Smoke Vent Control Panel PCB4 V4 Installation Manual

Size: px
Start display at page:

Download "Smoke Vent Control Panel PCB4 V4 Installation Manual"

Transcription

1 Smoke Vent Control Panel PCB4 V4 Installation Manual 10A PCB4 Control Panel Do Not Remove From PCB4 Control Panel Page 1

2 Contents Page 3) Important Regulations, Safety, Maintenance, Guarantee Page 4) General System Overview, Electrical Supply and System Operating Modes Page 5) System Operating Modes Page 6) PCB4 Connections and Cable Length Table Page 7) Example Installation Schematic Page 8) Technical Specification Page 9-10) Compatible System Field Devices Page 11) Troubleshooting Page 12) Commissioning and 6 Monthly Inspection and System Testing Page 13) System Testing Continued and Recommended Procedure on Discovery of Fire Page 14) System Sign Off Information Page 2

3 Please read these instructions carefully before proceeding and keep them for future reference on the inside of the control panel door. Important Regulations Please consult the relevant approving building bodies before installation to confirm the system meets the required building specification. This Control Panel is capable of satisfying the requirements for residential buildings designed in accordance with Approved Document B. Safety - The installer must instruct the client in the function of the system including resetting and location of these instructions. - This document must be located on the inside of the door of the PCB4 control panel. - Children must not be allowed to play with this system. - When resetting the system, make sure that no body parts can get caught in any AOV (Automatic Opening Vent). Provide suitable signage to warn of potential body part trapping. - LED (LED10) located on the PCB4 control panel must be lit Green at all times. Otherwise see Troubleshooting. Maintenance Every 12 months this system requires maintenance to be carried out by a suitably trained individual. The following tasks should be carried out during the maintenance. - Update Log Book - External examination and inspection of system components - Measuring of insulation resistance - Checking and testing of all relevant power supply units and batteries - Functional testing of all connected system components See below (12) for interim 6 monthly system inspection. Guarantee The PCB4 panel is guaranteed for 12 months from the initial date of delivery. This guarantee is void when connecting components not approved by Be Safe Direct and not installing and maintaining the system in accordance with this installation manual. Page 3

4 1) General System Overview The PCB4 is an 8 Zone AOV Control Panel with the added feature of environmental ventilation control. 16 Zone Control is possible when adding an additional PCB board. Stair and roof vents can also be operated on activation of any of the 8/16 zones. Individual AOV Zone control can be achieved by installing Smoke Detectors, Manual Call Points or Fire Alarm Interfaces. A 10Amp or 20Amp power supply is available and is backed up by batteries. This provides power in the event of mains power failure. A Power Fault output is also provided. Environmental ventilation control enables each zone to be individual controlled by a thermostat and rain sensor. A time clock and sequencer can also be incorporated to allow each zone to open and close at certain times of the day and in a specific order. An override switch panel is also available to enable manual control of all zones at one central point. This is designed only for fire fighter use in an emergency. Typically this panel would be located in the entrance lobby. Electrical Supply A 230V AC 50Hz supply is to be used to power the PCB4 power supply unit. This supply should be fed by a suitably rated fused outlet and fitted adjacent to the PCB4 control panel. The mains supply is to be connected to the correctly labelled terminals (L Live) (N Neutral) (E - Earth). It is recommended that the supply is fed from an independent fused supply at the electrical distribution board. Only suitably trained and competent individuals should undertake the installation and wiring of the PCB4 control units power supply. (System connections are to be made without live power connected). 24V DC Emergency Battery Supply Emergency power supply of 12 Hours when using 2x 12V DC 7AH batteries connected to 10A PSU. Emergency power supply of 12 Hours when using 2x 12V DC 7AH batteries connected to 20A PSU. The system will open a single zone AOV and Roof/Stair vent if operated within the 12 Hours. Any environmental mode must be disabled during mains power failure as opening and closing of AOV s while on battery backup will reduce the backup time according to how often AOV s are opened and closed. Environmental control can be disabled when mains power failure occurs by wiring the (PSU Rdy) terminals in series with the time clock and/or rain sensor. Page 4

5 2) System Operating Modes and Links Mode 4 = Locked Mode (Supplied as standard) (No links on S1 or S2) Current legislation for natural smoke shafts requires other zones other than the zone of activation to be locked out and disabled. Smoke detectors and manual call points located in other zones activated after the initial activation will be locked out and disabled. Any environmental inputs operated will be ignored and zones activated will close, other than the zone of activation. The override switch panel can be used to manually open zones other than the floor of activation if required by the fire service. The roof/stair vent output will open on the initial zone activation. To reset the system to normal status after smoke detector activation, insert and remove the test key into the centre underside cover, of the manual call point for the activation zone. The front cover will drop down, Push up the front cover fully to reset the plastic element to its normal position. This removes the power from the activated smoke detector and resets the activated zones AOV and stair/roof vent. Note: The call point must be wired first in the line before the first smoke detector and be wired in series with the zone smoke detectors 24v DC supply to reset. If the call point has not been wired in series, turn on and off the PCB4 panel s incoming power supply to reset. Ensure no smoke is present when system is reset otherwise system will not reset. Mode 3 = Un-Locked Mode (Link on S1 only) This mode enables additional zones other than the initial zone activated to open on smoke detection and by operating the zones manual call point. The roof/stair vent output will operate on the initial floor activation. Resetting of the system is achieved as outlined in Mode 4 above. Operating the Roof/stair vent output when an environmental input is operated: Link on S4 = Open on environmental No link = Not Active Page 5

6 Other Modes and Terminals Mode 1 = Not Used (For Future Development) Mode 2 = Not Used (For Future Development) Communication link between PCB4 s Link on S1 & S2 Link on S2 only S3 Terminal 3) PCB4 Connections Power Supply Input Voltage 230v AC 50Hz System Voltage 24V DC Do not run control cables with power cables Fire Resistant Cable is to be used Earth cable must be used where available Cable and Terminal boxes must be labelled Page 6

7 Example AOV Window Installation Schematic Page 7

8 4) Technical Specification Control Panel PCB4 10A PCB4 20A Supply Input Voltage 230V AC 50Hz 230V AC 50Hz Rated Zone Power Output 24V DC 2A Max 24V DC 2A Max, 24v DC 1A Max with Environmental Use Smoke Detectors Per Zone Call Points Per Zone Unlimited Unlimited IP Rating IP66 Effected by Cable Glands IP66 Effected by Cable Glands Mains Fuse 3.15A Anti Surge 6.3A Anti Surge CE Marked Yes Yes Battery Backup 2 x 12V DC 7AH 2 x 12v DC 7AH Housing Metal RAL 7035 Metal RAL 7035 Weight (Excl Batteries) 15Kg 16Kg Dimensions H 500mm x W 500mm x D 250mm H 500mm x W 500mm x D 250mm Fuses PCB4 zone output protection by resettable fuses. Fuses rated at 5A continuous load but subject to a maximum of 2A load per output. Fuses trip at twice the rated current and automatically reset when the fault is removed. Page 8

9 5) Compatible System Field Devices AOV Control Smoke Detectors: Provide automatic zone activation in the event of smoke being detected in that particular zone. Be Safe Direct approved latching smoke detectors and bases to be used only. A maximum of 10 smoke detectors can be installed per zone using a minimum 1.5mm² 3 Core Fire Resistant cable. Manual Call Points: Provides manual control of zones and stair vent. Be Safe Direct approved conventional manual call points to be used only. Multiple Call Points can be used in each zone and all are wired in series using a minimum 1.5mm² 2 Core Fire Resistant cable. Use 1.5mm² 3 Core Fire Resistant cable when wiring first in line, with the zones smoke detectors. AOV Zone Outputs: For reverse polarity and Motor Open/Motor Closed 24v DC actuators and motors. Note: Power is continuously supplied to this output and is not removed when switching. Actuators and motors must have limit switches fitted. Requires minimum 1.5mm² 2 Core Fire Resistant Cable for reverse polarity actuators and 1.5mm² 3 Core Fire Resistant Cable for Motor Open/Motor Closed actuators/motors. 12V DC actuators can be used by adding a 12V DC power supply to the control panel. This would connect to the Zone Input Supply Terminals instead of using the 24v DC power supply used to power the PCB4. This would also feature a battery backup facility. Fire Alarm Interfaces: The PCB4 Control Panel is compatible with Volt Free Normally Closed interfaces. This provides AOV control by utilising 3rd party addressable/conventional fire alarms. Interface output is to switch to open in fire condition. Requires minimum 1.5mm² 2 Core Fire Resistant Cable connected to detector zone inputs. Override Switch Panel: Located in the entrance lobby, the Override Switch Panel provides the Fire Service with manual control of additional zones after the initial fire zone has been activated. When a zone switch has been operated the relevant zone output and stair output will open. The stair output will be permanently open until all switches have been reset to their normal position. Requires a minimum 0.5mm² 10 Core Fire Resistant Cable. Sounders: Are not required in residential developments designed in accordance with Approved Document B and as such are not compatible with the PCB4 Control Panel. Please contact us for alternative systems. Environmental Ventilation Rain Sensor: Disables all environmental inputs when rains detected. If zone AOV s are already activated and open, the rain sensor will close all AOV s and not open again until the rain sensor detects no rain is present and an environmental zone input is triggered. Requires a minimum 0.5mm² 4 Core Cable. A Rain sensor requires a normally closed volt free contact opening when rain is detected. Using a normally closed volt free contact provides the added protection of the roof/stair vent closing if the rain sensor is disconnected or the power to the sensor is removed. Page 9

10 Thermostat: Provides individual zones with temperature control. On reaching the set temperature in the specific zone, its AOV output will activate and open. When the temperature falls below this set point the AOV output will close. The temperature is set using a dial located on the front of the thermostat and the temperature range can be set between 10 C and 30 C. Requires a minimum 0.5mm² 2 Core Cable. Open/Close Switches: This two position switch provides manual control of zone outputs providing an open and close feature. Switches will not override zone outputs when a smoke detector/ manual call point input has been triggered when system is in locked mode. A minimum 1.5mm 2 Core Fire Resistant cable is required. The switch contacts must closed to open the zone output. Time clock: This is 7 day time clock and has the facility to program up to 6 on/off times per day. The same or different times can be set for each day of the week. Time clock requires an open volt free contact closing when the time schedule is active. Sequencer: Please see TOC-8-RTC user guide for further information. NOTE: When a TOC-8-RTC Sequencer is used, a time clock is not required as the TOC-8-RTC has a built in 24 hour time clock. Other Device Connections MIOU Input: Multi Input Output Unit enables the PCB4 Control Panels Zone Outputs to be operated by a Hochiki Protocol, Kentec manufactured Addressable fire alarm system. Mimic Panel: The Mimic Panel provides remote visual indication of which zone has been operated using LED s. The relevant zones LED will illuminate when activated by a either a detection, environmental or override input. Volt Free Contacts: Two volt free contacts provide the necessary control to interface with 3 rd party equipment. When triggered the contacts will be capable of controlling other building systems to shut down Plant, Ground lifts, Informing BMS Systems of activation etc. A minimum 1.5mm ² 2 Core Fire Resistant cable is required for each set of contacts. This additional relay is powered from the relay 9 (I) output and is active when any smoke detector input is activated or the break glass input is activated. Note: If environmental mode is set to enable the roof/stair vent (relay 9) then the volt free relay would be activated also. Page 10

11 6) Troubleshooting Fault Cause Fix PCB4 Green Light not illuminated No Power to PCB4 Panel Check Power Input & Output Connections PSU Battery Fault Light Battery Fault, Under Charged or Misconnected Test Batteries are connected as per the above diagram and are giving correct output No 24v DC at Zone AOV Outputs 24v DC not connected at AOV supply terminals Check power supply output and power connections Red/Flashing Red LED on PCB4 Board PCB4 Failure Contact Be Safe Direct Smoke Detector Detector does not operate on detection of smoke Misconnected at the base or Faulty Detector Check base Connections or replace detector Detector does not reset when smoke is not present Power has not been removed from the detector line or Faulty Detector Check Power has been removed from the detector or replace detector Call Point Call point does not reset smoke detector Check Connections 3 rd Party Zone Interface Zone does not operate on activation of Interface Actuator/Motor Zone Outputs Zone operates when power is turned on and no input is triggered Not wired in series, before first smoke detector on its 24v line Interface is not wired Normally Closed Smoke detector input line is open, Environmental or time clock input line is closed, Override switch line is closed Check Connections Check Connections Stair Vent is permanently open Input Terminal BG is Open Change Input to Normally Closed Outputs operate when system is in normal Actuator/Motor is wired in reverse condition and all lines wired correctly Environmental Inputs Stair vent does not open when zone input is triggered Zone output operates when it s too hot / too cold Zone Outputs not opening at required times with Time clock Override Switch Panel No link on S4 Terminal Thermostat temperature dial requires adjusting Time clocks requires set times adjusting Change the polarity of the output by switching the positive and negative cores around Add Link to S4 terminal Adjust temperature dial on the zones thermostat to desired temperature Set time clock to desired opening and closing times LED s are not illuminated No 24v Supply Check 24V Supply and Connections Zones do not operate when sliding the Connection lines are not switching Check 0V and Input Connections switches from open to closed The Power supply unit has mains power connected and DC voltage low indicator. There is no battery fault light. There is also a volt free contact available (Rdy) on the PSU to indicate when the DC voltage drops below the low level or is not available. This contact closes when the DC voltage is correct and opens when it is low or not available. Note: There is no indication when the batteries are disconnected or faulty. PCB4 Green/Red LED A fixed green illuminated LED indicates that the PCB4 DC supply is healthy and that the PCB4 internal control is operating normally. It does not indicate that all external connections are correct. A steady red or flashing state indicates that the PCB4 logic has stopped or is in a fault condition. Page 11

12 7) Commissioning - Carry out external examination and inspection of system components before proceeding. - Notify the relevant persons of imminent system test. - Turn on the Power to PCB4 Control Panel. - Check Power Supply Voltages and lights, the Green Light on the PCB4 should also be lit. - Test all Zone Call Points by pushing the plastic element and spray the Zone Smoke Detectors using detector testing spray. - If fitted, Test environmental inputs using the thermostat dial to open and close the output and wetting the rain sensor to close all zone outputs. - If fitted, Test override zone switches individually and check the correct zone output operates. - Ensure no fault light appears in PCB4 control Panel - Provide electrical safety certification to client and sign to state system operates in accordance with the Approved Document B. - Ensure this installation manual is left inside the panel, Last page completed and panel is locked shut. 8) 6 Monthly Inspection and System Testing Every six months and after maintenance the below list is to be carried out by a suitably trained individual. -Fix any system errors immediately -Fill out log book -Advise the relevant parties that the system is going to be taken out of operation before starting the inspection -Disable remote alarm monitoring (If Fitted) -Visual Inspection: Check all components and cable connections for outer damage and dirt accumulation smoke detectors, call points and smoke vents etc must not be impaired in there function by goods in storage or structural changes. -Clamps and Connections Check connections terminals and fastenings of components are securely seated. -Actuators and Motors In case of excessive dirt accumulation, clean and re-grease outer mechanically moving parts using the manufactures recommended guidelines. -Smoke Detectors In case of severe external visible dirt accumulation or false alarms, Exchange with a new smoke detector. Test smoke detectors individually with Be Safe Direct smoke detector testing spray. Testing Always activate a different smoke detector or call point in each zone with every new test. 1. Open zones AOV using the zones call point and reset using the call point test key. Ensure zones AOV and stair vent open and close simultaneously. 2. Operate the zones smoke detector using detector testing spray. Reset by using call point test key or remove power from panel if no zone call point is fitted. Ensure zones AOV and stair vent open and close simultaneously. 3. Ensure no fault light appears in PCB4 control Panel. Page 12

13 Testing when system connected to 3 rd party Fire Alarm 1. Trigger smoke detector using smoke detector testing spray. Reset at Fire Alarm control panel and by using call point test key (if wired in series) or removing power from PCB4 Control Panel. 9) Recommended Procedure on Discovery of Fire 1. If safe to do so, operate the effected zones orange call point to open the zones AOV and stair vent. If smoke detectors are fitted to the lobbies or stair case, these will operate the zones AOV and stair vent automatically. 2. Leave the building using the staircase. Do not use lifts. 3. Call the Fire Brigade. 4. Do not re-enter the building until Fire Brigade say it is safe to do so. For further information consult the relevant Building Approving Body and Fire Strategy Consultant. Page 13

14 10) System Sign Off Information Please complete the following information at commissioning: Client Details Name: Site Address: System Installed By Company Name: _ Operative Name: _ Date System Commissioned: Page 14

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels Installation and user manual for the FX range of fire panels 1, 2, 4 and 8 zone panels Contents Panel installation 3 Panel connections 3 Wiring connection drawings 4 Panel facilities 6 Installation check

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd OPERATIONAL NOTES FOR CONCEPT FIRE PANEL. NOTE ON NEW FIRE PANELS, POSITION 1 ON THE SIX WAY INTERNAL OPTION SWITCH IS TURNED ON, DISABLING THE ZONAL SOUNDERS. TO ENABLE ZONAL SOUNDERS TURN OFF. Operation

More information

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel INSTALLATION, OPERATION AND MAINTENANCE MANUAL Version: CN-PM-1000.VER1.1-12/2012 EN54 INFORMATION In accordance with EN 54-2 clause 13.7, the maximum

More information

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009 Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual Man-1048 Issue 05 October 2009 CONTENTS Contents... Page Safety & Installation...2 Installation - continued...3

More information

Saffire User & Installation Manual. IMPORTANT This manual should be left with the panel after installation.

Saffire User & Installation Manual. IMPORTANT This manual should be left with the panel after installation. Saffire+ 8-12 User & Installation Manual IMPORTANT This manual should be left with the panel after installation. We reserve the right to change product specifications without prior notice. Copyright VRC

More information

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels CF5000, MF5000 and FXP5000 Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels 16 zone panels Contents PANEL INSTALLATION...3 Installation...3 PANEL WIRING... 3 Mains power

More information

Silent Alert Fire Safe System

Silent Alert Fire Safe System Silent Alert Fire Safe System Technical Manual This manual covers the FSTX-2225-EU Fire alarm interface PG3A-2204-EU Pager FSCH-2226-IN Fire Safe Charger or CH3A-2205-IN Alarm clock charger SW3A-2208-EU

More information

highline SVCS-1 INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10

highline SVCS-1 INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10 highline WINDOW CONTROLS INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM SVCS-1 * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10 CERTIFICATE OF COMPLIANCE SVCS-1 We the undersigned

More information

New Silent Alert Fire Safe System

New Silent Alert Fire Safe System 1 New Silent Alert Fire Safe System TECHNICAL MANUAL This manual covers the FSTX-2225-EU - Fire Alarm Interface PG3A-2204-EU - Pager Unit - Fire Safe Compatible FSCH-2226-IN - Fire Safe Charger or CH3A-2205-IN

More information

Door Release Power Supply

Door Release Power Supply www.protectingpeople.co.uk Door Release Power Supply Engineer / Installation Manual Document: VI55.1 Protecting People Printed : 04/03/2004-1 - Ventcroft Ltd Door Release Power Supply Engineer / Installation

More information

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS QUICK USER GUIDE FOR, 2 & 4 ZONE PANELS INDICATORS COLOUR INDICATION MON FAULT Yellow On when a fault condition has occurred, or if no other fault Led is on, this indicates 24v auxiliary fuse failure.

More information

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3 INTELLIGENT FIRE TECHNOLOGY Twinflex and Multipoint V3 User Guide (TO BE RETAINED BY USER) 26-0340 Issue 3 Rafiki Protection Limited Rafiki policy is one of continual improvement and the right to change

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE Deluge Devices 270a 1. PRODUCT NAME VIKING PAR-3 Available since 1991 2. MANUFACTURED FOR: THE VIKING CORPORATION 210 N. Industrial Park Road Hastings, Michigan 49058 U.S.A. Telephone: (269) 945-9501 (877)

More information

Maintenance Guide EMS Security Group Ltd. All rights reserved. MK154 Iss5 18/11/15 AJM

Maintenance Guide EMS Security Group Ltd. All rights reserved. MK154 Iss5 18/11/15 AJM Maintenance Guide 2015 EMS Security Group Ltd. All rights reserved. MK154 Iss5 18/11/15 AJM Contents Overview 3 Pre-testing Guidelines 4 Daily Maintenance 4 Weekly Maintenance 5 Six Monthly Maintenance

More information

Fire and Smoke Control Systems

Fire and Smoke Control Systems Control Systems Electrical Mechanical Standard Panel Modular design for control and monitoring Premier Panel Customised design for control and monitoring Fully Addressable Fully programmable data wired

More information

DCS-100. intelligent damper control & monitoring system

DCS-100. intelligent damper control & monitoring system DCS-100 intelligent damper control & monitoring system 02 //DCS-100 Introduction The Disys Technologies DCS-100 is a revolutionary new control system designed specifically for the fire/smoke damper controls

More information

MAG2/4. AL MAG2 Soft. Version 2.1 MAG4 Soft.Version 2.0 USER MANUAL

MAG2/4. AL MAG2 Soft. Version 2.1 MAG4 Soft.Version 2.0 USER MANUAL FIRE CONTROL PANEL MAG2/4 USER MANUAL AL MAG2 Soft. Version 2.1 MAG4 Soft.Version 2.0 READ THIS MANUAL BEFORE CONNECTING THE EQUIPMENT AND KEEP IT SAFE FOR FUTURE REFERENCE. To call our technical support

More information

Installation and user manual for the BiWire / Conventional Repeater Panel

Installation and user manual for the BiWire / Conventional Repeater Panel Panel EFBWCV-REPEATER Contents Introduction.... 3 Purpose... 3 The Panel.... 3 Indication Equipment (IE).... 3 Power Supply Equipment (PSE).... 4 System Wiring.... 5 Status Indications.... 5 Repeater I/O....

More information

Control Panel Engineering and Commissioning Instructions

Control Panel Engineering and Commissioning Instructions Twinflex - V3 Fire Detection & Alarm System Control Panel Engineering and Commissioning Instructions (TO BE RETAINED BY THE COMMISSIONING ENGINEER) 26-0338 Issue 9 Fike s policy is one of continual improvement

More information

Operation and Maintenance Manual

Operation and Maintenance Manual (FKER Series) Repeater Panel (FKER, FKER, FKER8) Operation and Maintenance Manual Man-9EL Issue June Index Section Page. Introduction.... Safety and mounting.... Technical specification.... Control panel

More information

AlertMaxx2. Installation & Operating Manual. Ground Water (DMS-298) Pump Station High Level Alarm

AlertMaxx2. Installation & Operating Manual. Ground Water (DMS-298) Pump Station High Level Alarm Ground Water (DMS-298) Installation & Operating Manual Pump Station High Level Alarm T. E. W. 01992 523 523 info@deltamembranes.com www.deltamembranes.com Delta House, Merlin Way, North Weald, Epping,

More information

5000 INSTALLATION GUIDE

5000 INSTALLATION GUIDE 5000 INSTALLATION GUIDE Table of Contents Section Page No 1. INTRODUCTION... 3 2. WARNINGS AND CAUTIONS... 3 3. UNPACKING... 3 4. INSTALLATION... 4 5. CONTROL PANEL - REMOVING ITEMS BEFORE MOUNTING...

More information

Rectifier RC-series. Manual RC-series English MA doc. Manual Wall and 19 English

Rectifier RC-series. Manual RC-series English MA doc. Manual Wall and 19 English Rectifier RC-series Manual RC-series English Manual Wall and 19 English Presentation The RC-series is a rectifier for either directly powering the load or for use together with batteries. It is designed

More information

Operating manual and Log book for the range of 1,2,4 and 8 zone fire Control and Repeat panels

Operating manual and Log book for the range of 1,2,4 and 8 zone fire Control and Repeat panels Operating manual and Log book for the range of 1,2,4 and 8 zone fire Control and Repeat panels The panels are designed in accordance with the requirements of EN54 Part 2:1997 (and include optional clauses

More information

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual We manage heat MANUAL Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual 1850 N Sheridan Street South Bend, Indiana 46628 (574) 233-1202 or (800) 234-4239

More information

ZSC100 Gas Detection and Alarm System Controller

ZSC100 Gas Detection and Alarm System Controller ZSC100 Gas Detection and Alarm System Controller User Guide 1- Introduction... 3 1.1- General description... 3 1.2- Cautions and warnings... 3 2- Control panel... 4 2.1 Control panel overview... 4 2.2

More information

GS100M Gas Detection Controller

GS100M Gas Detection Controller GS100M Gas Detection Controller GS100M 1 Zone Gas Detection Controller 1 Zone / Sensor Conventional Positive Safety IP44 EN61010-1 EN50270 FEATURES Single Zone Protection Positive Safety Option Detection

More information

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL Document No...G108WO1.DOC Serial No... Issue Date...17 th SEPTEMBER 1999 Software Version...1.4 APPROVED TO: NZS 4512:1997 AS/NZS 3548:1992 Fire Alarm

More information

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL 3500 CONVENTIONAL FIRE ALARM CONTROL PANEL USER MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273 Web:

More information

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER Application The unit is primarily intended for use where there is a requirement to integrate a limited fire protection function into a larger control equipment scheme, or in specialist applications where

More information

5, SE GÅNGHESTER,

5, SE GÅNGHESTER, KSUB Control and monitoring unit Valid from week of manufacture 48/2005 Description The KSUB is a control and monitoring unit designed to control various types of fire/smoke dampers and fans in a flexible

More information

The EN54 Part 2 & 4 Fire System

The EN54 Part 2 & 4 Fire System Scope of work: To design, supply, install and commission an Analogue Addressable Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54

More information

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08 Beacon 200 Gas Monitor Operator s Manual Part Number: 71-2102RK Released: 6/6/08 Table of Contents Chapter 1: Introduction.................................................3 Overview.............................................................3

More information

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL TRACON MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL TABLE OF CONTENTS FPT 130 Overview... 2 Installation... 3 Power Source and Load Connections... 4 Temperature Sensor... 5 External

More information

Control Panel User Guide

Control Panel User Guide Fire Detection & Alarm System Control Panel V4.14 Control Panel User Guide (TO BE RETAINED BY USER) 26-0397 Issue 6 Fike s policy is one of continual improvement and the right to change a specification

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd full installation, commissioning and operating manuals can be downloaded from www.haes-systems.co.uk combined addressable / conventional fire alarm control panel User Guide Approved Document No. MFBU-04

More information

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV LC1 & 2 Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV ZIRCONLC1 One Zone Conventional Fire Panel ZIRCONLC2 Two Zone Conventional Fire Panel Compliant with EN54-2:1998 & EN54-4:1998

More information

BiWire Flexi. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI Installation Manual

BiWire Flexi. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI Installation Manual BiWire Flexi BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI Installation Manual Contents Contents 1. INTRODUCTION... 4 1.1 Purpose...4 2. THE BIWIRE FLEXI FIRE DETECTION & ALARM

More information

Hydrosense. Vimpex Limited. Star Lane. Great Wakering. Essex SS3 0PJ. Tel: +44 (0) Fax +44 (0)

Hydrosense. Vimpex Limited. Star Lane. Great Wakering. Essex SS3 0PJ. Tel: +44 (0) Fax +44 (0) Overview of the Water Detection System 2 Components of a System 4 Design & Planning 5 System Installation Notes 7 Control Panel Installation - HSCPI-K3000 8 Control Panel Commissioning HSCPC-K3000 11 Front

More information

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL 3500 CONVENTIONAL FIRE ALARM CONTROL PANEL INSTALLATION AND COMMISSIONING MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax:

More information

USER MANUAL & MAINTENANCE GUIDE OG OO

USER MANUAL & MAINTENANCE GUIDE OG OO M+48. USER MANUAL & MAINTENANCE GUIDE OG OO What to do if the Fire Alarm Panel shows an Alarm (Red LED) Write down which LEDs are lit (either in the log book, or on a piece of paper for transferring to

More information

Smoke Vent Control Panel RZN 4202 V1

Smoke Vent Control Panel RZN 4202 V1 Instruction for use Smoke Vent Control Panel RZN 4202 V1 Safety system protects human life and material assets! Once a year functional testing by a specialist company, authorized by the manufacturer. Connection,

More information

Safegard V4 Bespoke Intelligent Damper Control and Monitoring System

Safegard V4 Bespoke Intelligent Damper Control and Monitoring System August 2016 Range and Features All system wide activity is logged and viewable for diagnostics and preventative maintenance Safegard V4 Bespoke Intelligent Damper Control and Monitoring System Devices

More information

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum. September 29, 1997 Firecycle III 433 a 1. PRODUCT NAME VIKING Model E-1 Manufactured 1997 Present 2. MANUFACTURED FOR THE VIKING CORPORATION 210 N Industrial Park Road Hastings, Michigan 49058, U.S.A.

More information

Scope. Warning sounders except specific requirements. Intercom Systems for Emergency Purposes. Sound Systems for Emergency Purposes

Scope. Warning sounders except specific requirements. Intercom Systems for Emergency Purposes. Sound Systems for Emergency Purposes Scope Section 6 covers all Control and Indicating Equipment including Local Alarm systems. Section 6 also covers all detectors and input/output devices, including Occupant Warning sounders except specific

More information

DMWD 1 to 4 Zone Water Detection Alarm with Distance to Leak Measurement Installation and Operation Manual

DMWD 1 to 4 Zone Water Detection Alarm with Distance to Leak Measurement Installation and Operation Manual CMR Electrical Ltd Bolton House Five Chimneys Lane Hadlow Down East Sussex TN22 4DX Tel: 01825 733600 DMWD 1 to 4 Zone Water Detection with Distance to Leak Measurement Installation and Operation Manual

More information

ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL

ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL PRODUCT Specification FEATURES Designed To Meet The Requirements Of EN54 Expandable From 1 To 5 Loops As Standard A Variety Of Networking Options

More information

LEAKSTOPPER MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND OPERATION MANUAL

LEAKSTOPPER MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND OPERATION MANUAL LEAKSTOPPER MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND OPERATION MANUAL The LeakStopper Multizone detects the presence of water in environments where it is not supposed to be. Should water

More information

System 800 Addressable Fire Detection & Alarm System

System 800 Addressable Fire Detection & Alarm System SECTION 5: page 1 Section 5: System 800 Addressable Fire Detection & Alarm System SECTION 5: page 3 10 reasons to specify 800 1 Plug and Play A user friendly panel not requiring special software tools

More information

FIRE ALARM CONTROL PANEL FVC01-08

FIRE ALARM CONTROL PANEL FVC01-08 FIRE ALARM CONTROL PANEL FVC01-08 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Radal Technology Limited Unit 1, Webber Court Billington Road, Burnley Lancashire, BB11 5UB Tel: +44 (0) 1282 463 770 Fax: +44

More information

Conventional Fire Alarm System 2014 V1.2

Conventional Fire Alarm System 2014 V1.2 Conventional Fire Alarm System 2014 V1.2 Product Overview Control Panel 2 Conventional Fire Panel GST102A 2 zone Fire panel GST104A 4 zone Fire panel GST108A 8 zone Fire panel GST116A 16 zone Fire Panel

More information

OPERATION AND INSTALLATION MANUAL

OPERATION AND INSTALLATION MANUAL EX+Plus 2 ZONE, 1AREA EXTINGUISHANT CONTROL PANEL OPERATION AND INSTALLATION MANUAL INTRODUCTION The Premier EX Plus is a 2 zone, single area panel for controlling the release of extinguishing gases in

More information

PRODUCT INSTRUCTIONS. Fire Door Control Panel (FDCP) Stock Code Description Doc No: PI-115. Ellard Fire Door Control Panel Ellard Slave Repeater Unit

PRODUCT INSTRUCTIONS. Fire Door Control Panel (FDCP) Stock Code Description Doc No: PI-115. Ellard Fire Door Control Panel Ellard Slave Repeater Unit PRODUCT INSTRUCTIONS Fire Door Control Panel (FDCP) Floats Rd, Wythenshawe, Manchester. M23 9WB T: 44 (0)161 945 4561 F: 44 (0)161 945 4566 Stock Code Description Doc No: PI115 00133 00134 Ellard Fire

More information

CellarSafe. Carbon Dioxide and Oxygen Safety Monitor

CellarSafe. Carbon Dioxide and Oxygen Safety Monitor CellarSafe Carbon Dioxide and Oxygen Safety Monitor Installation and operating instructions for the CellarSafe Monitor and the CellarSafe Calibration Unit M07234 May 2008 Issue 6 Warning Please take care

More information

Application, Installation, Operation & Maintenance Manual

Application, Installation, Operation & Maintenance Manual APPROVED BY:JBJ PRESCIENT III FIRE ALARM & GAS EXTINGUISHING CONTROL PANEL Application, Installation, Operation & Maintenance Manual PAGE 1 of 43 CONTENTS 1. INTRODUCTION... 3 2. GENERAL DESCRIPTION...

More information

3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL

3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL 3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL USER MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273 Web:

More information

USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4

USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4 PREMIER EX8 EXTINGUISHING PANEL USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN 12094 PART 1 & EN54 PARTS 2 & 4 USER MANUAL Approved Document No: GLT.MAN-132 INDEX Extinguishing

More information

FEC400 Series. Installation Manual

FEC400 Series. Installation Manual FEC400 Series Conventional microprocessor controlled fire detection and alarm panels with extinguishing control Installation Manual Version 2.3 / August 2004 Aritech is a GE Interlogix brand. http://www.geindustrial.com/ge-interlogix/emea

More information

PAT E N T System 88. COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00

PAT E N T System 88. COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00 PAT E N T System 88 COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00 Pg 1 of 12 CONTENTS 1. GENERAL 1.1 Introduction 2 1.2 System Description

More information

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117 Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel Revision E 61117 CAUTION: (Read This First) This panel has been designed to make it nearly bullet proof to mistakes made when wiring

More information

Networked Access Control Panel. Installation Guide

Networked Access Control Panel. Installation Guide XP2M Networked Access Control Panel V1.0X Installation Guide X P 2 M A C C E S S C O N T R O L S Y S T E M Installation Guide Document Ref: PLAN XP2M Installation Guide V4(G)2010 Access Control Services

More information

Remote Vacuum Sensor and Variable Speed Vacuum Pump Control Manual. Version Date - June Part Number

Remote Vacuum Sensor and Variable Speed Vacuum Pump Control Manual. Version Date - June Part Number Innovation In and Out of Parlour Remote Vacuum Sensor and Variable Speed Vacuum Pump Control Manual Version - 1.0 Date - June 2016 Part Number - 39-0038 Index Manual Version... 3 About the Remote Vacuum

More information

PERTRONIC INDUSTRIES LTD F4-RMAX Installation Note

PERTRONIC INDUSTRIES LTD F4-RMAX Installation Note Product Overview: The Pertronic F4 Remote LED Mimic / Aux Relay Module F4-RMAX is an optional extra for the Pertronic F4 conventional 4-zone fire alarm panel. This board enables the fire alarm panel to

More information

Control Panel User Guide

Control Panel User Guide Fire Detection & Alarm System Control Panel (Suitable for TWINFLEX pro control panels from V1.00) Control Panel User Guide (TO BE RETAINED BY THE USER) 26-1028 Issue 2 Fike s policy is one of continual

More information

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual We manage heat MANUAL Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual 1850 N Sheridan Street South Bend, Indiana 46628 (574) 233-1202 or (800) 234-4239

More information

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL USER MANUAL 1 Table of Contents 1 SAFETY INFORMATION...3 1.1 SAFETY PRECAUTIONS DURING NORMAL OPERATION OF PANEL...3 1.3 BATTERY INFORMATION...3

More information

The most user friendly Security Alarm System L S Section 1 Overview of System Section 2 Planning your Installation

The most user friendly Security Alarm System L S Section 1 Overview of System Section 2 Planning your Installation The most user friendly Contents Section 1 Overview of System 1.1 Kit Contents 1.2 Tools Required 1.3 System Features Security Alarm System L S 4 0 0 Section 2 Planning your Installation 2.1 Location of

More information

LEAKMONITOR MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND USER OPERATION MANUAL

LEAKMONITOR MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND USER OPERATION MANUAL LEAKMONITOR MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND USER OPERATION MANUAL The LeakMonitor alarm panel is a microprocessor controlled fully adjustable alarm system suitable for multizone

More information

The EN54 Part 2, 4 and 13 Fire System

The EN54 Part 2, 4 and 13 Fire System Scope of work: To design, supply, install and commission an Analogue Addressable Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54

More information

Excel-EN Conventional Fire Control Panel

Excel-EN Conventional Fire Control Panel Available as 2, 4, 6, 8,10 or 12 zones Approved to EN54-2 & 4 Modular expansion zone cards Programmable relays and outputs Optional additional sounder circuits Optional additional programmable outputs

More information

Operating instructions SENTRI4 Control panel based Fire detection and alarm system

Operating instructions SENTRI4 Control panel based Fire detection and alarm system 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32 Zones Healthy 15:45 Fault Power Fault System Fault SenTRI 4 Fire System Designed to EN54 Pt 2 & 4 Operating instructions

More information

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63 Fire Extinguishing Control Panel FS5200Е INSTRUCTION MANUAL Revision 8/01.17 Instruction Manual Page 1 1. 2. 3. 4. 4.1. 4.2. 4.2.1. 4.2.2. 4.2.3. 4.2.4. 4.2.5. 4.2.6. 4.2.7. 4.2.8. 4.2.9. 4.2.10. 4.2.11.

More information

User manual and installation instruction Control for Fire Ventilation RV / RV 24-32

User manual and installation instruction Control for Fire Ventilation RV / RV 24-32 User manual and installation instruction Control for Fire Ventilation RV 24-24 / RV 24-32 Fire ventilation Comfort ventilation 24VDC max. 24/32A 2 Actuator outputs 1 Fire ventilation group, 2 comfort groups

More information

VoCALL - CFVCC5. Compact 5 Line Exchange Unit. Installation & Commissioning Manual

VoCALL - CFVCC5. Compact 5 Line Exchange Unit. Installation & Commissioning Manual VoCALL - CFVCC5 Compact 5 Line Exchange Unit Installation & Commissioning Manual Introduction A VoCALL Emergency Voice Communications System (EVCS) is a fixed, secure, bi-directional, full duplex voice

More information

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE D (OPERATION) INITIATE A DYNAMIC BATTERY TEST The system tests the back-up battery once every 24 hours. The owner can initiate a dynamic battery test at any time with the following codes while the system

More information

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option Installation PS6 SERIES Power Supplies PS6 SERIES Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option Installation and Specifications Manual ISDPS6_SERIES 08121590 PCN15016 R05/15GR

More information

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT TRACON MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT TABLE OF CONTENTS GPT 130 Overview... 2 Installation... 3 Power Source and Load Connection... 4 Temperature Sensor Installation... 5 Panel

More information

Actionpac LNS3 Intelligent Damper Control and Monitoring System

Actionpac LNS3 Intelligent Damper Control and Monitoring System November 2005 Actionpac LNS 3 NEW AND ENHANCED Intelligent Damper Control and Monitoring System Range and Features Panel PC Driven system. User friendly, no need for operating and maintenance manual. Full

More information

INSTRUCTION MANUAL (ATEX/IECEx/SIL2) BExBG05D-SIL Flameproof Xenon SIL 2 Beacons For use in Flammable Gas and Dust Atmospheres

INSTRUCTION MANUAL (ATEX/IECEx/SIL2) BExBG05D-SIL Flameproof Xenon SIL 2 Beacons For use in Flammable Gas and Dust Atmospheres INSTRUCTION MANUAL (ATEX/IECEx/SIL2) BExBG05D-SIL Flameproof Xenon SIL 2 Beacons For use in Flammable Gas and Dust Atmospheres 1) Introduction The BExBG05D-SIL is a flameproof beacon which is certified

More information

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES POWER SUPPLY AND BATTERY CHARGER AC AND DC STATUS INDICATORS ENOUGH POWER TO SUPPORT UP TO 3 MAGLOCKS OR ELECTRIC STRIKES PLUS REQUIRED

More information

Surveyor Envoy-MINI 4

Surveyor Envoy-MINI 4 Surveyor Envoy-MINI 4 CONTENTS SECTION 1 INTRODUCTION Page 4 About this manual Page 4 System design and planning Page 4 Panel types Page 4 General Page 4 SECTION 2 INSTALLATION Page 5 General Page 5 ESD

More information

6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL

6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL 6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL USER MANUAL Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0)

More information

The EN54 Part 2 and 4 Fire System

The EN54 Part 2 and 4 Fire System Scope of work: To design, supply, install and commission a Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54 Part 2 and 4 Fire

More information

Logbook. Precept EN Fire Detection/Alarm Panel. & Precept EN Repeater

Logbook. Precept EN Fire Detection/Alarm Panel. & Precept EN Repeater APPROVED BY: JBJ Precept EN Fire Detection/Alarm Panel & Precept EN Repeater Logbook PAGE 1 of 19 List of Contents 1. FIRE ALARM SYSTEM MAINTENANCE... 3 2. USER RESPONSIBILITIES... 3 2.1. RESPONSIBLE PERSON...

More information

OPERATION & INSTALLATION MANUAL FOR ALARM PANEL M2AP01

OPERATION & INSTALLATION MANUAL FOR ALARM PANEL M2AP01 OPERATION & INSTALLATION MANUAL FOR ALARM PANEL M2AP01 Table of Contents Safety Instructions 4 Owner/Operator Responsibility 4 Specifications 5 Introduction 6 Installation Instructions 7 Setup 7 Wiring

More information

QUICKFIT INSTALL HOOK-UP SHEET FOR ESL KIT REV 1.17 OP

QUICKFIT INSTALL HOOK-UP SHEET FOR ESL KIT REV 1.17 OP QUICKFIT INSTALL HOOK-UP SHEET FOR ESL KIT REV 1.17 OP PROGRAMMING STARTS Entering Installer mode If you want to get into program mode press followed by your installer code, default set to 000000

More information

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual We manage heat MANUAL Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual 1850 N Sheridan Street South Bend, Indiana 46628 (574) 233-1202 or (800) 234-4239

More information

V3 Intelligent Damper Control and Monitoring System

V3 Intelligent Damper Control and Monitoring System March 2011 V3 Intelligent Damper Control and Monitoring System Range and Features All system wide activity is logged and viewable for diagnostics and preventative maintenance Devices powered by closest

More information

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module FIRE ALARM CONTROL EQUIPMENT Addendum October 2006 Instructions for new style EN54-4 Power supply unit module MXLK-05 Issue 2.0 June 2007 INSTALLATION Safety Suppliers of articles for use at work are required

More information

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN Honeywell 12 Clintonville Road Northford, CT 06472 http://www.honeywellpower.com HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN 04-350 Product Installation

More information

INSTRUCTION MANUAL A131 High Level Audible Warning System / Battery backup

INSTRUCTION MANUAL A131 High Level Audible Warning System / Battery backup 115 or 230VAC (90V to 264V AC range) Operating Temp: -20 to +55 C IP Rating: IP66 Weight: 5.5 kg single AC unit 7.0 kg four way AC unit Marking: Installation Requirements 1) Introduction The A131 high

More information

CONVENTIONAL CONTROL PANEL FL2/4/8/12 LT-XP

CONVENTIONAL CONTROL PANEL FL2/4/8/12 LT-XP FLx-LT-XP CONVENTIONAL CONTROL PANEL FL2/4/8/12 LT-XP Installation, Configuration and Operating Manual MAY 2008 MIE-MI-580I_FL rev.003 Information in this document is subject to change without notice.

More information

Control Panel User Guide (TO BE RETAINED BY THE USER)

Control Panel User Guide (TO BE RETAINED BY THE USER) Fire Detection & Alarm System Control Panel V3 (Suitable for Quadnet control panels from V2.00) Control Panel User Guide (TO BE RETAINED BY THE USER) 26-0585 Issue 7 Fike s policy is one of continual improvement

More information

Fire Control Panel. Installation & Programming Manual TABLE OF CONTENTS

Fire Control Panel. Installation & Programming Manual TABLE OF CONTENTS Fire Control Panel Installation & Programming Manual TBLE OF CONTENTS Page Getting Started 2 Power Supply Unit 3 Inputs 4 Outputs 4 LED Indications 4 User Keypad Functions 5 Engineer Keypad Functions 6

More information

Operating manual and Log book for the range of 1,2,4 and 8 zone fire Control and Repeat panels

Operating manual and Log book for the range of 1,2,4 and 8 zone fire Control and Repeat panels Operating manual and Log book for the range of 1,2,4 and 8 zone fire Control and Repeat panels The panels are designed in accordance with the requirements of EN54 Part 2:1997 (and include optional clauses

More information

Unity DAU Voice Alarm System

Unity DAU Voice Alarm System Unity DAU Voice Alarm System User Manual & Log Book Site Name Address Contractor Commissioned Introduction Voice Alarm (VA) systems are the quickest way to evacuate the public & staff from a building.

More information

Fire detection and alarm

Fire detection and alarm Fire detection and alarm Aesthetic Install all cabling and cable containment neatly and unobtrusively, meeting the highest electrical industry installation standards. Neatly lay and securely fix cables.

More information

An introduction to... Sigma

An introduction to... Sigma An introduction to... Sigma XT+ Sigma XT+ Overview The Sigma XT+ 21000 series are the latest additions to the Sigma family of control equipment from Kentec Electronics Limited. The Sigma XT+ range combines

More information

Fire Control Panel FS5100

Fire Control Panel FS5100 Fire Control Panel FS5100 INSTRUCTION MANUAL Revision 6/02.11 Contents 1. Introduction... 5 2. Terminology... 5 3. Function... 7 4. Technical data... 7 4.1. Modules... 7 4.1.1. Type of modules... 7 4.1.2.

More information