SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

Size: px
Start display at page:

Download "SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD"

Transcription

1 PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard is to be used in the development of all fire detection/alarm system designs for buildings and structures at The University of Texas at Austin. This standard is to apply to all fire detection/alarm system components and equipment installed at any University of Texas at Austin campus during new construction or as part of any improvement project. OBJECTIVES This standard is intended to achieve consistently high levels of fire detection/alarm system performance by: CONCEPTS Allowing designers to incorporate required or desired features as early in the design development process as possible. Assuring all systems are designed to meet all applicable codes, ordinances, laws, and sound engineering judgment. Providing a basis for a general understanding among all parties involved in the design of systems. All systems are to be compliant with applicable paragraphs of NFPA Code 101 "Life Safety Code". All systems are to be compliant with the requirements of National Fire Protection Association Code 72 "The National Fire Alarm Code". In addition to the requirements of Life Safety Code, The National Fire Alarm Code and the Americans with Disabilities Act, all fire detection/alarm systems installed in structures NOT protected throughout by a supervised, code compliant water-based fire suppression system are to be designed to provide smoke detection to the level of Partial Detection as described at NFPA 101, Par for all areas listed below: 1) The entire route of egress to include corridors, stairs, escalator locations, foyers, anterooms, reception areas, exit, etc. 2) Public or common access areas to include rest rooms, class rooms, reception areas, teaching laboratories, auditoria, gymnasia, cafeterias, theaters, conference rooms, duplication rooms, kitchens, etc. 3) Special hazard areas to include mechanical equipment rooms, electrical closets, storage rooms, janitorial storage areas, etc. Areas or rooms deemed by the Owner to deserve special protection due to high value content or historical significance such as library stack areas, art storage and/or restoration areas, rare book deposit areas, etc. In addition to the requirements of Life Safety Code, The National Fire Alarm Code and the Americans with Disabilities Act, all fire detection/alarm systems installed in structures that ARE protected throughout by a supervised, code compliant water-based fire suppression system are to be designed to provide smoke detection to the level of Partial Detection as described at NFPA 101, Par for all areas listed below: 1) The entire route of egress to include corridors, stairs, escalator locations, foyers, anterooms, reception areas, exit, etc. Design & Construction Standards, Revised December 14,

2 2) Special hazard areas to include mechanical equipment rooms, electrical closets, storage rooms, janitorial storage areas, etc. 3) Areas or rooms deemed by the Owner to deserve special protection due to high value content or historical significance such as library stack areas, art storage and/or restoration areas, rare book deposit areas, etc. Audible alarming as required by NFPA 72, must be provided throughout the building. Visual alarming to ADA levels must be provided throughout the building. Smoke detectors must be provided at all elevator lobbies, elevator equipment rooms and elevator hoistways to perform capture/recall functions. All systems must be designed to provide manual means of alarm initiation at every exit from every level. Elevators are not to be considered an exit or route of egress. DESCRIPTION OF WORK All designs must provide for each building a complete and working digital, addressable voice alarm, closed circuit, automatic and manual fire detection / alarm system for each floor of the building to perform detection, monitoring and alarm functions for the building. QUALITY ASSURANCE All equipment must be listed and approved by a testing laboratory that has been approved by the State of Texas Commission on Fire Safety. This listing is to be for all functions required by this standard. All systems must comply with applicable paragraphs of the National Electric Code. PART 2 - FIRE DETECTION AND ALARM SYSTEM EQUIPMENT TYPE OF SYSTEM All system product lines must be comprised of components capable of providing the following features when appropriate and specified: A. Floor above/floor below notification. B. Private alarm notification. C. Occupied/unoccupied notification. D. Voice alarm notification. E. Fireman's communications. F. Elevator capture/recall. G. Elevator power shunt trip. H. Smoke control/fan shutdown. I. Automatic door control. EQUIPMENT Fire Alarm Control Panel (FACP) : All fire alarm control panels must be Central Processing Unit (CPU) based. All FACP's must be capable of providing circuit integrity monitoring for all Signaling Line Circuits at a level of Style 6, (NFPA 72, Table 3-6.1, "Performance and Capacities of Signaling Line Circuits [SLC]"). Design & Construction Standards, Revised December 14,

3 All FACP's must be capable of providing circuit integrity monitoring of Initiating Device Circuits (IDC's) at a level of Style B (Class B), (NFPA 72, Table 3-5.1, "Performance and Capacities of Initiating Device Circuits [IDC]"). All FACP's must be capable of providing circuit integrity monitoring of Notification Appliance Circuits (NAC's) at a level of Style Y (Class B), (NFPA 72, Table 3-7.1, " Notification Appliance Circuits [NAC]"). All FACP's must be capable of providing circuit integrity monitoring of Control Device Circuits (CDC) at a level equal to a Style Y (Class B) Notification Appliance Circuit. Smoke detector "Alarm Verification" timing for Signaling Line Circuit systems must be provided. All FACP's must provide twenty percent (20%) excess power supply capacity to allow for future expansion by the owner. Zone labeling must be textual by alpha-numeric display at the FACP and remote annunciator to allow first response by persons not trained in fire alarm technology. Textual (alpha-numeric) language must be conventional, concise, clear and accurate to facilitate rapid response. All FACP's must provide a control to silence the Public Alarm to allow for maintenance and testing and to reduce disruption. All FACP's must provide a control to override the smoke control/fan shutdown feature to allow for maintenance and testing. All FACP's must be connected to a Primary and Secondary Power source. Batteries must be contained within an enclosure separate from all electronics components to prevent corrosive damage. All FACP's must provide a separate digital address for each initiating device except valve position supervisory switches to facilitate rapid response and maintenance and testing. All FACP's must provide a separate digital address for each individual flow switch. All FACP's must provide one digital address for each group of valve position supervisory switches physically located in one room, to a maximum of five (5) per address. All programming must be permanent and non-volatile to reduce outage time due to failure. All FACP's must provide a printed log of all status change activity. All FACP's must be listed and approved as the smoke detector sensitivity test set to reduce maintenance costs. All FACP's must be capable of providing drift compensation. Drift compensation is considered equal to adjustability at the detector. All FACP s must be field programmable, using internal or connected components, for all changes, alterations, modifications, additions, deletions and hardware and software upgrades. All FACP s must be capable, using internal or connected components, of generating comprehensive reports for sensitivity, verification counts, address registers. Remote Monitor Design & Construction Standards, Revised December 14,

4 All systems must be capable of interconnection to the campus-wide Proprietary Supervisory Signaling System by contact closure (EOL) for the following events: ALARM WATERFLOW TROUBLE SUPERVISORY All systems must provide a Wiring Interface Panel (junction box) to accommodate the connection between the new system and the existing Proprietary Protective Signaling System. The WIP must be located at the closest part of the mechanical equipment room closest to the campus utilities tunnel system. Conduit and conductors must be provided between this panel and the FACP to accomplished all features listed above. Distributed Power Supplies: Distributed power supplies for powering Notification Appliance Circuits, beam smoke detectors and control relays may be used. All distributed power supply inputs must be controlled by addressable interface devices located on the same floor levels as the power supply and controlled by the SLC serving the area to facilitate maintenance. Manual Stations: All manual stations must be of the plate glass deterrent, "double-action" type to reduce accidental or vandalized alarms. Each manual station must have a unique digital address on the SLC. Thermodetectors: All thermodetectors must be combination fixed temperature and rate-of-rise, spot type. Each thermodetector must have a unique address on the SLC. Non resetting detectors must give visual indication of "ALARM" condition to facilitate rapid response. Smoke Detectors: Each smoke detector, spot or beam, must have a unique digital address on the SLC. All smoke detectors must be field measurable and adjustable for sensitivity. Drift compensation will be considered equal to field adjustability. All smoke detectors, except projected beam type, must derive power from the SLC. The FACP must function as the smoke detector sensitivity test set and must be approved and listed for that service. All smoke detectors must meet or exceed the requirements of Underwriter's Laboratory Standard 268, as amended, and must be listed and approved for use with the FACP provided. Duct-Mounted Smoke Detectors: It is the responsibility of the Contractor to assure that all "supply air" is sampled. Projected-Beam Smoke Detectors: All projected-beam detectors must operate on the infrared principle. Design & Construction Standards, Revised December 14,

5 All projected-beam detectors must have automatic gain control circuits to compensate for deterioration of signal strength due to environmental factors such as dirt and dust accumulation, component aging and temperature fluctuations. Transmitting and receiving units of projected-beam detectors must be protected from physical damage. All projected-beam smoke detectors must have circuits to prevent "false" alarms due to sudden and complete obscuration. Waterflow Switches: Fire detection/alarm systems must be interconnected to the fire sprinkler systems by waterflow switches capable of delay (retard) prior to the "ALARM". Each waterflow switch must have a unique digital address on the SLC. It is the responsibility of the Contractor to decide the specific placement of the waterflow switches to assure indication of water flow within the building and at each level of the building to reduce water damage. All waterflow switches must be provided with a proper, code-compliant Inspector's Test valve and drain to allow proper testing. Supervisory (Tamper) Switches: Switches must be installed on all valves to indicate any disarrangement of valves within a sprinkler, fire hose cabinet or dry standpipe system which would reduce the effectiveness of the system. Audible Appliances: Audible notification appliances must be speakers or horns. Signal generated must be the distinctive threepulse temporal pattern described by NFPA and ANSI codes. When generated by speakers, The Evacuation Signal must be alternated with a custom textual message. Visual Appliances: All visual notification appliances must be xenon strobe, compliant with current requirements of the Americans With Disabilities Act (ADA), All visual notification appliances must be synchronized to prevent an effective flash rate of greater than one hertz in any space. Remote Annunciator: When allowed and/or required by the project documents, a remote annunciator may be located in an open accessible area at or adjacent to the main ground level entrance to the building. The FACP may then be located elsewhere. Remote annunciator must impart the same fire location information as the main FACP. Monitoring Devices: Addressable monitoring devices used to monitor contact-closure initiating devices such as duct-mounted smoke detectors, waterflow switches and tamper switches must derive power from the SLC to which they are connected. Each monitoring device must have a unique digital address on the SLC. Design & Construction Standards, Revised December 14,

6 Monitoring devices must not be used to interface smoke detectors other than duct-mounted smoke detectors to the SLC. Control Devices: Addressable control devices used to switch Notification Appliance Circuits must derive operating power from the SLC. Addressable control devices must not control more than one type of appliance/device. PART 3 - INTERCONNECTION AND OPERATION GENERAL SIGNALING LINE CIRCUITS (SLC) All FACP's must be capable of providing circuit integrity monitoring for all Signaling Line Circuits at a level of Style 6, (NFPA 72, Table 3-6.1, "Performance and Capacities of Signaling Line Circuits [SLC]"). All the following devices/appliances must be individually addressed on the SLC: a) Smoke detectors. b) Heat detectors. c) Manual stations. d) Monitor devices. e) Control devices. f) Fault isolation devices. g) IDC's. h) Audio NAC's. i) Visual NAC's. j) CDC's. Digital addressable loops must be configured as Class A, Style 6, Signaling Line Circuits (SLC) as described at Table 3-6.1, "Performance and Capacities of Signaling Line Circuits (SLC)", NFPA 72. A fault isolation device must be provided electrically between each building level. The device must be powered by the SLC loop. INITIATING DEVICE CIRCUITS (IDC) Initiating Device Circuits (IDC's) must be monitored at a level of Style B (Class B), (NFPA 72, Table 3-5.1, "Performance and Capacities of Initiating Device Circuits [IDC]"). Monitoring shall be accomplished by a monitoring device. IDC's are must limited to: 1) Only one duct mounted smoke detector or 2) Only one waterflow switch or 3) No more than five (5) tamper switches, all located in one room. NOTIFICATION APPLIANCE CIRCUITS (NAC) Design & Construction Standards, Revised December 14,

7 All Notification Appliance Circuits (NAC's) must be monitored at a level of Style Y (Class B), (NFPA 72, Table 3-7.1, " Notification Appliance Circuits [NAC]"). Direct current notification appliance power provided from the FACP must be distributed on Style 6 loop to all control devices in the system. Direct current notification appliance power provided from a distributed power supply must be controlled by a digital addressable control device on the SLC. Voice frequency notification appliance signal must be provided by the FACP amplifiers and distributed on a Style 6 loop. Audible notification appliances and visual notification appliances must always be connected to separate NAC's to facilitate maintenance. CONTROL DEVICE CIRCUITS (CDC) Control Device Circuits (CDC) must be monitored at a level equal to a Style Y (Class B) Notification Appliance Circuit. FLOOR ABOVE/FLOOR BELOW NOTIFICATION In high rise structures, each level must constitute a minimum of one audio Notification Appliance Circuit and one visual Notification Appliance Circuit. NAC's must cause the Public Alarm to sound on the level on which the "ALARM" condition originates, one level directly above, one level directly below. The FACP must also provide a control to allow sounding the Public Alarm throughout the structure (Allcall). PRIVATE ALARM NOTIFICATION When allowed, the Public Alarm must provide an adjustable delay to allow time for investigation. The Private Alarm must be audible and visual at a point designated on the project documents. If no response is made at the FACP within a set time, the Public Alarm must sound. Keyed override must be provided. OCCUPIED/UNOCCUPIED NOTIFICATION When appropriate the FACP must provide an "OCCUPIED/UNOCCUPIED" control to allow the disabling of portions of the Public Alarm to reduce panic hazard. VOICE ALARM NOTIFICATION The audible portion of the Public Alarm for all systems must be Voice Alarm. Signals generated must be the Distinctive Evacuation Signal (three-pulse temporal pattern) alternated with a digitized custom textual message. The FACP must allow voice paging to selected areas. The FACP must provide an "all-call" control. FIREMAN'S COMMUNICATIONS When appropriate a complete and separate Fireman's communications system must be provided. Design & Construction Standards, Revised December 14,

8 The command center must be at or adjacent to the FACP. Wiring for the Fireman's Communications System must remain separate from the fire detection/alarm system. Common raceway or conduit may be used. ELEVATOR CAPTURE/RECALL Elevator capture/recall must be initiated by the smoke detectors designated as recall detectors, including one in each elevator lobby, as required in hoistways and elevator equipment rooms. Elevator capture/recall must operate to a Primary destination level and to a Secondary destination level. SMOKE CONTROL/FAN SHUTDOWN Alarm initiation by duct-mounted smoke detectors must cause shutdown of associated air handling units. Motor control circuits must not be routed through the housing. The SLC must connect to a control device to interrupt the motor control circuits. The control device must be assigned a unique digital address on the SLC. A "BYPASS" control must be provided at the FACP. AUTOMATIC DOOR CONTROL Automatic Release-to-Close: Smoke control doors normally held open electrically must be allowed to close upon any "ALARM" condition. Automatic Unlock: Access control doors normally electrically locked for security must unlock on any "ALARM" condition. WIRING Basic wiring materials must comply with requirements of Division 16 Basic Electrical Materials and Methods sections, "Raceways" and "Electrical Boxes and Fittings"; types to be selected by contractor. Conductor sizes must be AWG #14 or larger, solid, except when decorative raceway is surface mounted. All wiring must be in conduit or raceway. PART 4 - SPECIAL CONDITIONS GENERAL It is the responsibility of the Contractor to assure that there is no disruption of The University's normal functions such as study, testing, class, research or administration. CONNECTING TO EXISTING SYSTEMS Connections to or operation of existing systems must be performed by or supervised by Electronics Shop staff. PART 5 - TESTING Design & Construction Standards, Revised December 14,

9 GENERAL: Upon completion of the system, the Contractor must perform a complete and comprehensive test of the entire system in accordance with the provisions of Chapter 7, NFPA 72, "The National Fire Alarm Code". SCOPE: It is the responsibility of the Contractor to demonstrate to The University's representative that the system is installed and functions in accordance with the project documents and applicable codes. SPECIFIC TESTS: An Acceptance Test will be conducted at the completion of each project. The test will be the responsibility of the contractor and must be performed in strict compliance with the provisions of NFPA 73, Chapter 7. In addition to the provisions of NFPA 72 and/or the above paragraph, it is the responsibility of the Contractor to provide: Smoke detector sensitivity report. Pressure differential readings for duct detector sample air flow. Closed loop resistance and EOL resistance readings for all field wiring. Programming volatility test. PART 6 - DOCUMENTATION GENERAL: A documentation package must be provided by the Contractor that shall include all information needed to allow The University to perform additions, modifications, maintenance and repair of the system. This must include: Equipment schematic diagrams for all components and modules. Equipment technical data. Field device address register. Equipment repair parts lists. Programming disk with all system software required for a re-start after traumatic failure. Software must be of appropriate and compatible update version for the firmware installed. "As-built " wiring, conduit diagrams to include: a. Floor plan layout drawings showing all significant conduit routes and sizes, wire amounts, sizes and color code and marshaling box locations. b. Riser diagram showing all significant conduit routes and sizes, wire amounts, sizes and color code and marshaling box locations. Floor plan device layout drawing to include: a. All initiating device locations and digital addresses. b. All notification appliance locations and NAC digital addresses. c. All control device locations and digital addresses. d. All monitor device locations for supervisory switch groups. e. All isolation device locations. f. All distributed power supply locations and digital addresses. g. Schematic representation of all SLC's, NAC's, control circuits, audio circuits and power circuits. Riser diagram to include: a. All initiating devices with their electrical location and digital address on the SLC. Design & Construction Standards, Revised December 14,

10 b. All notification appliances with their electrical location and digital address on the SLC. c. All control devices with their electrical location and digital address on the SLC. d. All supervisory switch locations and their interconnection to the monitor device (IDC's). e. All monitor devices with their electrical location and digital address on the SLC. f. The electrical location of all fault isolation devices. g. All distributed power supplies with their associated wiring and digital address(es) on the SLC. h. Schematic representation of all SLC's, NAC's, CDC's, audio circuits and power circuits. Interconnection diagram(s) for all internal components of the Fire Alarm Control Panel. Smoke detector calibration procedure. State of Texas or NFPA certification form. Programming guide for the functional programming to provide for changes to the zone schedule or other operational features. field WARRANTY: Backup copy of the operating system and/or all resident programming, software or firmware, which would be required to restore the system to full operation after a complete failure or equipment replacement. A system hardware component capable of storing and transporting the above listed programming and operating systems and reports. The warranty period of three years is to begin upon receipt of all required documents and the successful completion of the Acceptance Test. TRAINING The contractor shall provide, as part of the contract, training for two University technicians. Training shall be equivalent to the training provided for manufacturer s field service technicians. Training shall be provided at corporate training centers. Travel expenses, including transportation, housing and meals, shall be provided. Design & Construction Standards, Revised December 14,

2. HVAC and smoke control systems; fire, smoke, and combination fire/smoke dampers. 5. Central control and monitoring system.

2. HVAC and smoke control systems; fire, smoke, and combination fire/smoke dampers. 5. Central control and monitoring system. PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible.. This

More information

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used. PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire alarm and signaling systems at Sam Houston State University provide the highest level of life safety possible. This

More information

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications:

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications: PART 1 GENERAL 1.01 Quality Assurance A. Fire Alarm Contractor Qualifications: 1 The Fire Alarm contractor shall be an Edwards Systems Technology (EST) designated representative and authorized to sell,

More information

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications:

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications: PART 1 GENERAL 1.01 Quality Assurance A. Fire Alarm Contractor Qualifications: 1 The Fire Alarm contractor shall be an Edwards Systems Technology (EST) designated representative and authorized to sell,

More information

Smoke Detector Activation of any smoke detector shall start the alarm verification mode.

Smoke Detector Activation of any smoke detector shall start the alarm verification mode. Description: The purpose of the section is to provide the UMCP Design Standards for the design and implementation of Fire Alarm Systems at the UMCP campus. Related Sections: TBD Effective Date: July 10,

More information

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2

More information

DIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM

DIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM DIVISION 26 ELECTRICAL SECTION 26 81 11 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install all equipment and accessories for a complete local, analog addressable, manually and automatically actuated,

More information

Changes in NFPA

Changes in NFPA Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE Effective Date: 11/01/02 Purpose: MECKLENBURG COUNTY To establish a set of guidelines for performance testing of all newly installed or upgraded fire alarm systems in order to ensure that all devices and

More information

Michigan State University Construction Standards FIRE DETECTION AND ALARM PAGE

Michigan State University Construction Standards FIRE DETECTION AND ALARM PAGE PAGE 283100-1 SECTION 283100 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

Fire Alarm System Fundamentals

Fire Alarm System Fundamentals Fire Alarm System Fundamentals Mircom is the largest and oldest privately owned fire alarm and life safety manufacturer in North America and 5th largest overall with 50 years of industry experience. Mircom

More information

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016 Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting Prepared Especially for : OSFM TEC 2016 Acceptance Testing 11-2008 Agenda Before you begin Completing the

More information

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics. A28.1 Standard of Practice - Fire Alarm Systems NOTE: Significant revisions or additions to the previous standards are highlighted in italics. OBJECTIVE OF STANDARD To provide compliant smart addressable

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved

More information

Fire alarm system specification for multiple tenant retail buildings

Fire alarm system specification for multiple tenant retail buildings Date: June 20, 2011 Project name: Baederwood Shopping Center Multiple Tenant Buildings B & C City/ State: Abington, PA Landlord s Vendor Contact: Dan Morrin Jr., NECCO Security Phone: (215)638-7999 Email:

More information

Division 28 - Electronic Safety and Security

Division 28 - Electronic Safety and Security Division 28 - Electronic Safety and Security 28 31 11 Fire Alarm Systems Fire alarm systems shall be installed in buildings when required by this section. 1. Purpose: The primary purpose of a fire alarm

More information

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION FIRE ALARM SYSTEM

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION FIRE ALARM SYSTEM OSU PROJECT NO. 30-04-15 PAGE 1 PART 1 GENERAL 1.1 WORK INCLUDED A. Provide all labor, materials, and equipment required to provide a complete and operating system of manual and automatic detection devices,

More information

NFPA Changes

NFPA Changes Chapter 21, Emergency Control Functions and Interfaces Summary. Chapter 21 is new. These requirements were formerly found in Chapter 6, Protected Premises Fire Alarm Systems. The term fire safety function

More information

MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO

MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO Prepared For: Public Schools Facilities Authority State of New Mexico 2019 Galisteo, Suite

More information

Functional Performance Test

Functional Performance Test Fire Alarm Control Panel & Fire Alarm Annunciator Panel Notify all building occupants that testing will be conducted. Fire alarm contractor shall have personnel with 2-way radios at the fire alarm control

More information

COUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III

COUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III SECTION 28 3111 - DIGITAL ADDRESSABLE FIRE ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Brown University Revised April 12, 2013 Facilities Design & Construction Standards

Brown University Revised April 12, 2013 Facilities Design & Construction Standards SECTION 28 31 10 - FIRE ALARM SYSTEMS, SMOKE ALARMS, CARBON MONOXIDE PART 1 - GENERAL 1.1 SUMMARY: A. Section Includes: 1. Fire Alarm and Detection Systems 2. Single Station Smoke Alarms 3. Single Station

More information

Architect s Project Number of 12 Fire Alarm/Smoke Detection Systems District Master Specs 2013 Edition

Architect s Project Number of 12 Fire Alarm/Smoke Detection Systems District Master Specs 2013 Edition PART 1 GENERAL 1.1 SECTION INCLUDES SECTION 28 31 00 FIRE ALARM AND SMOKE DETECTION SYSTEMS A. Fire alarm and smoke detection systems 1.2 REFERENCES A. NFPA 72 B. NFPA 101 1.3 REGULATORY REQUIREMENTS A.

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Alarm System Plan Review 2009 International Fire Code and 2010 NFPA 72 Date of Review // BLD201 - Project Address: Project Name: _ Professional

More information

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R Region Project Page 1 PART 1 - GENERAL 1.1 REFERENCES.1 CAN/ULC-S524-2006, Standard for the Installation of Fire Alarm Systems..2 CAN/ULC-S525-2007, Audible Signal Device for Fire Alarm Systems..3 CAN/ULC-S526-2007,

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 13852- PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this

More information

FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS

FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS VALOUR COMMUNITY CENTRE FIRE ALARM SYSTEM Section 28 00 00 GYMNASIUM ADDITION & RENOVATION Page 1 of 3 28 00 00 FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS 1.2 SCOPE 1. The specification covering the General

More information

SECTION DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM SECTION 283111 DIGITAL, ADDRESSABLE FIRE ALARM PART 1 - GENERAL 1.1 GENERAL A. This Section includes the following: 1. Fire-alarm control panel. 2. Manual fire-alarm boxes. 3. Smoke detectors. 4. Heat

More information

1.3 REFERENCE STANDARDS

1.3 REFERENCE STANDARDS SECTION 28 4600 FIRE DETECTION AND ALARM PART 1 -GENERAL 1.1 SECTION INCLUDES A. Fire alarm system design and installation, including all components, wiring, and conduit. B. Circuits from protected premises

More information

STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018

STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018 STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018 STANDARD INFORMATION Standard Number: NFPA 72 Standard Name: National Fire Alarm and Signaling Code Standard Edition and Issue Date: 2016 Edition

More information

Hinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Hinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 28 3111 DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Manual fire-alarm boxes. 3. System smoke detectors. 4. Heat detectors.

More information

1. The fire detection and alarm system (including the conduit) shall be a separate bid item and not part of the general electrical contract.

1. The fire detection and alarm system (including the conduit) shall be a separate bid item and not part of the general electrical contract. PART 1 - GENERAL SECTION 28 31 11 STANDARD 1.1 FIRE ALARM SYSTEM REQUIREMENTS A. Contractor Requirements 1. The fire detection and alarm system (including the conduit) shall be a separate bid item and

More information

SECTION FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM

SECTION FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM SECTION 2 8 31 00 FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Request For Proposal apply to this Section.

More information

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline Moreno Valley Fire Department Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 8, 2017 Alarm & Signaling Systems PURPOSE Fire alarm and signaling systems are designed to

More information

Changes to this Division since the last issuance are indicated with yellow highlighted text.

Changes to this Division since the last issuance are indicated with yellow highlighted text. Table of Contents 28 10 00 ELECTRONIC ACCESS CONTROL AND INTRUSION DETECTION... 2 A. GENERAL... 2 B. DESIGN REQUIREMENTS... 2 C. CONSTRUCTION REQUIREMENTS... 3 28 20 00 ELECTRONIC SURVEILLANCE... 4 A.

More information

The CWSI System CALL WITH QUESTIONS. RELY ON OUR KNOWLEDGE. DEPEND ON OUR EXPERIENCE. (800)

The CWSI System CALL WITH QUESTIONS. RELY ON OUR KNOWLEDGE. DEPEND ON OUR EXPERIENCE. (800) The CWSI System The CWSI wireless fire alarm product line offers system versatility like none other. Frequency Hopping Spread Spectrum Technology (FHSS), coupled with Bi-directional RF Communication, Repeater

More information

DIVISION 28 ELECTRONIC SAFETY AND SECURITY

DIVISION 28 ELECTRONIC SAFETY AND SECURITY 281300 - ACCESS CONTROL A. General DIVISION 28 ELECTRONIC SAFETY AND SECURITY At the beginning of the project, schedule a meeting with the Facilities Access/Maintenance Coordinator with questions and concerns.

More information

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Rancho Cucamonga Fire Protection District Prevention Bureau Standard Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Updated: December 2016 for consistency

More information

Unified Fire Authority - Fire Prevention Bureau

Unified Fire Authority - Fire Prevention Bureau Unified Fire Authority - Fire Prevention Bureau FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance

More information

C. All control equipment must have transient protection devices to comply with UL864 requirements.

C. All control equipment must have transient protection devices to comply with UL864 requirements. SECTION 28 31 11 - PART 1 - GENERAL 1.1 SCOPE & RELATED DOCUMENTS A. The work covered by this section of the specifications includes the furnishing of all labor, equipment, materials, and performance of

More information

SECTION COMMON WORK RESULTS FOR SAFETY AND SECURITY 1.1 RELATED SECTIONS

SECTION COMMON WORK RESULTS FOR SAFETY AND SECURITY 1.1 RELATED SECTIONS SECTION 280500 COMMON WORK RESULTS FOR SAFETY AND SECURITY PART 1 - GENERAL 1.1 RELATED SECTIONS A. All division 28 work shall, in addition to all division 1 specification sections, comply with all of

More information

Mircom FX /01/16

Mircom FX /01/16 ENGINEERING SPECIFICATION 954-POINT INTELLIGENT FIRE DETECTION SYSTEM PART 1.0 - GENERAL 1.1. DESCRIPTION: A. This section of the specification includes the furnishing, installation, connection and testing

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-28 31 13.00 40 (February 2017) ----------------------------------- Preparing Activity: NASA Superseding UFGS-28 31 13.00 40 (May 2013) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

SECTION FIRE ALARM SYSTEMS

SECTION FIRE ALARM SYSTEMS SECTION 28 3100 PART 1 -GENERAL 1.01 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this

More information

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS PART 1 GENERAL 1.1 SECTION INCLUDES A. Fire alarm and smoke detection systems 1.2 REFERENCES A. NFPA 72 B. NFPA 101 1.3 REGULATORY REQUIREMENTS A. System: UL listed B. Conform to requirements of NFPA 101

More information

Type of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number:

Type of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number: DATE OF SUBMISSION TO: Department of Licenses and Inspections Commercial and Industrial Fire Inspection Unit 990 Spring Garden Street, 3 rd Floor, Philadelphia, PA 19123 AP# CITY OF PHILADELPHIA FIRE ALARM

More information

Multiple Input and Output Modules

Multiple Input and Output Modules Kingfisher Company, inc. Multiple Input and Output Modules Features: Removable 12 to 18 AWG plug-in terminal blocks Individual LED indicators Unused addresses may be disabled Rotary address switches Class

More information

Fire Alarm and Life Safety System Inspection Certificate

Fire Alarm and Life Safety System Inspection Certificate Fire Alarm and Life Safety System Inspection Certificate For Sample FireScan Healthcare 123 Main Street Anytown, State 55555 Tested to NFPA 72 Standards, 2007 Edition This Inspection was performed in accordance

More information

Fire Alarm, Water Flow Alarm & Signaling Systems

Fire Alarm, Water Flow Alarm & Signaling Systems Orange County Fire Authority Community Risk Reduction 1 Fire Authority Road, Building A, Irvine, CA 92602 www.ocfa.org 714-573-6100 Fire Alarm, Water Flow Alarm & Signaling Systems Guideline D-03 Serving

More information

FIRE & LIFE SAFTEY STANDARD

FIRE & LIFE SAFTEY STANDARD Title: Effective Date: 01/01/14 Revised Date: 1/1/14 Code References: Title 16, Chapter 16.16 of the Roseville Municipal Code, NFPA 72 Note: This standard is a summary of Fire Department clarifications

More information

Florida Building Code 2010

Florida Building Code 2010 Introduction Florida Building Code 2010 Chapter 9 Fire Protection Systems This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors are familiar with

More information

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. 2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is

More information

PROJECT MANUAL PART II TECHNICAL PROVISIONS. Concourse B Fire Alarm Replacement CONTRACT NO Issued for Bid January 13, 2016

PROJECT MANUAL PART II TECHNICAL PROVISIONS. Concourse B Fire Alarm Replacement CONTRACT NO Issued for Bid January 13, 2016 PROJECT MANUAL Concourse B Fire Alarm Replacement CONTRACT NO. 201524852 PART II TECHNICAL PROVISIONS Issued for Bid January 13, 2016 CITY & COUNTY OF DENVER DEPARTMENT OF AVIATION SECTION 283100 INTELLIGENT

More information

FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200

FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200 FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200 1.0 General 1.1 Manufacturer Manufacturer of the Fire Alarm Control Panel (FACP) equipment shall be: Digital Monitoring Products, Incorporated 2500 N.

More information

3.1 Introduction. 3.1 Introduction

3.1 Introduction. 3.1 Introduction DEPARTMENT OF ARCHITECTURE ABUBAKAR TAFAWA BALEWA UNIVERSITY, BAUCHI ARC 624: ADVANCED BUILDING SERVICES LESSON 3: FIRE DETECTION AND ALARM SYSTEMS IN BUILDINGS 3.1 Introduction 3.1 Introduction 3.2 Conventional

More information

SECTION FIRE DETECTION AND ALARM

SECTION FIRE DETECTION AND ALARM PART 1 - GENERAL 1.1 RELATED SECTIONS: Refer to Section 15300 for requirements regarding fire protection systems. 1.2 SCOPE OF SECTION: This section contains the requirements for equipment and installation

More information

Idaho Surveying & Rating Bureau, Inc South Cobalt Point Way Tel: (208) Meridian, Idaho FAX: (208)

Idaho Surveying & Rating Bureau, Inc South Cobalt Point Way Tel: (208) Meridian, Idaho FAX: (208) Idaho Surveying & Rating Bureau, Inc. 1871 South Cobalt Point Way Tel: (208) 343-5483 Meridian, Idaho 83642 FAX: (208) 895-8059 www.isrb.com e-mail info@isrb.com Joseph C. Harbacheck, CIC Secretary - General

More information

SECTION : FIRE ALARM & DETECTION SYSTEMS

SECTION : FIRE ALARM & DETECTION SYSTEMS SECTION 28 31 10: FIRE ALARM & DETECTION SYSTEMS 1. GENERAL A. This section applies to fire detection/alarm system and carbon monoxide system components and equipment installed during new construction

More information

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course Florida Building Code 2010 Chapter 9 Fire Protection Systems Advanced Course 1 Introduction This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors

More information

University Design Standard Fire Alarm Systems

University Design Standard Fire Alarm Systems 1.0 Overview University Design Standard Fire Alarm Systems This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit

More information

EIELSON AFB FIRE SYSTEMS STANDARDS 354 TH CIVIL ENGINEER SQUADRON ALARM MAINTENANCE SHOP

EIELSON AFB FIRE SYSTEMS STANDARDS 354 TH CIVIL ENGINEER SQUADRON ALARM MAINTENANCE SHOP EIELSON AFB FIRE SYSTEMS STANDARDS 354 TH CIVIL ENGINEER SQUADRON ALARM MAINTENANCE SHOP 1. FIRE ALARM PANELS: A. INTELLIGENT FIRE ALARM PANELS (ADDRESSABLE): An Intelligent type fire panel is required

More information

SECTION INTRUSION DETECTION

SECTION INTRUSION DETECTION (NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) SECTION 28 16 00 INTRUSION

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 283112 DIGITAL ADDRESSABLE FIRE ALARM SYSTEM VOICE NOTIFICATION PART 1 GENERAL 1.1 SUMMARY NETWORK FIRE ALARM CONTROL PANEL (NODE) A. Network fire alarm control panels shall include all features

More information

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2 Architectural & Engineering Specifications Control Panel 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality assurance...

More information

16721 FIRE ALARM AND DETECTION SYSTEMS

16721 FIRE ALARM AND DETECTION SYSTEMS 16721 FIRE ALARM AND DETECTION SYSTEMS PART 1: GENERAL 1.01 QUALITY ASSURANCE A. The integrated fire alarm system including all equipment, components, and accessories shall be UL listed for the purpose

More information

SECTION FIRE DETECTION AND ALARM

SECTION FIRE DETECTION AND ALARM SECTION 28 31 00 FIRE DETECTION AND ALARM SPEC WRITER NOTES: This specification addresses fire alarm systems installations of the following configurations/conditions: 1. A fully addressable fire alarm

More information

SECTION FIRE ALARM SYSTEM PART 1 GENERAL

SECTION FIRE ALARM SYSTEM PART 1 GENERAL SECTION 16720 - FIRE ALARM SYSTEM PART 1 GENERAL 1.1 SCOPE & RELATED DOCUMENTS A. The work covered by this section of the specifications includes the furnishing of all labor, equipment, materials, and

More information

16721 FIRE ALARM AND DETECTION SYSTEMS

16721 FIRE ALARM AND DETECTION SYSTEMS 16721 FIRE ALARM AND DETECTION SYSTEMS PART 1: GENERAL 1.01 QUALITY ASSURANCE A. The integrated fire alarm system including all equipment, components, and accessories shall be UL listed for the purpose

More information

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax) FIRE DEPARTMENT SANTA CLARA COUNTY 14700 Winchester Blvd., Los Gatos, CA. 95032-1818 (408) 378-4010 (408) 378-9342 (fax) www.sccfd.org STANDARD DETAILS & SPECIFICATIONS Spec No C-4 Rev. Date 03/10/10 SUBJECT:

More information

Addressable Fire Alarm Control Panel

Addressable Fire Alarm Control Panel PRODUCT SPECIFICATION XR2400F Addressable FACP Addressable Fire Alarm Control Panel Description The DMP XR2400F Addressable Fire Alarm Control Panel is an expandable Fire Alarm Control with built-in DACT

More information

DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM

DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

A. This Section covers fire alarm systems, including initiating devices, notification appliances, controls, and supervisory devices.

A. This Section covers fire alarm systems, including initiating devices, notification appliances, controls, and supervisory devices. SECTION 28 31 11 ADDRESSABLE FIRE ALARM SYSTEM 1. GENERAL 1.1 SUMMARY A. This Section covers fire alarm systems, including initiating devices, notification appliances, controls, and supervisory devices.

More information

SECTION FIRE ALARM SYSTEMS

SECTION FIRE ALARM SYSTEMS SECTION 16721 FIRE ALARM SYSTEMS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION FIRE ALARM SYSTEM (POINT GRAPHIC SYSTEM)

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION FIRE ALARM SYSTEM (POINT GRAPHIC SYSTEM) PART 0 DESIGN STANDARDS 0.01 USE OF THIS STANDARD A. Due to the extent of detail provided in this standard, the A/E may choose to edit this standard and incorporate portions of this standard in the construction

More information

Lake County / Multi-Department Storage Facility / Project / December 12, 2016 SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Lake County / Multi-Department Storage Facility / Project / December 12, 2016 SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS SECTION 283111 A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

Project Scenario Summary Report http://fusion.deltacollege.edu/code/planning/project/editfpu/scenariorpt.asp?id=2629&ce... Page 1 of 1 11/7/2017 California Community Colleges Project Scenario Summary 2019

More information

CITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM. Bid # Addendum #1

CITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM. Bid # Addendum #1 CITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM Bid #56-09 Addendum #1 This Addendum forms part of the original document marked Bid #56-09 MUNICIPAL COMPLEX FIRE ALARM. Device

More information

OKLAHOMA STATE UNIVERSITY

OKLAHOMA STATE UNIVERSITY ENVIRONMENTAL HEALTH & SAFETY ADDRESSABLE FIRE ALARM SYSTEM STANDARD Revised 6/15 Revised: 6/15 Contact(s) Implementation Date Comments Gerald Petre, EHS June 2016 Review and Update Page 1 1.1 GENERAL

More information

Fire Alarm Wiring. Circuit types, styles and limitations

Fire Alarm Wiring. Circuit types, styles and limitations Fire Alarm Wiring Circuit types, styles and limitations What we will cover Types Classes Notification Appliance Circuits (NAC) Initiating Device Circuits (IDC) Signaling Line Circuits (SLC) Class A, B,

More information

SECTION FIRE DETECTION AND ALARM

SECTION FIRE DETECTION AND ALARM PART 1 - GENERAL 1.1 DESCRIPTION SECTION 28 46 00 SPEC WRITER NOTES: 1. The A/E must obtain a copy of the VA ENGINEERING GUIDE FOR FIRE PROTECTION DESIGN which provides fire alarm system criteria that

More information

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10 Belleville, Ontario Page 1 of 10 1 GENERAL 1.1 GENERAL REQUIREMENTS.1 The General Conditions of CCDC2-2008, and the General requirements of Division 1, form part of this Section and must read in conjunction

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 8/2004 Fire Chief Lee Koontz Fire Marshal Paul Smith EFD-FMO 3-1 2003 International Fire & Building Code as Amended NFPA Standards

More information

Revised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required*

Revised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required* 1.0 Description of Services Required: Revised March 2015 Fire Alarm Systems Verification Schedule I(A) Services *Manditory Site visit required* Perform the annual fire alarm system and sprinkler system

More information

SECTION ADDRESSABLE FIRE ALARM SYSTEM

SECTION ADDRESSABLE FIRE ALARM SYSTEM SECTION 16723 ADDRESSABLE FIRE ALARM SYSTEM 1 PART 1 GENERAL 1.1 DESCRIPTION A. This section outlines the requirements for the installation, programming and configuration of Addressable Fire Alarm System

More information

109-B Concord Drive Casselberry, FL DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72. Owner s Address: Owner's Phone Number:

109-B Concord Drive Casselberry, FL DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72. Owner s Address: Owner's Phone Number: 109-B Concord Drive Casselberry, FL 32707 407.830.6500 DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72 Pg 1 of 4 Equity One 11180600 Owner/Representative: WO#: _Customer#: 1550 NE Miami Garden Dr

More information

NFPA 72 Code Changes vs 2013

NFPA 72 Code Changes vs 2013 NFPA 72 Code Changes - 2010 vs 2013 AFAA-NE Westborough, MA February 7, 2018 Richard Roux NFPA 72 National Fire Alarm and Signaling Code Overview and 2013 Changes NFPA 72 1993 Edition Aug 20, 1993 1996

More information

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 031703 Overview: The Altronix AL802ULADA is an extremely cost effective 8 amp voltage regulated

More information

WINDOW & HVAC REPLACEMENT PEMBERTON TOWNSHIP BOE REGAN YOUNG ENGLAND BUTERA, PC PROJECT #5450E

WINDOW & HVAC REPLACEMENT PEMBERTON TOWNSHIP BOE REGAN YOUNG ENGLAND BUTERA, PC PROJECT #5450E SECTION 283111 DIGITAL ADDRESSABLE FIRE ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary General Conditions of the

More information

Rocky Mountain Fire Protection District 4390 Eldorado Springs Drive Boulder, CO

Rocky Mountain Fire Protection District 4390 Eldorado Springs Drive Boulder, CO Rocky Mountain Fire Protection District 4390 Eldorado Springs Drive Boulder, CO 80303 303-494-3735 Contractor s Checklist and Installation Guide TABLE OF CONTENTS Fire Protection Narrative........... 3

More information

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Fire Alarm Systems Plan Review Checklist Date: Permit Number: Business Name: Address: Fire Alarm System Submittal

More information

Memphis Housing Authority High Rise Fire Alarm Upgrades. Questions from Contractors (Through Addendum #2) Communications Systems, Inc.

Memphis Housing Authority High Rise Fire Alarm Upgrades. Questions from Contractors (Through Addendum #2) Communications Systems, Inc. Memphis Housing Authority High Rise Fire Alarm Upgrades Questions from Contractors (Through Addendum #2) Communications Systems, Inc.: Legend 1. DL - Dome light symbol should be on the tenant emergency

More information

DESIGN & CONSTRUCTION GUIDELINES

DESIGN & CONSTRUCTION GUIDELINES Facilities Management 4202 E. Fowler Avenue, OPM 100 Phone: (813) 974-2625 Design & Construction Tampa, Florida 33620-7550 Website: usf.edu/fm-dc DESIGN & CONSTRUCTION GUIDELINES DIVISION 28 ELECTRONIC

More information

First Revision No. 158-NFPA [ Global Input ] Submitter Information Verification. Committee Statement

First Revision No. 158-NFPA [ Global Input ] Submitter Information Verification. Committee Statement of 326 11/21/2013 1:03 PM First Revision No. 158-NFPA 72-2013 [ Global Input ] Revise 2.3.1 to update UL 864 to "2003, revised 2012" and upate ANSI/ASME A17 to 2013. Submittal Date: Wed Sep 11 11:08:52

More information

Control/Communicator

Control/Communicator Architectural & Engineering Specifications Control/Communicator 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality

More information

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions. 11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

More information

Interfacing Fire Alarm, Sprinkler and Elevator Systems

Interfacing Fire Alarm, Sprinkler and Elevator Systems 1 Interfacing Fire Alarm, Sprinkler and Elevator Systems Rodger Reiswig, SET Director, Industry Relations SimplexGrinnell November 17, 2010 Interfacing to Elevators 2 ASME A17.1 Safety Code for Elevators

More information

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS SECTION 907 FIRE ALARM AND DETECTION SYSTEMS 907.1 General. This section covers the application, installation, performance and maintenance of fire alarm systems and their components in new and existing

More information

Mar H: SUPPLEMENTAL FIRE DETECTION AND ALARM (16720-H)

Mar H: SUPPLEMENTAL FIRE DETECTION AND ALARM (16720-H) 2101 Commonwealth Blvd, Suite B Ann Arbor, MI 48105-5759 www.med.umich.edu/facilities/plan/ 283100-H: SUPPLEMENTAL FIRE DETECTION AND ALARM (16720-H) Related Sections Basis Guideline: 283100 - Fire Detection

More information

STATE OF NORTH CAROLINA

STATE OF NORTH CAROLINA STATE OF NORTH CAROLINA DEPARTMENT OF ADMINISTRATION STATE CONSTRUCTION OFFICE Fire Alarm GUIDELINES AND POLICIES 2011 Instruction to Designers: 1. Designers for State projects involving fire alarm systems

More information