1 INSTALLATION MANUAL Document no: GLT PAGE 1

2 Contents Table of Contents 1.INTRODUCTION SAFETY INFORMATION & USE OF THIS MANUAL INSTALLATION INFORMATION BATTERY INFORMATION PRODUCT DISPOSAL AT THE END OF ITS WORKING LIFE INSTALLATION LOCATING THE VOICE ALARM PANEL MOUNTING THE VOICE EVACUATION PANEL RECOMMENDED CABLE TYPES AND THEIR LIMITATIONS... 9 MAINS WIRING RECOMMENDATIONS PLANNING CABLE ENTRY MAINS WIRING WIRING THE PCB SPEAKER CIRCUITS SOUNDER CIRCUITS NETWORKING THE PANEL CONNECTING THE EVACS 1-16 TO AN ANALOGUE ADDRESSABLE PANEL ADDRESS SETTINGS TABLE CONFIGURING THE PANEL ALARM CONFIGURATION ALERT CONFIGURATION MICROPHONE CONFIGURATION BATCH-LOAD AUDIO FILES DESCRIPTION OF SECTIONS LIST OF AVAILABLE TONES CHANNEL VOLUME TRIGGER MATRIX SETTINGS STATUS MONITOR FIRMWARE UPDATE OPERATING THE PANEL DISPLAY AND CONTROLS DISPLAY CONTROLS METHODS OF OPERATING THE PREMIER EVACS LIVE BROADCAST PRE-RECORDED MESSAGE (MANUAL) PRE-RECORDED MESSAGE (AUTOMATIC) RESETTING FROM A VOICE ALARM CONDITION FAULT DISPLAY & FAULT-FINDING OVERVIEW FAULT FINDING POWER SUPPLY FAULT SPEAKER CIRCUIT FAULT EARTH FAULT Document no: GLT PAGE 2

3 AMP FAULT SYSTEM FAULT BATTERY CALCULATION GENERAL GUIDELINES CALCULATING THE BATTERY REQUIRED EXAMPLE BATTERY REQUIREMENTS BATTERY CALCULATION WORKSHEET AUDIO OUTPUT INFORMATION OUTPUT POWER POWER CONSUMPTION CONFIGURATION SWITCH SETTINGS SPECIFICATIONS ELECTRICAL SPECIFICATIONS PHYSICAL SPECIFICATIONS FUSE RATINGS Document no: GLT PAGE 3

4 1. INTRODUCTION The Premier EVACS 1-16 Voice evacuation control panel has been designed and developed as a standalone system that will compliment any Zeta Fire Detection System. The control panel is a modular design, allowing up to 16 channels, units, to be networked via RS485. Each unit has 30 watts output divided to 2 sub-channels. Also 2x24v outputs are provided to drive alarm systems where needed. The Premier EVACS 1-16 configuration software lets you easily customise and program the panels features including: volume control, trigger matrix, microphone configuration, as well as downloading of bespoke alert and evacuate messages of up to a minute long each. The pre-recorded message can be initiated via the built-in keypad, via the remote trigger inputs or via the loop interface. The remote trigger inputs and the loop interface allow the EVACS 1-16 messages to be triggered by the outputs of a fire alarm control panel / Control & Indicating Equipment (CIE). It has an emergency (or fireman's) microphone which can be used to broadcast live messages; each panel can be individually configured to broadcast microphone messages either locally or system-wide. Document no: GLT PAGE 4

5 2. SAFETY INFORMATION & USE OF THIS MANUAL WARNING: Read this section completely before operating this equipment INSTALLATION INFORMATION THIS VOICE ALARM CONTROL & INDICATING EQUIPMENT (VACIE) IS CLASS-1 EQUIPMENT AND MUST BE EARTHED. This equipment must be installed and maintained by a qualified and technically experienced person. This VACIE must be wired to a fused spur rated at 5A. It must NOT be connected via a removable plug, or be connected through an RCD device. Prior to commencing installation of the control panel, ensure that adequate precautions are taken to prevent damage to the sensitive electronic components on the display board and the control board due to electrostatic discharge. If anti-static equipment (such as an anti-static wrist strap) is not available, you should discharge any static electricity you may have accumulated by touching a convenient earthed object such as an unpainted copper radiator pipe. You should repeat the process at regular intervals during the installation process, especially if you are required to walk over carpets. The panel must be located in a clean, dry position, which is not subject to excessive shock or vibration and at least 2 metres away from pager systems or any other radio transmitting equipment. The only items which are designed to be removed from the enclosure are the cable connectors. Ensure that all electrical power is removed from the equipment before removing, inserting or connecting cables to these connectors. Document no: GLT PAGE 5

6 2.2. BATTERY INFORMATION This VACIE uses 2 x 12V Sealed Lead Acid (SLA) batteries with a capacity in the range of 7.2Ah to 17Ah. CAUTION: RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE. DISPOSE OF USED BATTERIES ACCORDING TO BATTERY MANUFACTURERS INSTRUCTIONS. IMPORTANT NOTES ON BATTERIES: DANGER: Batteries are electrically live at all times. NEVER short circuit the battery terminals. Keep batteries in their packaging, with the terminal protection caps in place until they are ready to be installed. WARNING: Batteries are often heavy. Take great care when lifting and transporting batteries. DANGER: Do NOT attempt to remove the battery lid or tamper with the internal workings of the battery. Electrolyte is a highly corrosive substance, and presents significant danger to yourself and to anything else it touches. In case of accidental skin or eye contact, flush the affected area with plenty of clean, fresh water and seek immediate medical attention. Valve Regulated Lead Acid (VRLA) batteries are low maintenance, requiring no electrolyte top-up or measurement of specific gravity PRODUCT DISPOSAL AT THE END OF ITS WORKING LIFE Like all electronic equipment, at the end of its working life this unit should not be disposed of in a refuse bin. It should be taken to a local reprocessing site as per the guidelines of the WEEE directive, for correct disposal. Document no: GLT PAGE 6

7 3. INSTALLATION 3.1. LOCATING THE VOICE ALARM PANEL The control panel should be installed in accordance with the following recommendations:- The panel should be close to the main entrance of the building, so that it can be viewed by any firefighting personnel entering the building. It should be fitted to a sturdy wall that will not flex unnecessarily. It should be mounted at eye level, in order for it to be viewed without need of a ladder. It should be installed in a dry, weatherproof place, away from direct sunlight. It should be easily accessible, so that the responsible person can perform their regular fire alarm checks. Document no: GLT PAGE 7

8 3.2. MOUNTING THE VOICE EVACUATION PANEL Plan view of enclosure. Side view for surface installation. (Dimensions: mm) Fix the enclosure to the wall using the four mounting holes provided. Check the build & condition of the wall to decide a suitable screw fixing. The mounting holes are designed for No 8 round-head or countersunk wood-screws (or similar). Once installed, remove any debris from the enclosure. Document no: GLT PAGE 8

9 3.3. RECOMMENDED CABLE TYPES AND THEIR LIMITATIONS All wiring must be installed to meet BS5839: Pt1: A2:2008 and BS 7671:2008 (IEE Wiring Regulations) standards. Other National standards of fire alarm system installation should be adhered to where applicable. Screened cables should be used throughout the installation to help shield the Panel from outside interference and ensure EMC compatibility. The two categories of cable according to BS5839: Pt1: A2:2008, Clause 26 Fire Detection and Alarm Systems for Buildings (Code of Practice for System Design, Installation and Servicing) are: Standard fire resisting cable to PH30 classification of EN (including the 30 min survival time of Annex E) Enhanced fire resisting cable to PH120 classification of EN (including the 120 min survival time of BS ) Note that all cables should be at least 1mm 2 cross section On the Premier EVACS 1-16 Panel the general recommendation would be to use standard fire resistant cable, such as GLT Exports Fire Defence Cable, Firetuff, FP200 or an equivalent. These cables are screened, and will provide good EMC shielding when properly grounded at the panel. Certain system specifications may demand the use of a particular type of cable and due regard should be paid to this fact. Depending on the environment, the cables may need mechanical protection (such as a conduit). MAINS WIRING RECOMMENDATIONS The Mains supply to the VACIE is fixed wiring, using Fire resisting 3-core cable (Between 1 mm² and 2.5mm²), fed from an isolating double pole switch fused spur, and fused at 5A. IT SHOULD NOT BE CONNECTED THROUGH AN RCD. This should be secure from unauthorised operation and be marked FIRE ALARM: DO NOT SWITCH OFF. The supply must be exclusive to the Fire Panel. Document no: GLT PAGE 9

10 3.4. PLANNING CABLE ENTRY The Premier EVACS 1-16 comes with many cable entry holes located at the top and bottom of the unit. If another entry hole is required, it is strongly recommended that the panel door is removed to avoid accidental damage. Also the PCB assemblies should be removed and stored in a safe place. This may also help while fixing the back box to the wall. If a cable-entry push-out is removed, fill the hole with a cable strain-relief gland. If any knock-out is removed, but subsequently not used, it should be covered up using a 20mm blanking grommet MAINS WIRING The 230V AC Mains cable must be fed into the enclosure via one of the cable entries at the top right corner of the back box. This cable must be connected to the mains terminals of the power supply, which are marked L, N, (Live, Neutral, Earth) Take care not to damage the VACIE during installation. Document no: GLT PAGE 10

11 3.6. WIRING THE PCB The following connectors are available on the PCB: Connection Description Display Connect to display PCB of the EVACS 1-16 Loop input Allows connection to an analogue control panel such as the Premier Quatro Fault relay Connection to the fault relay, this is normally energised when the system is functioning correctly. Alert Trigger input for the Alert signal Evacuate Trigger input for the Evacuate signal Aux Auxiliary power output Network Network connection to other EVACS 1-16 panels Microphone input Connects to the panels microphone Channel 1 / 2 speaker output Speaker output Sounder 1 / 2 output Conventional sounder output Fault (Power supply) Monitors for fault signals from the power supply or charger unit Earth (Power supply) Earth monitoring connection Note: Unused speaker or sounder outputs require the appropriate end-of-line resistor to be installed. Document no: GLT PAGE 11

12 SPEAKER CIRCUITS The EVACS 1-16 has two 667Ω isolated speaker outputs running at 100v nominal allowing up to 30W RMS output per channel The premier EVACS II checks for line integrity by using a 10K End of Line resistor on each speaker circuit, which should be connected to the last speaker on the circuit. The end-of-line resistor should be rated at 1W or higher SOUNDER CIRCUITS The EVACS 1-16 has two sounder outputs that activate alongside the speaker outputs; they are each rated at 500mA at 28V DC (nominal) and are over-current protected by a self-resetting fuse. The sounder circuits are monitored and require a 10K End of line resistor rated at 1/8w or higher. Document no: GLT PAGE 12

13 3.7. NETWORKING THE PANEL The EVACS 1-16 allows up to 16 panels to be connected over RS485 network interface, with each panel, or module, acting as a 2-channel zone. Individual panels or zones can then be controlled by the master panel. The network connection terminals are labelled COMA, 0V and COMB. Each should be wired to the corresponding terminal of the next panel on the network. The panels themselves do not need to be wired in any particular order with regard to the address used. The network address can be set using switches 1-4 of the DIP switch located on the amplifier board. The master panel or a panel which is not part of a network must be set an address of 1. Address SW1 SW2 SW3 SW4 1 (Master, or stand-alone panel) OFF OFF OFF OFF 2 OFF OFF OFF ON 3 OFF OFF ON OFF 4 OFF OFF ON ON 5 OFF ON OFF OFF 6 OFF ON OFF ON 7 OFF ON ON OFF 8 OFF ON ON ON 9 ON OFF OFF OFF 10 ON OFF OFF ON 11 ON OFF ON OFF 12 ON OFF ON ON 13 ON ON OFF OFF 14 ON ON OFF ON 15 ON ON ON OFF 16 ON ON ON ON The master panel must be configured with the number of zones on the network (that is, the number of EVACS 1-16 panels, including the master panel). This is done with the EVACS 1-16 configuration software via the USB link. Document no: GLT PAGE 13

14 To set the number of zones, connect the PC to the EVACS 1-16 panel via a suitable USB cable and run the EVACS 1-16 configuration software. Note that the panel must be powered on. In the configuration software, select settings, select the desired number of zones and click OK. The panel should now be configured with the correct number of zones. Document no: GLT PAGE 14

15 3.8. CONNECTING THE EVACS 1-16 TO AN ANALOGUE ADDRESSABLE PANEL The EVACS 1-16 allows connection to an analogue addressable panel via the loop interface. In a network of multiple EVACS 1-16 panels, the CIE must be connected to the master panel. The EVACS 1-16 utilises the Fyreye MKII protocol and must be connected to a panel running the MKII software. The device address of the EVACS 1-16 is set by the 8-way dip switch located on the display PCB, the address is set in binary notation, with switch 1 being the most significant bit (MSB) and switch 8 being the least significant bit (LSB). Refer to the table on the left for a list of each switch value, or the tables on the following pages for a quick reference of all addresses. Note that address 0 is reserved and should not be used. Switch Address value SW SW2 +64 SW3 +32 SW4 +16 SW5 +8 SW6 +4 SW7 +2 SW8 +1 Document no: GLT PAGE 15

16 ADDRESS SETTINGS TABLE Document no: GLT PAGE 16

17 4. CONFIGURING THE PANEL The EVACS 1-16 panel can be configured using the EVACS software. To configure the software the panel must be powered on and plugged into the PC running the software using a suitable USB connector. For the EVACS 1-16 the drop-down list box in the centre of the dialogue should be set to EVACS For networked EVACS 1-16 panels, most settings are only available to the panel configured as master. On the Premier EVACS 1-16, alert and evacuation messages can be uploaded from a PC running the configuration software. The messages cannot be recorded direct to the panel due to the microphones limited dynamic range, which would result in poor quality pre-recorded messages. Any suitable Audio file can be uploaded. The file format is *.wav format, 16-bit, 1 channel (mono), uncompressed 16,000 samples/sec (256kbps) with a maximum length of 55 seconds A custom message can be recorded on a PC or in a sound studio if the best sound clarity is required. Alternatively, you can use one of the sample messages provided with the PC Configuration Software ALARM CONFIGURATION The alarm configuration dialogue allows the user to upload a custom alarm message, it also allows the user to Document no: GLT PAGE 17

18 set the alarm tone used, which is a short tone intended to grab people s attention before the alarm messages is played. The Readback button on this, as well as the other audio-file configuration dialogues will read the audio file configuration from the EVACS 1-16 and display it on screen: Document no: GLT PAGE 18

19 4.2. ALERT CONFIGURATION This dialogue allows the setting of the Alert message and pre-alert tone MICROPHONE CONFIGURATION The microphone signon/signoff dialog allows the customisation of the sign-on and sign-off tones, these are short tones or custom announcements that are played when the microphone is activated and de-activated respectively. Document no: GLT PAGE 19

20 4.4. BATCH-LOAD AUDIO FILES A batch-load option is available for the convenience of vendors who may work on multiple EVACS 1-16 systems utilising the same custom set of audio files. An example configuration file might look like this: [Alert] Message=C:\Program Files\Zeta Alarms\Messages\AlertFem.wav Tone=7 [Evac] Message=C:\Program Files\Zeta Alarms\Messages\EvacMale.wav Tone=1 [Mic] Signon=C:\Program Files\Zeta Alarms\Page\Page1.wav Signoff= C:\Program Files\Zeta Alarms\Page\Page2.wav [Comms] Port=COM3 DESCRIPTION OF SECTIONS [Alert] section: Specifies the message and tone to be played for zones in the ALERT status [Evac] section: Specifies the message and tone to be played for zones in the EVACUATE status [Mic] section: Specifies the audio files to be played for the sign-on and sign-off for the microphone [Comms] section: specifies the communications parameters. The communications port the EVACS 1-16 panel is detected on should be displayed in the lower left of the EVACS software main screen. Document no: GLT PAGE 20

21 LIST OF AVAILABLE TONES Tone Type Primary (f1) / start frequency (Hz) Secondary (f2) / end frequency (Hz) Sweep duration (ms) On Period or f1 time (ms) Off period or f2 time (ms) 1 Alternating Sweep Sweep Intermittent Continuous Sweep Intermittent Alternating Sweep Intermittent Sweep Continuous Alternating Intermittent Sweep Continuous Note: All times are in milliseconds (ms), where 1000mS = 1 second CHANNEL VOLUME This provides a volume control interface to set the output volume of each zone. Document no: GLT PAGE 21

22 4.6. TRIGGER MATRIX The trigger matrix tells the panel what to do in the event that the alarm is triggered in a particular zone via the alarm trigger input. In this exa mpl e the zon e acti vat ed will go into alar m, whi lst all oth er zon es will go into alert; however it is possible to set a variety of configurations using this interface. When you are happy with the configuration, be sure to click on the [Send] button to upload the trigger matrix to the panel. Document no: GLT PAGE 22

23 4.7. SETTINGS From here you can set the number of zones configured on a network. Select 1 for a standalone system. Each EVACS 1-16 connected to the network is counted as one zone STATUS MONITOR This displays the status of all nodes on the network, and reports any errors that may be present. Document no: GLT PAGE 23

24 4.9. FIRMWARE UPDATE Shows the version of the currently loaded firmware, and provides a utility to update the firmware image: WARNING: firmware updates should NOT be attempted unless under the specific instruction of the manufacturer. An incorrect firmware update may cause the panel to operate outside its design and conformity specifications, and may even cause permanent damage to the panel. Document no: GLT PAGE 24

25 5. OPERATING THE PANEL 5.1. DISPLAY AND CONTROLS DISPLAY The Premier EVACS1-16 has the following LED indicators:- LED COLOUR DESCRIPTION POWER ON GREEN The system has mains and/or battery backup present. The panel showing this LED only is the normal condition. SYSTEM FAULT YELLOW The system has developed a serious problem Contact your local dealer. POWER FAULT YELLOW The systems power supply is reporting a problem. EARTH FAULT YELLOW The system has detected a wiring fault shorting to earth. AMP FAULT YELLOW There is a problem with one of the systems amplifiers. COMMON FAULT YELLOW There is a fault on the system. Check specific LED for further information. COMMON ALARM RED The system is playing the pre-recorded alert message. DISABLEMENT YELLOW A zone has been disabled. MIC ACTIVE RED The panels live emergency microphone is being used to broadcast a message. REMOTE MIC RED A remote microphone is being used to broadcast a message. ACTIVE ALARM/ALERT RED The indicated zone(s) are playing the alarm or alert message (as indicated by ZONE 1-16 FAULT/DISABLE ZONE 1-16 YELLOW the common alarm/alert LEDs). The indicated zone(s) have a fault, or are in the disabled condition. Document no: GLT PAGE 25

26 Document no: GLT PAGE 26

27 CONTROLS The Premier EVACS 1-16 has the following controls:- LABEL TEST ALARM ALERT DISABLE SILENCE RESET STOP / START USE LED and buzzer test Used to initiate manual playback of the Evac / Alarm Message Used to initiate manual playback of the Alert Message Used to disable one or more of the speaker channels Used to silence the panels fault buzzer Used to reset the system from the voice alarm condition Used to Manually start playback of a selected message, or to stop an existing message Select buttons for channels 1 to 16 Document no: GLT PAGE 27

28 5.2. METHODS OF OPERATING THE PREMIER EVACS 1-16 The Premier EVACS 1-16 can operate in any one of the following ways:- LIVE BROADCAST The microphone is used to broadcast information about the alarm, and the responsible person would direct occupants what to do next. The Microphone broadcasts to all non-disabled channels. PRE-RECORDED MESSAGE (MANUAL) The Operator can select to play the pre recorded Evacuation or alert message to individual zones. The message(s) are only played to the selected zones. PRE-RECORDED MESSAGE (AUTOMATIC) Some or all of the Premier EVACS 1-16`s remote trigger inputs will be connected to I/O units in a fire panel. The panel will operate the I/O relays to link the relevant trigger to 0V. There are inputs for Evac on all zones, Alert on all zones, and an individual input for each zone, which can be configured via the PC Software. Sample configurations are:- Play evac / alarm on selected zone Play evac / alarm on selected zone, and alert on all other zones Play evac / alarm on selected zone, and alert on floor above & floor below As shown above, the number of zones operated will depend on the configuration of the remote inputs. Document no: GLT PAGE 28

29 5.3. RESETTING FROM A VOICE ALARM CONDITION The EVACS 1-16 can be reset in various ways, depending on how the Voice alarm condition was initiated. If the microphone is used for a live broadcast, simply releasing the microphone will return the EVACS 1-16 to its normal condition. If a pre-recorded message was started manually, it will need to be reset from the Voice Alarm Panel. Press Start/Stop to stop playing the message, then press reset to return the EVACS 1-16 to its normal condition. If a pre-recorded message was started automatically by a fire alarm panel, resetting the fire alarm panel will reset the Voice alarm panel automatically. Alternatively, the message can be stopped by pressing Stop/Start on the Voice alarm Panel. (Note if reset is then pressed, and the triggering signal is still active, the EVACS 1-16 will return to the voice alarm condition. Document no: GLT PAGE 29

30 6. FAULT DISPLAY & FAULT-FINDING 6.1. OVERVIEW The Premier EVACS 1-16 panel monitor for the following faults:- Power Supply Fault Speaker Channel open-circuit wiring fault Speaker Channel short-circuit wiring fault Sounder output open-circuit wiring fault Sounder output open-circuit wiring fault Earth Fault Amplifier Fault System Fault Most of these faults will need to be checked by an engineer. All faults in the Premier EVACS 1-16 are NON-LATCHING. IE they cannot be reset with the reset button. They will clear automatically when the fault has been fixed. The Premier EVACS 1-16 Voice Alarm panel also has a General Fault LED that will light when any fault is present. For system, power supply, or earth faults, a seperate LED will illuminate indicating the type of fault present (in the case of a power supply fault the Power LED will flash). Faults relating to speaker or sounder outputs will illuminate the AMP FAULT LED, the PC software can be connected to the panel for a more detailed report in the System status section. Where panels are networked, the zone fault LED corresponding to the panel reporting the fault will also illuminate. For stand-alone panels, only zone 1 will indicate a fault. Document no: GLT PAGE 30

31 6.2. FAULT FINDING POWER SUPPLY FAULT A power supply fault is indicative of one or more of the following faults: - Loss of Mains power Check that 230V AC is present at the mains terminal block Check mains fuse Check charger fuse FS1. Loss of Battery power Check that 2 X 12V batteries are fitted in series to give 24V backup Check battery fuse Check that battery connections are secure. Check that the batteries are not over 5 years old Loss of Charger The Evacs 1-16 will monitor the charger circuit. In the rare event of a component failure that affects the charger, the PSU will bring up a fault. Loss of Battery Capacity The Power supply will monitor the Battery condition. If it detects a high internal resistance, which usually means a loss of capacity in the battery, it will bring up a fault. SPEAKER CIRCUIT FAULT A Speaker Circuit Fault is indicative of one or more of the following faults:- Speaker Circuit Open Circuit fault. Check that there are no breaks in the cable, and that all screw connections are secure. As a panel check, disconnect the circuit indicating the fault, and press the calibrate button. If the fault clears, the panel is working correctly. Speaker Circuit Short Circuit Fault Check that all speakers are fitted the correct way round. Check than no other devices have been connected to the speaker circuit. Check for shorts to the cable screen. As a panel check, disconnect the circuit indicating the fault, and press the calibrate button. If the fault clears, the panel is working correctly. Document no: GLT PAGE 31

32 Speaker Failure Because the Premier EVACS 1-16 monitors the speaker circuits for a change in impedance, the system can usually detect a broken speaker. For example a broken wire to the drive cone will not affect the speaker line`s continuity, but it will affect its impedance. Presently, the only way to check for this is by verifying sound output at each speaker on the speaker circuit reporting the fault. EARTH FAULT The Premier EVACS 1-16 monitors it's cabling for short circuits to earth. Note: Earth faults may occur when connecting a PC to the panel via the USB cable as the data and power signals over USB are referenced to ground at the PC end. This is normal and will not cause harm to the unit, however take extra care not to cause any earth faults at the panel whilst a PC is connected to the unit. To trace an earth fault, first check for any obvious signs inside the panel, such as a loose wire shorting the earth. Next, disconnect each circuit (Speakers, sounders, loop and network) in turn until the earth fault clears. Once the circuit causing the fault has been identified, carefully check the wiring and connected devices for signs of a short to earth. AMP FAULT The Premier EVACS 1-16 monitors Amplifiers for correct operation. If one of its power amplifiers reports a fault, the EVACS 1-16 will report it. Try resetting the panel to clear the fault. Also check the fuses on the amplifier PCB are good. The Evacs configuration software may be able to supply more detailed information on AMP faults than the panel indicators alone. If the fault persists, contact your dealer. SYSTEM FAULT The Premier EVACS 1-16 monitors its internal software for correct operation. If it detects a possible problem, the EVACS 1-16 will report it. Try resetting the panel to clear the fault. If the fault persists, contact your dealer. Document no: GLT PAGE 32

33 7. BATTERY CALCULATION 7.1. GENERAL GUIDELINES As a general rule the battery selected as a backup power source for the panel should be calculated to provide at least 24 hours of standby power, plus 30 minutes power in the alarm condition plus a 25% reserve to account for battery life degradation, environmental factors or unexpected power drains. When calculating the backup power requirements for the audio system it is important to note that the relationship between output power, volume and power drain is non-linear, and may differ depending on the message store used. Refer to the section on audio output information for further details CALCULATING THE BATTERY REQUIRED Standby current will consist of the quiescent current draw of the panel, plus the current draw of any equipment connected to the aux power output. Alarm current will consist of: the alarm current of the panel plus the current draw of any equipment plus the current draw by the audio amplifiers Document no: GLT PAGE 33

34 7.3. EXAMPLE BATTERY REQUIREMENTS Consider a system consisting of: 1x 12W speaker system 1x 8W speaker system 100mA equipment draw on Aux power 300mA equipment draw on Aux power during alarm 480mA sounder channel 1 360mA sounder channel 2 The system must remain on standby for 24 hours The system must also be able to handle the alarm condition for a minimum of 1 hour Referring to the audio output power graph The 12W speaker system will have a maximum current draw of about 1.4A The 8W speaker system will have a maximum current draw of about 1.1A Standby requirements Quiescent current 0.06A Auxiliary equipment 0.1A Total standby current 0.16A x standby time of: 24h = 3.84 Ah (1) Alarm requirements System current Auxiliary equipment Sounder circuit 1 Sounder circuit 2 Audio channel 1 Audio channel 2 Total Alarm current 0.5 A 0.3 A 0.48 A 0.36 A 1.4 A 1.1 A 4.14 A x alarm time of: 1 h = 4.14 Ah (2) Total capacity requirements Sum of (1) and (2) = (1) 3.84 Ah + (2) 4.14 Ah = 7.98 Ah Minimum battery capacity = (3) 7.98 Ah x 1.25 = Ah The next battery capacity upwards from this is 12Ah, which would be suitable for this installation.. Document no: GLT PAGE 34

35 7.4. BATTERY CALCULATION WORKSHEET This worksheet can be filled out to calculate the batteries size required for a given installation. Standby requirements Quiescent current Auxiliary equipment A A Total standby current A x standby time of: h = Ah Alarm requirements System current Auxiliary equipment Sounder circuit 1 Sounder circuit 2 Audio channel 1 Audio channel 2 A A A A A A Total Alarm current A x alarm time of: h = Ah Total capacity requirements Sum of (1) and (2) = (1) (3) Ah + (2) Ah = Ah Minimum battery capacity = Ah x 1.25 = Ah When selecting the correct battery, always choose a battery with a higher capacity than the calculated minimum. Document no: GLT PAGE 35

36 Output power (single channel) PREMIER EVACS 1-16 INSTRUCTION MANUAL: 2-ZONE NETWORKED VOICE ALARM PANEL 8. AUDIO OUTPUT INFORMATION 8.1. OUTPUT POWER The following graph demonstrates typical performance characteristics for the Evacs The test panel was configured in standalone mode and audio output was set as a 1KHz sine wave with each speaker output played into a dummy load. Test me asur em ents are inte nde d as a gui de onl y as act ual po wer thro ugh put Power output vs volume setting (1KHz sine wave) Volume (db) 770Ω load 550Ω load will differ depending on the audio played, and may push the system beyond its recommended operating parameters. Please note that maximum output of the unit is indicative only and that setting the unit beyond the maximum recommended ratings may degrade audio performance. Actual output power will vary depending on the speaker system installed. Document no: GLT PAGE 36

37 Current draw (Amps) PREMIER EVACS 1-16 INSTRUCTION MANUAL: 2-ZONE NETWORKED VOICE ALARM PANEL 8.2. POWER CONSUMPTION The following graph shows typical power consumption characteristics of a single output channel. Current draw vs single channel output power Single channel output power (Watts) Document no: GLT PAGE 37

38 9. CONFIGURATION SWITCH SETTINGS The following table corresponds to the 8-way DIP on the amplifier PCB SWITCH ON OFF Notes SW1-4 Network address setting SW5 RESERVED RESERVED RESERVED SET TO OFF SW6 RESERVED RESERVED RESERVED SET TO OFF SW7 Master Alarm Local Alarm SW8 Local microphone Broadcast microphone Document no: GLT PAGE 38

39 10. SPECIFICATIONS ELECTRICAL SPECIFICATIONS ELECTRICAL DESCRIPTION VALUE MAINS VOLTAGE MAINS CURRENT V AC / V AC ± 50/60Hz 8.0A MAX SYSTEM VOLTAGE 29.5V NOMINAL ± 10% QUIESCIENT CURRENT DRAW 60mA ALARM CONDITION CURRENT DRAW 500mA MAX SYSTEM CURRENT DRAW 7.8A MAX SYSTEM POWER DRAW 255W BATTERY SPECIFICATION CHARGER SIZE SPEAKER LINE VOLTAGE MINIMUM SPEAKER IMPEDANCE MINIMUM RESISTIVE LOAD MAXIMUM CAPACITIVE LOAD OUTPUT PER CHANNEL TOTAL OUTPUT ALARM OUTPUT FAULT OUTPUT PANEL INPUTS 24V DC (2X 7.2AH, 12V SLA BATTERY) 24V, 7.2Ah 17Ah 100V NOMINAL 1KHz 1260Ω 110nF MAX 30W MAX 60W 2 x 500mA 28V DC 1X RELAY SELV NORMALLY ENERGISED 1X ALERT 1X EVACUATE PHYSICAL SPECIFICATIONS DESCRIPTION VALUE DIMENSIONS (h x w x d) x 400 x 173mm WEIGHT 7.1Kg TOP CABLE ENTRIES 28 BOTTOM CABLE ENTRIES 6 Document no: GLT PAGE 39

40 10.3. FUSE RATINGS FUSE NO DESCRIPTION RATING FS1 AMPLIFIER PROTECTION FUSE (CH1) 3.15A time delay 5x20mm ceramic FS2 AMPLIFIER PROTECTION FUSE (CH2) 3.15A time delay 5x20mm ceramic -- SOUNDER OUTPUT PROTECTION (S1) 500mA self-resetting PTC fuse -- SOUNDER OUTPUT PROTECTION (S1) 500mA self-resetting PTC fuse -- AUX POWER PROTECTION 500mA self-resetting PTC fuse -- BATTERY FUSE 5A Fast blow 5x20mm -- POWER SUPPLY FUSE 5A time delay 5x20mm -- MAINS FUSE 10A. Type depends on installation Document no: GLT PAGE 40

Prem1er EVACS16. Installation Manual VOICE ALARM CONTROL PANEL 4 16 ZONES

Prem1er EVACS16. Installation Manual VOICE ALARM CONTROL PANEL 4 16 ZONES Prem1er EVACS16 VOICE ALARM CONTROL PANEL 4 16 ZONES Installation Manual Approved Document No: GLT.MAN-141 PAGE 1 INDEX INDEX... 2 Summary... 3 Safety information & use of this manual... 5 Installation

More information

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL USER MANUAL 1 Table of Contents 1 SAFETY INFORMATION...3 1.1 SAFETY PRECAUTIONS DURING NORMAL OPERATION OF PANEL...3 1.3 BATTERY INFORMATION...3

More information

FIREPRO INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL. Approved Document No. GLT Issue: 1. 8 Author: NRPJ Date: 7/ 3/201 4

FIREPRO INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL. Approved Document No. GLT Issue: 1. 8 Author: NRPJ Date: 7/ 3/201 4 FIRE ALARM CONTROL PANEL INSTALLATION MANUAL Approved Document No. GLT -201-7-3 Issue: 1. 8 Author: NRPJ Date: 7/ 3/201 4 CONTENTS 1. INTRODUCTION... 1.1 HANDLING THE PCBS... 1.2 USING THIS MANUAL... 1.3

More information

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module FIRE ALARM CONTROL EQUIPMENT Addendum October 2006 Instructions for new style EN54-4 Power supply unit module MXLK-05 Issue 2.0 June 2007 INSTALLATION Safety Suppliers of articles for use at work are required

More information

INFINITY 8 INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL

INFINITY 8 INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL Approved Document No. GLT-201-7-1 CONTENTS 1. INTRODUCTION... 1.1 HANDLING THE PCBS... 1.2 USING THIS MANUAL... 1.3 ABOUT THE INFINITY FIRE ALARM CONTROL PANEL

More information

Unity DAU Voice Alarm System

Unity DAU Voice Alarm System Unity DAU Voice Alarm System User Manual & Log Book Site Name Address Contractor Commissioned Introduction Voice Alarm (VA) systems are the quickest way to evacuate the public & staff from a building.

More information

5000 INSTALLATION GUIDE

5000 INSTALLATION GUIDE 5000 INSTALLATION GUIDE Table of Contents Section Page No 1. INTRODUCTION... 3 2. WARNINGS AND CAUTIONS... 3 3. UNPACKING... 3 4. INSTALLATION... 4 5. CONTROL PANEL - REMOVING ITEMS BEFORE MOUNTING...

More information

Vocia VACIE. Reference Guide

Vocia VACIE. Reference Guide Vocia VACIE Reference Guide Document Revision 1.2.3, August 2015 Biamp Systems 9300 SW Gemini Drive Beaverton, Oregon 97008, U.S.A. (503) 641-7287 www.biamp.com INTRODUCTION... 3 SECTION 1... 4 VACIE CONFIGURATION...

More information

CFDAU30 Voice Alarm System

CFDAU30 Voice Alarm System CFDAU30 Voice Alarm System Installation and Maintenance Manual Cooper Lighting and Safety Ltd Wheatley Hall Road Doncaster South Yorkshire DN2 4NB TEL: +44 (0) 1302 321541 FAX: +44 (0) 1302 303220 Introduction

More information

PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions PANEL 1.84 & LOOP 3.70

PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions PANEL 1.84 & LOOP 3.70 PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions PANEL 1.84 & LOOP 3.70 MKII PROTOCOL - ONE TO FOUR LOOPS ANALOGUE ADDRESSABLE FIRE ALARM PANEL INSTALLATION MANUAL Doc No: GLT-215-7-1

More information

OPERATION AND INSTALLATION MANUAL

OPERATION AND INSTALLATION MANUAL EX+Plus 2 ZONE, 1AREA EXTINGUISHANT CONTROL PANEL OPERATION AND INSTALLATION MANUAL INTRODUCTION The Premier EX Plus is a 2 zone, single area panel for controlling the release of extinguishing gases in

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

Syncro Matrix Analogue Addressable Fire Alarm Mimic Panel Product Manual

Syncro Matrix Analogue Addressable Fire Alarm Mimic Panel Product Manual Syncro Matrix Analogue Addressable Fire Alarm Mimic Panel Product Manual Australia Issue 01 April 2012 Contents 1 Introduction 3 2 Safety 3 3 Installation 4 3.1 Mounting the Cabinet 4 4 Specifications

More information

VACIE REFERENCE GUIDE REVISION 1.2.6

VACIE REFERENCE GUIDE REVISION 1.2.6 VACIE REFERENCE GUIDE REVISION 1.2.6 November 2016 INTRODUCTION... 3 SECTION 1... 4 VACIE CONFIGURATION... 4 Communications... 4 Vocia VACIE Devices... 4 Vocia Support devices:... 5 Power Supply and Network

More information

Installation and user manual for the BiWire / Conventional Repeater Panel

Installation and user manual for the BiWire / Conventional Repeater Panel Panel EFBWCV-REPEATER Contents Introduction.... 3 Purpose... 3 The Panel.... 3 Indication Equipment (IE).... 3 Power Supply Equipment (PSE).... 4 System Wiring.... 5 Status Indications.... 5 Repeater I/O....

More information

FIRE ALARM CONTROL PANEL. COMPLIES WITH EN54 part 2 & part 4 MEETS THE FUNCTIONAL REQUIREMENT OF BS:EN 5839 part 1 INSTALLATION MANUAL

FIRE ALARM CONTROL PANEL. COMPLIES WITH EN54 part 2 & part 4 MEETS THE FUNCTIONAL REQUIREMENT OF BS:EN 5839 part 1 INSTALLATION MANUAL FIRE ALARM CONTROL PANEL COMPLIES WITH EN54 part 2 & part 4 MEETS THE FUNCTIONAL REQUIREMENT OF BS:EN 5839 part 1 INSTALLATION MANUAL CONTENTS 1. INTRODUCTION. 3 1.1 HANDLING THE PCBS 1.2 USING THIS MANUAL

More information

USER MANUAL & MAINTENANCE GUIDE OG OO

USER MANUAL & MAINTENANCE GUIDE OG OO M+48. USER MANUAL & MAINTENANCE GUIDE OG OO What to do if the Fire Alarm Panel shows an Alarm (Red LED) Write down which LEDs are lit (either in the log book, or on a piece of paper for transferring to

More information

Control Panel Engineering and Commissioning Instructions

Control Panel Engineering and Commissioning Instructions Twinflex - V3 Fire Detection & Alarm System Control Panel Engineering and Commissioning Instructions (TO BE RETAINED BY THE COMMISSIONING ENGINEER) 26-0338 Issue 9 Fike s policy is one of continual improvement

More information

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel INSTALLATION, OPERATION AND MAINTENANCE MANUAL Version: CN-PM-1000.VER1.1-12/2012 EN54 INFORMATION In accordance with EN 54-2 clause 13.7, the maximum

More information

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL ISSUE 1: DATE 8/10/2014 AUTH: NJ INSTALLATION MANUAL 1 Table of Contents 1 SAFETY INFORMATION...5 1.1 INSTALLATION INFORMATION...5 1.2 HANDLING

More information

16 Zone Voice Evacuation VA & PA Sound System

16 Zone Voice Evacuation VA & PA Sound System 16 Zone Voice Evacuation VA & PA Sound System 4 Channel Main Amp VA-MP4120 PC Server & Software VA-2000ST T-565 Zone 1-4 One Channel Standby Amp VA-2000RM VA-2000MA T-565 Zone 5-8 LAN CAT5 Cable CAT5 Data

More information

VoCALL - CFVCC5. Compact 5 Line Exchange Unit. Installation & Commissioning Manual

VoCALL - CFVCC5. Compact 5 Line Exchange Unit. Installation & Commissioning Manual VoCALL - CFVCC5 Compact 5 Line Exchange Unit Installation & Commissioning Manual Introduction A VoCALL Emergency Voice Communications System (EVCS) is a fixed, secure, bi-directional, full duplex voice

More information

EXTINGUISHING AGENT RELEASE MODULE

EXTINGUISHING AGENT RELEASE MODULE EXTINGUISHING AGENT RELEASE MODULE Operation, Installation & Programming Manual Revision 3.00 Distributors For: 18-20 Brookhollow Ave telephone 02 8850 2888 www.firesense.com.au Baulkham Hills NSW 2153

More information

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS QUICK USER GUIDE FOR, 2 & 4 ZONE PANELS INDICATORS COLOUR INDICATION MON FAULT Yellow On when a fault condition has occurred, or if no other fault Led is on, this indicates 24v auxiliary fuse failure.

More information

BiWire Flexi. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI Installation Manual

BiWire Flexi. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI Installation Manual BiWire Flexi BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI Installation Manual Contents Contents 1. INTRODUCTION... 4 1.1 Purpose...4 2. THE BIWIRE FLEXI FIRE DETECTION & ALARM

More information

The system is expanded via the RCC network with each RCC capable of passing information to and from up to 31 detection or output devices.

The system is expanded via the RCC network with each RCC capable of passing information to and from up to 31 detection or output devices. FireCell Radio Hub Fully addressable Wireless activation Third party approved (EN54) 2-way radio communication Loop powered Diagnostics port Range in excess of 150 metres Overview The model FCX-500-001

More information

DCA4. Digitally controlled Audio Matrix. Current Thinking. Product Specification March Document Number DDC DCA ACS

DCA4. Digitally controlled Audio Matrix. Current Thinking. Product Specification March Document Number DDC DCA ACS DCA4 Digitally controlled Audio Matrix Product Specification March 2002 Current Thinking Document Number DDC DCA 7001 01 ACS Introduction Voice Alarm (VA) systems are the quickest way to evacuate the public

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd OPERATIONAL NOTES FOR CONCEPT FIRE PANEL. NOTE ON NEW FIRE PANELS, POSITION 1 ON THE SIX WAY INTERNAL OPTION SWITCH IS TURNED ON, DISABLING THE ZONAL SOUNDERS. TO ENABLE ZONAL SOUNDERS TURN OFF. Operation

More information

FEC400 Series. Installation Manual

FEC400 Series. Installation Manual FEC400 Series Conventional microprocessor controlled fire detection and alarm panels with extinguishing control Installation Manual Version 2.3 / August 2004 Aritech is a GE Interlogix brand. http://www.geindustrial.com/ge-interlogix/emea

More information

Written by: A.C. Amended by G.G. Checked by: JBJ/PB Approved by:jbj

Written by: A.C. Amended by G.G. Checked by: JBJ/PB Approved by:jbj Written by: A.C. Amended by G.G. Checked by: JBJ/PB Approved by:jbj Control Equipment Limited 32 Zone, 40 Character Discovery Panel, Voyager Panel and Integra Network Repeater Installation, Commissioning

More information

FI6000 INSTRUCTION MANUAL. Thank you for choosing another quality product from Amperes Electronics. Fire Alarm Interface

FI6000 INSTRUCTION MANUAL. Thank you for choosing another quality product from Amperes Electronics. Fire Alarm Interface INSTRUCTION MANUAL FI6000 Fire Alarm Interface Thank you for choosing another quality product from Amperes Electronics. FI6000 is a phase evacuation controller which can be integrated with various Amperes

More information

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels CF5000, MF5000 and FXP5000 Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels 16 zone panels Contents PANEL INSTALLATION...3 Installation...3 PANEL WIRING... 3 Mains power

More information

EvacU Emergency Warning Control and Indicating Equipment (Occupant Warning Systems) Technical Manual MAN3072-5

EvacU Emergency Warning Control and Indicating Equipment (Occupant Warning Systems) Technical Manual MAN3072-5 EvacU Emergency Warning Control and Indicating Equipment (Occupant Warning Systems) Technical Manual MAN3072-5 MAN2995-2 05/09/12 TABLE OF CONTENTS Section Page No. 1 About This Manual... 3 1.1 Introduction...

More information

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL 3500 CONVENTIONAL FIRE ALARM CONTROL PANEL INSTALLATION AND COMMISSIONING MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax:

More information

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV LC1 & 2 Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV ZIRCONLC1 One Zone Conventional Fire Panel ZIRCONLC2 Two Zone Conventional Fire Panel Compliant with EN54-2:1998 & EN54-4:1998

More information

USER MANUAL FOR OPERATING SYSTEM

USER MANUAL FOR OPERATING SYSTEM P2262 ALARM PANEL USER MANUAL FOR OPERATING SYSTEM 21765-07 September 1999 Associated Controls (Aust) PTY. LTD. 29 Smith Street, Hillsdale, NSW, 2036. PH (02) 9311 3255, FAX (02) 9311 3779 Page 1 of 177

More information

Occupant Warning System

Occupant Warning System Operation / Technical Manual Standalone OWS Rev 2.3 Occupant Warning System BOWS020W, BOWS060W & BOWS120W MA380 September 2017 Document History Issue Date Description Written By Checked By Draft 0 25 Sep

More information

ECC-50/100C. Emergency Command Center

ECC-50/100C. Emergency Command Center ECC-50/100C Emergency Command Center Canadian DF-60815:B Emergency Communications General Fire-lite s ECC-50/100C is a multipurpose emergency voice evacuation panel for fire applications, mass notification

More information

Distributed Amplifier Unit (DAU) (EESDAU100) Emergency Microphone All Call (EMA) (EESEMA) User Operational & Maintenance Manual

Distributed Amplifier Unit (DAU) (EESDAU100) Emergency Microphone All Call (EMA) (EESEMA) User Operational & Maintenance Manual Emergency Evacuation System Distributed Amplifier Unit (DAU) (EESDAU100) Emergency Microphone All Call (EMA) (EESEMA) User Operational & Maintenance Manual Emergency Microphone Power ON System FAULT General

More information

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL Document No...G108WO1.DOC Serial No... Issue Date...17 th SEPTEMBER 1999 Software Version...1.4 APPROVED TO: NZS 4512:1997 AS/NZS 3548:1992 Fire Alarm

More information

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual CONTENTS Installation Precautions... 1 EN 54 Information... 2 Chapter 1 Product Overview... 3 1.1 Features... 3 1.2 Technical Specifications... 3 1.2.1 Operating Voltage... 3 1.2.2 Batteries... 3 1.2.3

More information

Control Panel Engineering and Commissioning Manual (TO BE RETAINED BY THE COMMISSIONING ENGINEER)

Control Panel Engineering and Commissioning Manual (TO BE RETAINED BY THE COMMISSIONING ENGINEER) Fire Detection & Alarm System Control Panel (Suitable for TWINFLEX pro control panels from V2.00) Control Panel Engineering and Commissioning Manual (TO BE RETAINED BY THE COMMISSIONING ENGINEER) 26-0959

More information

BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL

BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL 26 Aug 2015 V1.8 Page 1 SECTION CONTENTS PAGE NO. 1.0 SYSTEMS DESCRIPTION 1.1 General descriptions 2 1.2 Master Alarm PCB 2 1.3 Zone Display Board 2 1.4

More information

ACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel

ACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel ACC-25/50ZST Zoned System Voice with Telephone Evacuation Control Panel General The AUDIO COMMAND CENTER 25/50 Zone System with FireFighters Telephone (ACC-25/50ZST) is a state-of-the-art Emergency Voice

More information

JUNO-NET. Fire Alarm Control Panel OPERATION & MAINTENANCE MANUAL

JUNO-NET. Fire Alarm Control Panel OPERATION & MAINTENANCE MANUAL Fire Alarm Control Panel & MANUAL CONTENTS SECTION -. Description of the fire control panel fascia.... Alarm.... Reset the system.... Sound and silence the alarms.... Read the Fire, Fault, Test and Disabled

More information

Call stations and extensions

Call stations and extensions Novigo Call stations and extensions PT2001-A1, PT2002-A1, PT2008-A1, PT2009-A1, PTO2001-A1, PTO2002-A1, PTO2003-A1, PTO2004-A1, PTO2005-A1, PTO2006-A1, PTO2008-A1 EN 54-16-certified alarm and business

More information

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117 Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel Revision E 61117 CAUTION: (Read This First) This panel has been designed to make it nearly bullet proof to mistakes made when wiring

More information

Entero Voice Alarm system.

Entero Voice Alarm system. Entero Voice Alarm system. Entero ESC installation menu guide Rev. 1.0 The manufacturer reserves specification privileges. Information in this manual is subject to change without prior notice or obligation.

More information

FEC403EN Installation Manual

FEC403EN Installation Manual FEC403EN Installation Manual P/N 10-4101-501-2FC1-01 ISS 22JAN15 Copyright Trademarks and patents Manufacturer 2015 UTC Fire & Security. All rights reserved. The FEC403EN name and logo are trademarks of

More information

4100S. The operation and functions described in this manual are available from Software Version 4100S onwards.

4100S. The operation and functions described in this manual are available from Software Version 4100S onwards. 4100S The operation and functions described in this manual are available from Software Version 4100S-023-013 onwards. Specifications: Item Specification Details Enclosure Steel IP30 Dimensions H x W x

More information

PERTRONIC INDUSTRIES LTD F4-RMAX Installation Note

PERTRONIC INDUSTRIES LTD F4-RMAX Installation Note Product Overview: The Pertronic F4 Remote LED Mimic / Aux Relay Module F4-RMAX is an optional extra for the Pertronic F4 conventional 4-zone fire alarm panel. This board enables the fire alarm panel to

More information

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Firmware Versions: PANEL 1.84 & LOOP CARD 3.70 MKII PROTOCOL ONE TO FOUR LOOPS ANALOGUE ADDRESSABLE FIRE ALARM PANEL USER MANUAL, MAINTENANCE GUIDE & LOG BOOK #Doc No. GLT-215-7-2 TABLE OF CONTENTS WHAT

More information

ECC-50/100(E) Emergency Command Center. General. Features. Emergency Voice Evacuation TYPICAL APPLICATIONS

ECC-50/100(E) Emergency Command Center. General. Features. Emergency Voice Evacuation TYPICAL APPLICATIONS ECC-50/100(E) Emergency Command Center DF-60734:A4 General Firelite s ECC-50/100 and ECC-50/100E are multipurpose emergency voice evacuation panels for fire applications, mass notification applications,

More information

Algo-Tec 6500/6600 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS)

Algo-Tec 6500/6600 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS) Algo-Tec 6500/6600 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS) COMMISSIONING MANUAL Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT, ENGLAND +44

More information

ZIOU/230 - MAINS IO INSTRUCTION MANUAL

ZIOU/230 - MAINS IO INSTRUCTION MANUAL Description ZIOU/230 - MAINS IO INSTRUCTION MANUAL The Mains IO Modules are fully monitored loop powered devices which permit the interfacing of third party equipment with the Fire Alarm Control panel

More information

ICS Regent. Fire Detector Input Modules PD-6032 (T3419)

ICS Regent. Fire Detector Input Modules PD-6032 (T3419) ICS Regent Fire Detector Input Modules (T3419) Issue 1, March, 06 Fire detector input modules provide interfaces for 16 fire detector inputs such as smoke detectors, flame detectors, temperature detectors,

More information

Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses

Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses BCU Power Supplies Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses Installation, Commissioning and Operating Manual BCU RANGE OF

More information

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009 Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual Man-1048 Issue 05 October 2009 CONTENTS Contents... Page Safety & Installation...2 Installation - continued...3

More information

EvacU Emergency Warning Control and Indicating Equipment (Occupant Warning Systems) Technical Manual MAN3072-9

EvacU Emergency Warning Control and Indicating Equipment (Occupant Warning Systems) Technical Manual MAN3072-9 EvacU Emergency Warning Control and Indicating Equipment (Occupant Warning Systems) Technical Manual MAN3072-9 TABLE OF CONTENTS Section Page No. 1 About This Manual... 3 1.1 Introduction... 3 1.2 References...

More information

ECC-50/100(E) Emergency Command Center

ECC-50/100(E) Emergency Command Center ECC-50/100(E) Emergency Command Center DF-60734:A9 C-200 General Fire Lite s ECC-50/100 and ECC-50/100E are multipurpose emergency voice evacuation panels for fire applications, mass notification applications,

More information

Operation and Maintenance Manual

Operation and Maintenance Manual (FKER Series) Repeater Panel (FKER, FKER, FKER8) Operation and Maintenance Manual Man-9EL Issue June Index Section Page. Introduction.... Safety and mounting.... Technical specification.... Control panel

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd full installation, commissioning and operating manuals can be downloaded from www.haes-systems.co.uk combined addressable / conventional fire alarm control panel User Guide Approved Document No. MFBU-04

More information

FIRE ALARM CONTROL PANEL FVC01-08

FIRE ALARM CONTROL PANEL FVC01-08 FIRE ALARM CONTROL PANEL FVC01-08 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Radal Technology Limited Unit 1, Webber Court Billington Road, Burnley Lancashire, BB11 5UB Tel: +44 (0) 1282 463 770 Fax: +44

More information

DIVA8MG2. Compact PAVA System Master Unit. DIVA8 System

DIVA8MG2. Compact PAVA System Master Unit. DIVA8 System DIVA8MG2 Public Address - Voice Alarm Audio Distribution over IP Commercial Audio Intelligent Acoustic Solutions Intercommunication Loudspeakers Compact PAVA System Master Unit DIVA8 System DIVA8 system

More information

Application, Installation, Operation & Maintenance Manual

Application, Installation, Operation & Maintenance Manual APPROVED BY:JBJ PRESCIENT III FIRE ALARM & GAS EXTINGUISHING CONTROL PANEL Application, Installation, Operation & Maintenance Manual PAGE 1 of 43 CONTENTS 1. INTRODUCTION... 3 2. GENERAL DESCRIPTION...

More information

New Silent Alert Fire Safe System

New Silent Alert Fire Safe System 1 New Silent Alert Fire Safe System TECHNICAL MANUAL This manual covers the FSTX-2225-EU - Fire Alarm Interface PG3A-2204-EU - Pager Unit - Fire Safe Compatible FSCH-2226-IN - Fire Safe Charger or CH3A-2205-IN

More information

OPERATION / INSTALLATION

OPERATION / INSTALLATION OPERATION / INSTALLATION & PROGRAMMING MANUAL AFP-2800 LCD-80 Fire Alarm Panel Revision 1.01 November 16, 2004 NSW (Head Office) 7 Columbia Court Norwest Business Park Baulkham Hills NSW 2153 Ph: (02)

More information

Silent Alert Fire Safe System

Silent Alert Fire Safe System Silent Alert Fire Safe System Technical Manual This manual covers the FSTX-2225-EU Fire alarm interface PG3A-2204-EU Pager FSCH-2226-IN Fire Safe Charger or CH3A-2205-IN Alarm clock charger SW3A-2208-EU

More information

Product Data Sheet. Remote Terminals. Features:

Product Data Sheet. Remote Terminals. Features: Remote Terminals Product Data Sheet Features: Based around two core products, the Mx- 4010 Remote Display Terminal (RDT) and the fully functional Mx-4020 Remote Control Terminal (RCT). Both remote terminals

More information

Surveyor Excel. Fire Alarm Control Equipment Network version. Programming Manual MASTER MANUAL. VERSION 14.0 and Above

Surveyor Excel. Fire Alarm Control Equipment Network version. Programming Manual MASTER MANUAL. VERSION 14.0 and Above Surveyor Excel Fire Alarm Control Equipment Network version Programming Manual VERSION 14.0 and Above MASTER MANUAL Drawing S1606. PCB Layout guide for XLK range of control panels FCPXLK-2/4/6/8 & FCPXLK2/4/6/8TW

More information

Public Safety DAS Annunciator Panel

Public Safety DAS Annunciator Panel Public Safety DAS Annunciator Panel 120 VAC Models: 1221-A, 1221-B, 1221-C Revision D 91117 48 VDC Models: 1221-A-48, 1221-B-48, 1221-C-48 24 VDC Models: 1221A-24, 1221-B-24, 1221-C-24 CAUTION: (Read This

More information

Entero Voice Alarm system. User guide

Entero Voice Alarm system. User guide Entero Voice Alarm system. User guide The manufacturer reserves specification privileges. Information in this manual is subject to change without prior notice or obligation. 2 Table of Contents Introduction...

More information

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK FIRE ALARM CONTROL PANEL COMPLIES WITH EN54 part 2 & part 4 MEETS THE FUNCTIONAL REQUIREMENT OF BS:EN 5839 part 1 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK. CONTENTS 1. FIRE ALARM CONTROL PANEL SAFETY

More information

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels Installation and user manual for the FX range of fire panels 1, 2, 4 and 8 zone panels Contents Panel installation 3 Panel connections 3 Wiring connection drawings 4 Panel facilities 6 Installation check

More information

USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4

USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4 PREMIER EX8 EXTINGUISHING PANEL USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN 12094 PART 1 & EN54 PARTS 2 & 4 USER MANUAL Approved Document No: GLT.MAN-132 INDEX Extinguishing

More information

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK ONE OR TWO LOOP ANALOGUE ADDRESSABLE FIRE ALARM CONTROL PANEL USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Approved Document No: GLT.MAN-108 TABLE OF CONTENTS WHAT TO DO IF THE FIRE ALARM PANEL SHOWS AN ALARM

More information

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

Syncro AS. Analogue Addressable Fire Control Panel. User Manual Syncro AS Analogue Addressable Fire Control Panel User Manual Man-1100 Issue 02 Nov. 2008 Index Section Page 1. Introduction...3 2. Safety...3 3. Panel Controls...4 3.1 Access Level 1...4 3.2 Access Level

More information

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge Replaceable LED modules 11 Alarm Sequences as per ISA-18.1 standard Each channel/window fully field programmable RS232 or RS485 MODBUS-RTU communication Repeat relay for each window and multifunction relays

More information

Hydrosense. Vimpex Limited. Star Lane. Great Wakering. Essex SS3 0PJ. Tel: +44 (0) Fax +44 (0)

Hydrosense. Vimpex Limited. Star Lane. Great Wakering. Essex SS3 0PJ. Tel: +44 (0) Fax +44 (0) Overview of the Water Detection System 2 Components of a System 4 Design & Planning 5 System Installation Notes 7 Control Panel Installation - HSCPI-K3000 8 Control Panel Commissioning HSCPC-K3000 11 Front

More information

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum. September 29, 1997 Firecycle III 433 a 1. PRODUCT NAME VIKING Model E-1 Manufactured 1997 Present 2. MANUFACTURED FOR THE VIKING CORPORATION 210 N Industrial Park Road Hastings, Michigan 49058, U.S.A.

More information

VX-2000 SERIES INTEGRATED VOICE EVACUATION SYSTEM

VX-2000 SERIES INTEGRATED VOICE EVACUATION SYSTEM EN60849/IEC60849 compliant VX-2000 SERIES INTEGRATED VOICE EVACUATION SYSTEM Full compliance with EN60849/IEC60849 standards System status can be confirmed on Remote Microphones Fireman s Microphone included

More information

Syncro AS. Analogue Addressable Fire Control Panel. Product Manual

Syncro AS. Analogue Addressable Fire Control Panel. Product Manual Syncro AS Analogue Addressable Fire Control Panel Product Manual Man-1096 Issue 05 Nov 2008 Index Section Page 1. Introduction...4 2. Safety...4 3. Installation...5 4. Cabling...6 4.1 Cable Termination...

More information

Excel-EN Conventional Fire Control Panel

Excel-EN Conventional Fire Control Panel Available as 2, 4, 6, 8,10 or 12 zones Approved to EN54-2 & 4 Modular expansion zone cards Programmable relays and outputs Optional additional sounder circuits Optional additional programmable outputs

More information

DiMM Unit. LST Digital Interface Monitor Module (LST-DiMM) MAN3109

DiMM Unit. LST Digital Interface Monitor Module (LST-DiMM) MAN3109 LST Digital Interface Monitor Module (LST-DiMM) MAN3109 TABLE OF CONTENTS: Page No. 1 Important Guidelines... 3 2 General Description... 4 Digital Interface Monitor Module... 4 3 Specifications... 5 Leader

More information

System 800 Addressable Fire Detection & Alarm System

System 800 Addressable Fire Detection & Alarm System SECTION 5: page 1 Section 5: System 800 Addressable Fire Detection & Alarm System SECTION 5: page 3 10 reasons to specify 800 1 Plug and Play A user friendly panel not requiring special software tools

More information

INDEX 1- Introduction The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops The Control Panel 4 and 8 Loops...

INDEX 1- Introduction The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops The Control Panel 4 and 8 Loops... GUIDE MANUAL INDEX 1- Introduction...5...5...6 4- The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops...7 4.2- The Control Panel 4 and 8 Loops...9 5- Installation Guide...10 5.1- Pre-Installation

More information

Conventional Fire Alarm System 2014 V1.2

Conventional Fire Alarm System 2014 V1.2 Conventional Fire Alarm System 2014 V1.2 Product Overview Control Panel 2 Conventional Fire Panel GST102A 2 zone Fire panel GST104A 4 zone Fire panel GST108A 8 zone Fire panel GST116A 16 zone Fire Panel

More information

ZSC100 Gas Detection and Alarm System Controller

ZSC100 Gas Detection and Alarm System Controller ZSC100 Gas Detection and Alarm System Controller User Guide 1- Introduction... 3 1.1- General description... 3 1.2- Cautions and warnings... 3 2- Control panel... 4 2.1 Control panel overview... 4 2.2

More information

SECURIT 700L PLUS ENGINEERING MANUAL

SECURIT 700L PLUS ENGINEERING MANUAL SECURIT 700L PLUS ENGINEERING MANUAL C & K Systems Ltd 13/03/97 C031-096-02 NEW ENHANCED FEATURE SET Securit 700L PLUS Engineering instructions INTRODUCTION The Securit 700L is a microprocessor intruder

More information

Conventional Fire Control Panel (FKEP2, FKEP4, FKEP8) Operation and Maintenance Manual. Man-1078EL Issue 01 February 2014

Conventional Fire Control Panel (FKEP2, FKEP4, FKEP8) Operation and Maintenance Manual. Man-1078EL Issue 01 February 2014 Conventional Fire Control Panel (FKEP2, FKEP4, FKEP8) Operation and Maintenance Manual Man-1078EL Issue 01 February 2014 B Index Page 1. Introduction... 3 1B2. Safety and mounting... 3 2B3. Technical specification...

More information

SOLO Single Loop Addressable Fire Control Panel

SOLO Single Loop Addressable Fire Control Panel Solo Single Loop Analogue Addressable Fire Control Panel Apollo Protocol Installation, Commissioning & Operating Manual Issue 03 June 1999 CONTENTS Section... Page 1. Introduction...1 2. Safety...2 3.

More information

OPERATION & INSTALLATION MANUAL FOR ALARM PANEL M2AP01

OPERATION & INSTALLATION MANUAL FOR ALARM PANEL M2AP01 OPERATION & INSTALLATION MANUAL FOR ALARM PANEL M2AP01 Table of Contents Safety Instructions 4 Owner/Operator Responsibility 4 Specifications 5 Introduction 6 Installation Instructions 7 Setup 7 Wiring

More information

Series SPB Audio Boosters Installation, Testing, Operation, and Maintenance Manual

Series SPB Audio Boosters Installation, Testing, Operation, and Maintenance Manual Series SPB Audio Boosters Installation, Testing, Operation, and Maintenance Manual Part Number P84748 Assembly Number A84749 Revision C Revision A Copyright 2006 Printed in U.S.A. All rights reserved.

More information

Premier Hazard STC Instructions

Premier Hazard STC Instructions PREMIER HAZARD Ltd Bessingby Industrial Estate Bridlington YO16 4SJ Tel: +44 (0) 113 239 1111 Fax: +44 (0) 113 239 1131 www.premierhazard.co.uk info@premierhazard.co.uk Premier Hazard STC Instructions

More information

Document No Issue 02 operation & installation manual. ZXr-A ZXr-P

Document No Issue 02 operation & installation manual. ZXr-A ZXr-P ZXr-A ZXr-P Document No. 996-144 Issue 02 operation & installation manual MORLEY-IAS ZXr-A / ZXr-P Repeaters Table of Contents 1 INTRODUCTION... 3 1.1 NOTICE... 3 1.2 WARNINGS AND CAUTIONS... 3 1.3 NATIONAL

More information

Intelligent addressable fire alarm control panel

Intelligent addressable fire alarm control panel Intelligent addressable fire alarm control panel Input current consumption: Panel rating: Batteries: Networking and Interfaces Panel to panel communication: Number of panels: Interface port: System capacity

More information

LEAKMONITOR MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND USER OPERATION MANUAL

LEAKMONITOR MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND USER OPERATION MANUAL LEAKMONITOR MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND USER OPERATION MANUAL The LeakMonitor alarm panel is a microprocessor controlled fully adjustable alarm system suitable for multizone

More information

NFS Supra / VSN-2Plus / ESS-2Plus Conventional Fire Alarm Control Panel. Installation and Operating Manual

NFS Supra / VSN-2Plus / ESS-2Plus Conventional Fire Alarm Control Panel. Installation and Operating Manual / VSN-2Plus / ESS-2Plus Conventional Fire Alarm Control Panel Installation and Operating Manual HLSI-MN-025-I v.05 April 2015 Note: This manual is valid for the following control panel models: NFS-Supra

More information

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08 Beacon 200 Gas Monitor Operator s Manual Part Number: 71-2102RK Released: 6/6/08 Table of Contents Chapter 1: Introduction.................................................3 Overview.............................................................3

More information

OmniCare EVC System. Installation & Commissioning Manual

OmniCare EVC System. Installation & Commissioning Manual Manual name: OmniCare Issue: 10 ECR: 2721 Date of issue: Jan 2013 Jan 2013 Baldwin Boxall Communications Limited Wealden Industrial Estate Farningham Road, Jarvis Brook Crowborough East Sussex TN6 2JR

More information