ma for connection to an external gas sensor 5 freely programmable alarm switching points per measuring point Medium - Control - System Franke & Haqenest GmbH Borngasse 1a * 04600 Altenburg Tel: 03447-499 313-0 Fax: 03447-499 313-6 email: info@mcs-gaswarnanlagen.de MCS User Guide MCS GasController Microprocessor

More information

INSTRUCTION MANUAL T119 1MN0110 REV. 0. operates with ISO9001 certified quality system

INSTRUCTION MANUAL T119 1MN0110 REV. 0. operates with ISO9001 certified quality system INSTRUCTION MANUAL 1MN0110 REV. 0 operates with ISO9001 certified quality system TECSYSTEM S.r.l. 20094 Corsico (MI) Tel.: +39-024581861 Fax: +39-0248600783 http://www.tecsystem.it R. 1.1 25/08/16 ENGLISH

More information

Test Unit GTL 100 for Fire Detectors

Test Unit GTL 100 for Fire Detectors Test Unit GTL 100 for Fire Detectors Description and Operation Manual Zertifiziertes QM System Nach DIN EN ISO 9001 Description and Operation Manual Table of Contents 1. Instructions 1.1 General 1.2 Standards

More information

LC2200 Level Controller Installation and Maintenance Instructions

LC2200 Level Controller Installation and Maintenance Instructions 4025250/9 IM-P402-77 AB Issue 9 LC2200 Level Controller Installation and Maintenance Instructions LC2200 ALARM TEST >50% >100%

More information

Safety. Operating instructions UV sensor UVS 10 DANGER WARNING. Contents CAUTION Edition Please read and keep in a safe place

Safety. Operating instructions UV sensor UVS 10 DANGER WARNING. Contents CAUTION Edition Please read and keep in a safe place 8.. Edition 08.0 D GB F NL I E DK S N P GR TR CZ PL RUS H www.docuthek.com Operating instructions UV sensor UVS 0 Translation from the German 008 009 Elster GmbH Contents UV sensor UVS 0......................

More information

TIH 300 S / TIH 400 S / TIH 500 S / TIH 700 S / TIH 900 S / TIH 1100 S

TIH 300 S / TIH 400 S / TIH 500 S / TIH 700 S / TIH 900 S / TIH 1100 S TIH 300 S / TIH 400 S / TIH 500 S / TIH 700 S / TIH 900 S / TIH 1100 S EN OPERATING MANUAL INFRARED HEATING PANEL TRT-BA-TIH300S-TIH400S-TIH500S-TIH700S-TIH900S-TIH1100S-TC-002-EN Table of contents Notes

More information

Flameproof Manual Call Points

Flameproof Manual Call Points Operating instructions Additional languages www.r-stahl.com CS & Clifford & Snell Contents General Information.... Manufacturer.... Information regarding the operating instructions.... Further documents....

More information

User Manual GV25 GV35 GV702. Company information: Original instructions GV12066 (1)

User Manual GV25 GV35 GV702. Company information:   Original instructions GV12066 (1) User Manual Original instructions GV25 GV35 GV702 Company information: www.vipercleaning.eu info-eu@vipercleaning.com GV12066 (1) 2012-04-10 USER MANUAL ENGLISH TABLE OF CONTENTS Introduction... 4 Manual

More information

LFE50. UV Flame Safeguard. Siemens Building Technologies HVAC Products DETACTOGYR. Series 02

LFE50. UV Flame Safeguard. Siemens Building Technologies HVAC Products DETACTOGYR. Series 02 7 783 ISO 9001 DETACTOGYR Flame Safeguard Series 02 The... together with the QRA50M / QRA51M form a self-checking flame supervision system (DETACTOGYR ) designed for use with continuously operating oil

More information

KM300 Carbon Monoxide Detection System Installation Manual

KM300 Carbon Monoxide Detection System Installation Manual GE Security KM300 Carbon Monoxide Detection System Installation Manual P/N 1068922 REV 2.0 16SEP09 Copyright Copyright 2009 GE Security, Inc. All rights reserved. This document may not be copied in whole

More information

RT 10 RT 10 INSTALLATION, USER INSTRUCTIONS & CUSTOMER CARE GUIDE. Order no

RT 10 RT 10 INSTALLATION, USER INSTRUCTIONS & CUSTOMER CARE GUIDE. Order no RT 10 Installation and Operating Instructions Room temperature controller for heating ROOM TEMPERATURE appliances with CONTROLLER bus-enabled Heatronic 3 and TD 200 RT 10 7719 002 505 FOR WORCESTER HEATING

More information

AIRGOCLEAN 10 E OPERATING MANUAL AIR CLEANER TRT-BA-AIRGOCLEAN10E-TC-001-EN

AIRGOCLEAN 10 E OPERATING MANUAL AIR CLEANER TRT-BA-AIRGOCLEAN10E-TC-001-EN AIRGOCLEAN 10 E EN OPERATING MANUAL AIR CLEANER TRT-BA-AIRGOCLEAN10E-TC-001-EN Table of contents Notes regarding the operating manual... 1 You can download the current version of the operating manual and

More information

OilSET-1000 (12 VDC)

OilSET-1000 (12 VDC) Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel: +358 29 006 260 Fax: +358 29 006 1260 Internet: www.labkotec.fi 20.03.2009 1/11 OilSET-1000 (12 VDC) Oil Separator Alarm Device Copyright 2009

More information

allstor buffer cylinder Instructions for use Instructions for use For the operator Publisher/manufacturer Vaillant GmbH

allstor buffer cylinder Instructions for use Instructions for use For the operator Publisher/manufacturer Vaillant GmbH Instructions for use For the operator Instructions for use allstor buffer cylinder GB Publisher/manufacturer Vaillant GmbH Berghauser Str. 40 D-42859 Remscheid Telefon 021 91 18 0 Telefax 021 91 18 28

More information

OilSET Installation and Operating Instructions. Oil Separator Alarm Device with SET/DM3AL sensor

OilSET Installation and Operating Instructions. Oil Separator Alarm Device with SET/DM3AL sensor Labkotec UK Ltd Adminicle House 1 Lumb Lane Audenshaw Manchester M34 5WH GREAT BRITAIN Tel: 0844 3350 477 Fax: 0161 4281 179 E-mail: info@labkotec.co.uk 10.8.2012 Internet: www.labkotec.co.uk 1/13 OilSET-1000

More information

ELECTRIC FIRE PUMP CONTROLLER

ELECTRIC FIRE PUMP CONTROLLER ELECTRIC FIRE PUMP CONTROLLER INSTRUCTION MANUAL CONTENTS 1. INTRODUCTION 1.1 Safety 1.2 Warranty 1.3 Safety Precautions 1.4 Product Overview 1.5 AS2941-2008 Requirements 2. FEATURES 3. FUNCTIONS AND OPERATIONS

More information

LGA... Gas Burner Controls. Siemens Building Technologies HVAC Products

LGA... Gas Burner Controls. Siemens Building Technologies HVAC Products 7 418 Gas Burner Controls LGA... The LGA... are used for the startup and supervision of atmospheric gas burners of small to medium capacity (without fan) in intermittent operation. The LGA... and this

More information

SET-2000 Hi Level/Oil

SET-2000 Hi Level/Oil Labkotec Oy Labkotie 1 FI-36240 KANGASALA FINLAND Tel: + 358 29 006 260 Fax: + 358 29 006 1260 13.03.2008 Internet: www.labkotec.fi Alarm Device for Oil Separators Copyright 2008 Labkotec Oy We reserve

More information

Operating instructions

Operating instructions ebm-papst Mulfingen GmbH & Co. KG Bachmühle D-74673 Mulfingen Phone +49 (0) 793-0 Fax +49 (0) 793-0 info@de.ebmpapst.com www.ebmpapst.com CONTENTS. SAFETY REGULATIONS AND NOTES. Levels of hazard warnings.

More information

Warning Caution. Safety Precautions (Be sure to read these precautions before using our products.)

Warning Caution. Safety Precautions (Be sure to read these precautions before using our products.) INSTRUCTION MANUAL Infrared Temperature Sensor RD-715-HA No. RD71JE1 2013.09 Preface Thank you for purchasing our Infrared Temperature Sensor RD-715-HA. This manual contains instructions for the mounting,

More information

C Note! LGI16... Burner Controls. Building Technologies

C Note! LGI16... Burner Controls. Building Technologies 7 786 Burner Controls LGI16... Burner controls For use on industrial furnaces For burners in continuous operation Without fan control and air pressure supervision Flame supervision - with QR53... / QR55,

More information

KAB Gas Alarm Operation Manual

KAB Gas Alarm Operation Manual KAB Gas Alarm Operation Manual Henan Hanwei Electronics Co.,Ltd ISO9001-2008 Precautions: To avoid personal safety injury, Instrument damage and potential dangerous accident; do not use gas detector before

More information

Gas leak detectors. For a quick overview. testo testo testo testo gas detector testo 316-Ex

Gas leak detectors. For a quick overview. testo testo testo testo gas detector testo 316-Ex Gas leak detectors For a quick overview testo 317-2 testo 316-1 testo 316-2 testo gas detector testo 316-Ex CH4 C3H8 H2 Gas leak testing Over and over again, devastating explosions and fires are caused

More information

SET-2000 Oil/Sludge. Alarm Device for Oil Separators. Installation and Operating Instructions

SET-2000 Oil/Sludge. Alarm Device for Oil Separators. Installation and Operating Instructions SET-000 Oil/Sludge Alarm Device for Oil Separators Copyright 007 Labkotec Oy We reserve the right for changes without notice TABLE OF CONTENTS GENERAL... INSTALLATION... 4. SET-000 Oil/Sludge Control Unit...

More information

10yr O2NE & Safe-Ox. User Manual

10yr O2NE & Safe-Ox. User Manual Analox Ltd. 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT, UK T: +44 (0)1642 711400 F: +44 (0)1642 713900 W: www.analox.net E: info@analox.net This support line is closed on UK public

More information

Infrascan Passive Infrared Motion Sensor Surface-Mount 753SSR Series. Installation Instructions

Infrascan Passive Infrared Motion Sensor Surface-Mount 753SSR Series. Installation Instructions Infrascan Passive Infrared Motion Sensor Surface-Mount 753SSR Series Installation Instructions Contents 1.0 Product Range...3 2.0 Principle of Operation...3 3.0 Field of View...3 4.0 System Components

More information

Macurco HD-11 Hydrogen Gas Detector

Macurco HD-11 Hydrogen Gas Detector Macurco HD-11 Hydrogen Gas Detector User Instructions Important: Keep these User Instructions for reference TABLE OF CONTENTS GENERAL SAFETY INFORMATION 3 Intended Use 3 List of Warnings and Cautions 3

More information

Macurco HD-11 Hydrogen Gas Detector User Instructions. Important: Keep these User Instructions for reference

Macurco HD-11 Hydrogen Gas Detector User Instructions. Important: Keep these User Instructions for reference Macurco HD-11 Hydrogen Gas Detector User Instructions Important: Keep these User Instructions for reference 2 TABLE OF CONTENTS GENERAL SAFETY INFORMATION 4 INTENDED USE 4 LIST OF WARNINGS AND CAUTIONS

More information

Operations Manual GMA 313 CO 2. Gas Monitor for one detection point

Operations Manual GMA 313 CO 2. Gas Monitor for one detection point GMA 313 CO 2 Gas Monitor for one detection point Operations Manual 1194 Oak Valley Dr, Ste 20, Ann Arbor MI 48108 USA (800) 959-0329 (734) 769-0573 www.gfg-inc.com GfG Products for Increased Safety Congratulations

More information

HSGM Heißschneide-Geräte

HSGM Heißschneide-Geräte Operating Instructions Heat cutting machine Model HSG-00 General information These Operating Instructions belong to this product. They contain important information about commissioning and operation. Important

More information

Instruction Manual and Warranty

Instruction Manual and Warranty Instruction Manual and Warranty Copyright 2015, Ozeri GENERAL SAFETY Thank you for purchasing the Ozeri 3x Tower Fan. This product has passed extensive quality assurance tests for residential use. Every

More information

Operating instructions Safety-monitoring module SRB 302X3. 1 About this document

Operating instructions Safety-monitoring module SRB 302X3. 1 About this document 1 About this document Operating instructions... pages 1 to 6 Translation of the original operating instructions 1.1 Function This operating instructions manual provides all the information you need for

More information

UV Flame Supervision System

UV Flame Supervision System 7 783 UV Flame Supervision System DETACTOGYR LFE50 Series 02 ISO 9001 The LFE50 is a self-checking UV flame supervision system designed for use with continuously operating burners or for burners running

More information

OilSET Installation and Operating Instructions. Oil Separator Alarm Device

OilSET Installation and Operating Instructions. Oil Separator Alarm Device Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel: +358 29 006 260 Fax: +358 29 006 1260 18.11.2010 Internet: www.labkotec.fi 1/10 OilSET-1000 Oil Separator Alarm Device Copyright 2010 Labkotec

More information

A series of technical features make this gas detector extremely versatile, reliable, accurate, and safe.

A series of technical features make this gas detector extremely versatile, reliable, accurate, and safe. Belonging to Made in Italy GS911K Gas Detector GS911K Using the catalytic sensor inside it, the GS911K detector detects the presence of explosive gas such as: Methane, LPG, with trip sensitivity calibrated

More information

Installer manual AG-AA10. Air/air heat pump IHB GB AG-AA10-30 AG-AA10-40/50

Installer manual AG-AA10. Air/air heat pump IHB GB AG-AA10-30 AG-AA10-40/50 -30 Installer manual Air/air heat pump -40/50 IHB GB 1516-1 331554 Table of Contents 1 Important information 2 5 Installation 7 Safety information 2 Model combinations 7 Read before starting the installation

More information

1040 Gas Monitor INSTALLATION AND OPERATING INSTRUCTIONS AMC-1040 WITH INTEGRAL ELECTROCHEMICAL SENSOR

1040 Gas Monitor INSTALLATION AND OPERATING INSTRUCTIONS AMC-1040 WITH INTEGRAL ELECTROCHEMICAL SENSOR 1040 Gas Monitor INSTALLATION AND OPERATING INSTRUCTIONS AMC-1040 WITH INTEGRAL ELECTROCHEMICAL SENSOR IMPORTANT: Please read these installation and operating instructions completely and carefully before

More information

GMA 301. Operation Manual. Worldwide Supplier of Safety Solutions. Part Number

GMA 301. Operation Manual. Worldwide Supplier of Safety Solutions. Part Number Worldwide Supplier of Safety Solutions GfG Instrumentation 1194 Oak Valley Drive #20 Phone: 734-769-0573 Fax: 734-769-1888 E-Mail: info@gfg-inc.com Internet: www.gfg-inc.com GMA 301 Operation Manual Part

More information

INSTRUCTIONS. OJ-DV-Relay-Module. OJ Drives A DRIVES PROGRAMME DEDICATED TO VENTILATION SOLUTIONS. Optional module for OJ-DV motor controller

INSTRUCTIONS. OJ-DV-Relay-Module. OJ Drives A DRIVES PROGRAMME DEDICATED TO VENTILATION SOLUTIONS. Optional module for OJ-DV motor controller INSTRUCTIONS OJ-DV-Relay-Module 67439B 10/16 (OSH) 016 OJ Electronics A/S Optional module for OJ-DV motor controller OJ Drives A DRIVES PROGRAMME DEDICATED TO VENTILATION SOLUTIONS Contents 1. Product

More information

Installation instructions. For the competent person. Installation instructions VRT 350 VRT 350 GB, IE

Installation instructions. For the competent person. Installation instructions VRT 350 VRT 350 GB, IE Installation instructions For the competent person Installation instructions VRT 350 VRT 350 GB, IE Legal information Document type: Product: VRT 350 Target group: Language: Installation instructions Authorised

More information

TFV 900 OPERATING MANUAL RADIAL FAN TRT-BA-TFV900-TC-001-EN

TFV 900 OPERATING MANUAL RADIAL FAN TRT-BA-TFV900-TC-001-EN TFV 900 EN OPERATING MANUAL RADIAL FAN TRT-BA-TFV900-TC-001-EN Table of contents Notes regarding the operating manual... 1 Safety... 2 Information about the device... 3 Transport and storage... 4 Start-up...

More information

LGA... Gas Burner Controls. Building Technologies Division

LGA... Gas Burner Controls. Building Technologies Division 7 418 Gas Burner Controls LGA... The gas burner controls are used for supervision, startup and control of atmospheric gas burners of small to medium capacity without a fan in intermittent operation. The

More information

Operating Instructions. Accessory Units Melitta Cafina XT Series. Melitta Professional Coffee Solutions

Operating Instructions. Accessory Units Melitta Cafina XT Series. Melitta Professional Coffee Solutions Operating Instructions Accessory Units Melitta Cafina XT Series Melitta Professional Coffee Solutions Contents General... 4. Manufacturer information... 4.2 About these instructions... 4.3 Explanation

More information

TTV 1500 / TTV 3000 OPERATING MANUAL CONVEYING FAN TRT-BA-TTV TC EN

TTV 1500 / TTV 3000 OPERATING MANUAL CONVEYING FAN TRT-BA-TTV TC EN TTV 1500 / TTV 3000 EN OPERATING MANUAL CONVEYING FAN TRT-BA-TTV1500-3000-TC2016-26-004-EN Table of contents Notes regarding the operating manual... 2 You can download the current version of the operating

More information

Analox 1000 Series. User Manual. Analox Sensor Technology Ltd. 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT, UK

Analox 1000 Series. User Manual. Analox Sensor Technology Ltd. 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT, UK Analox 1000 Series User Manual Analox Sensor Technology Ltd. 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT, UK T: +44 (0)1642 711400 F: +44 (0)1642 713900 W: www.analox.net E: info@analox.net

More information

Excellence in Level Measurement

Excellence in Level Measurement Technical Data Sheet No. Novaflo 2000 'Fail-Safe' Level Alarm System Excellence in Level Measurement Afriso Eurogauge Ltd Imberhorne Lane, East Grinstead West Sussex. RH19 1RF Tel: 01342 323641 Fax: 01342

More information

CPS-1 USER S MANUAL AIR INLET / CURTAIN CONTROL

CPS-1 USER S MANUAL AIR INLET / CURTAIN CONTROL CPS-1 USER S MANUAL AIR INLET / CURTAIN CONTROL temperature / static pressure DIFF Opn Clo ALARM HI F2 DELAY ALARM LO OPEN DELAY CLOSE ADJUST Varifan + CPS-1 CPS-1 Although the manufacturer has made every

More information

Operation and Maintenance Manual

Operation and Maintenance Manual (FKER Series) Repeater Panel (FKER, FKER, FKER8) Operation and Maintenance Manual Man-9EL Issue June Index Section Page. Introduction.... Safety and mounting.... Technical specification.... Control panel

More information

Installation, Operation & Service Manual

Installation, Operation & Service Manual Installation, Operation & Service Manual WARNING Improper installation, adjustment, alteration, service or maintenance can result in death, injury or property damage. Read the Installation, Operation and

More information

Operating instructions Safety-monitoring module SRB 302X3. 1. About this document. Content

Operating instructions Safety-monitoring module SRB 302X3. 1. About this document. Content 8 Appendix 8.1 Wiring examples...4 8.2 Start configuration...4 8.3 Sensor configuration...4 8.4 Actuator configuration...5 Operating instructions.............pages 1 to 6 Original 9 EU Declaration of conformity

More information

Gas leak detectors. For a quick overview. testo testo testo testo gas detector testo 316-Ex.

Gas leak detectors. For a quick overview. testo testo testo testo gas detector testo 316-Ex. Data sheet testo 317-2 / testo 316-1 / testo 316-2 / testo gas detector / testo 316-EX Gas leak detectors For a quick overview testo 317-2 testo 316-1 testo 316-2 testo gas detector testo 316-Ex CH 4 C

More information

LGA... Gas Burner Controls. Siemens Building Technologies Landis & Staefa Division

LGA... Gas Burner Controls. Siemens Building Technologies Landis & Staefa Division 7 418 ISO 9001 Gas Burner Controls LGA... The LGA... are used for the startup and supervision of atmospheric gas burners of low to medium capacity, without fan assistance, in intermittent operation. The

More information

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS QUICK USER GUIDE FOR, 2 & 4 ZONE PANELS INDICATORS COLOUR INDICATION MON FAULT Yellow On when a fault condition has occurred, or if no other fault Led is on, this indicates 24v auxiliary fuse failure.

More information

BX444-Mc Gas Detector

BX444-Mc Gas Detector Installation and User Guide Rev.01. BX444-Mc Gas Detector Application Duomo is recognised within the gas industry for providing a comprehensive range of low cost, high reliability gas detection for many

More information

Manual Power relay SR853

Manual Power relay SR853 Manual Power relay SR853 Product types SR853.8.x.x, Rev. 1 SR853 manual page2 The symbols WARNING, CAUTION, NOTE This symbol warns of a serious hazard. Failure to observe this warning may result in death

More information

HXL. Operating instructions

HXL. Operating instructions HXL Operating instructions EN SCOPE OF DELIVERY FOR HXL: 1. HXL line laser 2. Battery adapter BA 3. AA batteries 4. Case 5. Magnetic holder MAH 6. Quick start guide 4 HXL 1. Laser beam output aperture

More information

1. Product characteristics 4 2. Safety 5 3. Proper use 5 4. Operation 6

1. Product characteristics 4 2. Safety 5 3. Proper use 5 4. Operation 6 307214 1103107701 EN Presence detector theronda S360-101 DE WH 2080565 theronda S360-101 DE GR 2080566 theronda S360-101 AP WH 2080555 theronda S360-101 AP GR 2080556 1. Product characteristics 4 2. Safety

More information

Safety. Operating instructions UV sensor UVS 5 DANGER. Contents WARNING CAUTION Elster GmbH Edition Please read and keep in a safe place

Safety. Operating instructions UV sensor UVS 5 DANGER. Contents WARNING CAUTION Elster GmbH Edition Please read and keep in a safe place 06 Elster GmbH Edition 0.6 Translation from the German 0556 D F NL I E DK S N P GR TR CZ PL RUS H www.docuthek.com Operating instructions UV sensor UVS 5 Cert. version 0.6 Contents UV sensor UVS 5... Contents...

More information

MAINS KLARGESTER SEPARATOR ALARM INSTALLATION & OPERATIONS MANUAL

MAINS KLARGESTER SEPARATOR ALARM INSTALLATION & OPERATIONS MANUAL MAINS KLARGESTER SEPARATOR ALARM INSTALLATION & OPERATIONS MANUAL Contents IMPORTANT... 3 General Description... 4 General Operation... 4 Changing Factory Settings... 4 Alarm Type... 4 Check Interval...

More information

3. Intended use. 4. Function. 1. Product characteristics. 2. Safety. Functional description. Channel A light. Motion detector

3. Intended use. 4. Function. 1. Product characteristics. 2. Safety. Functional description. Channel A light. Motion detector EN Motion detector themova S360-101 DE WH 1030565 themova S360-101 DE GR 1030566 themova S360-101 AP WH 1030555 themova S360-101 AP GR 1030556 1. Product characteristics 307067 Passive infra-red motion

More information

Operating Manual MS220KA and MSR220KA

Operating Manual MS220KA and MSR220KA Temperature Relays and MINIKA, Mains Monitoring, Digital Panel meters MINIPAN, Switching Relays and Controls Operating Manual MS220KA and MSR220KA ZIEHL industrie elektronik GmbH + Co KG Daimlerstraße

More information

ExDetector IRCO2. ExDetector IRHC. Operating and Installation Instructions. Gas Detection and Warning Systems

ExDetector IRCO2. ExDetector IRHC. Operating and Installation Instructions. Gas Detection and Warning Systems IRCO2 IRHC Operating and Installation Instructions Gas Detection and Warning Systems Important Instructions Prerequisites for safe and reliable operation of the system: Appropriate transport and handling

More information

Beacon 410A Gas Monitor Operator s Manual

Beacon 410A Gas Monitor Operator s Manual Beacon 410A Gas Monitor Operator s Manual Part Number: 71-0397 Revision: F Released: 12/5/17 www.rkiinstruments.com Product Warranty RKI Instruments, Inc., warrants gas alarm equipment sold by us to be

More information

FP120-Z1 Power supply kit A (70 W) Technical Manual

FP120-Z1 Power supply kit A (70 W) Technical Manual FP120-Z1 Power supply kit A (70 W) Technical Manual 2015-07-08 Control Products and Systems Legal notice Legal notice Technical specifications and availability subject to change without notice. Transmittal,

More information

Installation and operation manual DPC200 - DIFFERENTIAL PRESSURE CONTROLLER. Low pressure with PI-control-mode

Installation and operation manual DPC200 - DIFFERENTIAL PRESSURE CONTROLLER. Low pressure with PI-control-mode Installation and operation manual DPC200 - DIFFERENTIAL PRESSURE CONTROLLER Low pressure with PI-control-mode Manufacturer: Phone: Fax: E-Mail: Website: Issue: Doc.-no.: Arthur Grillo GmbH Am Sandbach

More information

Wiring Instructions for the 2900 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector

Wiring Instructions for the 2900 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector Wiring Instructions for the 900 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector CAUTION: FAILURE TO INSTALL OR ADJUST PROPERLY MAY RESULT IN INJURY OR

More information

MBCE-110/230UV Flame Sensor Module

MBCE-110/230UV Flame Sensor Module MBCE-1002 FEBRUARY 3, 2017 MBCE-110/230UV Flame Sensor Module DESCRIPTION The MBCE-110/230UV modules provide visual indication and electrical outputs that signal the user regarding flame presence in a

More information

CORONA BURNER CONTROLLER INSTRUCTION MANUAL RCF15 EXCLUSIVE FOR FLAME ROD. Corona Corporation

CORONA BURNER CONTROLLER INSTRUCTION MANUAL RCF15 EXCLUSIVE FOR FLAME ROD. Corona Corporation CORONA BURNER CONTROLLER INSTRUCTION MANUAL RCF15 EXCLUSIVE FOR FLAME ROD Corona Corporation This instruction manual contains important information for safe use of this device. Keep this instruction manual

More information

Steam Trap BK 45 BK 45-U BK 45-LT BK 46

Steam Trap BK 45 BK 45-U BK 45-LT BK 46 Steam Trap BK 45 BK 45-U BK 45-LT BK 46 Original Installation Instructions 810437-08 Contents Foreword... 3 Availability... 3 Formatting features in the document... 3 Safety... 3 Use for the intended purpose...

More information

Interrupted Ignition Series Oil Primary Control

Interrupted Ignition Series Oil Primary Control Interrupted Ignition Series Oil Primary Control Application Guide & Installation Instruction for ICM1511*, ICM1512*, ICM151*, ICM1514* For more information on our complete range of American-made products

More information

Archive. LC2200 Level Controller. 1. Safety information. 2. General product information. 3. Installation. 4. Setting up the controller

Archive. LC2200 Level Controller. 1. Safety information. 2. General product information. 3. Installation. 4. Setting up the controller 4025250/10 IM-P402-77 AB Issue 10 LC2200 Level Controller Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Setting up the controller 5.

More information

We measure it. testo 316-Ex CH 4 testo 316-1

We measure it. testo 316-Ex CH 4 testo 316-1 Gas leak detectors testo 317-2 testo 316-1 testo 316-2 testo gas detector testo 316-Ex CH 4 C 3 H 2 Gas leak testing Over and over again, devastating explosions and fires are caused by leaky gas pipelines.

More information

14300 MAINS SEPARATOR ALARM MANUAL

14300 MAINS SEPARATOR ALARM MANUAL Conder Environmental Solutions 14300 MAINS SEPARATOR ALARM MANUAL Separator and Alarm provided by: Alarm Installation, Commissioning & Servicing Support Please contact: www.envirotank.com.au www.envirotank.co.nz

More information

Drying Cabinet Installation and Operating Manual

Drying Cabinet Installation and Operating Manual Drying Cabinet Installation and Operating Manual Model:- ECO Dryer 2.0 HP Heat Pump Technology CONTENTS THIS USER MANUAL 3 DATA PLATE DETAILS 3 ADVICE ON SAFE OPERATION 3 DESCRIPTION OF THE CABINET 4 AIR

More information

TMC. Installation and Operation Manual TMC. Temperature and Pressure Monitoring for Heating and Cooling Applications. Temperature Monitoring Control

TMC. Installation and Operation Manual TMC. Temperature and Pressure Monitoring for Heating and Cooling Applications. Temperature Monitoring Control Installation and Operation Manual Temperature and Pressure Monitoring for Heating and Cooling Applications Temperature Monitoring Control VALVE OPEN ALARM System= 128 o F Alarm At= 130 o F RESET /BACK

More information

INSTRUCTION MANUAL & 8200 Monitor. Manual Issue 06

INSTRUCTION MANUAL & 8200 Monitor. Manual Issue 06 INSTRUCTION MANUAL 8100 & 8200 Monitor Manual Issue 06 ** This page is intentionally left blank ** Table of Contents 1 Introduction... 4 1.1 Manual Conventions... 4 1.2 Version 4 PCBA's... 4 1.3 Product

More information

TTV 4500 / TTV 4500 HP / TTV 7000

TTV 4500 / TTV 4500 HP / TTV 7000 TTV 4500 / TTV 4500 HP / TTV 7000 EN OPERATING MANUAL AXIAL FAN TRT-BA-TTV4500-4500HP-7000-TC-003-EN Table of contents The current version of the operating manual can be found at: Notes regarding the operating

More information

SCHMIDT LED Measured Value Display MD Instructions for Use

SCHMIDT LED Measured Value Display MD Instructions for Use SCHMIDT LED Measured Value Display MD 10.010 Instructions for Use Table of Contents 1 Important Information... 3 2 Application range... 4 3 Mounting instructions... 4 4 Electrical connection... 6 5 Signalizations...

More information