FACILITY MANAGEMENT DEFICIENCIES IN ACUTE CARE SETTINGS
|
|
- Barnard Snow
- 5 years ago
- Views:
Transcription
1 FACILITY MANAGEMENT DEFICIENCIES IN ACUTE CARE SETTINGS Presented by: Alise Howlett, Assoc. AIA,CFPE, CHFM Standards Advisor, EM/PE/LS HFAP A better healthcare survey experience 1
2 FREQUENT PHYSICAL ENVIRONMENT FINDINGS 5/21/2018 HFAP A better healthcare survey experience 2
3 Physical Environment Findings Frequent Physical Environment Findings Absence of PE policies and no review/update in 36 months Lack of credible security assessments Hazardous Materials lists & training Eyewash stations issues Lack of knowledge of Fire Response Plan by staff No inventory of utility system components Improper pressure relationships 5/21/2018 HFAP A better healthcare survey experience 3
4 Physical Environment Findings Absence of PE policies and no review/update in 36 months. 1. Building Safety 2. Building Security 3. Hazardous Materials & Waste 4. Fire Safety Control 5. Medical Equipment Management 6. Utility Systems Management 5/21/2018 HFAP A better healthcare survey experience 4
5 Physical Environment Findings Required Management Plans Building Safety Building Security The organization has to have policies that identifies and minimizes security risks to patients, visitors, and staff as well as addressing areas they believe are security sensitive. 5/21/2018 HFAP A better healthcare survey experience 5
6 Physical Environment Findings Hazardous Materials & Waste Program The organization must have a system to identify, handle, process, and dispose of hazardous materials and waste Each service area of the hospital must have their own list of hazardous materials used/created in their area. Lack of staff training for access to SDS data 5/21/2018 HFAP A better healthcare survey experience 6
7 Physical Environment Findings Eyewash Stations & Emergency Showers When there is a need for eyewash stations, they must comply with ANSI Z All eyewash stations and emergency showers must be flow-tested weekly (long enough to flow any stagnant water from the supply pipe), and inspected annually. 5/21/2018 HFAP A better healthcare survey experience 7
8 Physical Environment Findings Eyewash Stations & Emergency Showers When you have caustic/corrosive materials and there is no eyewash station, the organization needs a risk assessment regarding the need for an eyewash station to adequately prove an eyewash station is not required. Safety Data Sheets will specify if an eye wash station is required, by the listed emergency treatment of flushing the eyes with water for 15 minutes. HFAP and CMS do not specify the location for eye wash stations related to need. 5/21/2018 HFAP A better healthcare survey experience 8
9 Physical Environment Findings Written Fire Control Plans The hospital must have written fire control plans that contains provisions for: Prompt reporting of fires Extinguishing fires Protection for patients, staff and visitors Evacuation Cooperation with fire-fighting authorities 5/21/2018 HFAP A better healthcare survey experience 9
10 Physical Environment Findings Fire Response Staff Training Staff must be trained on the proper procedure to follow regarding fire situations; Where are the fire barriers? Staff includes employees, contract-workers, volunteers, students, physicians, and chaplains. 5/21/2018 HFAP A better healthcare survey experience 10
11 Physical Environment Findings Plant Equipment Inventory The hospital must have a written inventory of all plant equipment available for use. All means all every piece of plant equipment must be on the inventory. Check areas for independent HVAC units to ensure accuracy. NOTE: Often overlooked are portable fans, portable utility pumps, approved space heater, etc. 5/21/2018 HFAP A better healthcare survey experience 11
12 Physical Environment Findings Ventilation, Light & Temp. Control The hospital must have proper ventilation in appropriate areas. All soiled utility rooms or decontamination rooms must have a negative air-pressure relationship to surrounding areas. All clean utility rooms or sterile environments must have a positive airpressure relationship to surrounding areas. Check the policy for determined testing intervals and review results. 5/21/2018 HFAP A better healthcare survey experience 12
13 FREQUENT LIFE SAFETY FINDINGS 5/21/2018 HFAP A better healthcare survey experience 13
14 Frequent Life Safety Findings Fire Alarm Install & Test Fire Sprinkler - Install & Test Medical Gas Systems Generators Utility Systems Door Locks Facility Demographic Report FDR) Suites Signage Fire-Rated Barriers & Ceilings Life Safety Drawings 5/21/2018 HFAP A better healthcare survey experience 14
15 Fire Alarm System - Installation Smoke detectors mounted too close to air diffusers Must be a minimum of 36 inches from supply and return air diffusers 5/21/2018 HFAP A better healthcare survey experience 15
16 Fire Alarm System -Installation Smoke detectors are mounted more than 12 inches below the deck/ceiling 5/21/2018 HFAP A better healthcare survey experience 16
17 Fire Alarm System - Testing Not all devices tested (Interface relays; Devices not available) Interface relays connect the fire alarm system to other systems, such as kitchen hood suppression systems, smoke dampers, magnetic locks, etc. 5/21/2018 HFAP A better healthcare survey experience 17
18 Fire Alarm System - Testing No device inventory identifying Pass or Fail decision NOTE!! Every individual device connected to the fire alarm system must be accounted for in a documented list (i.e. inventory), with a Pass or Fail decision. 5/21/2018 HFAP A better healthcare survey experience 18
19 Fire Alarm System - Testing Report not signed by technician (Every test report must be signed by the technician performing the service) Report does not reference correct standard and edition (NFPA 72, 2010 edition) NOTE!! Verify all reports against standard for the required eight (8) elements of reports. 5/21/2018 HFAP A better healthcare survey experience 19
20 Sprinklers Install. & Maintenance Ceiling mounted objects are mounted too close to sprinkler heads. Hospital policy regarding 18 rule not followed Dust and dirt on heads (checked annually?) 5/21/2018 HFAP A better healthcare survey experience 20
21 Sprinklers Test & Inspection No annual inspection for sprinklers and pipe/hangers (visible from the floor) Many issues with valves & gauges: Failing to inspect control valves on a monthly basis Failing to exercise control valves on an annual basis Failing to inspect pressure gauges on a monthly basis Failing to internally inspect the check valves on a 5-year basis Failing to replace or calibrate pressure gauges on a 5-year basis 5/21/2018 HFAP A better healthcare survey experience 21
22 Sprinklers Test & Inspection Failing replace dry sprinkler heads on a 10- year basis Failing to test or replace quick response sprinklers on a 20-year basis Failing to test or replace standard response heads on a 50-year basis. 5/21/2018 HFAP A better healthcare survey experience 22
23 Medical Gas Systems The most common problem surveyors find with medical gas systems (shut-off valves excluded), is failing to test and inspect according to their policy. Another common problem with medical gas systems is failing to make repairs recommended by their testing vendor. 5/21/2018 HFAP A better healthcare survey experience 23
24 Medical Gas Shutoff Valves access to them is obstructed labels on gas valves do not match the rooms they control 5/21/2018 HFAP A better healthcare survey experience 24
25 Generator Inspection Electrolyte levels (specific gravity) on batteries not being recorded during weekly generator inspection. NFPA , section requires weekly recorded of the battery electrolyte levels (i.e. specific gravity) or electrical conductance testing (sealed lead acid batteries) Run times for testing and cool down not recorded 5/21/2018 HFAP A better healthcare survey experience 25
26 Utility Systems Junction boxes located above the ceiling do not have cover plates installed Access to electrical panels is obstructed A minimum of 36 inches of clearance is required [NFPA ,110.26] 5/21/2018 HFAP A better healthcare survey experience 26
27 Door Locks Doors in the path of egress are locked, and do not comply with the Life Safety Code NOTE: This will likely lead to a Condition Level Finding. Non-compliant locked EXIT doors may lead to an Immediate Jeopardy decision. 5/21/2018 HFAP A better healthcare survey experience 27
28 Door Locks Delayed egress locks on doors in buildings that are not fully protected with sprinklers or smoke detectors, as per of the 2000 LSC. 5/21/2018 HFAP A better healthcare survey experience 28
29 Door Locks Inappropriate use of Clinical Needs locks. Clinical needs locks are permitted in behavioral health units (i.e. Psychiatric, Alzheimer s, Substance Abuse unit), and cannot be used for infant security or on other units. 5/21/2018 HFAP A better healthcare survey experience 29
30 Door Locks Facilities do not review sections 18/ to verify compliance. The need for infant abduction security DOES NOT over-ride the need for safety, they must work concurrently. 5/21/2018 HFAP A better healthcare survey experience 30
31 Facility Demographic Report (FDR) Not completed properly (unanswered questions) Every question must be answered on the FDR. Construction type not listed in NFPA 220 nomenclature Type I (443) Type I (332) Type II (222) Type II (111) Type II (000) Type III (211) Type III (200) Type IV (2HH) Type V (111) Type V (000) 5/21/2018 HFAP A better healthcare survey experience 31
32 Facility Demographic Report (FDR) Occupancy classification not listed in NFPA nomenclature Healthcare Ambulatory Healthcare Business Other per NFPA 101, 2012 edition 5/21/2018 HFAP A better healthcare survey experience 32
33 Means of Egress Suites Too large Not enough exits (100-0 max. travel distance) Suite barrier walls do not meet corridor requirements Corridor entrance doors do not positively latch Exit signs directing the means of egress from the corridor into and through the suite to get to an exit 5/21/2018 HFAP A better healthcare survey experience 33
34 Signage Exit signs not installed where the path of egress is not readily apparent 5/21/2018 HFAP A better healthcare survey experience 34
35 Signage No Exit signs not installed where a door may be confused as an exit ( Not An Exit not acceptable) 5/21/2018 HFAP A better healthcare survey experience 35
36 Signage No Exit signs must say No Exit with the word No 2 inches tall, and the word Exit 1 inch tall 5/21/2018 HFAP A better healthcare survey experience 36
37 Fire Rated Barriers Unsealed penetrations and improper patching in fire Top of fire rated walls do not go to the deck above. 5/21/2018 HFAP A better healthcare survey experience 37
38 Ceilings Holes and gaps in ceiling larger than 1/8 inch Ceilings that have smoke detectors, heat detectors, or sprinkler heads, must have a monolithic seal to trap all heat and smoke. Any holes or gaps greater than 1/8 inch will impair these devices. 5/21/2018 HFAP A better healthcare survey experience 38
39 Life Safety Drawings Drawings do not include all of the required features Rated walls Smoke compartments Travel distances Boundaries & travel distances for Suites of Rooms Exits (Exit Stairwells, Horizontal Exits, Exit Discharge) Hazardous rooms Smoke partitions Background plans do not accurately reflect as-built conditions 5/21/2018 HFAP A better healthcare survey experience 39
40 Fire Rated Door Assemblies Fire-rated label covered or missing (i.e. painted) Door not fire rated If the Life Safety drawings identify the wall is a fire rated wall, then the door must be appropriately listed as a fire rated door. Surveyors will go by what the LS drawings say. 5/21/2018 HFAP A better healthcare survey experience 40
41 Life Safety - Reminders Doors Corridor doors must latch & open to 90 degrees Staff must be trained not to impede the ability of the door to latch Construction Type The wrong type for the number of stories and sprinkler coverage of the building Sections of the structural steel have no fireproofing. 5/21/2018 HFAP A better healthcare survey experience 41
42 THANK YOU Questions? Contact Alise Howlett at: Phone: 815/ /21/2018 HFAP A better healthcare survey experience 42
FACILITY MANAGEMENT DEFICIENCIES IN CRITICAL ACCESS HOSPITALS (CAH)
FACILITY MANAGEMENT DEFICIENCIES IN CRITICAL ACCESS HOSPITALS (CAH) Presented by: Alise Howlett, Assoc. AIA, CFPE, CHFM Standards Advisor, EM/PE/LS HFAP A better healthcare survey experience 1 FREQUENT
More informationCrosswalk of 2014 HFAP Standards against HFAP Standards Acute Care Hospital Manual
09.00.01 Operations Plan 11.07.01 09.00.02 Hazard Vulnerablity Analysis (HVA) 09.01.01 Safety & Security 11.00.02 New Name 09.01.02 Supplies 09.01.03 482.41(a)(2) Utilities 11.03.21; 11.03.22 09.01.04
More information10/28/2015. Enjoy Your TJC Survey. Bill H. McCully CHFM SASHE. Senior Consultant MSL Healthcare Partners. MSL Healthcare Partners, 2015 PREPARATION
Enjoy Your TJC Survey Bill H. McCully CHFM SASHE Senior Consultant MSL Healthcare Partners PREPARATION 1 Top Eight Most Cited Standards (George Mills) EC News May 2015 Top Citations EC.02.06.01 56% EC.02.05.01
More informationNFPA CODE TESTING & INSPECTION. Requirements & Recommendations for. Licensed Florida Hospitals, Ambulatory Surgery Centers,
NFPA CODE TESTING & INSPECTION Requirements & Recommendations for Licensed Florida Hospitals, Ambulatory Surgery Centers, ICF/IID Healthcare, & In-patient Hospice Facilities per NFPA Life Safety Code 101
More informationLIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE
California Society for Healthcare Engineering SOUTHERN CALIFORNIA SEMINAR LIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE 1 PROGRAM AGENDA Adoption of 2012 LSC CMS Final Rule / Amendments
More informationTIPS FOR BETTER JOINT COMMISSION SURVEYS
TIPS FOR BETTER JOINT COMMISSION SURVEYS Washington Society for Healthcare Engineering September 21, 2011 Yakima, Washington The BASICS Most Failed Standards. Scoring. Electronic S. O. C. I.L.S.M. Building
More informationLife Safety Code NFPA 10 NFPA 13 NFPA 25 NFPA 72 NFPA 90A NFPA 110 NFPA 99 THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #7
THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #7 AGENDA: Life Safety Code Referenced Publications Overview Life Safety Code NFPA 10 NFPA 13 NFPA 25 NFPA 72 NFPA 90A NFPA 110 NFPA 99
More informationUNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY
Revision No.: 11 Page 1 of 12 I. PURPOSE This procedure establishes a tool to help maintain a safe environment for all patients, visitors and staff by evaluating the loss of a life safety feature during
More informationLife Safety Code Common Discepancies Course# LSC102. EZpdh.com All Rights Reserved
Life Safety Code Common Discepancies Course# LSC102 EZpdh.com All Rights Reserved 1. K147 Electrical - Electrical wiring and equipment shall be in accordance with NFPA 70, National Electrical Code. 9.1.2
More informationOther EC and LS documents may be requested by surveyors, as needed, throughout the survey.
Documentation required by the Hospital Accreditation program Life Safety (LS) and selected Environment of Care (EC) standards is presented in the following pages. These documents will be reviewed by the
More informationTHE HEALTHCARE ENVIRONMENT UPDATE. Anne M. Guglielmo, Engineer Engineering Department The Joint Commission. Copyright, The Joint Commission
2013 THE HEALTHCARE ENVIRONMENT UPDATE Anne M. Guglielmo, Engineer Engineering Department The Joint Commission Standard/NPSG 2012 Non Compliance 2013 Non Compliance (1 st Six Months) RC.01.01.01 61% 55%
More informationAgency for Health Care Administration
Page 1 of 92 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0100 - General Requirements
More informationE25 (D) Automatic controls for general means of egress lighting
Adhoc Health Care MOE Study Group Study Group Report of Adhoc Meeting July 12&13, 2012 Possible Public Comments E25, E69, E74, G71, G77/G80 Study Group E25 (D) Automatic controls for general means of egress
More informationAgency for Health Care Administration
Page 1 of 94 ST - K0000 - Initial Comments Title Initial Comments Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0100 - General
More informationIowa State Fire Marshal
Iowa State Fire Marshal LIFE SAFETY CODE REQUIREMENTS LONG TERM CARE Kyle R. Gorsh, Special Agent in Charge Iowa Department of Public Safety State Fire Marshal Division 2012 LSC & Applicable Standards
More informationLIFE SAFETY & FIRE PREVENTION MANAGEMENT PLAN
Title/Description: Life Safety & Fire Prevention Management Department: Facilities Management Personnel: All Effective Date: 5/97 Revised: 7/00, 7/01, 7/02, 7/03, 7/04, 7/05, 7/08 LIFE SAFETY & FIRE PREVENTION
More informationCMS Announcement 3/27/2017. Adoption of 2012 Life Safety Code Health Care Facilities Code. Kenneth Daily, LNHA
Adoption of 2012 Life Safety Code Health Care Facilities Code Kenneth Daily, LNHA kenn@qissurvey.com CMS Announcement May 2016 Life Safety Code Health Care Code Effective July 5 th Numerous changes many
More informationInterim Life Safety Measures. Healthcare Construction Certificate - Level 1
Interim Life Safety Measures Purpose of Interim Life Safety Management BASIC SAFETY: During renovations projects in healthcare occupancies, the basic level of protection for the occupants must be maintained
More information1. Are there any annual sprinkler head inspection forms available? No, there are none available at this time.
Sprinkler 1. Are there any annual sprinkler head inspection forms available? No, there are none available at this time. 2. Does the annual sprinkler head inspection have to be done by a licensed technician
More informationTop 8 Findings & SAFER Matrix for the 2017 ACE Summit & Expo
Top 8 Findings & SAFER Matrix for the 2017 ACE Summit & Expo February 20, 2017 Atlanta, GA Larry F. Rubin CHFM, CHSP, CPE, CEM Life Safety Code Surveyor The Joint Commission Engineering Department 2015-1
More informationInterim Life Safety Measures (ILSM)
1 Interim Life Safety Measures (ILSM) Frank D. Rudilosso P.E., M.Eng, CHSP Manager Facilities Regulatory Life Safety Compliance frr9035@nyp.org Tom Singh MPH, MHA, CHSP Field Director Facilities Regulatory
More informationPresented by: Brad Keyes, CHSP Senior Consultant Keyes Life Safety Compliance, LLC
Presented by: Brad Keyes, CHSP Senior Consultant Keyes Life Safety Compliance, LLC Changes to Life Safety Compliance Healthcare leaders will have to deal with many changes in Life Safety compliance when
More informationAgency for Health Care Administration
Page 1 of 92 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS Type Memo Tag FED - KA100 - General Requirements - Other Title
More informationTaming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes JENSEN & HALSTEAD LTD.
Taming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes Comparing the Codes: NFPA 101 Life Safety Code (2000) (NFPA) International Building Code (2012) (IBC) Chicago
More informationFire & Life Safety Code Compliance. Common Safety Deficiencies and Tips for Compliance for Long Term Care and Skilled Nursing Facilities
Fire & Life Safety Code Compliance Common Safety Deficiencies and Tips for Compliance for Long Term Care and Skilled Nursing Facilities LTC, Skilled Nursing Facilities COMMON LIFE SAFETY DEFICIENCIES
More informationAgency for Health Care Administration
Page 1 of 100 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS CFR Type Memo Tag FED - KA100 - General Requirements - Other
More informationTop (15) Life Safety Code Deficiencies and Tips for Compliance (10/01/2011 thru 02/22/2012)
1. K62 Automatic Sprinkler Systems - Automatic sprinkler systems are continuously maintained in reliable operating condition and are inspected and tested periodically. 18.7.6, 19.7.6, 4.6.12, NFPA 13,
More informationEmergency Planning for Institutional Facilities
Emergency Planning for Institutional Facilities Pacific ADA Emergency Preparedness Webinars Presented by: Kimberly Paarlberg, ICC Based on the 2015 edition of the International Building Code (IBC) and
More informationNew DATE OF BLDG. PERMIT OR PLAN APPROVAL: SURVEYOR (SIGNATURE) TITLE OFFICE DATE REVIEW AUTHORITY OFFICIAL (SIGNATURE) TITLE OFFICE DATE
DEPARTMENT OF HEALTH & HUMAN SERVICES CENTERS FOR MEDICARE & MEDICAID SERVICES FIRE SAFETY SURVEY REPORT - AMBULATORY SURGICAL CENTERS Medicare 1. (A) PROVIDER NUMBER Identifying information as shown in
More informationChanges to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH)
Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH) The following represents a review of the Life Safety chapter of the new 2018 Joint Commission CAMH manual for
More informationFirst Aspen Federal Regulation Set: K LSC 2000 Health Existing
First Aspen Federal Regulation Set: K 01.01 LSC 2000 Health Existing K 0000 Title CFR Type INITIAL COMMENTS Memo K 0011 If the building has a common wall with a nonconforming building, the common wall
More informationOhio Department of Health NFPA 2012 Life Safety Code Tips Sheet
Ohio Department of Health NFPA 2012 Life Safety Code Tips Sheet This document is used for frequently cited Life Safety Code violations. This is not an all-inclusive list and is intended for reference only.
More informationTHE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #6
THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #6 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1 QUESTIONS How To Ask a Question: POLLING There will be occasional
More informationNFPA 101 and NFPA 99, 2012 Editions Code Update. where art meets engineering
NFPA 101 and NFPA 99, 2012 Editions Code Update where art meets engineering Austin Dallas Denver Houston Kansas City Miami Nashville Phoenix Richmond Washington DC NFPA 101 and NFPA 99 where art meets
More informationAgency for Health Care Administration
Page 1 of 130 ST - K0000 - Initial Comments Title Initial Comments Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. Based on the LSC
More informationThe Physical Environment Portal: Module 5, LS Leadership
The Physical Environment Portal: Module 5, LS.02.01.10 - Leadership Fire Safety: Background Fire safety impacts both the lives of the occupants and the physical structures. In the early 1900 s many buildings
More informationBarrier Management- Defending the Safety of Patients, Visitors, & Staff
Barrier Management- Defending the Safety of Patients, Visitors, & Staff About Your Speaker Rick Tinsley: 3 Years as Healthcare Construction Electrician 38 Years in Healthcare Facility Maintenance 13 Years
More information2012 Life Safety and Health Care Facility Codes - Door Inspections and Other Critical Inspection, Testing and Maintenance
2012 Life Safety and Health Care Facility Codes - Door Inspections and Other Critical Inspection, Testing and Maintenance Will begin at 1 pm Housekeeping Announcements Problems during the call? Press *0
More informationTennessee Department of Health Bureau of Health Licensure and Regulations Division of Health Care Facilities
Tennessee Department of Health Bureau of Health Licensure and Regulations Division of Health Care Facilities 1 Colby Henson Fire Safety Supervisor 665 Mainstream Drive 2nd floor 615-806-4798 Colby.Henson@tn.gov
More informationK SURVEY FOR DATE OF PLAN APPROVAL SURVEY UNDER
DEPARTMENT OF HEALTH AND HUMAN SERVICES CENTERS FOR MEDICARE & MEDICA SERVICES FIRE SAFETY SURVEY REPORT - HEALTH CARE Form Approved OMB No. 0938-0242 1. (A) PROVER NUMBER 1. (B) MEDICA I.D. NO. 1. HOSPITAL
More informationCenter for Clinical Standards and Quality /Survey & Certification Group
DEPARTMENT OF HEALTH & HUMAN SERVICES Centers for Medicare & Medicaid Services 7500 Security Boulevard, Mail Stop C2-21-16 Baltimore, Maryland 21244-1850 Center for Clinical Standards and Quality /Survey
More informationTHE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5
THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5 AGENDA: Ambulatory Health Care & Business Occupancies Definitions / Examples Mixed & Contiguous Occupancies Ambulatory Health Care &
More informationMeasures (ILSM) Process
Managing the Interim Life Safety Measures (ILSM) Process 1 A Program for The Texas Association of Healthcare Facility Management Monday, April 30, 2012 Robert H. Bartels, CHFM CHSP CHEP SASHE President,
More informationDanilo B. Concepcion, CBNT, CCHT-A Operations Manager St. Joseph Hospital Renal Services
Life Safety Code Danilo B. Concepcion, CBNT, CCHT-A Operations Manager St. Joseph Hospital Renal Services danilo.concepcion@stjoe.org 714-771-8944 The findings and conclusions in this presentation are
More informationDeveloping a Healthcare Facility Fire Door Inspection Program
Developing a Healthcare Facility Fire Door Inspection Program WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio QUESTIONS How To Ask a Question: 1 POLLING There will be occasional interactive
More informationFIRE AND SAFETY PROJECT REVIEW REPORT
1. A001 2. A001 3. A001 4. D102/103 5. A102/103 *VA enforces/applies the National Fire Protection Association (NFPA) 101 (current edition is 2015) and not the International Building Code (IBC). Ideally
More informationCompliance w/ the 2012 Life Safety Code
Compliance w/ the 2012 Life Safety Code Implications of the 2012 NFPA Code Set for Existing & New ASCs William E. Lindeman, AIA http://www.weldesigns.com Financial Interest Disclosure The presenter provides
More informationNirmal Chandra Sinha. Supposed to complete(dd/ MM/YYYY) Comments after Physical Inspection
Factory Name Address Fire Safety Follow up INTIMATE APPARELS LTD Karnaphuli EPZ, Plot no. 91-93, rth Patenga Date 05/20/2014 Date Report Received 11-August/15 Date of 1 st Follow-up 08-vember/15 Date of
More informationEC 5.10 FIRE PREVENTION MANAGEMENT
EC 5.10 FIRE PREVENTION MANAGEMENT The organization manages fire safety risks. 1 The organization develops and maintains a written management plan describing the processes it implements to effectively
More information2016 Joint Commission Update
2016 Joint Commission Update Bert M. Gumeringer, MBA, CHFM, FASHE Asst. Vice President-Facilities Operations Texas Children s Hospital August 12, 2016 11:30am-12:30pm Top 10 Findings Comparison-2015 vs.2016
More information2017 Accreditation Updates
2017 Accreditation Updates Tennessee Healthcare Engineers Association 2017 Spring Conference Pickwick Landing State Park Counce, Tennessee 38326 Presented May 17, 2017 By Ken Gregory Vice President, Accreditation
More informationAgency for Health Care Administration
Page 1 of 41 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K0011 - LIFE SAFETY CODE STANDARD If the building has a common wall with a nonconforming building, the common
More informationPublic Health Fax: Web Site:
State of Alabama Department of Public Health Fax: 334-206-5890 Web Site: www.adph.org.facmgmt Mike Free Building Construction Specialist Technical Services Unit Office of Facilities Management 334-206-5221
More informationPublic. Mike Free Health. State of Alabama Department of
State of Alabama Department of Mike Free Building Construction Specialist Technical Services Unit Office of Facilities Management Public 334-206-5221 334-206-5177 Health Fax: 334-206-5890 Web Site: www.adph.org.facmgmt
More informationPRINTED: 06/09/2017 FORM APPROVED CENTERS FOR MEDICARE & MEDICAID SERVICES OMB NO (X2) MULTIPLE CONSTRUCTION A. BUILDING 03 - A BUILDING
SUMMARY PROVER'S PLAN OF CORRECTION K 000 INITIAL COMMENTS K 000 A Life Safety Code Survey was conducted by the State Fire Marshal beginning on May 9th, 2017 and ending on May 10th, 2017. Adair Acute Care
More informationFIRE SAFETY MAINTENANCE INFORMATION for Agricultural Livestock Structures
FIRE SAFETY MAINTENANCE INFORMATION for Agricultural Livestock Structures Building Name: Building Address: Plan Prepared By (please print): Date: Revision Date Comments Approval FIRE SAFETY MAINTENANCE
More informationInterim Life Safety Assessments and Infection Prevention Assessments
Interim Life Safety Assessments and Infection Prevention Assessments 1 Healthcare Construction ILSM and ICRAs PRESENTED BY Bob Dubiel, CHFM, CHC -Mayo Clinic Health System NWWI -Projects and Construction
More informationBuilding Codes & Standards for Healthcare. Healthcare Construction Certificate - Level 1
Building Codes & Standards for Healthcare Building Codes and Standards AHJs Codes Defend in Place Walls Sprinklers Fire Alarm Important Dates for Healthcare Facilities 7/5/16 NFPA Life Safety Code 101
More informationThe Surveyor s Perspective. Understanding How The Joint Commission Surveyors Conducts Surveys
The Surveyor s Perspective Understanding How The Joint Commission Surveyors Conducts Surveys Tim Markijohn MBA\MHA, CHFM, CHE Field Director, Life Safety Learning Objectives At the conclusion of this presentation,
More informationFIRE SAFETY SURVEY REPORT 2000 CODE - HEALTH CARE Medicare Medicaid
DEPARTMENT OF HEALTH AND HUMAN SERVICES CENTERS FOR MEDICARE & MEDICA SERVICES FIRE SAFETY SURVEY REPORT - HEALTH CARE Medicare Medicaid 1. (A) PROVER NUMBER PART I Life & Safety Code, New and Existing
More informationWritten Fire Safety Plans
Written Fire Safety Plans 2012 LSC KATHARINE ACHOR SEPTEMBER 2016 NFPA Standard: 2012 NFPA 101, 19.1.1.3.1 All health care facilities shall be designed, constructed, maintained, and operated to minimize
More informationAgency for Health Care Administration
Page 1 of 51 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K0130 - MISCELLANEOUS Title MISCELLANEOUS OTHER LSC DEFICIENCY NOT ON 2786 FED - K9999 - FINAL OBSERVATIONS Title
More informationThis policy may also be used for routine work orders that are Life Safety in nature and cannot be completed within 45-days.
Policy: It is the policy of the St. Joseph Mercy Health System (SJMHS- Ann Arbor, Oakland, Livingston, Brighton, Chelsea and St. Mary Mercy Hospital- Livonia) and associated satellite facilities to assure
More informationAre there any policies regarding outlets that contain USB ports?
Answers to the Questions Mark J. Blackburn, P.E., CFPS February, 2016 Question 1 Are there any policies regarding outlets that contain USB ports? There is no direct reference in code about these types
More informationFIRE SAFETY AND EVACUATION PLANNING FOR ASSISTED LIVING FACILITIES AND NURSING HOMES
FIRE SAFETY AND EVACUATION PLANNING FOR ASSISTED LIVING FACILITIES AND NURSING HOMES West Metro Fire Rescue Life Safety Division 433 South Allison Parkway Lakewood, Colorado 80226 (303) 989-4307 Fax (303)
More informationPlan Review Check List Fire Alarm System
Plan Review Check List Fire Alarm System EXCELSIOR FIRE DISTRICT 241OO SMITHTOWN ROAD SHOREWOOD, MN 55331 Alarm system must be installed according to NFPA 72, 2010 Edition, National Fire Alarm and Signaling
More informationDEALING WITH FIRE SAFETY
DEALING WITH FIRE SAFETY Personal Care Homes And Assisted Living Facilities Presented by: Harold D. Hicks, P.E., FSFPE Fire Protection Engineer 1 Atlantic Code Consultants 2 Our Objectives Recognize the
More informationRevised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required*
1.0 Description of Services Required: Revised March 2015 Fire Alarm Systems Verification Schedule I(A) Services *Manditory Site visit required* Perform the annual fire alarm system and sprinkler system
More informationTHE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2
THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1 QUESTIONS How To Ask a Question: POLLING There will be occasional
More informationNFPA 101 Code Update from 2012 Edition to the 2015 Edition
NFPA 101 Code Update from 2012 Edition to the 2015 Edition Presented by: Gary Furdell AHCA Fire Protection Specialist 1 2 2012 Update to 2015 Chapter 18 New Health Care Occupancies 4 18.1.3.2 Atrium walls
More informationChanges to Environment of Care and Life Safety Chapters Related to Life Safety Code Updates
Issued June 28, 207 Changes to Environment of Care and Life Safety Chapters Related to Life Safety Code Updates Environment of Care (EC) Chapter Nursing Care Center (NCC) Accreditation Program Standard
More informationFire/General Safety Review Program Key Performance Indicators Environmental Health and Safety
Fire/General Safety Review Program Key Performance Indicators Environmental Health and Safety Fire and CO Detection Systems Fire alarm pull station obstructed. Annunciation panel obstructed. Lack of approved
More informationGENERAL AREAS OF INSPECTION
This information is intended to assist you in preparation for the annual high-rise inspection. This is not a complete list and the Inspector may identify other conditions or issues in the building that
More informationCity of South Salt Lake Fire Code Training Exiting, Egress Systems and Egress Control
City of South Salt Lake Fire Code Training Exiting, Egress Systems and Egress Control 11-27-12 This document is designed as a summary guide using IFC requirements for the provisions associated with exiting,
More informationPresented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC Web: Lauzon-LSC.com
Presented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC 262-945-4567 Lauzon.lsc@gmail.com Web: Lauzon-LSC.com 1 Wis Professional Engineer Experienced Facility Director Experienced AHJ WHEA Code
More informationAgency for Health Care Administration
Page 1 of 133 ST - Y0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - Y1001 - Awareness of the
More informationFIRE SAFETY SURVEY REPORT AMBULATORY SURGICAL CENTERS (ASC) & END STAGE RENAL DISEASE (ESRD) MEDICARE
DEPARTMENT OF HEALTH AND HUMAN SERVICES CENTERS FOR MEDICARE & MEDICA SERVICE Form Approved OMB Exempt FIRE SAFETY SURVEY REPORT AMBULATORY SURGICAL CENTERS (ASC) & END STAGE RENAL DISEASE (ESRD) MEDICARE
More informationAgency for Health Care Administration
Page 1 of 21 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0300 - Other
More informationIs the address of your property clearly visible and marked in large numbers that can be easily seen from the street?
PRE-INSPECTION CHECKLIST THE FOLLOWING INFORMATION IS PROVIDED TO YOU TO ASSIST YOUR FACILITY IN BECOMING COMPLIANT WITH THE NEW YORK STATE FIRE CODE, LOCAL LAWS, AND ORDINANCES GOVERNING THE TOWN OF BABYLON.
More informationRenovation Program. Renovation Program GENERAL
Renovation Program GENERAL This program provides guidance and protocols for renovation projects in occupied, operational acute hospitals. Team building is essential to quality control and HFD Services
More informationC. None (No sprinkler system) K3 E. NUMBER OF BEDS CERTIFIED FOR MEDICAID
DEPARTMENT OF HEALTH AND HUMAN SERVICES CENTERS FOR MEDICARE & MEDICAID SERVICES FIRE SAFETY SURVEY REPORT - 2000 LIFE SAFETY CODE Intermediate Care Facilities for the Mentally Retarded LARGE PART I Figure
More informationASHE Advocacy Team. Q4 ASHE Advocacy Liaison Webinar 12/7/16 12/7/16. Tim Adams, FASHE, CHFM, CHC Director of Leadership Development
Q4 ASHE Advocacy Liaison Webinar 12/7/16 ASHE Advocacy Team Chad E. Beebe, AIA, CHFM, CFPS, CBO, SASHE Deputy Executive Director of Advocacy cbeebe@aha.org Tim Adams, FASHE, CHFM, CHC Director of Leadership
More informationEstablished /10/2015. Doran Pruisner Dan Wood
Established 1911 Doran Pruisner Dan Wood The International Fire Code, 2009 Edition shall apply to all occupancies except for those that are explicitly excluded by these provisions. 1 Buildings built between
More informationFIRE SAFETY SURVEY REPORT 2000 CODE - HEALTH CARE Medicare Medicaid
DEPARTMENT OF HEALTH AND HUMAN SERVICES CENTERS FOR MEDICARE & MEDICA SERVICES FIRE SAFETY SURVEY REPORT - HEALTH CARE Medicare Medicaid 2. NAME OF FACILITY 2. (A) MULTIPLE CONSTRUCTION (BLDGS) 3. SURVEY
More informationAgency for Health Care Administration
Page 1 of 98 ST - Y0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. Based on the LSC surveyor's determination
More informationResidential-based Care Facility R-4 Guideline
Moreno Valley Fire Department Fire Prevention Bureau Residential-based Care Facility R-4 Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: April 7, 2017 Residential-based Care
More informationSAF-BCF SECOND REVISIONS WITH STATEMENTS
Page 196 of 331 32.2.1.3 ] Second Revision No. 153-NFPA 101-2013 [ New Section after 32.2.1.4 Multiple-Level Buildings. For purposes of applying requirements of this chapter that utilize the term level
More informationFIRE INSPECTORS GUIDELINES FOR PLAN REVIEWS AND INSPECTIONS OF NEW CONSTRUCTION / ADDITIONS AND CHANGE OF OCCUPANCY
FIRE INSPECTORS GUIDELINES FOR PLAN REVIEWS AND INSPECTIONS OF NEW CONSTRUCTION / ADDITIONS AND CHANGE OF OCCUPANCY PLAN REVIEWS SITE PLANS: 1) Access to buildings (Volume V NC Building Code sections 602.6.1
More informationJOINT COMMISSION PREPAREDNESS / STATEMENT OF CONDITIONS DRAWINGS WSSHE SOUTHWEST CHAPTER NOVEMBER 19, 2015
JOINT COMMISSION PREPAREDNESS / STATEMENT OF CONDITIONS DRAWINGS WSSHE SOUTHWEST CHAPTER NOVEMBER 19, 2015 AGENDA INTRODUCTION OF PRESENTERS SOC VS. FIRE & LIFE SAFETY DRAWINGS HAZARDOUS AREAS VS. INCIDENTAL
More informationAgency for Health Care Administration
Page 1 of 75 ST - K0000 - Initial Comments Title Initial Comments Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0001 - OTHER
More informationAgency for Health Care Administration
Page 1 of 34 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0001 - OTHER
More informationNFPA 101 Life Safety Code Culture change 2012
NFPA 101 Life Safety Code Culture change 2012 Produced by Kansas Fire Marshal April, 2012 On March 9, 2012 Centers for Medicare & Medicaid Services implements a policy where they have formally adopted
More informationThe Healthcare Environment Update
2017 The Healthcare Environment Update John Maurer, SASHE, CHFM, CHSP Engineering Department The Joint Commission Engineering Department 2017-1 Most Cited Standards Standard 2015 % Noncompliance 2016 %
More informationSafety & Risk Management Policies and Procedures
Title: Date: July 2014 Safety & Risk Management Policies and Procedures Rationale: The fire safety policy plan is necessary to create a campus-wide system for preventing and/or responding to potential
More informationNFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES
NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES Sharon S. Gilyeat, P.E., Principal Koffel Associates, Inc. www.koffel.com sgilyeat@koffel.com Expertly Engineering Safety From Fire
More information2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.
2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is
More informationINITIAL FIRE SAFETY ASSESSMENT - EXPANSION
INITIAL FIRE SAFETY ASSESSMENT - EXPANSION 228/1, Tin Sharak, Luxmipura, Joydevpur, Gazipur Joydebpur, Gazipur The Alliance for Bangladesh Worker Safety Page 1/18 Introduction to the Report The following
More informationUniversity of California, Davis Laboratory Self-Inspection Checklist
University of California, Davis Laboratory Self-Inspection Checklist Principal Investigator/Laboratory Supervisor: Laboratories Reviewed: Date: Reviewer: Revised 11/2014 I. SAFETY PROGRAM ADMINISTRATON
More informationOsceola County Department of Fire Rescue and Emergency Medical Services
St. Number Dir Street Name Street Type Inspected Time of Day to be Re-inspected Zip Code Occupancy Type Emergency Contact Phone (Inc. Area Code) Building Owner Building Owner Mailing Address Bldg. Owner
More informationGROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES
[B] APPENDIX SR GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES The provisions contained in this appendix are adopted by the Building Codes Division of the State of Oregon. SECTION SR101 GENERAL
More information