1 E-PDD Duct Smoke Installation Sheet E-PDD operation The duct smoke detector's primary purpose is to provide early warning of an impending fire and shut down the HVAC unit in order to prevent smoke from circulating throughout the building. The duct smoke detector is designed for use in duct applications where temperatures can exceed standard detector capabilities. Air is introduced to the duct smoke detector's sensing chamber through a sampling that extends into the HVAC duct and is directed back into the ventilation system through an exhaust. The difference in air pressure between the two s pulls the sampled air through the sensing chamber. When a sufficient amount of smoke is detected in the sensing chamber, the duct smoke detector notifies the fire alarm control panel. The device address is set using the two rotary switches located on the front of the unit. One device address is required. The detector is capable of performing comprehensive selfdiagnostics and storing the results. In installations where the duct smoke detector s controls and indicators are hidden from view, a remote test station or an LED indicator can be connected to the detector to provide these functions. Jumper setting operation The following jumper settings determine the operation of the detector. Jumper setting Jumper settings 3 1 JP3 Setting Operation Description 1- Alarm Factory Default: Configures the detector for alarm latching operation -3 Supervisory Configures the detector for supervisory operation LED operation The detector provides two LEDs, visible from the front side of the detector, that show its status. LED Power LED Alarm/active LED Description Off when the detector is in the alarm state Flashes intermittently when the detector is in the normal state Indicates the detector is in the alarm/active state as follows: Flashes at a continuous rate if the first detector is in alarm/active Flashes intermittently if not the first detector in alarm/active P/N REV 1.0 ISS 05OCT07 1 of 7

2 E-PDD installation WARNINGS The duct smoke detector is not intended as a substitute for open area protection. This detector will not operate without electrical power. As fires frequently cause power interruption, you should discuss further safeguards with your local fire protection specialist. The duct smoke detector will not operate as designed outside of the listed electrical and environmental specifications. The duct smoke detector will not sense smoke unless the ventilation system is operating and the sensor s cover is properly installed. The duct smoke detector may not operate as designed unless installed in accordance with these instructions and all applicable national and local codes as determined by the local authority having jurisdiction. Note: Read these instructions thoroughly before installing. In addition to this document, important information can be found in Technical Bulletin P/N If the air velocity does not fall within the specified range, relocate the detector and seal the hole in the HVAC duct. Refer to Technical Bulletin P/N for additional information pertaining to installation locations. Select the appropriate sampling : Select a sampling that extends at least two-thirds across the width of the duct. For duct widths greater than 36 inches, use a sampling that is longer than the width of the duct. s are available in the following lengths: Model SD-T8 SD-T18 SD-T4 SD-T36 SD-T4 SD-T60 SD-T78 Description 8-inch sampling 18-inch sampling 4-inch sampling 36-inch sampling 48-inch sampling 60-inch sampling 78-inch sampling Installation guidelines SD-T10 10-inch sampling To ensure correct operation, install the duct detector using the following guidelines: Install the duct smoke detector on a flat section of HVAC duct between six and ten duct widths from any bends or obstructions. Install supply-side detectors at a point downstream from the supply fan and after the air filter. Install return-side detectors at a point before the return air stream is diluted by outside air. Verify the duct air velocity In order to verify airflow direction and velocity, air must be moving through the HVAC system. To assemble the detector: 1. Assemble the duct smoke detector as shown in the illustration.. Rotate the air sampling so the inlet holes face the direction of airflow. 3. The sampling is normally installed from the rear, but it can also be installed from the front of the detector as shown in the illustration. This method requires that you remove the detector cover. To verify the duct air velocity: 1. Drill a small hole at the point where the duct smoke detector is being installed.. Using the SD-VTK Air Velocity Test Kit and a suitable air velocity meter, verify that the air velocity in the HVAC duct falls within the specified operating range of the detector and note which direction the air flows. of 7 P/N REV 1.0 ISS 05OCT07

3 Duct detector assembly socket Exhaust socket 5. Mount the duct smoke detector on the HVAC duct and secure it using two sheet metal screws provided. 6. If using an air sampling that is longer than the width of the duct, cut the so that approximately one inch of the extends through the duct. Seal the opening around the with an approved duct sealant as shown in the illustration. Exhaust Duct detector installation Thin gasket Thick gasket HVAC duct Coupling (ordered separately) Plug installation #10 sheet metal screw (X) connector support HVAC duct Exhaust (fully assembled) Sealant To install the detector: 1. Attach the drill template to the HVAC duct at desired mounting location.. Drill (or punch) the mounting holes where indicated. Note: s longer than 36 inches must be supported at both ends of the duct. 3. If using an air sampling that is longer than the width of the duct, drill a 3/4-inch hole on the opposite side of the duct for to pass through. 4. Remove any rough edges from the holes. Plug 36 in 7. Verify that all field wiring is free of opens, shorts, and ground faults. P/N REV 1.0 ISS 05OCT07 3 of 7

4 8. Make all wiring connections as shown in E-PDD wiring. 9. Set the module address as follows: Use a screwdriver to adjust the two rotary switches on the front of the module. Set the TENS rotary switch (0 through 1) for the 10s and 100s digit and the ONES rotary switch for the 0 through 9 digit. For example: device address 1, set TENS rotary switch to and set the ONES rotary switch to 1. Refer to E-PDD specifications for available address numbers. Duct detector address 3. If the air pressure differential measured does not fall within the specified operating range of the detector, make sure the sampling air holes are not obstructed and are facing the HVAC system airflow. Air pressure differential HVAC duct Exhaust opening Insert screwdriver here Set jumper JP3 to appropriate position. Refer to E-PDD operation. 11. Verify the air pressure differential value falls within the specified operating range of the detector in accordance with procedures specified in E-PDD maintenance and testing. 1. After completing installation of the duct smoke detector, test the detector to ensure it is operating correctly in accordance with procedures specified in E- PDD maintenance and testing. E-PDD maintenance and testing Verify the air pressure differential: In order to verify air pressure differential, air must be moving through the HVAC system. To verify the air pressure differential: 1. Connect a suitable air pressure differential meter to the sampling and exhaust openings as shown in illustration.. Verify that the air pressure differential measured falls within the specified operating range of the detector. opening Testing the duct smoke detector Air pressure differential meter After completing installation of the duct smoke detector, test the detector to ensure it is operating correctly prior to leaving the site. For details, refer to Technical Bulletin P/N Replacement parts The following table lists the replacement parts for the duct smoke detector. Model E-SDPCB Description Cleaning the duct smoke detector PCB replacement kit for duct smoke detector Clean the duct smoke detector when it becomes 80% to 99% dirty or sooner if conditions warrant. Caution: Before cleaning the duct smoke detector, notify the proper authorities that the fire alarm system is undergoing maintenance and take steps to prevent the control panel from responding to a false alarm. 4 of 7 P/N REV 1.0 ISS 05OCT07

5 To clean the duct smoke detector: 1. Disable the detector/zone to prevent false alarms.. Remove the detector s cover then power down the detector by disconnecting the SLC wiring. 3. Using a vacuum cleaner, clean compressed air, or a soft bristle brush, remove loose dirt and debris from inside the detector housing and cover. 4. Remove dirt and other contaminants from the gasket on the detector s cover using isopropyl alcohol and a lint-free cloth. 5. Squeeze the retainer clips on both sides of the optic housing then lift the housing away from the printed circuit board. 6. Gently remove dirt and debris from around the optic plate and inside the optic housing. 7. Replace the optic housing and detector cover, then connect the SLC wiring. 8. Test the detector and verify sensitivity. For details, refer to Technical Bulletin P/N Duct detector cleaning HVAC duct housing Optic plate Retainer clip Optic housing P/N REV 1.0 ISS 05OCT07 5 of 7

6 E-PDD wiring Wire in accordance with NFPA 7 and CAN/ULC S54. Be sure to observe the polarity of the terminals on the terminal block as shown in the diagram. Duct detector wiring Remote alarm/active indicator [1] Alarm/active + Auxiliary equipment [] or Remote test station [1] Alarm/active Test SLC( ) SLC( + ) SLC( ) SLC( + ) JP3 Power indicator Alarm indicator Notes [1] No more than one remote test station or LED indicator can be connected to the detector at the same time. Wiring is unsupervised. Maximum wire resistance is 10 ohms per wire. [] Power-limited when connected to a power-limited source. If connected to a nonpower-limited source, all power-limited wiring in box must use FPL, FPLR, or FPLP cable or equivalent per NEC. 6 of 7 P/N REV 1.0 ISS 05OCT07

7 E-PDD specifications Communication line voltage Operating current Normal Alarm Inrush Common alarm relay/auxiliary equipment Air velocity Air pressure differential Smoke sensitivity range Smoke detection method Alarm test response time Dimensions Operating environment Temperature Humidity Wire size address Maximum 0 V peak-to-peak 45 µa 45 µa 1 ma Unsupervised and power-limited Quantity: 1 Type: Form C Ratings:.0 A at 30 VDC (resistive) or 0.5 A at 15 VAC (resistive) 100 to 4,000 ft./min to 1.00 inches of water 0.79 to.46%/ft. obscuration Photoelectric (light scattering principle) 5 seconds 8.70 x 5.45 x 1.90 inches -0 to 158 F (-9 to 70 C) 0 to 93% RH, noncondensing 14 to AWG wire 01 to 64 (64 point control panel) 01 to 17 (17 point control panel) Accessories SD-TRM SD-TRK SD-MAG SD-VTK R-LED Remote test-reset station, magnetic Remote test-reset station, keyed Test magnet kit Air velocity test kit Remote LED alarm indicator P/N REV 1.0 ISS 05OCT07 7 of 7

FX-PDD Duct Smoke Detector Installation Sheet

FX-PDD Duct Smoke Detector Installation Sheet FX-PDD Duct Smoke Detector Installation Sheet Table 2: LEDs LED Power LED Alarm/active LED Off when the detector is in the alarm state. Flashes intermittently when the detector is in the normal state.

More information

Installation Instructions

Installation Instructions CRSMKKIT002A00 CRSMKSEN002A00 FIELDINSTALLEDSMOKEDETECTORS FOR MEDIUM ROOFTOP UNITS 15 to 25 TONS Installation Instructions TABLE OF CONTENTS PACKAGE CONTENTS... 1 SAFETY CONSIDERATIONS... 1 GENERAL...

More information

Application Data ! WARNING FACTORY INSTALLED SMOKE DETECTORS FOR SMALL AND MEDIUM ROOFTOP UNITS 2TO25TONS TABLE OF CONTENTS PART NUMBERS

Application Data ! WARNING FACTORY INSTALLED SMOKE DETECTORS FOR SMALL AND MEDIUM ROOFTOP UNITS 2TO25TONS TABLE OF CONTENTS PART NUMBERS FACTORY INSTALLED SMOKE DETECTORS FOR SMALL AND MEDIUM ROOFTOP UNITS 2TO25TONS Application Data TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 PART NUMBERS... 1 APPLICABLE UNITS... 1 GENERAL... 2 DESCRIPTIONS...

More information

INSTALLATION AND MAINTENANCE

INSTALLATION AND MAINTENANCE INSTALLATION AND MAINTENANCE DH100ACDCIA & DH100ACDCPA Air Duct Smoke Detector Before Installing ULC standard CAN/ULC-S524-M91 Standard For The Installation Of Fire Alarm Systems should be referenced for

More information

D350PL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS

D350PL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS D350PL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS I56-1975-004R Before installing detectors, please thoroughly read the NEMA Guide for

More information

DH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range

DH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range INSTALLATION AND MAINTENANCE INSTRUCTIONS DH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range 3825 Ohio Avenue, St. Charles, Illinois 60174 800-736/7672, FAX: 630-377-6495 Before

More information

DETECTOR TEST LOG. Detector Identification Information DHX-501 INTELLIGENT AIR DUCT SMOKE DETECTOR HOUSING INSTALLATION AND MAINTENANCE INSTRUCTIONS

DETECTOR TEST LOG. Detector Identification Information DHX-501 INTELLIGENT AIR DUCT SMOKE DETECTOR HOUSING INSTALLATION AND MAINTENANCE INSTRUCTIONS TEST LOG Detector Identification Information Manufacturer and Serial Date Detector Model: Number: Installed: Description of Detector Location: Test Results and Maintenance Data Date Test Test Maintenance

More information

Installation Manual: PAD100-DUCTR Analog Addressable Duct Detector

Installation Manual: PAD100-DUCTR Analog Addressable Duct Detector Installation Manual: PAD100-DUCTR Analog Addressable Duct Detector NOTICE TO THE INSTALLER This manual provides an overview and the installation instructions for the PAD100-DUCTR module. This module is

More information

Air Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608)

Air Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608) FORM ASX-40020 INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS SL-2000 Series Smoke Detectors, Model EXSAA and EXSAB (Ionization), EXSAG and EXSAH (Photoelectric) Air Specialties Express, 448 S. Main

More information

D350RPL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS

D350RPL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS D350RPL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS Before installing detectors, please thoroughly read the NEMA Guide for Proper Use

More information

DH100LP Air Duct Smoke Detector with Extended Air Speed Range

DH100LP Air Duct Smoke Detector with Extended Air Speed Range INSTALLATION AND MAINTENANCE INSTRUCTIONS DH100LP Air Duct Smoke Detector with Extended Air Speed Range 3825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 The Innovair DH100LP

More information

DH100ACDCI Ionization Air Duct Smoke Detector

DH100ACDCI Ionization Air Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS Ionization Air Duct Smoke Detector Before Installing Please thoroughly read the System Sensor Guide for Proper Use of Smoke Detectors in Duct Applications (A05-1004),

More information

D2E Duct Smoke Detector

D2E Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS D2E Duct Smoke Detector Specifications Operating Temperature: 20 to 60 C Storage Temperature: 20 to 60 C Humidity: 0% to 93% Relative Humidity Non-condensing Air

More information

DH400 Air Duct Smoke Detector

DH400 Air Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS DH400 Air Duct Smoke Detector Before Installing Please thoroughly read System Sensor s Guide for Proper Use of Smoke Detectors in Duct Applications (I56-473-XX),

More information

SK-Duct Air Duct Smoke Detector

SK-Duct Air Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS I56-3432-001R 12 Clintonville Road Northford, CT 06472 203.484.7161; Fax: 203.484.7118 SK-Duct Air Duct Smoke Detector http://www.silentknight.com Specifications

More information

DH100ACDCI Ionization Air Duct Smoke Detector

DH100ACDCI Ionization Air Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS Ionization Air Duct Smoke Detector Before Installing Please thoroughly read the System Sensor Guide for Proper Use of Smoke Detectors in Duct Applications (A05-1004),

More information

Air Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608)

Air Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608) FORM ASX-40021 INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS SM-501 Series Smoke Detectors, Model EXSAC and EXSAD (Ionization), EXSAJ and EXSAK (Photoelectric) Air Specialties Express, 448 S. Main

More information

Installation Instructions

Installation Instructions 48/50A2,A3,A4,A5020-060, 48/50P2,P3,P4,P5030-100, 48/50N 75 to 105 Ton Return Smoke Detector Accessory Installation Instructions Part No. CRSMKDET002C00 CONTENTS GENERAL........................................

More information

D343. Installation Instructions. Air Duct Smoke Housing

D343. Installation Instructions. Air Duct Smoke Housing D E Installation Instructions Air Duct Smoke Housing D Installation Instructions.0 Overview. Trademarks ational Fire Alarm Code is a trademark of the ational Fire Protection Association, Inc. ife Safety

More information

TRN100BPT, TRN100BP, and TRN100BPC Air Duct Smoke Detector with Extended Air Speed Range

TRN100BPT, TRN100BP, and TRN100BPC Air Duct Smoke Detector with Extended Air Speed Range INSTALLATION AND MAINTENANCE INSTRUCTIONS TRN100BPT, TRN100BP, and TRN100BPC Air Duct Smoke Detector with Extended Air Speed Range 825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 60-77-6495

More information

DH100ACDCLP Air Duct Smoke Detector with Extended Air Speed Range

DH100ACDCLP Air Duct Smoke Detector with Extended Air Speed Range INSTALLATION AND MAINTENANCE INSTRUCTIONS Air Duct Smoke Detector with Extended Air Speed Range A Division of Pittway 825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 60-77-6495 The Innovair

More information

DH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range

DH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range INSTALLATION AND MAINTENANCE INSTRUCTIONS DH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range 3825 Ohio Avenue, St. Charles, Illinois 60174 800/736-7672, FAX: 630-377-6495 www.systemsensor.com

More information

DH500ACDC Intelligent Air Duct Smoke Detector Housing

DH500ACDC Intelligent Air Duct Smoke Detector Housing INSTALLATION AND MAINTENANCE INSTRUCTIONS DH500ACDC Intelligent Air Duct Smoke Detector Housing 3825 Ohio Avenue St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 Specifications Length: 14.5

More information

DH200RPL Intelligent Air Duct Smoke Detector with Extended Air Speed Range

DH200RPL Intelligent Air Duct Smoke Detector with Extended Air Speed Range INSTALLATION AND MAINTENANCE INSTRUCTIONS DH200RPL Intelligent Air Duct Smoke Detector with Extended Air Speed Range 3825 Ohio Avenue, St. Charles, Illinois 60174 800/736-7672, FAX: 630-377-6495 Before

More information

Addressable Detectors & Bases

Addressable Detectors & Bases Edwards Signaling Catalog u Intelligent Initiating Addressable Detectors & Bases Detectors: E-PD, E-PHD, E-HD Bases: B4U, RB4U, IB4U, SB4U Overview Edwards intelligent addressable detectors are meticulously

More information

DH500 Intelligent Air Duct Smoke Detector Housing

DH500 Intelligent Air Duct Smoke Detector Housing INSTALLATION AND MAINTENANCE INSTRUCTIONS DH500 Intelligent Air Duct Smoke Detector Housing 3825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 www.systemsensor.com Specifications

More information

Duct smoke housings, 4-wire D341/D341P and D342/D342P

Duct smoke housings, 4-wire D341/D341P and D342/D342P Duct smoke housings, 4-wire D341/D341P and D342/D342P en Installation manual Duct smoke housings, 4-wire Notices en 3 1 Notices These instructions cover the installation of the D341/D342 Duct smoke housings

More information

SIGA-CC1 Single Input Signal Module Installation Sheet

SIGA-CC1 Single Input Signal Module Installation Sheet SIGA-CC1 Single Input Signal Module Installation Sheet Personality codes Use the personality codes described below to configure the SIGA-CC1 module. See Table 1 for listing information Table 1: Personality

More information

Duct smoke housing, 2-wire D340/D340P

Duct smoke housing, 2-wire D340/D340P Duct smoke housing, 2-wire D340/D340P en Installation manual Duct smoke housing, 2-wire Notices en 3 1 Notices These instructions cover the installation of the D340 Duct smoke housing and D340P Duct smoke

More information

TYPE C: RETURN AIR UNDER POSITIVE PRESSURE FROM SEPARATE BLOWER

TYPE C: RETURN AIR UNDER POSITIVE PRESSURE FROM SEPARATE BLOWER Installation Instructions Model AD-HR Air Duct Monitoring Housing INTRODUCTION The SIEMENS Model AD-HR is a sampling tube, air duct monitoring housing. When used with a compatible smoke detector, smoke

More information

8600 EMR SERIES. INSPK NO Rev.06/ INS NO. GENERAL DESCRIPTION

8600 EMR SERIES. INSPK NO Rev.06/ INS NO. GENERAL DESCRIPTION 00 EMR SERIES GENERAL DESCRIPTION Each 00 EMR series unit contains a door closer, hold open electromagnet and smoke detector. The unit can be used as a single installation or as a series of singles powered

More information

D7050DH. Installation Instructions. Multiplex Photoelectric Duct Smoke Detector

D7050DH. Installation Instructions. Multiplex Photoelectric Duct Smoke Detector D700DH EN Installation Instructions Multiplex Photoelectric Duct Smoke Detector D700DH Installation Instructions.0 Description Notices These instructions cover the installation of the D700DH Multiplex

More information

7251DH Intelligent Air Duct Smoke Detector

7251DH Intelligent Air Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS 7251DH Intelligent Air Duct Smoke Detector Specifications Length: Width: Depth: Weight: Operating Temperature Range: Operating Humidity Range: Duct Air Velocity:

More information

DNRHS Intelligent Air Duct Smoke Detector

DNRHS Intelligent Air Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS DNRHS Intelligent Air Duct Smoke Detector Specifications Length: Width: Depth: Weight: Operating Temperature Range: Operating Humidity Range: Duct Air Velocity:

More information

Signature Series Auto-Sync Output Module (CC1S)

Signature Series Auto-Sync Output Module (CC1S) Signature Series Auto-Sync Output Module (CC1S) Product description Mounting The Signature Series can be mounted in a North American 2-1/2 in (64 mm) deep 2-gang box or a standard 4 in square box 1-1/2

More information

Print Specification. Publication. Instructions. Specific requirements. General requirements

Print Specification. Publication. Instructions. Specific requirements. General requirements Print Specification Publication GSA-CC1 Single Input Signal Module Installation Sheet P/N P-047550-1802-EN REV 04 ISS 23JUN15 Instructions This page is the print specification for the publication. It is

More information

DNR-AUS Duct Smoke Detector

DNR-AUS Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS I56-3642-000R DNR-AUS Duct Smoke Detector Specifications Operating Temperature: 20 to 70 C ( 4 to 158 F) 0 C to 49 C (32 F to 120 F) with module installed in the

More information

SECTION FIRE ALARM SYSTEMS

SECTION FIRE ALARM SYSTEMS SECTION 16721 FIRE ALARM SYSTEMS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work

More information

DNR Duct Smoke Detector

DNR Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS I56-3051-007R DNR Duct Smoke Detector Specifications Operating Temperature: 4 to 158 F ( 20 to 70 C); 32 F to 120 F (0 C to 49 C) with module installed in the

More information

PRODUCT OVERVIEW SM-501 AT-A-GLANCE

PRODUCT OVERVIEW SM-501 AT-A-GLANCE AIR PRODUCTS AND CONTROLS INC. INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR SM-501 SERIES DUCT SMOKE DETECTORS SM-501-N SM-501-P PRODUCT APPLICATION SM-501 Series duct smoke detectors provide early detection

More information

DNR Duct Smoke Detector

DNR Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS I56-3051-004R DNR Duct Smoke Detector Specifications Operating Temperature: 4 to 158 F ( 20 to 70 C); 32 F to 120 F (0 C to 49 C) with module installed in the

More information

TrueAlarm Analog Sensing

TrueAlarm Analog Sensing TrueAlarm Analog Sensing UL, ULC Listed* Addressable Duct Sensor Housings with TrueAlarm Photoelectric Sensor; Available with Multiple Relay Features Compact air duct sensor housing with clear cover to

More information

TS93 EMR WITH SMOKE DETECTOR

TS93 EMR WITH SMOKE DETECTOR TS EMR WITH SMOKE GENERAL DESCRIPTION Each TS EMR series unit contains a door closer, hold open electromagnet and smoke detector. The unit can be used as a single installation or as a series of singles

More information

Wiring Instructions. Single Doors 99 Checkmate Series Use one or Master Unit each door or one or Support unit each door

Wiring Instructions. Single Doors 99 Checkmate Series Use one or Master Unit each door or one or Support unit each door CAUTION Hinge Edge of Door Wiring Instructions Checkmate Series with Single Point Hold-Open Combination Door Closer-Holder and Releasing Device with or without Integral Smoke Detector INSTALLER: LEAVE

More information

TrueAlarm Analog Sensing

TrueAlarm Analog Sensing TrueAlarm Analog Sensing UL, ULC Listed, CSFM Approved* Features Air aspiration duct smoke detection** system provides remote sensor location for ducts with difficult service access: Available as either

More information

PRODUCT OVERVIEW. SL-2000 AT-A-GLANCE MODEL NUMBER: SL-2000-N 4-Wire Ionization Duct Smoke Detector SL-2000-P 4-Wire Photoelectric Duct Smoke Detector

PRODUCT OVERVIEW. SL-2000 AT-A-GLANCE MODEL NUMBER: SL-2000-N 4-Wire Ionization Duct Smoke Detector SL-2000-P 4-Wire Photoelectric Duct Smoke Detector AIR PRODUCTS AND CONTROLS You in Control AIR PRODUCTS AND CONTROLS INC. INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR SERIES DUCT SMOKE DETECTORS -N 4-Wire, Ionization Type -P 4-Wire, Photoelectric Type

More information

D285DH. Installation Instructions Photoelectric Duct Smoke Detector

D285DH. Installation Instructions Photoelectric Duct Smoke Detector D85DH EN Installation Instructions Photoelectric Duct Smoke Detector D85DH Installation Instructions.0 Introduction FCC Notice The D85DH Photoelectric Duct Smoke Detector complies with Part 5 of the Federal

More information

1400 Direct Wire Ionization Smoke Detector

1400 Direct Wire Ionization Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS 1400 Direct Wire Ionization Smoke Detector A Division of Pittway 3825 Ohio Avenue, St. Charles, Illinois 60174 1800SENSOR2, FAX: 6303776495 Specifications Diameter:

More information

DNRECL Eclipse Duct Smoke Detector

DNRECL Eclipse Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS DNRECL Eclipse Duct Smoke Detector 3825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 www.systemsensor.com SPECIFICATIONS Operating

More information

Wiring Instructions for the 2900 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector

Wiring Instructions for the 2900 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector Wiring Instructions for the 900 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector CAUTION: FAILURE TO INSTALL OR ADJUST PROPERLY MAY RESULT IN INJURY OR

More information

SILENT KNIGHT. IntelliKnight Smoke Detector Cleaning and Testing Instruction. Equipment Needed. Testing Equipment. Cleaning Equipment

SILENT KNIGHT. IntelliKnight Smoke Detector Cleaning and Testing Instruction. Equipment Needed. Testing Equipment. Cleaning Equipment SILENT KNIGHT IntelliKnight Smoke Detector Cleaning and Testing Instruction This document contains information necessary to properly test and clean analog photoelectric and ionization smoke detectors connected

More information

Single Doors FIREGUARD Series Use one Master Unit each door or one 2409 Support unit each door. Pairs of Doors

Single Doors FIREGUARD Series Use one Master Unit each door or one 2409 Support unit each door. Pairs of Doors Hinge Edge of Door Hinge Edge of Door Wiring Instructions for the Sargent 0 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector CAUTION: FAILURE TO INSTALL

More information

PAD100-6DB & PAD100-4DB PAD100-PD

PAD100-6DB & PAD100-4DB PAD100-PD Installation Manual Detector Bases: PAD100-6DB & PAD100-4DB PAD100-PD Photoelectric Smoke Detector (ANSI/UL 268 Listed) PAD100-PHD Photoelectric Smoke / Heat Detector Combination (ANSI/UL 268 and ANSI/UL

More information

Duct and Rough Service Carbon Monoxide Sensor

Duct and Rough Service Carbon Monoxide Sensor Product Identification and Overview Duct and Rough Service Carbon Monoxide Sensor BAPI s Carbon Monoxide Sensor offers enhanced electrochemical sensing with outstanding accuracy at low concentrations.

More information

Addressable NAC Output Module D327A

Addressable NAC Output Module D327A Installation Instructions Notice Addressable NAC Output Module D327A These instructions cover the installation of the D327A Addressable NAC Output Module in an analog system controlled by a Bosch D8024,

More information

DUCTSD Duct Smoke Detector

DUCTSD Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS 82 Ohio Avenue, St. Charles, Illinois 07-800-SENSOR2, FAX: 0-77-9 Duct Smoke Detector www.systemsensor.com SPECIFICATIONS Operating Temperature: to 8 F ( to 70

More information

Installation Manual. Detector Bases: PAD100-IB, PAD100-RB & PAD100-SB

Installation Manual. Detector Bases: PAD100-IB, PAD100-RB & PAD100-SB - + - + - + 1. Description This document provides instructions for mounting and wiring the Detector Bases PAD100-, PAD100-RB and PAD100-SB. The following detectors are compatible with Detector Bases PAD100-,

More information

TrueAlarm Analog Sensing

TrueAlarm Analog Sensing UL, ULC Approved* TrueAlarm Analog Sensing TrueAlarm Analog Sensors Photoelectric and Heat; Standard Bases and Accessories Features TrueAlarm analog sensing provides: Digital transmission of analog sensor

More information

Wiring Instructions (01-09)

Wiring Instructions (01-09) CAUTION Wiring Instructions 0--00-0 (0-0) Power Track Series with Single Point Hold-Open Electromechanical Releasing Device with Multi-Point Hold- Open TO PREVENT ELECTRICAL SHOCK AND EQUIPMENT DAMAGE,

More information

ESL 500N Series Smoke Detector Installation Sheet

ESL 500N Series Smoke Detector Installation Sheet ESL 500N Series Smoke Detector Installation Sheet Additional features Depending on the model, the smoke may also provide the following features. CleanMe: Enables a CleanMe compatible control panel to receive

More information

You in Control PRODUCT OVERVIEW

You in Control PRODUCT OVERVIEW AIR PRODUCTS AND CONTROLS You in Control AIR PRODUCTS AND CONTROLS INC. INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR SERIES PLENUM DUCT SMOKE DETECTORS NO-FLOW LOW-FLOW SPECIAL APPLICATION -N -P PRODUCT

More information

DH100ACDCLPX Air Duct Smoke Detector with Extended Air Speed Range

DH100ACDCLPX Air Duct Smoke Detector with Extended Air Speed Range INSTALLATION AND MAINTENANCE INSTRUCTIONS DH100ACDCLPX Air Duct Smoke Detector with Extended Air Speed Range 3825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 The Innovair

More information

Installation Manual. Detector Base: PAD100-SPKB

Installation Manual. Detector Base: PAD100-SPKB 1. Description This document provides instructions for mounting and wiring the detector base PAD100-SPKB. The following detectors are compatible with detector base PAD100-SPKB. PAD100-PD: Photoelectric

More information

You in Control PRODUCT OVERVIEW SM-501 AT-A-GLANCE

You in Control PRODUCT OVERVIEW SM-501 AT-A-GLANCE AIR PRODUCTS AND CONTROLS You in Control AIR PRODUCTS AND CONTROLS INC. INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR SM-501 SERIES DUCT SMOKE DETECTORS SM-501-N 4-Wire, Ionization Type SM-501-P 4-Wire,

More information

DD205RF/TX Detector Installation Sheet

DD205RF/TX Detector Installation Sheet GE Security DD205RF/ Detector Installation Sheet EN DE EL ES FR IT NL PT RU TR 2009 GE Security, Inc. 1 of 28 P/N 1060783 REV 1.00 ISS 26FEB09 2 of 28 P/N 1060783 REV 1.00 ISS 26FEB09 EN: Installation

More information

MODEL /4" Conduit. (By others) Terminal Strips Companion unit (without electronics) not shown. Approximate Preload

MODEL /4 Conduit. (By others) Terminal Strips Companion unit (without electronics) not shown. Approximate Preload 2900 FIREGUARD Electromechanical Closer-Holder Device Models 12-2960, 9-2960 and 2960 Multipoint Hold Open with Rigid Arms Pull (Hinge) Side Installation Instructions CAUTION: FAILURE TO INSTALL OR ADJUST

More information

, -9686, -9688, -9755, Duct Detector/Sensor Installation Instructions

, -9686, -9688, -9755, Duct Detector/Sensor Installation Instructions 574-776 Rev. C 4098-9685, -9686, -9688, -9755, -9756 Duct Detector/Sensor Installation Instructions Blank Page Cautions and Warnings DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED. Upon unpacking

More information

Instructions. Duct Mount Accessory Q Rev: 11/

Instructions. Duct Mount Accessory Q Rev: 11/ Instructions Duct Mount Accessory Q5016 Rev: 11/16 95-8752 Table of Contents DESCRIPTION...1 FEATURES...1 OPERATION...1 SPECIFICATIONS.... 2 INSTALLATION... 2 Detector Location...2 Tools for Assembly...4

More information

TrueAlarm ES Analog Sensing

TrueAlarm ES Analog Sensing TrueAlarm ES Analog Sensing UL, ULC, CSFM Listed; FM Approved* Features TrueAlarm addressable sensor base with 520 Hz sounder TrueAlarm sensor bases with 520 Hz tone require a TrueAlarm photoelectric,

More information

LASER ASPIRATED SMOKE DETECTOR

LASER ASPIRATED SMOKE DETECTOR LASER ASPIRATED SMOKE DETECTOR LASD1 (Single Channel) INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS (CE) 1 INTRODUCTION The LASD1 utilises one or two high-sensitivity laser point detectors in an aspirated

More information

30.45 Electric Release PDRP-2001

30.45 Electric Release PDRP-2001 The PDRP-2001 Fire Alarm Control Panel (FACP) is a six-zone control panel for single and dual hazard deluge and preaction applications. The FACP is compatible with conventional input devices (2-wire or

More information

LASER ASPIRATED SMOKE DETECTOR

LASER ASPIRATED SMOKE DETECTOR LASER ASPIRATED SMOKE DETECTOR LASD2 (Dual Channel) INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS (CE) 1 INTRODUCTION The LASD2 utilises two, high-sensitivity laser point detectors in an aspirated

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE Deluge Devices 270a 1. PRODUCT NAME VIKING PAR-3 Available since 1991 2. MANUFACTURED FOR: THE VIKING CORPORATION 210 N. Industrial Park Road Hastings, Michigan 49058 U.S.A. Telephone: (269) 945-9501 (877)

More information

TrueAlarm Smoke Detectors

TrueAlarm Smoke Detectors UL, ULC Approved* TrueAlarm Smoke Detectors TrueAlarm Photoelectric Smoke Detector with TrueSense Smoke/Heat Detection Features detection. If any of these alarm conditions are experienced, an alarm is

More information

Smoke Alarm User s Manual

Smoke Alarm User s Manual V-MUL-007-D(A0) Smoke Alarm User s Manual Please read and save this manual PHOTOELECTRIC SMOKE ALARM( HUSH FEATURE) MODEL: VST-S588H Class II Apparatus Photoelectric smoke alarms are generally more effective

More information

Reflective Beam Smoke Detector

Reflective Beam Smoke Detector Reflective Beam Smoke Detector SRA-ET Features! 5-30m range! Small flat reflector! Powered directly from the zone! Full line continuity options! Automatic compensation! Approved by LPCB & VdS Description

More information

D4120 Duct Smoke Detector D4S Sensor Component D4P120 Power Board Component

D4120 Duct Smoke Detector D4S Sensor Component D4P120 Power Board Component INSTALLATION AND MAINTENANCE INSTRUCTIONS Duct Smoke Detector DS Sensor Component DP Power Board Component 82 Ohio Avenue, St. Charles, Illinois 607-800-SENSOR2, FAX: 60-77-69 www.systemsensor.com NOTE:

More information

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL MADE IN THE U.S.A. U.L. LISTED CANADIAN LISTED CSFM: 7300-1418:100 GENERAL DESCRIPTION SERIAL NUMBER The Cookson Company FIREFLY II PLUS Time Delay Release

More information

SC-6 Six Supervised Control Module

SC-6 Six Supervised Control Module INSTALLATION AND MAINTENANCE INSTRUCTIONS SC-6 Six Supervised Control Module SPECIFICATIONS Normal Operating Voltage: Stand-By Current: Alarm Current: Temperature Range: Humidity: Dimensions: Accessories:

More information

THE "SS90" SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL

THE SS90 SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL S S S S S S S S 90 OLID TATE ECURITIES, INC SOLID STATE FAIL-SAFE UNIT * PATENT PENDING LISTED U 99Y9 RESET L RELEASING DEVICE SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE

More information

Booster Power Supply Manual

Booster Power Supply Manual Supply Manual DEVELOPED BY COPYRIGHT NOTICE General Signal Building Systems Corporation 6411 Parkland Drive Sarasota, FL 34243 (941) 739-4300 Copyright 1999 General Signal Building Systems Corporation

More information

Control Relay Modules

Control Relay Modules TM INTERNATIONAL ANALOG ADDRESSABLE INPUT/OUTPUT DEVICES Control Relay Modules Model SIGA-CR, SIGA-MCR, SIGA-CRR, Features! Provides one no/nc contact (SIGA-CR/MCR) Form C dry relay contact can be used

More information

RF280THS. Installation Instructions Wireless (RF) Photoelectric Smoke Detectors

RF280THS. Installation Instructions Wireless (RF) Photoelectric Smoke Detectors RF80THS EN Installation Instructions Wireless (RF) Photoelectric Smoke Detectors RF80THS Installation Instructions Trademarks Trademarks Chamber Check is a registered trademark of Bosch Security Systems

More information

IDP-Zone-6 Six Zone Interface Module

IDP-Zone-6 Six Zone Interface Module INSTALLATION AND MAINTENANCE INSTRUCTIONS IDP-Zone-6 Six Zone Interface Module BEFORE INSTALLING If the modules will be installed in an existing operational system, inform the operator and local authority

More information

CZ-6A Six Zone Interface Module

CZ-6A Six Zone Interface Module INSTALLATION AND MAINTENANCE INSTRUCTIONS CZ-6A Six Zone Interface Module 658 Kitimat Rd. Unit #6 Mississauga, Ontario L5N T5-800-SENSOR, FAX: 905-8-077 www.systemsensor.ca SPECIFICATIONS Normal Operating

More information

Installation Smoke Detector ELQZ , GOLD

Installation Smoke Detector ELQZ , GOLD Installation Smoke Detector ELQZ-2-428-2, GOLD General The ELQZ-2-428-2 smoke detector is used for measuring any smoke present in ventilation ducts. It consists of an ionising detector mounted in an adaptor

More information

Multi-Point Peripherals

Multi-Point Peripherals UL, ULC Approved* Multi-Point Peripherals TrueAlarm CO Sensor Bases for Smoke, Heat, and Photo/Heat Sensors using IDNet Communications Features Fig 1: TrueAlarm CO Sensor Base with Sounder (shown with

More information

MMF Six Zone Interface Module

MMF Six Zone Interface Module Installation and Maintenance Instructions I56-900-005 MMF-0-6 Six Zone Interface Module SPECIFICATIONS Normal Operating Voltage: 5- VDC Stand-By Current: ma Alarm Current: 40 ma (assumes all six LEDs solid

More information

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels R 12 Clintonville Road, Northford, CT 06472 Phone: (203) 484-7161 FAX: (203) 484-7118 Instruction Manual for the MS-4012/4024 and CMS-4012/4024 Fire Alarm Control Panels Document 15586 5/11/93 Revision:

More information

D4120 Duct Smoke Detector D4S Sensor Component D4P120 Power Board Component

D4120 Duct Smoke Detector D4S Sensor Component D4P120 Power Board Component INSTALLATION AND MAINTENANCE INSTRUCTIONS D Duct Smoke Detector DS Sensor Component DP Power Board Component 82 Ohio Avenue, St. Charles, Illinois 07-800-SENSOR2, FAX: 0-77-9 www.systemsensor.com NOTE:

More information

MODEL B2 INSTALLATION MANUAL

MODEL B2 INSTALLATION MANUAL RELEASE DEVICES GENERAL DESCRIPTION MODEL B2 INSTALLATION MANUAL S/N: The B2 Series Time Delay Release Devices are UL Listed, Canadian Listed, and CSFM Listed for use on rolling doors, single-slide and

More information

Filtrex A Smoke Detector for Difficult Environments

Filtrex A Smoke Detector for Difficult Environments A P P L I C A T I O N S G U I D E Filtrex A Smoke Detector for Difficult Environments A P P L I C A T I O N S G U I D E Filtrex A Smoke Detector for Difficult Environments Contents Section 1 Product Overview...2

More information

0 A EIS Intrinsically-Safe Plug-in Intelligent Photoelectronic Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS

0 A EIS Intrinsically-Safe Plug-in Intelligent Photoelectronic Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS INSTALLATION AND MAINTENANCE INSTRUCTIONS 2251EIS Intrinsically-Safe Plug-in Intelligent Photoelectronic Smoke Detector A Division of Pittway 3825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2,

More information

Conventional Smoke Detectors KFAPO

Conventional Smoke Detectors KFAPO Kingfisher Company, inc. Conventional Smoke Detectors KFAPO Features: Wide operating voltage, 9-33 VDC Advanced electronic technology Flashing LED Magnetic test switch Proven detection performance Designed

More information

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev Installation Guide for AL600ULM Multi-Output Access Control Power Supply Charger Rev. 091800 1 AL600ULM - Multi-Output Access Control Power Supply/Charger Overview: The AL600ULM multi-output access control

More information

HEALTHY HOME SYSTEM CONTROL Plus Model: HHSC+

HEALTHY HOME SYSTEM CONTROL Plus Model: HHSC+ HEALTHY HOME SYSTEM CONTROL Plus Model: HHSC+ The Field Controls Healthy Home System Controller Plus (HHSC+) is designed to work in conjunction with the forced air HVAC system to periodically introduce

More information

Instruction Manual EVA-PY

Instruction Manual EVA-PY Instruction Manual EVA-PY Analog Photoelectric Smoke Detector NITTAN COMPANY, LIMITED 1-54-5 SASAZUKA, SHIBUYA-KU, TOKYO 151-8535, JAPAN http://www.nittan.com Before Installation Please read these instructions

More information

Installation and Operation Manual

Installation and Operation Manual [Please read this installation & operation manual before install and use this Installation and Operation Manual Address: 8-701,Dongfangming Industry Zone, Dabao Road., Baoan, Shenzhen, China-518101 Page

More information

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum. September 29, 1997 Firecycle III 433 a 1. PRODUCT NAME VIKING Model E-1 Manufactured 1997 Present 2. MANUFACTURED FOR THE VIKING CORPORATION 210 N Industrial Park Road Hastings, Michigan 49058, U.S.A.

More information

UEI-1 UNIVERSAL END-OF-LINE / ISOLATOR TESTER

UEI-1 UNIVERSAL END-OF-LINE / ISOLATOR TESTER UEI1 UNIVERSAL ENDOFLE / ISOLATOR TESTER With Easy Testing Technology STALLATION & OPERATG STRUCTIONS These instructions are provided to ensure compliance with the installation requirements of NFPA72 (National

More information