1 Iowa State Fire Marshal LIFE SAFETY CODE REQUIREMENTS LONG TERM CARE Kyle R. Gorsh, Special Agent in Charge Iowa Department of Public Safety State Fire Marshal Division 2012 LSC & Applicable Standards National LTC Top-10 LSC Deficiencies Fire Alarm Testing Paperwork Fire Alarm / Sprinkler Outage Policies Electrical Outlet Testing Surge Protector Enforcement Fire Door Annual Testing Emergency Preparedness Plans 2 3 1

2 NFPA Standards Important NFPA standards NFPA 10, 2010 edition NFPA 13, 2010 edition NFPA 25, 2011 edition NFPA 72, 2010 edition NFPA 96, 2011 edition NFPA 99, 2012 edition NFPA 110, 2010 edition 4 National LTC Top 10 LSC Deficiencies FY17 K353 - Sprinkler Maintenance K363 - Corridor Doors K321 - Hazardous Areas K372 - Smoke Partitions K920 - Power Strips K712 - Fire Drills K345 - Fire Alarm Maintenance K918 - Generator Maintenance K511 - Gas and Electrical Utilities K324 - Cooking Facilities 5 Fire Alarm Testing Reports All devices connected to your fire alarm system need to have evidence that each individual device was tested. You need an accurate inventory of every device, complete with a description as to where it is located. The test report needs to list each and every individual device, a description of where it is located, and whether it passed or failed its test. Here is a list of the most common interface relays used in healthcare fire alarm systems: Magnetic hold open devices Hood suppression system Air handler shutdown Magnetic locks Fire pump Overhead rolling fire doors Smoke dampers Sprinkler dry pipe/pre-action systems Elevator Recall 6 2

3 Fire Alarm Impairments NFPA Standard: 2012 NFPA 101, Where a required fire alarm is out of service for more than 4 hours in a 24-hour period, the authority having jurisdiction shall be notified, and the building shall be evacuated, or an approved fire watch shall be provided for all parties left unprotected by the shutdown until the fire alarm system has been returned to service. Pre-planned or emergency Shall be dedicated Fire watch shall be continuous Shall be trained in fire prevention Shall have means to notify the fire department Occupants notified Local fire department, Department of Inspections & Appeals, & Fire Marshal shall be notified Documentation maintained for one year 7 Sprinkler Impairments (See Handout) NFPA Standard: 2012 NFPA 101, Sprinkler impairment procedures shall comply with NFPA 25. NFPA Standard: 2011 NFPA 25, Where an impairment to a water-based fire protection occurs, the procedures outlined in Chapter 15 of this standard shall be followed, including the attachment of a tag to the impaired system. NFPA Standard: 2011 NFPA 25, Where a water based fire protection system is returned to service following an impairment, the system shall be verified to be working properly by means of an appropriate inspection or test. 8 Sprinkler Impairments NFPA 25, 2011 Edition (Chapter 15) Assignment of an Impairment Coordinator The system shall be tagged to indicate the system has been removed from service at each FD connection, system control valve, and any other location deemed by the AHJ. Where the sprinkler system is out of service for more than 10 hours in a 24-hour period, the impairment coordinator shall arrange for the following: a) Evacuation of the building (or) portion of the building affected by the outage b) An approved fire watch c) Establishment of a temporary water supply d) Establishment and implementation of an approved program to eliminate potential ignition sources and limit the amount of fuel available to the fire. 9 3

4 Sprinkler Impairments NFPA 25, 2011 Edition (Chapter 15) The fire department shall be notified. The insurance carrier, the alarm company, property owner or designated representative, DIA, SFM have been notified. The supervisors in the areas to be affected have been notified. A tag impairment system has been implemented (Section 15.3) All necessary tools and materials have been assembled on the impairment site. 10 Sprinkler Impairments NFPA 25, 2011 Edition (Chapter 15) 15.6 Emergency Impairments Emergency impairments shall include, but are not limited to, system leakage, interruption of water supply, frozen or ruptured piping, and equipment failure When emergency impairments occur, emergency action shall be taken to minimize potential injury and damage The coordinator shall implement the steps outlined in Section Electrical Outlet Testing NFPA 99, 2012 Edition, Where hospital-grade receptacles are required at patient bed locations and in locations where deep sedation or general anesthesia is administered, testing shall be performed after initial installation, replacement, or servicing of the device Receptacles not listed as hospital-grade, at patient bed locations and in locations where deep sedation or general anesthesia is administered, shall be tested at intervals not exceeding 12 months. 12 4

5 Surge Protector Use SURGE PROTECTORS USED FOR PATIENT CARE RELATED EQUIPMENT (VENTILATORS, BREATHING MACHINES, OXYGEN CONCENTRATORS, FEEDING PUMPS, ETC.: MUST BE [UL 1363A (OR) UL ] POWER STRIPS USED IN PATIENT CARE VICINITY TO POWER RACK, TABLE, PEDESTAL, OR CART MOUNTED PATIENT CARE RELATED ELEC. EQUIPMENT HAVE RECEPTACLES THAT ARE PERMANATELY ATTACHED TO THE EQUIPMENT ASSEMBLY. 13 Surge Protector Use POWER STRIPS MAY NOT BE USED IN PATIENT CARE VICINITY (6 feet) TO POWER PERSONAL ELECTRONICS (Only if patient care related equipment is in use) IN RESIDENT ROOMS WITH PATIENT CARE RELATED EQUIPMENT, POWER STRIPS PROVIDING POWER TO NON-PATIENT CARE RELATED ELECTRICAL EQUIPMENT (OUTSIDE THE VICINITY) MUST BE LISTED AS UL1363. ALL OTHER SURGE PROTECTORS MUST MEET SFM POLICY. 14 Annual inspection & testing in accordance with NFPA 80, 2010 edition is required for all fire door assemblies. * Non-rated door assemblies (including corridor doors to resident rooms and smoke barrier doors) are not subject to annual inspection and testing requirements. Full compliance with annual fire door assembly inspection & testing was required by January 1,

6 5.2.1 Fire door assemblies shall be inspected and tested not less than annually, and a written record of the inspection shall be signed and kept for inspection by the AHJ Functional testing of fire door and window assemblies shall be performed by individuals with knowledge and understanding of the operating components of the type of door being subject to testing Before testing, a visual inspection shall be performed to identify any damaged or missing parts that can create a hazard during testing or affect operation or resetting Inspection shall include an operational test for automatic-closing doors and windows to verify that the assembly will close under fire conditions As a minimum, the following items shall be verified: (1) No open holes or breaks exist in surfaces of either the door or frame. (2) Glazing, vision light frames, and glazing beads are intact and securely fastened in place, if so equipped. (3) The door, frame, hinges, hardware, and noncombustible threshold are secured, aligned, and in working order with no visible signs of damage. (4) No parts are missing or broken. 18 6

7 As a minimum, the following items shall be verified: (5) Door clearances do not exceed clearances listed in and (6) The self-closing device is operational; that is, the active door completely closes when operated from the full open position. (7) If a coordinator is installed, the inactive leaf closes before the active leaf. (8) Latching hardware operates and secures the door when it is in the closed position As a minimum, the following items shall be verified: (9) Auxiliary hardware items that interfere or prohibit operation are not installed on the door or frame. (10) No field modifications to the door assembly have been performed that void the label. (11) Gasketing and edge seals, where required, are inspected to verify their presence and integrity Hardware shall be examined, and inoperative hardware, parts, or other defects shall be replaced without delay Door openings and the surrounding areas shall be kept clear of anything that could obstruct or interfere with the free operation of the door. 21 7

8 CMS does NOT require a certified person to complete the door inspections Qualified Person. A person who, by possession of a recognized degree, certificate, professional standing, or skill, and who, by knowledge, training, and experience, has demonstrated the ability to deal with the subject matter, the work, or the project. ** Anyone who has knowledge of the subject can do the work. Training is available if a facility needs to send staff to learn how to conduct the door inspections. 22 All providers were required to be in full compliance with the new regulation by November 15, * Emergency Preparedness Checklist Handout (This will be a living document) 23 The program must include all of the elements set forth in the requirement: Emergency Plan Policies & Procedures Communication Plan Training & Testing Emergency Power Systems 24 8

9 Risk Assessment The emergency plan must be based on and include documented, facility-based and community-based risk assessments utilizing an all-hazards approach & include strategies for addressing emergency events identified by the risk assessment. Risk assessments should be specific to the location of the facility and consider hazards most likely to occur in the surrounding area including, but not limited to: Natural disasters Natural disasters Man-made disasters 25 Risk Assessment LTC facilities must include provisions in the emergency plan to account for missing residents. Facilities must document facility-based & community-based risk assessments. Community-based risk assessments ensure that facilities collaborate with other entities within their community to promote an integrated response to emergency events. (Health care providers, emergency management agencies, regional healthcare coalitions) 26 Emergency Plan The emergency plan is one part of the facility s emergency preparedness program. The plan will provide the framework to assist facilities in addressing patient population needs and identifying business operations necessary for support during an actual emergency. 27 9

10 Emergency Plan Persons at risk identified Strategies for addressing all emergency events Strategies in place to address needs of at-risk pop. Staff roles identified Services the facility must provide in an emergency Emergency plan reviewed/updated annually Delegations of authority Documentation of annual review date Succession Planning (authorized & qualified person to act in absence of Administrator Continuity of operations (essential personnel, functions, and critical resources to continue operations) 28 Cooperation & Collaboration Facility must document cooperation and collaboration with local, regional, state, and federal emergency preparedness officials to ensure an integrated response during an emergency. Document who was contacted and who participated in emergency preparedness planning efforts. 29 Policies & Procedures Basic needs of residents & staff to maintain life System to track the location of on-duty staff & residents The use of volunteers in an emergency Safe evacuation from the facility A means to shelter in place A system of medical documentation Arrangements with other facilities Policies were developed based on facility & community based risk assessments, using an all hazards approach We will verify that documentation verifies the facility reviews policies and procedures at least annually and updates them as necessary, based on results of the review

11 Policies & Procedures The policies and procedures must address provisions including: Food Medical Needs Water Pharmaceutical supplies for patients/staff. Policies shall also provide adequate alternate energy sources to maintain: Temperatures to protect resident safety Extinguishing systems Safe & sanitary storage of provisions Alarm systems Emergency lighting Fire detection Sewage & waste disposal 31 Policies & Procedures Tracking Residents & Staff: Must be able to document a tracking system as part of your emergency policies & procedures. Evacuations: Must have a policy that addresses elements for safe evacuation from the facility. Sheltering in Place: Must have a policy that addresses how the facility will provide the means to shelter in place for residents, staff, & volunteers. 32 Policies & Procedures Continuity of Services: Must have copies of transfer agreements and arrangements with other facilities to receive residents in the event the facility cannot care for them in an emergency

12 Communications Plan The communications plan demonstrates how the facility coordinates resident care within the facility, across health care providers, and with state and local public health departments. YES NO The communications plan demonstrates how the facility coordinates with emergency management agencies and systems to protect resident health and safety in the event of a disaster. YES NO The facility has identified alternate communications methods in the event of phone/internet failure (Examples: CB radios, short-wave radios, satellite phones). YES NO Does the communications plan include names and contact information for the following: (Facility staff, all entities providing services under the plan, Patients physicians, next of kin, guardian, or custodian, Other facilities of similar provider or supplier type? YES NO Does the facility have evidence the communications plan has been reviewed & updated (as necessary) on an annual basis? YES NO 34 Communications Plan Reviewing Contact Information: Must have a list of facilities contact information in the communication plan. This information must be reviewed and updated annually. Means of Communication: There must be a primary and alternate means to communicate with facility staff, federal, state, regional, and local emergency management agencies. 35 Sharing Information The Communication Plan must include a method for sharing resident information and documentation with other health care providers to maintain continuity during an emergency. There must be policies & procedures in place that address the means your facility will use to release resident information, including the general condition & location of residents. Facility staff should be able to explain/demonstrate how they share emergency plan information with residents & their families

13 Training & Testing Could the facility document an annual full-scale community based exercise (or when not available) an individual facility-based exercise? YES NO If a full-scale community based exercise was not available, did the facility document all local and state agencies that were contacted to make such request? YES NO Did the facility document an additional exercise (full scale OR tabletop exercise that includes a group discussion led by a facilitator, using a narrated relevant emergency scenario and set of problems with prepared questions designed to challenge an emergency plan? YES NO Did the facility provide documentation of the post exercise analysis and information of revisions made to the plan? YES NO 37 Training & Testing Does the facility have a written training and testing program and review and update it annually? Y / N Documented EP training provided for all new and existing staff members, volunteers? YES NO Has the facility documented specific training for the staff? YES NO Did the facility document the method(s) used to demonstrate knowledge of the training program content? YES NO Was the facility able to verify (through staff training files) that staff members were in fact trained in EP? YES NO 38 Emergency Power Systems Does the facility have emergency power systems in place (or) plans to provide emergency power while sheltering in place during an emergency? YES NO If the facility maintains an on-site fuel source for a generator, does it have a plan to sustain generator operations during an emergency? YES NO 39 13

14 Annual Testing Could the facility document an annual full-scale community based exercise (or when not available) an individual facility-based exercise? YES NO If a full-scale community based exercise was not available, did the facility document all local and state agencies that were contacted to make such request? YES NO Did the facility document an additional exercise (full scale OR tabletop exercise that includes a group discussion led by a facilitator, using a narrated relevant emergency scenario and set of problems with prepared questions designed to challenge an emergency plan? YES NO Did the facility provide documentation of the post exercise analysis and information of revisions made to the plan? YES NO

Department of Health Life Safety Code Update

Department of Health Life Safety Code Update Department of Health Life Safety Code Update Presented by: Charlie Schlegel, Director Division of Safety Inspection Overview CMS Adoption of the 2012 Life Safety Code (LSC) and 2012 Health Care Facilities

More information

Written Fire Safety Plans

Written Fire Safety Plans Written Fire Safety Plans 2012 LSC KATHARINE ACHOR SEPTEMBER 2016 NFPA Standard: 2012 NFPA 101, 19.1.1.3.1 All health care facilities shall be designed, constructed, maintained, and operated to minimize

More information

Developing a Healthcare Facility Fire Door Inspection Program

Developing a Healthcare Facility Fire Door Inspection Program Developing a Healthcare Facility Fire Door Inspection Program WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio QUESTIONS How To Ask a Question: 1 POLLING There will be occasional interactive

More information

WHAT TO EXPECT DURING A FIRE DOOR INSPECTION

WHAT TO EXPECT DURING A FIRE DOOR INSPECTION WHAT TO EXPECT DURING A FIRE DOOR INSPECTION Basic Fire Door Inspections 1. Fire door basic function 2. Understanding codes 3. Responsibility of end user 4. Common fire door deficiencies 5. What your door

More information

Table OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS

Table OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.

More information

2012 Life Safety and Health Care Facility Codes - Door Inspections and Other Critical Inspection, Testing and Maintenance

2012 Life Safety and Health Care Facility Codes - Door Inspections and Other Critical Inspection, Testing and Maintenance 2012 Life Safety and Health Care Facility Codes - Door Inspections and Other Critical Inspection, Testing and Maintenance Will begin at 1 pm Housekeeping Announcements Problems during the call? Press *0

More information

Established /10/2015. Doran Pruisner Dan Wood

Established /10/2015. Doran Pruisner Dan Wood Established 1911 Doran Pruisner Dan Wood The International Fire Code, 2009 Edition shall apply to all occupancies except for those that are explicitly excluded by these provisions. 1 Buildings built between

More information

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY Revision No.: 11 Page 1 of 12 I. PURPOSE This procedure establishes a tool to help maintain a safe environment for all patients, visitors and staff by evaluating the loss of a life safety feature during

More information

Fire and Smoke Door Inspections Qualified Training 02/03/17

Fire and Smoke Door Inspections Qualified Training 02/03/17 Fire and Smoke Door Inspections Qualified Training 02/03/17 Basis of Requirements NFPA 101 requires annual fire and smoke door inspections (Section 18/19.2.2.2.1) Sections 18/19.2.2.1 require compliance

More information

THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4

THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4 THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1 QUESTIONS How To Ask a Question: POLLING There will be occasional

More information

NFPA 80 Overview January 21, 2016

NFPA 80 Overview January 21, 2016 NFPA 80 Overview January 21, 2016 Kristin Bigda, P.E. Senior Fire Protection Engineer National Fire Protection Association Presenter Kristin Bigda, P.E. Senior Fire Protection Engineer, NFPA Building Fire

More information

Swinging Egress and Fire Doors

Swinging Egress and Fire Doors Presented by: AHCA Seminar: Inspecting and Maintaining Swinging Egress and Fire Doors Current State CMS Memorandum July 28, 2017 Tuesday May, 3, 2016 CMS issued the final rule adopting the 2012 Life Safety

More information

FACILITY MANAGEMENT DEFICIENCIES IN CRITICAL ACCESS HOSPITALS (CAH)

FACILITY MANAGEMENT DEFICIENCIES IN CRITICAL ACCESS HOSPITALS (CAH) FACILITY MANAGEMENT DEFICIENCIES IN CRITICAL ACCESS HOSPITALS (CAH) Presented by: Alise Howlett, Assoc. AIA, CFPE, CHFM Standards Advisor, EM/PE/LS HFAP A better healthcare survey experience 1 FREQUENT

More information

B. The Facility Emergency Planners and Alternate Planners will successfully complete the in-house DJJ Fire Prevention course.

B. The Facility Emergency Planners and Alternate Planners will successfully complete the in-house DJJ Fire Prevention course. GEORGIA DEPARTMENT OF JUVENILE JUSTICE Applicability: { } All DJJ Staff { } Administration { } Community Services {x} Secure Facilities (RYDCs & YDCs) Chapter 8: SAFETY, SECURITY & CONTROL Subject: FIRE

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 34 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0001 - OTHER

More information

Emergency Preparedness: New CMS Rules for ICFs/IID

Emergency Preparedness: New CMS Rules for ICFs/IID Emergency Preparedness: New CMS Rules for ICFs/IID OHCA / OCID August 24, 2017 Dustin M. Ellinger BSN, MHA, RN Rolf Consulting LLC So What s New? 2012 Life Safety Code Published: May 4, 2016 (S&C 16-22-LSC)

More information

Are there any policies regarding outlets that contain USB ports?

Are there any policies regarding outlets that contain USB ports? Answers to the Questions Mark J. Blackburn, P.E., CFPS February, 2016 Question 1 Are there any policies regarding outlets that contain USB ports? There is no direct reference in code about these types

More information

PRINTED: 06/09/2017 FORM APPROVED CENTERS FOR MEDICARE & MEDICAID SERVICES OMB NO (X2) MULTIPLE CONSTRUCTION A. BUILDING 03 - A BUILDING

PRINTED: 06/09/2017 FORM APPROVED CENTERS FOR MEDICARE & MEDICAID SERVICES OMB NO (X2) MULTIPLE CONSTRUCTION A. BUILDING 03 - A BUILDING SUMMARY PROVER'S PLAN OF CORRECTION K 000 INITIAL COMMENTS K 000 A Life Safety Code Survey was conducted by the State Fire Marshal beginning on May 9th, 2017 and ending on May 10th, 2017. Adair Acute Care

More information

10/25/2018. Facilitators. Emergency Preparedness &Life Safety Code for Administrators. Participant Guide

10/25/2018. Facilitators. Emergency Preparedness &Life Safety Code for Administrators. Participant Guide Emergency Preparedness &Life Safety Code for Administrators 1 Participant Guide Emergency PreparednessHandouts Graphic Organizer Sample Checklist for Emergency Preparedness Regulation Compliance Crosswalk

More information

FACILITY MANAGEMENT DEFICIENCIES IN ACUTE CARE SETTINGS

FACILITY MANAGEMENT DEFICIENCIES IN ACUTE CARE SETTINGS FACILITY MANAGEMENT DEFICIENCIES IN ACUTE CARE SETTINGS Presented by: Alise Howlett, Assoc. AIA,CFPE, CHFM Standards Advisor, EM/PE/LS HFAP A better healthcare survey experience 1 FREQUENT PHYSICAL ENVIRONMENT

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 92 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS Type Memo Tag FED - KA100 - General Requirements - Other Title

More information

CMS Announcement 3/27/2017. Adoption of 2012 Life Safety Code Health Care Facilities Code. Kenneth Daily, LNHA

CMS Announcement 3/27/2017. Adoption of 2012 Life Safety Code Health Care Facilities Code. Kenneth Daily, LNHA Adoption of 2012 Life Safety Code Health Care Facilities Code Kenneth Daily, LNHA kenn@qissurvey.com CMS Announcement May 2016 Life Safety Code Health Care Code Effective July 5 th Numerous changes many

More information

The Impact the Reference Standards in the 2012 Edition of NFPA 101 have on the Operation of Health Care Facilities: NFPA 80 and 99

The Impact the Reference Standards in the 2012 Edition of NFPA 101 have on the Operation of Health Care Facilities: NFPA 80 and 99 The Impact the Reference Standards in the 2012 Edition of NFPA 101 have on the Operation of Health Care Facilities: NFPA 80 and 99 Sharon S. Gilyeat, P.E. Lauren Schrumpf August 8, 2018 Expertly Engineering

More information

Procedure DESCRIPTION/OVERVIEW

Procedure DESCRIPTION/OVERVIEW Applies To: UNMH Responsible Department: Life Safety Revised: 07.08.16 Procedure Patient Age Group: (X ) N/A ( ) All Ages ( ) Newborns ( ) Pediatric ( ) Adult DESCRIPTION/OVERVIEW To assure the safety

More information

Interim Life Safety Measures. Healthcare Construction Certificate - Level 1

Interim Life Safety Measures. Healthcare Construction Certificate - Level 1 Interim Life Safety Measures Purpose of Interim Life Safety Management BASIC SAFETY: During renovations projects in healthcare occupancies, the basic level of protection for the occupants must be maintained

More information

First Aspen Federal Regulation Set: K LSC 2000 Health Existing

First Aspen Federal Regulation Set: K LSC 2000 Health Existing First Aspen Federal Regulation Set: K 01.01 LSC 2000 Health Existing K 0000 Title CFR Type INITIAL COMMENTS Memo K 0011 If the building has a common wall with a nonconforming building, the common wall

More information

NFPA CODE TESTING & INSPECTION. Requirements & Recommendations for. Licensed Florida Hospitals, Ambulatory Surgery Centers,

NFPA CODE TESTING & INSPECTION. Requirements & Recommendations for. Licensed Florida Hospitals, Ambulatory Surgery Centers, NFPA CODE TESTING & INSPECTION Requirements & Recommendations for Licensed Florida Hospitals, Ambulatory Surgery Centers, ICF/IID Healthcare, & In-patient Hospice Facilities per NFPA Life Safety Code 101

More information

Danilo B. Concepcion, CBNT, CCHT-A Operations Manager St. Joseph Hospital Renal Services

Danilo B. Concepcion, CBNT, CCHT-A Operations Manager St. Joseph Hospital Renal Services Life Safety Code Danilo B. Concepcion, CBNT, CCHT-A Operations Manager St. Joseph Hospital Renal Services danilo.concepcion@stjoe.org 714-771-8944 The findings and conclusions in this presentation are

More information

Risk Management Services

Risk Management Services Risk Management Services FIRE PROTECTION IMPAIRMENT PROGRAM Introduction Fire protection systems represent a significant capital investment for organizations. Companies want to make sure that they are

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 100 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS CFR Type Memo Tag FED - KA100 - General Requirements - Other

More information

Ch. 569 FIRE AND SAFETY SERVICES 28 CHAPTER 569. FIRE AND SAFETY SERVICES GENERAL PROVISIONS INTERNAL DISASTER PLAN EVACUATION DRILLS

Ch. 569 FIRE AND SAFETY SERVICES 28 CHAPTER 569. FIRE AND SAFETY SERVICES GENERAL PROVISIONS INTERNAL DISASTER PLAN EVACUATION DRILLS Ch. 569 FIRE AND SAFETY SERVICES 28 CHAPTER 569. FIRE AND SAFETY SERVICES Sec. 569.1. Principle. 569.2. Fire safety standards. 569.3. Policies and procedures. GENERAL PROVISIONS 569.11. Firefighting service.

More information

EC 5.10 FIRE PREVENTION MANAGEMENT

EC 5.10 FIRE PREVENTION MANAGEMENT EC 5.10 FIRE PREVENTION MANAGEMENT The organization manages fire safety risks. 1 The organization develops and maintains a written management plan describing the processes it implements to effectively

More information

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment February 2017 Alberta Fire Code safety equipment maintenance requirements: The Black Diamond Fire Department has

More information

This policy may also be used for routine work orders that are Life Safety in nature and cannot be completed within 45-days.

This policy may also be used for routine work orders that are Life Safety in nature and cannot be completed within 45-days. Policy: It is the policy of the St. Joseph Mercy Health System (SJMHS- Ann Arbor, Oakland, Livingston, Brighton, Chelsea and St. Mary Mercy Hospital- Livonia) and associated satellite facilities to assure

More information

Facility Manager Training

Facility Manager Training Joint Base Elmendorf-Richardson I n t e g r i t y - S e r v i c e - E x c e l l e n c e Facility Manager Training OVERVIEW Fire Safety Deficiencies Facility Manager Responsibilities Fire Prevention Folder

More information

Fire/Life Safety Policy

Fire/Life Safety Policy Fire/Life Safety Policy On Campus Student Housing A. Purpose The University supports and maintains a strong commitment to the safety and health of each student living in On Campus Student Housing. The

More information

Chapter 4: Fire Protection Systems

Chapter 4: Fire Protection Systems Chapter 4: Fire Protection Systems Automatic Extinguishing Systems (Fire Sprinklers) One of the most important aspects of a storage warehouse inspection is ensuring that the automatic extinguishing system

More information

Fire Rated Door Assemblies: Compliant Designs

Fire Rated Door Assemblies: Compliant Designs Fire Rated Door Assemblies: Compliant Designs Steel Door Institute www.steeldoor.org AIA Provider #G389 Course #: SDIFIRE 1 HSW CE hour 1 Credit(s) earned on completion of this course will be reported

More information

LIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE

LIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE California Society for Healthcare Engineering SOUTHERN CALIFORNIA SEMINAR LIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE 1 PROGRAM AGENDA Adoption of 2012 LSC CMS Final Rule / Amendments

More information

St. Vincent s Health System Page 1 of 6

St. Vincent s Health System Page 1 of 6 St. Vincent s Health System Page 1 of 6 TITLE: Fire Plan Code Red FACILITY: St. Vincent s East FUNCTION: ORIGINATING DEPT: HOSPITAL SHARED POLICY? EFFECTIVE DATE: _X Yes No DOCUMENT NUMBER: 801 ORIGINATION

More information

Fire System Impairment Policy

Fire System Impairment Policy Fire System Impairment Policy Purpose: To establish procedures to be followed, when a fire protection or suppression system is taken out of service, due to construction, alteration, power outage, repair,

More information

About the Instructor & Presenter:

About the Instructor & Presenter: About the Instructor & Presenter: Paul G. Baillargeon, AHC, FDAI Vice President, Technical Consulting Door Security & Safety Foundation A noted veteran in the door and hardware industry, Mr. Baillargeon

More information

School Fire Safety Checklist

School Fire Safety Checklist Community Risk Reduction The (SFSC) includes many of the most common fire prevention and life safety issues found in schools. The SFSC is not intended to be an all inclusive list, but rather highlights

More information

2018 Joint Commission Standards What s New in the EC/LS/UM GASHE Annual March Meeting Lake Blackshear Resort

2018 Joint Commission Standards What s New in the EC/LS/UM GASHE Annual March Meeting Lake Blackshear Resort 2018 Joint Commission Standards What s New in the EC/LS/UM GASHE Annual March Meeting Lake Blackshear Resort Presented March 9, 2018 By Ken Gregory, CHSP President Ken Gregory Consulting 1 2018 Joint Commission

More information

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES Sharon S. Gilyeat, P.E., Principal Koffel Associates, Inc. www.koffel.com sgilyeat@koffel.com Expertly Engineering Safety From Fire

More information

Title: BFST1505 Syllabus

Title: BFST1505 Syllabus DEPARTMENT OF FINANCIAL SERVICES Division of State Fire Marshal Bureau of Fire Standards and Training Title: BFST1505 Syllabus Revision: April 5, 2018 Section I - Course Information Course Title: Fire

More information

Winnipeg Fire Department Fire Prevention Branch

Winnipeg Fire Department Fire Prevention Branch Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of

More information

STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT

STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT The interaction of fire protection systems can be extremely complex. The detection of a fire in a building by an automatic device

More information

INSPECTOR I SKILLS ADMINISTRATION

INSPECTOR I SKILLS ADMINISTRATION INSPECTOR I SKILLS ADMINISTRATION 1- Prepare inspection reports so that the report is clear and concise and reflects the findings of the inspection in accordance with the applicable codes and standards..

More information

Regulations Regarding Emergency Planning & Preparedness for Long Term Care Facilities. Regulation Explanation Document Reference

Regulations Regarding Emergency Planning & Preparedness for Long Term Care Facilities. Regulation Explanation Document Reference Regulations Regarding Emergency Planning & Preparedness for Long Term Care Facilities Mandatory Immediate Notifications to NJDHSS 8:39-9.4(e)1 8:39-9.4(e)4 Interruption for 3 or more hours of physical

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 51 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K0130 - MISCELLANEOUS Title MISCELLANEOUS OTHER LSC DEFICIENCY NOT ON 2786 FED - K9999 - FINAL OBSERVATIONS Title

More information

Subject: Fire Protection Impairment Program Reference: NFPA (see bottom of page 5) Effective Date: August 2014 Distribution All YC Employees

Subject: Fire Protection Impairment Program Reference: NFPA (see bottom of page 5) Effective Date: August 2014 Distribution All YC Employees Subject: Fire Protection Impairment Program Reference: NFPA (see bottom of page 5) Effective Date: August 2014 Distribution All YC Employees Purpose: To establish procedures to be followed when a fire

More information

NFPA 101 Code Update from 2012 Edition to the 2015 Edition

NFPA 101 Code Update from 2012 Edition to the 2015 Edition NFPA 101 Code Update from 2012 Edition to the 2015 Edition Presented by: Gary Furdell AHCA Fire Protection Specialist 1 2 2012 Update to 2015 Chapter 18 New Health Care Occupancies 4 18.1.3.2 Atrium walls

More information

Crosswalk of 2014 HFAP Standards against HFAP Standards Acute Care Hospital Manual

Crosswalk of 2014 HFAP Standards against HFAP Standards Acute Care Hospital Manual 09.00.01 Operations Plan 11.07.01 09.00.02 Hazard Vulnerablity Analysis (HVA) 09.01.01 Safety & Security 11.00.02 New Name 09.01.02 Supplies 09.01.03 482.41(a)(2) Utilities 11.03.21; 11.03.22 09.01.04

More information

1-300 Fire and/or Smoke Dampers to Inspect $ Fire and/or Smoke Dampers to Inspect $34.30

1-300 Fire and/or Smoke Dampers to Inspect $ Fire and/or Smoke Dampers to Inspect $34.30 Life Safety Services, LLC TXMAS Schedule Contract Number: TXMAS-12-03FAC030 Passive Fire Protection Services Authorized Federal Supply Schedule Price List Quantity of Dampers to Inspect Per Damper to Survey

More information

SURREY FIRE SERVICE. Construction Fire Safety Plan Bulletin

SURREY FIRE SERVICE. Construction Fire Safety Plan Bulletin SURREY FIRE SERVICE Construction Fire Safety Plan Bulletin The B.C. Fire Code requires building owners/contractors to comply with the requirements of the BC Fire Code 5.6 Construction and Demolition Sites

More information

TG FIRE DRILLS. Office of the Fire Marshal and Emergency Management

TG FIRE DRILLS. Office of the Fire Marshal and Emergency Management FIRE DRILLS Office of the Fire Marshal and Emergency Management Preface This guideline updates TG-01-2004 published in October 2004. Portions of the guideline have been changed to reflect the current requirements

More information

Measures (ILSM) Process

Measures (ILSM) Process Managing the Interim Life Safety Measures (ILSM) Process 1 A Program for The Texas Association of Healthcare Facility Management Monday, April 30, 2012 Robert H. Bartels, CHFM CHSP CHEP SASHE President,

More information

The New Life Safety Code & Texas Responds with New Small House Nursing Design Standards

The New Life Safety Code & Texas Responds with New Small House Nursing Design Standards The New Life Safety Code & Texas Responds with New Small House Nursing Design Standards Fred Worley, Architect Architectural Unit Manager, TDADS Wes Wells, Administrator Buckner Westminster Place DADS

More information

1. Are there any annual sprinkler head inspection forms available? No, there are none available at this time.

1. Are there any annual sprinkler head inspection forms available? No, there are none available at this time. Sprinkler 1. Are there any annual sprinkler head inspection forms available? No, there are none available at this time. 2. Does the annual sprinkler head inspection have to be done by a licensed technician

More information

A Comprehensive Community Risk Reduction Initiative A COMPREHENSIVE COMMUNITY RISK REDUCTION INITIATIVE

A Comprehensive Community Risk Reduction Initiative A COMPREHENSIVE COMMUNITY RISK REDUCTION INITIATIVE A Comprehensive Community Risk Reduction Initiative A COMPREHENSIVE COMMUNITY RISK REDUCTION INITIATIVE Fire Department Core Values Protect lives, property, and the environment through preparedness, prevention,

More information

FIRE SAFETY SURVEY REPORT AMBULATORY SURGICAL CENTERS (ASC) & END STAGE RENAL DISEASE (ESRD) MEDICARE

FIRE SAFETY SURVEY REPORT AMBULATORY SURGICAL CENTERS (ASC) & END STAGE RENAL DISEASE (ESRD) MEDICARE DEPARTMENT OF HEALTH AND HUMAN SERVICES CENTERS FOR MEDICARE & MEDICA SERVICE Form Approved OMB Exempt FIRE SAFETY SURVEY REPORT AMBULATORY SURGICAL CENTERS (ASC) & END STAGE RENAL DISEASE (ESRD) MEDICARE

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 75 ST - K0000 - Initial Comments Title Initial Comments Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0001 - OTHER

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 130 ST - K0000 - Initial Comments Title Initial Comments Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. Based on the LSC

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST FIRE AND LIFE SAFETY SYSTEMS FOR STRUCTURES FIVE OR MORE STORIES IN HEIGHT AND LESS THAN 75 FEET IN HEIGHT FROM THE POINT

More information

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting life and

More information

Builders Risk - Fire Prevention Inspection Checklist

Builders Risk - Fire Prevention Inspection Checklist Builders Risk - Fire Prevention Inspection Checklist Use our inspection checklist tool to help you identify and monitor risk related to builders risk of fire on the job site. Inspection Details: Inspector

More information

H BUTCH BROWNING FIRE MARSHAL BUILDING REHABILITATION

H BUTCH BROWNING FIRE MARSHAL BUILDING REHABILITATION STATE OF LOUISIANA Department of Public Safety and Corrections Office of State Fire Marshal Code Enforcement and Building Safety 8181 Independence Boulevard Baton Rouge, Louisiana 70806 225-925-4920 H

More information

LIFE SAFETY & FIRE PREVENTION MANAGEMENT PLAN

LIFE SAFETY & FIRE PREVENTION MANAGEMENT PLAN Title/Description: Life Safety & Fire Prevention Management Department: Facilities Management Personnel: All Effective Date: 5/97 Revised: 7/00, 7/01, 7/02, 7/03, 7/04, 7/05, 7/08 LIFE SAFETY & FIRE PREVENTION

More information

Hands On Training for Fire Door Products and Fire Door Assemblies

Hands On Training for Fire Door Products and Fire Door Assemblies 2017 NFPA Conference & Expo Hands On Training for Fire Door Products and Fire Door Assemblies Presented by: Paul M. Goldense, FDAI Goldense Building Products, Inc. Jeffery S. Batick, FDAI Allegion Why

More information

WHEA FSE inspections.

WHEA FSE inspections. WHEA FSE inspections www.jfahern.com FEC.02.03.05 Features of Fire Safety Buildings are protected from fire by a series of detection, notification and suppression devices Each feature of fire safety must

More information

Life Safety Code Common Discepancies Course# LSC102. EZpdh.com All Rights Reserved

Life Safety Code Common Discepancies Course# LSC102. EZpdh.com All Rights Reserved Life Safety Code Common Discepancies Course# LSC102 EZpdh.com All Rights Reserved 1. K147 Electrical - Electrical wiring and equipment shall be in accordance with NFPA 70, National Electrical Code. 9.1.2

More information

The Physical Environment Portal: Module 5, LS Leadership

The Physical Environment Portal: Module 5, LS Leadership The Physical Environment Portal: Module 5, LS.02.01.10 - Leadership Fire Safety: Background Fire safety impacts both the lives of the occupants and the physical structures. In the early 1900 s many buildings

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 92 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0100 - General Requirements

More information

Compliance w/ the 2012 Life Safety Code

Compliance w/ the 2012 Life Safety Code Compliance w/ the 2012 Life Safety Code Implications of the 2012 NFPA Code Set for Existing & New ASCs William E. Lindeman, AIA http://www.weldesigns.com Financial Interest Disclosure The presenter provides

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 21 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0300 - Other

More information

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY Revision No.: 5 Page 1 of 6 I. PURPOSE This policy outlines the guidelines for posting a fire watch if the fire alarm and/or fire suppression system in any University building becomes inoperable and the

More information

Meagan Ray, RN Safety Director

Meagan Ray, RN Safety Director Meagan Ray, RN Safety Director A fire can be a great hazard in a patient care setting. The 4 most common hospital fires include clothing, wastebasket, burning liquid or gas, and electrical fires. Follow

More information

Chapter 43, Building Rehabilitation allows for degrees of compliance based on the work category such as the extent of work.

Chapter 43, Building Rehabilitation allows for degrees of compliance based on the work category such as the extent of work. 3610 COMMERCE DR SUITE 817 BALTIMORE MD 21227 P 410.737.8677 F 410.737.8688 www.haifire.com May 5, 2014 Review of Regulations 42 CFR Parts 403, 416, 418, 460, 482, 483 and 485 Medicare and Medicaid Programs;

More information

Koffel Associates, Inc.

Koffel Associates, Inc. NFPA 25: STANDARD FOR THE INSPECTION, TESTING, AND MAINTENANCE OF WATER BASED FIRE PROTECTION SYSTEMS William E. Koffel, P.E., FSFPE President Koffel Associates, Inc. www.koffel.com wkoffel@koffel.com

More information

Building, plumbing, and fire safety requirements.

Building, plumbing, and fire safety requirements. ACTION: Final DATE: 03/09/2007 8:18 AM 3701-17-63 Building, plumbing, and fire safety requirements. (A) The building or buildings in which a residential care facility is located shall be approved by and

More information

CALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL UL 300

CALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL UL 300 CALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL UL 300 FREQUENTLY ASKED QUESTIONS CONCERNING COMMERCIAL COOKING PROTECTION Published by FIRE ENGINEERING DIVISION

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 41 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K0011 - LIFE SAFETY CODE STANDARD If the building has a common wall with a nonconforming building, the common

More information

Safety & Security Services Services de Sûreté et Sécurité. Hot Work Protocol

Safety & Security Services Services de Sûreté et Sécurité. Hot Work Protocol Article 1 Purpose Vanier College has established a to minimize the potential for injuries and loss of property due to fire or explosion as a result of hot work. Article 2 Scope This protocol applies to

More information

Principal s Guide for Fire Safety Planning in Schools. To be kept in School Administration Office

Principal s Guide for Fire Safety Planning in Schools. To be kept in School Administration Office FIRE SAFETY PLAN INFORMATION FOR IN- PERSONNEL Principal s Guide for Fire Safety Planning in Schools To be kept in School Administration Office Crown Copyright, Province of Nova Scotia 2004 Prepared by

More information

10/28/2015. Enjoy Your TJC Survey. Bill H. McCully CHFM SASHE. Senior Consultant MSL Healthcare Partners. MSL Healthcare Partners, 2015 PREPARATION

10/28/2015. Enjoy Your TJC Survey. Bill H. McCully CHFM SASHE. Senior Consultant MSL Healthcare Partners. MSL Healthcare Partners, 2015 PREPARATION Enjoy Your TJC Survey Bill H. McCully CHFM SASHE Senior Consultant MSL Healthcare Partners PREPARATION 1 Top Eight Most Cited Standards (George Mills) EC News May 2015 Top Citations EC.02.06.01 56% EC.02.05.01

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 133 ST - Y0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - Y1001 - Awareness of the

More information

Fire Department Fire Prevention Inspection Services. HIGH RISE STRUCTURE Fire Inspection Program

Fire Department Fire Prevention Inspection Services. HIGH RISE STRUCTURE Fire Inspection Program HIGH RISE STRUCTURE Fire Inspection Program Meeting Agenda Fire Prevention Mission High Rise Fire Inspection Program Question and Answer 2 Fire Chief Bertral Washington 3 Our Mission Deputy Fire Marshal

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 98 ST - Y0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. Based on the LSC surveyor's determination

More information

UC Irvine Environmental Health & Safety TITLE: FIRE WATCH AND OUT OF SERVICE NOTIFICATION

UC Irvine Environmental Health & Safety TITLE: FIRE WATCH AND OUT OF SERVICE NOTIFICATION SECTION: UC Irvine Environmental Health & Safety TITLE: FIRE WATCH AND OUT OF SERVICE NOTIFICATION INITIATOR: DALE SAUNDERS REVISION DATE: September 2015 1. Program Description 2. Scope 3. Definitions

More information

Patrick County Horizons Jeb Stuart Hwy. Stuart, Va

Patrick County Horizons Jeb Stuart Hwy. Stuart, Va Patrick County Horizons 24141 Jeb Stuart Hwy. Stuart, Va. 24171 Emergency Preparedness Plan Severe Weather/Earthquake/Building Damage/Fire/Missing Person Policy: Per page 22 of the PCS licensure manual:

More information

Evacuation Fire Safety Program

Evacuation Fire Safety Program Evacuation Fire Safety Program Emergency Procedures Provisions must be made for prompt medical attention in case of serious injury. The location and phone number of emergency service providers will be

More information

FIRE SAFETY AND EVACUATION PLANNING FOR ASSISTED LIVING FACILITIES AND NURSING HOMES

FIRE SAFETY AND EVACUATION PLANNING FOR ASSISTED LIVING FACILITIES AND NURSING HOMES FIRE SAFETY AND EVACUATION PLANNING FOR ASSISTED LIVING FACILITIES AND NURSING HOMES West Metro Fire Rescue Life Safety Division 433 South Allison Parkway Lakewood, Colorado 80226 (303) 989-4307 Fax (303)

More information

COMPLIANCE WITH THIS PUBLICATION IS MANDATORY

COMPLIANCE WITH THIS PUBLICATION IS MANDATORY BY ORDER OF THE SUPERINTENDENT HQ UNITED STATES AIR FORCE ACADEMY INSTRUCTION 32-2001 9 APRIL 2014 Civil Engineering FIRE PREVENTION PRACTICES AND FIRE PROTECTION ENGINEERING STANDARDS COMPLIANCE WITH

More information

Prepublication New Text Jan 2018 Changes to Environment of Care and Life Safety Chapters

Prepublication New Text Jan 2018 Changes to Environment of Care and Life Safety Chapters Prepublication New Text Jan 2018 Changes to Environment of Care and Life Safety Chapters EC.01.01.01 EP3 Related to Life Safety Code Updates Hospital (HAP) Accreditation Program The hospital has a library

More information

X0.01 Emergency Management. Approved: September 27, 2002 Revised: July 15, Next Scheduled Review: July 15, 2014 PROCEDURE STATEMENT

X0.01 Emergency Management. Approved: September 27, 2002 Revised: July 15, Next Scheduled Review: July 15, 2014 PROCEDURE STATEMENT Texas A&M AgriLife Extension Service Procedures 34.07.99.X0.01 Emergency Management Approved: September 27, 2002 Revised: July 15, 2012 Next Scheduled Review: July 15, 2014 PROCEDURE STATEMENT Texas A&M

More information

FIRE PROTECTION INTRODUCTION

FIRE PROTECTION INTRODUCTION SECTION IV. Fire/Life Safety Chapter 1. Fire Protection Revision Date 11/19/02 Review Date 01/2007 FIRE PROTECTION INTRODUCTION PURPOSE It is the policy of Duke University to take all possible steps to

More information

Date Issued: December 14, 2017 Revision: 2.1

Date Issued: December 14, 2017 Revision: 2.1 2.1 1. Introduction A is implemented to ensure the fire safety of building occupants or a building area when the Fire Alarm System or a Fire Protection System has been temporarily disabled due to malfunction,

More information

Narrative Reports As Regulated by 780 CMR, Section 903.0

Narrative Reports As Regulated by 780 CMR, Section 903.0 EXHIBIT 20 Narrative Reports As Regulated by 780 CMR, Section 903.0 903.1.1 - FIRE PROTECTION CONSTRUCTION DOCUMENTS a. Basis (methodology) of design for the protection of the occupancy and hazard for

More information

LIFE SAFETY CODE MAINTENANCE MANUAL

LIFE SAFETY CODE MAINTENANCE MANUAL LIFE SAFETY CODE MAINTENANCE MANUAL 1 P a g e Table of Contents Introduction 3 Alcohol Based Hand Rub (ABHR) Dispensers 4 Corridor Walls 4 Corridor Width 5 Doors 5 Electrical 6 Elevators & Dumbwaiters

More information