ANSUL AUTOMAN II-C EXPLOSION PROOF RELEASING DEVICE Installation, Operation, and Maintenance Manual

Size: px
Start display at page:

Download "ANSUL AUTOMAN II-C EXPLOSION PROOF RELEASING DEVICE Installation, Operation, and Maintenance Manual"

Transcription

1 ANSUL AUTOMAN II-C EXPLOSION PROOF RELEASING DEVICE Installation, Operation, and Maintenance Manual

2 This manual is intended for use with the ANSUL AUTOMAN Il-C Explosion-Proof Releasing Device. Those who install, inspect, maintain or service this releasing device should read the entire manual. Specific sections will be of particular interest depending upon one s responsibility. ANSUL AUTOMAN Il-C is an electrical/mechanical device. It requires periodic care. Maintenance should be conducted at six month intervals to provide maximum assurance that your releasing device will operate effectively and safely. Inspection should be conducted at more frequent intervals to provide reasonable assurance that your releasing device is operable.

3 General InstructIons E Page 1 ansul automan Il-c releasing DeVIce For HaZarDous locations VISUAL INDICATOR WINDOW 2. WIRING INSTRUCTIONS 3. RELEASE MECHANISM 4. RESET LEVER 5. STRIKE BUTTON 6. ACTUATION CARTRIDGE FIGure IntroDuctIon The ANSUL AUTOMAN Il-C Releasing Device is for use with ANSUL fire suppression systems. Model Il-C provides automatic-pneumatic actuation of fixed nozzle fire suppression systems. DescrIPtIon The Model Il-C is comprised of a metal enclosure which contains a spring-loaded puncture pin release mechanism, an actuation cartridge, and an explosion-proof electrical solenoid. Knockouts for the connection of conduit are provided in the top, bottom and sides of the steel enclosure. The enclosure also contains four surface mounting holes. operation When energized by a fire condition, a solenoid mounted on the actuator trips the release mechanism puncturing the cartridge. The solenoid operates approximately 50 milli - seconds after energized. Then actuation gas from the cartridge is directed through piping to pneumatically activate the fire suppression system. Manual actuation is provided by means of an integral STRIKE button at the release enclosure which may be supplemented by use of a remote manual cable pull station.

4 InstallatIon InstructIons E Page 2 MountInG ansul automan Il-c release The reliability of an ANSUL fixed nozzle fire suppression system depends greatly upon proper installation of the releasing device, associated equipment and wiring. For example, the ANSUL AUTOMAN Il-C utilizes a special pressure cartridge activating a fire suppression system that must be located in an area where the air temperature will not fall below 32 F (0 C) nor exceed 120 F (49 C). This requirement and other instructions to follow are critical to reliable operation. Install release 1. Select a shock and vibration free surface in a clean dry area for mounting the ANSUL AUTOMAN release. The mounted release should be completely visible and accessible for maintenance. note: The bottom of the release must be located no higher than 50 in. (127 cm) from the floor to enable manual actuation of STRIKE button. If the release cannot be mounted in this manner, a remote manual pull station (cable type or electric) should be installed to facilitate manual actuation. 2. Open the release cover and secure the enclosure at location utilizing the four mounting holes. Use lag screws or toggle bolts depending on the mounting surface. Figure 2 provides detailed mounting data. MountInG Data 3. DO NOT INSTALL CARTRIDGE AT THIS TIME. 4. Connect the release and the extinguishing agent tank(s)/activating mechanism with Schedule 40 or Schedule 80 pipe of 1/4 in. diameter, starting from the gas outlet port in the release as shown in Figure 3. 3/8 IN. X 1/4 IN. REDUCING BUSHING 1/4 IN. CLOSE NIPPLE 45 ELBOW, 1/4 IN. 90 ELBOW, 1/4 IN. FIGure Use one of the 1/2 in. (13 mm) knockouts provided in the top and bottom or side of the release enclosure to exit the pipe and install balance of pipe, fittings and pressure relief valve as shown in Figure 4. Wrench tighten all pipe joints to prevent leakage of gas. PRESSURE RELIEF VALVE* 4 3/16 IN. (106 mm) 1 1/8 IN. (29 mm) 9 7/8 IN. (229 mm) 5/16 IN. (8 mm) DIA. HOLES 1 1/4 IN. (32 mm) 21 1/2 IN. (546 mm) FIGure *In some systems, the actuation line vent is used rather than the pressure relief valve. SURFACE MOUNTING KNOCKOUTS ON 4 SIDES OF BOX 6. Proceed with wiring instructions beginning on the next page. DO NOT INSTALL CARTRIDGE. FIGure

5 InstallatIon InstructIons E Page 3 WIrInG ansul automan Il-c release The ANSUL AUTOMAN Il-C is designed for use with a separately listed fire detection/control unit which will initiate the electrical signal to operate the release. Accordingly, conduit and wiring connections between the release and the detection/alarm control system suitable for hazardous locations should be made by, or under the supervision, of the detection/control system manufacturer s technician. Installation of Wiring Connect number 18 AWG min. wiring to the solenoid leads and enclose wiring in suitable conduit and fittings for hazardous locations. Adequate room is provided for installation of explosion-proof junction boxes within the ANSUL AUTOMAN Il-C enclosure. WIrInG Data NOTES: INPUT POWER: NOTED ON SOLENOID LABEL PART NO.: ( 24 VDC) (120 VAC) (240 VAC) ALL INTERCONNECTING WIRING NUMBER 18 AWG MIN. ENCLOSED IN CONDUIT SUITABLE FOR HAZARD - OUS LOCATIONS. DISCONNECT POWER CIRCUIT BEFORE DECOUPLING EXPLOSION PROOF FITTINGS. operating sequence As the normally open/external alarm contacts close, power is applied to solenoid SOL 1 to operate the ANSUL AUTOMAN Il-C. As the release operates, the gas cartridge is punctured allowing actuation gas to pneumatically operate a fire suppression system. note: The solenoid is a continuous duty type and there is no internal switch to remove the solenoid power. If it is desirable to remove power, a pneumatic pressure switch or time delay relay which is approved for hazardous locations should be used. ANSUL AUTOMAN Il-C FOR HAZARDOUS LOCATIONS, PART NO. (SEE NOTES) SOL 1 N.O. ALARM RELEASING CONTACTS POWER SOURCE FOR RELEASE FIGure

6 InstallatIon InstructIons E Page 4 test of WIrInG Electrical tests should be conducted jointly by the installer and the technical representatives of both the detection/alarm control system and the fire suppression system manufacturers. 1. Raise the release manual reset lever up to the armed position. DO NOT INSTALL CARTRIDGE. ARMED FIRED FIGure Energize the detector/alarm control system. 3. Activate a detector in accordance with procedures as recommended by the detector/alarm control system manufacturer. Check that the ANSUL AUTOMAN release has operated reset lever should be in the down (Fired) position as illustrated in Figure 6. RESET LEVER RING PIN FIGure Return detector/alarm control system to normal supervisory operation, reset the ANSUL AUTOMAN release and install ring pin as illustrated in Figure 7 to safety the release puncture pin mechanism. test activation of extinguisher(s) Depending upon the hazard s requirements, the activation system design for the agent tank assembly will differ. For this reason, the operational test of the actuation/activation system must be performed by an authorized ANSUL distributor. 1. Refer to the installation, operation and maintenance instruction manual(s) furnished with the ANSUL Fire Suppression System and prepare the agent tank assembly activation mechanism for test firing. note: Precise execution of each step is necessary to avoid discharge of the agent. 2. Check ANSUL AUTOMAN release reset lever should be in the (Armed) position and ring pin inserted in the puncture pin assembly shaft. 3. Weigh and install the proper cartridge in the release. Hand tighten. note: Be certain when replacing cartridges that the proper type is used, and that it meets the weight requirements outlined in the instruction manual for that type of system. The pressure relief device in the actuation line may be either the actuation line vent (which relieves automatically) or the pressure relief valve (pull ring to effect total pressure relief). 4. Pull ring pin, close and lock the release cover. 5. Operate the release by depressing the STRIKE button. 6. Confirm that the detector/alarm control system performed all of its associated functions and that the agent tank assembly activation system functioned properly. 7. Leak test the pneumatic pipe and fittings between the release and agent tank assembly. 8. Verify that the actuation pressure has been fully relieved. If your system has a relief valve in the actuation line, pull the ring to release pressure. If your system has an actuation line vent plug, the pressure will be relieved automatically. 9. Restore the agent tank(s) activation mechanism to operation. 10. Rearm release and insert ring pin. 11. Replace spent cartridge with fully-charged cartridge. 12. Remove ring pin, close cover. 13. Insert ring pin in STRIKE button and attach lead and wire seal. MaIntenance ANSUL AUTOMAN Il-C release is a mechanical device. It requires periodic care. Maintenance to provide maximum assurance that your release will operate effectively and safely should be conducted at six month intervals in accordance with Steps 1 through 13 listed under Test Activation Of Extinguisher(s). Inspection to provide reasonable assurance that your release is charged and operable should be conducted at more frequent intervals by visually determining that the ring pin is properly inserted and sealed in the STRIKE button and that the reset lever is in the up (Armed) position. note: Every ANSUL engineered fixed nozzle system is subject to a mandatory inspection upon completion of your system s installation. This inspection must be performed by an authorized ANSUL distributor to ensure that the complete system is installed properly and is ready for service.

7 InstallatIon InstructIons E Page 5 remote Manual Pull station (cable type) Remote pull station, (Part No. 4835), allows the ANSUL AUTOMAN Il-C to be manually actuated from some point distant to the release. The pull station should be installed at a height convenient for manual operation. To install the pull station: 1. Insert ring pin in ANSUL AUTOMAN release (see Page 4, Figure 7). 2. Remove cartridge and install safety shipping cap. 3. Select location for mounting manual remote cable pull station. note: Pull station must be located within 100 ft (30 m) of the release. 4. Fasten 4 inch junction box (not furnished) to wall where pull station is to be mounted. note: Orient the junction box so that when cover is in place, printing will be right side up. 5. Install and secure 1/2 in. rigid conduit from ANSUL AUTOMAN release assembly to pull station using pulley elbows for changes in direction. note: Do not use more than 8 pulley elbows between the release and the pull station. 6. Feed wire rope through pull station junction box and conduit into release. note: Make sure wire rope rides on top of and in center of pulley sheave. If the 50 ft (15.2 m) wire rope provided is not long enough, obtain wire rope, (Part No. 4595), and splice lengths with two sleeves, (Part No. 4596). Do not allow wire rope splice to be within 12 in. (305 mm) of any pulley elbow. 7. Fasten pull station assembly cover to junction box. 8. Thread wire rope through rear guide hole in manual trip lever on release. 9. Pull slack out of wire rope and thread end through sleeve, (Part No. 4596). 10. Loop the wire rope back up around and through top of sleeve. 11. Position sleeve approximately 1/2 in. (13 mm) below trip lever and crimp to secure wire rope. 12. Remove ring pin from release puncture pin assembly. 13. Remove red glass indicator rod from pull station by removing set screws on side of stud and slide rod out. 14. Pull ring on pull station. If release mechanism is tripped easily, pull station is properly installed. If release does not trip easily, remove pulley covers and check to see that wire rope is in pulley elbow sheave. 15. Cut off excess wire rope 3/4 in. (19 mm) below sleeve assembly. 16. Reset release and insert ring pin. 17. Reinstall glass indicating rod. 18. Remove safety shipping cap and install cartridge. 19. Remove ring pin and close cover. 20. Insert ring pin in STRIKE button and attach lead and wire seal. SEE DETAIL A 1/2 IN. DETAIL A FIGure

8 TYCO FIRE PROTECTION PRODUCTS Copyright 2011 Tyco Fire Protection Products ONE STANTON STREET All rights reserved. MARINETTE, WI Part No

ANSUL ANSUL AUTOMAN II-C RELEASING DEVICE

ANSUL ANSUL AUTOMAN II-C RELEASING DEVICE ANSUL INSTALLATION OPERATION AND MAINTENANCE MANUAL ANSUL AUTOMAN II-C RELEASING DEVICE 001799 This manual is intended for use with the ANSUL AUTOMAN II-C Releasing Device. Those who install, inspect,

More information

Agent Tanks PCL PCL PCL PCL - 600

Agent Tanks PCL PCL PCL PCL - 600 Components Pg 2-1 Agent Tanks PCL - 160 PCL - 300 PCL - 460 PCL - 600 Model No. Diameter Height to top of valve Height with control head Height to valve outlet Weight PCL - 160 8.00 in. 17.65 in. 23.50

More information

Types of Detection. Fusible Link Detection - Most Common

Types of Detection. Fusible Link Detection - Most Common Types of Detection Fusible Link Detection - Most Common Types of Detection Electric Detection Types of Detection Pneumatic Detection-Tubing Pneumatic Tubing 3 Year Service life Survey Hazard 1) List all

More information

PriceList Category PartNbr Part Description Weight (l MSRP

PriceList Category PartNbr Part Description Weight (l MSRP Date Printed :4/22/2014 12:04:43 PM Effective 4-MAR-2014 CATALOG PRICING Note:Price amounts shown are in US$ PriceList Category PartNbr Part Description Weight (l MSRP ANSUL Restaurant Systems PIRANHA

More information

MANUAL RESET ALARM RELEASE

MANUAL RESET ALARM RELEASE Fire Door Release MODEL AR-D MANUAL RESET ALARM RELEASE INSTRUCTION MANUAL AR-D GENERAL INFORMATION 1. Review all installation instructions, procedures, cautions and warnings contained within this manual

More information

KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.01 SUMMARY SECTION 15371 KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM A. Section Includes: A complete automatic fire suppression system for the exhaust hood, including necessary accessories.

More information

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.01 SUMMARY SECTION 15371 KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM A. Section Includes: A complete wet chemical automatic fire suppression system for the exhaust hood, including necessary

More information

CHECKFIRE 110 DETECTION AND ACTUATION SYSTEM

CHECKFIRE 110 DETECTION AND ACTUATION SYSTEM CHECKFIRE 110 DETECTION AND ACTUATION SYSTEM OWNERS GUIDE 2017 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject

More information

CORE Protection Fire System Specification

CORE Protection Fire System Specification CORE Protection Fire System Specification The CORE restaurant fire suppression system is a pre-engineered, duct and plenum water spray system in conjunction with a wet chemical, cartridge-operated, regulated

More information

LGB Gas fired boiler

LGB Gas fired boiler LGB Gas fired boiler Control Supplement LGB-5 Series 2 Propane gas CSD-1 Control System Part Number 550-110-682/0304 Please read this page first Hazard definitions To the installer... The following terms

More information

Twin-Agent Fire Fighting/Securing Systems Specifications

Twin-Agent Fire Fighting/Securing Systems Specifications Twin-Agent Fire Fighting/Securing Systems Specifications Models 450/50, 450/100, 900/100 & 1350/200 INDEX 1.0 GENERAL 1.1 References 1.2 Submittals 1.3 System Capabilities 1.4 Quality Control 1.5 Warranty,

More information

VIZOR Electronic Dry Pipe Accelerator (EDPA) Quick-Opening Device for Dry Pipe Systems General Description

VIZOR Electronic Dry Pipe Accelerator (EDPA) Quick-Opening Device for Dry Pipe Systems General Description Worldwide Contacts www.tyco-fire.com VIZOR Electronic Dry Pipe Accelerator (EDPA) Quick-Opening Device for Dry Pipe Systems General Description The TYCO VIZOR Electronic Dry Pipe Accelerator (EDPA) is

More information

MANUAL RESET ALARM RELEASE

MANUAL RESET ALARM RELEASE Fire Door Release MODEL AR-D2 MANUAL RESET ALARM RELEASE INSTRUCTION MANUAL AR-D2 GENERAL INFORMATION 1. Review all installation instructions, procedures, cautions and warnings contained within this manual

More information

Specification/ Data Sheet

Specification/ Data Sheet Specification/ Data Sheet TRITON RP Agent Release Control Panel FEATURES Agent Release Control Panel designed specifically for suppression release operation with: Four initiating device circuits (IDCs)

More information

STEAMPRO. Steam Generator Troubleshooting and Service Guide

STEAMPRO. Steam Generator Troubleshooting and Service Guide STEAMPRO Steam Generator Troubleshooting and Service Guide TABLE OF CONTENTS Page PREFACE... 1 I. STEAMPRO STEAM GENERATOR SYSTEM...2 II. PLUMBING AND ELECTRICAL...3-4 III. SYSTEM OVERVIEW... 5-10 IV.

More information

CHECKFIRE 210 Detection and Actuation System

CHECKFIRE 210 Detection and Actuation System DATA SHEET CHECKFIRE 210 Detection and Actuation System Features Supervised power, detection, release, and communication circuits Display module with LED system status indicators Adjustable mounting bracket

More information

CATALOG OF REPLACEMENT PARTS HSROG SERIES SINGLE RACK OVEN. A product of HOBART CORPORATION 701 S. RIDGE AVENUE TROY, OHIO

CATALOG OF REPLACEMENT PARTS HSROG SERIES SINGLE RACK OVEN. A product of HOBART CORPORATION 701 S. RIDGE AVENUE TROY, OHIO CATALOG OF REPLACEMENT PARTS HSROG SERIES SINGLE RACK OVEN HSROG ML-111148 A product of HOBART CORPORATION 701 S. RIDGE AVENUE TROY, OHIO 45374-0001 FORM 43003 (June 2001) HOT SECTION 26 OVEN TOP SECTION

More information

RELEASE DEVICES RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: :100 GENERAL DESCRIPTION:

RELEASE DEVICES RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: :100 GENERAL DESCRIPTION: RELEASE DEVICES MADE IN THE U.S.A. RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: 7300-1418:100 GENERAL DESCRIPTION: S/N: The "WPS" World Power Series, Time Delay Release

More information

DAF DETECT-A-FIRE. DAF DETECT-A-FIRE Detection and Release Devices

DAF DETECT-A-FIRE. DAF DETECT-A-FIRE Detection and Release Devices DAF DETECT-A-FIRE DAF DETECT-A-FIRE Detection and Release Devices FEATURES Repeatable - resets itself, nothing to replace, testable Rugged - withstands shock and vibration Versatile - offers various temperature

More information

24 VAC SYSTEM CONTROL KIT

24 VAC SYSTEM CONTROL KIT 24 VAC SYSTEM CONTROL KIT Model: CK-91F and CK-91FG Designed for use with the SWG Series Power Venter for controlling Natural Gas or L.P. Gas draft induced appliances with a 24 VAC Gas Valve and a 30-millivolt

More information

R-102 RESTAURANT FIRE SUPPRESSION SYSTEM

R-102 RESTAURANT FIRE SUPPRESSION SYSTEM R-102 RESTAURANT FIRE SUPPRESSION SYSTEM DESIGN, INSTALLATION, Recharge, and Maintenance Manual One Stanton Street / Marinette, WI 54143-2542, USA / +1-715-735-7411 / www.ansul.com Copyright 2014 Tyco

More information

Firefly II Multi Voltage RELEASE DEVICES. Firefly II & IIB-MV INSTALLATION MANUAL

Firefly II Multi Voltage RELEASE DEVICES. Firefly II & IIB-MV INSTALLATION MANUAL Firefly II Multi Voltage RELEASE DEVICES Firefly II & IIB-MV INSTALLATION MANUAL GENERAL DESCRIPTION: S/N The The Cookson Company Firefly II-MV time delay release devices are designed for use on rolling

More information

Kidde Nitrogen Inert Gas Clean Agent Fire Suppression System

Kidde Nitrogen Inert Gas Clean Agent Fire Suppression System 1. GENERAL 1.1 INTENT OF SPECIFICATIONS A. This specification details the requirements for an engineered inert gas fire suppression system Model Kidde Nitrogen. These requirements, combined with good engineering

More information

ANSUL. Twin-Agent Fire Fighting/Securing Systems Specifications. Models 450/50-B, 450/100-B, 900/100-B INDEX SPECIFICATIONS

ANSUL. Twin-Agent Fire Fighting/Securing Systems Specifications. Models 450/50-B, 450/100-B, 900/100-B INDEX SPECIFICATIONS ANSUL Twin-Agent Fire Fighting/Securing Systems Specifications Models 450/50-B, 450/100-B, 900/100-B INDEX 1.0 GENERAL 1.1 References 1.2 Submittals 1.3 System Capabilities 1.4 Quality Control 1.5 Warranty,

More information

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS INDEECO Circulation Heaters are designed to provide years of trouble free operation if properly installed and maintained. Please read and follow these instructions for installing and maintaining the heater.

More information

+ + CHECKFIRE MARINE ELECTRIC DETECTION AND CONTROL SYSTEM. CHECKFIRE Marine Electric Detection and Control System (Part No.

+ + CHECKFIRE MARINE ELECTRIC DETECTION AND CONTROL SYSTEM. CHECKFIRE Marine Electric Detection and Control System (Part No. CHECKFIRE Marine Electric CHECKFIRE MARINE ELECTRIC DETECTION AND CONTROL SYSTEM NAME 2016-JAN-30 REV. 03 PAGE 1 Installation, Inspection, and Maintenance Manual + + + + 002997 One Stanton Street / Marinette,

More information

MODEL B2 INSTALLATION MANUAL

MODEL B2 INSTALLATION MANUAL RELEASE DEVICES GENERAL DESCRIPTION MODEL B2 INSTALLATION MANUAL S/N: The B2 Series Time Delay Release Devices are UL Listed, Canadian Listed, and CSFM Listed for use on rolling doors, single-slide and

More information

USER INSTRUCTIONS FOR FLANGE IMMERSION HEATERS USED IN HAZARDOUS LOCATIONS

USER INSTRUCTIONS FOR FLANGE IMMERSION HEATERS USED IN HAZARDOUS LOCATIONS USER INSTRUCTIONS FOR FLANGE IMMERSION HEATERS USED IN HAZARDOUS LOCATIONS APPLICATION INDEECO Explosion proof Electric Immersion Heaters for Hazardous Locations are ccsaus Certified for use in areas (external

More information

Data/ Specification Sheet

Data/ Specification Sheet Data/ Specification Sheet MONARCH Dry Chemical Automotive Paint Spray Booth Fire Suppression System TM 1. Fixed temperature mechanical or thermal detectors 2. Electrical conduit protecting stainless steel

More information

SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. SS90-WPS MODEL A/B INSTALLATION MANUAL

SOLID STATE SECURITIES, INC. THE SS90 SERIES RELEASE DEVICES MADE IN THE U.S.A. SS90-WPS MODEL A/B INSTALLATION MANUAL S S S S S S LISTED L * PATENT PENDING S S 90 OLID TATE ECURITIES, INC SOLID STATE FAIL-SAFE UNIT U 99Y9 RESET RELEASING DEVICE SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE

More information

Engineering Specifications

Engineering Specifications Engineering Specifications ANSUL INERGEN Clean Agent Fire Suppression System with AUTOPULSE Control System 2012-AUG-20 FIRE DETECTION / INERGEN FIRE SUPPRESSION SYSTEM ENGINEERING SPECIFICATIONS Tyco

More information

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL MADE IN THE U.S.A. U.L. LISTED CANADIAN LISTED CSFM: 7300-1418:100 GENERAL DESCRIPTION SERIAL NUMBER The Cookson Company FIREFLY II PLUS Time Delay Release

More information

Hospitals and Major Medical Centers

Hospitals and Major Medical Centers Hospitals and Major Medical Centers INERGEN Fire Suppression Systems AUTOPULSE Detection and Control Equipment SENTRY Hand Portable Fire Extinguishers Medical centers have special concerns for fire safety

More information

Service Bulletin No. 2930

Service Bulletin No. 2930 Service Bulletin No. 2930 MODEL TYPE SECTION/GROUP DATE E / J Series Coaches Service Information 8--Engine Mar. 30, 2006 SUBJECT AMEREX FIRE SUPPRESSION SYSTEM CONDITIONS Service Information Only Description:

More information

Ventless Operation Supplement GBF-D-VH

Ventless Operation Supplement GBF-D-VH Operations & Service Manual GBF-5D-VH GBF-50D-VH Ventless Operation Supplement GBF-D-VH Giles Enterprises, Inc. An ISO900 Registered Company Committed to Quality 750 Gunter Park Drive West Montgomery,

More information

Analog Room Pressure Monitor RPC Series

Analog Room Pressure Monitor RPC Series Description The Room Pressure Monitor is used to measure differential pressure in the range of 0.125 to 1"wc or 30 to 250 Pa. It combines precision high sensitivity silicon sensing capabilities and the

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE October 10, 2008 Deluge Devices 281a 1. PRODUCT DESCRIPTION The Viking Model C-1 is a rate-of-rise releasing device for use on hydraulic and pneumatic release systems controlling operation of Viking deluge

More information

THE "SS90" SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL

THE SS90 SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL S S S S S S S S 90 OLID TATE ECURITIES, INC SOLID STATE FAIL-SAFE UNIT * PATENT PENDING LISTED U 99Y9 RESET L RELEASING DEVICE SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE

More information

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM SECTION 1 - GENERAL CONDITIONS SPECIFICATION FOR A TOTAL FLOOD I. SCOPE: This specification outlines the requirements for a Total Flood ECARO-25 TM clean agent fire suppression system utilizing HFC-125

More information

WARNING. Installation Tip: Try out this unit before installing onto a fire door system. Test and learn the release INTRODUCTION

WARNING. Installation Tip: Try out this unit before installing onto a fire door system. Test and learn the release INTRODUCTION WARNING 1. CAUTION: Review all installation instructions, procedures, cautions and warnings contained within this manual prior to installing and/or servicing this product. As with all releasing device

More information

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL RELEASE DEVICES MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL The LiftMaster Fire Control (LM21-AFC) Release Device/Control Panel is UL/CUL listed normally energized fail-safe device incorporating

More information

Remote Chexit Module (RCM) System. General Information

Remote Chexit Module (RCM) System. General Information *911032-00* 911032-00 Wiring and Configuration Remote Chexit Module (RCM) System Installation Instructions General Information The Von Duprin RCM is designed for controlled egress applications. It meets

More information

Axiom Technologies L.L.C Telephone: Pennbright Dr., Suite 220 Fax: XP7 USER S MANUAL

Axiom Technologies L.L.C Telephone: Pennbright Dr., Suite 220 Fax: XP7 USER S MANUAL L.L.C Telephone: 281 931 0907 255 Pennbright Dr., Suite 220 Fax: 281 931 6562 Houston, Texas 77090 www.axiomsafety.com XP7 USER S MANUAL COMPACT MULTI-CHANNEL ALARM & SHUTDOWN SYSTEM GENERAL The XP7 alarm

More information

MANUAL RESET ALARM RELEASE BOX

MANUAL RESET ALARM RELEASE BOX MANUAL RESET ALARM RELEASE BOX (For 100~240VAC or 24VAC or 24VDC) INSTRUCTION MANUAL WARNING 1. CAUTION: Review all installation instructions, procedures, cautions and warnings contained within this manual

More information

SERVICE BY QUALIFIED PERSONNEL ONLY

SERVICE BY QUALIFIED PERSONNEL ONLY Installation Instructions Automatic Load Control Relay For Emergency Lighting! IMPORTANT SAFEGUARDS! WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD ALWAYS BE FOLLOWED, INCLUDING THE FOLLOWING:

More information

Typical Applications: Excavators Haul Trucks Wheeled Loaders Drag Lines Large Dozers Drills

Typical Applications: Excavators Haul Trucks Wheeled Loaders Drag Lines Large Dozers Drills Today s Mega-Class non-road mobile equipment requires MEGA-CLASS fire protection. Ansul twin-agent system technology provides protection to help keep equipment productive and minimize downtime due to fire.

More information

DE5300 Delayed Egress System. General Information

DE5300 Delayed Egress System. General Information *911031-00* 911031-00 Wiring and Configuration DE5300 Delayed Egress System Installation Instructions General Information The Von Duprin DE5300 is designed for controlled egress applications when used

More information

MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL

MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL RELEASE DEVICES MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: 7300-1418:100 GENERAL DESCRIPTION: S/N: These Time Delay Release Devices are U.L. Listed, Canadian Listed,

More information

THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL

THE SS90 SERIES RELEASE DEVICES MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL S S S S S S OLID TATE ECURITIES, INC S S 90 SOLID STATE FAIL-SAFE UNIT * PATENT PENDING LISTED 99Y9 RESET U L RELEASING DEVICE SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with automatic detection and control. The work described in

More information

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual UHIR Series Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater Owner s Manual This manual covers installation, maintenance and repair parts. Read carefully before attempting to

More information

WATLOW IND. WATROD Modular Duct Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2

WATLOW IND. WATROD Modular Duct Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2 I&M NUMBER: 316-42-15-1 Page: 1 _ Pre Installation Check to make sure that heater received is the same as that ordered. Elements may come in contact with each other during shipment. Minor adjustments to

More information

INSTALLATION GUIDE Dual Fuel Ranges

INSTALLATION GUIDE Dual Fuel Ranges INSTALLATION GUIDE Dual Fuel Ranges Contents Wolf Dual Fuel Ranges......................... 3 Safety Instructions............................ 4 Dual Fuel Range Specifications.................. 5 Dual Fuel

More information

TRAINING BULLETIN TOOLS 1 May 27, 2011 PRESSURIZED WATER EXTINGUISHER

TRAINING BULLETIN TOOLS 1 May 27, 2011 PRESSURIZED WATER EXTINGUISHER TRAINING BULLETIN TOOLS 1 May 27, 2011 1. DESCRIPTION Weight is approximately 30 lbs. Water 2½ gallons. Operating Pressure: 100 psi @ 70 degrees F. Note: Water expelled in 55 seconds. Stainless Steel Cylinder

More information

ACSI MODEL 1410 POWER SUPPLY INSTALLATION INSTRUCTIONS

ACSI MODEL 1410 POWER SUPPLY INSTALLATION INSTRUCTIONS II 1400-3 ACSI MODEL 1410 POWER SUPPLY INSTALLATION INSTRUCTIONS Features: For use with doors or groups of doors that must interlock with each other to regulate control of accessing one area from another,

More information

24 VAC SYSTEM CONTROL KIT

24 VAC SYSTEM CONTROL KIT 24 VAC SYSTEM CONTROL KIT Model: CK-92F and CK-92FG Designed for use with the SWG Series Power Venter for controlling Natural Gas or L.P. Gas appliances with a 24 VAC Gas Valve and a 30-millivolt controlled

More information

Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing

Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing Important: To protect the unit and avoid damage to the heat exchanger, the blower speed

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with a Cheetah Xi 50 addressable detection and control system.

More information

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE CHEETAH Xi 50 CONTROL PANEL SYSTEM

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE CHEETAH Xi 50 CONTROL PANEL SYSTEM SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Total Flood ECARO-25 TM clean agent fire suppression system utilizing HFC-125 as the fire extinguishing agent

More information

FRAME AND CONSOLE PARTS

FRAME AND CONSOLE PARTS FRAME AND CONSOLE PARTS UNDERCOUNTER DISHWASHER 1 3375275 Console (Includes Item 2) 2 3376026 Insert, Console 3 3376029 Switch, 5 Pushbutton 4 3369529 Follower, Cam 5 3373626 Timer 6 3369415 Cam 7 304231

More information

TECHNICAL DATA. model c-2

TECHNICAL DATA. model c-2 Page 1 of 6 1. PRODUCT DESCRIPTION The Viking Model C-2 is a rate-of-rise releasing device for use on hydraulic and pneumatic release systems controlling operation of Viking deluge valves on deluge or

More information

F-CLASS MODEL M6L WET CHEMICAL FIRE EXTINGUISHER Installation, Operation, Recharge and Maintenance Manual

F-CLASS MODEL M6L WET CHEMICAL FIRE EXTINGUISHER Installation, Operation, Recharge and Maintenance Manual F-CLASS MODEL M6L WET CHEMICAL FIRE EXTINGUISHER Installation, Operation, Recharge and Maintenance Manual 008094 All fire extinguishers should be installed, inspected and maintained in accordance with

More information

Worldwide Contacts.

Worldwide Contacts. Worldwide Contacts www.tyco-fire.com Series Multiple Jet Controls DN20, DN25, DN40, and DN50, 2 bar BSPT Inlet & Outlets Threads General Description The TYCO Series Multiple Jet Controls are control valves

More information

Crypto-Lock. Model CC-8521B Updated 7/17. Access Control System. MONITEQ, Inc. INSTRUCTION MANUAL

Crypto-Lock. Model CC-8521B Updated 7/17. Access Control System. MONITEQ, Inc. INSTRUCTION MANUAL Crypto-Lock Model CC-8521B Updated 7/17 Access Control System INSTRUCTION MANUAL MONITEQ, Inc. 2 TABLE OF CONTENTS 1. INTRODUCTION..4 2. SPECIFICATIONS.....6 3. SUPPLIED EQUIPMENT.. 6 4. FUNCTIONS OF CONTROLS

More information

Badger Universal Control Head

Badger Universal Control Head Badger Universal Control Head P/N: 60-120099-002 FEATURES For Use in: Range Guard Commercial Cooking Fire Suppression Systems Industry Guard Industrial Fire Suppression Systems Pneumatic Release of up

More information

PARTS LIST PL503 WVF-886 VENTLESS FRYER WITH OR WITHOUT ROLL WARMER CONTENTS

PARTS LIST PL503 WVF-886 VENTLESS FRYER WITH OR WITHOUT ROLL WARMER CONTENTS WELLS BLOOMFIELD, LLC 2 ERIK CIRCLE, P. O. Box 280 Verdi, NV 89439 telephone: 775-689-5703 fax: 775-689-5976 www.wellsbloomfield.com 503 PARTS LIST PL503 WVF-886 VENTLESS FRYER WITH OR WITHOUT ROLL WARMER

More information

GENERAL BULLETIN NO. 5397

GENERAL BULLETIN NO. 5397 ANSUL INCORPORATED ONE STANTON STREET MARINETTE, WI 54143-2542 715-735-7411 www.ansul.com GENERAL BULLETIN NO. 5397 DATE: August 20, 2008 TO: FROM: SUBJECT: All Authorized ANSUL Vehicle System s Distributors

More information

Carey Automatic Door, LLC 1 - PNEUMATIC OPERATOR FOR SINGLE SWINGING DOOR

Carey Automatic Door, LLC 1 - PNEUMATIC OPERATOR FOR SINGLE SWINGING DOOR Carey Automatic Door, LLC 1 - PNEUMATIC OPERATOR FOR SINGLE SWINGING DOOR IN for Doors Swinging under Operator OUT for Doors Swinging away from Operator Packages 1, 2 & 3 Packages 4, 5 & 6 FACTORS TO CONSIDER

More information

FMP-DIS & FMP-EIS. Interstitial BriteSensor & Standard Sensor. Installation Instructions

FMP-DIS & FMP-EIS. Interstitial BriteSensor & Standard Sensor. Installation Instructions FMP-DIS & FMP-EIS Interstitial BriteSensor & Standard Sensor Installation Instructions FMP-DIS Sensor FMP-EIS Sensor Franklin Fueling Systems 3760 Marsh Rd. Madison, WI 53718 USA Tel: +1 608 838 8786 800

More information

INSTRUCTION MANUAL. AlarmGard Chain Operator (Model FCA) AlarmGard Crank Operator (Model FKA)

INSTRUCTION MANUAL. AlarmGard Chain Operator (Model FCA) AlarmGard Crank Operator (Model FKA) INSTRUCTION MANUAL AlarmGard Chain Operator (Model FCA) & AlarmGard Crank Operator (Model FKA) WARNING 1. CAUTION: Review all installation instructions, procedures, cautions and warnings contained within

More information

ENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS

ENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS ENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS SECTION 1 GENERAL SPECIFICATIONS I. SCOPE This specification outlines the requirements for a pre-engineered

More information

FIre Extinguishers. K-GUARD Wet Chemical Fire Extinguishers Manual INSTALLATION 2014-DEC-29 REV. 03 PAGE 1 EXTINGUISHERS

FIre Extinguishers. K-GUARD Wet Chemical Fire Extinguishers Manual INSTALLATION 2014-DEC-29 REV. 03 PAGE 1 EXTINGUISHERS K-GUARD Wet Chemical K-GUARD K-Guard WET CHEMICAL Wet Chemical EXTINGUISHERS FIre Extinguishers INSTALLATION 2014-DEC-29 REV. 03 PAGE 1 Installation, OPERATION, Recharge, and Maintenance Manual 004327

More information

GTD20A Installation Instructions BRANCH CIRCUIT TRANSFER SWITCH/LIGHTING CONTROL DEVICE

GTD20A Installation Instructions BRANCH CIRCUIT TRANSFER SWITCH/LIGHTING CONTROL DEVICE Installation Instructions BRANCH CIRCUIT TRANSFER SWITCH/ CONTROL DEVICE UL 1008-BCELTS UL 924-Switch Bypass! IMPORTANT SAFEGUARDS! WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD ALWAYS

More information

24V PCU CORE FIRE PROTECTION INSTALLATION SUMMARY

24V PCU CORE FIRE PROTECTION INSTALLATION SUMMARY 24V PCU CORE FIRE PROTECTION INSTALLATION SUMMARY 06/13/2011 Rev. 6 Pollution Control Unit PCU CORE CONNECTIONS, 3/8" NPT CONNECTION, ONE PER MODULE LINE FROM PACKAGE MUST BE BRANCHED TO EACH MODULE..

More information

TS93 EMR WITH SMOKE DETECTOR

TS93 EMR WITH SMOKE DETECTOR TS EMR WITH SMOKE GENERAL DESCRIPTION Each TS EMR series unit contains a door closer, hold open electromagnet and smoke detector. The unit can be used as a single installation or as a series of singles

More information

"SS90" SERIES CONTROLS MODEL C INSTALLATION MANUAL

SS90 SERIES CONTROLS MODEL C INSTALLATION MANUAL S S S SS O L I D S S90 TATE ECURITIES, INC SOLID STATE FAIL-SAFE UNIT * PATENT PENDING LISTED U L 99Y9 RESET RELEASING DEVICE SOLID STATE SECURITIES, INC. "SS90" SERIES CONTROLS MADE IN THE U.S.A. MODEL

More information

FMP-MWS. (Discriminating Monitoring Well Sensor BriteSensor ) Installation Instructions

FMP-MWS. (Discriminating Monitoring Well Sensor BriteSensor ) Installation Instructions FMP-MWS (Discriminating Monitoring Well Sensor BriteSensor ) Installation Instructions Franklin Fueling Systems 3760 Marsh Rd. Madison, WI 53718 USA Tel: +1 608 838 8786 800 225 9787 Fax: +1 608 838 6433

More information

CHECKFIRE 110 DETECTION AND ACTUATION SYSTEM

CHECKFIRE 110 DETECTION AND ACTUATION SYSTEM CHECKFIRE 110 DETECTION AND ACTUATION SYSTEM PLANNING, INSTALLATION, Operation, and Maintenance Manual One Stanton Street / Marinette, WI 54143-2542, USA / +1-715-735-7411 / www.ansul.com Copyright 2014

More information

AutoTest VSR (VSR-AT) (EU) Vane Type Waterflow Alarm Switch With Electronic Retard and Auto Test Feature

AutoTest VSR (VSR-AT) (EU) Vane Type Waterflow Alarm Switch With Electronic Retard and Auto Test Feature AutoTest VSR (VSR-AT) (EU) Features Assembled in USA 0-30 second field replaceable electronic retard Two SPDT (Form C) switch contacts Weatherproof Easy to read wire terminal designations Easy to read

More information

JUL 17 Rev C

JUL 17 Rev C Hydraulic Crimping Head, PN 1752787-1 Instruction Sheet 408-8914 31 JUL 17 Rev C 1. INTRODUCTION Products Crimped AMPLI-BOND* and PLASTI-GRIP* Terminals TERMINYL* Terminals and Splices Pre-Insulated AMPOWER*

More information

NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM

NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM PART 1 - GENERAL 1.1 SUMMARY A. This section outlines the requirements for the nitrogen-generating sprinkler corrosion inhibiting system. The work

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Thermo-Platens. Cast-In Aluminum and Bronze Platen Die Heaters for Plastics Processing Equipment

Thermo-Platens. Cast-In Aluminum and Bronze Platen Die Heaters for Plastics Processing Equipment Cast-In Aluminum and Bronze Platen Die Heaters for Plastics Processing Equipment Cast-In Platen Heaters are widely accepted as the industry standard for heating critical, temperaturesensitive plastics

More information

Hakki Pilke Raven spare parts manual

Hakki Pilke Raven spare parts manual 1 ENGLISH Hakki Pilke Raven spare parts manual Valimotie 1, FI-85800 Haapajärvi, FINLAND Tel. +358 8 772 7300, Fax +358 8 772 732 info@maaselankone.fi, www.maaselankone.fi 2 Table of contents 1 Upper section

More information

HEAT/ COOL/ DEFROST FORD THUNDERBIRD

HEAT/ COOL/ DEFROST FORD THUNDERBIRD specializing in AIR CONDITIONING, PARTS AND SYSTEMS for your classic vehicle PERFECT FIT IN-DASH HEAT/ COOL/ DEFROST 1964-66 FORD THUNDERBIRD CONTROL & OPERATING INSTRUCTIONS The controls on your new Perfect

More information

TECHNICAL MANUAL UNIT, INTERMEDIATE DIRECT SUPPORT AND INTERMEDIATE GENERAL SUPPORT MAINTENANCE MANUAL (INCLUDING REPAIR PARTS AND SPECIAL TOOLS LIST)

TECHNICAL MANUAL UNIT, INTERMEDIATE DIRECT SUPPORT AND INTERMEDIATE GENERAL SUPPORT MAINTENANCE MANUAL (INCLUDING REPAIR PARTS AND SPECIAL TOOLS LIST) TM 55-1925-227-24&P TECHNICAL MANUAL UNIT, INTERMEDIATE DIRECT SUPPORT AND INTERMEDIATE GENERAL SUPPORT MAINTENANCE MANUAL (INCLUDING REPAIR PARTS AND SPECIAL TOOLS LIST) FIRE FIGHTING SYSTEM FOR LARGE

More information

MAXIMUM KNOCKDOWN ABILITY Large Dry Chemical Fire Suppression Systems

MAXIMUM KNOCKDOWN ABILITY Large Dry Chemical Fire Suppression Systems MAXIMUM KNOCKDOWN ABILITY Large Dry Chemical Fire Suppression Systems ANSUL PIONEERED DRY CHEMICAL FIRE PROTECTION IN 1939, WHICH HELPED CREATE LARGE DRY CHEMICAL SYSTEMS WITH SUPERIOR FIREFIGHTING CAPABILITIES

More information

Industrial Dry Chemical Fire Suppression System

Industrial Dry Chemical Fire Suppression System Industrial Dry Chemical Fire Suppression System INSTALLATION, OPERATION AND MAINTENANCE MANUAL, P/N 15040 Revision B, April 9, 2013 AMEREX CORPORATION INC. - 7595 GADSDEN HIGHWAY - TRUSSVILLE, AL 35173

More information

WATLOW IND. WATROD Circulation Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 6/11/2008 Rev: 2.00

WATLOW IND. WATROD Circulation Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 6/11/2008 Rev: 2.00 I&M NUMBER: 316-42-5-1 Page: 1 Pre Installation Check to make sure that heater received is the same as that ordered. Watlow heaters are built to comply with UL and CSA dielectric requirements, it may be

More information

Attached is Supplement three for service manual We suggest you file this with your Manual for reference.

Attached is Supplement three for service manual We suggest you file this with your Manual for reference. INTRODUCTION Attached is Supplement three for service manual 16008203. We suggest you file this with your 16008203 Manual for reference. Models covered in this manual: MAH21PD MAH21PN MAH21PR MAH21PS CONTENTS

More information

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPUSLE VALVE, Fike FK AGENT & SHP PRO CONTROL PANEL

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPUSLE VALVE, Fike FK AGENT & SHP PRO CONTROL PANEL SECTION 1 GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Total Flood Clean Agent Fire Suppression System utilizing FK-5-1-12 as the fire extinguishing agent and with a

More information

MEGA. cal electronic gas alarm. Installation, Operation, and Maintenance Instructions. Part No Rev. D Pg.

MEGA. cal electronic gas alarm. Installation, Operation, and Maintenance Instructions. Part No Rev. D Pg. WARD OXYGEN Installation, Operation, and Maintenance Instructions MEGA medical electronic gas alarm MEGA WARD MEGA medical electronic gas alarm WARD POWER SUPPLY Medical Electronic Gas Alarm OXYGEN SYSTEM

More information

FMP-DDS & FMP-DTS. Discriminating Dispenser Sump & Turbine Sump BriteSensor. Installation Instructions

FMP-DDS & FMP-DTS. Discriminating Dispenser Sump & Turbine Sump BriteSensor. Installation Instructions & Discriminating Dispenser Sump & Turbine Sump Brite Installation Instructions Franklin Fueling Systems 3760 Marsh Rd. Madison, WI 53718 USA Tel: +1 608 838 8786 800 225 9787 Fax: +1 608 838 6433 www.franklinfueling.com

More information

PARTS MANUAL. American Dish Service MODEL: 5-AG-S ADS LOW TEMPERATURE DISHWASHER EFFECTIVE: JULY, 2013 C 4/08

PARTS MANUAL. American Dish Service MODEL: 5-AG-S ADS LOW TEMPERATURE DISHWASHER EFFECTIVE: JULY, 2013 C 4/08 EFFECTIVE: JULY, 2013 ADS LOW TEMPERATURE DISHWASHER MODEL: PARTS MANUAL 900 Blake Street Edwardsville, Kansas 66111 (913)422-3700 C 4/08 The American Dish Service part numbers contained in this publication

More information

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2

More information

Parts and Service Manual

Parts and Service Manual Section II Parts and Service Manual (70241A) CLARKE TECHNOLOGY Operator's Manual - MINI MAX Page -29- Frame and Front Cover Assembly Drawing 2/01 Page -30- CLARKE TECHNOLOGY Operator's Manual -MINI MAX

More information

24 VAC SYSTEM CONTROL KIT Model: CK-91F and CK-91FG

24 VAC SYSTEM CONTROL KIT Model: CK-91F and CK-91FG 24 VAC SYSTEM CONTROL KIT Model: CK-91F and CK-91FG Designed for use with the SWG Series Power Venter for controlling Natural Gas or L.P. Gas draft induced appliances with a 24 VAC Gas Valve and a 30-millivolt

More information

Technical Data. Minimum Inlet Supply Pressure All MCC Models...0 psi. Minimum Inlet Supply Capacity Match system design calculations

Technical Data. Minimum Inlet Supply Pressure All MCC Models...0 psi. Minimum Inlet Supply Capacity Match system design calculations Worldwide Contacts www.tyco-fire.com AQUAMIST Mist Control Center (MCC) Pump Skid Unit General Description Center (MCC) Pump Skid Unit is a preassembled, self-contained, control center for Ultra Low Flow

More information

VSR-M REPLACEMENT Waterflow Switch for Globe Sprinkler Model UMC Manifold

VSR-M REPLACEMENT Waterflow Switch for Globe Sprinkler Model UMC Manifold Features NEMA 4 solid metal enclosure Factory installed neoprene gasket 0-90 second field replaceable pneumatic retard 350 PSI system pressure rated Synchronized switch action Waterflow switches that are

More information

Installation Instructions. PS902 Power Supply. These instructions cover the following parts: PS902 Power Supply Specifi cations:

Installation Instructions. PS902 Power Supply. These instructions cover the following parts: PS902 Power Supply Specifi cations: F1! 44487023 These instructions cover the following parts: PS902 Power Supply Installation Instructions! DANGER: To avoid risk of electric shock, turn off AC power before installing or servicing PS902

More information